Exhibit F - Drawings and Specifications.pdf
PDF 5 MB Posted
- Attached to
- Hope Coliseum AC-4 Replacement
- Solicitation number
- RFP202790000749
- Issued by
- West Virginia
About this file
Exhibit F - Drawings and Specifications Summary
This file comprises the electrical drawings and specifications for the Hope Coliseum AC-4 Replacement project at West Virginia University, located at 3450 Monongahela Boulevard, Morgantown, West Virginia. The project involves removing the existing indoor packaged HVAC unit AC-4 and replacing it with a contractor-furnished replacement unit. The electrical work includes disconnecting and removing the existing power connection to the mechanical equipment, disconnecting and removing the disconnect switch, conductors, and conduit serving the existing equipment, and reutilizing existing conductors and conduits under new work. Additional electrical requirements include connecting the new AC-4 unit to the existing circuit previously serving the existing equipment, providing conductor and conduit extensions as required, connecting to the nearest existing 120-volt normal circuit for a new AC-4 DDC (Direct Digital Control) control panel located in the electrical room below, and providing one CAT6/6A data drop for the new control panel with cabling routed from the nearest patch panel. The electrical contractor is responsible for the entire project document set, including all specifications, contract drawings, and addendums, and must review all contract documents prior to bidding and coordinate with all trades to ensure complete operational systems.
The specifications establish detailed electrical requirements including grounding in accordance with the National Electrical Code, labeling of all panelboards, cabinets, disconnect switches, and controllers using machine-engraved, laminated plastic labels, testing of all wiring for continuity and grounds before connecting fixtures, insulation resistance testing on all wiring #8 or larger, and delivery of typewritten signed test reports to the engineer. The electrical contractor must secure extra marked drawings to record all deviations and changes, arrange all necessary inspections, provide temporary electrical service as required for the construction project, verify underground utility locations three working days prior to digging, and schedule all work and power outages at times convenient to the owner with prior notification before turning off any circuits. Additional requirements include coordination with mechanical and other contractors for equipment locations and rough-in specifications, compliance with conductor size specifications for circuit runs exceeding specified distances, provision of panelboard directory cards with circuit load information, and cleanup at project closeout to remove all paint spatters and replace inoperative lamps.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Exhibit F - Drawings and Specifications
TELE/DATAELECTRICAL GENERAL NOTES POWER FIRE ALARMGENERAL
GENERAL DEMOLITION NOTES
SHEET
DET #
GENERAL
UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN
ON THE ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED
UNDER THIS CONTRACT. THE CONTRACTOR IS RESPONSIBLE FOR
THE ENTIRE PROJECT DOCUMENT SET, INCLUDING ALL
SPECIFICATIONS, CONTRACT DRAWINGS, ADDENDUMS, ETC. PRIOR
TO THEIR BID, THE CONTRACTOR SHALL REVIEW ALL CONTRACT
DOCUMENTS. IF WORK ON OTHER TRADE DRAWINGS OR WITHIN
OTHER DIVISION SPECIFICATIONS HAS EQUIPMENT, DEVICES,
APPURTENANCES, ETC. INCLUDED WITHIN THEM REQUIRING
ELECTRICAL EQUIPMENT OR POWER FEEDS IN ORDER TO PROVIDE
A COMPLETE OPERATIONAL SYSTEM, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO INCLUDE WITHIN THEIR BID AND PAY FOR ALL
ELECTRICAL WORK REQUIRED TO COMPLETE THOSE SYSTEMS.
THE CONTRACTOR SHALL SUBMIT REQUESTS FOR INFORMATION
DURING THE BIDDING PHASE FOR ALL DISCREPANCIES,
CONFLICTS, CONSTRUCTABILITY ISSUES, AND CLARIFICATIONS
NEEDED IN ORDER FOR THE CONTRACTOR TO PROVIDE COMPLETE
OPERATIONAL SYSTEMS FOR THIS PROJECT.
