ESBD_376044_1727188140556_ACM SurveyGibson D Lewis Health Science Library.pdf

PDF 6 MB Posted

Attached to
UNTHSC Gibson Library 3rd Floor Provost Suite
Solicitation number
RFCSP769-25-992ER
Issued by
Tarrant County, Frankston Town, Texas

About this file

This document is an asbestos survey report prepared by Apex TITAN, Inc. for the University of North Texas Health Science Center regarding the Gibson D. Lewis Library located at 955 Montgomery Street in Fort Worth, Texas. The survey was conducted from July 29-31, 2020 and included sampling of the second, third, and fourth floors. The report identifies asbestos-containing materials (ACMs) present in the building, including duct mastic, mastic associated with perimeter walls, and assumed ACMs such as ceramic floor and wall tiles. The report recommends that all identified ACMs be abated prior to any renovation or demolition activities in the building. The report also notes that materials on the roof and building envelope were not evaluated and should be assumed to contain asbestos until tested.

The report provides details on the analysis methodology, including the use of Polarized-Light Microscopy (PLM) to analyze 190 bulk samples from 59 homogeneous materials. The report outlines the condition and estimated quantities of the identified ACMs. No pricing information, set asides, or funding details are provided in the document. The report was prepared solely for the use of the University of North Texas Health Science Center in determining the presence of asbestos at the site.

View the file

Other files

File Type Posted
ESBD_376044_1728073218364_Questions #2.pdf PDF
ESBD_376044_1726669576342_Pre-Solicitation Presentation HSC Gibson Lib 3rd Fl Provost Suite.pdf PDF
ESBD_376044_1725994034374_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.1.pdf PDF
ESBD_376044_1725994126022_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.2.pdf PDF
ESBD_376044_1727809746584_Questions #1.pdf PDF
ESBD_376044_1727187834372_Site Visit Sign In Sheet 9-19-24.pdf PDF
ESBD_376044_1726669643381_Pre-Solicitation Meeting -Sign In Sheet -.pdf PDF
ESBD_376044_1726167242588_Notice to locate Drawings.pdf PDF
ESBD_376044_1725993614065_RFCSP769-25-992ER UNTHSC Gibson Library 3rd Fl Provost Suite (1).pdf PDF
ESBD_376044_1726167242588_Notice to locate Drawings.pdf PDF
ESBD_376044_1726669643381_Pre-Solicitation Meeting -Sign In Sheet -.pdf PDF
ESBD_376044_1727188140556_ACM SurveyGibson D Lewis Health Science Library.pdf PDF
ESBD_376044_1725994126022_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.2.pdf PDF
ESBD_376044_1725994034374_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.1.pdf PDF
ESBD_376044_1726669576342_Pre-Solicitation Presentation HSC Gibson Lib 3rd Fl Provost Suite.pdf PDF
ESBD_376044_1727187834372_Site Visit Sign In Sheet 9-19-24.pdf PDF
ESBD_376044_1728073218364_Questions #2.pdf PDF
ESBD_376044_1725993614065_RFCSP769-25-992ER UNTHSC Gibson Library 3rd Fl Provost Suite (1).pdf PDF
ESBD_376044_1727809746584_Questions #1.pdf PDF
ESBD_376044_1727188140556_ACM SurveyGibson D Lewis Health Science Library.pdf PDF
ESBD_376044_1726167242588_Notice to locate Drawings.pdf PDF
ESBD_376044_1726669643381_Pre-Solicitation Meeting -Sign In Sheet -.pdf PDF
ESBD_376044_1725994126022_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.2.pdf PDF
ESBD_376044_1727187834372_Site Visit Sign In Sheet 9-19-24.pdf PDF
ESBD_376044_1725993614065_RFCSP769-25-992ER UNTHSC Gibson Library 3rd Fl Provost Suite (1).pdf PDF
ESBD_376044_1725994034374_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.1.pdf PDF
ESBD_376044_1726669576342_Pre-Solicitation Presentation HSC Gibson Lib 3rd Fl Provost Suite.pdf PDF
ESBD_376044_1725994034374_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.1.pdf PDF
ESBD_376044_1726669643381_Pre-Solicitation Meeting -Sign In Sheet -.pdf PDF
ESBD_376044_1726669576342_Pre-Solicitation Presentation HSC Gibson Lib 3rd Fl Provost Suite.pdf PDF
ESBD_376044_1726167242588_Notice to locate Drawings.pdf PDF
ESBD_376044_1725993614065_RFCSP769-25-992ER UNTHSC Gibson Library 3rd Fl Provost Suite (1).pdf PDF
ESBD_376044_1725994126022_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.2.pdf PDF
ESBD_376044_1726167242588_Notice to locate Drawings.pdf PDF
ESBD_376044_1725993614065_RFCSP769-25-992ER UNTHSC Gibson Library 3rd Fl Provost Suite (1).pdf PDF
ESBD_376044_1725994126022_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.2.pdf PDF
ESBD_376044_1725994034374_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.1.pdf PDF
ESBD_376044_1725993614065_RFCSP769-25-992ER UNTHSC Gibson Library 3rd Fl Provost Suite (1).pdf PDF
ESBD_376044_1725994034374_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.1.pdf PDF
ESBD_376044_1725994126022_2024.07.03_UNTHSC Provost Suite Renovation_Project Manual Vol.2.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Apex TITAN, Inc., a subsidiary of Apex Companies, LLC 12100 Ford Road, Suite 401, Dallas, TX 75234 T 469.365.1100 F 469.365.1199 www.apexcos.com

December 23, 2020

University of North Texas Health Science Center 3416 Darcy Street Fort Worth, Texas Attention: Mr. Robert E. Short, Jr. P.E.

