Exhibit_D_-_Volusia_Co._EOC_AV_IT_Renovations_100%_CD_Specs.pdf

PDF 1 MB Posted

Attached to
Emergency Operations Center (EOC) Audio/Visual (A/V) Information Technology (IT) Renovations
Solicitation number
26-P-33JRD
Issued by
Volusia County, Florida

About this file

This is a construction specification document for the Volusia County Emergency Operations Center (EOC) Audio/Visual and Information Technology (IT) Renovations project located at 3825 Tiger Bay Road, Daytona Beach, Florida. The project encompasses comprehensive A/V and IT system upgrades including electrical infrastructure, structured cabling, data communications, audio-video communications, and distributed communications systems. The specifications detail Division 26 (Electrical) and Division 27 (Communications) work requirements across multiple subsections covering basic electrical requirements, conductors and cable installation, grounding and bonding, hangers and supports, raceways and boxes, electrical identification, wiring devices, enclosed switches and circuit breakers, and integrated audio-video systems. The document establishes 100% construction document specifications prepared by CMTA, Inc. (Project No. 2025-0093.00) dated October 22, 2025, with work required to comply with the National Electrical Code (NEC), National Fire Protection Association (NFPA) standards, ANSI standards, TIA/EIA standards, and local codes and ordinances.

The specifications require contractors to be factory-authorized resellers and certified installers with minimum five years of documented experience completing similar projects and providing valid references. Contractor qualifications mandate on-site Registered Communications Distribution Designers (RCDD) for cabling work, Cisco Certified Network Administrators (CCNA) for network electronics, and Certified Technology Specialists (CTS) for audio-video systems. All materials must be new, UL-listed, and free of defects, with manufacturers maintaining satisfactory use records of at least five years. The specifications mandate a minimum 15-year manufacturer warranty on installed systems, with all labor and materials provided at no cost during normal working hours. Contractors must obtain all required permits and inspections, coordinate with local utility services, provide comprehensive as-built documentation in AutoCAD format, deliver Operations and Maintenance manuals, and provide on-site training for County personnel. The project requires strict adherence to fire-stopping requirements, grounding and bonding standards per ANSI/TIA 607, cable testing to 350 MHz minimum for Category 6 compliance, and comprehensive field quality control testing including infrared scanning of electrical connections within 60 days of substantial completion.

View the file

Other files

File Type Posted
Emergency_Operations_Center_(EOC)_Audio_Visual_(A_V)_Information_Technology_(IT)_Renovations_(Addendum_#7_Revision).pdf PDF
Exhibit_E_-_Volusia_Co._EOC_AV_IT_Renovations_100%_CD_Drawings_-_Revision_1.pdf PDF
Exhibit_D_-_Volusia_Co._EOC_AV_IT_Renovations_100%_CD_Specs_-_Revision_1.pdf PDF
Exhibit_H_-_Supplemental_Building_Plans.pdf PDF
Exhibit_G_-_AV_As-Built_Drawings_-_redacted.pdf PDF
Exhibit_B_-_25-P-33JRD_Price_Sheet_-_Revision_1.xlsx XLSX spreadsheet
Emergency_Operations_Center_(EOC)_Audio_Visual_(A_V)_Information_Technology_(IT)_Renovations.pdf PDF
Emergency_Operations_Center_(EOC)_Audio_Visual_(A_V)_Information_Technology_(IT)_Renovations.pdf PDF
Exhibit_B_-_25-P-33JRD_Price_Sheet.xlsx XLSX spreadsheet
Exhibit_B_-_25-P-33JRD_Price_Sheet.xlsx XLSX spreadsheet
Exhibit_D_-_Volusia_Co._EOC_AV_IT_Renovations_100%_CD_Specs.pdf PDF
Exhibit_E_-_Volusia_Co._EOC_AV_IT_Renovations_100%_CD_Drawings.pdf PDF
Exhibit_E_-_Volusia_Co._EOC_AV_IT_Renovations_100%_CD_Drawings.pdf PDF
Exhibit_F_-_Sample_Agreement___EOC_AV_Technology_Renovation.pdf PDF
Exhibit_F_-_Sample_Agreement___EOC_AV_Technology_Renovation.pdf PDF
Exhibit_F_-_Sample_Agreement___EOC_AV_Technology_Renovation.pdf PDF
Exhibit_C_-_County_Computing_Security_Procedures_03-08-23.pdf PDF
Exhibit_C_-_County_Computing_Security_Procedures_03-08-23.pdf PDF
Exhibit_C_-_County_Computing_Security_Procedures_03-08-23.pdf PDF
Exhibit_A_-_26-P-33JRD_-_Required_Types_and_Limits_of_Insurance.pdf PDF
Exhibit_A_-_26-P-33JRD_-_Required_Types_and_Limits_of_Insurance.pdf PDF
Exhibit_A_-_26-P-33JRD_-_Required_Types_and_Limits_of_Insurance.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Manual Volusia County

Emergency Operations Center

A/V IT Renovations

3825 Tiger Bay Road, #102

Daytona Beach, FL 32124

100% Construction Documents

10/22/2025

Prime Engineer

CMTA, Inc.