COORDINATION
COORDINATE AND COOPERATE WITH ALL TRADES ON THE
PROJECT.
RECORD DRAWINGS
SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON
SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE PROJECT
PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL
DEVIATIONS BETWEEN THE WORK SHOWN ON THE DRAWINGS AND
THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKED
DRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND
REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS IN THE
COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE
OWNER AT PROJECT CLOSE OUT.
TESTS
TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE
CONNECTING ANY FIXTURES OR DEVICES. PERFORM INSULATION
RESISTANCE TESTS ON ALL WIRING #8 OR LARGER TO ENSURE
THAT ALL PORTIONS ARE FREE FROM SHORT-CIRCUITS AND
GROUNDS. PROVIDE TYPEWRITTEN SIGNED REPORTS TO
ENGINEER WITH RESULTS.
INSPECTIONS
ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED
INSPECTION CERTIFICATES TO THE OWNER.
GROUNDING
PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE
ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES, CONDUITS,
SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS,
AND OTHER EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN
ALL POWER CIRCUITS.
LABELS
PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY
SWITCHES, MOTOR-DISCONNECT SWITCHES, AND MOTOR
CONTROLLERS. LABELS SHALL BE MACHINE ENGRAVED,
LAMINATED PLASTIC, PERMANENTLY ATTACHED WITH
SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF ADHESIVE
LABELS. PROVIDE ADDITIONAL LABELS FOR CLARITY AT THE
ENGINEER'S REQUEST.
J-BOX LABELING
LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER
IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS
WITHIN.
CONDUCTOR SIZE
USE #10 AWG CONDUCTORS (MINIMUM) FOR ALL 20 AMP, 120 VOLT
CIRCUIT RUNS GREATER THAN 50' ONE WAY FROM PANELBOARD
TO FIRST DEVICE/FIXTURE. USE #10 AWG CONDUCTORS (MINIMUM)
FOR ALL 20 AMP, 277 VOLT CIRCUIT RUNS GREATER THAN 100' ONE
WAY FROM PANELBOARD TO FIRST DEVICE/FIXTURE.
PANEL DIRECTORY
PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH
PANELBOARD INCLUDING EXISTING PANELBOARDS MODIFIED FOR
THIS PROJECT WITH CIRCUIT LOAD INFORMATION AND ROOM
NUMBER CLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN
THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THE
CONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT.
MOTOR COORDINATION
MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL
DISCONNECT SWITCHES, AND CONTACTORS SHALL BE PROVIDED
WITH THEIR RESPECTIVE PIECES OF EQUIPMENT BY THE
EQUIPMENT SUPPLIER. COMMUNICATE WITH THE TRADES
PROVIDING THE EQUIPMENT, VERIFYING ALL REQUIREMENTS.
PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED THEREIN, AND
INSTALL MOTOR STARTERS.
MOTOR DISCONNECTS
ALL MOTORS SHALL HAVE DISCONNECTING MEANS.
MOTOR FUSE PROTECTION
WHERE FUSE PROTECTION IS SPECIFICALLY REQUIRED BY THE
EQUIPMENT MANUFACTURER, PROVIDE FUSED SWITCHES IN LIEU
OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED CIRCUIT
BREAKERS, OR OTHER DEVICES INDICATED.
CONNECTION DETAILS
SECURE APPROVED SHOP DRAWINGS SHOWING WIRING
DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER
INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE
CONNECTED ELECTRICALLY.
EQUIPMENT DETAILS
MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY
THE MECHANICAL CONTRACTOR. THE LOCATIONS SHOWN ON THE
ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH
THE MECHANICAL CONTRACTOR TO DETERMINE THE EXACT
LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE THE
EXACT ROUGH-IN AND CONNECTION REQUIREMENTS.
