ESBD_363502_1721661117716_Attachment H1 - Revised Project Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- HHS0014827
- Issued by
- Taylor County, Abilene City, Texas
About this file
This document is a state and local contract opportunity for the Generator Replacement Project at the Abilene State Supported Living Center in Texas. The project scope includes furnishing all labor, materials, and equipment for the generator replacement work. The overall project is estimated to cost $4,680,000. Key dates include a mandatory site visit on June 26 or June 27, the proposal due date of July 16, and the anticipated contract start date of September 2024.
The pricing and funding details are not provided in the document. No information is given about set asides, incumbents, or specific funding sources and amounts. The document indicates this is a standalone state and local contract opportunity, rather than part of a larger contract or program.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
ENGINEERS, INC.
PO Box 362, 2504 CR 911
Joshua, TX 76058 817..360..2900 faiengineers.net
PROJECT NO. 20-104-ABL
ABILENE SSLC – ABILENE, TX
GENERATOR REPLACEMENT – PHASE B
ADDENDUM DATED 7/22/2024
CONSTRUCTION DOCUMENTS
The following sheets are revised and included as part of this Addendum:
Sheets E2.03, E2.04, E2.06 Sheets E3.00, E3.01, E3.02, E3.03 Sheets E4.00, E4.01, E4.02 Sheets E5.00, E5.01, E5.02, E5.03, E5.04, E5.06 Sheet E7.01 Sheet E8.02 Sheet E9.00 Sheet E10.01 Sheet E11.02 Sheet E12.02 Sheet E13.01 Sheet E20.03 Sheet E30.01 Sheets E31.01, E31.02, E31.03, E31.04, E31.05 E31.06, E31.07 Sheet E40.01
The above sheets correspond to the answers to the Contractors questions as attached and included as Part of this Addendum.
GENERATOR REPLACEMENT
PROJECT No. 20-104-ABL
PHASE B
ABILENE STATE SUPPORTED LIVING CENTER
TEXAS HEALTH AND HUMAN SERVICES COMMISSION
LOCATION PLAN (ABILENE, TX) VICINITY MAP
FOR
Project Directory
HHSC Maintenance and Construction:
Texas Health and Human Services Commission P.O. Box 12668 Mail Code 2064 Austin, TX 78711-2668 (909 W. 45th Street, Bldg. 633, Austin, TX 78751)
(512) 206-5911
Austin
Renu Razdan - Director Roger Brigance - Senior Director of Construction Services
(512) 206-5204
Project Manager Jason Staggs Project Manager Facility Maintenance and Construction Austin, TX 78751
(830) 777-4283
Facility Plant Maintenance Manager Kenny Day Plant Manager 2501 Maple Street Abilene State Supported Living Center Abilene, TX 79602
(325) 795-3582
Engineer Larry W. Akers, LEED Green Associate FAI Engineers, Inc.
2504 CR 911, P.O. Box 362 Joshua, TX 76058
(817) 296-8167
AutoCAD SHX Text www.faiengineers.net
SET NO.
DATE: APRIL 15, 2024
PROJECT NO. 202001800
TEXAS BOARD OF PROFESSIONAL ENGINEERS F-298
MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION
FOR CONSTRUCTION
NORTH
NOT TO SCALE
ABILENE, TEXAS
JOB SITE
202001800
APRIL 15, 2024
STATUS:
SHEET NO.
PROJECT NO:
DRAWN BY:
DESIGN BY:
DATE:
SHEET TITLE:
CHECKED BY:
REVISIONS
FAI - 2023C
LWA
w
.fa ie ng in ee rs .n et
TE
X A
S
BO
R
D O
F
PR
FE
SS
IO
N
L
EN
G
IN
EE
F-
M
EC
H
IC
EL
TR
PL
U
BI
IR
E
CT
LE
ST
PP
IV
C
EA
LT
ER
V
ES
IS
SI
TO
EP
LA
CE
T
JE
o.
0-
4-
BL
PH
SE
B
MAA
G.1
GENERAL SITE PLAN
1 GENERAL SITE PLAN
GENERAL NOTES
NOTES BY SYMBOL
1 ST STREET
2 ND STREET
3 RD STREET
3 RD STREET
4 TH STREET
5 TH STREET
6 TH STREET
7 TH STREET
7 TH STREET
24 TH STREET
24 TH STREET
MAPLE STREET
PLUM AVENUE
SERVICE AVENUE
WALNUT AVENUE
PALM AVENUE
LAKESIDE DRIVE
SERVICE AVENUE
PLUM AVENUE
8TH STREET
PARTIAL PLAN
ENCHANTED BARN
MEGA UNIT
OFFICES
GUEST
HOUSE
STORAGE
GUEST
RED STORAGE
BARN
BARN/
RESIDENCE
LA 5962
S/A 5961
SEWING/
REIMBURSEMENT
WATER HEATER
ACTIVITY
CENTER
WATER HEATER
MAINTENANCE
HAZMAT
BIG BLUE
MOTOR POOL
WELDING SHOP
FLAMMABLE
CARPENTRY
SHOP
LUMBER
TETC #3
TETC #2
QUONSET
BLDG
TETC #1
MATERIALS
LA 6350
LA 6330
CHILL H20 #1
LA 6360
ACTIVITY CENTER
CAIN PAVILION
CHAPEL
FOOD SVC
CENTRAL KITCHEN
H20 HEATER
LAUNDRY
EDITION ST
SUNSHINE INN
RECREATION
SPEECH/AUDIOLOGY
HRD/SCHOOL
COMMUNITY
RELATIONS
HOUSEKEEPING
UTILITY BLDG
GOLFCART
SHED
LA 6400
LA 6390
LA 6380
LA 5971/
S/A 5972
CHILL H20 #2
TEAM,TV,STORAGE
ORTHOTIC STORAGE
IS/ORTHOTICS
H20 HEATER
SWIMMING POOL
ENCLOSURE
PRINTER
REPAIR
CHILL H20 #3
RECREATION
GARAGE
CONFERENCE
ORTHOTICS
GREENHOUSE
LA 6370
LA 6500
OT/PT CENTER
LA 6510
FLAMMABLE
COTTAGE
COTTAGE 6740
COTTAGE 6750
COTTAGE 6760
BEEHIVE
COTTAGE 6730
TRAINING
LA 6450 S/A
LA 6460 T/A
SHIRLEY'S CINEMA
LA 6480 S/A
ADMINISTRATION
INFIRMARY
FUELING STATION
AB2
AB1
AHJ COMM. 4/25/24
SCALE: 1"=140'-0"
1) All work is new unless otherwise indicated to be All work is new unless otherwise indicated to be "existing" or "reused" or "relocated". 2) Where new work is applicable to patient/client living, Where new work is applicable to patient/client living, use, or support areas; Contractor shall obtain an approved Infection Control Permit prior to initiating actual work. Permit application shall be initiated with his mobilization submittal. (See UGCs/SGCs Article 7.8.) 3) Existing underground utility locations shown are Existing underground utility locations shown are approximate. Contractor shall field verify exact locations prior to excavation or trenching. Contractor shall HAND DIG within 5 feet either side of potential utility conflicts/interferences until the utility is physically exposed prior to performing mechanical trenching or excavating. 4) Contractor shall field verify by measurement exact Contractor shall field verify by measurement exact locations depicted and all dimensions. 5) Prospective bidders are highly encouraged to attend Prospective bidders are highly encouraged to attend the scheduled pre-bid site visit to thoroughly familiarize themselves with any and all existing site and project location conditions which may affect the work under this contract. The Owner and Engineer will not be responsible for Contractor errors or omissions which could be made reasonably known by attending a scheduled site visit. 6) The plans indicate the extent and general requirements The plans indicate the extent and general requirements of the demolition, alterations, relocations, and additions. If any departures from the drawings are deemed necessary by the Contractor, details of such departures and the reasons therefore shall be submitted as soon as possible to the Engineer and Owner for action. No such departures shall be made without prior approval of the Engineer and Owner. 7) Every effort has been made to clearly and fully depict Every effort has been made to clearly and fully depict all known existing conditions and items requiring removal, relocation, demolition and/or alteration. Due to the small scale of the drawings and the nature of renovation and rehab work, certain items such as those concealed behind equipment, finishes, or structural members and the like; or those not accessible for inspection or identifiable as abandoned or to be abandoned without destruction; may not be specifically and/or separately defined or shown. The Contractor shall provide all required removal, relocation, demolition, and/or alteration of such items reasonably inherent with such renovation and rehabilitation work at no additional cost to the Owner in accordance with the best commercial practices and these contract documents to provide a complete and useable facility within the scope of the work to be performed. No consideration shall be given to the nature of the materials, and all demolition shall be designated as unclassified demolition. Demolition of every description and of whatever substances encountered shall be performed to the degree required for the installation of the items/finishes required herein or as specified. 8) Wherever the word(s) "provide", "furnish", "install" Wherever the word(s) "provide", "furnish", "install" and/or the like is/are used; it is to be defined as and understood to require that the Contractor shall provide the item/system(s) totally and completely furnished, installed, and fully operable and useable for its/their intended purpose(s) unless specifically noted otherwise in the contract documents.
