Attachment 17-Keesler Outside Plant Infrastructure Install., Apr 2022.pdf
PDF 1 MB Posted
- Attached to
- Fiber Optic Cable (FOC) IDIQ Requirement Federal contract opportunity
- Solicitation number
- FA301022R0016
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
81st COMMUNICATIONS SQUADRON OUTSIDE PLANT GUIDANCE
This guide is supplemental in nature and not all inclusive.
April 2022 Page 1 of 20
OUTSIDE PLANT GUIDANCE
April 2022
April 2022 Page 2 of 20
Table of Contents
GENERAL ……………………………………………………………………………….3
Purpose ……………………………………………………………………………….3
CS in design review process …………………………………….……………….3
Contractor Responsibilities …………………………………………….3
PERMITS ……………………………………………………………………………….4
Dig Permit AF Form 103 ………………………………………….………….4
Confined Space Entry AF Form 1024 …………………………………………….4
CE Work Request AF Form 332 …………………………………………….……….4
MAINTENANCE HOLES/HAND HOLES (MH/HH) ………………………...………….4
Man Holes ……………………………………………………………...……….5
Hand Holes …………………………………………...………………………….5
Cable Racks and Cable Rack Supports …………………………………………….6
UNDERGROUND CONDUIT SYSTEM …………………………………………….8
New Conduits/Ducts ………………………………………..…………………….8
Bends and Sweeps ……………………………….…………………….9
Joins and Connectors ………………………………………..……………………10
Pull Tape …………………………………………………...…………………11
Plugs and Sealers ……………………………………..………………………11
Spacers ………………………………………………………………………………12
Tracer Wire …………………………………...…………………………………12
Warning Tape …………………………………………...…………………………13
Utility separation ……………………………………………..………………13
SPLICE CONNECTIONS/TERMINATIONS ……………………………………………13
Copper Cable Splices …………………………………………..…………………13
Copper Cable Terminations …………………………………….………………13
Fiber Optic Splices …………………………………………..…………………14
Fiber Optic Terminations ………………………………….…………………14
LABELING ………………………………………………………………………………14
Cable Tags (Copper/Fiber) ………………………………….…………………14
Fiber Optic Distribution Panel (FODP) ……………………………………………15
COMM EQUIPMENT/MECHANICAL ROOMS ……………...……………………16
Backboards …………………………………………………...…………………16
Equipment Cabinets ……………………………………..………………………16
CABLE MANAGEMENT ……………………………………..………………………16
FOC Maintenance Loop …………………………………………..…………………16
GROUNDING AND BONDING ……………………….……………………………17
Racks/Cabinets ………………………………………………...……………………17
Equipment/Mechanical Rooms ……………………………….……………………18
MH’s/HH’s …………………………………………...…………………………19
DELIVERABLES …………………………………………...…………………………19
As-Built Drawings ……………………………………..………………………19
Butterfly Drawings ……………………………………..………………………19
Copper Test Results …………………………………………..…………………20
Fiber Test Results …………………………………………..…………………20
April 2022 Page 3 of 20
GENERAL
1. The purpose of this document is to supplement Telecommunications Industry
Association/Electronic Industry Alliance (TIA/EIA) commercial standards for outside plant installations on Keesler AFB.
2. New construction or renovations programming outside plant work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 377-7500 prior to implementation.
3. All outside plant cabling infrastructure installed on Keesler AFB will conform to
TIA/EIA cabling standards and the supplemental guidance contained within this document.
4. Any deviations from this supplement shall be coordinated through 81 CS/SCXP and the applicable maintenance work center for final approval by 81 CS.
5. Contractual responsibilities:
5.1 Contractors selected to complete outside plant work must have at least one experienced\technically certified Building Industry Consulting Service International
(BICSI) technician on site.
5.2 Provide as-built drawings for the outside plant cable work accomplished identifying installation/relocation work.
5.3 Provide test results (hand written results will not be accepted) for new\relocated outside plant cabling work accomplished.
5.4 Contractors shall be responsible for restoring work areas to original condition, to include removal of utility marking flags.
5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for outside plant cabling work accomplished in new construction or renovations.
April 2022 Page 4 of 20
PERMITS (If required)
The Contractor shall be responsible to coordinate, complete and process all permits required to complete the installation prior to any trenching, horizontal directional boring or modifications to a facility, MH or HH. For example:
Digging permit, AF Form 103 shall be submitted through BCE 14 calendar days in advance of digging activities. The Contractor is responsible for maintaining all markings and for ensuring AF Form 103 remains current.
