FIBERGLASim Pipe Insulation

INNOVATIONS FOR LIVING'

A.

O Evolution TM - Paper-Free ASJ

O SSL 11°- ASJ

O SSL° I - ASJ

O No-Wrap

Description

Owens Corning FIBERGLAS TM Pipe Insulations are molded of heavy density resin bonded inorganic glass fibers. The one-piece, 36" (914mm) long, hinged sections are opened, placed over the pipe, closed and secured by means specific to the type as described below.

FIBERGLAS TM Pipe Insulation with Evolution TM Paper-Free ASJ is jacketed with durable, paper free all-service vapor retarder jacket.

The SSL Il® double adhesive closure provides positive mechanical and vapor sealing of the longitudinal jacket seam. All Evolution TM Paper-Free ASJ sizes come with the SSL Il ® closure system.

FIBERGLAS SSL Il ® Pipe Insulation is jacketed with a smooth, reinforced, wrinkle resistant all-service vapor retarder jacket (ASJ). This product has the same SSL Il® closure system as EvolutionTM Paper-Free ASJ and is

Product Data Sheet available in the most popular pipe sizes. For the larger ASJ sizes, FIBERGLAS TM Pipe Insulation is furnished with a SSL°1 single adhesive lap seal.

Both systems include pressure sensitive butt strip seals that complete the positive closure system.

FIBERGLAS TM Pipe Insulation is also available without a jacket.

"No Wrap" pipe insulation intended for field installation with jacketing appropriate to the vapor control, damage or corrosion resistance requirements of the application.

Uses

Insulation of hot, cold, concealed and exposed piping operating at temperatures from 0°F (-18°C) to 850°F (454°C) in commercial buildings, industrial facilities and process or power plants.

Product Attributes

EvolutionTM Jacket The jacket is over 3X tougher* than standard ASJ. The paper free all service jacket does not support mold growth** and is designed to have compatble finished job appearance with standard ASJ.

SSL II ® Positive Closure System The double adhesive lap seal and two-part butt strip seal provide effective long tem vapor sealing of the longitudinal and butt joints.

Positive closure is fast, neat and foolproof. There is no need for staples which promotes job site productivity.

Jacket and Lap Shipped Adhered Short pieces of insulation can be cut without jacket loss and the section will not come apart in handling. There are no "dog-ears" in or out of the carton. Dust and moisture cannot reach the lap seal. Butt strips come in sealed bags inside the carton so they can stay clean until the moment of use.

Excellent Thermal Performance FIBERGLAS TM Pipe Insulation's low thermal conductivity contributes to lower operating costs of heating and cooling equipment.

Meets Model Code Fire Ratings The flame spread rating of 25 or less and smoke developed rating of 50 or less usually means that FIBERGLAS TM Pipe Insulation will be granted immediate building code approval.

Application Recommendations

The hinged sections of FIBERGLASTM Pipe Insulation are opened, placed over the pipe, carefully aligned, and sealed or jacketed as required by the form of the insulation and the application.

All jacketed SSL Il® Pipe Insulation is shipped with the jacket and longitudinal lap closed, the two adhesives separated by a release strip. The insulation is opened by pulling the release strip from between the two adhesive strips.

The insulation is placed on the pipe, carefully aligned, and the two adhesives rubbed firmly together to close and seal. The two part butt strip seal completes the positive closure. Application may be at ambient temperatures from 25°F (-4°C) to I10°F (43°C).

Based on puncture resistance, burst strength and tensile strength testing.

" Evolutionim Jacket does not support mold growth when tested in accordance with ASTM CI338.

Fl BERGLASim

INNOVATIONS FOR LIVING'

Product Data Sheet

FIBERGLASTM "No-Wrap" Pipe Insulation is designed for field-jacketing. The pipe covering is secured by wires or bands, and vapor sealed where required.

Outdoor applications must be protected from weather. If painting is required, use only water based latex paint.

E?ecification Compliance

• ASTM C 547, Minera.I Fiber Pipe Insulation, Type I to 850°F (454°C)

• ASTM C 1136, Flexible Low Permeance Vapor Retarders for Thermal Insulation:

Types 1-1V

• ASTM C 795, Thermal Insulation for Use in Contact with Austenitic Stainless Steel'

• ML--22344D, Insulation, Pipe, Thermal, Fibrous Glass

• Nuclear Regulatory Commission Guide 1.36, Non- Metallic Thermal Insulation'

• MIL- I -24244C (Ships) Insulation Material with Special Corrosion, Chloride, and Fluoride Requirements'

• U.S. Coast Guard Approval No. 164.009, Noncombustible Materials (no-wrap)

• CAN/CGSB-5L9 — Type I, Class 22

• New York City MEA No, 344-83, 408-07-M

• NFPA 90A

Notes 1 1-

lot:NI
for totalo.:.•.

