Building 1548 HVAC Site Visit Questions
- Spec. Section 26 05 00.00 2.3 Splices and Connectors – requires that splices in AWG #8 and smaller be done with approved indenter crimp-type connectors and compression tools. Is this going to be required, or will the electrical contractor be allowed to used UL listed, industry standard, approved for the purpose “wire nuts”?
Provide as specified.
- The same section requires that AWG #6 and larger be spliced using bolted clamp-type connectors, and wrapped with insulating tape. Will we be allowed to use the UL listed, pre-insulated type?
Provide as specified.
- Drawing E-0.01 General Note #7 states that EMT shall not be used……provide rigid steel conduit in all areas. Does this include above suspended ceilings and other interior locations?
EMT shall not be used. Provide as specified.
- Drawing E-1.20 Notes 5 & 6 state to reuse existing conduit, but replace existing feeder to RTU-10……..Drawing E-1.30 **Note states to reuse existing feeder. What is to be reused and what is to be replaced?
Dwg E-1-20 is correct, feeder shall be replaced. Disregard note on the dwg E-1-30.