Questions and Answers

Q. What does it mean by “Frequency” on the bid schedule? What does it mean when it says 2 years? Overall clarification of the bid schedule is needed.

A. Please see the attached document titled, “Fire Suppression – Explanation of Dates” for the full clarification in red type.

Q. What about the fire panel?

A. Alarm assistance will be provided by Civil Engineering Q. Are the fire pumps electric or diesel?

A. They are all electrical, none are diesel.

Q. What about the hydrants?

A. There is nothing to be done with the hydrants.

Q. What about the floor control valves?

A. There are isolation valves.