NOTES APPLY TO ALL SHEETS
LEGEND
BUILDINGS IN PROJECT GENERATOR NUMBER ALTERNATE BID #1 ALTERNATE BID #2
AB1
EXISTING GENERATOR SHALL BE REMOVED AND REPLACED WITH NEW GENERATOR. NUMBER AS INDICATED. EXISTING GENERATOR SHALL REMAIN. NO WORK UNDER THIS PROJECT. NEW GENERATOR SHALL BE INSTALLED. NUMBER AS INDICATED. EXISTING GENERATOR SHALL BE SALVAGED AND TURNED OVER TO FACILITY AT LOCATION AS DIRECTED BY FACILITY. GENERATORS TO BE SALVAGED: #4, 5, 6, 7, 9 AND 12. EXISTING GENERATOR #12 SHALL BE REMOVED, AND RELOCATED UNDER ADD ALT. #1. BECOMES GEN #17.
AB2
E.0
SHEET INDEX
DESIGN CRITERIA
A. MECHANICAL DESIGN CRITERIA: MECHANICAL DESIGN CRITERIA: 1. DESIGN TEMPERATURE CONDITIONS: DESIGN TEMPERATURE CONDITIONS: A. OUTSIDE OUTSIDE SUMMER 105 F 105°FWINTER 22 F 22°FB. INSIDE INSIDE SUMMER 75 F 75°FWINTER 70 F 70°F2. TYPE OF SYSTEM: TYPE OF SYSTEM: A. HVAC: N/A HVAC: N/A N/A B. VENTILATION: N/A VENTILATION: N/A N/A C. EXHAUST: N/A EXHAUST: N/A N/A D. LIGHTING LOWAD BASIS: N/A LIGHTING LOWAD BASIS: N/A N/A E. AIR: N/A AIR: N/A N/A F. TOTAL COOLING CAPACITY : N/A TOTAL COOLING CAPACITY : N/A : N/A N/A G. TOTAL HEATING CAPACITY: N/A TOTAL HEATING CAPACITY: N/A N/A H. REQUIRED EER: N/A REQUIRED EER: N/A N/A
B. ELECTRICAL DESIGN CRITERIA: ELECTRICAL DESIGN CRITERIA: 1. SYSTEM DESCRIPTION BASED ON EXISTING IN EACH BUILDING. SYSTEM DESCRIPTION BASED ON EXISTING IN EACH BUILDING. A. SERVICE: 208-120V/3 (EXISTING) SERVICE: 208-120V/3 (EXISTING) 208-120V/3 (EXISTING)B. SERVICE: 240V/3 (EXISTING) SERVICE: 240V/3 (EXISTING) 240V/3 (EXISTING)C. SERVICE: 480V/3 (EXISTING) SERVICE: 480V/3 (EXISTING) 480V/3 (EXISTING)C. CODES: CODES: 1. BUILDING CODE: 2012 INTERNATIONAL BUILDING CODE BUILDING CODE: 2012 INTERNATIONAL BUILDING CODE 2012 INTERNATIONAL BUILDING CODE 2. MECHANICAL CODE: 2012 INTERNATIONAL MECHANICAL CODE MECHANICAL CODE: 2012 INTERNATIONAL MECHANICAL CODE 2012 INTERNATIONAL MECHANICAL CODE 3. PLUMBING CODE: 2012 INTERNATIONAL PLUMBING CODE PLUMBING CODE: 2012 INTERNATIONAL PLUMBING CODE 2012 INTERNATIONAL PLUMBING CODE 4. ELECTRICAL CODE: 2011 NATIONAL ELECTRIC CODE ELECTRICAL CODE: 2011 NATIONAL ELECTRIC CODE 2011 NATIONAL ELECTRIC CODE 5. ENERGY CODE: 2012 INTERNATIONAL ENERGY CONSERVATION CODE ENERGY CODE: 2012 INTERNATIONAL ENERGY CONSERVATION CODE 2012 INTERNATIONAL ENERGY CONSERVATION CODE 6. FIRE CODE: 2012 INTERNATIONAL FIRE CODE FIRE CODE: 2012 INTERNATIONAL FIRE CODE 2012 INTERNATIONAL FIRE CODE 7. LIFE SAFETY 2012 LIFE SAFETY CODE LIFE SAFETY 2012 LIFE SAFETY CODE 2012 LIFE SAFETY CODE 8. NFPA 110 2010 EMERGENCY AND STANDBY POWER SYSTEMS NFPA 110 2010 EMERGENCY AND STANDBY POWER SYSTEMS 2010 EMERGENCY AND STANDBY POWER SYSTEMS
Sheet List Table
Sheet Number
Sheet Title
COVER
G.1
GENERAL SITE PLAN
E.0
SHEET INDEX
E.1
SYMBOLS AND GENERAL NOTES
E.2
BUILDING MATRIX EXISTING AND NEW
Sheet List Table
Sheet Number
Sheet Title
ELECTRICAL
E1.01
FLOOR PLAN - BLDG.596 - ELEC - DEMO
E1.02
FLOOR PLAN - BLDG.596 - ELEC.
E2.00
PARTIAL SITE PLAN - GENERATOR
E2.01
FLOOR PLAN - BLDG.633 - ELEC.
E2.02
FLOOR PLAN - BLDG.634 - ELEC.
E2.03
FLOOR PLAN - BLDG.635 - ELEC.
E2.04
FLOOR PLAN - BLDG.636 - ELEC.
E2.05
ONE LINE ELECTRICAL SCHEMATIC DIAGRAM (BLDG. 633,634,635 & 636)
E2.06
ONE LINE ELECTRICAL SCHEMATIC DIAGRAM (BLDG.633, 634, 635 & 636)
E3.00
E3.01
FLOOR PLAN - BLDG.645 - ELEC.
E3.02
FLOOR PLAN - BLDG.646 - ELEC.
E3.03
FLOOR PLAN - BLDG. 648 - ELEC.
E4.00
PARTIAL SITE PLAN - GENERATOR 5 - ELEC.
E4.01
FLOOR PLAN - BLDG. 650 - ELEC.
E4.02
FLOOR PLAN - BLDG.651 - ELEC.
E5.00
E5.01
FLOOR PLAN - BLDG.637 - ELEC.
E5.02
FLOOR PLAN - BLDG.638 - ELEC.
E5.03
FLOOR PLAN - BLDG.639 - ELEC.
E5.04
FLOOR PLAN - BLDG.640 - ELEC.
E5.05
ONE LINE ELECTRICAL SCHEMATIC DIAGRAM (BLDG.637,633,639 AND 640)
E5.06
ONE LINE ELECTRICAL SCHEMATIC DIAGRAM (BLDG.637,633,639 AND 640)
E6.01
FLOOR PLAN - BLDG.597 - ELEC. - DEMO
E6.02
FLOOR PLAN - BLDG.597 - ELEC.
E7.01
FLOOR PLAN - BLDG.652 - ELEC. - DEMO
E7.02
FLOOR PLAN - BLDG.652 - ELEC.
E8.01
FLOOR PLAN - BLDG.659 - ELEC. - DEMO
E8.02
FLOOR PLAN - BLDG.659 - ELEC.
E9.00
E9.01
FLOOR PLAN - BLDG.669 & 670 - ELEC.
E9.02
FLOOR PLAN - BLDG.671 & 672 - ELEC.
E9.03
FLOOR PLAN - BLDG.673 & 674 - ELEC.
E9.04
FLOOR PLAN - BLDG.675 & 676 - ELEC.
E10.01
FLOOR PLAN - BLDG.547 - ELEC.
E11.01
FLOOR PLAN - BLDG.656 - ELEC. - DEMO
E11.02
FLOOR PLAN - BLDG. 656 - ELEC.
E12.01
FLOOR PLAN - BLDG.641 - ELEC. - DEMO
E12.02
FLOOR PLAN - BLDG. 641 - ELEC.
E13.01
FLOOR PLAN - BLDG.665 - ELEC.