Confine space entry permit, AF Form 1024 The Contractor shall be prepared to provide proof of their Confined Space Training Program to the base safety office.
The use of an AF Form 1024 may be required.
Base Civil Engineering Work Clearance Request, AF Form 332 shall be submitted through BCE 14 calendar days in advance of planned work.
The Contractor shall trench, excavate, mark and barricade open trenches IAW
OSHA Standards.
All utility markings, flags, etc. shall be maintained by the contractor after the responsible work center/shop identifies/locates them and ensure that the AF Form 103 remains current. Contractor shall remove marking flags upon project completion.
The contractor shall take precautions to protect existing infrastructure.
If a utility is severed or damaged due to neglect or if attributed to the fault of the contractor, then the contractor shall repair and return the utility back to the condition it was in prior to the damage.
MAINTENANCE HOLES/HAND HOLES (MH/HH) (If installed)
Communications (not electrical MHs) MH’s/HH’s installed on Keesler AFB shall have an American Association of State Highway and Transportation
Officials (AASHTO) rating of H-20 and meet the requirements of EIA/TIA.
MHs/HHs shall be of concrete construction; Polymer concrete (i.e., Quazite) construction is NOT authorized.
MH’s/HH’s shall be installed so that they are reasonably level on a gravel bed of 6 inches to allow drainage of water from the walls. The gravel bed should extend 8 inches to 12 inches beyond the outer edges of the MH/HH.
MH/HH covers shall be labeled with 1/8” raised letters stating
“COMMUNICATIONS”.
It is understood that some MHs/HHs are precast with bonding ribbons or some similar connection, to the manhole rebar and therefore do not require a ground
April 2022 Page 5 of 20 rod. This method of grounding in lieu of a ground rod is satisfactory just as long as the achieved impedance to ground is ten (10) ohms or less.
Coordination with 81 CS/SCXP will be required to identify key information and to identify local grounding procedures.
All MH’s/HH’s shall be fitted with a locking mechanism (Lockdown Security
Devices with Abloy locks are the standard for KAFB).
All MH’s/HH’s shall be free of debris upon project acceptance.
Maintenance Holes:
Unless otherwise stated, new MHs shall have minimum interior dimensions of 6’
W x 6’ L x 7’ H (Width, Length, and Height).
MHs shall be furnished with telecommunications industry standard cable racks, cable hooks, pulling irons, a sump pan (with removable perforated cover), a ladder, water resistance gaskets, bonding ribbon and a ground rod on the outside of the MH, connected to the MH ground system..
MHs shall have predrilled duct entry holes (sealed with knockouts configured for splayed entry in the end walls) with duct terminators to accept 4-inch I.D.
schedule 40 conduit.
Prefabricated MHs are preferred (Oldcastle Precast is the standard for Keesler
AFB).
Hand Holes:
Unless otherwise stated, new HH’s shall have minimum interior dimensions of 4’
W X 4’ L X 4’ H (Width, Length, and Height).
HH’s shall be furnished with telecommunications industry standard cable racks, cable hooks, pulling irons, a sump pan (with removable perforated cover), water resistance gaskets, bonding ribbon and a grounding system.
The HHs shall have predrilled duct entry holes (sealed with knockouts configured for splayed entry in the end walls) with duct terminators to accept 4-inch I.D.
schedule 40 conduit.
Prefabricated HHs are preferred (Oldcastle Precast is the standard for Keesler
AFB)
April 2022 Page 6 of 20
Cable Racks and Cable Rack Supports:
Cable racks shall be installed in existing MH’s/HH’s as required. All new HHs shall have a minimum of 2 cable racks on each wall. All new MHs shall have a minimum of 3 cable racks installed on each wall. The use of cable rack stand-offs is required when new racks are installed in MHs.
All cables shall be supported using cable racks, cable hooks and cable rack locking clips.
All splices shall be supported by cable hooks under the splice case, NOT the cables that enter each end of the splice case.
Telecommunications industry standard cable hooks of the appropriate length shall be provided to support cables and splice cases.
All cable hooks shall be secured using cable hook locking clips.