Re: Asbestos Survey University of North Texas Health Science Center Gibson D. Lewis Library (LIB) 955 Montgomery Street Fort Worth, Texas Apex project No.725010720021

Apex TITAN, Inc., a subsidiary of Apex Companies, LLC (Apex) was retained by University of North Texas Health Science Center to conduct an asbestos survey of the second, third, and fourth floors of the Gibson D. Lewis Library (LIB) located at 955 Montgomery Street in Fort Worth, Texas. At the request of the client results from the previous sampling of the first floor, Apex Project Number 725010720014, dated March 16, 2020 have been included in this report.

The survey was performed from July 29 - 31, 2020 by Mr. Zurisaday Diego, a Texas Department of State Health Service (TDSHS) licensed asbestos inspector (TDSHS License No.

60-3759). This survey has been performed in accordance with Apex Proposal No.

P725010720021rev dated July 1, 2020. The following is a summary of the suspect asbestos containing materials (ACM) collected from the building. ACM previously identified by Apex was incorporated into this report.

The following materials were observed on the day of the survey; however, they were not sampled due to the destructive nature of the sampling:

First Floor o Mastic associated with Raised Wooden Floor Pedestals o Mirror Mastic - Restrooms

Second Floor o 12” x 12” Ceramic Floor Tile (Grey) - Restrooms o Mirror Mastic - Restrooms o 12” x 16” Ceramic Wall Tile (White) - Restrooms

Third Floor o Resilient Vinyl Flooring (Red, Wood Pattern) o 12” x 12” Ceramic Floor Tile (Grey) - Restrooms o Mirror Mastic - Restrooms o 12” x 16” Ceramic Wall Tile (White) - Restrooms

Fourth Floor o Mastic associated with Corner Guards o 12” x 12” Ceramic Floor Tile (Grey) - Restrooms o Mirror Mastic - Restrooms o 12” x 16” Ceramic Wall Tile (White) - Restrooms

University of North Texas Science Center – Gibson D. Lewis Library (LIB) December 23, 2020 Apex project No. 725010720021 Page 2

These materials must be sampled prior to disturbance or assumed to be asbestos containing and handled according to local, state, and federal regulations.

This survey applies only to the materials sampled on the interior of the Gibson D. Lewis Library located at the above referenced address. Any materials located on the roof and building envelope were not evaluated as part of this survey should be assumed to contain asbestos until testing is performed.

This survey applies only to the materials sampled in the above referenced locations. Any materials located in the building not evaluated as part of this survey should be assumed to contain asbestos until testing is performed.

The survey activities began with a preliminary visual observation of readily accessible portions of the survey area by Apex personnel to identify homogeneous areas of suspect ACM. A homogeneous area consists of building materials, which appear similar throughout in terms of color, texture and date of application. A visual assessment was conducted throughout the areas surveyed. The identification of homogeneous materials was made by visual observations.

Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols.

Each homogeneous area of suspect ACM was physically touched to assess the friability and condition of the materials. A friable material is defined by the EPA as a material which can be crumbled, pulverized or reduced to powder by hand pressure when dry.

The suspect ACM samples collected were obtained by physically removing a small portion of the suspect material using a sharp instrument. Disturbance of adjacent material was kept to a minimum during the sampling program. Appropriately attired inspectors collected bulk samples using wet methods as applicable to reduce the potential for fiber release. Each sample was placed into a separate labeled container, which was then sealed. The sampling instrument was cleaned after each sample was collected. Each sample was placed into a sealable container and labeled with a sample number with an indelible marker.

A total of one hundred ninety (190) samples of suspect ACM were obtained from fifty-nine (59) homogeneous materials. Analyses was conducted utilizing Polarized-Light Microscopy (PLM), following the Environmental Protection Agency (EPA) PLM Method EPA-600/R-93/116. The bulk samples were analyzed by Cates Laboratories located in Dallas, Texas. Cates is accredited by the National Institute of Standards and Technology National Voluntary Laboratory Accreditation Program (NVLAP No. 200569-0) and the TDSHS (License No. 30-0287).

A list of the homogeneous areas/materials sampled as part of this asbestos survey is included in Appendix B.

Apex identified friable and non-friable asbestos containing materials (ACM) within the areas surveyed. The materials identified to contain asbestos are presented in the Asbestos Containing Materials Summary table within Appendix A. It is Apex’s understanding that the areas surveyed are scheduled for renovation/demolition. If any renovation/demolition activities will impact the identified ACMs, the ACMs must be abated prior to the renovation/demolition. The asbestos abatement must be performed by a State of Texas licensed asbestos abatement contractor in accordance with a project design prepared by a State of Texas licensed asbestos consultant. In addition, third party air monitoring must be performed during the abatement. Some category I

Apex project No. 725010720021 Page 3 non-friable materials may be demolished in place with the structure; however, for the purpose of this report, Apex recommends that all ACM be abated prior to demolition.

If the identified ACM is not abated, the materials should be incorporated into the existing management plan.

Apex performed its services in a manner consistent with the level of care and expertise exercised by asbestos professionals performing the same or similar services at the same time and in the same geographic area. No express or implied warranties apply to these services or this report. Due to the limited extent of the assessment and sampling activities at the Site, Apex cannot and does not imply, warranty or guarantee that materials not sampled contain no asbestos. This Asbestos Survey was intended to identify reasonably accessible materials most likely to contain asbestos in quantities subject to regulation. Please note that due to the non-destructive nature of the survey, the potential exists for additional materials to be present in hidden or concealed areas.