181 Melody Lane, Suite 107

Ft. Pierce, FL 34950

772.466.1165

THIS PAGE INTENTIONALLY LEFT BLANK

VOLUSIA COUNTY EMERGENCY OPERATIONS CENTER CMTA PROJECT NO. 2025-0093.00

A/V IT RENOVATIONS

TABLE OF CONTENTS 00 00 00 - 1

TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

260100 Basic Electrical Requirements 260500 Basic Electrical Materials and Methods 260519 Conductors and Cable 260526 Grounding and Bonding 260529 Hangers and Supports for Electrical Systems 260533 Raceway and Boxes 260553 Electrical Identification 262726 Wiring Devices 262816 Enclosed Switches and Circuit Breakers

DIVISION 27 - COMMUNICATIONS

274100 Audio Video Systems Technology Systems Design and Installation Guidelines

TABLE OF CONTENTS 00 00 00 - 2

BASIC ELECTRICAL REQUIREMENTS 260100 - 1

SECTION 260100 - BASIC ELECTRICAL REQUIREMENTS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division-01 Specification Sections, apply to work of this Section.

1.2 SUMMARY

A. This Section specifies the basic requirements for electrical installations and includes requirements common to all sections of Division-26. It expands and supplements the requirements specified in sections of Division-01.

1.3 CODES AND STANDARDS

A. Install all work in accordance with the applicable requirements of the latest edition of the following:

1. National Electric Code (NEC)

2. Local, State, County and City Codes

3. National Fire Protection Association (NFPA)

4. American National Standards Institute (ANSI)

5. NEMA Standards

B. It is the intent of the Contract Documents to comply with the applicable codes, ordinances, regulations, and standards. Where discrepancies occur, notify the Architect in writing, and ask for interpretation. Correct any installation that fails to comply with the applicable codes and standards at no additional cost to the Owner.

C. All materials shall be new and free of defects, and shall be U.L. listed, bear the U.L. label or be labeled or listed with an approved, nationally recognized Electrical Testing Agency.

Where no labeling or listing service is available for certain types of equipment, test data shall be submitted to prove to the Engineer that equipment meets or exceeds available standards.

1.4 PERMITS AND INSPECTIONS

A. Obtain and make all payments for permits and inspections required. At the completion of the project and before final acceptance of the electrical work, provide evidence of final inspection and approval by the authorities having jurisdiction.

1.5 QUALITY ASSURANCE

A. Manufacturers: Firms regularly engaged in manufacture of electrical products specified, whose products have been in satisfactory use in similar service for not less than 5 years.

BASIC ELECTRICAL REQUIREMENTS 260100 - 2

B. Installer's Qualifications: Firm with at least 5 years of successful installation experience on projects with electrical work similar to that required for this project.

1.6 IDENTIFICATION

A. The following items shall be equipped with nameplates: All new switchboards, panelboards, circuit breakers, and transformers.

B. Nameplates shall adequately describe the function of the particular equipment involved.

Nameplates for panelboards and switchboards shall include the panel designation, branch (normal), voltage and phase of the supply. For example, "Panel A, Normal Branch, 480Y/277V, 3-phase, 4-wire."

C. Nameplates shall be laminated phenolic plastic, black front and back with white core, with

3/8" high lettering etched through the outer covering. White engraved letters on black background. Attach with plated self-tapping screws or brass bolts.

D. Provide nameplates on all existing equipment that a circuit under this contract is fed from.

E. All junction box covers shall be hand marked with a 1/8" wide permanent black marking pen, indicating panel and circuit numbers contained, or system contained, i.e., fire alarm, telephone, etc.

1.7 ROUGH-IN

A. Verify final locations for rough-ins with field measurements and with the requirements of the actual equipment to be connected, and architectural room elevations.

1.8 ELECTRICAL INSTALLATIONS

A. Coordinate electrical equipment and materials installation with other building components.

B. Verify all dimensions by field measurements.

C. Arrange for chases, slots, and openings in other building components to allow for electrical installations.

D. Coordinate the installation of required supporting devices and sleeves to be set in poured in place concrete and other structural components, as they are constructed.

E. Sequence, coordinate, and integrate installations of electrical materials and equipment for efficient flow of the Work. Give particular attention to large equipment requiring positioning prior to closing-in the building.

F. Coordinate the cutting and patching of building components to accommodate the installation of electrical equipment and materials.

G. Coordinate connection of electrical systems with local utility services. Comply with requirements of governing regulations, franchised service companies, and controlling agencies. Provide required connections for each service.