MH/HH Requirements
Cable Rack Cable Hook Hook Locking Clip
Hook Locking Clip Pulling Iron Sump Pan w/Lid
Lock Down Device MH Lid
April 2022 Page 7 of 20
MH/HH Examples of Unacceptable Standards
Installed Above Grade Cable Left On Floor Tracer Wire Not Capped
Plastic Not Removed Debris Left in Hole Debris, Cable & Tracer in Water
MH/HH Examples of Acceptable Standards
Installed at Grade Tracer Tagged and Capped Ropes Tied to Steps
Mx Loop Racked Duct Destination Marked Ducts Properly Sealed
April 2022 Page 8 of 20
UNDERGROUND CONDUIT SYSTEM
The Contractor shall be responsible for any required trenching and/or boring necessary to lay the duct system. Contractor is also responsible for backfilling trench lines and compaction of fill materials with appropriate compaction tools.
Provide a minimum of 12" cover of clean fill above the conduit. Backfill material shall be clean and free from all organic material, clay, marl or unstable materials, debris, lumps, or broken paving. No rocks or stones larger than 3 inches in diameter shall be allowed in backfill. Material for backfill may be material resulting from excavation, if it meets the above requirements.
Directional drilling will be used for major road crossings. Otherwise, crossing of paved surfaces may be performed by pavement cuts and resurfacing with appropriate matching road material (road cuts must be coordinated and pre-approved by 81 CES 14 days in advance).
Ducts will be appropriately protected when placed under paved surfaces.
New Conduits/Ducts:
Installation of underground conduits/ducts shall be IAW EIA/TIA/RUS Bulletin standards.
New conduits/ducts shall be corrosion resistant and 4-inch inside diameter (I.D.)
round or metric equivalent.
Ducts shall be made of EPC-40 Polyvinyl Chloride (PVC) (Schedule 40) IAW
NEMA TC-2. For unique situations the ducts shall be EPC-80-PVC (Schedule 80)
IAW NEMA TC-2, high density polyethylene (HDPE) SDR 11.5, Galvanized Iron
Pipe (GIP) or “thick wall” stainless steel. Schedule 80 PVC shall be limited to risers.
High density polyethylene (HDPE) SDR 11.5 shall be used when directional boring is used.
HDPE shall NOT be placed directly into a MH/HH without the appropriate PVC
Terminator. The preferred method is to transition from HDPE to PVC prior to terminating conduit into these structures.
GIP or stainless steel shall be used under taxiways and runways.
Ducts shall have beveled bell ends and enter the MH/HH perpendicular to the surface of the wall through which it is entering and shall be cut flush with the interior wall of the MH/HH. Ducts and openings around ducts shall be sealed to prevent moisture from entering the maintenance holes.
April 2022 Page 9 of 20
All ducts installed, to include beneath roads, sidewalks, parking areas, other paved surfaces or areas to be paved, etc. shall be installed a minimum of 36" below grade.
The Contractor shall provide other protective measures, concrete cap, etc., in those areas where the minimum ground cover cannot be achieved.
New conduits/ducts shall be permanently labeled on the wall of each
Building/MH/HH indicating the connecting Building/MH/HH at the other end of the duct (for example, “To MH-306H” or “To Bldg 1101”).
New single ducts (or a minimum of 1 duct per duct bank) shall be populated with
3 each, 3 inch, 3 cell geotextile/maxcell (1 with tracer wire) for maximum cable placement. Deviations require coordination through 81 CS/SCXP and the responsible maintenance work center for approval.
Upon completion of conduit sections, a test mandrel ¼” (6.4mm) smaller than the inside diameter of the conduit shall be pulled through two diagonally opposite ducts to ensure proper alignment. In addition, all ducts shall be cleared of loose materials such as concrete, mud, dirt, stones, etc.
Bends and Sweeps:
Accomplish changes in the direction of runs exceeding a total of 10 degrees, either vertically or horizontally, by long sweeping bends having a minimum radius of 20 feet. All bends between MHs shall be a minimum of ten times (10X) the diameter of the duct size (i.e., 4 inch duct = 40 inches) with the sum of bends in all directions not exceeding a total of 90 degrees where practical. Coordination with 81 CS/SCXP is required if runs have bends that total more than 90 degrees.
Long sweeps may be made up of one or more curved or straight sections and/or combinations thereof. Bends made manually shall not reduce the internal diameter of the conduit.
The following definitions apply:
o 90-degree bend: Any radius bends in a piece of pipe that changes the direction of the pipe by 90 degrees.
