This document is a Statement of Work for on-site calibration and testing of approximately 315 portable and fixed gas detectors at the National Renewable Energy Laboratory (NREL) facilities. The Subcontractor shall perform zero and span calibrations per the manufacturer's instructions, use certified traceable test gas, and label all gas detectors with the inspection date. The Subcontractor shall provide reports within 10 business days detailing the inspection results, any deficiencies identified, and recommendations for corrective actions. The Subcontractor must respond to service requests within 24 hours, complete standard repairs/testing within 10 business days, and shall not exceed the stated contingency funding. The work must be performed in accordance with NREL's environmental, safety, health, and quality requirements. The services will be provided at NREL's South Table Mountain campus in Colorado.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPENDIX A

STATEMENT OF WORK

FOR

On-site Calibration and Testing for Fixed/Portable Gas Detectors

Revision 0

July 31st, 2024

1) Background:

The National Renewable Energy Laboratory (NREL) is a national laboratory owned by the U.S. Department of Energy (DOE). NREL is the only federal laboratory dedicated to research, development, commercialization, and deployment of renewable energy and energy efficiency technologies. NREL is managed and operated for DOE’s Office of Energy Efficiency and Renewable Energy by The Alliance for Sustainable Energy (Alliance), the “M&O Contractor”.

NREL takes pride in its world-class research, talented staff, sustainable campus, and results that positively impact our local, national and global communities. On the NREL sites there are state-of-the-art facilities available to industry entrepreneurs, engineers, scientists, and universities for researching and developing their energy technologies. The National Renewable Energy Laboratory (NREL) consists of three campuses in Colorado, with 65+ buildings that range in age from new construction to 40+ years old. NREL appoints internal Facility Managers to manage multiple buildings throughout all campuses.

The Subcontractor shall provide all personnel, labor, management, tools, equipment, and services necessary to ensure that NREL’s fixed and portable gas detectors are tested and calibrated. The Subcontractor shall ensure that all objectives outlined in this Appendix A – Statement of Work are met in a timely and professional manner.

Many services performed by Subcontractors on-site at NREL are applicable to Service Contract Labor Standards Wage Determinations. Subcontractor shall reference the executed Subcontract Schedule or Purchase Order to confirm SCLS applicability.

2) Description of Work:

a) Variable Services: As-Needed Testing and Calibration

1. Per the manufacturer’s recommendations, perform on-site calibration and testing of approximately 315 portable and fixed gas detectors.

i. Perform Zero calibration per the manufacturer's instructions

ii. Perform Span calibration per the manufacturer's instructions

2. Only use a certified traceable test gas and ensure the test gas is not expired.

Subcontractor shall provide a certificate of analysis for every test gas cylinder.

3. To the extent possible, Subcontractor shall calibrate sensors in environmental conditions that are the same as (or similar to) the actual workplace conditions.

4. Label all gas detectors with the date of inspection.

5. Provide reports within 10 business days of completion of testing/calibration. Reports shall include the following:

i. Record results of all inspections. Include the building, room number, detector type, pass/fail, inspection dates, comments.

ii. Inform NREL TM of all deficiencies identified.

iii. Provide NREL TM with recommendations for corrective actions.

6. Standard Request response time shall be within 24 hours to acknowledge the NREL TM request for service.

i. Initial assessment report and quote to be provided to NREL’s TM within 5 business days of initial request unless otherwise noted by the Technical Monitor.

ii. Repair or testing shall be completed within 10 business days of requested standard as-needed service.

7. The Subcontractor shall not exceed the stated contingency funding as outlined in the Subcontract or Purchase Order.

i. In the event that estimated repairs, parts, or a combination of both meet or exceed 85% of the contingency funding on the Subcontract – the Subcontractor shall notify both the NREL TM and NREL SA of such when providing the quote for those services and parts (within 48 hours of initial request).

ii. Additional funds cannot be awarded without the review and concurrence of the NREL SA listed in the Subcontract.

b) Personnel Requirements

1. Subcontractor Employees (All Staff):

i. All Subcontractor employees shall be trained in and provide current training records on the following:

a. OSHA

ii. The Subcontractor must assure that the employees/subcontractors have sufficient English language speaking skills and/or interpretive services available to successfully communicate with the NREL TM at each site.

2. Supervisor

i. The Subcontractor shall assign at least two (one primary and one backup)

Supervisor with all contact information to be provided to the NREL TM in writing prior to the execution of the Subcontract or within 48 hours of any personnel change via written notice to NREL TM.

ii. Regular employees do NOT qualify as backups for on-site supervisors.

c) Exhibits

1. Exhibit A – Fixed and Portable Gas Detectors

3) NREL Points of Contact:

a) NREL Technical Monitor (TM)

1. The Primary TM for this requirement is Elizabeth Latino, Elizabeth.Latino@nrel.gov,

(303) 598-9745

2. The Secondary TM for this requirement is Matthew Lynch, Matthew.Lynch@nrel.gov,

(303) 598-2772

3. The Primary Subject Matter Expert (SME) for this requirement is Joshua Korosec, Joshua.Korosec@nrel.gov, (303) 598-2795

4. The Secondary SME for this requirement is Michael Wodzianski, Michael.Wodzianski@nrel.gov, (303) 264-4591

5. The Subcontractor is responsible for coordinating all questions, problems, or operational technical matters of this subcontract with the NREL TM.

mailto:Elizabeth.Latino@nrel.gov mailto:Matthew.Lynch@nrel.gov mailto:Joshua.Korosec@nrel.gov mailto:Michael.Wodzianski@nrel.gov

6. In the event the NREL TM is not available at the time of the request, operational questions can be directed to the NREL Work Control Center (WCC) at (303) 384- 7344.

b) Standard Performance Scheduling

1. The point of contact for scheduling on this subcontract is NREL WCC at (303) 384-

7344.

c) NREL ESH&Q Point of Contact(s):

1. The Primary ESH&Q Point of Contact for this requirement is Steve Aldridge, Steven.Aldridge@nrel.gov, (720) 490-0064.

2. The Secondary ESH&Q Point of Contact for this requirement is John Boysen, John.Boysen@nrel.gov, (720) 641-1107.

d) NREL Subcontract Administrator (SA)

1. Contractual questions shall be directed to the SA listed in the Subcontract Schedule or Purchase Order.

4) Environmental, Safety, Health, and Quality (ESH&Q) & Security:

a) All Subcontractor employees are to wear a NREL identification badge on their outer garment, upper portion of their body at all times while on the premises.

