Exhibit F - Drawings and Specifications.pdf

PDF 5 MB Posted

Attached to
Hope Coliseum AC-4 Replacement
Solicitation number
RFP202790000749
Issued by
West Virginia

About this file

Exhibit F - Drawings and Specifications Summary

This file comprises the electrical drawings and specifications for the Hope Coliseum AC-4 Replacement project at West Virginia University, located at 3450 Monongahela Boulevard, Morgantown, West Virginia. The project involves removing the existing indoor packaged HVAC unit AC-4 and replacing it with a contractor-furnished replacement unit. The electrical work includes disconnecting and removing the existing power connection to the mechanical equipment, disconnecting and removing the disconnect switch, conductors, and conduit serving the existing equipment, and reutilizing existing conductors and conduits under new work. Additional electrical requirements include connecting the new AC-4 unit to the existing circuit previously serving the existing equipment, providing conductor and conduit extensions as required, connecting to the nearest existing 120-volt normal circuit for a new AC-4 DDC (Direct Digital Control) control panel located in the electrical room below, and providing one CAT6/6A data drop for the new control panel with cabling routed from the nearest patch panel. The electrical contractor is responsible for the entire project document set, including all specifications, contract drawings, and addendums, and must review all contract documents prior to bidding and coordinate with all trades to ensure complete operational systems.

The specifications establish detailed electrical requirements including grounding in accordance with the National Electrical Code, labeling of all panelboards, cabinets, disconnect switches, and controllers using machine-engraved, laminated plastic labels, testing of all wiring for continuity and grounds before connecting fixtures, insulation resistance testing on all wiring #8 or larger, and delivery of typewritten signed test reports to the engineer. The electrical contractor must secure extra marked drawings to record all deviations and changes, arrange all necessary inspections, provide temporary electrical service as required for the construction project, verify underground utility locations three working days prior to digging, and schedule all work and power outages at times convenient to the owner with prior notification before turning off any circuits. Additional requirements include coordination with mechanical and other contractors for equipment locations and rough-in specifications, compliance with conductor size specifications for circuit runs exceeding specified distances, provision of panelboard directory cards with circuit load information, and cleanup at project closeout to remove all paint spatters and replace inoperative lamps.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Exhibit F - Drawings and Specifications

TELE/DATAELECTRICAL GENERAL NOTES POWER FIRE ALARMGENERAL

GENERAL DEMOLITION NOTES

SHEET

DET #

GENERAL

UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN

ON THE ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED

UNDER THIS CONTRACT. THE CONTRACTOR IS RESPONSIBLE FOR

THE ENTIRE PROJECT DOCUMENT SET, INCLUDING ALL

SPECIFICATIONS, CONTRACT DRAWINGS, ADDENDUMS, ETC. PRIOR

TO THEIR BID, THE CONTRACTOR SHALL REVIEW ALL CONTRACT

DOCUMENTS. IF WORK ON OTHER TRADE DRAWINGS OR WITHIN

OTHER DIVISION SPECIFICATIONS HAS EQUIPMENT, DEVICES,

APPURTENANCES, ETC. INCLUDED WITHIN THEM REQUIRING

ELECTRICAL EQUIPMENT OR POWER FEEDS IN ORDER TO PROVIDE

A COMPLETE OPERATIONAL SYSTEM, IT IS THE CONTRACTOR'S

RESPONSIBILITY TO INCLUDE WITHIN THEIR BID AND PAY FOR ALL

ELECTRICAL WORK REQUIRED TO COMPLETE THOSE SYSTEMS.

THE CONTRACTOR SHALL SUBMIT REQUESTS FOR INFORMATION

DURING THE BIDDING PHASE FOR ALL DISCREPANCIES,

CONFLICTS, CONSTRUCTABILITY ISSUES, AND CLARIFICATIONS

NEEDED IN ORDER FOR THE CONTRACTOR TO PROVIDE COMPLETE

OPERATIONAL SYSTEMS FOR THIS PROJECT.