Availability FIBERGLAS T" Pipe Insulations are available in thicknesses and for pipe sizes as follows':

Insulation Thickness Nominal Pipe Size

in. (mm) in. (mm)

(13) -2 (15 - 65)

I (25) 1/, - 33 (15 -825)

I IA (38) IA - 33 (15 -825)

2 (51) IA - 33 (15 -825)

2 IA (64) IA - 32 (15 - 800)

3 (76) IA -3I

3V (89)

4 (102) IA -29

4 IA (114) IA -28 (15 700)

5 (127) 'A - 27 (15 - 675)

5IA (140) 6-26 (150 -650)

6 (152) 6-25 (150 - 625)

'Please refer to product packaging and data guide for load factors, standard products, minimum order quantity and carton sizes. Contact your customer service representative for productleadtime.

Physical Property Data Property

Test Method Value

Density (size dependent)

ASTM C302 3.5 to 5.5 pcf

Operating Temperature Range'

ASTM C 411 0°F to 850°F (-I8°C to 454°C)

Jacket Temperature Limitation

ASTM C 1136 to 15u - lr (-29C to 64 - L)

Jacket Permeance

ASTM E 96, Proc.A 0.02 perm

Burst Strength, min

ASf D 774/D 774M 55 psi

Composite Surface Burning Characteristics' uL E 84 or Flame spread 25 c;Irc,M Smoke Developed 50

'Limited to single layer applications above 650°F (343°C), L.ater than 6" (152mm) thickness.
bui ni .t'1ucl1inrth ULTM

1 j1 t H t r s, nearest 5 rating.

Thermal Conductivity

Mean Temperature ° F k

Bt.:., , Ii/hr•li. ,. F

0.22

Mean Temperature

°C

'Aill •:- .. C:

0.032

, 0.23 25 0.034

100 0.24 50

150 0.27 100 0.043

200 0.29 125 0,047

250 0.32 150 0.051

300 0.35 75 0.056

350 0.39 200 0.062

400 0.43 225 0.068

450 0.48 250 0 075

500 0.54 275 0.082

Apparent thermal conductivity values determined in accordance with ASTM practice C 1045 with data obtained by ASTM Test Method C 335. Values are nominal, subject to normal testing and manufacturing tolerances.

FIBERGLASim

INNOVATIONS FOR LIVING'

Product Data Sheet

Personnel Protection Table

Nominal Pipe Size

in. (mm)

0.5 (15)

200 °F

0.5

(93 °C)

(15)

300 °F

0.5

(149 °C)

(15)

System Operating Temperatures °F (°C)

400 °F (204 °C) SOO °F (260 °C)

0.5 (15) 1.0 (25)

600 °F

1.0

(316°C)

(25)

800°F

1.5

(427 °C)

(38)

(20) 0.5 (15) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51)

1 (25) 0.5 (15) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51)

1.25 (32) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.0 (51)

1.5 (40) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.0 (51)

2 (50) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.0 (51)

2.5 (65) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.0 (51)

3 (80) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.5 (64)

4 (100) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.5 (64)

5 (125) 0.5 (15) 0.5 (15) 1.0 (25) 1.0 (25) 1.5 (38) 2.5 (64)

6 (150) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 1.5 (38) 2.5 (64)

7 (175) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 1.5 (38) 2.5 (64)

8 (200) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 1.5 (38) 2.5 (64)

9 (225) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 1.5 (38) 2.5 (64)

10 (250) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 1.5 (38) 2.5 (64)

12 (300) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 1.5 (38) 3.0 '76)

14 (350) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51) 3.0 /6)

16 (400) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51) 3.0

18 (450) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51) 3.0

20 (500) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51) 3.0

24 (600) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51) 3.0

30 (750) 0.5 (15) 0.5 (15) 1.0 (25) 1.5 (38) 2.0 (51) 3.0

'Calculations estimated usIng NA MA 3r Plu, Ver -sI , 4 • d DesIpx, conditions: 9mepl horIzont - PI pipi and outer surface jacket emittance of 0.9. For alternate design conditions, contact your Owens Corning representative.