STARTER MOUNTING
WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH, STARTER, OR
CIRCUIT BREAKER IS SHOWN ADJACENT TO ITS RESPECTIVE LOAD
AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS,
BRACKETS, ANCHORING, ETC. NECESSARY TO PROPERLY
SUPPORT THE DEVICE.
LIGHTING ARRANGEMENT
ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE
ARCHITECTURAL REFLECTED CEILING PLANS.
LIGHTING COORDINATION
COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS,
SPRINKLER HEADS, AND ACCESS PANELS, ETC.
MATERIAL COORDINATION
VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR
TO ORDERING LIGHT FIXTURES OR OTHER DEVICES TO ENSURE
PROPER FIXTURE OR DEVICE IS FURNISHED TO MATCH
CONSTRUCTION.
MOUNTING HEIGHTS
MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR
TO THE CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE
NOTED. MOUNTING HEIGHTS OF LIGHTING FIXTURES ARE TO THE
BOTTOM OF THE FIXTURE UNLESS OTHERWISE NOTED.
DEVICE LOCATIONS
COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND
TELE/DATA OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH
AS THERMOSTATS AND CONTROL STATIONS. DO NOT MOUNT
WIRING DEVICES BACK TO BACK. PROVIDE MINIMUM OF ONE STUD
SEPARATION.
EWC RECEPTACLES
RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC) SHALL BE
INSTALLED OUT OF VIEW AND BEHIND THE EWC ENCLOSURE.
VERIFY THE MOUNTING HEIGHT WITH THE EQUIPMENT SUPPLIER
PRIOR TO ROUGH-IN.
DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE
ALL CASEWORK, DOOR SWINGS, AND CABINET DRAWINGS AND
ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO
ROUGH-IN OF OUTLET BOXES.
BARRIERS
WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT
VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE
SEPARATED, PROVIDE THE CODE-REQUIRED SEPARATION USING
A FULL HEIGHT AND DEPTH BARRIER PLATE.
FIRE PROOFING
FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED
STRUCTURES, PROVIDE FIRE-PROOFING TO SEAL ALL THE
PENETRATIONS AFTER THE RACEWAY HAS BEEN INSTALLED. FIRE
PROOFING FOR PENETRATIONS SHALL BE UL APPROVED PER THE
PENETRATION MADE IN ORDER TO MAINTAIN FIRE RATED
INTEGRITY OF THE STRUCTURE.
CLEAN UP
ON PROJECT CLOSE-OUT, CLEAN ALL ELECTRICAL DEVICES,
LIGHTING FIXTURES, LAMPS AND LENSES, AND REMOVE ALL PAINT
SPATTERS FROM DEVICES, FIXTURES, AND PLATES. REPLACE ALL
INOPERATIVE LAMPS.
OWNER FURNISHED EQUIPMENT
CONTRACTOR SHALL OBTAIN CUT SHEETS, INSTALLATION DATA,
AND ROUGH-IN REQUIREMENTS FOR OWNER FURNISHED,
CONTRACTOR INSTALLED EQUIPMENT AND COORDINATE
ROUGH-IN AND POWER REQUIREMENTS WITH THE OWNER'S
REPRESENTATIVE PRIOR TO STARTING ANY ASSOCIATED WORK.
CONDUIT ROUTING
ALL CONDUIT RUN OVERHEAD SHALL BE RUN AT THE BOTTOM OF
THE FLOOR, ROOF STRUCTURE, OR LOWEST CHORD OF JOIST
SPACE (AS APPLICABLE) ABOVE IN ORDER TO AVOID CONFLICTS
WITH OTHER TRADES. ALL CONDUITS SHALL BE RUN PARALLEL OR
PERPENDICULAR TO BUILDING LINES AND USE RIGHT ANGLE
OFFSETS TO CHANGE DIRECTION.
WIRING DEVICES
ALL RECEPTACLES AND SWITCHES SHALL BE LABELED WITH
PLASTIC LAMINATED LABEL WITH THE PANELBOARD DESIGNATION
AND CIRCUIT NUMBER FROM WHICH IT IS FED.