All conclusions and recommendations in this report represent the professional opinions of the Apex personnel involved with the project. The results, findings, conclusions and recommendations expressed in this report are based on access provided and conditions observed, and samples taken during Apex survey of the building. The information contained in this report is relevant as of the date on which the field work was performed and should not be relied upon to represent Site’s conditions at a later date. This study and report were prepared on behalf of and for the exclusive use of University of North Texas solely for their use and reliance in determining the presence of asbestos in identified areas of the site. The results of this report are not intended or to be construed as legal interpretation of existing federal, state or local environmental, health and safety laws or regulations. Apex assumes no responsibility or liability for errors in information or data provided to Apex by the Client or any third party or developments resulting from activities or situations outside the scope of this project. This report is not to be used as a bidding document.

Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Apex does not warrant the work of regulatory agencies, laboratories or other third parties supplying information, which may have been used in the preparation of this report. No warranty, express or implied is made.

Apex project No. 725010720021 Page 4

Apex appreciates the opportunity to be of service on this project. If we can be of further assistance, please contact our office at 469-365-1100.

Sincerely yours, Apex TITAN, Inc.

Zurisaday Diego Asbestos Inspector TDSHS Lic. No. 60-3759

Phillip G. Fronczek, CHMM Program Manager Industrial Hygiene Services TDSHS Lic. No. 10-5737

Attachments:

Appendix A: Asbestos Containing Materials Summary Appendix B: Analytical Results/Chain(s) of Custody Appendix C: Figures Appendix D: Previous Report Appendix E: Licenses

Asbestos Containing Materials University of North Texas Health Science Center

Gibson D. Lewis Library (LIB) 955 Montgomery Street

Fort Worth, Texas Apex Project No. 725010720021

Sample No.

ACM

Sample

Description Location

Friable/ Non-

Friable

Asbestos

Assessment Condition Estimated Quantity

2-143 2-144 2-145

Duct Mastic (white)

2nd Floor NF 5% 5 Good Through out

2-182 2-183 2-184

Mastic (black) associated w/Perimeter

Walls

2nd Floor NF 5% 5 Good Through out

3-204 3-205 3-206

Mastic (black) associated w/Perimeter

Walls

3rd Floor NF 5% 5 Good Through out

3-207 3-208 3-209

Duct Mastic (white)

3rd Floor NF 5% 5 Good Through out

4-276 4-277 4-278

Mastic (black) associated w/Perimeter

Walls

4th Floor NF 3% 5 Good Through out

Assumed Materials

N/A

Mastic associated with Raised

Wooden Floor Pedestals

1st Floor NF Assumed 5 Good 250SF

N/A Mirror Mastic 1st, 2nd, 3rd, and

4th Floors NF Assumed 5 Good 400SF

N/A 12” x 12”

Ceramic Floor Tile (Grey)

2nd, 3rd, and 4th Floors

NF Assumed 5 Good 1,800SF

N/A 12” x 16”

Ceramic Wall Tile (White)

2nd, 3rd, and 4th Floors

NF Assumed 5 Good 800SF

N/A

Mastic associated with Corner

Guards

4th Floor NF Assumed 5 Good Through out

Assessment:

1) Damaged or significantly damaged thermal system insulation ACM;

2) Damaged friable surfacing ACM;

3) Significantly damaged friable surfacing ACM;

4) Damaged or significantly damaged friable miscellaneous ACM;

5) ACBM with potential for damage;

6) ACBM with potential for significant damage;

7) Any remaining friable ACBM or friable suspected ACBM

Identified Homogeneous Materials University of North Texas Health Science Center

Gibson D. Lewis Library (LIB) 955 Montgomery Street

Fort Worth, Texas Apex Project No. 725010720021

Material Category Condition ACM Sample Number

First Floor Survey (Apex Project Number 725010720014)

12”x 12” Floor Tile (Pink with Grey Streaks) and Mastic

(Yellow)

Category I Non-friable

G Non-Detected 1-1 1-2 1-3

Mastic (Yellow) associated with Carpet (Dark Green with

Red, and White Stripe Pattern) Multilayer

Category II Non-friable

G Non-Detected 1-4 1-5 1-6

Mastic (Tan) associated with Carpet (Brown with Dark

Brown Stripe Pattern) Multilayer

Category II Non-friable

G Non-Detected 1-7 1-8 1-9

Mastic (Yellow) associated with Carpet (Yellow, with Multicolor Dot Pattern)

Multilayer

Category II Non-friable

G Non-Detected 1-10 1-11 1-12

Mastic (Yellow) associated with Carpet (Dark Yellow with

Multicolor Dot Pattern)

Category II Non-friable

G Non-Detected 1-13 1-14 1-15

Mastic (Yellow) associated with Carpet (Blue with Multicolor Dot Pattern)

Multilayer

Category II Non-friable

G Non-Detected 1-16 1-17 1-18

Mastic (Yellow) associated with Carpet (Light Brown)

Category II Non-friable

G Non-Detected 1-19 1-20 1-21

Mastic (Clear) associated with Carpet (Red) Multilayer

Category II Non-friable

G Non-Detected 1-22 1-23 1-24

Mastic (Yellow) associated with Carpet (Dark Blue with Light Grey Streak Pattern)

Multilayer

Category II Non-friable

G Non-Detected 1-25 1-26 1-27

Mastic (Yellow) associated with Carpet (Brown with Dark

Brown and Grey Stripe Pattern)