E20.01
ELECTRICAL DETAILS
E20.02
ELECTRICAL DETAILS
E20.03
SPECIAL DETAILS
E30.01
E30.02
E30.03
E30.04
PARTIAL SITE PLAN - GENERATOR - BLDG. 664
E31.01
ELECTRICAL SCHEMATIC DIAGRAMS
E31.02
E31.03
E31.04
E31.05
E31.06
E31.07
E40.01
ELECTRICAL SCHEDULES
E40.02
ELECTRICAL SCHEDULES
ELECTRICAL SYMBOLSSTANDARD ABBREVIATIONSGENERAL NOTES (TYPICAL FOR ALL SHEETS)GENERAL NOTES (TYPICAL FOR ALL SHEETS)
E.1
SYMBOLS AND
DUPLEX RECEPTACLE
THREE WAY SWITCH
FOUR WAY SWITCH
KEY SWITCH
DIMMER
PUSH BUTTON
K
3K
THREE WAY KEY SWITCH
WALL SPEAKER
CLOCK OUTLET ONLY
DISCONNECT SWITCH
J
FOUR WAY KEY SWITCH
4K
SWITCH WITH PILOT LIGHT
P
SINGLE RECEPTACLE
SINGLE FACE CLOCK
DOUBLE FACE CLOCK
BELL
BUZZER
HORN
SMOKE DETECTOR
THERMAL DETECTOR
MOTOR CIRCUIT SWITCH
MP
MOTOR
INTERCOM OUTLET
AUDIO VISUAL OUTLET
AUDIO OUTLET
A.F.F.
WP
ABOVE FINISHED FLOOR
WEATHERPROOF
G.F.I.
ALL SYMBOLS SHOWN IN SYMBOL LIST ARE NOT NECESSARILY USED.
I
AV
PHOTOCELL
BLANK PLATE
FLUORESCENT LIGHT FIXTURE LETTER DENOTES TYPE
RECESSED LIGHT FIXTURE LETTER DENOTES TYPE
SURFACE MOUNTED LIGHT FIXTURE, LETTER DENOTES TYPE
WALL MOUNTED LIGHT FIXTURE - LETTER DENOTES TYPE
EXIT LIGHT - ARROW AS INDICATED
LIGHT FIXTURE EQUIPPED WITH EMERGENCY BALLAST
JUNCTION BOX
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT CONCEALED IN, OR BELOW FLOOR - SEE SPECS
CONDUIT EXPOSED, PARALLEL TO BUILDING LINES
CONDUIT HOMERUN
CONDUIT STUBBED UP
CONDUIT STUBBED DOWN
LIQUID TIGHT FLEXIBLE CONDUIT UNLESS NOTED OTHERWISE
SINGLE POLE SWITCH
TWO POLE SWITCH
SURFACE FLOOR DUPLEX RECEPTACLE
MULTI-OUTLET ASSEMBLY - SEE SPECS
SPECIAL PURPOSE OUTLET
QUADRAPLEX RECEPTACLE
WALL TELEPHONE OUTLET
SURFACE FLOOR DATA/TELEPHONE OUTLET
FLUSH FLOOR DATA/TELEPHONE OUTLET
WALL COMPUTER TERMINAL
SURFACE FLOOR COMPUTER TERMINAL
FLUSH FLOOR COMPUTER TERMINAL
WALL MICROPHONE OUTLET
FLOOR MOUNTED MICROPHONE OUTLET
WALL TELEVISION OUTLET
WALL VOLUME CONTROL
RECESSED CEILING SPEAKER
FIRE ALARM PULL STATION
FIRE ALARM AUDIBLE/VISUAL WARNING DEVICE
FIRE ALARM WARNING BELL (WEATHERPROOF)
FIRE ALARM WARNING LIGHT
SMOKE DETECTOR IN DUCT
MOTOR CIRCUIT SWITCH WITH PILOT LIGHT
MOTOR CONTROLLER OR STARTER
GROUND FAULT INTERRUPTER
FLUSH FLOOR AUDIO OUTLET
EXPLOSION PROOF SEAL
OCCUPANCY SENSOR SWITCH
OS
CEILING FAN
NURSE CALL
LIGHT POLE
FLOOD LIGHT
WALL WASH
TRACK LIGHT
STRIP LIGHT
SC
CEILING MOTION SENSOR
WALL MOTION SENSOR
CAMERA
CAMERA (CEILING MOUNTED)
FC
FAN CONTROL
FLUSH FLOOR DUPLEX RECEPTACLE
DUPLEX GFI RECEPTACLE
DATA / TELEPHONE
COAX
DESCRIPTION
SYMBOL
DESCRIPTION
ABOVE FINISHED FLOOR
AFF
INCLOSURE
INC
ABOVE
ABV
INDICATE
IND
ACOUSTICAL LINING
AL
INSIDE DIAMETER
ID
AIR CONDITIONING
AC
JUNCTION BOX
J-BOX
ALTERNATE
ALT
KILOVOLT-AMPERES
KVA
ALUMINUM
AL
KILOWATT-HOUR
KWH
AMPERE
AMP
KILOWATTS
KW
AMPS
LAVATORY
LAV
ANGLE VAVLE
ANV
LENGTH
LG
ANNUNCIATOR
ANNUN
LIGHT
APPROXIMATE
APPROX
LOCATE
LOC
ARCHITECT
ARCH
MINIMUM CIRCUIT AMPACITY
MCA
ASSEMBLE
ASSEM
MAIN CIRCUIT BREAKER
MCB
AT
MAIN LUGS ONLY
MLO
AUTOMATIC TRANSFER SWTICH
ATS
MAIN DISTRIBUTION PANEL
MDP
AUTOMATIC
AUTO
MAINTENANCE
MAINT
AUTOMATIC AIR VENT
AAV
MANUFACTURE
MFR
AUXILIARY
AUX
MANUFACTURED
MFD
AMPERE INTERRUPTING CAPACITY
AIC
MANUFACTURING
MFG
BALANCE
BAL
MAXIMUM
MAX
BASEMENT
BSMT
MAX. OVERCURR. PROT. DEVICE
MOPD
BELOW
BEL
MECHANICAL
MECH
BETWEEN
BET
METAL
MET
BOTTOM
BOT
MISCELLANEOUS
MISC
BRAKE HORSEPOWER
BHP
MOTOR
MOT
BREAKER
BKR
MOUNTED
MTD
BRITISH THERMAL UNIT
BTU
NATIONAL ELECTRICAL CODE
NEC
BUILDING
BLDG
NTS
BUTTERFLY VALVE
BFU
NUMBER
NO
CAPACITY
CAP
OFFICE
OFF
CAST IRON
CI
ON CENTER
OC
CEILING
CLG
OPPOSITE
OPP
CENTERLINE
CL
OUTSIDE DIAMETER
OD
CIRCUIT
CKT
PIPE ANCHOR
PA
CLEANOUT PLUG
CO
PIPE GUIDE
PG
COMBUSTION
COMB
PLUGGED TEE
PT
CONCENTRIC REDUCER
CR
PLUMBING
PLBG
CONCRETE
CONC
POLE
CONDUIT
POUNDS PER SQ. IN.