1. Subcontractors will not be allowed on site without badges.

2. All issued badges must be returned immediately to the Site Entrance Building upon termination of the work at NREL.

b) The Subcontractor shall comply with all safety requirements at the following website:

https://www.nrel.gov/about/ehs-construction.html

i. At a minimum, the Service and Maintenance Subcontractor Environment, Safety &

Health Manual is applicable to this SOW.

ii. The Subcontractor shall submit an Environmental, Safety, and Health Risk

Evaluation Worksheet.

iii. The Subcontractor shall provide proper personal protection equipment.

iv. The Subcontractor shall attend a NREL Contractor Safety Orientation meeting with a

NREL Environmental Safety, Health, and Quality (ESH&Q) representative.

5) Working Hours:

NREL regular business hours are 7:00am to 5:00pm., Monday through Friday except NREL recognized holidays. The Subcontractor personnel scheduled to work during non-working hours must notify the NREL TM prior to the start of work to ensure the Site Entrance Building has knowledge of the Subcontractor coming on-site after-hours.

Emergency or as-needed repairs and testing will be available during normal business hours from 7:00 a.m. through 5:00 p.m., Monday through Friday, except NREL recognized holidays.

The days designated as NREL holidays (i.e., New Year’s Day, Martin Luther King Jr. Day, Memorial Day, Juneteenth, Independence Day, Labor Day, Thanksgiving Day, Day after Thanksgiving, and Christmas Day) are not NREL workdays. If a NREL holiday falls on a mailto:Steven.Aldridge@nrel.gov mailto:John.Boysen@nrel.gov https://www.nrel.gov/about/ehs-construction.html

Saturday or Sunday, the preceding Friday or the following Monday may not be a NREL workday. The Friday after Thanksgiving is not a NREL workday.

6) Locations:

a) The Subcontractor shall perform services outlined in this Appendix A – Statement of

Work at the following locations. Future locations may be added or removed via mutually agreed to Subcontract modification completed by the NREL Subcontract Administrator.

1. South Table Mountain Site (STM), 15013 Denver West Pkwy, Golden, CO 80401.

i. ESIF, 15257 Denver West Parkway, Golden, CO 80401. (LEED Platinum)

ii. S&TF, 15253 Denver West Parkway, Golden, CO 80401. (LEED Platinum)

iii. RSF, 15301 Denver West Parkway, Golden, CO 80401. (LEED Platinum)

iv. SERF, 15313 Denver West Parkway, Golden, CO 80401.

v. FTLB, 15523 Denver West Parkway, Golden, CO 80401.

vi. OTF, 15883 Denver West Parkway, Golden, CO 80401.

vii. TTF, 15973 Denver West Parkway, Golden, CO 80401.

viii. IBRF, 16173 Denver West Parkway, Golden, CO 80401. (LEED Gold)

ix. Shipping/Receiving Building, 16253 Denver West Parkway, Golden, CO 80401.

x. ADD ALTERNATE: EMAPS, TBD

xi. ADD ALTERNATE: RAIL, 15503 Denver West Parkway, Golden CO 80401.

xii. ADD ALTERNATE: New Waste Handling Facility

b) Please reference the maps located on the NREL website links below. See Technical Monitor for additional information on locations as necessary.

1. Golden STM Campus: https://www.nrel.gov/about/golden.html

7) Glossary:

a) Definitions:

1. As-Needed – Any service required beyond the regularly scheduled tasks to ensure performance standards are met. May be at the request of the NREL Technical Monitor (TM) or On-Site Supervisor based on each individual situation encountered.

2. NREL – National Renewable Energy Laboratory

3. SOW – Statement of Work

4. TM – Technical Monitor

5. SA – Subcontract Administrator

6. SCLS – Service Contract Labor Standards

7. Toxic Gas - any gas that has a median lethal concentration (LC50) in air of more than 200 ppm but not more than 2000 ppm by volume of gas vapor, or more than 2 mg/L but not more than 20 mg/L of mist, fume, or dust

b) Location Acronyms:

1. STM – South Table Mountain Campus

i. EMAPS – Energy Materials and Processing at Scale Facility

ii. ESIF – Energy Systems Integration Facility

iii. FTLB – Field Test Laboratory Building

iv. IBRF – Integrated Biorefinery Research Facility

v. OTF – Outdoor Test Facility https://www.nrel.gov/about/golden.html

vi. RAIL – Research and Innovation Laboratory

vii. RSF – Research Support Facility

viii. S&TF – Science & Technology Facility

ix. SERF – Solar Energy Research Facility

x. TTF – Thermal Test Facility

xi. WHF – Waste Handling Facility

NREL SITE OPERATIONS Work order No.

Service work sheet for STATIONARY (FIXED) (F) gas detection Date:

Technician(s):

FTLB Building Technician(s):

SNSR ## Sensor Type Sensor Make Sensor Model Sensor Location Calibration Gas and Concentration

Calibration Gas Flow Rate

Pass / Fail Calibration Date / Comments

DAR

101-01 Hydrogen Cyanide OLDHAM iTRANS 2 101 S POD HCN 10 PPM 0.5 LPM pass 3/1/2024 James Stunkel

101-02 Ammonia OLDHAM iTRANS 2 101 S POD NH3 50 PPM 1 LPM pass 3/1/2024 James Stunkel

101-03 LEL/CH4 OLDHAM iTRANS 2 101 S POD H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 James Stunkel

101-04 Nitrogen Dioxide OLDHAM iTRANS 2 101 S POD NO2 5PPM 0.5 LPM pass 3/1/2024 James Stunkel

101-05 Carbon Monoxide OLDHAM iTRANS 2 101 S POD CO 100 PPM 0.5 LPM pass 3/1/2024 James Stunkel

101-06 Nitrogen Dioxide OLDHAM iTRANS 2 101 N POD NO2 5PPM 0.5 LPM pass 3/1/2024 James Stunkel

101-07 Carbon Monoxide OLDHAM iTRANS 2 101 N POD CO 100 PPM 0.5 LPM pass 3/1/2024 James Stunkel

101-08 LEL/CH4 OLDHAM iTRANS 2 101 N POD H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 James Stunkel

101-09 Hydrogen Cyanide OLDHAM iTRANS 2 101 N POD HCN 10 PPM 0.5 LPM pass 3/1/2024 James Stunkel

101-10 Ammonia OLDHAM iTRANS 2 101 N POD NH3 50 PPM 1 LPM pass 3/1/2024 James Stunkel

101-11 LEL/H2 HONEYWELL XCD-RTD 101 BETWEEN PODS H2 500PPM 0.5LPM Not Testing 3/1/2024 James Stunkel