Category II Non-friable

G Non-Detected 1-28 1-29 1-30

UNT- Gibson D. Lewis Library (LIB)

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Material Category Condition ACM Sample Number

12” x 12” Ceramic Floor Tile (Light Grey) with Grout (Grey) and Mortar (Grey)

Category I Non-friable

G Non-Detected 1-31 1-32 1-33

Epoxy Floor Coating (Grey, Sandy)

Category II Non-friable

G Non-Detected 1-34 1-35 1-36

Resilient Vinyl Flooring (Grey with Multicolor Stripes) with

Mastic (Yellow) and Leveling Compound (Grey)

Category I Non-friable

G Non-Detected 1-37 1-38 1-39

Resilient Vinyl Flooring (Brown, Wood Pattern) with

Mastic (Yellow)

Category I Non-friable

G Non-Detected 1-40 1-41 1-42

2”x 6” Ceramic Floor Tile (Brown) with Grout (Grey) and

Mortar (Grey)

Category II Non-friable

G Non-Detected 1-43 1-44 1-45

Mastic (Yellow) associated with 4” Cove Base (Black)

Category II Non-friable

G Non-Detected 1-46 1-47 1-48

Mastic (Yellow) associated with Fiberglass Reinforced

Panel (FRP) (White)

Category II Non-friable

G Non-Detected 1-49 1-50 1-51

Concrete Wall Texture (Grey, Sandy)

Category II Non-friable

G Non-Detected

1-52 1-53 1-54 1-55 1-56

CMU Wall Texture (White) with Grout (Grey)

Category II Non-friable

G Non-Detected 1-57 1-58 1-59

Unfinished Drywall/Joint Compound

Category II Non-friable

G Non-Detected 1-60 1-61 1-62

Ceiling/Wall Texture (White, Blue, Tan, Sandy)

Drywall/Joint Compound

Category II Non-friable

G Non-Detected

1-63 1-64 1-65 1-66 1-67 1-68 1-69

12”x 24” Ceramic Wall Tile (White) with Grout (White) and

Thinset (White)

Category II Non-friable

G Non-Detected 1-70 1-71 1-72

Sink Under Coating (Black) Category I Non-friable

G Non-Detected 1-73 1-74 1-75

Interior Building Expansion Joint Caulking (Tan)

Category II Non-friable

G Non-Detected 1-76 1-77 1-78

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Material Category Condition ACM Sample Number

2’x4’ Acoustical Ceiling Tile (White, Pinhole and Fissured)

Category II Non-friable

G Non-Detected 1-79 1-80 1-81

2’x2’ Acoustical Ceiling Tile (White, Rough Finish)

Category II Non-friable

G Non-Detected 1-82 1-83 1-84

Duct Mastic (White) Category I Non-friable

G Non-Detected 1-85 1-86 1-87

Duct Mastic (Grey) Category I Non-friable

G Non-Detected 1-88 1-89 1-90

Thermal System Insulation (White)

Category II Non-friable

G Non-Detected 1-91 1-92 1-93

Second Floor Survey

Mastic (yellow) associated w/Carpet (grey w/blue & green stripe pattern) & Leveling Compound (grey) -

Category I Non-friable

G Non-Detected 2-94 2-95 2-96

Mastic (yellow) associated w/Carpet (green w/yellow, blue & red spot pattern)

Category I Non-friable

G Non-Detected 2-97 2-98 2-99

Mastic (yellow) associated w/Carpet (tan w/green & red dot pattern) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 2-100 2-101 2-102

Mastic (yellow) associated w/Carpet (light grey w/dark grey stripe pattern) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 2-103 2-104 2-105

Resilient Vinyl Flooring (tan wood pattern) & Mastic

(yellow)

Category I Non-friable

G Non-Detected 2-106 2-107 2-108

Resilient Vinyl Flooring (dark brown wood pattern) & Mastic (yellow) & Leveling Compound

(grey)

Category I Non-friable

G Non-Detected 2-109 2-110 2-111

Resilient Vinyl Flooring (light brown wood pattern) & Mastic (yellow) & Leveling Compound

(grey)

Category I Non-friable

G Non-Detected 2-112 2-113 2-114

12" X 12" Floor Tile (pink w/black & white streaks) & Mastic (yellow) & Leveling

Compound (grey)

Category I Non-friable

G Non-Detected 2-115 2-116 2-117

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Material Category Condition ACM Sample Number

4" Cove Base (black) w/Mastic (tan)

Category I Non-friable

G Non-Detected

2-118 2-119 2-120 2-121 2-122 2-123 2-124

Wall/Ceiling Texture (white, semi-smooth) Drywall/Joint

Compound

Category II Non-friable

G Non-Detected 2-125 2-126 2-127

4' X 6' Acoustical Ceiling Tile (light grey, pinhole)

Category II Non-friable

G Non-Detected 2-128 2-129 2-130

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish)

Category II Non-friable

G Non-Detected 2-131 2-132 2-133

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured)

Category II Non-friable

G Non-Detected 2-134 2-135 2-136

2' X 4' Acoustical Ceiling Tile (white, fissured)

Category II Non-friable

G Non-Detected 2-137 2-138 2-139

Duct Mastic (grey) Category I Non-friable

G Non-Detected 2-140 2-141 2-142

Duct Mastic (white) Category I Non-friable

G 5% Chrysotile -

White Mastic

2-143 2-144 2-145

Interior Building Caulking (white) above Ceiling

Category II Non-friable

G Non-Detected 2-146 2-147 2-148

Firestop (red, yellow) Category II Non-friable

G Non-Detected 2-149 2-150 2-151

Thermal System Insulation (white)