BASIC ELECTRICAL REQUIREMENTS 260100 - 3

1.9 CUTTING AND PATCHING

A. This Article specifies the cutting and patching of electrical equipment, components, and materials to include removal and legal disposal of selected materials, components, and equipment.

B. Do not endanger or damage installed Work through procedures and processes of cutting and patching.

C. Arrange for repairs required to restore other work, because of damage caused as a result of electrical installations.

D. No additional compensation will be authorized for cutting and patching Work that is necessitated by ill-timed, defective, or non-conforming installations.

E. Perform cutting, fitting, and patching of electrical equipment and materials required to:

1. Uncover Work to provide for installation of ill-timed work;

2. Remove and replace defective Work;

3. Remove and replace Work not conforming to requirements of the Contract Documents;

4. Remove samples of installed Work as specified for testing;

5. Upon written instructions from the Architect/Engineer, uncover and restore Work to provide for Architect/Engineer observation of concealed Work.

6. Install electrical work in existing facilities.

1.10 ELECTRICAL SUBMITTALS

A. Refer to the Conditions of the Contract (General and Supplementary) and Division-01

Section: SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES for submittal definitions, requirements, and procedures.

B. Submittal of shop drawings, product data, and samples will be accepted only when submitted by the Contractor. Data submitted from subcontractors and material suppliers directly to the Architect/Engineer will not be processed.

1.11 PRODUCT OPTIONS AND SUBSTITUTIONS

A. Refer to the Instructions to Bidders and the Division-01 for requirements in selecting products and requesting substitutions. Where a listing of acceptable manufacturers has been given, use one of those manufacturers given only.

1.12 PRODUCT LISTING

A. Prepare listing of major electrical equipment and materials for the project.

B. Provide all information requested.

C. Submit this listing as a part of the submittal requirement specified in Division-01.

BASIC ELECTRICAL REQUIREMENTS 260100 - 4

D. When two or more items of the same material or equipment are required they shall be of the same manufacturer, i.e., panelboards, motor starters, transformers, etc. Product manufacturer uniformity does not apply to raw materials, bulk materials, wire, conduit, fittings, sheet metal, steel bar stock, welding rods, solder, fasteners, motors for dissimilar equipment units, and similar items used in Work, except as otherwise indicated.

E. Provide products which are compatible within systems and other connected items.

1.13 DELIVERY, STORAGE, AND HANDLING

A. Deliver products to project properly identified with names, model numbers, types, grades, compliance labels, and similar information needed for distinct identifications; adequately packaged and protected to prevent damage during shipment, storage, and handling.

B. Store equipment and materials at the site, unless off-site storage is authorized in writing.

Protect stored equipment and materials from damage.

C. Coordinate deliveries of electrical materials and equipment to minimize construction site congestion. Limit each shipment of materials and equipment to the items and quantities needed for the smooth and efficient flow of installations.

1.14 RECORD DOCUMENTS

A. Refer to the Division-01 Section: PROJECT CLOSEOUT or PROJECT RECORD

DOCUMENTS for requirements. The following paragraphs supplement the requirements of Division-01.

B. Mark Drawings to indicate revisions to conduit size and location both exterior and interior;

actual equipment locations, distribution and branch electrical circuitry; fuse and circuit breaker size and arrangements; support and hanger details.

C. Mark Specifications to indicate approved substitutions; Change Orders; actual equipment and materials used.

1.15 OPERATION AND MAINTENANCE DATA

A. Refer to the Division-01 Section; PROJECT CLOSEOUT or OPERATION AND

MAINTENANCE DATA for procedures and requirements for preparation and submittal of maintenance manuals.

1.16 WARRANTIES

A. Refer to individual equipment specifications for warranty requirements.

B. Compile and assemble the warranties specified in Division-26, into a separate set of vinyl covered, three ring binders, tabulated and indexed for easy reference.

C. Provide complete warranty information for each item to include product or equipment, date of beginning of warranty or bond; duration of warranty or bond; and names, addresses, and telephone numbers and procedures for filing a claim and obtaining warranty services.

BASIC ELECTRICAL REQUIREMENTS 260100 - 5

1.17 CLEANING

A. Refer to the Division-01 Section; PROJECT CLOSEOUT or FINAL CLEANING for general requirements for final cleaning.

B. Clean all light fixtures, lamps and lenses prior to final acceptance. Replace all inoperative lamps.

1.18 TEMPORARY POWER

A. Provide and pay for all temporary electrical service if required for construction.

B. Provide all temporary lighting and power distribution as required for construction. All temporary electrical work shall be in accordance with the N.E.C.

1.19 ELECTRONIC FILES

A. CADD files will be available on a limited basis to qualified firms at the Architects prerogative.

Recipients are cautioned that these files may not accurately show actual conditions as constructed. Users are responsible to verify actual field conditions. These files are not intended to be used as shop drawings.