April 2022 Page 10 of 20 o Kick: A bend in a piece of pipe, usually less than 45 degrees, made to change the direction of the pipe.
o Offset: Two bends usually having the same degree of bend, made to avoid an obstruction blocking the run of the pipe.
o 90-degree sweep: A bend that exceeds the manufacturer’s standard size
90-degree bend (e.g., 24 inches is standard for 4-inch conduit).
o Back-to-back 90-degree bend: Any two 90-degree bends placed closer together than 10 feet in a conduit run. Utilize radius-manufactured bends to the maximum extent possible.
Sweeping 90 Elbow 90
Joints and Connectors:
Ducts shall be joined (with glue/cement) in such a manner as to be water tight.
Joints shall form a sufficiently smooth interior surface between joining sections so that cables shall not be damaged when pulled past the joint.
Joints between dissimilar types of ducts (PVC, HDPE, galvanized steel pipe
(GSP), EB, DB, etc.) shall use the appropriate connectors designed for the purpose of providing a seal between the ducts and preventing damage to cables pulled through these joints.
All joint surfaces shall be prepared IAW the manufacturer’s instructions, and, at a minimum, the mating surfaces shall be wiped clean before they are joined.
April 2022 Page 11 of 20
Pull Tape:
All newly installed ducts left vacant shall have a waterproof, corrosion resistant, pre-lubricated flat woven polyester pull tape installed with sequential footage markings, (1250 lb. pulling strength) for future cable installations.
The pull tape shall extend into the maintenance holes/handholes and be secured to a cable rack or pulling iron, etc.
Plugs and Sealers:
All ducts, sub-ducts, HDPE roll pipes and, inner-ducts, whether main or subsidiary runs, shall be plugged using universal duct plugs or removable putty sealants in all MHs, HHs, and building entrances.
Outdoor-rated ducts (sub-ducts, etc.) entering a building will be fire-stopped IAW
NFPA 101, 8.3.4.2.1, local codes, and per manufacturer’s instructions.
Foam spray is not an acceptable sealant on Keesler AFB.
Duct Plug Duct Seal Firestop
April 2022 Page 12 of 20
Spacers:
If the ducts are installed by trenching or excavation, spacers shall be placed at five
(5) foot intervals along the entire length of the duct run.
Tracer Wire:
At least one duct or roll pipe shall have a tracer wire or be otherwise locatable from the surface. NOTE: Maxcell with a Tracer Wire is the preferred method.
The tracer wire shall be exposed; free from the conduit, capped with a wire nut and must NOT be connected to grounds.
The tracer wire shall be secured and routed to the MH/HH neck to a point where maintenance personnel may access the wire without having to enter the MH/HH.
For buildings/communications rooms, attach the tracer wire to backboard above duct entrance.
The tracer wire shall be tagged with a label so indicating it as a “Duct Tracer Wire to xxx – Do Not Remove” (where xxx is the other end of the wire).
April 2022 Page 13 of 20
Warning Tape:
Cable warning tape shall be buried 1’ below the surface and follow the duct route when excavation is the method of duct installation. The tape shall be a minimum of 3” wide and orange in color with the appropriate warning message.
Utility separation:
When communications ducts cross either power duct or buried power cable, maintain a minimum separation of 3 inches of concrete or 12 inches of well-tamped earth between the two or 12 inches of well tamped earth when parallel; for pipes (e.g., gas, water, oil) maintain 6 inches when crossing or 12 inches when parallel.
SPLICE CONNECTIONS/TERMINATIONS
Copper Cable Splices:
All copper cable splicing shall be performed in accordance with EIA/TIA/RUS
Bulletin Standards for Splicing Copper and Fiber Cable. The contractor shall use pic-a-bonds for cables 200-pair and below and 3M 710 splice connectors, or equivalent, for all cables larger than 200-pair.
All copper cable OSP underground splices shall be encased in an appropriate size and type enclosure and installed IAW manufacturer installation guidelines (Ex.
Preformed Line Stainless Steel Splice Enclosure or equivalent).
For Copper OSP no service loop/slack shall be allowed at the terminal or within the MH/HH. Direct buried cables shall be spliced above ground only in a buried distribution terminal or cabinet for ease of maintenance.