Category II Non-friable

G Non-Detected 2-179 2-180 2-181

Mastic (black) associated w/Perimeter Walls

Category I Non-friable

G 10% Chrysotile 2-182 2-183 2-184

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Material Category Condition ACM Sample Number

Third Floor Survey

Mastic (yellow) associated w/Carpet (tan w/blue & red stripe pattern)

Category I Non-friable

G Non-Detected 3-152 3-153 3-154

Mastic (yellow) associated w/Carpet (tan w/yellow & black spot design)

Category I Non-friable

G Non-Detected 3-145 3-156 3-157

Mastic (yellow) associated w/Carpet (red, blue, & tan multi-color pattern) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 3-158 3-159 3-160

Mastic (yellow) associated w/Carpet (grey w/blue & green stripe pattern) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 3-161 3-162 3-163

Resilient Vinyl Flooring (light brown, wood pattern) & Mastic

(brown

Category I Non-friable

G Non-Detected 3-164 3-165 3-166

4" Cove Base (dark grey) w/Mastic (tan) -

Category I Non-friable

G Non-Detected 3-167 3-168 3-169

Sink Undercoating (grey) Category I Non-friable

G Non-Detected 3-170 3-171 3-172

Wall/Ceiling Texture (grey, semi-smooth) Drywall/Joint

Compound

Category II Non-friable

G Non-Detected

3-173 3-174 3-175 3-176 3-177 3-178 3-179

Wall/Ceiling Cover Paper (light purple, rough)

Drywall/Joint Compound

Category II Non-friable

G Non-Detected 3-180 3-181 3-182

Unfinished Drywall/Joint Compound

Category II Non-friable

G Non-Detected 3-183 3-184 3-185

4' X 6' Acoustical Ceiling Tile (light grey, pinhole)

Category II Non-friable

G Non-Detected 3-186 3-187 3-188

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish)

Category II Non-friable

G Non-Detected 3-189 3-190 3-191

Firestop (red) Category II Non-friable

G Non-Detected 3-192 3-193 3-194

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Material Category Condition ACM Samp3e Number

Thermal System Insulation (white)

Category II Non-friable

G Non-Detected 3-195 3-196 3-197

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured)

Category II Non-friable

G Non-Detected 3-198 3-199 3-200

Firestop (grey) Category II Non-friable

G Non-Detected 3-201 3-202 3-203

Mastic (black) associated w/Perimeter Walls

Category I Non-friable

G 5% Chrysotile 3-204 3-205 3-206

Duct Mastic (white) Category I Non-friable

G 20% Chrysotile 3-207 3-208 3-209

Duct Mastic (grey) Category I Non-friable

G Non-Detected 3-210 3-211 3-212

Fireproofing (grey Category II Non-friable

G Non-Detected

3-213 3-214 3-215 3-216 3-217

Fourth Floor Survey

Mastic (red) associated w/Carpet (tan w/multi-color green stripes) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 4-218 4-219 4-220

Mastic (yellow) associated w/Carpet (red, blue, & tan multi-color pattern)

Category I Non-friable

G Non-Detected 4-221 4-222 4-223

Mastic (yellow) associated w/Carpet (tan w/green spot pattern) (stairway, all levels)

Category I Non-friable

G Non-Detected 4-224 4-225 4-226

12" X 12" Floor Tile (grey w/dark grey & white streaks) &

Mastic (yellow) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 4-227 4-228 4-229

12" X 12" Floor Tile (dark blue w/black streaks) & Mastic

(yellow) & Leveling Compound (grey)

Category I Non-friable

G Non-Detected 4-230 4-231 4-232

Resilient Vinyl Flooring (light brown, wood pattern) & Mastic

(yellow)

Category I Non-friable

G Non-Detected 4-233 4-234 4-235

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Material Category Condition ACM Sample Number

4" Cove Base (dark grey) w/Mastic (tan)

Category I Non-friable

G Non-Detected 4-236 4-237 4-238

Sink Undercoating (grey) Category I Non-friable

G Non-Detected 4-239 4-240 4-241

Wall/Ceiling Texture (grey, semi-smooth) Drywall/Joint

Compound

Category II Non-friable

G Non-Detected

4-242 4-243 4-244 4-245 4-246 4-247 4-248

Unfinished Drywall/Joint Compound

Category II Non-friable

G Non-Detected 4-249 4-250 4-251

Firestop (red) Category II Non-friable

G Non-Detected 4-252 4-253 4-254

Firestop (grey) Category II Non-friable

G Non-Detected 4-255 4-256 4-257

4' X 6' Acoustical Ceiling Tile (light grey, pinhole)

Category II Non-friable

G Non-Detected 4-258 4-259 4-260

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish)

Category II Non-friable

G Non-Detected 4-261 4-262 4-263

2' X 4' Acoustical Ceiling Tile (white, fissured)

Category II Non-friable

G Non-Detected 4-264 4-265 4-266

Duct Mastic (grey) Category I Non-friable

G Non-Detected 4-267 4-268 4-269

Duct Mastic (white) Category I Non-friable

G Non-Detected 4-270 4-271 4-272

Thermal System Insulation (white)