EQUIPMENT DEMONSTRATION
PROVIDE A DEMONSTRATION OF THE OPERATION OF ALL
ELECTRICAL COMPONENTS UPON REQUEST OF THE OWNER.
REFER TO SPECIFICATION SECTION 260501 FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
CEILING PLENUM
ALL WIRING THAT WILL NOT BE RUN IN CONDUIT SHALL BE PLENUM
RATED.
TEMPORARY ELECTRICAL SERVICE
PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR
CONSTRUCTION PROJECT. REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
UNDERGROUND WORK
THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL
UNDERGROUND UTILITIES WITHIN THE CONSTRUCTION AREA
THREE WORKING DAYS PRIOR TO DIGGING. NOTIFY THE STATE
AUTHORITY HAVING JURISDICTION AND AWAIT THE REQUIRED
TIME BEFORE COMMENCING EXCAVATION.
CONFLICT NOTIFICATION
NOTIFY THE OWNER'S REPRESENTATIVE, ARCHITECT, AND
ENGINEER PRIOR TO PROCEEDING WITH WORK IF A CONFLICT IS
FOUND BETWEEN THE DRAWINGS, SPECIFICATIONS, AND/OR FIELD
CONDITIONS. THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL
COSTS AND CONSEQUENCES IF THE ABOVE LISTED PARTIES ARE
NOT CONTACTED FOR A RESOLUTION PRIOR TO PROCEEDING
WITH THE WORK.
WIRE SIZE NOTE
ALL 15A AND 20A BRANCH AND LIGHTING CIRCUITS OVER 100 FEET
IN LENGTH SHALL UTILIZE #10 AWG FOR HOT CONDUCTORS AND
#12 FOR GROUND CONDUCTORS UNLESS OTHERWISE NOTED ON
DRAWINGS OR SPECIFICATIONS.
GENERAL
DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND
FIELD INVESTIGATION PRIOR TO DEMOLITION. VISIT THE
EXISTING BUILDING PRIOR TO BID IN ORDER TO BECOME
FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TO
AVOID CONFLICTS.
DEMOLITION (DASHED) ITEMS
ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS, AND/OR
TAGGED WITH 'DM', ARE EXISTING, AND SHALL BE REMOVED
COMPLETE INCLUDING: BOXES, CONDUIT, WIRE, FASTENERS,
AND ASSOCIATED APPURTENANCES, UON.
EXISTING TO REMAIN (SOLID) ITEMS
ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS, AND/OR
TAGGED WITH 'XR', ARE EXISTING TO REMAIN.
CIRCUITING TO REMAIN
EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED OR
RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW
WORK IN ORDER TO MAINTAIN CONTINUITY OF CIRCUIT.
REUSE OF EXISTING CIRCUITRY
EXISTING CIRCUITRY SERVING LIGHTING FIXTURES AND/OR
RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED WHERE
CONVENIENT TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT
MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO
MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUIT THAT
REMAIN.
EXTENSION OF EXISTING CIRCUITS
WHERE AN EXISTING CIRCUIT IS NOTED TO BE SAVED AND
REUTILIZED, EXTEND EXISTING CIRCUIT SAVED DURING
DEMOLITION AS REQUIRED TO SERVE EQUIPMENT IN NEW
LOCATION.
EXISTING CONDUIT
ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE
REUSED SHALL BE REMOVED WHERE THEY WILL BE EXPOSED
UPON COMPLETION OF NEW WORK. EXISTING CONDUIT TO
REMAIN CONCEALED IN WALLS SHALL BE ABANDONED.
EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE
CUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED
FLUSH. ALL EXISTING WIRING IN CONDUITS TO BE ABANDONED
SHALL BE DISCONNECTED FROM POWER SOURCE AND
REMOVED.
REPAIR DAMAGE
EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT
NO ADDITIONAL COST TO OWNER, AND DAMAGE CAUSE TO
EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.
