ESBD_363502_1722290655181_Attachment H3 - Updates to Project Drawings per Addendum No. 3.pdf

PDF 704 KB Posted

Attached to
Project 20-104-ABL-B Generator Replacement at Abilene SSLC
Solicitation number
HHS0014827
Issued by
Taylor County, Abilene City, Texas

About this file

This document is an addendum to a state contract opportunity released by the Abilene State Supported Living Center in Texas. The addendum updates the project drawings for the Generator Replacement Phase B project, including changes to electrical schedules, panel schedules, and transformer details. The $4.68 million project requires furnishing all labor, materials, and equipment for generator replacement at the Abilene State Supported Living Center. Key deadlines include a mandatory site visit on June 26 or June 27, 2024, proposal submission by July 16, 2024, and an anticipated contract start date in September 2024.

The project specifications indicate the use of step-up and step-down transformers, as well as new electrical distribution panels to support the generator replacements across multiple buildings. The electrical work includes updating panel schedules and adding new transformers and panels to replace existing infrastructure. Pricing and funding details are not provided in this addendum, but the overall project estimate is $4.68 million.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NO. 20-104-ABL

GENERATOR REPLACEMENT PHASE B

ABILENE STATE SUPPORTED LIVING CENTER

ABILENE, TEXAS

FAI PROJECT NO. 202201800

FAI ENGINEERS

P.O. BOX 362

JOSHUA, TEXAS 76058

TEXAS REGISTERED ENGINEERING FIRM F-298

DATE: July 29, 2024

ADDENDUM NO. 3

ITEM NO. 1: Sheet E40.02; Electrical Schedule: Generator Schedule (diesel); Generator Number 11 should read 240 volt/1 phase.

ITEM NO. 2: Sheet E1.01; Floor Plan – Bldg. 596-Elec Demo: Existing kitchen panel noted by Note by Symbol 13 is an overhead service.

ITEM NO. 3: Sheet E2.06, E5.06, E7.02: IPC #3-1, IPC #6-1 and #9-1 shall be deleted and replaced with new step-down transformers “T-3:, “T-4” and “T-5” and new electrical distribution panels “EDP-3A”, “EDP-6A” and “EDP-9”. Refer to partial schematic diagrams on 8 ½ x 11 sheets EAD.01, EAD.02 and EAD.03 dated 7/26/24 attached and included as part of this Addendum.

ITEM NO. 4: Sheet E5.06; One Line Schematic Diagram -Gen #6; Note by Symbol 6: Change voltage “480v/3⊘” to read “208v/3⊘”

ITEM NO. 5: Sheet E6.02; Floor Plan – Bldg 597-Elec:

1. Note by Symbol 23 shown on conduit between power pole and electrical equipment rack should be labeled Note by Symbol 24.

2. Note by Symbol 24 shown in Room 170 should be labeled as Note by Symbol 25.

3. Note by Symbol 25 shown in Room 169 should be labeled as Note by Symbol 26.

ITEM NO. 6: Sheet E40.01; Electrical Schedule:

1. Revised Panel Schedules EDP-3 Gen #3 and EDP-6 Gen #6 are attached and included as part of this Addendum.

2. New Panel Schedules EDP-3A Gen #3, EDP-6A Gen. #6, EDP-9 Bldg 652 and Transformer Schedule are attached and included as part of this Addendum.

EAD.01

SHEET NO.

DRAWN BY: MAA

DESIGNED BY: LWA

PROJ. No: 202001800

DATE: 7-26-2024GENERATOR REPLACEMENT Pro. No. 20-104-ABL

ABILENE STATE SUPPORTED LIVING CENTER ABILENE, TEXAS

FAI - 2024C

P.O. Box 362 Joshua, Texas 76058

(817) 360-2900

AutoCAD SHX Text

CHILLER PANEL 400A B666

AutoCAD SHX Text 480V/3 400A

AutoCAD SHX Text

ATS 666 480V/3

AutoCAD SHX Text 480V/3 451A

AutoCAD SHX Text

NP

AutoCAD SHX Text 480V/3

AutoCAD SHX Text

STEP-UP XFMR 375 KVA "T-1"

AutoCAD SHX Text

EP

AutoCAD SHX Text 208V/3 1000A

AutoCAD SHX Text

208V TO 480V 375 KVA

AutoCAD SHX Text 480V/3

AutoCAD SHX Text

NP

AutoCAD SHX Text

TO BLDGS. 208V/3

AutoCAD SHX Text

J-BOX

AutoCAD SHX Text 208V/3 2081A

AutoCAD SHX Text 480V/3 900A

AutoCAD SHX Text

EDP-3

AutoCAD SHX Text

GEN #3 208V/3

AutoCAD SHX Text

TO BLDGS. 208V/3

AutoCAD SHX Text

480V TO 208V 750 KVA "T-3" STEP-DOWN XFMR

AutoCAD SHX Text

GEN #3 - B633, B634, B635, B636, B666B633, B634, B635, B636, B666

AutoCAD SHX Text 633-636 (208V/3 )666 (480V/3 )