104A-01 Carbon Monoxide OLDHAM iTRANS 2 104A CO 100 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104A-02 Hydrogen Sulfide OLDHAM iTRANS 2 104A H2S 25 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104B-01 Carbon Monoxide OLDHAM iTRANS 2 104B CO 100 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104B-02 Hydrogen Sulfide OLDHAM iTRANS 2 104B H2S 25 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104B-03 LEL/C5H12 OLDHAM iTRANS 2 104B H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Kellene Orton

104B-04 LEL/CH4 OLDHAM iTRANS 2 104B H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Kellene Orton

104C-01 Carbon Monoxide OLDHAM iTRANS 2 104C CO 100 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104C-02 Hydrogen Sulfide OLDHAM iTRANS 2 104C H2S 25 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104C-03 LEL/C5H12 OLDHAM iTRANS 2 104C H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Kellene Orton

104C-04 Hydrogen Sulfide OLDHAM iTRANS 2 104C H2S 25 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104MEZ-01 LEL/C5H12 OLDHAM iTRANS 2 104M H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Kellene Orton

104MEZ-02 Carbon Monoxide OLDHAM iTRANS 2 104M CO 100 PPM 0.5 LPM pass 3/1/2024 Kellene Orton

104MEZ-03 LEL/CH4 OLDHAM iTRANS 2 104M H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Kellene Orton

105-01 Carbon Monoxide OLDHAM iTRANS 2 105 CO 100 PPM 0.5 LPM pass 3/1/2024 Jessica Olstad

105-02 LEL/CH4 OLDHAM iTRANS 2 105 H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Jessica Olstad

105-03 Hydrogen Sulfide OLDHAM iTRANS 2 105 H2S 25 PPM 0.5 LPM pass 3/1/2024 Jessica Olstad

105-04 Carbon Monoxide OLDHAM iTRANS 2 105 CO 100 PPM 0.5 LPM pass 3/1/2024 Jessica Olstad

Technician(s):

FTLB Building Technician(s):

SNSR ## Sensor Type Sensor Make Sensor Model Sensor Location Calibration Gas and Concentration

Calibration Gas Flow Rate

Pass / Fail Calibration Date / Comments

DAR

105-05 LEL/CH4 OLDHAM iTRANS 2 105 H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Jessica Olstad

105-06 Carbon Monoxide OLDHAM iTRANS 2 105 CO 100 PPM 0.5 LPM pass 3/1/2024 Jessica Olstad

105-07 LEL/CH4 OLDHAM iTRANS 2 105 H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Jessica Olstad

105-08 Carbon Monoxide OLDHAM iTRANS 2 105 CO 100 PPM 0.5 LPM pass 3/1/3024 Jessica Olstad

105-09 LEL/CH4 OLDHAM iTRANS 2 105 H2 2% VOL (50%LEL) 0.5 LPM pass 3/1/2024 Jessica Olstad

105-10 LEL/H2 HONEYWELL XCD-RTD 105 H2 500PPM 0.5LPM Not Testing Mar-24 Jessica Olstad

113-01 LEL/H2 HONEYWELL XCD-RTD 113 MANIFOLD H2 500PPM 0.5LPM Not Testing Mar-24 Jeremy Basard

113-02 Carbon Monoxide HONEYWELL XCD-RTD 113 AMBIENT CO 100 PPM 0.5LPM pass Mar-24 Jeremy Basard

113-03 Carbon Monoxide HONEYWELL XCD-RTD 113 MANIFOLD CO 100 PPM 0.5LPM pass Mar-24 Jeremy Basard

113-04 LEL/H2 HONEYWELL XCD-RTD 113 HOOD #1 H2 500PPM 0.5LPM Not testing Mar-24 Jeremy Basard

113-05 LEL/H2 HONEYWELL XCD-RTD 113 HOOD #2 H2 500PPM 0.5LPM Not testing Mar-24 Jeremy Basard

113-06 LEL/H2 HONEYWELL XCD-RTD 113 HOOD #3 H2 500PPM 0.5LPM not testing Mar-24 Jeremy Basard

113-07 LEL/H2 HONEYWELL XCD-RTD 113 ROLL-IN #1 H2 500PPM 0.5LPM not testing Mar-24 Jeremy Basard

113-08 LEL/H2 HONEYWELL XCD-RTD 113 ROLL-IN #2 H2 500PPM 0.5LPM not testing Mar-24 Jeremy Basard

113-09 Carbon Monoxide HONEYWELL XCD-RTD 113 HOOD #1 CO 100 PPM 0.5LPM pass Mar-24 Jeremy Basard

113-10 Carbon Monoxide HONEYWELL XCD-RTD 113 HOOD #2 CO 100 PPM 0.5LPM pass Mar-24 Jeremy Basard

113-11 Carbon Monoxide HONEYWELL XCD-RTD 113 HOOD #3 CO 100 PPM 0.5LPM pass Mar-24 Jeremy Basard

113-12 Carbon Monoxide HONEYWELL XCD-RTD 113 ROLL-IN #1 CO 100 PPM 0.5LPM pass Mar-24 Jeremy Basard

117-01 Oxygen ALPHA OMEGA 1000-R 117 O2 18% 0.5 LPM pass Mar-24 David Mulder

118-01-01 Oxygen ALPHA OMEGA 1000-R 118-01 O2 18% 0.5 LPM pass Mar-24 David Mulder

115- 01 Oxygen ALPHA OMEGA 1300 115 O2 18% 0.5 LPM Pass Mar-24 Jeremy Basard

119H-01 Oxygen ALPHA OMEGA 1000 119H O2 18% 0.5 LPM pass Mar-24 Josie

120-01 Oxygen ALPHA OMEGA 1300 120 O2 18% 0.5 LPM pass Mar-24 Bennett Addison

120-02 Oxygen Alpha Omega 1300 115 O2 18% 0.5 LPM Pass Mar-24 Bennett Addison

120-03 Oxygen ALPHA OMEGA 1300 120 O2 18% 0.5 LPM pass Mar-24 Bennett Addison

121-01 Carbon Monoxide HONEYWELL E3SA 121 CO 100 PPM 0.5 LPM pass Mar-24 Jianping Yu

121-02 LEL/H2 HONEYWELL E3SA 121 H2 2% VOL (50%LEL) 0.5 LPM pass Mar-24 Jianping Yu

121-03 LEL/H2 HONEYWELL XCD-RTD 121 H2 500PPM 0.5LPM Not Testing Mar-24 Jianping Yu