ASSOCIATED APPURTENANCES
REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS,
STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT
TO BE REMOVED BY OTHERS.
KNOCKOUT PLUGS AND COVERS
ALL CONDUIT REMOVED SHALL BE REMOVED IN ITS ENTIRETY,
INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE,
ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS
CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER
PLATES FOR ALL OPENED OUTLET BOXES CREATED BY THE
REMOVAL OF THE EQUIPMENT AND/OR DEVICES.
DEMOLISHED MATERIALS
ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE
RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER,
SHALL BECOME PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED COMPLETELY FROM THE SITE.
SCHEDULE OUTAGES
ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING
SHALL BE SCHEDULED AT TIMES CONVENIENT TO THE OWNER.
NOTIFICATION
NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.
EXISTING CIRCUITS
IF DURING THE COURSE OF CONSTRUCTION, IT ITS DETERMINED BY
THE CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE,
THE CONTRACTOR SHALL UPDATE THE PANELBOARD DIRECTORY
TO INDICATE SUCH, EVEN IF IT IS NOT EXPLICITLY MARKED ON THE
ELECTRICAL PLANS.
DJ
J
M
M
VFD
# NUMBERED NOTE
DETAIL OR SECTION NOTATION
INDICATES CONTINUATION OF LINE
BRANCH CIRCUIT WIRING
HOMERUN BACK TO PANELBOARD
ABBREVIATIONS
XD
A AMPERE
ADM ADMINISTRATOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CURRENT
AV AUDIO/VISUAL
BFG BELOW FINISHED GRADE
CM CEILING MOUNTED
C CONDUIT
CATV CABLE ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CB CIRCUIT BREAKER
CF COFFEE MAKER
CH CHIME
CKT CIRCUIT
CO CENTER OFF
DM DEMOLISH
DO DOOR OPEN
E EMERGENCY
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EPO EMERGENCY POWER OFF
EWC ELECTRIC WATER COOLER
EXP EXPLOSION PROOF
F
FIRE ALARM
FF FLUSH FLOOR MOUNTED
FHP FRACTIONAL HORSE POWER
FL FLUORESCENT
FLA FULL LOAD AMPS
FO FIBER OPTIC
FPC FIRE PROTECTION CONTRACTOR
FSS FUSED SAFETY SWITCH
FU FUSE
G GROUND FAULT CIRCUIT INTERRUPTER
GC GENERAL CONTRACTOR
GND GROUND
HOA HAND-OFF INTERRUPTER
HP HORSE POWER
HVAC HEATING VENTILATING, AND AIR CONDITIONING
IR INFRARED
IG ISOLATED GROUND
JB JUNCTION BOX
K KEY
KVA KILO-VOLT AMPERE
KW KILO-WATT
LTG LIGHTING
LV LOW VOLTAGE
LVC LOW VOLTAGE CONTRACTOR
M MOTOR
MCA MINIMUM CIRCUIT AMPS
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
ML MULTI-LINE
MLO MAIN LUGS ONLY
MTD MOUNTED
MW MICROWAVE
N NURSE CALL
NE NORMAL / EMERGENCY
NEC NATIONAL ELECTRICAL CODE
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION AGENCY
NFSS NON-FUSED SAFETY SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
P POLE
PA PAGING SYSTEM
PC PLUMBING CONTRACTOR
PF POWER FACTOR
PH PHASE
PL PILOT LIGHT
PNL PANEL
RED RELOCATED EXISTING DEVICE
REF REFRIGERATOR
REL RELOCATE
S SOUND SYSTEM
SE SERVICE ENTRANCE
SPD SURGE PROTECTIVE DEVICE
SW SWITCH
T TELEPHONE
TBB TELEPHONE BACKBOARD
TL TWIST LOCK
TR TAMPER RESISTANT
TYP TYPICAL
U ULTRASONIC
UGC UNDERGROUND COMMUNICATIONS
UGE UNDERGROUND ELECTRIC
UF UNDERGROUND FIBER
UPS UNINTERRUPTED POWER SUPPLY
USB UNIVERSAL SERIAL BUS
UT UNDERGROUND TELEPHONE
UON UNLESS OTHERWISE NOTED
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
WM WALL MOUNTED
W WATTS
WG WIRE GUARD
WR WEATHER RESISTANT
WT WATER TIGHT
XFMR TRANSFORMER
XR EXISTING TO REMAIN
XRN EXISTING TO BE REPLACED WITH NEW
F
DM
DUPLEX RECEPTACLE, 20A/120V
JUNCTION BOX FLUSH IN WALL
JUNCTION BOX ABOVE CEILING
MOTOR CONNECTION
MOTOR STARTING SWITCH
VARIABLE FREQUENCY DRIVE, FURNISHED BY
MECHANICAL EQUIPMENT SUPPLIER, INSTALLED AND
POWERED BY EC
DISCONNECT SWITCH. FRAME AND FUSE AS NOTED
FUSED DISCONNECT SWITCH. FRAME AND FUSE AS
NOTED.