AutoCAD SHX Text

REPLACES IPC 3-1

AutoCAD SHX Text

EDP-3A 208V/3 2000A

EAD.02

DRAWN BY: MAA

DESIGNED BY: LWA

PROJ. No: 202001800

DATE: 7-26-2024GENERATOR REPLACEMENT Pro. No. 20-104-ABL

ABILENE STATE SUPPORTED LIVING CENTER ABILENE TEXAS

FAI - 2024C

P.O. Box 362 Joshua, Texas 76058

(817) 360-2900

AutoCAD SHX Text

CHILLER PANEL 400A B667

AutoCAD SHX Text 480V/3 400A

AutoCAD SHX Text

ATS 667 480V/3 400A

AutoCAD SHX Text 480V/3 451A

AutoCAD SHX Text

NP

AutoCAD SHX Text 480V/3

AutoCAD SHX Text

STEP-UP XFMR 375 KVA "T-2"

AutoCAD SHX Text

EP

AutoCAD SHX Text 208V/3 1000A

AutoCAD SHX Text

208V TO 480V 375 KVA

AutoCAD SHX Text 480V/3

AutoCAD SHX Text

NP

AutoCAD SHX Text

TO BLDGS. 208V/3

AutoCAD SHX Text

J-BOX

AutoCAD SHX Text 208V/3 2081A

AutoCAD SHX Text 480V/3 900A

AutoCAD SHX Text

EDP-6

AutoCAD SHX Text

GEN #6 208V/3

AutoCAD SHX Text

TO BLDGS. 208V/3

AutoCAD SHX Text

480V TO 208V/3 750 KVA STEP-DOWN XFMR "T-4"

AutoCAD SHX Text

GEN #6 - B637, B638, B639, B640, B667B637, B638, B639, B640, B667

AutoCAD SHX Text 637-640 (208V/3 )667 (480V/3 )

AutoCAD SHX Text

REPLACES IPC 6-1

AutoCAD SHX Text

EDP-6A 208V/3 2000A

EP

EAD.03

DRAWN BY: MAA

DESIGNED BY: LWA

PROJ. No: 202001800

DATE: 7-26-2024GENERATOR REPLACEMENT Pro. No. 20-104-ABL

ABILENE STATE SUPPORTED LIVING CENTER ABILENE, TEXAS

FAI - 2024C

P.O. Box 362 Joshua, Texas 76058

(817) 360-2900

AutoCAD SHX Text

GEN #9 - B652B652

AutoCAD SHX Text

REPLACES IPC 9-1

AutoCAD SHX Text

EDP-9 208V/3 1600A

AutoCAD SHX Text

NP/EP

AutoCAD SHX Text

J-BOX

AutoCAD SHX Text 480V/3 600A

AutoCAD SHX Text 480V/3

AutoCAD SHX Text

CHILLER PANEL 225A

AutoCAD SHX Text

TO BLDG PANELS

AutoCAD SHX Text 208V/3 1387A

AutoCAD SHX Text 480V/3

AutoCAD SHX Text

FROM DISCONNECT

480V TO 208V/3 STEP-DOWN XFMR "T-5", 500 KVA

CKT

# DESCRIPTION

LOAD

KVA

BKR

POLES

FRAME

AMPS TRIP AMPS

EDP-3 GEN.#3 CKT BKR TYPE

V (L-L) 208 PHASE 3 MLO

V (L-N) 120 WIRE 4

MLO (A) 2500 SECTION

SURFACE MOUNTED

65,000 A.I.C

CKT LOAD BKR FRAME TRIP

# DESCRIPTION (KVA) POLES AMPS AMPS

1 BLDG 633 145 3 800 800

4 BLDG 634 145 3 800 800

7 BLDG 635 145 3 800 800

10 BLDG 636 145 3 800 800

13 BLDG 666 173 3 1000 1000

CONN. N.E.C.

LOAD MULT.

(KVA) (KVA)

LIGHTING 40 50

MOTOR 116 141

HEATING 75 94 CONNECTED

KITCHEN 320 320 2091 LOAD (AMPS)

RECEPTACLE 100 55 2116 NEC MULT.(AMPS)

MISCELLANEOUS 30 30 9 PERCENT SPARE

SPARE 72 72 1.00 KIT. MULTIPLIER

TOTAL 753 762 1.00 MISC. MULTIPLIER

LOAD

KVA

EDP-3A GEN.#3 CKT BKR TYPE

V (L-L) 208 PHASE 3 MLO

V (L-N) 120 WIRE 4

MLO (A) 2000 SECTION

SURFACE MOUNTED

65,000 A.I.C

CKT LOAD BKR FRAME TRIP

# DESCRIPTION (KVA) POLES AMPS AMPS

1 BLDG 633 145 3 800 800

4 BLDG 634 145 3 800 800

7 BLDG 635 145 3 800 800

10 BLDG 636 145 3 800 800

CONN. N.E.C.

LOAD MULT.