'Thermal conductivity values used in these calculations are subject to normal manufacturing tolerances.

Thickness to Prevent Surface Condensation

Owens Corning ASJ Jacket for up to 16" NPS (400mm DN), in. (mm) 1.2

Ambient Temperature

°F (°C)

110 03)

Relative Humidity 35°F

I

System Operating Temperatures

(2°C) 45°F (7°C) 55°F

(25) I (25)

(13°C)

, 25)

1 (38) 1 (38) 1 (38)

3 1/, (89) 3 1/, (89) 3 ( /6)

100 (38) , 1 (25) 1 (25) I (25)

8( IV, (38) IV, (38) I (25)

90% 3 1/, (89) 3 (76) 2 1/ (64)

90 (32) 1 (25) 1 (25) I (25)

- IV, (38) 1 (25) I (25)

3 1/, (89) 3 ( /6) 2 1/ (64)

80 (27) 8( IV, (38) 1 (25) I (25)

3 (76) 2 1/, (64) 2 (51)

70 (21) 1 (25) 1 (25) I (25)

, 2 1/, (64) 2 (51) I (25)

'Calculations estimated using NAIMA 3E Plus version 4.0 software. Fixed design conditions: Steel Horizontal Piping, 16" NPS, Omph wind speed, Outer Surface Jacket Fmittance of 0.9.

'Thermal conductivity values used in these calculations are subject to normal manufacturing tolerances.

pHnt tp.mperature, 0 mph

Knauf Data Sheet PE-DS-1e 07-10

EarthwoolTM 1000° Pipe Insulation

• The Knauf Insulation rotary manufacturing process produces insulation with concentric inside diameters and consistent wall thicknesses.

• ASJ+ will provide a professional finished appearance — dimple and wrinkle resistant.

• Earthwool 1000° Pipe offers an extended temperature range—for all applications from 0° to 1000°F.

• ASJ+ is cleanable with a wet cloth and soapy water.

• Earthwool 1000° Pipe’s superior compressive strength allows for fast installation and a neat finished appearance.

• Size, wall thickness and Proto 25/50 rated PVC fitting cover identification are printed on the jacket.

• ECOSE Technology bio-based binder eliminates non-renewable petroleum-based ingredients.

No formaldehyde, no phenol, no acrylics.

• Earthwool contains 40% post-consumer recycled bottle glass.

• Durability: UV light and puncture resistance.

• ASJ+ meets ASTM C 1136 Type I, II, III, IV and meets VIII based on the 85% better puncture resistance (Mullen Burst).

• ASJ+ has substantially less degradation and discoloration after exposure to UV light than traditional ASJ. Earthwool 1000° Pipe Insulation with ASJ+ is not intended for unprotected outdoor use.

• Knauf’s “wind-up” forming mandrel process prevents gaps and inconsistent densities, while making it easy to cleanly notch out sections.

• ASJ+ is moisture resistant to intermittent, short duration liquid water exposure, such as precipitation during construction phase. Earthwool 1000° Pipe Insulation with ASJ+ is not intended for unprotected outdoor use.

Facts at a glance

ASJ ASJ+

EarthwoolTM 1000° Pipe Insulation

Description Knauf Insulation Earthwool™ 1000° Pipe Insulation is a molded, heavy-density, one-piece insulation made from inorganic glass fibers bonded with ECOSE® Technology. It is produced in 3' lengths with or without a factory-applied jacket.

ASJ+ is the newest generation all-service jacket composed of aluminum foil, reinforced with a glass scrim bonded to a kraft paper interleaving with an outer film layer leaving no paper exposed.

A matching ASJ+ butt strip is furnished in the carton for each section. The jacket is white, and the longitudinal lap of the jacket has a self-sealing adhesive.

Earthwool Earthwool is the new benchmark that stands apart for its genuine sustainability, unsurpassed perfor-mance and consistently high product quality.

ECOSE Technology ECOSE Technology is a revolutionary binder based on rapidly renewable bio-based materials rather than non-renewable petroleum-based chemicals such as phenol, formaldehyde or acrylics.

ECOSE Technology reduces Knauf Insulation’s binder embodied energy and contains no phenol, formaldehyde, acrylics or artificial colors found in traditional fiber glass insulation.

Application Earthwool 1000° Pipe Insulation is used to insulate iron and copper piping in industrial applications and in commercial and institutional buildings. Earthwool 1000° Pipe Insulation is suitable for hot, cold, concealed and exposed piping systems operating at temperatures from 0°F-1000°F (-18°C to 538°C).