PSI
CONNECT
CONN
PREFABRICATED
PREFAB
CONSTRUCTION
CONST
PRESSURE REDUCER VALVE
PRV
CONTRACTOR
CONT
PRESSURE RELIEF VALVE
PV
DEIONIZED WATER
DE
PRESSURE
PRESS
DELTA
Δ
PRESSURE SWITCH
PS
DETAIL
DET
PB
DIAGRAM
DIAG
REINFORCE
REINF
DIAMETER
DIA
REMOVE
REM
DISCHARGE
DISCH
REQUIRED
REQ'D
DISTILLED WATER
DI
REQUIREMENT
REQM'TS
DOWN
DN
RETURN
RET
DRAIN
REVOLUTIONS PER MINUTE
RPM
DRAWING
DWG
ROOM
RM
EACH
SCHEDULE
SCH
ECCENTRIC REDUCER
SCHEMATIC
SCHEM
ELECTRIC WATER COOLER
EWC
SHEET
SHT
ELECTRICAL
ELECT
SINGLE PHASE
ELECTRICAL CONTRACTOR
SINGLE POLE DOUBLE THROW
SPDT
ELEVATION
ELEV
SPECIFICATIONS
SPEC'S
EMERGENCY
EMERG
SQUARE
SQ
ENGINEER
ENGR
STANDARD
STD
EQUIPMENT
EQUIPT
STEEL
STL
EXHAUST
EXH
STRAINER
STR
EXISTING
EXIST
STRUCTURAL
STRUCT
EXPANSION JOINT
EJ
SURFACE
SURF
EXPLOSION PROOF
EXP PRO
SWITCH
SW
EXTERNAL
EXT
SWITCHBOARD
SWBD
FEET
FT
SYM
FINISH
FIN
SYSTEM
SYS
FIRE DEPARTMENT CONNECTION
FDC
TELEPHONE
TELE
FIRE HOSE CABINET
FHC
THERMOMETER
TH
FIRE HOSE RACK
FHR
THICK
THK
FIRE HYDRANT
FH
TRANSFORMER
XFMR
FLOOR
FLR
TYPICAL
TYP
FLOOR CLEANOUT
FCO
UNDERGROUND
UG
FLOW SWITCH
FS
UNION
UN
FULL LOAD AMPS
FLA
VACUUM
VAC
GALVANIZE
GALV
VALVE
VAL
GATE VALVE
GV
VOLTS
GENERATOR
GEN
WALL CLEANOUT
WCO
GLOBE VALVE
GLV
WATT
W
GRADE
GR
WEATHERPROOF
WP
GROUND
GRD
WITH
W/
HEATING
HTG
WITHOUT
W/O
HIGH PRESSURE
HP
Sheet Metal
SM
HORIZONTAL
HORIZ
HORESPOWER
HP
HOSE BIBB
HB
CONSTRUCTION: 1. COMPLETE INSTALLATIONS SHALL CONFORM TO ALL COMPLETE INSTALLATIONS SHALL CONFORM TO ALL APPLICABLE FEDERAL CODES, STATE CODES AND LOCAL ORDINANCES. 2. COMPLETE INSTALLATIONS SHALL CONFORM TO THE COMPLETE INSTALLATIONS SHALL CONFORM TO THE CONTRACT DOCUMENTS, SPECIFICATIONS AND ADDENDUMS ISSUED. IF ANY CONFLICTS OCCUR, THE MOST STRINGENT SHALL APPLY. 3. ALL WORK SHALL BE DONE IN AN ACCEPTABLE ALL WORK SHALL BE DONE IN AN ACCEPTABLE WORKMANSHIP MANNER USING THE MOST CURRENT ACCEPTABLE INDUSTRY STANDARDS. 4. EXISTING UTILITY LAYOUTS SHOWN ARE BASED ON EXISTING UTILITY LAYOUTS SHOWN ARE BASED ON EXISTING ORIGINAL CONSTRUCTION DOCUMENTS AND MAY OR MAY NOT REFLECT THE ACTUAL EXACT LOCATIONS OF ROUTINGS. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ON CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ON JOBSITE THE ACTUAL ROUTINGS, ELEVATIONS, SIZES, MATERIALS, ETC. ON JOBSITE. 6. ANY ROUTINGS FOR NEW WORK SHALL BE VERIFIED ON ANY ROUTINGS FOR NEW WORK SHALL BE VERIFIED ON JOBSITE WITH EXISTING CONDITIONS PRIOR TO STARTING ANY DEMOLITION OR NEW CONSTRUCTION WORK. 7. CONTRACTOR SHALL FIELD VERIFY ACTUAL CONDITIONS CONTRACTOR SHALL FIELD VERIFY ACTUAL CONDITIONS ON JOBSITE AS ACTUAL CONDITIONS MAY VARY BETWEEN BUILDINGS, AND IT SHALL BE THE CONTRACTOR RESPONSIBILITY TO MAKE MINOR ADJUSTMENTS NECESSARY TO COMPLETE THE INSTALLATION OF THE WORK. IF EXISTING CONDITIONS PROHIBIT WORK, CONTRACTOR SHALL NOTIFY THE A/E FOR REDIRECTION AS REQUIRED. 8. CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH DO CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH DO REGARD TO REQUIRED MAINTENANCE ACCESS INCLUDING BUT NOT LIMITED TO PANELS, ELECTRICAL J-BOX CONNECTIONS, CONTROLS, VALVES, COILS, FILTERS, MOTORS, ETC. 9. MOUNT ALL BUILDING ANNUNICATOR PANELS. AT 48" MOUNT ALL BUILDING ANNUNICATOR PANELS. AT 48" ABOVE FINISH FLOOR TO CENTER LINE OR TO OTHER DIMENSIONS AS REQUIRED FOR HANDICAP MOUNTING REQUIREMENTS. 10. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY TRANSITIONS OFF-SETS FOR PROPER CONNECTIONS. CONTRACTOR SHALL REFER TO MANUFACTURERS EQUIPMENT SUBMITTALS FOR ALL CONNECTION SIZES. 11. DEMOLITION: CONTRACTOR SHALL FULLY COORDINATE ALL DEMOLITION: CONTRACTOR SHALL FULLY COORDINATE ALL CONTRACTOR SHALL FULLY COORDINATE ALL DEMOLITION ON JOBSITE WITH EXISTING CONDITIONS AND OTHER TRADES TO VERIFY EXACTLY WHAT IS BEING REMOVED. REMOVAL OF ANY WORK NOT REQUIRED SHALL BECOME THE CONTRACTOR'S RESPONSIBILITY TO RE-INSTALL AS REQUIRED FOR PROPER OPERATION OF SYSTEMS. 12. SITE SECURITY: CONTRACTOR SHALL BE RESPONSIBLE SITE SECURITY: CONTRACTOR SHALL BE RESPONSIBLE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A PORTABLE 8' TALL CHAIN LINK FENCE AROUND THE BUILDING DURING THE TIME THE CONTRACTOR HAS POSSESSION OF THE BUILDING. ALL GATES SHALL BE SECURED WITH A LOCK. A SET OF KEYS FOR CONTRACTOR'S LOCKS HALL BE PROVIDED TO THE FACILITY IN CASE THE FACILITY HAS TO HAVE ACCESS TO THE BUILDING WHEN THE CONTRACTOR IS NOT ON SITE. 13. FIRE PROTECTION: CONTRACTOR SHALL MAINTAIN AND FIRE PROTECTION: CONTRACTOR SHALL MAINTAIN AND CONTRACTOR SHALL MAINTAIN AND MAKE SURE FIRE SPRINKLERS AND FIRE ALARM ARE KEPT IN OPERATION AS MUCH AS POSSIBLE. ANY DOWNTIME OF THESE SYSTEMS SHALL BE FULLY COORDINATED WITH THE FACILITY AND FIRE DEPARTMENT IF REQUIRED. 14. HVAC: CONTRACTOR SHALL MAINTAIN HEATING TO THE HVAC: CONTRACTOR SHALL MAINTAIN HEATING TO THE CONTRACTOR SHALL MAINTAIN HEATING TO THE BUILDING AT ALL TIMES DURING PERIODS OF COLD WEATHER FOR FREEZE PROTECTION. CONTRACTOR SHALL PROVIDE PORTABLE HEATERS TO MAINTAIN A MINIMUM OF 50°F INSIDE THE BUILDING.15. POWER: CONTRACTOR SHALL MAINTAIN BUILDING POWER POWER: CONTRACTOR SHALL MAINTAIN BUILDING POWER CONTRACTOR SHALL MAINTAIN BUILDING POWER UNLESS THE BUILDING MAIN POWER HAS TO BE SHUT OFF. IF BUILDING POWER HAS TO BE SHUT OFF, FACILITY SHALL BE NOTIFIED TWO (2) WEEKS IN ADVANCE OF THE SHUT-DOWN. 16. WATER: WATER USAGE SHALL ONLY BE USED AS WATER: WATER USAGE SHALL ONLY BE USED AS WATER USAGE SHALL ONLY BE USED AS REQUIRED FOR CONSTRUCTION. 17. ALL DEMOLITION MATERIALS SHALL BE PLACED IN A ALL DEMOLITION MATERIALS SHALL BE PLACED IN A DUMPSTER AS REMOVED AND NOT STORED IN THE CONSTRUCTION FENCE AREA UNLESS NECESSARY WHILE WAITING REMOVAL. 18. CONDUITS TO BE REMOVED SHALL BE REMOVED BACK CONDUITS TO BE REMOVED SHALL BE REMOVED BACK TO JOINT, EQUIPMENT CONNECTION, ETC. EXACT POINT OF TERMINATION SHALL BE VERIFIED ON JOBSITE. 19. CONDUIT HANGERS SHALL BE NEW OR IF APPROVED CONDUIT HANGERS SHALL BE NEW OR IF APPROVED THE EXISTING HANGERS CAN BE REUSED. IF REUSED THE CONTRACTOR SHALL CLEAN OFF ANY RUST, PAINTED WITH A RUST INHIBITOR, AND THEN PAINTED WITH COLD GALVANIZED PAINT. 20. ANY MATERIALS THAT HAVE TO BE REMOVED TO MAKE ANY MATERIALS THAT HAVE TO BE REMOVED TO MAKE ROOM FOR NEW EQUIPMENT SHALL BE STORED AND PROTECTED FOR RE-INSTALLATION. ANY MATERIALS DAMAGED SHALL BE REPLACED AT CONTRACTORS EXPENSE. 21. ALL NEW CONTROL CONDUIT SHALL BE SECURELY ALL NEW CONTROL CONDUIT SHALL BE SECURELY MOUNTED AT PROPER INTERVALS TO PREVENT SAGGING. 22. ALL NEW PENETRATIONS LOCATIONS SHALL BE VERIFIED ALL NEW PENETRATIONS LOCATIONS SHALL BE VERIFIED ON JOBSITE WITH EXISTING STRUCTURAL CONDITIONS. 23. ANY ROOF PENETRATIONS SHALL BE COORDINATED WITH ANY ROOF PENETRATIONS SHALL BE COORDINATED WITH FACILITY WITH REGARD TO ANY ROOF WARRANTY THAT MAY BE IN PLACE. IF THE ROOF IS STILL UNDER WARRANTY, ROOF PATCHING SHALL BE AS PER ROOFING MANUFACTURERS RECOMMENDATION AND REQUIREMENTS OR AS INDICATED AND DETAILED. 