COORDINATION

COORDINATE AND COOPERATE WITH ALL TRADES ON THE

PROJECT.

RECORD DRAWINGS

SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON

SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE PROJECT

PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL

DEVIATIONS BETWEEN THE WORK SHOWN ON THE DRAWINGS AND

THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKED

DRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND

REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS IN THE

COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE

OWNER AT PROJECT CLOSE OUT.

TESTS

TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE

CONNECTING ANY FIXTURES OR DEVICES. PERFORM INSULATION

RESISTANCE TESTS ON ALL WIRING #8 OR LARGER TO ENSURE

THAT ALL PORTIONS ARE FREE FROM SHORT-CIRCUITS AND

GROUNDS. PROVIDE TYPEWRITTEN SIGNED REPORTS TO

ENGINEER WITH RESULTS.

INSPECTIONS

ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED

INSPECTION CERTIFICATES TO THE OWNER.

GROUNDING

PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE

ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES, CONDUITS,

SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS,

AND OTHER EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN

ALL POWER CIRCUITS.

LABELS

PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY

SWITCHES, MOTOR-DISCONNECT SWITCHES, AND MOTOR

CONTROLLERS. LABELS SHALL BE MACHINE ENGRAVED,

LAMINATED PLASTIC, PERMANENTLY ATTACHED WITH

SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF ADHESIVE

LABELS. PROVIDE ADDITIONAL LABELS FOR CLARITY AT THE

ENGINEER'S REQUEST.

J-BOX LABELING

LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER

IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS

WITHIN.

CONDUCTOR SIZE

USE #10 AWG CONDUCTORS (MINIMUM) FOR ALL 20 AMP, 120 VOLT

CIRCUIT RUNS GREATER THAN 50' ONE WAY FROM PANELBOARD

TO FIRST DEVICE/FIXTURE. USE #10 AWG CONDUCTORS (MINIMUM)

FOR ALL 20 AMP, 277 VOLT CIRCUIT RUNS GREATER THAN 100' ONE

WAY FROM PANELBOARD TO FIRST DEVICE/FIXTURE.

PANEL DIRECTORY

PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH

PANELBOARD INCLUDING EXISTING PANELBOARDS MODIFIED FOR

THIS PROJECT WITH CIRCUIT LOAD INFORMATION AND ROOM

NUMBER CLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN

THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THE

CONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT.

MOTOR COORDINATION

MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL

DISCONNECT SWITCHES, AND CONTACTORS SHALL BE PROVIDED

WITH THEIR RESPECTIVE PIECES OF EQUIPMENT BY THE

EQUIPMENT SUPPLIER. COMMUNICATE WITH THE TRADES

PROVIDING THE EQUIPMENT, VERIFYING ALL REQUIREMENTS.

PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED THEREIN, AND

INSTALL MOTOR STARTERS.

MOTOR DISCONNECTS

ALL MOTORS SHALL HAVE DISCONNECTING MEANS.

MOTOR FUSE PROTECTION

WHERE FUSE PROTECTION IS SPECIFICALLY REQUIRED BY THE

EQUIPMENT MANUFACTURER, PROVIDE FUSED SWITCHES IN LIEU

OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED CIRCUIT

BREAKERS, OR OTHER DEVICES INDICATED.

CONNECTION DETAILS

SECURE APPROVED SHOP DRAWINGS SHOWING WIRING

DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER

INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE

CONNECTED ELECTRICALLY.

EQUIPMENT DETAILS

MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY

THE MECHANICAL CONTRACTOR. THE LOCATIONS SHOWN ON THE

ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH

THE MECHANICAL CONTRACTOR TO DETERMINE THE EXACT

LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE THE

EXACT ROUGH-IN AND CONNECTION REQUIREMENTS.