Additional weather protection is needed outdoors.

Features and Benefits Energy Conservation

• Offers excellent resistance to heat loss or gain, which saves energy and lowers operating costs.

• A low thermal conductivity of .23 at 75°F (24°C).

Low-Cost Installation

• Available with self-sealing lap, which eliminates need for staples, additional material and tools.

• Fast, easy installation reduces labor costs.

Condensation Control

• Installed properly, the foil vapor retarder and pressure-sensitive lap assure a positive vapor seal.

Easy Size Identification

• Pipe size, wall thickness and Proto 25/50 Rated

PVC fitting cover size are printed in a repeat pattern along the longitudinal lap.

• Easy identification at job site.

• Simplifies restocking.

ASJ+

• Professional finished appearance — dimple and wrinkle resistant.

• Cleanable with a wet cloth and soapy water.

• Moisture resistant to intermittent, short duration liquid water exposure, such as precipitation during construction phase.

• ASJ+ has substantially less degradation and discoloration when exposed to UV.

• ASJ+ meets ASTM C1136 Type I, II, III, IV, and meets VIII based on the 85% better puncture resistance of ASJ+ (Mullen Burst).

• Excellent SSL adhesion.

Indoor Air Quality

• Certified for indoor air quality as a low emitting product by The GREENGUARD Environmental Institute to both the GREENGUARD Certification ProgramSM and the more stringent GREENGUARD Children and SchoolsSM standard.

Sustainability

• Carbon negative: meaning Knauf Insulation products used for thermal insulating purposes recover the energy that it took to make them in just hours or a few days, depending on the application. Once installed, the product continues to save energy and reduce carbon generation as long as it is in place.

• Earthwool fiber glass insulation contains three primary ingredients:

• Sand, one of the world’s most abundant and renewable resources

• 40% post-consumer recycled bottle glass

• ECOSE Technology which reduces binder embodied energy by up to 70%

• It is anticipated to reduce its Global

Warming Potential (GWP) by approximately 4%, a significant reduction in our carbon footprint

Specification Compliance In U.S.:

• ASTM C 547; Type I, Type IV

• ASTM C 585

• ASTM C 1136 (jackets); Type I, II, III, IV,VIII

• HH-I-558C; Form D, Type III, Class 12; Class 13

(to 1000°F, 538°C)

• GREENGUARD Certification

• GREENGUARD Children & SchoolsSM Certification

• NFPA 90A and 90B

• USCG 164.109/4/0 (plain, unjacketed only) In Canada:

• CAN/ULC S102-M88

• CCG F1-304 (plain only)

• CGSB 51-GP-9M

• CGSB 51-GP-52M (jacket)

Technical Data - Earthwool 1000° Pipe Insulation Surface Burning Characteristics

• Does not exceed 25 Flame Spread, 50 Smoke

Developed when tested in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 255 and UL 723.

Temperature Range

• Pipe operating temperatures from 0°F to 1000°F

(-18°C to 538°C) at a maximum recommended thickness of 6".

Corrosiveness (ASTM C 665)

• Does not accelerate corrosion on steel, copper or aluminum.

Corrosion (ASTM C 1617)

• The corrosion rate in mils/yr will not exceed that of 1 ppm chloride solution.

Mean Temperature k k (SI)

75°F (24°C) .23 .033

100°F (38°C) .24 .035

200°F (93°C) .28 .040

300°F (149°C) .34 .049

400°F (204°C) .42 .061

500°F (260°C) .51 .074

600°F (316°C) .62 .089

-18

(˚F ) (˚C)

.70

.60

.50

.40

.30

.20

.10

.00

.101

.087

.072

.058

.043

.029

.014

Mean Temperature

Th er m al

C on du ct iv it y (S

I U ni ts

W /m

C)

Th er m al

C on du ct iv it y (B

TU

-i n.

/h r• ft

2 • ° F)

Alkalinity (ASTM C 871)

• Less than 0.6% as Na2O.

• pH between 7.5 and 10.0.

Microbial Growth (ASTM C 1338)

• Does not promote microbial growth.

Water Vapor Sorption (ASTM C 1104)

• Less than 0.2% by volume.

Linear Shrinkage (ASTM C 356)

• Negligible.