(KVA) (KVA)

LIGHTING 32 40

MOTOR 16 17

HEATING 60 75 CONNECTED

KITCHEN 320 320 1611 LOAD (AMPS)

RECEPTACLE 80 45 1581 NEC MULT.(AMPS)

MISCELLANEOUS 20 20 9 PERCENT SPARE

SPARE 52 52 1.00 KIT. MULTIPLIER

TOTAL 580 569 1.00 MISC. MULTIPLIER

LOAD

KVA

EDP-6 GEN.#6 CKT BKR TYPE

V (L-L) 208 PHASE 3 MLO

V (L-N) 120 WIRE 4

MLO (A) 2500 SECTION

SURFACE MOUNTED

65,000 A.I.C

CKT LOAD BKR FRAME TRIP

# DESCRIPTION (KVA) POLES AMPS AMPS

1 BLDG 637 135 3 600 600

4 BLDG 638 165 3 800 800

7 BLDG 639 165 3 800 800

10 BLDG 640 165 3 800 800

13 BLDG 667 156 3 1000 1000

CONN. N.E.C.

LOAD MULT.

(KVA) (KVA)

LIGHTING 40 50

MOTOR 106 129

HEATING 85 106 CONNECTED

KITCHEN 380 380 2183 LOAD (AMPS)

RECEPTACLE 80 45 2235 NEC MULT.(AMPS)

MISCELLANEOUS 30 30 8 PERCENT SPARE

SPARE 65 65 1.00 KIT. MULTIPLIER

TOTAL 786 805 1.00 MISC. MULTIPLIER

LOAD

KVA

EDP-6A GEN.#6 CKT BKR TYPE

V (L-L) 208 PHASE 3 MLO

V (L-N) 120 WIRE 4

MLO (A) 2000 SECTION

SURFACE MOUNTED

65,000 A.I.C

CKT LOAD BKR FRAME TRIP

# DESCRIPTION (KVA) POLES AMPS AMPS

1 BLDG 637 135 3 600 600

4 BLDG 638 165 3 800 800

7 BLDG 639 165 3 800 800

10 BLDG 640 165 3 800 800

CONN. N.E.C.

LOAD MULT.

(KVA) (KVA)

LIGHTING 32 40

MOTOR 16 17

HEATING 70 88 CONNECTED

KITCHEN 380 380 1750 LOAD (AMPS)

RECEPTACLE 60 35 1754 NEC MULT.(AMPS)

MISCELLANEOUS 20 20 8 PERCENT SPARE

SPARE 52 52 1.00 KIT. MULTIPLIER

TOTAL 630 632 1.00 MISC. MULTIPLIER

LOAD

KVA

EDP-9 - BLDG. 652 CKT BKR TYPE

V (L-L) 208 PHASE 3 MLO

V (L-N) 120 WIRE 4

MLO (A) 1600 SECTION

SURFACE MOUNTED

65,000 A.I.C

CKT LOAD BKR FRAME TRIP

# DESCRIPTION (KVA) POLES AMPS AMPS

1 MDP-652-1 150 3 600 600

4 MDP-652-2 150 3 600 600

7 Panel N 40 3 225 150

CONN. N.E.C.

LOAD MULT.

(KVA) (KVA)

LIGHTING

MOTOR

HEATING CONNECTED

KITCHEN 944 LOAD (AMPS)

RECEPTACLE 944 NEC MULT.(AMPS)

MISCELLANEOUS 340 340 PERCENT SPARE

SPARE 1.00 KIT. MULTIPLIER

TOTAL 340 340 1.00 MISC. MULTIPLIER

TRANSFORMER SCHEDULE

NUMBER KVA PRIMARY SECONDARY PHASE REMARKS

T-1 375 208 480 3 Step-up

T-2 375 208 480 3 Step-up

T-3 750 480 208 3 Step-down

T-4 750 480 208 3 Step-down

T-5 500 480 208 3 Step-down

3. Dry-type transformers shall be ANSI/NEMA ST20: factory-assembled, air cooled dry type transformers; ratings as shown.

4. Enclosure shall be ANSI/NEMA ST20; Type 3R. Provide lifting eyes on brackets.

NOTES:

1. Submit manufacturer's data on dry-type transformers, vibratiion isolators and accessories.

2. Include outline and support point dimensions of enclosures and accessories; unit weight; voltage; KVA; impendence ratings and characteristics; loss data; efficiency at 25, 50, 75 and 100 percent rates load; sound leve; tap configurations; insulation system type and rated temperature rise.

5. Name plate on transformer shall include transformer connection data and overload capacity based on rated allowable temperature rise.

6. Installer shall examine the areas and conditions under which dry-type transformers are to be installed and notify A/E in writing of conditions detrimental to the proper and timeply completion of the work. Do not proced with the work until unsatisfactory conditions have been corrected.

7. Use liquid-tight flexible conduit, 2 ft. minimum length, for connections to transformer case.

Sheets and Views
EAD-01-EAD.01
EAD-02-EAD.02
EAD-03-EAD.03
ADPF1AF.tmp
SWBD
ADP7B24.tmp
SWBD
ADPF846.tmp
SWBD
ADP3466.tmp
SWBD
ADPD878.tmp
SWBD
ADP1890.tmp
TRANS