Exhibit_E-_Ocean_Kitchen_Reno_Calculations_package_SS_(1).pdf

PDF 930 KB Posted

Attached to
Daytona Beach Ocean Center Kitchen Renovation
Solicitation number
26-P-126JD, C2096
Issued by
Volusia County, Florida

About this file

This is a structural calculations package prepared by Bliss & Nyitray, Inc., a structural engineering firm, for the City of Daytona Beach, Florida, in support of the Ocean Center Kitchen Renovation Project. The document contains detailed structural engineering calculations and wind load analyses for rooftop structures and equipment installations associated with the kitchen renovation. The project is located at 101 N Atlantic Ave, Daytona Beach, FL 32118, and the calculations were issued on April 22, 2026, by Professional Engineer Alejandra Martinez McCombie (Florida P.E. Registration No. 87411). The structural analysis addresses wind pressures, snow loads, and seismic requirements in accordance with the 2023 Florida Building Code for an Assembly occupancy classification (Risk Category III). The building parameters include a length of 435.5 feet, width of 291.0 feet, and mean roof height of 76.8 feet with specific load calculations for rooftop structures and canopies.

The calculations establish nominal wind pressures and load cases for two rooftop equipment installations, with vertical and horizontal wind force calculations presented for multiple wind directions. Wind load analyses indicate base pressures of 35.2 psf at the mean roof height with directional factors applied. The document includes windborne debris zone mapping from Volusia County, Florida, and specifies live loads for assembly areas at 100 psf for lobbies and corridors and 12-20 psf for roof areas. The structural design accounts for wind factors of 1.00 and seismic importance factors of 1.25, with fire ratings of 1.0 hour for both roof and floor systems. This engineering support documentation provides the technical foundation required for contractor bid preparation and project execution for the kitchen renovation improvements.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5835 Waterford Distr ic t Drive, Sui te 400 | Miami , F lorida 33126 | PHONE 305-442-7086 www.bniengineers .com

Miami | Tal lahassee | West Palm Beach

Structural Calculations for Daytona Beach

Ocean Center Kitchen Renovations

Pages 1-4

Daytona Beach, Florida

Issued

April 22, 2026

Prepared by:

Bliss & Nyitray, Inc.

Structural Engineers

5835 Waterford District Drive, Suite 400 Miami, Florida 33126

Tel. 305.442.7086 www.BNIengineers.com

CA 674

BNI Project No. 26M52

Alejandra Martinez McCombie, P.E.

Florida P.E. Registration No. 87411

April 22, 2026

Calculations have been prepared by the undersigned engineer assuming responsibility for manual and computer-generated information.

L I C E N S

E

P R

O F

E

S S I O NA L E NG

I N E

E R

F L

O R I D A

STATE OF

AL

EJ

ANDRA MART I NEZ

NO. 87411

McCOMB I E

Seal:

http://www.bniengineers.com/

Windspeed Contours - Cat 1 Bldgs

Windspeed Contours - Cat 2 Bldgs

Windspeed Contours - Cat 3 Bldgs

Windspeed Contours - Cat 4 Bldgs

Windspeed Zones - Cat 1 Bldgs

Windspeed Zones - Cat 2 Bldgs

Windspeed Zones - Cat 3 Bldgs

Windspeed Zones - Cat 4 Bldgs

Debris Zone - Cat 1 Bldg

Debris Zone - Cat 2 Bldgs

Debris Zone - Cat 3 Bldgs

Debris Zone - Cat 4 Bldgs & Health Care Facilities

Legend

FDEP, Esri, TomTom, Garmin, SafeGraph, GeoTechnologies, 0 2 4mi

Zoom to

Category 3 Bldgs: 120

CAT1_BLDGS 120

CAT2_BLDGS 130

CAT3_BLDGS 140

CAT4_BLDGS 150

WINDBRNE1 N

WINDBRNE2 N

WINDBRNE3 Y

WINDBRNE4 Y

4/6/26, 3:32 PM Windborne Debris Zones & Contours https://volusiacountyfl.maps.arcgis.com/apps/Embed/index.html?webmap=794f11cc7d394594a05cdf2601898518&extent=-81.7309,28.7883,-80.4098,… 1/1

Source:

https://volusiacountyfl.maps.arcgis.com/apps/Embed/index.html?webmap=794f11cc7d394594a05cdf2601898518&extent=-81.7309,28.7883,-80.4098,29.

3429&zoom=true&scale=true&search=true&searchextent=true&legendlayers=true&basemap_gallery=true&disable_scroll=true&theme=light javascript:void(0);

JOB TITLE Ocean Center Daytona Beach

JOB NO. 26M52 SHEET NO.