END OF SECTION 260100

BASIC ELECTRICAL REQUIREMENTS 260100 - 6

BASIC ELECTRICAL MATERIALS AND METHODS 260500 - 1

SECTION 260500 - BASIC ELECTRICAL MATERIALS AND METHODS

1.1 SUMMARY

A. This Section includes the following:

1. Electrical equipment coordination and installation.

2. Sleeves for raceways and cables.

3. Common electrical installation requirements.

1.2 SUBMITTALS

A. Product Data: For each type of product indicated.

1.3 QUALITY ASSURANCE

A. Test Equipment Suitability and Calibration: Comply with NETA ATS, "Suitability of Test

Equipment" and "Test Instrument Calibration."

1.4 COORDINATION

A. Coordinate arrangement, mounting, and support of electrical equipment:

1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.

2. To provide for ease of disconnecting the equipment with minimum interference to other installations.

3. To allow right of way for piping and conduit installed at required slope.

4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.

B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

C. Coordinate electrical testing of electrical, mechanical, and architectural items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.

PART 2 - PRODUCTS

2.1 SLEEVES FOR RACEWAYS AND CABLES

A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

BASIC ELECTRICAL MATERIALS AND METHODS 260500 - 2

B. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Through-Penetration Firestop Systems."

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right of Way: Give to raceways and piping systems installed at a required slope.

3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.

B. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Through-Penetration Firestop Systems."

C. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.

D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.

E. Extend sleeves installed in floors 2 inches above finished floor level.

F. Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and raceway or cable unless sleeve seal is to be installed.

G. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Refer to Division 07 Section "Joint Sealants" for materials and installation.

H. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with firestop materials. Comply with Division 07 Section "Through- Penetration Firestop Systems."

BASIC ELECTRICAL MATERIALS AND METHODS 260500 - 3

I. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.

J. Aboveground, Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.

K. Underground, Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size sleeves to allow for 1-inch annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals.

3.3 FIRESTOPPING

A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly. Firestopping materials and installation requirements are specified in Division 07 Section "Through-Penetration Firestop Systems."

END OF SECTION 260500

BASIC ELECTRICAL MATERIALS AND METHODS 260500 - 4

CONDUCTORS AND CABLE 260519 - 1

SECTION 260519 - CONDUCTORS AND CABLE

A. Provide all equipment, labor, material, accessories, and mounting hardware to properly install all conductors and cables rated 600 volts and less for a complete and operating system for the following:

1. Conductors and cable.

2. Wiring connectors and connections.

B. All sizes shall be given in American Wire Gauge (AWG) or in thousand circular mils (MCM).

A. Product Data: Submit catalog cut sheet showing, type and U.L. listing of each type of conductor, connector and termination.

A. Conform to requirements of ANSI/NFPA 70.

B. Furnish products listed and classified by Underwriters Laboratories, Inc. as suitable for purpose specified and shown.

1.4 PROJECT CONDITIONS

A. Verify that field measurements are as shown on Drawings.

B. Conductor sizes are based on copper unless noted otherwise.

C. Wire and cable routing shown on Drawings is approximate unless dimensioned. Route wire and cable as required to meet Project Conditions.

D. Where wire and cable routing is not shown, and destination only is indicated, determine exact routing and lengths required.

1.5 COORDINATION

A. Determine required separation between cable and other work.

B. Determine cable routing to avoid interference with other work.

CONDUCTORS AND CABLE 260519 - 2

2.1 BUILDING WIRE AND CABLE

A. Aluminum and Copper Conductors: Comply with NEMA WC 70.

B. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN and XHHW.

C. Insulation Voltage Rating: 600 volts.

PART 3 - EXECUTION

3.1 GENERAL

A. Install products in accordance with manufacturer’s instructions.

B. Conductors #10 AWG or #12 AWG shall be 600 volt type THWN/THHN unless noted otherwise, rated 90 degrees C. dry.

C. Use solid conductor for feeders and branch circuits 10 AWG and smaller (except for control circuits).

D. Use conductor not smaller than 12 AWG for power and lighting circuits.

E. Neatly train and lace wiring inside boxes, equipment, and panelboards.

F. All homerun conductors shall be installed in raceway.

G. MC Cable is approved for use in concealed walls and ceilings only. All circuit Homeruns shall be in conduit to the area in which the circuit serves.

H. Conductor sizes indicated on circuit homeruns or in schedules shall be installed over the entire length of the circuit unless noted otherwise on the drawings or in these specifications.

I. Before installing raceways and pulling wire to any mechanical equipment, verify electrical characteristics with final submittal on equipment to assure proper number and AWG of conductors. (As for multiple speed motors, different motor starter arrangements, etc.).

J. Coordinate all wire sizes with lug sizes on equipment, devices, etc. Provide/install lugs as required to match wire size.

K. Where oversized conductors are called for (due to voltage drop, etc.) provide/install lugs as required to match conductors, or provide/install splice box, and splice to reduce conductor size to match lug size.