Technician(s):

FTLB Building Technician(s):

SNSR ## Sensor Type Sensor Make Sensor Model Sensor Location Calibration Gas and Concentration

Calibration Gas Flow Rate

Pass / Fail Calibration Date / Comments

DAR

121-04 Carbon Monoxide HONEYWELL XCD-RTD 121 CO 100 PPM 0.5LPM Pass Mar-24 Jianping Yu

127-01 Oxygen OLDHAM iTRANS 2 127 N 99.9% / O2 20.9% VOL 0.5 LPM Pass Mar-24 Matt Oliver

127-02 LEL/C5H12 OLDHAM iTRANS 2 127 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Matt Oliver

127-03 Hydrogen Sulfide OLDHAM iTRANS 2 127 H2S 25 PPM 0.5 LPM pass Mar-24 Matt Oliver

127-04 Carbon Monoxide OLDHAM iTRANS 2 127 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

127-05 Carbon Monoxide OLDHAM iTRANS 2 127 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

127-06 LEL/CH4 OLDHAM iTRANS 2 127 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Matt Oliver

131-01 Carbon Monoxide OLDHAM iTRANS 2 131 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

131-02 Carbon Monoxide OLDHAM iTRANS 2 131 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

131-03 Carbon Monoxide OLDHAM iTRANS 2 131 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

131-04 LEL/CH4 OLDHAM iTRANS 2 131 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Matt Oliver

131-05 Carbon Monoxide OLDHAM iTRANS 2 131 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

131-06 LEL/CH4 OLDHAM iTRANS 2 131 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Matt Oliver

131-07 LEV/C5H12 OLDHAM iTRANS 2 131 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Matt Oliver

131-08 Carbon Monoxide OLDHAM iTRANS 2 131 CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

131-09 LEL/H2 HONEYWELL XCD-RTD 131 (FOR LAB 127) H2 500PPM 0.5LPM Fail Mar-24 Matt Oliver

131MEZ-01 Carbon Monoxide OLDHAM iTRANS 2 131 MEZ CO 100 PPM 0.5 LPM Pass Mar-24 Matt Oliver

131MEZ-02 LEL/C5H12 OLDHAM iTRANS 2 131 MEZ H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Matt Oliver

131MEZ-03 Carbon Monoxide OLDHAM iTRANS 2 131 MEZ CO 100 PPM 0.5 LPM Pass 3/1/2024 Matt Oliver

131MEZ-04 LEL/C5H12 OLDHAM iTRANS 2 131 MEZ H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Matt Oliver

131MEZ-05 LEV/CH4 OLDHAM iTRANS 2 131 MEZ H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Matt Oliver

134-01 Oxygen ALPHA OMEGA 1000 134 O2 18% 0.5 LPM pass 3/1/2024 William Michener

150-01 Oxygen HONEYWELL E3SA 150 N 99.9% / O2 20.9% VOL 0.5 LPM Pass 3/1/2024 Steven Rowland

150-02 Carbon Monoxide OLDHAM iTRANS 2 150 CO 100 PPM 0.5 LPM Pass 3/1/2024 Steven Rowland

150-03 LEL/CH4 OLDHAM iTRANS 2 150 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Steven Rowland

150-04 LEL/H2 HONEYWELL MIDAS 150 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Steven Rowland

150-05 LEL/CH4 OLDHAM iTRANS 2 150 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Steven Rowland

150-06 LEL/H2 HONEYWELL XCD-RTD 150 H2 500PPM 0.5LPM Fail 3/1/2024 Steven Rowland

Technician(s):

FTLB Building Technician(s):

SNSR ## Sensor Type Sensor Make Sensor Model Sensor Location Calibration Gas and Concentration

Calibration Gas Flow Rate

Pass / Fail Calibration Date / Comments

DAR

150-07 Carbon Monoxide HONEYWELL XCD-RTD 150 CO 100 PPM 0.5LPM Pass 3/1/2024 Steven Rowland

155-01 Carbon Monoxide OLDHAM iTRANS 2 155 CO 100 PPM 0.5 LPM Pass 3/1/2024 Scott Palmer

155-02 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-03 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass Mar-24 Scott Palmer

155-04 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-05 Carbon Monoxide OLDHAM iTRANS 2 155 CO 100 PPM 0.5 LPM Pass 3/1/2024 Scott Palmer

155-06 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-07 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-08 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-09 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-10 LEL/CH4 OLDHAM iTRANS 2 155 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Scott Palmer

155-11 LEL/H2 HONEYWELL XCD-RTD 155 H2 500PPM 0.5LPM Fail 3/1/2024 Scott Palmer

173-01 LEL/H2 HONEYWELL E3SA 173 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Jianping Yu

173-02 Carbon Monoxide HONEYWELL E3SA 173 CO 100 PPM 0.5 LPM Pass 3/1/2024 Jianping Yu

175-01 LEL/H2 HONEYWELL E3SA 175 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 David Mulder

175-02 Carbon Monoxide HONEYWELL E3SA 175 CO 100 PPM 0.5 LPM Pass 3/1/2024 David Mulder

201-01 Carbon Monoxide OLDHAM iTRANS 2 201 CO 100 PPM 0.5 LPM Pass 3/1/2024 Matt Oliver

201-01 LEL/C5H12 OLDHAM iTRANS 2 201 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Matt Oliver

204-01 Oxygen HONEYWELL E3SA 204 N 99.9% / O2 20.9% VOL 0.5 LPM Pass 3/1/2024 Rianna Martinez

204-02 LEL/H2 HONEYWELL XCD-RTD 204 H2 500PPM 0.5 LPM Fail Rianna Martinez

204-03 LEL/H2 HONEYWELL XCD-RTD 204 H2 500PPM 0.5LPM Fail Rianna Martinez

205-01 Oxygen HONEYWELL E3SA 205 N 99.9% / O2 20.9% VOL 0.5 LPM Pass 3/1/2024 Vladimir Lunin

235-01 Carbon Monoxide HONEYWELL E3SA 235 CO 100 PPM 0.5 LPM Pass 3/1/2022 Wade Braunecker

235-02 LEL/H2 HONEYWELL E3SA 235 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Wade Braunecker

248-01 Carbon Monoxide HONEYWELL E3SA 248 CO 100 PPM 0.5 LPM Pass 3/1/2024 Wei Wang

248-02 LEL/H2 HONEYWELL E3SA 248 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Wei Wang

248-03 Carbon Monoxide HONEYWELL E3SA 248 CO 100 PPM 0.5 LPM Pass 3/1/2024 Wei Wang