Technical Data - ASJ+ Specification Compliance

• ASTM C 1136 (jackets); Type I, II, III, IV, VIII Water Vapor Transmission (ASTM E 96, Procedure A)

• Jacket has a water vapor permeance of

.02 perms or less.

Water Vapor Sorption (ASTM C 1104)

• Less than 0.2% by volume.

Product Forms amd Sizes Produced in 3' (914 mm) sections:

• For iron pipe from ½" to 24" nominal pipe size (15 mm to 610 mm).

• For copper tube from ⅝" to 6 ⅛"

(16 mm to 156 mm).

• Wall thicknesses from ½" to 6" (13 mm to

152 mm) in single layer (for most sizes).

• All insulation inner and outer diameters comply with ASTM C 585.

Packaging

• Four convenient carton sizes for easy ordering, inventory tracking and storage.

• Reinforced carton handles for strength and easy lifting.

• Bar-coded cartons for accurate shipments and tracking.

• Full product range stocked at distributors for fast availability.

Precautions Hot Pipe

• May be installed while the system is in operation, at all temperatures up to 1000°F (538°C).

Thermal Efficiency (ASTM C 335)

Minimum Pipe Insulation (In.)a (to meet ASHRAE 90.1 Requirements)

Insulation Conductivity Nominal Pipe Diameter (in.)

Fluid Design Operating

Temperature Range, °F

Conductivity Range

BTU-in./ (hr∙ft3∙°F)

Mean Temperature

Rating, °F Runoutsb up to 2

1 & less

1 ¼ to 2

2 ½ to 4 5 & 6 8 & up

Heating Systems (Steam, Steam Condensate and Hot Water)

Above 350 32-34 250 1½ 2½ 2½ 3 3½ 3½

251-350 29-31 200 1½ 2 2½ 2½ 3½ 3½

201-250 27-30 150 1 1½ 1½ 2 2 3½

141-200 25-29 125 ½ 1½ 1½ 1½ 1½ 1½

105-140 24-28 100 ½ 1 1 1 1½ 1½ Domestic and Service Hot Water Systemsc

105 and Greater 24-28 100 ½ 1 1 1½ 1½ 1½ Cooling Systems (Chilled Water, Brine, Refrigerant)d

40-55 23-27 75 ½ ½ ½ 1 1 1

Below 40 23-27 75 1 1 1½ 1½ 1½ 1½ a For minimum thicknesses of alternative insulation types, see 9.4.8.2, ASHRAE 90.1.

b Runouts to individual terminal units not exceeding 12 ft. in length.

c Applies to recirculating sections of service or domestic hot water systems and first 8 ft. from storage tank for non-recirculating systems.

d The required minimum thicknesses do not consider water vapor transmission and condensation. Additional insulation, vapor retarders, or both, may be required to limit water vapor transmission and condensation.

For more information call (800) 825-4434, ext. 8300 or visit us online at www.knaufinsulation.us

• Knauf Insulation recommends, for insulation thicknesses greater than 6” (152 mm) the temperature must be increased from 500°F (260°C) to maximum temperature at a rate not exceeding 100°F (56°C) per hour.

• During initial heat-up to operating temperatures above 350°F (177°C), a slight odor and some smoke may be given off as a portion of the bonding material used in the insulation begins to undergo a controlled decomposition.

• If natural convection is not adequate in confined areas, forced ventilation should be provided in order to protect against any harmful fumes and vapors that might be generated.

• Care must also be taken when using sealants, solvents or flammable adhesive during installation.

• A maximum of 6″ (152 mm) wall thickness is recommended.

Cold Pipe

• Use a continuous vapor retarder on piping operating below ambient temperatures.

• Seal all joints, surfaces, seams and fittings to prevent condensation.

• On below freezing applications, and in high-abuse areas, the ASJ+ jacket shall be protected with a PVC vapor retarding outer jacket. In addition, exposed ends of insulation shall be sealed with vapor barrier mastic installed per the mastic manufacturer’s instructions. Vapor seals at butt joints shall be applied at every fourth pipe section joint and at each fitting to isolate any water incursion.

• On chilled water systems operating in high humidity conditions, it is recommended that the same guidelines be followed as listed above for below freezing applications.

• Exterior hanger supports are recommended.

Outside Application

• Do not expose pipe insulation to weather. It must be covered with appropriate jacketing, mastic or vapor retardant adhesives.

• All exposed surfaces must be protected. Proto® Indoor/Outdoor PVC Jacketing is recommended.