3.2 EXAMINATION

A. Verify that interior of building has been protected from weather.

CONDUCTORS AND CABLE 260519 - 3

B. Verify that mechanical work likely to damage wire has been completed.

3.3 PREPARATION

A. Completely and thoroughly swab raceway before installing wire.

3.4 WIRING METHODS

A. Use only building wire, Type THHN/THWN insulation, in raceway unless noted otherwise.

B. Wiring in vicinity of heat producing equipment: Use only XHHW insulation, in raceway.

3.5 INTERFACE WITH OTHER PRODUCTS

A. Identify wire and cable under provisions of Section 26 05 53.

B. Identify each conductor with its circuit number or other designation indicated on Drawings.

C. Identify neutrals with its associated circuit number(s).

3.6 FIELD QUALITY CONTROL

A. Perform field inspection and testing under provisions of the General Requirements of the

Contract Documents.

B. Inspect wire for physical damage and proper connection.

C. Measure tightness of bolted connections and compare torque measurements with manufacturer's recommended values.

D. Verify continuity of each branch circuit conductor.

3.7 PULLING

A. No wire shall be pulled until the conduit system is complete from pull point to pull point and major equipment terminating conduits have been fixed in position.

B. Mechanical pulling devices shall not be used on conductors sized #8 and smaller. Pulling means which might damage the raceway shall not be used.

C. Use only powdered soapstone or other pulling lubricant acceptable to the A/E. Compound or lubricant shall not cause the conductor or insulation to deteriorate.

D. All conductors to be installed in a common raceway shall be pulled together. The manufacturer's recommended pulling tensions shall not be exceeded.

E. Bending radius of insulated wire or cable shall not be less than the minimum recommended by the manufacturer.

CONDUCTORS AND CABLE 260519 - 4

F. Where communications type conductors are installed, special requirements shall apply as outlined under that specific system detail specifications.

3.8 CONTROL AND SIGNAL CIRCUITS

A. For control and signal circuits above 50 VAC, conductors shall be #14 AWG minimum size, Type XHHW or THWN-THHN as permitted by NFPA 70, within voltage drop limits, increased to

#12 AWG as necessary for proper operation.

B. For control and signal circuits 50 VAC and below, conductors, at the Contractor's option, may be #16 AWG, 300 volt rated, PVC insulated, except where specifically noted otherwise in the contract documents.

C. Conductor insulation for Fire Alarm Systems shall be as accepted by Code Inspection Authority only. Wire acceptance by the A/E shall not supersede this final Acceptance for conditions of this specific project.

D. Install circuit conductors in conduit.

E. Circuit conductors to be stranded.

3.9 COLOR CODING

A. All power feeders and branch circuits No. 6 and smaller shall be wired with color-coded wire with the same color used for a system throughout the building. Power feeders above No. 6 shall either be fully color-coded or shall have black insulation and be similarly color-coded with tape or paint in all junction boxes and panels. Tape or paint shall completely cover the full length of conductor insulation within the box or panel.

B. Unless otherwise accepted or required by A/E to match existing, color-code shall be as follows:

Neutrals to be white for 120/208V system, natural grey for 277/480V system; ground wire green, bare. 120/208V, Phase A - black; Phase B - red; Phase C - blue. 480/277V, Phase A brown; Phase B - orange; Phase C - yellow. All switch legs, other voltage system wiring, control and interlock wiring shall be color-coded other than those above.

3.10 TAPS/SPLICES/CONNECTORS/TERMINATIONS

A. Clean conductor surfaces before installing lugs and connectors.

B. Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible temperature rise.

C. Power and lighting conductors shall be continuous and unspliced where located within conduit.

Splices shall occur within troughs, wireways, outlet boxes, or equipment enclosures where sufficient additional room is provided for all splices. No splices shall be made in in-ground pull boxes (without written acceptance of engineer).

D. Splices in lighting and power outlet boxes, wireway, and troughs shall be kept to a minimum, pull conductors through to equipment, terminal cabinets, and devices.

CONDUCTORS AND CABLE 260519 - 5

E. No splices shall be made in junction box, and outlet boxes (wire No. 8 and larger) without written acceptance of Engineer.

F. No splices shall be made in communications outlet boxes, pull boxes or wireways (i.e., fire alarm, computer, telephone, intercom, sound system, etc.) without written acceptance of

Engineer. Pull cables through to equipment cabinets, terminal cabinets and devices.

G. Allow adequate conductor lengths in all junction boxes, pull boxes and terminal cabinets. All termination of conductors in which conductor is in tension will be rejected and shall be replaced with conductors of adequate length. This requirement shall include the providing by the

Contractor of sleeve type vertical cable supports in vertical raceway installations provided in pullboxes at proper vertical spacings.

H. A calibrated torque wrench shall be used for all bolt tightening.

I. Interior Locations:

1. All (non-electronic systems) copper taps and splices in No. 8 or smaller shall be fastened together by means of "spring type" connectors. All taps and splices in wire larger than No.