248-04 LEL/H2 HONEYWELL E3SA 248 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Wei Wang

Technician(s):

FTLB Building Technician(s):

SNSR ## Sensor Type Sensor Make Sensor Model Sensor Location Calibration Gas and Concentration

Calibration Gas Flow Rate

Pass / Fail Calibration Date / Comments

DAR

251-01 Carbon Monoxide HONEYWELL E3SA 251 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-02 LEL/H2 HONEYWELL E3SA 251 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-03 Carbon Monoxide HONEYWELL E3SA 251 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-04 LEL/H2 HONEYWELL E3SA 251 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-05 Carbon Monoxide HONEYWELL E3SA 251 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-06 LEL/H2 HONEYWELL E3SA 251 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-07 Carbon Monoxide HONEYWELL E3SA 251 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-08 LEL/H2 HONEYWELL E3SA 251 H2 2% VOL (50%LEL) 0.5 LPM Not In Service 3/1/2024 Nicholas Katsiotis

251-09 Carbon Monoxide HONEYWELL E3SA 251 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-10 LEL/H2 HONEYWELL E3SA 251 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

251-11 LEL/H2 HONEYWELL XCD-RTD 251 H2 500PPM 0.5LPM Not testing 3/1/2024 Nicholas Katsiotis

252-01 Carbon Monoxide OLDHAM iTRANS 2 252 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

252-02 Ammonia OLDHAM iTRANS 2 252 NH3 50 PPM 1 LPM Pass 3/1/2024 Nicholas Katsiotis

252-03 Hydrogen Sulfide OLDHAM iTRANS 2 252 H2S 25 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

252-04 Carbon Monoxide HONEYWELL E3SA 252 CO 100 PPM 0.5 LPM Pass 3/1/2024 Nicholas Katsiotis

269-01 Hydrogen Sulfide OLDHAM iTRANS 2 269 H2S 25 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-02 LEL/CH4 OLDHAM iTRANS 2 269 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-03 Carbon Monoxide OLDHAM iTRANS 2 269 CO 100 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-04 LEL/CH4 OLDHAM iTRANS 2 269 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-05 Carbon Monoxide OLDHAM iTRANS 2 269 CO 100 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-06 Hydrogen Sulfide OLDHAM iTRANS 2 269 H2S 25 PPM 0.5 LPM Pass Mar-24 Dan Dupuis

269-07 LEL/CH4 OLDHAM iTRANS 2 269 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-08 Carbon Monoxide OLDHAM iTRANS 2 269 CO 100 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-09 Ammonia OLDHAM iTRANS 2 269 NH3 50 PPM 1 LPM Pass 3/1/2024 Dan Dupuis

269-10 LEL/CH4 OLDHAM iTRANS 2 269 H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-11 Carbon Monoxide OLDHAM iTRANS 2 269 CO 100 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

269-12 Ammonia OLDHAM iTRANS 2 269 NH3 50 PPM 1 LPM Pass 3/1/2024 Dan Dupuis

269GASPAD-01 Carbon Monoxide OLDHAM iTRANS 2 269 GAS PAD CO 100 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

269GASPAD-02 LEL/CH4 OLDHAM iTRANS 2 269 GAS PAD H2 2% VOL (50%LEL) 0.5 LPM Pass 3/1/2024 Dan Dupuis

Technician(s):

FTLB Building Technician(s):

SNSR ## Sensor Type Sensor Make Sensor Model Sensor Location Calibration Gas and Concentration

Calibration Gas Flow Rate

Pass / Fail Calibration Date / Comments

DAR

269GASPAD-03 Ammonia OLDHAM iTRANS 2 269 GAS PAD NH3 50 PPM 1 LPM Pass 3/1/2024 Dan Dupuis 269GASPAD-04 Hydrogen Sulfide OLDHAM iTRANS 2 269 GAS PAD H2S 25 PPM 0.5 LPM Pass 3/1/2024 Dan Dupuis

C102-01 Carbon Monoxide MACURCO CM-6 C102 CO 200 PPM 0.5 LPM Pass 3/1/2024 Mike Wodzianski C102-02 Carbon Monoxide MACURCO CM-6 C102 CO 200 PPM 0.5 LPM Pass 3/1/2024 Mike Wodzianski C102-03 Carbon Monoxide MACURCO CM-6 C102 CO 200 PPM 0.5 LPM Pass 3/1/2024 Mike Wodzianski

C103-02-01 Carbon Monoxide MACURCO CM-6 C103-02 CO 200 PPM 0.5 LPM Pass 3/1/2024 Mike Wodzianski C106-01 Carbon Monoxide MACURCO CM-6 C105 CO 200 PPM 0.5 LPM Pass 3/1/2024 Mike Wodzianski

Service work sheet for PORTABLE (P) gas detection Date:

Technician(s):

FTLB Building Technician(s):

P SNSR ## Sensor Type Sensor Make Sensor Model Sensor Serial No. Sensor Location

Calibration Gas and Concentration Pass / Fail Calibration Date / Comments

DAR

P 103-01 4 GAS DRAGER X AM 2000 ERED-0286 103 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass 3/1/2024 James Stunkel

P 104A-01 4 GAS DRAGER X AM 2500 ARMM-0067 104A H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Kellene McKinney

P 104A-02 4 GAS DRAGER X AM 2500 ARMM-0074 104A H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Out of service Mar-24 Kellene McKinney

P 104B-01 4 GAS DRAGER X AM 2000 ERDN-0479 104B H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Dan Dupuis

P 104B-02 4 GAS DRAGER X AM 2000 EREA-0189 104B H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Dan Dupuis

P 105-01 4 GAS DRAGER X AM 2500 ARFD-1192 105 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Jessica Olstad

P 105-02 4 GAS DRAGER X AM 2500 ARFD-1197 105 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Jessica Olstad

P 120-01 O2 DRAGER PAC 7000 ARKB-3038 120 O2 17% Pass Mar-24 Renee Happs

P 121-01 4 GAS DRAGER X AM 2500 ARKE-3442 121 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Jianping Yu

P 131-01 CO DRAGER Pac 5500 ERFN-0646 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-02 CO DRAGER Pac 5500 ERHH-1506 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-03 CO DRAGER Pac 5500 ERFN-0636 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-04 CO DRAGER Pac 5500 ERHH-1512 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-05 CO DRAGER Pac 5500 ERFN-0640 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-06 CO DRAGER Pac 5500 ERHH-1513 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-07 CO DRAGER Pac 5500 ERFN-0642 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-08 CO DRAGER Pac 5500 ERFN-0649 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-09 CO DRAGER Pac 5500 ERFN-0870 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-10 CO DRAGER Pac 5500 ERFN-0863 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-11 CO DRAGER Pac 5500 ERHH-1521 131 CO 100PPM Pass Mar-24 Matt Oliver