24. WHEN NEW EQUIPMENT CONCRETE PADS ARE FORMED WHEN NEW EQUIPMENT CONCRETE PADS ARE FORMED AND POURED, CONTRACTOR SHALL ALLOW FOR NOTCHING OF CONCRETE PAD TO MISS ANY EXISTING CONDITIONS. CONTRACTOR SHALL VERIFY REQUIREMENTS ON JOBSITE. 25. CONTROL CONTRACTOR SHALL MAINTAIN BAS CONTROL CONTRACTOR SHALL MAINTAIN BAS COMMUNICATION CAMPUS LOOP DURING PERIODS WHEN BUILDINGS ARE UNDER CONSTRUCTION. 26. CONTRACTOR SHALL COVER AND/OR PROTECT ALL THE CONTRACTOR SHALL COVER AND/OR PROTECT ALL THE EXISTING EQUIPMENT, PANELS, ETC. DURING CONSTRUCTION. 27. ALL CONSTRUCTION OPENINGS SHALL BE CLOSED OFF ALL CONSTRUCTION OPENINGS SHALL BE CLOSED OFF AT THE END OF EACH WORK DAY. 28. ANY "HOT WORK" SHALL BE COORDINATED THRU THE ANY "HOT WORK" SHALL BE COORDINATED THRU THE FACILITY RISK MANAGEMENT GROUP AS REQUIRED FOR PERMITTING. 29. REMOVAL OF ALL EXISTING DETECTORS OR ANY OTHER REMOVAL OF ALL EXISTING DETECTORS OR ANY OTHER DEVICES DIRECTLY CONNECTED TO THE BUILDING FIRE ALARM SYSTEM SHALL BE COORDINATED WITH THE FACILITY TO ADDRESS POINTS SHUTDOWN UNTIL RECONNECTION. 30. ANY NEW EQUIPMENT SHALL BE STORED IN THE ANY NEW EQUIPMENT SHALL BE STORED IN THE CONTRACTOR'S STORAGE AREA AND BE PROTECTED FROM WEATHER CONDITIONS OR STORED IN CONNEX STORAGE CONTAINERS. 31. THE CONTROL CONTRACTOR SHALL BE FULLY THE CONTROL CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR MAINTAINING CONTROLS TO ALL BUILDING THAT ARE NOT INCLUDED IN THIS PROJECT. 32. CONTRACTOR IS RESPONSIBLE FOR VERIFYING EXACT CONTRACTOR IS RESPONSIBLE FOR VERIFYING EXACT LOCATION OF EXISTING UNDERGROUND UTILITIES IN ALL AREAS OF NEW ROUTINGS OF ELECTRICAL CONDUITS, ETC. 33. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING ALL AREAS DISTURBED BY INSTALLATION OF ANY UNDERGROUND ELECTRICAL CONDUITS, WIRING, ETC. SEE SHEET E20.03 FOR TYPICAL PATCHING AND INSTALLATION DETAILS FOR CONCRETE, ASPHALT AREAS, ETC. 34. IT IS ACCEPTABLE TO INSTALL NEW UNDERGROUND IT IS ACCEPTABLE TO INSTALL NEW UNDERGROUND CONDUITS, ETC, BY BORING UNDERGROUND IF IT IS MORE ECONOMICAL TO DO SO. 35. ALL SALVAGED GENERATORS SHALL BE REMOVED BY ALL SALVAGED GENERATORS SHALL BE REMOVED BY CONTRACTOR AND TURNED OVER TO OWNER. DELIVER TO LOCATION ON CAMPUS AS DIRECTED BY FACILITY. 36. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING NEW PANEL ID TAGS AND NEW PANEL INDEX SHEET LOGS ON AND IN ALL PANELS INVOLVED ON THIS PROJECT. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
NOTE: THESE NOTES FOR ALL SHEETS. REFER TO EACH SHEETS FOR ADDITIONAL GENERAL NOTES THAT RELATE TO THOSE SHEETS. THESE NOTES FOR ALL SHEETS. REFER TO EACH SHEETS FOR ADDITIONAL GENERAL NOTES THAT RELATE TO THOSE SHEETS.
GENERAL ELECTRICAL NOTES: 1. PROVIDE LABOR MATERIALS, EQUIPMENT AND PROVIDE LABOR MATERIALS, EQUIPMENT AND TRANSPORTATION TO RECEIVE, INSTALL, ADJUST, AND PUT INTO OPERATION COMPLETE ELECTRICAL SYSTEMS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. PROVIDE PRODUCTS NOT MENTIONED BUT OBVIOUSLY NECESSARY AND INCIDENTAL TO THE COMPLETION OF THIS WORK. 2. ALL WORK DONE SHALL BE PERFORMED BY QUALIFIED ALL WORK DONE SHALL BE PERFORMED BY QUALIFIED ELECTRICIANS, UNDER THE SUPERVISION AND DIRECTION OF A SUPERINTENDENT HAVING SUCCESSFUL EXPERIENCE INSTALLING AND SUPERVISING EQUIPMENT AND SYSTEMS OF SIMILAR TYPE AND SIZE AS INDICATED BY CONTRACT DOCUMENTS. 3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH CURRENT RULES, REGULATIONS, AND INDUSTRY STANDARDS OF THE NATIONAL ELECTRICAL CODE, UL, NEMA, NFPA, OSHA, NATIONAL ELECTRICAL SAFETY CODE, AND ANY LOCAL CODES, LAWS, OR ORDINANCES. IN THE EVENT THAT A DISCREPANCY IS FOUND IN THE CONTRACT DOCUMENTS, THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY. 4. EXAMINE AND BECOME FAMILIAR WITH ALL CONTRACT EXAMINE AND BECOME FAMILIAR WITH ALL CONTRACT DOCUMENTS IN THEIR ENTIRETY. SURVEY THE PROJECT AND BECOME FAMILIAR WITH CONDITIONS AND SCOPE OF WORK. 5. COORDINATE WORK WITH ALL OTHER TRADES. GIVE COORDINATE WORK WITH ALL OTHER TRADES. GIVE SPECIAL CONSIDERATION TO COORDINATING INSTALLATION. VERIFY EXACT LOCATION, AND FINISH OF DEVICES WITH A/E OR OWNER REPRESENTATIVE PRIOR TO INSTALLATION. 6. ALL PRODUCTS SHALL BE U.L. LISTED AND INSTALLED IN ALL PRODUCTS SHALL BE U.L. LISTED AND INSTALLED IN ACCORDANCE WITH NATIONALLY RECOGNIZED AND ACCEPTED STANDARDS AND PROCEDURES. 7. ALL ELECTRICAL DISTRIBUTION EQUIPMENT, TRANSFORMERS, ALL ELECTRICAL DISTRIBUTION EQUIPMENT, TRANSFORMERS, PANELBOARDS, AND OTHER ENCLOSED EQUIPMENT SHALL BE IDENTIFIED AS INDICATED ON THE CONTRACT DRAWINGS. SAID IDENTIFICATION SHALL CONSIST OF PERMANENTLY ATTACHED ENGRAVED LAMINATED PLASTIC NAMEPLATES. EACH BRANCH CIRCUIT OVERCURRENT PROTECTION DEVICE SHALL BE IDENTIFIED BY CIRCUIT NUMBER. EACH BRANCH CIRCUIT SPLICE OR TERMINATION SHALL BE IDENTIFIED BY PANEL AND CIRCUIT DESIGNATION SHOWN ON THE JUNCTION OR OUTLET BOX, OR UPON INDIVIDUAL WIRES IN CASES WHERE MORE THAN ONE OF EACH PHASE CONDUCTOR OCCURS. 8. REFERENCE ELECTRICAL SPECIFICATIONS FOR DEVICES, REFERENCE ELECTRICAL SPECIFICATIONS FOR DEVICES, MATERIALS AND WORKMANSHIP REQUIREMENTS NOT SPECIFIED ON THESE DRAWINGS. 9. "RECORD" DRAWINGS SHALL INCLUDE ALL BRANCH CIRCUIT "RECORD" DRAWINGS SHALL INCLUDE ALL BRANCH CIRCUIT WORK, ANY PANELBOARD INFORMATION AVAILABLE, FINAL SWITCHING, ETC. 10. ELECTRONIC COPIES WILL BE ACCEPTABLE IN LIEU OF ELECTRONIC COPIES WILL BE ACCEPTABLE IN LIEU OF "HARD COPIES". 11. ELECTRICAL PLAN DRAWINGS ARE DIAGRAMMATIC; ELECTRICAL PLAN DRAWINGS ARE DIAGRAMMATIC; THEREFORE, DO NOT SCALE FROM THESE DRAWINGS. 12. REFER TO DRAWINGS FOR GUIDANCE AND VERIFICATION OF REFER TO DRAWINGS FOR GUIDANCE AND VERIFICATION OF DIMENSIONS. 13. INSTALL LIGHTING FIXTURES AS INDICATED ON ELECTRICAL INSTALL LIGHTING FIXTURES AS INDICATED ON ELECTRICAL PLANS. 14. PENETRATIONS OF WALLS, FLOORS AND ROOF FOR THE PENETRATIONS OF WALLS, FLOORS AND ROOF FOR THE PASSAGE OF ELECTRICAL RACEWAYS TO BE APPROVED. ALL SUCH PENETRATIONS TO BE PROPERLY SEALED AFTER INSTALLATION OF RACEWAYS SO AS TO MAINTAIN THE STRUCTURAL, WATERPROOF AND FIREPROOF INTEGRITY OF THE WALL, FLOOR OR ROOF SYSTEM TO BE PENETRATED. 15. CONNECT EMERGENCY LIGHTS AS INDICATED. CONNECT EMERGENCY LIGHTS AS INDICATED. 16. ALL EQUIPMENT REQUIRING STARTERS OR COMBO ALL EQUIPMENT REQUIRING STARTERS OR COMBO STARTER/ DISCONNECTS SHALL BE PROVIDED AS COORDINATED. 17. ALL CONDUCTORS ARE TO BE COPPER U.N.O. ALL CONDUCTORS ARE TO BE COPPER U.N.O. 18. CONDUCTORS, RACEWAYS AND CABLES, IN EXPOSED AND CONDUCTORS, RACEWAYS AND CABLES, IN EXPOSED AND CONCEALED LOCATIONS, MUST BE PROTECTED AGAINST PHYSICAL DAMAGE. 19. MAINTAIN DEDICATED WORKING SPACE CLEARANCE FOR MAINTAIN DEDICATED WORKING SPACE CLEARANCE FOR ELECTRICAL EQUIPMENT, PER NEC 110.26.
