Exhibit_B_-_Report_Sample.pdf
PDF 2 MB Posted
- Attached to
- MDAD HVAC CHILLERS
- Solicitation number
- EVN0060585
- Issued by
- Miami-Dade County, Fruitville CDP, Florida
About this file
This is an exhibit document for the Miami-Dade Aviation Department (MDAD) HVAC Chillers full-service contract opportunity in Florida. The exhibit provides a sample report template that contractors must follow when submitting documentation and performance reports throughout the contract term. The sample report format establishes standardized requirements for how contractors will document their maintenance activities, system inspections, and compliance with Original Equipment Manufacturer (OEM) standards and applicable Federal, State, and Local Laws and Environmental Regulations. The template demonstrates the specific data fields, report structure, and documentation standards that the successful contractor must utilize to ensure consistent and comprehensive tracking of all HVAC system maintenance and auxiliary equipment servicing across the Miami-Dade Aviation Department's facilities.
The sample report exhibit serves as a critical compliance tool that enables MDAD to monitor contractor performance and verify adherence to contract specifications throughout the service period. By establishing this standardized reporting format in advance, the solicitation ensures that all bidders understand the administrative and documentation expectations, allowing for accurate cost estimation and operational planning. The report template reflects MDAD's commitment to maintaining detailed records of all HVAC system preservation activities and ensuring transparent accountability in the full-service contract execution.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Name: Service Report - Johnson Controls Incorporated - DCAD - Bldg 707 - 10/28/2024 - 01:53 AM Status: Approved Account No: Report ID: 42934Work Order:
City Make Up Condenser Water Chilled Water pH
Conductivity (as mmhos)
PTSA
Hardness, total (ppm as CaCO³)
Alkalinity, M (ppm as CaCO³)
Chlorides as Cl-
Nitrite (ppm as NaNO³)
Alkalinity, P (ppm as CaCO³)
Test
9 8.9 8 - 9.5
9.7 >=9
341 1707 1400 - 2200
350.8 >=800
6.8 113.1 >=60
80 400 <=550
70 360 <=500
50 300 <=300
>=400
>=100
Water Meter Report
Meter Name UOM Current Reading Daily Avg. Monthly Avg.
Blowdown Meter Gal 1,944,160.00 8,443 Gal 261,719 Gal
Makeup Meter Gal 66,389,405.00 0.03 Gal 0.93 Gal
Inventory & Pump Report Inventory Current Refilled Final Pump Speed Stroke
Biocide - KTND 5 gal 10 gal 15 gal 0.00 65.00
CWT 1644 4 gal 10 gal 14 gal 0.00 60.00
Today I checked the condenser water bypass loop for proper flow. I also checked the chemical feed pumps for prime and proper operation. The water chemistry was all within the recommended range of control. Everything was in good condition.
Your condenser water system is properly protected against corrosion and mineral scale deposition.
The CHW system is in need of additional treatment. I will come back and add CST-1308 to the loop to bring the levels more into the appropriate range.
Supplementary biocide was added to the tower in order to aid in the control of microbiological growth.
Report Notes
SERVICE REPORT
Created By: Gustavo Perez De Vita Phone: 786-714-4972 Email: gustavoaperezdv@gmail.com
Time Out: 02:18 (AM)
Created On: 10/28/2024 1:53 (AM)Service Address:
Johnson Controls Incorporated DCAD - Bldg 707 15901 SW 29th Street, Miramar, Florida 33027
Time In: 01:53 (AM)
SAMPLE
Report Images
Condenser Water Conductivity Logsheet
Makeup Meter Blowdown Meter
SERVICE REPORT
Created By: Gustavo Perez De Vita Phone: 786-714-4972 Email: gustavoaperezdv@gmail.com
Time Out: 02:18 (AM)
Created On: 10/28/2024 1:53 (AM)Service Address:
Johnson Controls Incorporated DCAD - Bldg 707 15901 SW 29th Street, Miramar, Florida 33027
Time In: 01:53 (AM)
SAMPLE