EXISTING PANELBOARD
FIRE ALARM SYSTEM DUCT MOUNTED
PHOTO-ELECTRIC SMOKE DETECTOR, PROVIDE
REMOTE INDICATOR IN NEAREST ACCESSIBLE
LOCATION.
DAMPER MOTOR CONNECTION
WALL MOUNTED DATA OUTLET, 4"X4"X2 1/4" BOX
WITH SINGLE GANG PLASTER RING, WITH 3/4"C
STUBBED ABOVE ACCESSIBLE CEILING AND
TERMINATED WITH INSULATED BUSHING. XD
INDICATES DATA CABLE COUNT FROM OUTLET TO
PATCH PANEL
A
Pittsburgh 2000 Park Lane Drive Suite 250 Pittsburgh, PA 15275 P 412.262.1220 www.cjlengineering.com
Johnstown 232 Horner Street Johnstown, PA 15902 P 814.536.1651
Frederick 5285 Westview Drive Suite 203 Frederick, MD 21703 P 301.695.9424
Erie 153 East 13th Street Suite 2200 Erie, PA 16503 P 814.636.0878
Baltimore 1266 Battery Avenue Baltimore, MD 21230 P 304.695.9424
Morgantown 1097 Chaplin Road Morgantown, WV 26501 P 304.983.7001
Seal / Signature
WEST VIRGINIA
UNIVERSITY
HOPE COLISEUM
AC-4 REPLACEMENT
3450 Monongahela Blvd Morgantown, WV 26505
10/29/2026
BID & PERMIT SET
Project Number 26-0614 © 2026 CJL Engineering, Inc.
Sheet Number
Sheet Description
Date Issued 00-00-0000
Rev Description Date
10/29/2026 4:41 PM
B
C
D
E
F
G
87654321
ENGINEERING
E001
ELECTRICAL
COVER SHEET
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text 15969
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text T
AutoCAD SHX Text S
M
DM
DM
DM
EXISTING AC-4
NUMBERED NOTES
DISCONNECT AND REMOVE EXISTING POWER
CONNECTION TO EXISTING MECHANICAL EQUIPMENT.
DISCONNECT AND REMOVE DISCONNECT SWITCH,
CONDUCTORS, AND CONDUIT SERVING EXISTING
EQUIPMENT. UNDER NEW WORK EXISTING
CONDUCTORS AND CONDUITS SHALL BE REUTILIZED.