8 shall be made with compression type connectors and taped to provide insulation equal to wire.

J. Exterior Locations:

1. Make splices, taps and terminations above grade in splice or termination cabinets. Do not splice any cable in ground or below finished grade.

2. All taps and splices shall be made with compression type connectors and covered with

Raychem heavywall cable sleeves (type CRSM-CT, WCSM or MCK) with type "S" sealant coating with sleeve kits as per manufacturer's installation instructions or be terminated/connected to terminal strips in above grade terminal boxes suitable for use.

3. Provide and install above grade termination cabinets sized to meet applicable codes and standards, where required for splicing.

END OF SECTION 260519

CONDUCTORS AND CABLE 260519 - 6

GROUNDING AND BONDING 260526 - 1

SECTION 260526 - GROUNDING AND BONDING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes methods and materials for grounding systems and equipment, plus the following special applications:

1. Common ground bonding with lightning protection system.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Other Informational Submittals: Plans showing dimensioned as-built locations of grounding features specified in Part 3 "Field Quality Control" Article, including the following:

1. Test wells.

2. Ground rods.

3. Ground rings.

4. Grounding arrangements and connections for separately derived systems.

5. Grounding for sensitive electronic equipment.

C. Field quality-control test reports.

D. Operation and Maintenance Data: For grounding to include the following in emergency, operation, and maintenance manuals:

1. Instructions for periodic testing and inspection of grounding features at test wells, ground rings, and grounding connections for separately derived systems based on NFPA 70B.

a. Tests shall be to determine if ground resistance or impedance values remain within specified maximums, and instructions shall recommend corrective action if they do not.

b. Include recommended testing intervals.

1.4 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with UL 467 for grounding and bonding materials and equipment.

GROUNDING AND BONDING 260526 - 2

2.1 CONDUCTORS

A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.

B. Bare Copper Conductors:

1. Stranded Conductors: ASTM B 8.

2. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.

2.2 CONNECTORS

A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having jurisdiction for applications in which used, and for specific types, sizes, and combinations of conductors and other items connected.

B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type, with at least two bolts.

1. Pipe Connectors: Clamp type, sized for pipe.

C. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.

2.3 GROUNDING ELECTRODES

A. Ground Rods: Copper-clad steel; 3/4 inch by10 feet in diameter. Increase lengths as required to meet and achieve specified resistance.

PART 3 - EXECUTION

3.1 APPLICATIONS

A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger, unless otherwise indicated.

B. Underground Grounding Conductors: Install bare copper conductor, No. 2/0 AWG minimum.

1. Bury at least 24 inches below grade.

C. Isolated Grounding Conductors: Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.

D. Grounding Bar: Install in electrical and communication equipment rooms, in rooms housing service equipment, and elsewhere as indicated.

GROUNDING AND BONDING 260526 - 3

1. Install bus on insulated spacers 1 inch, minimum, from wall 6 inches above finished floor, unless otherwise indicated.

E. Conductor Terminations and Connections:

1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.

2. Underground Connections: Welded connectors, except at test wells and as otherwise indicated.

3. Connections to Ground Rods at Test Wells: Bolted connectors.

4. Connections to Structural Steel: Welded connectors.

3.2 GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS

A. Comply with IEEE C2 grounding requirements.

B. Grounding Manholes and Handholes: Install a driven ground rod through manhole or handhole floor, close to wall, and set rod depth so 4 inches will extend above finished floor. If necessary, install ground rod before manhole is placed and provide No. 1/0 AWG bare, tinned-copper conductor from ground rod into manhole through a waterproof sleeve in manhole wall. Protect ground rods passing through concrete floor with a double wrapping of pressure-sensitive insulating tape or heat-shrunk insulating sleeve from 2 inches above to 6 inches below concrete. Seal floor opening with waterproof, nonshrink grout.

C. Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts, cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to ground rod or grounding conductor. Make connections with No. 4 AWG minimum, stranded, hard-drawn copper bonding conductor. Train conductors level or plumb around corners and fasten to manhole walls. Connect to cable armor and cable shields as recommended by manufacturer of splicing and termination kits.

D. Pad-Mounted Transformers and Switches: Install two ground rods and ground ring around the pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground cable and grounding electrodes. Install tinned-copper conductor not less than No. 2 AWG for ground ring and for taps to equipment grounding terminals. Bury ground ring not less than 6 inches from the foundation.

3.3 EQUIPMENT GROUNDING

A. Install insulated equipment grounding conductors with all feeders and branch circuits.

B. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:

1. Feeders and branch circuits.

2. Flexible raceway runs.

3.4 INSTALLATION

A. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

GROUNDING AND BONDING 260526 - 4

B. Common Ground Bonding with Lightning Protection System where available: Comply with NFPA 780 and UL 96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit.

C. Ground Rods: Drive rods until tops are 2 inches below finished floor or final grade, unless otherwise indicated.

1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating, if any.

2. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor.

D. Test Wells: Ground rod driven through drilled hole in bottom of handhole. Handholes are specified in Division 02 Section "Underground Ducts and Utility Structures," and shall be at least 12 inches deep, with cover.

1. Test Wells: Install at least one test well for each service, unless otherwise indicated.

Install at the ground rod electrically closest to service entrance. Set top of test well flush with finished grade or floor.

E. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance, except where routed through short lengths of conduit.

1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.

2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install so vibration is not transmitted to rigidly mounted equipment.

3. Use exothermic-welded connectors for outdoor locations, but if a disconnect-type connection is required, use a bolted clamp.

F. Grounding and Bonding for Piping:

1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes, using a bolted clamp connector or by bolting a lug-type connector to a pipe flange, using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.

2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.

3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.

G. Grounding for Steel Building Structure: Install a driven ground rod at base of each corner column and at intermediate exterior columns at distances not more than 60 feet apart.

H. Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70, using a minimum of 20 feet of bare copper conductor not smaller than No. 4 AWG.

GROUNDING AND BONDING 260526 - 5

1. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Extend grounding conductor below grade and connect to building grounding grid or to grounding electrode external to concrete.

3.5 FIELD QUALITY CONTROL

A. Perform the following tests and inspections and prepare test reports:

1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.

2. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, and at individual ground rods. Make tests at ground rods before any conductors are connected.

a. Measure ground resistance not less than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.

b. Perform tests by fall-of-potential method according to IEEE 81.

3. Prepare dimensioned drawings locating each test well, ground rod and ground rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.

B. Report measured ground resistances that exceed the following values:

1. Power and Lighting Equipment or System with Capacity 500 kVA and Less: 10 ohms.

2. Power Distribution Units or Panelboards Serving Electronic Equipment: 5 ohm(s).

3. Substations and Pad-Mounted Equipment: 5 ohms.

4. Manhole Grounds: 10 ohms.

C. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground resistance.

END OF SECTION 260526

GROUNDING AND BONDING 260526 - 6

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 1

SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

A. Section includes:

1. Hangers and supports for electrical equipment and systems.

2. Construction requirements for concrete bases.

1.2 PERFORMANCE REQUIREMENTS

A. Delegated Design: Design supports for multiple raceways, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.

B. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.

C. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

D. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.

1.3 SUBMITTALS

A. Product Data: For steel slotted support systems.

B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:

1. Steel slotted channel systems. Include Product Data for components.

2. Equipment supports.

1.4 QUALITY ASSURANCE

A. Comply with NFPA 70.

2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly.

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 2

1. Manufacturers:

a. Allied Tube & Conduit.

b. Cooper B-Line, Inc.; a division of Cooper Industries.

c. Thomas & Betts Corporation.

d. Unistrut; Tyco International, Ltd.

2. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA-4.

3. Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA-4.

4. Painted Coatings: Manufacturer's standard painted coating applied according to MFMA-

4.

5. Channel Dimensions: Selected for applicable load criteria.

B. Raceway and Cable Supports: As described in NECA 1 and NECA 101.

C. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

D. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be malleable iron.

E. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

F. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:

1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.

a. Manufacturers:

1) Hilti Inc.

2) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.

3) MKT Fastening, LLC.

4) Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.

2. Mechanical-Expansion Anchors: Insert-wedge-type, stainless steel, for use in hardened portland cement concrete with tension, shear, and pullout capacities appropriate for supported loads and building materials in which used.

a. Manufacturers:

1) Cooper B-Line, Inc.; a division of Cooper Industries.

2) Empire Tool and Manufacturing Co., Inc.

3) Hilti Inc.

4) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.

5) MKT Fastening, LLC.

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 3

3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS Type 18; complying with MFMA-4 or MSS SP-58.

4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for attached structural element.

5. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM A 325.

6. Toggle Bolts: All-steel springhead type.

7. Hanger Rods: Threaded steel.

2.2 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES

A. Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.

B. Materials: Comply with requirements in Division 05 Section "Metal Fabrications" for steel shapes and plates.

3.1 APPLICATION

A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical equipment and systems except if requirements in this Section are stricter.

B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for EMT, IMC, and RMC as scheduled in NECA 1, where its Table 1 lists maximum spacings less than stated in NFPA 70. Minimum rod size shall be 1/4 inch in diameter.

C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

1. Secure raceways and cables to these supports with clamps approved for application by an agency acceptable to authorities having jurisdiction.

D. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1- 1/2-inch and smaller raceways serving branch circuits and communication systems above suspended ceilings and for fastening raceways to trapeze supports.

3.2 SUPPORT INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this Article.

B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC, and

RMC may be supported by openings through structure members, as permitted in NFPA 70.

C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200 lb.

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 4

D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

1. To Wood: Fasten with lag screws or through bolts.

2. To New Concrete: Bolt to concrete inserts.

3. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor fasteners on solid masonry units.