April 2022 Page 14 of 20
Copper Cable Terminations:
All OSP copper cable shall be terminated on a protected Building Entrance
Terminal (BET) 110 type/710 splice connectors or 388 central office connectors with primary protector blocks equipped with 5-pin solid state or gas protector module accessories installed.
Fiber Optic Splices:
Intermediate cable splices shall be minimized and consist of fusion splices in a high quality re-enterable splice case.
Only splice closures intended for underground applications shall be used in the underground system. The Contractor shall use standard re-enterable fiber splice closures. The closures shall have adequate strength to protect the splice and maintain cable shield electrical continuity in the below ground environment.
The Government quality inspector shall have the opportunity to inspect the inside of the splice case before closure, pressure testing, and encapsulation is performed.
A coil of 25 feet of cable shall be provided on each cable entering and leaving a splice case in a MH or HH.
Fiber Optic Terminations:
Fiber optic cable termination will be accomplished with SC (UPC) connectors, with no splicing (home run installation), no cassettes and no jumpers/pigtails.
LABELING
The Contractor shall label all equipment and cables they install and cables identified for re-use in accordance with EIA/TIA Standards and as directed by 81 CS/SCXP.
Cable Tags:
All tags shall be permanently labeled, easily visible and corrosion resistant.
Install cable tags in all maintenance holes/hand-holes, cable vaults, pull boxes and building entrance terminal locations.
When cables pass through a maintenance-hole, put a tag on the cable, approximately 2 feet from each duct entrance.
Information on the cable tag shall identify cable by Size, Type, Cable Number and Count. Tagging and labeling of new cables shall be IAW the following:
April 2022 Page 15 of 20
Fiber-Optic Cable Tag Copper Cable Tag
Building fiber is being installed for
ITB 6901 to Building Number 1101
Number of Strands and Cable Type
Fiber Optic Distribution Panel (FODP):
Each FODP shall be stenciled/marked with black ink or paint or adhesive backed decals in letters and numbers. The cover of all new FODPs shall be labeled to conform to the system used by local maintenance personnel to identify FODPs that terminate fiber.
If the manufacturer has not identified the sequence in which ports on FODPs are counted, the Contractor shall provide designation labels/strips to identify the sequence in which they are counted.
Each splice tray shall be marked to identify the fiber count contained in the splice tray. The marking shall identify the FODP by number (building number), cable number, and count.
Example (FODP Label):
Building FODP is installed in
Building FO Cable Connects to
Number of Strands and Cable Type
FO 1101
6901-1101
1-36 SM or MM
FODP 1101
FO 1101 – 6901
1-36 SM or MM
April 2022 Page 16 of 20
COMM EQUIPMENT/MECHANICAL ROOMS
Backboards:
Fire rated Backboards (void-free interior grade A-C plywood, 3/4 inch thick 4’ by
8’ feet shall be provided on three (3) walls and installed 6” from the floor in all telecommunication rooms.
Backboards shall be fire rated by manufacturing process. Fire Stamp shall be clearly visible. Otherwise, non-fire rated plywood must have 2 coats of UL 723 fire retardant paint applied on all 6 sides.
Equipment Cabinets:
All new equipment cabinets shall be lockable and compatible with existing lockable cabinets. Coordinate with the 81 CS/SCXP to ensure a common lock/key in all cabinets matching existing locks/keys.
Equipment cabinets shall have sufficient ventilation, cable pathway access, and space to allow for maintenance and operation of the equipment.
Wall mounted cabinets shall have a fire rated or painted plywood backboard
(same as above) and be securely attached to the wall.
Rail settings within cabinets must be secured, be in a level condition and be positioned so all installed hardware and cables interfacing the hardware do not obstruct the closing of doors when door is in its final position.
Existing/previously installed cabinets shall be re-used to the maximum extent possible.
CABLE MANAGEMENT
The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards.
FOC Maintenance Loop:
The Contractor shall install a minimum of a 25 foot fiber optic cable maintenance loop at every MH/HH location, starting/ending in the first maintenance hole outside each end building.
The maintenance loop shall be properly labeled with a cable tag and securely supported by two cable hooks. Cable hooks are to be positioned so the highest one supports the underside of the top of the coil and the bottom hook supports the underside of the bottom of the coil.
April 2022 Page 17 of 20
The same information shall appear on the Contractor’s completed as-built-drawings.
GROUNDING AND BONDING (TIA-607-B) (If required)
All grounds will be labeled IAW ANSI/TIA Standards (see below for example).