See Knauf Guide Specifications for recommended PVC jacketing application guidelines.

• Apply jacketing, mastics or vapor retardant adhesives per manufacturer’s instructions.

For metallic jackets, factory-applied condensate retarders are recommended.

ASJ+ SSL

• Keep adhesive and contact surfaces free from dirt and water, and seal immediately once adhesive is exposed.

• Apply when ambient and insulation temperatures are between 20°F and 130°F (-6.7°C and 54°C).

• If stored below 20°F or above 130°F, allow insulation cartons to stand within recommended temperature range for 24 hours prior to application.

• Do not store product below -20°F (-29°C) or above 150°F (66°C).

• When using Knauf Insulation’s SSL closure system, make sure the longitudinal and circumferential joints are properly sealed by rubbing the closure firmly with a squeegee.

Use of staples is not recommended.

• When using Earthwool 1000° Pipe Insulation, the surface temperature of the insulation should be between -20°F and 150°F (-29°C and 66°C) during the life of the insulation.

Fittings and Hangers

• Use Proto 25/50 Rated (ASTM E 84) PVC

Fitting Covers, applying PVC fittings per Proto’s Data Sheet.

• Fittings should be insulated to same thickness as the adjoining insulation.

• Apply fittings per manufacturer’s instructions.

• When required by specification, a hard insert of sufficient length should be used to avoid compression of the insulation.

Additional Precautions Fiber glass may cause temporary skin irritation.

Wear long-sleeved, loose-fitting clothing, head covering, gloves and eye protection when handling and applying material. Wash with soap and warm water after handling. Wash work clothes separately and rinse washer. Use a disposable mask/respirator designed for nuisance-type dusts where sensitivity to dust and airborne particles may cause irritation to the nose or throat.

Application Guidelines Storage

• Protect insulation from water damage or other abuse, welding sparks and open flame.

• Cartons are not designed for outside storage.

Preparation

• Apply only on clean, dry surfaces.

• Pipe or vessel should be tested and released before insulation is applied.

General Guidelines

• All sections should be firmly butted.

• Seal circumferential joint with a minimum 3"

(76 mm) wide butt strip.

• Jackets, coating and adhesives should have a comparable F.H.C. rating.

• ASJ+ may be painted. As with traditional ASJ, Knauf Insulation does not encourage the painting of ASJ+ because the application of any paint may change the surface burning characteristics and will void the Knauf Insulation Limited Warranty. Where painting is necessary use common water, oil, or solvent-based paints. All paints should be tested for compatibility and adhesion before use.

• All piping should have continuous insulation.

• Position longitudinal lap downward to avoid dirt and moisture infiltration.

• Do not expose pipe insulation to excessive vibration or physical abuse.

• Faced insulation should not have a facing temperature above 150°F (66°C).

Recommended Thicknesses

(ASHRAE 90.1-1989)

The minimum thicknesses are based on ASHRAE 90.1-1989 standards and do not necessarily represent the Economic Thickness of Insulation or the thickness required for proper condensation control. Rather, they serve as minimum recommendations for commercial applications.

For recommended Economic Thickness, install according to Knauf Insulation or NAIMA 3E programs or as specified.

Fiber Glass and Mold Fiber glass insulation will not sustain mold growth.

However, mold can grow on almost any material

Knauf Insulation GmbH One Knauf Drive Shelbyville, IN 46176

Sales and Marketing (800) 825-4434, ext. 8283

Technical Support (800) 825-4434, ext. 8212

Fax (317) 398-3675

Information info.us@knaufinsulation.com

World Wide Web www.knaufinsulation.us

©2010 Knauf Insulation GmbH.

LEED Eligible Product Use of this product may help building projects meet green building standards as set by the Leadership in Energy and Environmental Design (LEED) Green Building Rating System.

MR Credit 4.1 – 4.2 Recycled Content

MR Credit 5.1 – 5.2 Regional Materials

Knauf Earthwool 1000° Pipe Insulation with ECOSE® Technology products are certified for indoor air quality by The GREENGUARD Environmental Institute™, to both the GREENGUARD Certification ProgramSM and the more stringent GREENGUARD For Children and SchoolsSM Standard. www. greenguard.org

The GREENGUARD INDOOR AIR QUALITY CERTIFIED Mark is a registered certification mark used under license through the GREENGUARD Environmental Institute.

when it becomes wet and contaminated. Carefully inspect any insulation that has been exposed to water. If it shows any sign of mold it must be discarded. If the material is wet but shows no evidence of mold, it should be dried rapidly and thoroughly. If it shows signs of facing degradation from wetting, it should be replaced.

