This is a draft salient characteristics document establishing technical specifications for fluid coolers, circulation pumps, and control panels required for HVAC system replacement at Buildings 590 and 591 at JBSA-FSH. The fluid cooler must meet or exceed the cooling capacity of the existing SPX ReCold MW-30C model, operate on 208/230V three-phase power, include dual fans of approximately 3.0 HP each (or equivalent configuration), and feature an internal basin heater rated at approximately 4.0 KW. The circulation pump requirements specify a minimum flow rate of 120 GPM, a 5 HP continuous duty motor operating at standard four-pole speed (approximately 1750-1760 RPM), and 208/230V three-phase electrical compatibility. The control panel must be rated for 208/120V three-phase four-wire power, include a 100A main breaker and two 20A three-pole breakers, and feature a NEMA 3R outdoor-rated enclosure. These specifications establish the performance and compatibility standards that proposed "equal" products must meet to be considered acceptable replacements for the existing equipment, ensuring seamless integration with current facility infrastructure and adequate cooling capacity for the required loads.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

FLUID COOLERS AND PUMPS REPLACEMENT (BLDGS 590 & 591)

To be considered an acceptable "equal" product, all proposed equipment must strictly adhere to the physical dimensions, electrical requirements, and performance capabilities outlined below to ensure compatibility with existing infrastructure and meet required facility cooling loads.

1. Fluid Cooler (Cooling Tower)

· Performance: Must meet or exceed the cooling capacity/tonnage of the existing SPX ReCold MW-30C.

· Electrical: Must operate on 208/230V, 3-Phase power.

· Fans: Dual fans (approx. 3.0 HP each) or an equivalent fan configuration that meets the required cooling performance.

· Heater: Must include an internal basin heater (approx. 4.0 KW).

2. Circulation Pumps

· Flow Rate: Minimum 120 GPM.

· Motor: 5 HP, continuous duty, standard 4-pole speed (approx. 1750-1760 RPM)

· Electrical: Must operate on 208/230V, 3-Phase power.

3. Control Panel

· Power: Rated for 208/120V, 3-Phase, 4-Wire.

· Protection: Includes a 100A, and two 20A 3-pole main breakers

· Enclosure: NEMA 3R (outdoor rated).