P 131-12 CO DRAGER Pac 5500 ERHF-0024 131 CO 100PPM Pass Mar-24 Matt Oliver

P 147-01 4 GAS DRAGER X AM 2000 ERDN-0476 147 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Stephen Tifft

P 155-01 4 Gas DRAGER X AM 2000 ARRD-0013 155 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Scott Palmer

P 155-02 4 GAS DRAGER X AM 2500 ARMM-0100 155 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Scott Palmer

P RESOPS-01 4 GAS DRAGER X AM 2500 ARKF-1625 205 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-02 4 GAS DRAGER X AM 2500 ARKF-1604 118-03 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-03 4 GAS DRAGER X AM 2500 ARKF- 2532 180-7A H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-04 4 GAS DRAGER X AM 2500 ARME-0176 167-01 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-05 4 GAS DRAGER X AM 2500 ARME-0156 168 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-06 4 GAS DRAGER X AM 2500 ARME-0197 167 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-07 4 GAS DRAGER X AM 2500 ARME-0210 IBRF 290 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

Service work sheet for PORTABLE (P) gas detection Date:

Technician(s):

FTLB Building Technician(s):

P SNSR ## Sensor Type Sensor Make Sensor Model Sensor Serial No. Sensor Location

Calibration Gas and Concentration Pass / Fail Calibration Date / Comments

DAR

P RESOPS-08 4 GAS DRAGER X AM 2500 ARKE-3451 IBRF 290 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-09 4 GAS DRAGER X AM 2500 ARKF-1643 105 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-10 4 GAS DRAGER X AM 2500 ARKF-1605 155 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P RESOPS-11 4 GAS DRAGER X AM 2500 ARKE-3440 IBRF 290 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Athanasia Kendl

P 269-01 4 GAS DRAGER X AM 2500 ARLE-3841 269 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Dan Dupuis

P 269-02 4 GAS DRAGER X AM 2500 ARLE-3801 269 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Dan Dupuis

P 269-03 4 GAS DRAGER X AM 2500 ERDN-0478 269 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Dan Dupuis

P 269-04 4 GAS DRAGER X AM 2500 ERDH-1152 269 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Dan Dupuis

P SITEOPS-01 4 GAS DRAGER X AM 5000 ARFM-0084 C103 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Joshua Korosec

P SITEOPS-02 4 GAS DRAGER X AM 5000 ARFE-0681 C103 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% Pass Mar-24 Joshua Korosec p P-21 CO Drager PAC 5500 ERHH1498 131 Co 100PPM pass Mar-24 Matt Oliver p Farrell 4 Gas Drager XAM5000 DRPJ0122 168 H2S 25PPM, CO 100PPM, CH4 50%LEL, O2 17% pass Mar-24 ???

ESIF ECO SENSORS FOR LABS

LAB: SENSOR: NOTE: ORIGINAL INSTALLATION AT ESIF

C221 NO2 XTRALIS ECO SENSORS

C221 CO 17 S54334-Z20-A1 HYDROGEN 0-2000 PPM, CALIBRATION SCALE RANGE 1000PPM

C221 O2 OUT OF SERVICE 5 S54334-Z22-A1 CARBON MONOXIDE 0-500 PPM, CALIBRATION SCALE RANGE 100 PPM C220 NO2 OUT OF SERVICE 4 S54334-Z21-A1 OXYGEN 0-25%, CALIBRATION SCALE RANGE 21% C220 CO OUT OF SERVICE 2 S54334-Z26-A1 NITROGEN DIOXIDE 0-10 PPM, CALIBRATION SCALE RANGE 5 PPM

C220 O2 OUT OF SERVICE 1 S54334-Z23-A1 AMMONIA 0-100 PPM

C332 H2 1 S54334-Z24-A1 HYDROGEN SULFIDE 1-100 PPM , CALIBRATION SCALE RANGE 25 PPM C331 H2 C330 H2 C329 H2

C329 CO

C339 H2 C339 H2 C339 H2 C339 H2 C339 H2 C339 H2 C325 H2 C325 H2

C325 O2 OUT OF SERVICE

C325 CO OUT OF SERVICE

C324 H2 C323 H2

C323 H2S OUT OF SERVICE

C323 CO OUT OF SERVICE

C323 O2 OUT OF SERVICE

C323 NH3 OUT OF SERVICE

C321 H2 C319 H2 C317 H2

ESIF GAS CABINET DETECTION ATI SENSORS

C312-05 H2 25 % LEL T# C12-17-1993 S#D10-17-3181

C312-08 H2 50 %LEL T# C12-17-1992 S# D10-17-3180

C312-09 CO 100% LEL T# B12-16-0604-OE S# C10-16-1213

C313-04 CO 100% LEL GAS BOTTLE STOREAGE LABEL MISSING

C313-06 CO2 OUT OF SERVICE T# B12-15-0976-OE S# C10-15-1595

C313-07 CO 100% LEL T# B12-16-0605-OE S# C10-16-1214

C313-08 CO 50% LEL NO LABEL

C313-09 H2 25% LEL T# C12-17-1987 S#D10-17-3175

C315-02 H2 25% LEL T# C12-17-1989 S# D10-17-3177

C315-04 GAS BOTTLE STOREAGE NOW T# C12-17-1990 S# D10-17-3178

C312-03 GAS BOTTLE STOREAGE NOW T# C12-17-1991 S# D10-17-3179

ESIF GAS DETECTION SENSORS OTHER THAN ECO

LAB: Sensor:

C331 CO HONEYWELL SENSEPOINT XCD

C312 O2 ALPHA OMEGA INSTRUMENTS SERIES 1000

Generated by jkorosec Page 1 of 4

Input Points List

Sites: NREL

Date: July 16, 2024 14:10 Generated by: jkorosec

Object ID Name Calibration Sensor Type Description

NREL

30303.AI6 SERF E007 ZN3 O2 SNSR

(O2-1)

0.1 MIDAS O2 SENSOR AIC new sensor 8/20 good

to 8/23 ss

30304.AI1306 SERF E015 OXYGEN LVL

AI (O2-8)

0 MIDAS O2 SENSOR AIC

30305.AI5 SERF E0C5 ZN1 O2 SNSR

(O2-2)