LIGHTING: 1. ALL HOME RUNS SHOWN ARE (2) #12 & #12 GND ALL HOME RUNS SHOWN ARE (2) #12 & #12 GND IN 1/2" C. UNLESS OTHERWISE NOTED. HOME RUNS OVER 100 FT IN LENGTH TO THE LAST FIXTURE SHALL BE (2) #10 & #12 GND IN 1/2" C. 2. REFERENCE ELECTRICAL DETAIL SHEET(S) FOR REFERENCE ELECTRICAL DETAIL SHEET(S) FOR SCHEDULES, ELECTRICAL SYMBOLS, ETC.
SPECIAL SYSTEM/FIRE ALARM GENERAL NOTES: 1. INSTALLATION SHALL CONFORM TO ALL REQUIREMENTS OF INSTALLATION SHALL CONFORM TO ALL REQUIREMENTS OF APPLICABLE ELECTRICAL CODES. 2. WIRING METHODS AND MATERIALS SHALL CONFORM WITH WIRING METHODS AND MATERIALS SHALL CONFORM WITH ALL APPLICABLE SECTION OF NEC 760. 3. 120 VAC @ 60Hz INPUT POWER SHALL BE INSTALLED BY 120 VAC @ 60Hz INPUT POWER SHALL BE INSTALLED BY LICENSE ELECTRICAL CONTRACTOR. 4. ALL SLEEVES AND PENETRATION AND FIRE CAULKING ALL SLEEVES AND PENETRATION AND FIRE CAULKING SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR. 5. DEDICATED LOCKING BREAKER PROPERLY LABELED DEDICATED LOCKING BREAKER PROPERLY LABELED SOURCE SHALL SUPPLY FIRE ALARM CONTROL(S). 6. 120 VAC IS NOT PERMITTED IN THE SAME RACEWAY AS 120 VAC IS NOT PERMITTED IN THE SAME RACEWAY AS LOW VOLTAGE WIRING. 7. FIRE ALARM CONTRACTOR SHALL REFER TO ELECTRICAL FIRE ALARM CONTRACTOR SHALL REFER TO ELECTRICAL SHEETS AND MECHANICAL FOR EXTENT OF FIRE ALARM WORK. 8. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN. ANY THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN. ANY NEW DEVICES ETC. SHALL BE MATCHING DEVICES TO FULLY INTEGRATE WITH THE EXISTING SYSTEM. 9. THE EXISTING FIRE ALARM ANNUNCIATOR PANEL SHALL BE THE EXISTING FIRE ALARM ANNUNCIATOR PANEL SHALL BE REMOVED IN EACH BUILDING INVOLVED WITH THIS PROJECT AND REPLACED WITH NEW ANNUNICATOR PANEL AND WIRING. 10. ALL INITIATING CIRCUIT SHALL BE CLASS "A" WIRING WITH ALL INITIATING CIRCUIT SHALL BE CLASS "A" WIRING WITH A MINIMUM OF (6) SIX FOOT SEPARATION.
NOTE: THESE NOTES FOR ALL SHEETS. REFER TO EACH SHEETS FOR ADDITIONAL GENERAL NOTES THAT RELATE TO THOSE SHEETS. THESE NOTES FOR ALL SHEETS. REFER TO EACH SHEETS FOR ADDITIONAL GENERAL NOTES THAT RELATE TO THOSE SHEETS.
POWER: 1. ALL HOME RUNS SHOWN ARE (2) #12 & #12 GND ALL HOME RUNS SHOWN ARE (2) #12 & #12 GND IN 1/2" C. UNLESS OTHERWISE NOTED. HOME RUNS OVER 100 FT IN LENGTH TO THE LAST FIXTURE SHALL BE (2) #10 & #12 GND IN 1/2" C. 2. REFERENCE ELECTRICAL DETAIL SHEET(S) FOR REFERENCE ELECTRICAL DETAIL SHEET(S) FOR PANELBOARD SCHEDULES, ELECTRICAL RISER DIAGRAM, SYMBOLS, ETC.
CONNECT TO EXISTING
NORMAL POWER
EMERGENCY POWER
NP
E.2
BUILDING MATRIX
EXISTING AND NEW
SEE SHEET E40.02 FOR GENERATOR SCHEDULE
NOTE::
E1.01
FLOOR PLAN -
BLDG.596 - ELEC -
DEMO1 FLOOR PLAN - BLDG.596 - ELEC - DEMO
BUILDING 596
GENERATOR #1
145A
P101
P102
P104
P103
123A
147A
158A
UE
16'
32'
48'
1/16" = 1'-0"
SCALE IN FEET
SCALE: 1/16" = 1'-0"
EXISTING MECHANICAL BUILDING. EXISTING AUTOMATIC TRANSFER SWITCH SHALL BE REMOVED AND TURNED OVER TO OWNER. EXISTING ELECTRIC PANEL "MDP", 120V/280V, 3 , 500A, FED FROMOVERHEAD EXISTING WATER COOLING TOWER. EXISTING PANEL 2, 120/208V/3 , 400A,FED FROM UNDERGROUND EXISTING MECHANICAL ROOM. EXISTING GEN. #1 SHALL BE DISCONNECTED AND REMOVED. EXISTING PANEL E, EMERGENCY PANEL, 120V/208V, 3 , 150AEXISTING UNDERGROUND EMERGENCY POWER FEED SHALL BE ABANDONED. SEE DETAIL 1, SHEET E31.01 FOR ELECTRICAL SCHEMATIC DIAGRAM EXISTING POWER POLE EXISTING EMERGENCY PANEL E1A, 120/208/3 , 100A SHALL REMAIN ANDBE REUSED. EXISTING KITCHEN PANEL SERVICE FEED SHALL REMAIN EXISTING UNDERGROUND ELECTRICAL SERVICE SHALL BE ABANDONED EXISTING OVERHEAD ELECTRICAL SERVICE SHALL BE REWORKED AS REQUIRED. SEE POWER CO.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT. 5. ALL EXISTING EQUIPMENT SHOWN CROSS ALL EXISTING EQUIPMENT SHOWN CROSS HATCHED SHALL BE REMOVED UNLESS INDICATED OTHERWISE. 6. ALL EXISTING EQUIPMENT DISCONNECTS ALL EXISTING EQUIPMENT DISCONNECTS SHALL BE REMOVED, ON EQUIPMENT BEING REMOVED.
