Atch 3 - Equipment Salient Characteristics.pdf

PDF 124 KB Posted

Attached to
Purchase and installation of two (2) Closed-Circuit Fluid Coolers and Associated Pumps
Solicitation number
FA301626Q0120
Issued by

About this file

This document is a Salient Characteristics specification for fluid coolers and pumps replacement in Buildings 590 and 591. The specification establishes strict requirements for acceptable "equal" products to ensure compatibility with existing infrastructure and adequate facility cooling loads.

The fluid cooler (cooling tower) must meet or exceed the cooling capacity of the existing SPX ReCold MW-30C model, operate on 208/230V, 3-Phase power, feature dual fans of approximately 3.0 HP each (or equivalent configuration meeting required cooling performance), and include an internal basin heater rated at approximately 4.0 KW. Circulation pumps must deliver a minimum flow rate of 120 GPM, utilize a 5 HP continuous duty motor with standard 4-pole speed (approximately 1750-1760 RPM), and operate on 208/230V, 3-Phase power. The control panel must be rated for 208/120V, 3-Phase, 4-Wire power with protection consisting of one 100A breaker and two 20A 3-pole main breakers, housed in a NEMA 3R outdoor-rated enclosure. All proposed equipment must strictly adhere to these physical dimensions, electrical requirements, and performance capabilities to be considered acceptable replacements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

FLUID COOLERS AND PUMPS REPLACEMENT (BLDGS 590 & 591)

To be considered an acceptable "equal" product, all proposed equipment must strictly adhere to the physical dimensions, electrical requirements, and performance capabilities outlined below to ensure compatibility with existing infrastructure and meet required facility cooling loads.

1. Fluid Cooler (Cooling Tower)

• Performance: Must meet or exceed the cooling capacity/tonnage of the existing SPX ReCold MW-30C.

• Electrical: Must operate on 208/230V, 3-Phase power.

• Fans: Dual fans (approx. 3.0 HP each) or an equivalent fan configuration that meets the required cooling performance.

• Heater: Must include an internal basin heater (approx. 4.0 KW).

2. Circulation Pumps

• Flow Rate: Minimum 120 GPM.

• Motor: 5 HP, continuous duty, standard 4-pole speed (approx. 1750-1760 RPM)

• Electrical: Must operate on 208/230V, 3-Phase power.

3. Control Panel

• Power: Rated for 208/120V, 3-Phase, 4-Wire.

• Protection: Includes a 100A, and two 20A 3-pole main breakers

• Enclosure: NEMA 3R (outdoor rated).

SALIENT CHARACTERISTICS

File details come from the government source that posted it. Updated .