Notes The chemical and physical properties of Knauf Insulation Earthwool 1000° Pipe Insulation represent typical average values determined in accordance with accepted test methods. The data is subject to normal manufacturing variations.

The data is supplied as a technical service and is subject to change without notice. References to numerical flame spread ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions.

Check with your Knauf Insulation sales representative to assure information is current.

Ceel-Co® 550 PVC Insulated Fitting Covers and Jacketing

Description

Ceel-Co 550 PVC fitting covers are designed to insulate and to provide a protective covering for pipe fittings. The fitting covers are supplied with Hi-Lo® Temp formaldehyde-free fiber glass insulation inserts from the factory. Ceel-Co PVC jacketing provides a protective covering for insulated or bare pipes. Ceel-Co 550 PVC fitting covers and Ceel-Co jacketing are manufactured from high-impact, gloss white, UV-resistant, polyvinyl chloride which provides a simple, quickly installed system.

Available Shapes and Sizes

Fitting Covers. Ceel-Co 550 Series PVC fitting covers are available for the following: 45° and 90° (0.8 and 1.6 rad.) short and long radius elbows, tees and valves, flanges, reducers, end caps, soil pipe hubs, traps and mechanical groove-type fittings.

Jacketing. Ceel-Co PVC jacketing is available in rolls in thicknesses of 10, 15, 20 and 30 mil (0.3, 0.4, 0.5 and 0.8 mm).

Cut & Curled™ Jacketing. Ceel-Co PVC Cut & Curled jacketing is available in thicknesses of 20 or 30 mil (0.5 mm or 0.8 mm) (30 mil [0.8 mm] recommended for outdoor applications). It is available in factory-cut sizes to fit up to 30” (762 mm) O.D. All sections of Ceel-Co PVC Cut & Curled jacketing are 48” (1219 mm) in length and are factory curled to fit snugly.

Uses

Ceel-Co 550 PVC fitting covers and jacketing are ideally suited for indoor or outdoor use on chilled water, hot water, steam and other piping systems in commercial, institutional, and industrial applications. The fitting covers, when combined with Ceel-Co PVC jacketing and Ceel-Co solvent welding adhesive, form a completely sealed system which meets the requirements of the USDA and FDA for applications in food, beverage, and pharmaceutical facilities.

Qualifications for Use

Hot Systems

• PVC covers must be kept below 150°F (66°C) by use of proper insulation thickness.

• PVC covers should be kept away from contact with, or exposure to, sources of direct or radiated heat.

• For fittings where operating temperatures exceed 250°F

(121°C), or where pipe insulation thickness is greater than 11/2" (38 mm), two or more layers of Hi-Lo Temp insulation inserts are required beneath fitting cover.

Cold Systems

• An approved vapor retarder mastic compatible with PVC must be applied between pipe insulation and fitting cover, and on fitting cover throat overlap seam.

• For fittings where operating temperature is below 45°F (7°C) or where the pipe insulation thickness is greater than 11/2" (38 mm), two or more layers of Hi-Lo Temp insulation inserts are required beneath fitting cover.

CI-80 10-03 (Replaces 2-02)

Refrigerant Systems and Cold Systems in Severe Ambient Conditions

• Mitered pipe insulation segments. Fabricated or premolded insulation shapes may be used in lieu of Hi-Lo Temp insulation inserts.

• An intermediate vapor retarder compatible with PVC is required to completely seal the insulation prior to installing the Ceel-Co 550 PVC fitting cover. Care should be taken to ensure that the vapor barrier mastic is applied between the pipe insulation and the fitting cover, and on fitting cover throat overlap seam.

Totally Sealed Systems (USDA Approval)

• System requires that 20 or 30 mil (0.5 mm or 0.8 mm)

Ceel-Co PVC jacketing is applied to pipe insulation in conjunction with Ceel-Co 550 PVC fitting covers.

• All circumferential and longitudinal seams of jackets and fitting covers should be sealed with Ceel-Co solvent welding adhesive. Circumferential seams should be a minimum 1" (25 mm) overlap, and longitudinal seams should be 11/2" to 2" (38 mm to 51 mm) overlap.

• Upon completion, all seams should visually be checked for seal and touched up, if necessary.