STARTER MOUNTING

WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH, STARTER, OR

CIRCUIT BREAKER IS SHOWN ADJACENT TO ITS RESPECTIVE LOAD

AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS,

BRACKETS, ANCHORING, ETC. NECESSARY TO PROPERLY

SUPPORT THE DEVICE.

LIGHTING ARRANGEMENT

ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE

ARCHITECTURAL REFLECTED CEILING PLANS.

LIGHTING COORDINATION

COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS,

SPRINKLER HEADS, AND ACCESS PANELS, ETC.

MATERIAL COORDINATION

VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR

TO ORDERING LIGHT FIXTURES OR OTHER DEVICES TO ENSURE

PROPER FIXTURE OR DEVICE IS FURNISHED TO MATCH

CONSTRUCTION.

MOUNTING HEIGHTS

MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR

TO THE CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE

NOTED. MOUNTING HEIGHTS OF LIGHTING FIXTURES ARE TO THE

BOTTOM OF THE FIXTURE UNLESS OTHERWISE NOTED.

DEVICE LOCATIONS

COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND

TELE/DATA OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH

AS THERMOSTATS AND CONTROL STATIONS. DO NOT MOUNT

WIRING DEVICES BACK TO BACK. PROVIDE MINIMUM OF ONE STUD

SEPARATION.

EWC RECEPTACLES

RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC) SHALL BE

INSTALLED OUT OF VIEW AND BEHIND THE EWC ENCLOSURE.

VERIFY THE MOUNTING HEIGHT WITH THE EQUIPMENT SUPPLIER

PRIOR TO ROUGH-IN.

DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE

ALL CASEWORK, DOOR SWINGS, AND CABINET DRAWINGS AND

ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO

ROUGH-IN OF OUTLET BOXES.

BARRIERS

WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT

VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE

SEPARATED, PROVIDE THE CODE-REQUIRED SEPARATION USING

A FULL HEIGHT AND DEPTH BARRIER PLATE.

FIRE PROOFING

FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED

STRUCTURES, PROVIDE FIRE-PROOFING TO SEAL ALL THE

PENETRATIONS AFTER THE RACEWAY HAS BEEN INSTALLED. FIRE

PROOFING FOR PENETRATIONS SHALL BE UL APPROVED PER THE

PENETRATION MADE IN ORDER TO MAINTAIN FIRE RATED

INTEGRITY OF THE STRUCTURE.

CLEAN UP

ON PROJECT CLOSE-OUT, CLEAN ALL ELECTRICAL DEVICES,

LIGHTING FIXTURES, LAMPS AND LENSES, AND REMOVE ALL PAINT

SPATTERS FROM DEVICES, FIXTURES, AND PLATES. REPLACE ALL

INOPERATIVE LAMPS.

OWNER FURNISHED EQUIPMENT

CONTRACTOR SHALL OBTAIN CUT SHEETS, INSTALLATION DATA,

AND ROUGH-IN REQUIREMENTS FOR OWNER FURNISHED,

CONTRACTOR INSTALLED EQUIPMENT AND COORDINATE

ROUGH-IN AND POWER REQUIREMENTS WITH THE OWNER'S

REPRESENTATIVE PRIOR TO STARTING ANY ASSOCIATED WORK.

CONDUIT ROUTING

ALL CONDUIT RUN OVERHEAD SHALL BE RUN AT THE BOTTOM OF

THE FLOOR, ROOF STRUCTURE, OR LOWEST CHORD OF JOIST

SPACE (AS APPLICABLE) ABOVE IN ORDER TO AVOID CONFLICTS

WITH OTHER TRADES. ALL CONDUITS SHALL BE RUN PARALLEL OR

PERPENDICULAR TO BUILDING LINES AND USE RIGHT ANGLE

OFFSETS TO CHANGE DIRECTION.

WIRING DEVICES

ALL RECEPTACLES AND SWITCHES SHALL BE LABELED WITH

PLASTIC LAMINATED LABEL WITH THE PANELBOARD DESIGNATION

AND CIRCUIT NUMBER FROM WHICH IT IS FED.

