Exhibit_D-Norman_Report.pdf

PDF 320 KB Posted

Attached to
cooling tower & closed loop system water treatment
Solicitation number
EV00000722
Issued by
Cleveland County, Oklahoma

About this file

These are Global Water Technology (GWT) service reports documenting water treatment services for the Norman Veterans Center in Oklahoma from December 2024 to April 2025, focusing on a condenser closed loop system. The reports detail monthly testing and monitoring of the facility's water system, with key metrics including conductivity, pH levels, nitrite, and iron concentrations. Initially, GWT was instructed not to add chemical inhibitors to prevent potential pipe leaks, which meant the system was at risk of ongoing corrosion. However, in the April 2025 report, a closed loop inhibitor was introduced, and the service technician noted that the system now has "proper corrosion control".

The service reports were conducted by different GWT representatives - Kyle J. Rossi in December 2024 and January 2025, and Grayson Lavin in April 2025. The testing was performed at the Oklahoma Veterans Center located at 1776 E Robinson St. in Norman, Oklahoma. Throughout the reports, consistent recommendations are provided about minimizing system risks, with a specific reference to ASHRAE Standard 188-2015 regarding water management programs and proactive biological testing. The site visit contact was Andrew Harnack from the Oklahoma Department of Veterans Affairs (ODVA), and the reports consistently warn that failure to follow recommendations could increase risks of contamination, corrosion, scaling, or system failure.

View the file

Other files

File Type Posted
Exhibit_C-Lawton_Reports.pdf PDF
Exhibit_B-Clinton_Service_Reports.pdf PDF
AttachmentBStateGeneralTerms.pdf PDF
OMESformCP076.pdf PDF
Water_Testing-RFP.pdf PDF
Exhibit_E-Sulphur_Reports.pdf PDF
Exhibit_A-Ardmore_Service_Report.pdf PDF
Attachment_Price_Sheet.pdf PDF
OMESFormCP004.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Condenser Closed Loop

System

Conductivity (as mmhos) 621 pH 8.76 8 - 8.8

Nitrite (ppm as NO2) 0 500 min

Iron (ppm as Fe) 0.08

0.2 max

Opening Comment The purpose of my visit today was to perform initial testing on the closed loop system at this facility.

Condenser Closed Loop System Online I was told today that we are not able to add chemistry to prevent corrosion into this closed loop. GWT will not add any chemistry until we are told to do so. Corrosion of the system piping will continue without chemical protection.

Nitrite (ppm as NO2) There is no chemical inhibitor in the system. We were advised to not add inhibitor to prevent pipe leaks.

The facility is feeding powered sulfite to help scavange oxygen. There were less than 5.0 ppm in the closed loop today.

Closing Comment Thank you for your business!

Please contact me with any questions:

Kyle J. Rossi, CWT krossi@gwt-inc.com

(714) 329-1405

Service Report GWT Water Treatment Service Report December

2024Tuesday, December 17, 2024 4:27 PM CST

Oklahoma Veterans Centers Norman Veterans Center 1776 E Robinson St.

Norman Oklahoma 73071

(808) 469-8856

Report Number: 181787 Recorded By: Kyle J. Rossi, CWT

(714) 329-1405 krossi@gwt-inc.com

Norman Veterans Center - Cooling and Loop

The above recommendations are designed to minimize risk and maximize efficiency. Failure to adhere to recommendations may put your system and facility at an increased risk of contamination, corrosion, scaling or system failure. Notify your rep of any current or upcoming system changes. GWT advises facilities falling under the scope of ASHRAE Standard 188-2015 and subsequent revisions to assemble a compliant water management program including proactive biological testing (Legionella).

Global Water Technology, Inc. - 354 West Armory Drive, South Holland IL 60473 (708) 349-9991

Site Visit Contact:

Andrew Harnack Andrew.Harnack@odva.ok.gov

EXHIBIT D

System

Conductivity (as mmhos) 636 pH 8.59 8 - 8.8

Nitrite (ppm as NO2) 0 500 min

Iron (ppm as Fe) 0.05

0.2 max

Opening Comment The purpose of my visit today was to perform initial testing on the closed loop system at this facility.

Condenser Closed Loop System Online I was told today that we are not able to add chemistry to prevent corrosion into this closed loop. GWT will not add any chemistry until we are told to do so. Corrosion of the system piping will continue without chemical protection.

Nitrite (ppm as NO2)

There is no chemical inhibitor in the system. We were advised to not add inhibitor to prevent pipe leaks.

The facility is feeding powered sulfite to help scavange oxygen. There were less than 5.0 ppm in the closed loop today.

Closing Comment Thank you for your business!

Please contact me with any questions:

Kyle J. Rossi, CWT krossi@gwt-inc.com

(714) 329-1405

Service Report GWT Water Treatment Service Report January 2025

Wednesday, January 29, 2025 5:15 PM CST

Oklahoma Veterans Centers Norman Veterans Center 1776 E Robinson St.

Norman Oklahoma 73071

(808) 469-8856

Report Number: 191369 Recorded By: Kyle J. Rossi, CWT

(714) 329-1405 krossi@gwt-inc.com

Norman Veterans Center - Cooling and Loop

The above recommendations are designed to minimize risk and maximize efficiency. Failure to adhere to recommendations may put your system and facility at an increased risk of contamination, corrosion, scaling or system failure. Notify your rep of any current or upcoming system changes. GWT advises facilities falling under the scope of ASHRAE Standard 188-2015 and subsequent revisions to assemble a compliant water management program including proactive biological testing (Legionella).

Global Water Technology, Inc. - 354 West Armory Drive, South Holland IL 60473 (708) 349-9991

System

Conductivity (as mmhos) 962 pH 8.76 8 - 8.8

Nitrite (ppm as NO2) 650 500 min

Iron (ppm as Fe) 0.06

0.2 max

Condenser Closed Loop System Online Closed loop inhibitor was introduced to the system. I will continue to monitor these levels and make adjustments as needed.

The system now has proper corrosion control.

Closing Comment Thank you for reading through today's report. Please feel free to reach out to me with any questions or concerns you may have.

Best regards, Grayson Lavin - Senior Analyst, Water and Energy Services glavin@gwt-inc.com

(281) 731-0650

Service Report April Monthly Service

Friday, April 18, 2025 8:34 AM CDT

Oklahoma Veterans Centers Norman Veterans Center 1776 E Robinson St.

Norman Oklahoma 73071

(808) 469-8856

Report Number: 212964 Recorded By: Grayson Lavin

(708) 349-9991 glavin@gwt-inc.com

Norman Veterans Center - Cooling and Loop

The above recommendations are designed to minimize risk and maximize efficiency. Failure to adhere to recommendations may put your system and facility at an increased risk of contamination, corrosion, scaling or system failure. Notify your rep of any current or upcoming system changes. GWT advises facilities falling under the scope of ASHRAE Standard 188-2015 and subsequent revisions to assemble a compliant water management program including proactive biological testing (Legionella).