0 MIDAS O2 SENSOR AIC new sensor 8/20 good to 8/23 ss

30305.AI6 SERF E005 ZN2 O2 SNSR

(O2-3)

-3 ALPHA OMEGA O2

SENSOR AIC

THIS IS A OMEGA

CONTROLLER WILL

RESET BY IT'S SELF -3

calibration to match controller calibrated in lab E004

31100.AI5 SERF W125 H2 SNSR

(H2-1)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31100.AI6 SERF W125 H2 SNSR

(H2-2)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31100.AI7 SERF W125 H2 SNSR

(H2-3)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31200.AI2 SERF W128 H2 SNSR

(H2-4)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31200.AI3 SERF W128 H2 SNSR

(H2-5)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31200.AI4 SERF W128 H2 SNSR

(H2-6)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31200.AI5 SERF W128 H2 SNSR

(H2-7)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31200.AI6 SERF W128 H2 SNSR

(H2-8)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31300.AI2 SERF W129 H2 SNSR

(H2-9)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31300.AI3 SERF W129 H2 SNSR

(H2-10)

0 Hydrogen 4-20mA

0-100 %LEL AIC

Generated by jkorosec Page 2 of 4

NREL

31300.AI4 SERF W129 H2 SNSR

(H2-11) 0 Hydrogen 4-20mA

0-100 %LEL AIC

31300.AI5 SERF W129 H2 SNSR

(H2-12)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31400.AI2 SERF W1C3 W H2 SNSR

(H2-13)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31400.AI3 SERF W1C3 E H2 SNSR

(H2-14)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31500.AI2 SERF W2C3 H2 SNSR

(H2-15)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31500.AI3 SERF W2C3 H2 SNSR

(H2-16)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31500.AI4 SERF W2C3 H2 SNSR

(H2-17)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31500.AI5 SERF W2C3 H2 SNSR

(H2-18)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31500.AI6 SERF W2C3 H2 SNSR

(H2-19)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31500.AI7 SERF W206 H2 SNSR

(H2-20)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31700.AI2 SERF W211 H2 SNSR

(H2-21)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31700.AI3 SERF W211 H2 SNSR

(H2-22)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31700.AI4 SERF W209 H2 SNSR

(H2-23)

0 Hydrogen 4-20mA

0-100 %LEL AIC

SENSOR IS IN VMB

CABINET #1 SENSOR

31700.AI5 SERF W209 H2 SNSR

(H2-24)

0 Hydrogen 4-20mA

0-100 %LEL AIC

AMBIENT ABOVE TOOL

NEXT TO FUMEHOOD #2

SENSOR

31700.AI6 SERF W209 O2 SNSR

(O2-4)

-0.2 Oxygen 4-20mA 0-25%

O2 AIC

Generated by jkorosec Page 3 of 4

NREL

31700.AI7 SERF W209 O2 SNSR

(O2-5) 0 Oxygen 4-20mA 0-25%

O2 AIC

cal was at -0.130 10/2016 but unit was in hand adjusted calibration to+ 0.800 10/2016 ss cartridge expiring and occationally drops to 0% in Delta, while reading 20.9% on local display.

Overridden until replaced, second O2 sensor in room functioning as backup.

12/23/2017 JLR

31800.AI2 SERF W213 H2 SNSR

(H2-25)

0 Hydrogen 4-20mA

0-100 %LEL AIC

inside east duct work on mfc exhaust

31800.AI3 SERF W213 H2 SNSR

(H2-26)

0 Hydrogen 4-20mA

0-100 %LEL AIC

hanging in front of east mfc enclosure ambient point

31800.AI4 SERF W213 H2 SNSR

(H2-27)

0 Hydrogen 4-20mA

0-100 %LEL AIC

half way between west mfc cabinet and e system for ambbient between two systems

31800.AI5 SERF W213 H2 SNSR

(H2-28)

0 Hydrogen 4-20mA

0-100 %LEL AIC

inside duct work on west mfc exhaust duct

31800.AI6 SERF W213 H2 SNSR

(H2-29)

0 Hydrogen 4-20mA

0-100 %LEL AIC

near e system loadk lock door for maintenance on system when opened.

31900.AI1102 SERF W212 H2 SNSR

(H2-30)

0 Hydrogen 4-20mA

0-100 %LEL AIC

31900.AI1103 SERF W212 H2 SNSR

(H2-31)

0.2 Hydrogen 4-20mA

0-100 %LEL AIC

31900.AI1104 SERF W212 H2 SNSR

(H2-32)

0.1 Hydrogen 4-20mA

0-100 %LEL AIC

31900.AI1201 SERF W212 H2 SNSR

(H2-33)

0.2 Hydrogen 4-20mA

0-100 %LEL AIC

31900.AI1302 SERF W212 O3 SNSR

(O3-2)

0 Ozone O3 4-20mA 0-700 ppb AIC

31900.AI1303 SERF W212 O3 SNSR

(O3-3)

0 Ozone O3 4-20mA 0-700 ppb AIC

31900.AI1304 SERF W212 O3 SNSR

(O3-4)

0 Ozone O3 4-20mA 0-700 ppb AIC

32500.AI1101 SERF C1C2 H2 SNSR

(H2-38)

0 Hydrogen 4-20mA

0-100 %LEL AIC

Generated by jkorosec Page 4 of 4

NREL

32500.AI1102 SERF C1C2 H2 SNSR

(H2-39) 0 Hydrogen 4-20mA

0-100 %LEL AIC

32500.AI1103 SERF H124 H2 SNSR

(H2-40)

0 Hydrogen 4-20mA

0-100 %LEL AIC

33600.AI12 SERF E1C3 O2 SNSR

(O2-6)

0.1 MIDAS O2 SENSOR AIC new sensor 8/20 good

to 8/23 ss

33700.AI12 SERF E2C3 O2 SNSR

(O2-7)

0.1 MIDAS O2 SENSOR AIC new sensor 8/20 good

to 8/23 ss

36400.AI1101 SERF E216 H2 SNSR

(H2-34)

0 H2 AIC

36400.AI1102 SERF E216 NH3 SNSR

(NH3-1)

0 H2 AIC

36400.AI1103 SERF E216 H2 SNSR

(H2-35)

0 H2 AIC

36400.AI1104 SERF E216 NH3 SNSR

(NH3-2)

0 H2 AIC

36400.AI1105 SERF E216 H2 SNSR

(H2-36)

0 H2 AIC

36400.AI1106 SERF E216 NH3 SNSR

(NH3-3)

0 H2 AIC

36400.AI1107 SERF E216 H2 SNSR

(H2-37)