EQUIPMENT DEMONSTRATION

PROVIDE A DEMONSTRATION OF THE OPERATION OF ALL

ELECTRICAL COMPONENTS UPON REQUEST OF THE OWNER.

REFER TO SPECIFICATION SECTION 260501 FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

CEILING PLENUM

ALL WIRING THAT WILL NOT BE RUN IN CONDUIT SHALL BE PLENUM

RATED.

TEMPORARY ELECTRICAL SERVICE

PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR

CONSTRUCTION PROJECT. REFER TO SPECIFICATIONS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS.

UNDERGROUND WORK

THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL

UNDERGROUND UTILITIES WITHIN THE CONSTRUCTION AREA

THREE WORKING DAYS PRIOR TO DIGGING. NOTIFY THE STATE

AUTHORITY HAVING JURISDICTION AND AWAIT THE REQUIRED

TIME BEFORE COMMENCING EXCAVATION.

CONFLICT NOTIFICATION

NOTIFY THE OWNER'S REPRESENTATIVE, ARCHITECT, AND

ENGINEER PRIOR TO PROCEEDING WITH WORK IF A CONFLICT IS

FOUND BETWEEN THE DRAWINGS, SPECIFICATIONS, AND/OR FIELD

CONDITIONS. THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL

COSTS AND CONSEQUENCES IF THE ABOVE LISTED PARTIES ARE

NOT CONTACTED FOR A RESOLUTION PRIOR TO PROCEEDING

WITH THE WORK.

WIRE SIZE NOTE

ALL 15A AND 20A BRANCH AND LIGHTING CIRCUITS OVER 100 FEET

IN LENGTH SHALL UTILIZE #10 AWG FOR HOT CONDUCTORS AND

#12 FOR GROUND CONDUCTORS UNLESS OTHERWISE NOTED ON

DRAWINGS OR SPECIFICATIONS.

GENERAL

DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND

FIELD INVESTIGATION PRIOR TO DEMOLITION. VISIT THE

EXISTING BUILDING PRIOR TO BID IN ORDER TO BECOME

FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TO

AVOID CONFLICTS.

DEMOLITION (DASHED) ITEMS

ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS, AND/OR

TAGGED WITH 'DM', ARE EXISTING, AND SHALL BE REMOVED

COMPLETE INCLUDING: BOXES, CONDUIT, WIRE, FASTENERS,

AND ASSOCIATED APPURTENANCES, UON.

EXISTING TO REMAIN (SOLID) ITEMS

ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS, AND/OR

TAGGED WITH 'XR', ARE EXISTING TO REMAIN.

CIRCUITING TO REMAIN

EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED OR

RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW

WORK IN ORDER TO MAINTAIN CONTINUITY OF CIRCUIT.

REUSE OF EXISTING CIRCUITRY

EXISTING CIRCUITRY SERVING LIGHTING FIXTURES AND/OR

RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED WHERE

CONVENIENT TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT

MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO

MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUIT THAT

REMAIN.

EXTENSION OF EXISTING CIRCUITS

WHERE AN EXISTING CIRCUIT IS NOTED TO BE SAVED AND

REUTILIZED, EXTEND EXISTING CIRCUIT SAVED DURING

DEMOLITION AS REQUIRED TO SERVE EQUIPMENT IN NEW

LOCATION.

EXISTING CONDUIT

ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE

REUSED SHALL BE REMOVED WHERE THEY WILL BE EXPOSED

UPON COMPLETION OF NEW WORK. EXISTING CONDUIT TO

REMAIN CONCEALED IN WALLS SHALL BE ABANDONED.

EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE

CUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED

FLUSH. ALL EXISTING WIRING IN CONDUITS TO BE ABANDONED

SHALL BE DISCONNECTED FROM POWER SOURCE AND

REMOVED.

REPAIR DAMAGE

EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT

NO ADDITIONAL COST TO OWNER, AND DAMAGE CAUSE TO

EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.