E1.02
BLDG.596 - ELEC.1 FLOOR PLAN - BLDG.596 - ELEC.
BUILDING 596
GENERATOR #1
145A
123A
147A
158A
ANN
32'
48'
1/16" = 1'-0"
SCALE: 1/16" = 1'-0"
EXISTING MECH. BUILDING. NEW ATS #596-1 MOUNTED ON EXISTING MOUNTED ON EXISTING WALL NEW GENERATOR #1 SET ON NEW SET ON NEW GENERATOR PAD, 200KW, 208V, 3 EXISTING MDP PANEL 2, 120/208V/3 , 400AEXISTING PANEL "MDP", 120/208V/3 , 500A.NEW GENERATOR PAD. SIZE TO FIT GENERATOR AND DOCKING STATION. SEE DETAIL 4, SHEET E20.02. NEW UNDERGROUND EMERGENCY FEEDER CIRCUIT 2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GRD. IN EACH. NEW NORMAL POWER FEED FROM ATS TO MDP. 2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GRD. IN EACH. REFER TO SHEET E20.01 FOR TYPICAL GENERATOR INSTALLATION DETAILS, SCHEMATIC, ETC. EXISTING OVERHEAD PRIMARY SERVICE ON ROOF. VERIFY REQUIREMENTS WITH POWER CO. NEW PRIMARY SERVICE, 2-3 1/2"C. WITH 4-350 KCMIL AND 1 #1 GRD. IN EACH. NEW SAFETY DISCONNECT (WP) 1000A, (WP) 1000A, 208V/3 , NEMA 3R.SHEET E31.01 FOR SCHEMATIC DIAGRAM NEW DOCKING STATION (DUAL PURPOSE)- 208V/3 TO MATCH NEW GENERATOR.EXISTING CRITICAL C-596 PANEL, 120V/208V/3 , 150ASEE DETAIL 1, SHEET E31.01 FOR ONE-LINE SCHEMATIC DIAGRAM. NEW FEED TO NEW LIFE SAFETY PANEL LS-596, 2 #1 AND 1 #6 GRD. IN 1 1/2"C. FURNISH AND INSTALL NEW 6' HIGH CHAIN LINK FENCE WITH 4'-0" GATE REMOVE EXISTING EMERGENCY REMOTE STOP BUTTON AND INSTALL NEW STOP BUTTON. FURNISH AND INSTALL NEW CONDUIT AND WIRING AS REQUIRED. MOUNT ON OUTSIDE OF BUILDING. FURNISH AND INSTALL NE ANNUNICATOR PANEL WITH NEW WIRING AND CONDUIT. VERIFY LOCATION ON JOBSITE. REMOVE OLD ANNUNICATOR PANEL, VERIFY LOCATION. EXISTING EMERGENCY PANEL SHALL BE MODIFIED TO BE NEW LIFE SAFETY PANEL LS-596.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT.
ADM 7/15/24
PARTIAL SITE PLAN -
GENERATOR
1 PARTIAL SITE PLAN - GENERATOR #3 - ELECT.
GENERATOR #3
E2.00
BLDG. 636 SEE SHEET E2.04
BLDG. 635 SEE SHEET E2.03
BLDG. 634 SEE SHEET E2.02
BLDG. 633 SEE SHEET E2.01
OE
BLDG. 666
SCALE: 1/32" = 1'-0"
SCALE: AS NOTED
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT.
EXISTING GENERATOR SHALL BE REMOVED AND NEW GEN. #3 (600 KW) 480V/3 NEW GEN. #3 (600 KW) 480V/3 (600 KW) 480V/3 SHALL BE INSTALLED. SET ON EXISTING CONCRETE PAD. SEE SHEET E30.01. EXISTING EMERGENCY LIGHT POLE SHALL REMAIN. EXISTING OVERHEAD ELECTRIC POWER LINE. NEW UNDERGROUND FEEDER CIRCUIT. 2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GRD. IN EACH. EXISTING DISTRIBUTION PANEL #MDP-1-90 SHALL BE REMOVED EXISTING POWER POLE. EXISTING POLE MOUNTED XFMR #29, #30, #31 ON POLE #13. EXISTING UNDERGROUND BUILDING POWER SERVICE FEEDER FROM EXISTING TRANSFORMER SHALL BE ABANDONED. EXISTING SERVICE ENTRY J-BOX'S. REMOVE AND REPLACE FOR NEW SERVICE J-BOX, SERVICE RATED (WP) EXISTING ATS SHALL BE REMOVED AND TURNED OVER TO OWNER EXISTING BUILDING EMERGENCY DISTRIBUTION PANEL. SHALL BE REMOVED AND TURNED OVER TO OWNER. EXISTING CHAIN LINK FENCE ENCLOSURE SHALL BE REMOVED FOR ACCESS THEN RE-INSTALLED. SEE LARGE SCALE PARTIAL SITE PLAN SHEET E30.01, DETAIL 1 FOR WORK IN THIS AREA. EXISTING UNDERGROUND NORMAL POWER FEED TO EXISTING ATS. 3 #1/0, 1 #6G, 1 1/2"C., 208V/3 TO BE ABANDONEDNEW SAFETY DISCONNECT (WP) 800A, 208V/3 , SERVICE RATEDSEE SHEET E2.05 AND E2.06 FOR ONE LINE SCHEMATIC. EXISTING ELECTRICAL DISTRIBUTION TRANS-CLOSER, SEE SHEET E2.02 FOR WORK IN THIS AREA. NEW ATS #633-1, MOUNTED ON , MOUNTED ON CONCRETE PAD. NEW ATS #634-1, MOUNTED ON , MOUNTED ON CONCRETE PAD. NEW ATS #635-1, MOUNTED ON , MOUNTED ON CONCRETE PAD. NEW ATS #636-1, MOUNTED ON , MOUNTED ON CONCRETE PAD. SEE DETAIL 1, SHEET E30.01 FOR CONTINUATION.
E2.01
BLDG.633 - ELEC.
1 FLOOR PLAN - BLDG.633 - ELEC.
BUILDING 633
EXISTING NORMAL POWER SHALL BE ABANDONED
NURSES STATION
ATS #633-1
8'
24'
1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
EXISTING PANEL "MDP". 120/208V-3 , 200ASHALL BE REMOVED, AND NEW PANEL MDP-633 INSTALLED. EXISTING ANNUNICATOR PANEL SHALL BE REMOVED AND REPLACED WITH NEW ANNUNICATOR PANEL. VERIFY EXACT MOUNTING LOCATION ON JOBSITE EXISTING PANEL "L", 225A, 120/208V/3 EXISTING PANEL "E", 225A, 120/208V/3 NEW ELECT. J-BOXES (WP) SERVICE RATED EXISTING UNDERGROUND EMERGENCY POWER CIRCUIT SHALL BE ABANDONED. NEW 4" FEEDER CONDUITS, REMOVE EXISTING CONDUITS AS REQUIRED TO INSTALL NEW FEEDER CONDUITS. NEW SAFETY DISCONNECT (WP) 800A, 208V/3 ,NEMA 3R, WP SEE SHEET E2.05 AND E2.06 FOR ONE LINE SCHEMATIC DIAGRAM. EXISTING PANEL "H", 400A, 120/208V/3 EXISTING DISCONNECT SWITCH FOR EXISTING KITCHEN PANEL "K", 120/208V/3 , 225A.NEW SERVICE FEED TO ELECTRICAL PANELS. SEE SHEET E2.05 AND E2.06. EXISTING PANEL A-90 (K), 120/208V,3 , 225A(KITCHEN) NEW AUTOMATIC TRANSFER SWITCH (ATS) ATS #633-1, 208V/3 , 208V/3 2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GROUND IN EACH. SEE SHEET E2.00 FOR CONTINUATION. NEW LIFE SAFETY PANEL "LS-633" 120/208V/3 , 150A. MOUNTED ON WALL. VERIFYLOCATION ON JOBSITE.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT.
E2.02
BLDG.634 - ELEC.