CALCULATED BY AM DATE

CHECKED BY DATE

CS2024 Ver 2024-01-24 www.struware.com

STRUCTURAL CALCULATIONS

FOR

Ocean Center Daytona Beach

101 N Atlantic Ave, Daytona Beach, FL 32118

Bliss & Nyitray, Inc. JOB TITLE Ocean Center Daytona Beach

Structural Engineers

Miami | West Palm Beach | Tallahasse | Tampa | Dallas JOB NO. 26M52 SHEET NO.

CALCULATED BY AM DATE

CHECKED BY DATE

www.struware.com

Code Search

Code:

Occupancy:

Occupancy Group = A

Risk Category & Importance Factors:

Risk Category = III

Wind Factor = 1.00 use 0.60 NOTE: Output will be nominal wind pressures

Snow Factor 1.00

Seismic Importance factor = 1.25

Type of Construction:

Fire Rating:

Roof = 1.0 hr

Floor = 1.0 hr

Building Geometry:

Roof angle (θ) 0.00 / 12 0.0 deg

Building length 435.5 ft

Least width 291.0 ft

Mean Roof Ht (h) 76.8 ft

Parapet ht above grd 0.0 ft

Minimum parapet ht 0.0 ft hb for Elevated bldg 0.0 ft

Live Loads:

Roof 0 to 200 sf: 20 psf

200 to 600 sf: 24 - 0.02Area, but not less than 12 psf over 600 sf: 12 psf

Roofs used for roof gardens 100 psf

Floor:

Typical Floor 60 psf

Partitions N/A

Private rooms & corridors serving them 40 psf

Lobbies & first floor corridors 100 psf

Stairs and exit ways 100 psf

Florida Building Code 2023

Assembly

Bliss & Nyitray, Inc. JOB TITLE Ocean Center Daytona Beach

Structural Engineers

Miami | West Palm Beach | Tallahasse | Tampa | Dallas JOB NO. 26M52 SHEET NO.

CALCULATED BY AM DATE

CHECKED BY DATE

Wind Loads - Rooftop Structures & Canopies Nominal Wind Pressures

Building (L) = 435.5 ft

Building (B) = 291.0 ft

Directionality (Kd) = 0.85

Rooftop Structures & Equipment #1

Equipment length parallel to L = 7.2 ft

Equipment length parallel to B = 3.3 ft

Height of equipment = 4.0 ft Base pressure (Kd qh) = 35.2 psf

Vertical wind pressure Wind normal to building B Wind normal to building L

Ar = 23.3 sf Af = 13.0 sf Af = 28.7 sf

GCr = 1.500 GCr = 1.90 GCr = 1.90

F = KdqhGCr Ar = 52.8 Ar (psf) F = KdqhGCr Af = 66.8 Af (psf) F = KdqhGCr Af = 66.8 Af (psf)

Fv = 1.2 kips Fh = 0.9 kips Fh = 1.9 kips

Rooftop Structures & Equipment #2

Equipment length parallel to L = 4.8 ft

Equipment length parallel to B = 4.8 ft

Height of equipment = 4.8 ft Base pressure (Kd qh) = 35.2 psf

Vertical wind pressure Wind normal to building B Wind normal to building L

Ar = 23.4 sf Af = 23.4 sf Af = 23.4 sf

GCr = 1.500 GCr = 1.90 GCr = 1.90

F = KdqhGCr Ar = 52.8 Ar (psf) F = KdqhGCr Af = 66.8 Af (psf) F = KdqhGCr Af = 66.8 Af (psf)

Fv = 1.2 kips Fh = 1.6 kips Fh = 1.6 kips

Attached Canopies on Buildings : Alternate design 60'<h<90'

Mean Roof Ht (h )= 76.8 ft

Mean eave height (he) = 32.0 ft Base pressure (Kd qh) = 35.2 psf

Mean Canopy height (hc) = 26.0 ft hc/he = 0.81

C&C Surface Pressure (psf) User input

Area 10 sf 50 sf 100 sf 1000 sf 75 sf

Separate Individual Surfaces:

Upper surface negative pressure -55.5 -48.5 -45.5 -31.4 -46.7

Lower surface negative pressure -32.1 -27.7 -25.8 -19.8 -26.6

Upper or Lower surface pos pressure 28.1 23.1 21.0 21.0 21.9

Combined Upper & Lower Surfaces (net):

Negative pressure -39.7 -29.3 -24.8 -24.8 -26.7

Positive pressure 31.6 25.4 22.8 22.8 23.9

Cover sheet Vol I
26M52 Windborne Debris Zones & Contours
20260406 G-07 Wind Seismic Snow Rain Pressures (Adam) 1
20260406 G-07 Wind Seismic Snow Rain Pressures (Adam) 2
20260406 G-07 Wind Seismic Snow Rain Pressures (Adam) 3
2026-04-22T17:55:21-0400
Alejandra M McCombie
This item has been electronically signed and sealed by Alejandra Martinez McCombie, P.E., on the date indicated using Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.