Exhibit M10 - PV Service Description.pdf

PDF 270 KB Posted

Attached to
Full Maintenance/O&M Services for Baton Rouge, Houma & Lafayette, LA
Solicitation number
47PH0221R0002
Issued by

View the file

Other files

File Type Posted
Standard Form 30 Solicitation 47PH0221R0002 Amendment PA02.pdf PDF
Clarification Questions Solicitation 47PH0221R0002.pdf PDF
Baton Rouge Houma and Lafayette OM FM Reprocurement Questions and Answers Sol 47PH0221R0002.pdf PDF
Standard Form 33 Solicitation 47PH0221R0002.pdf PDF
Solicitation 47PH0221R0002 Pre-Proposal Conference Agenda Baton Rouge Houma and Lafayette.pptx PPTX presentation
Solicitation 47PH0221R0002 Statement of Work Baton Rouge Houma and Lafayette LA Amendment PA01.pdf PDF
Standard Form 30 Solicitation 47PH0221R0002 Amendment PA01.pdf PDF
Sign-In Sheet for Wednesday March 17 2021.pdf PDF
Figure B-3 Pricing of Services Solicitation 47PH0221R0002 Baton Rouge Lafayette and Houma LA OM FM REVISED Amendment PA01.xlsx XLSX spreadsheet
Sign-In Sheet for Tuesday March 16 2021.pdf PDF
Sign-In Sheet for Monday March 15 2021.pdf PDF
Figure L-3 Past Performance Questionnaire Solicitation No. 47PH0221R0002.pdf PDF
Figure B-3 Pricing of Services Solicitation 47PH0221R0002 Baton Rouge Lafayette and Houma LA OM FM.xlsx XLSX spreadsheet
Exhibit M2 - Green Purchasing Report.pdf PDF
Exhibit C1 - Building Information Sheet LA0006BT Baton Rouge FOB and Courthouse Grounds.pdf PDF
Exhibit M1 - FM Quality Assurance Surveillance Plan Baton Rouge Houma and Lafayette.pdf PDF
Attachment 3 - Service Contract Act (SCA) Wage Determination 2015-5177 Rev No. 12 Dated 12.21.2020 East Baton Rouge Parish.pdf PDF
Exhibit C7 - PBS Waste Audits.pdf PDF
Exhibit M11 - Flag Policy.pdf PDF
Exhibit M5 - Smart Buildings.pdf PDF
Attachment 3 - Service Contract Act (SCA) Wage Determination 2015-5183 Rev No. 15 Dated 12.21.2020 Lafayette Parish.pdf PDF
Attachment 1 - Collective Bargaining Agreement (CBA) Sol 47PH0221R0002.pdf PDF
Exhibit M7 - Qualificaiton of Electrical Testing Technicians.pdf PDF
Exhibit M3 - Environmental Sustainable Products and GSA Attribute Preferences.pdf PDF
Exhibit C5 - Erosion and Sediment Control.pdf PDF
Figure B-2 SCA DOL_CBA Wage Adjustment Spreadsheet for Full Main Comb Union AND Non Union Contracts.xlsx XLSX spreadsheet
Exhibit M6 - Water Treatment .pdf PDF
Figure B-1 for Union and Non Union Contracts.xlsx XLSX spreadsheet
Solicitation 47PH0221R0002 Statement of Work Baton Rouge Houma and Lafayette LA.pdf PDF
Exhibit C1 - Building Information Sheet LA0099ZZ Lafayette.pdf PDF
Exhibit C1 - Building Information Sheet LA0097BT Baton Rouge Long Fed Bldg Grounds.pdf PDF
Exhibit M9 - Preventative Maintenance (PM) 2018 GSA O_M Guide.pdf PDF
Attachment 2 - CBA Wage Determination Sol 47PH0221R0002.pdf PDF
Exhibit C6 - Recycle Solid Waste Trash Report.pdf PDF
Exhibit C4 - Building Exterior and Hardscape Plan.pdf PDF
Figure L-1 Combined Management Plan.xlsx XLSX spreadsheet
Attachment 3 - Service Contract Act (SCA) Wage Determination 2015-5179 Rev No. 12 Dated 12.21.2020 Terrebonne Parish.pdf PDF
Figure L-2 Management Plan Baseline.pdf PDF
Exhibit M4 - Bldg Op Plan Template.pdf PDF
Exhibit M8 - Misc Best Practices Shave Energy.pdf PDF
Exhibit C1 - Building Information Sheet LA0070ZZ Houma.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Exhibit M10

Item

PV Service Description

Frequency/ Response

Time

Visual inspection of Solar Facility’s general site conditions, PV arrays, electrical equipment, mounting structure, fence, shading, trackers, vegetation, animal damage, erosion, corrosion, and discolored panels.

Every 6 months

Visual inspection and correction of Solar Facility for loose electrical connections and ground connections.

String-level open-circuit voltage, DC operating current tests, and I-V curve traces on 100% of all strings.

1x per year

4 All switches and disconnects tested to ensure they are not jammed.

Infrared scans on 100% combiner and re-combiner boxes; tighten connections to manufacturer's torque specification; report broken terminal blocks.

Every 3 years

100% check calibration expiration on sensors and meters, including pyranometers, and anemometers and perform other service such as cleaning and replacement of any desiccant.

Turn off and on logging and communications to ensure they are communicating and ensure battery backups are working.

Inverter preventive maintenance for 100% of all inverters per manufacturer’s operating guidelines

See

8a,8b,8c & 8d

8a Clean inverter cabinet air vents.

8b Clean and change inverter air filters, if present, per manufacturer’s warranty requirements.

8c Clean/remove dust from inverter heat sinks per manufacturer’s warranty requirements.

8d Check torque marks and re-tightening appropriate wiring connections to design specification torque force per manufacturer’s guidelines.

9 Inspect roof penetrations to ensure sealant is applied properly and not degrading.

10 PV array module maintenance for all modules See 10a & 10b

10a Wash all panels with water with no chemicals in a method approved by the

Owner.

10b Perform infrared scan of 100% of modules for two types of circuitry connections: cells on the front and junction boxes on the back.

Every 3 years

*Adapted from the following authority:

Technical Report

NREL/TP-7A40-73822

December 2018