ASSOCIATED APPURTENANCES

REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS,

STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT

TO BE REMOVED BY OTHERS.

KNOCKOUT PLUGS AND COVERS

ALL CONDUIT REMOVED SHALL BE REMOVED IN ITS ENTIRETY,

INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE,

ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS

CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER

PLATES FOR ALL OPENED OUTLET BOXES CREATED BY THE

REMOVAL OF THE EQUIPMENT AND/OR DEVICES.

DEMOLISHED MATERIALS

ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE

RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER,

SHALL BECOME PROPERTY OF THE CONTRACTOR AND SHALL BE

REMOVED COMPLETELY FROM THE SITE.

SCHEDULE OUTAGES

ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING

SHALL BE SCHEDULED AT TIMES CONVENIENT TO THE OWNER.

NOTIFICATION

NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.

EXISTING CIRCUITS

IF DURING THE COURSE OF CONSTRUCTION, IT ITS DETERMINED BY

THE CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE,

THE CONTRACTOR SHALL UPDATE THE PANELBOARD DIRECTORY

TO INDICATE SUCH, EVEN IF IT IS NOT EXPLICITLY MARKED ON THE

ELECTRICAL PLANS.

DJ

J

M

M

VFD

# NUMBERED NOTE

DETAIL OR SECTION NOTATION

INDICATES CONTINUATION OF LINE

BRANCH CIRCUIT WIRING

HOMERUN BACK TO PANELBOARD

ABBREVIATIONS

XD

A AMPERE

ADM ADMINISTRATOR

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CURRENT

AV AUDIO/VISUAL

BFG BELOW FINISHED GRADE

CM CEILING MOUNTED

C CONDUIT

CATV CABLE ANTENNA TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

CB CIRCUIT BREAKER

CF COFFEE MAKER

CH CHIME

CKT CIRCUIT

CO CENTER OFF

DM DEMOLISH

DO DOOR OPEN

E EMERGENCY

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EPO EMERGENCY POWER OFF

EWC ELECTRIC WATER COOLER

EXP EXPLOSION PROOF

F

FIRE ALARM

FF FLUSH FLOOR MOUNTED

FHP FRACTIONAL HORSE POWER

FL FLUORESCENT

FLA FULL LOAD AMPS

FO FIBER OPTIC

FPC FIRE PROTECTION CONTRACTOR

FSS FUSED SAFETY SWITCH

FU FUSE

G GROUND FAULT CIRCUIT INTERRUPTER

GC GENERAL CONTRACTOR

GND GROUND

HOA HAND-OFF INTERRUPTER

HP HORSE POWER

HVAC HEATING VENTILATING, AND AIR CONDITIONING

IR INFRARED

IG ISOLATED GROUND

JB JUNCTION BOX

K KEY

KVA KILO-VOLT AMPERE

KW KILO-WATT

LTG LIGHTING

LV LOW VOLTAGE

LVC LOW VOLTAGE CONTRACTOR

M MOTOR

MCA MINIMUM CIRCUIT AMPS

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

ML MULTI-LINE

MLO MAIN LUGS ONLY

MTD MOUNTED

MW MICROWAVE

N NURSE CALL

NE NORMAL / EMERGENCY

NEC NATIONAL ELECTRICAL CODE

NF NON-FUSED

NFPA NATIONAL FIRE PROTECTION AGENCY

NFSS NON-FUSED SAFETY SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

