FA301620Q0054 SOW Checklist Amendment 01.pdf

PDF 98 KB Posted

Attached to
Aircraft Sun Shade Inspection
Solicitation number
FA301620Q0054
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12 MX LOCAL CHECKLIST

SUN SHADE RECURRENT INSPECTION CRITERIA

(Comprehensive)

Note: At least semi-annually, or whenever the Shelter Monitor changes, accomplish a comprehensive phased inspection of each shelter performed by the Shelter Monitor, work center supervisor, or their designated representatives IAW AFI21-136 and

AFMAN23-110.

SHELTER #s: 1-11, 16-20, 51-54, AGE Wash Rack, and Sound Suppressor OFFICE SYMBOL: MXI and MXM

ITEM INSPECTED / ESTABLISHED STANDARD

STRUCTURE:

Inspect all columns, beams, joists, girders and lateral cross bracing for proper connections, faulty/cracked welds, loose or missing bolts (tighten or replace as necessary), severe corrosion and fatigue. Document (report) findings.

Inspect turnbuckles and cables for severe corrosion, fraying or breaks, tightness, proper connection and security, tighten as necessary.

Inspect for loose/missing and damaged attaching hardware, tighten as necessary.

Inspect anchor plate bolts for embedment, tightness and severe corrosion. Tighten as necessary and document corrosion findings.

Inspect anchor plate for levelness (i.e. ensure it is flat on the ground).

Inspect concrete around all anchor plates for cracks/spalling.

Inspect shelter frame for severe corrosion and document findings.

METAL ROOFING:

Inspect roof panels and fasteners for security, tighten as necessary.

Inspect for loose/missing and damaged attaching hardware, tighten as necessary.

Inspect metal roof for severe corrosion, and document findings.

END SCREEN FABRIC ROOFING:

Inspect end screen fabric for proper tautness, adjust as nescessary.

Inspect all end screen bolts, nuts, cables, and lacing, tighten as necessary.

Inspect all end screen fabric for holes, tears, scuffs or scrapes, and document conditions in report.

ELECTRICAL

Inspect all obstruction lights, bay lights, wall pack lights, power outlets, photocell, switches for proper operation and serviceability.

Inspect all conduit, distribution panels, lighting control panels, step-down transformer for proper operation and serviceability.

MISCELLANEOUS:

Inspect the complete Lightning protection system, including air terminals, ground rods, and cross run conductors. Inspect connectors where the lightning air terminal penetrates the roof material. Remove neoprene grommet attached to the metal roof and replace with high temp. silicon sealant.

If installed, inspect gutters to ensure they are securely fastened.

Inspect bird mitigation systems for secureness.

Inspect grounding systems IAW AFI 32-1065, Table 1. Aircraft Parking and Apron Grounds.

AMENDMENT 01

File details come from the government source that posted it. Updated .