0 H2 AIC

36400.AI1108 SERF E216 NH3 SNSR

(NH3-4)

0 H2 AIC

Total : 55 Objects

Generated by jkorosec Page 1 of 3

Input Points List

Sites: NREL

Date: July 16, 2024 14:14 Generated by: jkorosec

NREL

37400.AI1101 STF 213 BAY2 H2 SNSR

(H2-1)

0 H2 AIC

37400.AI1102 STF 213 BAY3 H2 SNSR

(H2-2)

0 H2 AIC

37400.AI1103 STF 213 BAY3 H2 SNSR

(H2-3)

0 H2 AIC

37400.AI1104 STF 213 BAY4 H2 SNSR

(H2-4)

0 H2 AIC

37400.AI1201 STF 213 BAY5 H2 SNSR

(H2-5)

0.5 H2 AIC

37400.AI1203 STF 200C3 BAY4 H2

SNSR (H2-6)

0 H2 AIC

37400.AI1301 STF 203A HVPE1 H2

SNSR (H2-8)

0.5 H2 AIC 7400.AI1301 HVPE

TOOL EAST ENCLOSURE

H2 SENSOR #8

37400.AI1302 STF 203A HVPE1 H2

SNSR (H2-9)

0.5 H2 AIC 7400.AI1302 HVPE

TOOL WEST ENCLOSURE

H2 SENSOR #9

37400.AI1303 STF 203A HVPE1 H2

SNSR (H2-10)

0.5 H2 AIC 7400.AI1303 HVPE

TOOL BUBBLERS

CABINET ENCLOSURE H2

SENSOR #10

37400.AI1304 STF 214 CLN RM H2

SNSR (H2-11)

0 H2 AIC

37400.AI1401 STF 214 CLN RM H2

SNSR (H2-12)

0 H2 AIC

37400.AI1402 STF 214 CLN RM H2

SNSR (H2-13)

0 H2 AIC

37400.AI1403 STF 214 CLN RM H2

SNSR (H2-14)

0 H2 AIC

37400.AI1404 STF 214 CLN RM H2

SNSR (H2-15)

Generated by jkorosec Page 2 of 3

NREL

37400.AI2101 STF 200C3 204 W H2

SNSOR (H2-16)

0 H2 AIC

37400.AI2102 STF 200C3 204 E H2

SNSR (H2-17)

0 H2 AIC

37400.AI2103 STF 200C3 203B W H2

SNSR (H2-18)

0 H2 AIC LOCATED OUT SIDE

203B LAB IN CENTER

BUMP OUT IN CORRIDOR

AMBIENT POINT

37400.AI2104 STF 200C3 203B E H2

SNSR (H2-19)

0.5 H2 AIC LOCATED OUT SIDE

203B LAB CENTER

CORRIDOR EASTERN

BUMP OUT CLOSER TO

203A LAB AMBIENT

POINT

37400.AI2201 STF 203A HVPE1 H2

SNSR (H2-20)

0 H2 AIC 7400.AI2201 HVPE

TOOL SCRUBBER H2

SENSOR #7 LOCATED

ABOVE MDA PANEL IN

LAB 203 THIS UNITS

READS LEL SCRUBBER

CABINET WEST SIDE

WHITE CABINET

37400.AI2202 STF 200C3 BAY1 H2

SNSR (H2-21)

0 H2 AIC

37400.AI2203 STF 200C3 BAY3 H2

SNSR (H2-22)

0 H2 AIC

37400.AI2301 STF 214 CLN RM H2

SNSR (H2-23)

0 H2 AIC

37400.AI2302 STF 214 CLN RM H2

SNSR (H2-24)

0 H2 AIC

37400.AI2303 STF 214 CLN RM CH4

SNSR (CH4-1)

0 H2 AIC

37400.AI2304 STF 214 CLN RM CH4

SNSR (CH4-2)

0 H2 AIC

37400.AI4302 STF 203A HVPE1 H2

SNSR (H2-25)

0.5 STF H2 ppm AIC 7400.AI4302 HVPE

TOOL WEST ENCLOSURE

H2 SENSOR #1 LOCATED

ABOVE MDA PANEL IN

LAB 203 THIS UNITS

READS PPM CONTROLS

EAST REACTOR IN EAST

ENCLOSURE

37400.AI4303 STF 203B H2 SNSR

(H2-26)

0.5 H2 AIC LOCATED IN 203B EAST

SIDE ON CABLE TRAY

AMBIENT

Generated by jkorosec Page 3 of 3

NREL

37400.AI4304 STF 203B H2 SNSR

(H2-27)

0.5 H2 AIC LOCATED IN 203B

CENTER OF LAB ON

CABLE TRAY AMBIENT

37400.AI4401 STF 203B H2 SNSR

(H2-28)

0.5 H2 AIC LOCATED IN 203B

CENTER OF LAB ON

CABLE TRAY AMBIENT

37400.AI4402 STF 203A HVPE1 H2

SNSR (H2-29)

0.5 H2 AIC 7400.AI4302 HVPE

TOOL AMBIENT H2

SENSOR #5 LOCATED

ABOVE MDA PANEL IN

LAB 203 THIS UNITS

READS LEL LOCATED IN

FRONT OF TOOL

AMBIENT POINT

37400.AI4403 STF 204 H2 SNSR

(H2-30)

0.5 H2 AIC

37400.AI4404 STF 200C3 BAY3 CH4

SNSR (CH4-3)

0.5 H2 AIC 200C3-1 located in

corridor outside bay 3 listed as methane

37400.AI5201 STF 203A HVPE3 H2

SNSR (H2-31)

0 H2 AIC

37400.AI5202 STF 203A HVPE3 H2

SNSR (H2-32)

0 H2 AIC

37400.AI5203 STF 203A HVPE3 H2

SNSR (H2-33)

0 H2 AIC

37400.AI5204 STF 203A HVPE3 H2

SNSR (H2-34)

0 H2 AIC

37400.AI5205 STF 203A HVPE3 H2

SNSR (H2-35)

0 H2 AIC

37400.AI5206 STF 203A HVPE2 H2

SNSR (H2-36)

0 H2 AIC

37400.AI5207 STF 203A HVPE2 H2

SNSR (H2-37)

0 H2 AIC

37400.AI5208 STF 203A HVPE2 H2

SNSR (H2-38)

0 H2 AIC

37400.AI5301 STF 203A HVPE2 H2

SNSR (H2-39)

0 H2 AIC

37400.AI5302 STF 203A HVPE2 H2

SNSR (H2-40)

Total : 42 Objects