P POLE

PA PAGING SYSTEM

PC PLUMBING CONTRACTOR

PF POWER FACTOR

PH PHASE

PL PILOT LIGHT

PNL PANEL

RED RELOCATED EXISTING DEVICE

REF REFRIGERATOR

REL RELOCATE

S SOUND SYSTEM

SE SERVICE ENTRANCE

SPD SURGE PROTECTIVE DEVICE

SW SWITCH

T TELEPHONE

TBB TELEPHONE BACKBOARD

TL TWIST LOCK

TR TAMPER RESISTANT

TYP TYPICAL

U ULTRASONIC

UGC UNDERGROUND COMMUNICATIONS

UGE UNDERGROUND ELECTRIC

UF UNDERGROUND FIBER

UPS UNINTERRUPTED POWER SUPPLY

USB UNIVERSAL SERIAL BUS

UT UNDERGROUND TELEPHONE

UON UNLESS OTHERWISE NOTED

V VOLTS

VFD VARIABLE FREQUENCY DRIVE

WM WALL MOUNTED

W WATTS

WG WIRE GUARD

WR WEATHER RESISTANT

WT WATER TIGHT

XFMR TRANSFORMER

XR EXISTING TO REMAIN

XRN EXISTING TO BE REPLACED WITH NEW

F

DM

DUPLEX RECEPTACLE, 20A/120V

JUNCTION BOX FLUSH IN WALL

JUNCTION BOX ABOVE CEILING

MOTOR CONNECTION

MOTOR STARTING SWITCH

VARIABLE FREQUENCY DRIVE, FURNISHED BY

MECHANICAL EQUIPMENT SUPPLIER, INSTALLED AND

POWERED BY EC

DISCONNECT SWITCH. FRAME AND FUSE AS NOTED

FUSED DISCONNECT SWITCH. FRAME AND FUSE AS

NOTED.

EXISTING PANELBOARD

FIRE ALARM SYSTEM DUCT MOUNTED

PHOTO-ELECTRIC SMOKE DETECTOR, PROVIDE

REMOTE INDICATOR IN NEAREST ACCESSIBLE

LOCATION.

DAMPER MOTOR CONNECTION

WALL MOUNTED DATA OUTLET, 4"X4"X2 1/4" BOX

WITH SINGLE GANG PLASTER RING, WITH 3/4"C

STUBBED ABOVE ACCESSIBLE CEILING AND

TERMINATED WITH INSULATED BUSHING. XD

INDICATES DATA CABLE COUNT FROM OUTLET TO

PATCH PANEL

A

Pittsburgh 2000 Park Lane Drive Suite 250 Pittsburgh, PA 15275 P 412.262.1220 www.cjlengineering.com

Johnstown 232 Horner Street Johnstown, PA 15902 P 814.536.1651

Frederick 5285 Westview Drive Suite 203 Frederick, MD 21703 P 301.695.9424

Erie 153 East 13th Street Suite 2200 Erie, PA 16503 P 814.636.0878

Baltimore 1266 Battery Avenue Baltimore, MD 21230 P 304.695.9424

Morgantown 1097 Chaplin Road Morgantown, WV 26501 P 304.983.7001

Seal / Signature

WEST VIRGINIA

UNIVERSITY

HOPE COLISEUM

AC-4 REPLACEMENT

3450 Monongahela Blvd Morgantown, WV 26505

10/29/2026

BID & PERMIT SET

Project Number 26-0614 © 2026 CJL Engineering, Inc.

Sheet Number

Sheet Description

Date Issued 00-00-0000

Rev Description Date

10/29/2026 4:41 PM

B

C

D

E

F

G

87654321

ENGINEERING

E001

ELECTRICAL

COVER SHEET

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text 15969

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text T

AutoCAD SHX Text S

M

DM

DM

DM

EXISTING AC-4

NUMBERED NOTES

DISCONNECT AND REMOVE EXISTING POWER

CONNECTION TO EXISTING MECHANICAL EQUIPMENT.

DISCONNECT AND REMOVE DISCONNECT SWITCH,

CONDUCTORS, AND CONDUIT SERVING EXISTING

EQUIPMENT. UNDER NEW WORK EXISTING

CONDUCTORS AND CONDUITS SHALL BE REUTILIZED.