Category II Non-friable

G Non-Detected 4-273 4-274 4-275

Mastic (black) associated w/Perimeter Walls

Category II Non-friable

G 5% Chrysotile 4-276 4-277 4-278

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Assumed ACM Materials

First floor Assumed Materials

Mastic associated with Raised Wooden Floor

Pedestals

Category I Non-friable

G Assumed N/A

Mirror Mastic Category I Non-friable

G Assumed N/A

Second Floor Assumed Materials

12”x 12” Ceramic Floor Tile (Grey)

Category II Non-friable

G Assumed N/A

Mirror Mastic Category I Non-friable

G Assumed N/A

12” x 16” Ceramic Wall Tile (White)

Category II Non-friable

G Assumed N/A

Third Floor Assumed Materials

Resilient Vinyl Flooring (Red, Wood Pattern)

Category I Non-friable

G Assumed N/A

12”x 12” Ceramic Floor Tile (Grey)

Category II Non-friable

G Assumed N/A

Mirror Mastic Category I Non-friable

G Assumed N/A

12” x 16” Ceramic Wall Tile (White)

Category II Non-friable

G Assumed N/A

Fourth Floor Assumed Material

Mastic Associated with Corner Guards

Category I Non-friable

G Assumed N/A

12”x 12” Ceramic Floor Tile (Grey)

Category II Non-friable

G Assumed N/A

December 23, 2020

G – Good, D – Damaged, SD – Significantly Damaged

Mirror Mastic Category I Non-friable

G Assumed N/A

12” x 16” Ceramic Wall Tile (White)

Category II Non-friable

G Assumed N/A

PLM REPORT SUMMARY

Cates Laboratories NVLAP Lab No. 200569-0

1339 Motor Circle TDSHS License No. 30-0287

Dallas, Texas 75207 (214) 920-5006

Client: Apex TITAN Lab Job No.: PLM-23736

Project (Line 1): UNT - Gibson Library Floor #2 Set No.: 35092

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 1 of 6

On 8/13/2020, sixty-four (64) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Lab

Sample No.

Client

Field I.D.

Sample Description/Location Asbestos Content

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced except in full.

CL847809

2-94

Mastic (yellow) associated w/Carpet (grey w/blue & green stripe pattern)

& Leveling Compound (grey) - Room 200

None Detected - Yellow Mastic

None Detected - Leveling Compound

CL847810

2-95

& Leveling Compound (grey) - Room 230H

CL847811

2-96

& Leveling Compound (grey) - Room 222G

CL847812

2-97

Mastic (yellow) associated w/Carpet (green w/yellow, blue & red spot pattern) - Room 234

CL847813

2-98 pattern) - Room 230D

CL847814

2-99 pattern) - Room 230A

CL847815

2-100

Mastic (yellow) associated w/Carpet (tan w/green & red dot pattern) &

Leveling Compound (grey) - Room 210

CL847816

2-101

Leveling Compound (grey) - Room 212

CL847817

2-102

Leveling Compound (grey) - Room 208

CL847818

2-103

Mastic (yellow) associated w/Carpet (light grey w/dark grey stripe pattern) & Leveling Compound (grey) - Room 218E

CL847819

2-104 pattern) & Leveling Compound (grey) - Room 218B

CL847820

2-105 pattern) & Leveling Compound (grey) - Room 218D

CL847821

2-106

Resilient Vinyl Flooring (tan wood pattern) & Mastic (yellow) - Room

None Detected - Flooring

CL847822

2-107

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 2 of 6

On 8/13/2020, sixty-four (64) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847823

2-108

CL847824

2-109

Resilient Vinyl Flooring (dark brown wood pattern) & Mastic (yellow) &

Leveling Compound (grey) - Room 218

CL847825

2-110

CL847826

2-111

CL847827

2-112

Resilient Vinyl Flooring (light brown wood pattern) & Mastic (yellow) &

Leveling Compound (grey) - Room 230

CL847828

2-113

Leveling Compound (grey) - Room 222

CL847829

2-114

Leveling Compound (grey) - Room 202

CL847830

2-115

12" X 12" Floor Tile (pink w/black & white streaks) & Mastic (yellow) &

Leveling Compound (grey) - Room 222A

None Detected - Floor Tile

CL847831

2-116

CL847832

2-117

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 3 of 6

On 8/13/2020, sixty-four (64) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847833

2-118

4" Cove Base (black) w/Mastic (tan) - Room 206

None Detected - Cove Base

None Detected - Tan Mastic

CL847834

2-119

4" Cove Base (black) w/Mastic (tan) - Hallway 2L4

CL847835

2-120

4" Cove Base (black) w/Mastic (tan) - Room 222C

CL847836

2-121

Wall/Ceiling Texture (white, semi-smooth) Drywall/Joint Compound -

Room 2L2

None Detected - Paint Texture

None Detected - Joint Tape

None Detected - Joint Compound

None Detected - Paper

None Detected - Wallboard Material

CL847837

2-122

Room 234

None Detected - Joint Compound

CL847838

2-123

Room 222F

None Detected - Joint Compound

CL847839

2-124

Room 220

None Detected - Joint Compound

CL847840

2-125

Room 218E

None Detected - Joint Compound

CL847841

2-126

Room 211

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 4 of 6

On 8/13/2020, sixty-four (64) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847842