A
Pittsburgh 2000 Park Lane Drive Suite 250 Pittsburgh, PA 15275 P 412.262.1220 www.cjlengineering.com
Johnstown 232 Horner Street Johnstown, PA 15902 P 814.536.1651
Frederick 5285 Westview Drive Suite 203 Frederick, MD 21703 P 301.695.9424
Erie 153 East 13th Street Suite 2200 Erie, PA 16503 P 814.636.0878
Baltimore 1266 Battery Avenue Baltimore, MD 21230 P 304.695.9424
Morgantown 1097 Chaplin Road Morgantown, WV 26501 P 304.983.7001
Seal / Signature
WEST VIRGINIA
UNIVERSITY
HOPE COLISEUM
AC-4 REPLACEMENT
3450 Monongahela Blvd Morgantown, WV 26505
10/29/2026
BID & PERMIT SET
Project Number 26-0614 © 2026 CJL Engineering, Inc.
Sheet Number
Sheet Description
Date Issued 00-00-0000
Rev Description Date
10/29/2026 4:42 PM
B
C
D
E
F
G
87654321
ENGINEERING
E101
PARTIAL
EQUIPMENT LEVEL
DEMOLITION PLAN -
ELECTRICAL
PARTIAL EQUIPMENT LEVEL DEMOLITION PLAN - ELECTRICAL
1/4" = 1'-0"
E101
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text 15969
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text T
VFD
M
AC-4
2 3
NUMBERED NOTES
CONNECT TO EXISTING CIRCUIT PREVIOUSLY
SERVING EXISTING AC-4. PROVIDE CONDUCTOR AND
CONDUIT EXTENSIONS AS REQUIRED.
CONNECT TO NEAREST EXISTING 120V NORMAL
CIRCUIT FOR NEW AC-4 DDC CONTROL PANEL IN
ELECTRICAL ROOM BELOW. COORDINATE FINAL
CONTROL PANEL LOCATION WITH THE MECHANICAL
CONTRACTOR AND OWNER. PROVIDE CONDUCTOR
AND CONDUIT EXTENSIONS AS REQUIRED.
PROVIDE (1) CAT6/6A DATA DROP FOR NEW AC-4 DDC
CONTROL PANEL IN ELECTRICAL ROOM BELOW.
PROVIDE CAT6/6A CABLING FROM THE TO NEAREST
PATCH PANEL TO THE NEW AC-4 DDC CONTROL
PANEL. COORDINATE FINAL CONTROL PANEL
LOCATION WITH THE MECHANICAL CONTRACTOR
AND OWNER. COORDINATE CATEGORY CABLING AND
COLOR WITH THE OWNER PRIOR TO PURCHASE.
APPROXIMATE LOCATION OF ELECTRICAL ROOM ON
FLOOR BELOW.
A
Pittsburgh 2000 Park Lane Drive Suite 250 Pittsburgh, PA 15275 P 412.262.1220 www.cjlengineering.com
Johnstown 232 Horner Street Johnstown, PA 15902 P 814.536.1651
Frederick 5285 Westview Drive Suite 203 Frederick, MD 21703 P 301.695.9424
Erie 153 East 13th Street Suite 2200 Erie, PA 16503 P 814.636.0878
Baltimore 1266 Battery Avenue Baltimore, MD 21230 P 304.695.9424
Morgantown 1097 Chaplin Road Morgantown, WV 26501 P 304.983.7001
Seal / Signature
WEST VIRGINIA
UNIVERSITY
HOPE COLISEUM
AC-4 REPLACEMENT
3450 Monongahela Blvd Morgantown, WV 26505
10/29/2026
BID & PERMIT SET
Project Number 26-0614 © 2026 CJL Engineering, Inc.
Sheet Number
Sheet Description
Date Issued 00-00-0000
Rev Description Date
10/29/2026 4:42 PM
B
C
D
E
F
G
87654321
ENGINEERING
E201
PARTIAL
EQUIPMENT LEVEL
PLAN - ELECTRICAL
PARTIAL EQUIPMENT LEVEL PLAN - ELECTRICAL
1/4" = 1'-0"
E201
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text 15969
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text E
AutoCAD SHX Text W
AutoCAD SHX Text T
File details come from the government source that posted it. Updated .