A

Pittsburgh 2000 Park Lane Drive Suite 250 Pittsburgh, PA 15275 P 412.262.1220 www.cjlengineering.com

Johnstown 232 Horner Street Johnstown, PA 15902 P 814.536.1651

Frederick 5285 Westview Drive Suite 203 Frederick, MD 21703 P 301.695.9424

Erie 153 East 13th Street Suite 2200 Erie, PA 16503 P 814.636.0878

Baltimore 1266 Battery Avenue Baltimore, MD 21230 P 304.695.9424

Morgantown 1097 Chaplin Road Morgantown, WV 26501 P 304.983.7001

Seal / Signature

WEST VIRGINIA

UNIVERSITY

HOPE COLISEUM

AC-4 REPLACEMENT

3450 Monongahela Blvd Morgantown, WV 26505

10/29/2026

BID & PERMIT SET

Project Number 26-0614 © 2026 CJL Engineering, Inc.

Sheet Number

Sheet Description

Date Issued 00-00-0000

Rev Description Date

10/29/2026 4:42 PM

B

C

D

E

F

G

87654321

ENGINEERING

E101

PARTIAL

EQUIPMENT LEVEL

DEMOLITION PLAN -

ELECTRICAL

PARTIAL EQUIPMENT LEVEL DEMOLITION PLAN - ELECTRICAL

1/4" = 1'-0"

E101

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text 15969

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text T

VFD

M

AC-4

2 3

NUMBERED NOTES

CONNECT TO EXISTING CIRCUIT PREVIOUSLY

SERVING EXISTING AC-4. PROVIDE CONDUCTOR AND

CONDUIT EXTENSIONS AS REQUIRED.

CONNECT TO NEAREST EXISTING 120V NORMAL

CIRCUIT FOR NEW AC-4 DDC CONTROL PANEL IN

ELECTRICAL ROOM BELOW. COORDINATE FINAL

CONTROL PANEL LOCATION WITH THE MECHANICAL

CONTRACTOR AND OWNER. PROVIDE CONDUCTOR

AND CONDUIT EXTENSIONS AS REQUIRED.

PROVIDE (1) CAT6/6A DATA DROP FOR NEW AC-4 DDC

CONTROL PANEL IN ELECTRICAL ROOM BELOW.

PROVIDE CAT6/6A CABLING FROM THE TO NEAREST

PATCH PANEL TO THE NEW AC-4 DDC CONTROL

PANEL. COORDINATE FINAL CONTROL PANEL

LOCATION WITH THE MECHANICAL CONTRACTOR

AND OWNER. COORDINATE CATEGORY CABLING AND

COLOR WITH THE OWNER PRIOR TO PURCHASE.

APPROXIMATE LOCATION OF ELECTRICAL ROOM ON

FLOOR BELOW.

A

Pittsburgh 2000 Park Lane Drive Suite 250 Pittsburgh, PA 15275 P 412.262.1220 www.cjlengineering.com

Johnstown 232 Horner Street Johnstown, PA 15902 P 814.536.1651

Frederick 5285 Westview Drive Suite 203 Frederick, MD 21703 P 301.695.9424

Erie 153 East 13th Street Suite 2200 Erie, PA 16503 P 814.636.0878

Baltimore 1266 Battery Avenue Baltimore, MD 21230 P 304.695.9424

Morgantown 1097 Chaplin Road Morgantown, WV 26501 P 304.983.7001

Seal / Signature

WEST VIRGINIA

UNIVERSITY

HOPE COLISEUM

AC-4 REPLACEMENT

3450 Monongahela Blvd Morgantown, WV 26505

10/29/2026

BID & PERMIT SET

Project Number 26-0614 © 2026 CJL Engineering, Inc.

Sheet Number

Sheet Description

Date Issued 00-00-0000

Rev Description Date

10/29/2026 4:42 PM

B

C

D

E

F

G

87654321

ENGINEERING

E201

PARTIAL

EQUIPMENT LEVEL

PLAN - ELECTRICAL

PARTIAL EQUIPMENT LEVEL PLAN - ELECTRICAL

1/4" = 1'-0"

E201

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text 15969

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text T

File details come from the government source that posted it. Updated .