2-127

Room 206

CL847843

2-128

4' X 6' Acoustical Ceiling Tile (light grey, pinhole) - Room 200

None Detected

CL847844

2-129

4' X 6' Acoustical Ceiling Tile (light grey, pinhole) - Room 129

CL847845

2-130

4' X 6' Acoustical Ceiling Tile (light grey, pinhole) - Room 200

CL847846

2-131

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish) - Room 222

CL847847

2-132

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish) - Room 202

CL847848

2-133

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish) - Room 2T2

CL847849

2-134

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured) - Room 2L2

CL847850

2-135

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured) - Room 230C

CL847851

2-136

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured) - Room 230

CL847852

2-137

2' X 4' Acoustical Ceiling Tile (white, fissured) - Room 2A

CL847853

2-138

2' X 4' Acoustical Ceiling Tile (white, fissured) - Room 222F

CL847854

2-139

2' X 4' Acoustical Ceiling Tile (white, fissured) - Room 212

CL847855

2-140

Duct Mastic (grey) - Room 204

CL847856

2-141

Duct Mastic (grey) - Room 2ME2

CL847857

2-142

Duct Mastic (grey) - Room 2T1A

CL847858

2-143

Duct Mastic (white) - Room 200

5% Chrysotile - White Mastic

None Detected - Wrap

None Detected - Insulation

CL847859

2-144

Duct Mastic (white) - Room 222

Not Analyzed - Positive Stop

CL847860

2-145

Duct Mastic (white) - Room 204D

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 5 of 6

On 8/13/2020, sixty-four (64) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847861

2-146

Interior Building Caulking (white) above Ceiling - Room 2T1A

CL847862

2-147

Interior Building Caulking (white) above Ceiling - Room 230

CL847863

2-148

Interior Building Caulking (white) above Ceiling - Room 218C

CL847864

2-149

Firestop (red, yellow) - Room 2T1A

CL847865

2-150

Firestop (red, yellow) - Room 206

CL847866

2-151

Firestop (red, yellow) - Room 2ME1

CL847867

2-279

Thermal System Insulation (white) - Room 200

None Detected - White Mastic

CL847868

2-280

Thermal System Insulation (white) - Room 204A

CL847869

2-281

Thermal System Insulation (white) - Room 206

CL847870

2-282

Mastic (black) associated w/Perimeter Walls - Room 207

10% Chrysotile

CL847871

2-283

Mastic (black) associated w/Perimeter Walls - Room 218D

CL847872

2-284

Mastic (black) associated w/Perimeter Walls - Room 220

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 6 of 6

On 8/13/2020, sixty-four (64) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein.

STATEMENT OF LABORATORY ACCREDITATION

The samples were analyzed in general accordance with the procedures outlined in the Method for the

Determination of Asbestos in Bulk Building Materials, EPA/600/R-93/116 or the U.S. Environmental

Protection Agency EPA 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of

Asbestos in Bulk Insulation Samples, by polarized light microscopy. The results of each bulk sample relate only to the material tested and the results shall not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government.

Specific questions concerning bulk sample results shall be directed to the Laboratory Director.

Analyst:

Curtis Grigg

Laboratory Director: John R. Cates, P.G.

Approved Signatory:

NVLAP LAB CODE 200569-0

Project (Line 1): UNT - Gibson Library Set No.: 35093

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 1 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847873

3-152

Mastic (yellow) associated w/Carpet (tan w/blue & red stripe pattern) -

Room 300

CL847874

3-153

Room 302

CL847875

3-154

Room 318

CL847876

3-155

Mastic (yellow) associated w/Carpet (tan w/yellow & black spot design) -

Room 316

CL847877

3-156

Room 306

CL847878

3-157

Room 316

CL847879

3-158

Mastic (yellow) associated w/Carpet (red, blue, & tan multi-color pattern)

& Leveling Compound (grey) - Room 308

CL847880

3-159

CL847881

3-160

CL847882

3-161

& Leveling Compound (grey) - Room 313

CL847883

3-162

& Leveling Compound (grey) - Room 313B

CL847884

3-163

& Leveling Compound (grey) - Room 313A

CL847885

3-164

Resilient Vinyl Flooring (light brown, wood pattern) & Mastic (brown) -

Room 310

None Detected - Sheet Flooring

None Detected - Vapor Barrier

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 2 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847886

3-165

Room 310C

CL847887

3-166

Hallway 3A

CL847888

3-167

4" Cove Base (dark grey) w/Mastic (tan) - Room 300

CL847889

3-168

4" Cove Base (dark grey) w/Mastic (tan) - Room 310G

CL847890

3-169

4" Cove Base (dark grey) w/Mastic (tan) - Room 312

CL847891

3-170

Sink Undercoating (grey) - Room 313A

CL847892

3-171

CL847893

3-172

CL847894

3-173

Wall/Ceiling Texture (grey, semi-smooth) Drywall/Joint Compound -

Room 320

None Detected - Joint Compound

CL847895

3-174

Room 311

CL847896

3-175

Room 313

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 3 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847897

3-176

Room 311A

None Detected - Texture

CL847898

3-177

Room 310

CL847899

3-178

Room 310D

CL847900

3-179

Room 3SC1

CL847901

3-180

Wall/Ceiling Cover Paper (light purple, rough) Drywall/Joint Compound

- Room 300

None Detected - Wall Covering

None Detected - Joint Compound

CL847902

3-181

None Detected - Joint Compound

CL847903

3-182

None Detected - Joint Compound

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 4 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847904