• Slip joints are required periodically between fixed supports and on continuous long runs of straight piping. Slip joints are achieved by increasing circumferential overlap to 8 to 10 inches (203 mm to 254 mm) and applying a flexible white caulking in the overlap area to maintain a sealed system.

Operating Temperature Limits:

PVC: Up to 150°F (66˚C) Insert: 0°F to 450°F (-18°C to 232°C) Flame Spread: 25 or less (up to 30 mil [0.8 mm]) Smoke Developed: 50 or less (up to 30 mil [0.8 mm]) Grade: Weatherable Color: White Finish: Gloss

PVC Fitting Covers and Jacketing

Ceel-Co® 550 PVC Insulated Fitting Covers and Jacketing

CI-80 10-03 (Replaces 2-02)

The physical and chemical properties of Ceel-Co® 550 Series PVC Fitting Covers and Jacketing represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject to change without notice. Any references to numerical flame spread or smoke developed ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the Ceel-Co plant to assure current information.

Specification Compliance USDA, Agriculture Canada New York City MEA #7-87

ICBO

SBCCI

BOCA

ASTM D 1784, Class 16354-C L-P-535E*, Composition A, Type II, Grade GU L-P-1035A*, Composition A, Type II, Grade GU Canada: CGSB 51-GP-53M

CAN/ULC S102-M88

*Impact strength determined by Gardner—SPI test method rather than Izod, since Gardner is more appropriate for PVC sheeting materials.

Physical Properties of Ceel-Co 550 PVC ASTM Test

Property Value Method Specific Gravity 1.48 D 792 Tensile Strength at Yield, psi (kPa) 6,000 (41,370) D 638 Elongation at Yield (MD), % 3.0 D 638 Tensile Modulus,psi (kPa) 470,000 (3,240,650) D 638 Flexural Strength,psi (kPa) 11,600 (79,982) D 638 (min.

.125” [3 mm] thick)

Flexural Modulus, psi (kPa) 460,000 (3,171,700) D 790 Flame Spread 25 or less E 84

(up to 30 mil [0.8 mm]) Smoke Developed 50 or less E 84

(up to 30 mil [0.8 mm]) Electrical Conductance Non-Conductor D 257 Gardner—SPI Impact, 10 mil (0.3 mm) 1.3 D 3679

in. Ib./mil by Ductile Failure 15 mil (0.4 mm) 1.4 (4 lb. [1.8 kg] 20 mil (0.5 mm) 1.5 weight;

30 mil (0.8 mm) 1.6 8 lb. [3.6 kg] for 30 mil [0.8 mm])

Note: Chemical resistance data available on request.

Copyright © 2003 Johns Manville Printed in USA

General Properties of Hi-Lo Temp Formaldehyde-Free Fiber Glass Insulation Insert

“k” Thermal Mean Temperature Btu•in/ conductivity °F °C (hr•ft2•°F) W/m•°C

75 24 .28 .040 150 66 .34 .049 300 149 .45 .065

Temperature limits 0°F to 450°F (-18°C to +232°C) Sanitary Odorless. Will not absorb odors.

Provides no food for insects, rodents, or mildew.

Vibration resistant Will not settle or separate.

Fire safety Meets most requirements of federal, state and local codes. Accepted for commercial, institutional, industrial, and residential projects in all parts of U.S. The fiber glass inserts have UL 25/50 rating and are non-combustible per ASTM E 136.

A Business of Johns Manville

Performance Materials Division P.O. Box 5108 Denver, CO 80217-5108 www.jm.com http://web.jm.com/msds/en2001.pdf

Sheet1
1 Typical Submittal.pdf
Sheet1
CSU Laurel Village Submittal.pdf
Sheet1
H&M Castle Rock Submittal.pdf
Sheet1
1.pdf
Sheet1
1.pdf
Sheet1
H&M Castle Rock Submittal.pdf
Sheet1
1 Typical Submittal.pdf
Sheet1
CSU Laurel Village Submittal.pdf
Sheet1
H&M Castle Rock Submittal.pdf
Sheet1
1.pdf
Sheet1
1.pdf
Sheet1
H&M Castle Rock Submittal.pdf
Sheet1
1 Typical Submittal.pdf
Sheet1
CSU Laurel Village Submittal.pdf
Sheet1
H&M Castle Rock Submittal.pdf
Sheet1
1.pdf
Sheet1
1.pdf
Sheet1
H&M Castle Rock Submittal.pdf
Sheet1

View MSDS:

File details come from the government source that posted it. Updated .