4. To Existing Concrete: Expansion anchor fasteners.

5. Instead of expansion anchors, powder-actuated driven threaded studs provided with lock washers and nuts may be used in existing standard-weight concrete 4 inches thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4 inches thick.

6. To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers and nuts.

7. To Light Steel: Sheet metal screws.

8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate.

E. Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing bars.

3.3 INSTALLATION OF FABRICATED METAL SUPPORTS

A. Comply with installation requirements in Division 05 Section "Metal Fabrications" for site-fabricated metal supports.

B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment.

C. Field Welding: Comply with AWS D1.1/D1.1M.

3.4 CONCRETE BASES

A. Construct concrete bases of dimensions indicated but not less than 4 inches larger in both directions than supported unit, and so anchors will be a minimum of 10 bolt diameters from edge of the base.

B. Use 3000-psi, 28-day compressive-strength concrete. Concrete materials, reinforcement, and placement requirements are specified in Division 03 Section "Cast-in-Place Concrete."

C. Anchor equipment to concrete base.

1. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

2. Install anchor bolts to elevations required for proper attachment to supported equipment.

3. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 5

3.5 PAINTING

A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils.

B. Touchup: Comply with requirements in Division 09 painting Sections for cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.

C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A 780.

END OF SECTION 260529

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 6

RACEWAYS AND BOXES 260533 - 1

SECTION 260533 - RACEWAYS AND BOXES

A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.

A. Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

B. Shop Drawings: For custom enclosures and cabinets. Include plans, elevations, sections, details, and attachments to other work.

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA

70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with NFPA 70.

2.1 METAL CONDUIT AND TUBING

A. Rigid Steel Conduit: ANSI C80.1.

B. IMC: ANSI C80.6.

C. EMT: ANSI C80.3.

D. FMC: Zinc-coated steel.

E. LFMC: Flexible steel conduit with PVC jacket.

F. Fittings for Conduit (Including all Types and Flexible and Liquid tight), EMT, and Cable:

NEMA FB 1; listed for type and size raceway with which used, and for application and environment in which installed.

1. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 886.

2. Fittings for EMT: Set-screw or compression type, steel for all exposed applications or die-cast for concealed applications.

3. Fittings for MC: Set-screw or compression type, steel.

RACEWAYS AND BOXES 260533 - 2

2.2 NONMETALLIC CONDUIT AND TUBING

A. RNC: NEMA TC 2, Schedule 40 and 80 PVC.

B. Fittings for RNC: NEMA TC 3; match to conduit or tubing type and material.

2.3 METAL WIREWAYS

A. Manufacturers:

1. Cooper B-Line, Inc.

2. Hoffman.

3. Square D; Schneider Electric.

4. Or equal approved by Engineer.

B. Description: Sheet metal sized and shaped as indicated, NEMA 250, Type 1, unless otherwise indicated.

C. Fittings and Accessories: Include couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

D. Wireway Covers: Hinged type.

E. Finish: Manufacturer's standard enamel finish.

2.4 SURFACE RACEWAYS

A. Surface Metal Raceways: Galvanized steel with snap-on covers.

1. Manufacturers:

a. Thomas & Betts Corporation.

b. Walker Systems, Inc.; Wiremold Company (The).

c. Wiremold Company (The); Electrical Sales Division.

2.5 BOXES, ENCLOSURES, AND CABINETS

A. Sheet Metal Outlet and Device Boxes: NEMA OS 1.

B. Cast-Metal Outlet and Device Boxes: NEMA FB 1, Type FD, with gasketed cover.

C. Metal Floor Boxes: Cast metal, fully adjustable, rectangular.

D. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.

E. Cast-Metal Access, Pull, and Junction Boxes: NEMA FB 1, cast aluminum with gasketed cover.

F. Hinged-Cover Enclosures: NEMA 250, Type 1, with continuous-hinge cover with flush latch, unless otherwise indicated.

RACEWAYS AND BOXES 260533 - 3

1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.

G. Cabinets:

1. NEMA 250, Type 1, galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel.

2. Hinged door in front cover with flush latch and concealed hinge.

3. Key latch to match panelboards.

4. Metal barriers to separate wiring of different systems and voltage.

5. Accessory feet where required for freestanding equipment.

3.1 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below, unless otherwise indicated:

1. Exposed Conduit: Rigid steel conduit or IMC.

2. Concealed Conduit, Aboveground: Rigid steel conduit or IMC.

3. Underground Conduit: RNC, Type EPC-40-PVC, direct buried.

4. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.

5. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R.

B. Comply with the following indoor applications, unless otherwise indicated:

1. Exposed, Not Subject to Physical Damage: EMT.

2. Concealed in Ceilings and Interior Walls and Partitions: EMT.

3. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet locations.

4. Damp or Wet Locations: Rigid steel conduit.

5. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 4.

C. Minimum Raceway…