3-183

Unfinished Drywall/Joint Compound - Room 3ME1

CL847905

3-184

Unfinished Drywall/Joint Compound - Room 3ME2

CL847906

3-185

Unfinished Drywall/Joint Compound - Room 3ME2

CL847907

3-186

4' X 6' Acoustical Ceiling Tile (light grey, pinhole) - Room 300

CL847908

3-187

4' X 6' Acoustical Ceiling Tile (light grey, pinhole) - Room 300

CL847909

3-188

4' X 6' Acoustical Ceiling Tile (light grey, pinhole) - Room 306

CL847910

3-189

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish) - Room 319

CL847911

3-190

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish) - Room 312

CL847912

3-191

2' X 2' Acoustical Ceiling Tile (white, pinhole, rough finish) - Restroom

3T1

CL847913

3-192

Firestop (red) - Room 3ME1

CL847914

3-193

Firestop (red) - Room 3ME2

CL847915

3-194

Firestop (red) - Room 3ME2

CL847916

3-195

Thermal System Insulation (white) - Room 3ME2

CL847917

3-196

Thermal System Insulation (white) - Room 300

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 5 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847918

3-197

Thermal System Insulation (white) - Room 300

CL847919

3-198

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured) - Room 313

CL847920

3-199

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured) - Room 313AA

CL847921

3-200

2' X 4' Acoustical Ceiling Tile (white, pinhole & fissured) - Room 310

CL847922

3-201

Firestop (grey) - Room 3ME1

CL847923

3-202

Firestop (grey) - Room 3ME2

CL847924

3-203

Firestop (grey) - Room 3ME2

CL847925

3-204

Mastic (black) associated w/Perimeter Walls - Room 300

5% Chrysotile

CL847926

3-205

Mastic (black) associated w/Perimeter Walls - Room 312A

CL847927

3-206

Mastic (black) associated w/Perimeter Walls - Room 310B

CL847928

3-207

Duct Mastic (white) - Room 300

20% Chrysotile

CL847929

3-208

Duct Mastic (white) - Room 300

CL847930

3-209

Duct Mastic (white) - Room 320

CL847931

3-210

Duct Mastic (grey) - Room 300

CL847932

3-211

Duct Mastic (grey) - Room 300

CL847933

3-212

Duct Mastic (grey) - Room 311

CL847934

3-213

Fireproofing (grey) - Room 300

CL847935

3-214

CL847936

3-215

CL847937

3-216

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 6 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847938

3-217

Project (Line 2): Report Date: 8/14/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 7 of 7

On 8/13/2020, sixty-six (66) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Protection Agency EPA 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of

Asbestos in Bulk Insulation Samples, by polarized light microscopy. The results of each bulk sample relate only to the material tested and the results shall not be used by the client to claim product certification, approval, Kathy Schosek

Project (Line 1): UNT - Gibson Library Floor #4 Set No.: 35094

Project (Line 2): Report Date: 8/17/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 1 of 6

On 8/13/2020, sixty-one (61) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847939

4-218

Mastic (red) associated w/Carpet (tan w/multi-color green stripes) &

Leveling Compound (grey) - Room 470

CL847940

4-219

Leveling Compound (grey) - Room 450

CL847941

4-220

Leveling Compound (grey) - Hallway 4L1

CL847942

4-221

- Room 404

CL847943

4-222

- Room 404

CL847944

4-223

- Room 405

CL847945

4-224

Mastic (yellow) associated w/Carpet (tan w/green spot pattern) (stairway, all levels) - Stairway 4S4

CL847946

4-225 all levels) - Stairway 3S4

CL847947

4-226 all levels) - Stairway 2S4

CL847948

4-227

12" X 12" Floor Tile (grey w/dark grey & white streaks) & Mastic

(yellow) & Leveling Compound (grey) - Room 450A

CL847949

4-228

CL847950

4-229

CL847951

4-230

12" X 12" Floor Tile (dark blue w/black streaks) & Mastic (yellow) &

Leveling Compound (grey) - Room 410

CL847952

4-231

Project (Line 2): Report Date: 8/17/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 2 of 6

On 8/13/2020, sixty-one (61) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847953

4-232

CL847954

4-233

Resilient Vinyl Flooring (light brown, wood pattern) & Mastic (yellow) -

Room 401

CL847955

4-234

Room 400

CL847956

4-235

Room 454

CL847957

4-236

4" Cove Base (dark grey) w/Mastic (tan) - by Room 470

CL847958

4-237

4" Cove Base (dark grey) w/Mastic (tan) - by Room 4T1

CL847959

4-238

4" Cove Base (dark grey) w/Mastic (tan) - Room 448

CL847960

4-239

Sink Undercoating (grey) - Room 401

CL847961

4-240

CL847962

4-241

CL847963

4-242

Room 470

None Detected - Joint Compound

Project (Line 2): Report Date: 8/17/2020

Project No: 725010720021 Sample Date: Not Provided

Identification: Asbestos, Bulk Sample Analysis

Test Method: Polarized Light Microscopy/Dispersion Staining (PLM/DS)

EPA Method 600/R-93/116 Page 3 of 6

On 8/13/2020, sixty-one (61) bulk samples were submitted by Mr. Edgar Roque of Apex TITAN for asbestos analysis by PLM/DS.

Copies of the lab data sheets are attached; additional information may be found therein. The results are summarized below:

Client

These samples were analyzed by layers. The overall percent asbestos for the sample is reported when relevant. The EPA considers a material to be asbestos containing only if it contains greater than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing

Materials (RACM) – materials that are friable or may become friable – be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. CatesLab utilizes CVAE on a routine basis and does not include point counting unless specifically requested by the client. The results may not be reproduced

CL847964

4-243

Room 460

None Detected - Joint Compound

CL847965

4-244

Room 428

None Detected - Joint Compound

CL847966

4-245

Room 401

None Detected - Joint Compound

CL847967

4…