Grounding and Bonding (Racks/Cabinets):
All new and existing racks/cabinets housing equipment, ladder rack and cable tray shall be bonded and grounded to the Equipotential Ground Plane IAW EIA/TIA
Standards.
Equipment cabinets shall be capable of containing any standard equipment shelves for communications equipment per the current EIA/TIA Standards.
The Contractor shall test any new or extended ground at the cabinet/rack and at the new grounding/bonding points.
Cabinets, racks and other enclosures shall not be bonded serially, each shall have its own dedicated bonding conductor IAW EIA/TIA Standards.
April 2022 Page 18 of 20
The government reserves the right to test and validate newly installed grounds to ensure they meet compliance.
Grounding and Bonding (Equipment/Mechanical Rooms):
In the Equipment room/Mechanical room in which the cable is to be terminated, there is either a telecommunications main grounding busbar (TMGB) or a telecommunications grounding busbar (TGB).
If a grounding busbar doesn’t exist in the equipment room/mechanical room, then the Contractor shall provide it and bond it to the electrical service equipment
(power) ground.
The grounding conductor shall be tagged with a nonmetallic tag as close as practicable to the point of termination in a readable position. The information on the tag shall contain the following “If this connector or wire is loose or must be removed, please contact the Base Communications Squadron” or some similar wording.
All ground connections will have a clear margin of bare metal-to-metal contact
IAW ANSI/EIA/TIA Standards.
April 2022 Page 19 of 20
Grounding and Bonding (MH’s/HH’s)
All MH’s/HH’s shall be grounded in accordance with RUS/NEC Standards. The resistance for OSP grounding shall be nominally 10 ohms or less.
All new MH’s/HH’s installed shall include bonding ribbon and grounding system.
Ground rods will be installed externally and connected to MH/HH grounding system.
NOTE - The surface mounted bonding ribbon may only be omitted when the following conditions apply:
o MHs are designed and constructed with an integral ground system with all ironwork bonded together.
o MHs are identified as containing an integral ground system with a manufacturer’s label.
DELIVERABLES
As-Built Drawings:
The 81 CS/SCXP shall supply existing system drawings, and the Contractor shall provide updated drawings in Visio for building and rack elevation; Visio and .pdf for OSP. These drawings shall depict the entire pathway and details of the installation, including but not limited to: labeling, cables, inner-ducts and maintenance holes/handholes, conduits, maintenance loops, distances, bores, trenches, building entrances. Detailed butterfly drawings will also be required. If the existing cable diagram or butterfly drawings are not available; the contractor shall create the missing cable diagram/ butterfly drawings to include all the components used in this project. The Contractor shall record/deliver geospatial data of new outside plant distribution system.
Butterfly Drawings:
The Contractor shall record and submit butterfly, cable path and building penetration drawing information for all new installations including butterfly drawings for all maintenance holes and pull boxes that contain new or reused
FOC. Drawings shall record the path and arrangement of new and reused fiber optic cables, splices, and the arrangement duct banks, ducts, inner-duct and shall show maintenance hole orientation with respect to geodetic north. Drawings shall be submitted in an easily read electronic format such as pdf. Scanned data sheets or legible sketches are acceptable.
April 2022 Page 20 of 20
Copper Test Results:
Testing of new copper cables shall be conducted on 100% of pairs and shall identify any discrepancies. All new copper installations shall be free from any and all cable faults or splicer’s errors to allow for 100% cable usage. The test results shall be documented, corrections implemented and retesting conducted and documented as required. In addition, documentation shall be presented to show the length of the cable between telecommunications rooms. Testing shall be per industry standards. Specific testing procedures will be provided to the contractor by the owning maintenance work center
Fiber Test Results:
All testing shall be accomplished IAW all applicable industry standards.
Attenuation testing for optical fiber shall be performed and documented 1) from manufacturer, 2) upon delivery acceptance/prior to installation, 3) after cable placement/post installation and 4) after all splicing/end terminations have been completed. Any errors or above allowable loss readings will be repaired to bring the faulted fibers to within acceptable parameters. No additional splicing will be allowed in lieu of fiber end-to-end replacement due to manufacturer or installation damage. All strands are to be usable and free of errors providing 100% cable usage. Test Results: Certification of the cable(s) being tested is required to ensure it meets/exceeds requirements.
File details come from the government source that posted it. Updated .