MODEL SN5507S SN5509S

Full Load Pressure - psig 100 125

Capacity at Full Load Pressure - acfm 387 354

Power at Full Load Pressure - bhp 84.8 85.1

Package kW Air-Cooled 68.3 68.5

Package kW Water-Cooled 66.9 67.0

Gear Ratio 1.33 1.22

Fluid Flow - gpm 19.0 17.0

Heat Rejection - Fluid Clr. BTU/min. 2893 2937

Heat Rejection - Aft. Clr. BTU/min. 705 636

Flow at 80°F Water in - gpm 19.0 19.0

Pipe connection NPT In/Out - in. 1 1/2 / 1 1/2 1 1/2 / 1 1/2

Max./Min. Water Pressure - psig 75/25 75/25

Water Outlet Temperature F° 110 110

Air Flow Water-Cooled Fan w/encl. - cfm 2845 2845

Water-Cooled Vent Fan - hp 1/4 1/4

Air Flow Air-Cooled Fan - cfm 6000 6000

Air-Cooled Fan Motor - hp 2.0 2.0

Air-Cooled Fan Motor Nominal Efficiency 88.5% 88.5%

Standard Fan Water Column - in. 1/8 1/8

High Static Fan Water Column - in. 3/4 3/4

Fluid Fill Capacity - U.S. Gal. 5.0 5.0

Volume - Cubic Feet Air (U.S. Gal.) 3.1 (23) 3.1 (23)

Rated Pressure - psig 210 210

Air-Cooled w/enclosure 70 70

Water-Cooled w/enclosure

Inlet Air

Main Lubricant Flow Beta

99.9% Eff. To 3 Microns Per SAE J726C

Beta 20 = 200 Per ISO 16889

SN55S Series - 75 HP 60 Hz Horsepower Rated

Compressor Performance*

Cooling Data

Water-Cooled Series Flow (w/aftercooler)

Cooling Air Flows

Air/Fluid Housing dBA Ratings at 1 Meter (Typical)

CONSULT FACTORY

Filter Rating

For more information, contact Sullair at

219.879.5451 or sullairsolutions@sullair.com www.sullair.com

Sullair Proprietary and Confidential

© 2017 Sullair etankersley Rectangle jkomperud Cloud

Length - in. 87.6 (97.0) 87.6 (97.0)

Width - in. 43.4 (49.9) 43.4 (49.9)

Height - in. 68.5 (77.2) 68.5 (77.2)

Weight - lbs. 3455 (3785) 3455 (3785)

Discharge Connection - in. NPT 2 2

Moisture Drain Connection - in. NPT 1/4 1/4

Electrical Data (Typical across all models) 230V 460V 575V

Motor HP 75 75 75

Motor Nominal Efficiency 95.0% 95.0% 95.0%

Nominal RPM 1780 1780 1780

Frame Size (TEFC) 364/5TSC 364/5TSC 364/5TSC

Service Factor 1.2 1.2 1.2

Nameplate Amps 168.0 84.1 65.8

Locked Rotor Amps - Max. 1076 538 480

Starter Enclosure Rating NEMA 4 NEMA 4 NEMA 4

Starter Size Amp Rating 300 115 115

Fan Amps (Air Cooled) 6.45 3.23 2.58

Package Amps (Air Cooled) 197.3 98.7 78.9

Package Amps (Water Cooled) 193.3 96.8 77.3

NOTE: Data subject to change without notice

TC Doc #: TDS-000346/00

Dimensions & Weights w/Enclosure - Uncrated (Crated)

* Capacity per CAGI/PNEUROP PN2CPTC2 (Annex C to ISO 1217)

For more information, contact Sullair at

219.879.5451 or sullairsolutions@sullair.com www.sullair.com