1 FLOOR PLAN - BLDG.634 - ELEC.
BUILDING 634
EXISTING NORMAL POWER
ATS #634-1
EXISTING PANEL "MDP". 120/208V-3 , 200ASHALL BE REMOVED, AND NEW PANEL MDP-634 INSTALLED. EXISTING ANNUNICATOR PANEL SHALL BE REMOVED AND REPLACED WITH NEW ANNUNICATOR PANEL. VERIFY EXACT MOUNTING LOCATION ON JOBSITE. EXISTING PANEL "E", 225A, 120/208V/3 EXISTING ELECT. J-BOXES (WP), SERVICE RATED EXISTING UNDERGROUND EMERGENCY POWER CIRCUIT SHALL BE ABANDONED. NEW 4" FEEDER CONDUITS, REMOVE EXISTING CONDUITS AS REQUIRED TO INSTALL NEW FEEDER CONDUITS. NEW SAFETY DISCONNECT (WP) 800A, 208V/3 ,SERVICE RATED. SEE SHEET E2.05 AND E2.06 FOR ONE LINE SCHEMATIC DIAGRAM EXISTING ELECTRICAL DISTRIBUTION TRANS-CLOSER. EXISTING DISTRIBUTION PANEL #MDP-1-90 SHALL BE REMOVED. NEW AUTOMATIC TRANSFER SWITCH (ATS) ATS #634-1, 208V/3 , 208V/3 EXISTING PANEL "H", 400A, 120/208V/3 NEW SERVICE FEED TO ELECTRICAL PANELS. SEE SHEET E2.05 AND E2.06 EXISTING PANEL "B", 120/208V/3 , 225AEXISTING DISTRIBUTION PANEL #1, 120/208V/3 ,1000A EXISTING PAD MOUNTED TRANSFORMER #2 2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GRD. IN EACH SEE SHEET E2.00 FOR CONTINUATION NEW LIFE SAFETY PANEL "LS-634". . 120/208V/3 , 150A. MOUNTED ON WALL. VERIFYLOCATION ON JOBSITE.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT.
E2.03
BLDG.635 - ELEC.
1 FLOOR PLAN - BLDG.635 - ELEC.
BUILDING 635
EXISTING NORMAL POWER SHALL BE ABANDONED
ATS #635-1
EXISTING PANEL "MDP", 120/208V/3 , 200ASHALL BE REMOVED AND NEW PANEL MDP-635 INSTALLED. EXISTING ANNUNICATOR PANEL SHALL BE REMOVED AND REPLACED WITH NEW ANNUNICATOR PANEL. VERIFY EXACT MOUNTING LOCATION ON JOBSITE. EXISTING PANEL "L", 225A, 120/208V/3 EXISTING PANEL "E", 225A, 120/208V/3 NEW ELECT. J-BOXES (WP), SERVICE RATED EXISTING UNDERGROUND EMERGENCY POWER CIRCUIT SHALL BE ABANDONED. NEW 4" FEEDER CONDUITS, REMOVE EXISTING CONDUITS AS REQUIRED TO INSTALL NEW FEEDER CONDUITS. NEW SAFETY DISCONNECT (WP) 800A, 208V/3 ,SERVICE RATED, NEMA 3R. SEE SHEET E2.05 AND E2.06 FOR ONE LINE SCHEMATIC DIAGRAM EXISTING PANEL "H", 400A, 120/208V/3 NEW SERVICE FEED TO ELECTRICAL PANELS. SEE SHEET E2.05 AND E2.06. EXISTING PANEL A-90 "K", 120/208V,3 , 225A(KITCHEN) NEW AUTOMATIC TRANSFER SWITCH (ATS) ATS #635-1, 208V/3 , 208V/3 EXISTING DISCONNECT SWITCH FOR EXISTING KITCHEN PANEL "K", 120/208V/3 , 225A.2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GROUND IN EACH SEE SHEET E2.00 FOR CONTINUATION. NEW LIFE SAFETY PANEL "LS-635". . 120/208V/3 , 150A. MOUNTED ON WALL. VERIFYLOCATION ON JOBSITE.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT.
E2.04
BLDG.636 - ELEC.
1 FLOOR PLAN - BLDG.636 - ELEC.
BUILDING 636
EXISTING UNDERGROUND NORMAL POWER SHALL BE ABANDONED
ATS #636-1
EXISTING PANEL "MDP". 120/208V-3 , 200A,SHALL BE REMOVED, AND NEW PANEL MDP-636 INSTALLED. EXISTING ANNUNICATOR PANEL SHALL BE REMOVED AND REPLACED WITH NEW ANNUNICATOR PANEL. VERIFY EXACT MOUNTING LOCATION ON JOBSITE. EXISTING PANEL "E", 225A, 120/208V/3 NEW ELECT. J-BOXES (WP), SERVICE RATED EXISTING UNDERGROUND EMERGENCY POWER CIRCUIT SHALL BE ABANDONED. NEW 4" FEEDER CONDUITS, REMOVE EXISTING CONDUITS AS REQUIRED TO INSTALL NEW FEEDER CONDUITS. NEW SAFETY DISCONNECT (WP) 800A, 208V/3 ,SERVICE RATED. SEE SHEET E2.05 AND E2.06 FOR ONE LINE SCHEMATIC DIAGRAM. EXISTING PANEL "H", 400A, 120/208V/3 NEW AUTOMATIC TRANSFER SWITCH )ATS) ATS #636-1, 208V/3 , 208V/3 NEW SERVICE FEED TO ELECTRICAL PANELS. SEE SHEET E2.05 AND E2.06. 2-4"C. WITH 4-600 KCMIL AND 1 #1/0 GRD. IN EACH. SEE SHEET E2.00 FOR CONTINUATION EXISTING PANEL "L", 120/208V/3 , 225ANEW LIFE SAFETY PANEL "LS-636". 120/208V/3 , 150A. MOUNTED ON WALL. VERIFYLOCATION JOBSITE.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, CONNECTIONS AND EXACT LOCATION OF EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING. 3. VERIFY DEMO/SALVAGE OF ALL EXISTING VERIFY DEMO/SALVAGE OF ALL EXISTING ITEM TO BE REMOVED WITH OWNER. 4. FINAL CONNECTION TO ALL ROTATING AND FINAL CONNECTION TO ALL ROTATING AND VIBRATING EQUIPMENT SHALL BE MADE WITH LIQUID - TIGHT FLEXIBLE CONDUIT.
E2.05
ONE LINE ELECTRICAL SCHEMATIC DIAGRAM - GENERATOR #3
(BLDG. 633, 634, 635, AND 636) - DEMOLITION
ONE LINE ELECTRICAL
SCHEMATIC DIAGRAM -
GENERATOR #3 (BLDG.
633, 634, 635, AND 636) -
DEMOLITION
NOTES BY SYMBOLGENERAL NOTES
EXISTING TRANSFORMER #2
EXISTING DIST. PANEL #1 120/208V/3 1000A
BUILDING #633
225A
EXISTING DIST. PANEL "MDP" MDP-1-90 120/208V/3 800A
BUILDING #634
EXIST. PANEL "MDP" 200A
EXIST. PANEL "E" 225A
EXIST. PANEL "L" 225A
EXISTING GEN. #3
EXIST. "ATS"
EXIST. PANEL "H" 400A
EXISTING FEEDER 1
EXISTING FEEDER 2
EXISTING EMERGENCY FEEDERS
EXIST. PANEL "K" 225A
DISC. 225A
BUILDING #635
EXIST. PANEL "K" 225A
DISC. 225A
BUILDING #636
EXISTING GENERATOR #3 SHALL BE REMOVED. EXISTING AUTOMATIC TRANSFER SWITCH "ATS" SHALL BE REMOVED. EXISTING GENERATOR SERVICE FEED SHALL BE REMOVED. EXISTING DISTRIBUTION PANEL #1, SHALL BE ABANDONED. EXISTING DISTRIBUTION PANEL "MDP-1-90" SHALL BE REMOVED. EXISTING CONDUCTORS AND CONDUITS SHALL BE ABANDONED. EXISTING TRANSFORMER #2 SHALL REMAIN. EXISTING MDP PANEL SHALL BE REMOVED. CAP EXISTING SERVICE FEEDER CONDUIT. SEAL WATER TIGHT. VERIFY SIZE ON JOBSITE. CAP BELOW GRADE OR INSIDE ELECTRIC ROOM. LABEL ABANDONED. NOT USED EXISTING DISCONNECT SWITCH FOR KITCHEN PANEL "K". 120/208V/3 , 225AEXISTING SERVICE FEEDER SHALL BE REMOVED. EXISTING ELECTRICAL SERVICE FEED FROM SEPERATE TRANSFORMER. VERIFY ON JOBSITE.
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONTRACTOR SHALL VERIFY ALL EXISTING CONNECTIONS, CONDITIONS AND EXACT LOCATIONS OF ALL EXISTING EQUIPMENT ON JOBSITE. 2. CONTRACTOR SHALL VISIT JOBSITE AND CONTRACTOR SHALL VISIT JOBSITE AND VERIFY EXTENT OF DEMOLITION BEFORE BIDDING.
E2.06
ONE LINE ELECTRICAL SCHEMATIC DIAGRAM - GENERATOR #3
(BLDG. 633, 634, 635, AND 636) - NEW WORK
ONE LINE ELECTRICAL
SCHEMATIC DIAGRAM -
GENERATOR #3 (BLDG.
633, 634, 635, AND 636) -
NEW YORK
NEW "ATS" #633-1
(NP)
NEW "ATS" #634-1
UE(NP)
UE(EP)
AutoCA