BRIDGE INSPECTION REPORT
PIMMIT RUN BRIDGE
GWMP OVER PIMMIT RUN
GEORGE WASHINGTON MEMORIAL PARKWAY
LN
STRUCTURE NO. 3300-005P
INSPECTION TYPE: ROUTINE
INSPECTION DATE: 4/15/11
Federal Highway Administration
Report prepared by: WU
MILE POINT:
KILOMETER POINT:
4.51 7.26
Federal Lands Bridge Office Bridge Inspection and Management Program 21400 Ridgetop Circle Sterling, Virginia 20166 http://www.efl.fhwa.dot.gov/FLHBO/BIP
STRUCTURE SUMMARY STRUCTURE NO. 3300-005P
PIMMIT RUN BRIDGE INSPECTION DATE: 4/15/11
BRIDGE IDENTIFICATION AND DESCRIPTION
MAIN SPAN MATERIAL: ....... STEEL CONTINUOUS NO. OF MAIN SPANS:
MAIN SPAN TYPE: ............... GIRDER & FLOOR BEAM SYSTEM NO. OF APPR. SPANS:
# OF BEAMS, MAIN SPAN: .. 2 STRUCT. TOTAL LENGTH: .. 353.0 FT (107.6 M)
DECK TYPE: ......................... CONCRETE PRECAST PANELS MAX. SPAN LENGTH: .......... 131.0 FT (39.9 M)
WEARING SURFACE: .......... MODIFIED CONCRETE DECK WIDTH: ...................... 68.0 FT (20.7 M)
ABUT. FOUNDATIONS: ........ SPREAD FTG ON BEARING MAT'L CURB TO CURB WIDTH: ..... 62.5 FT (19.1 M)
PIER FOUNDATION(S): ........ SPREAD FTG ON BEARING MAT'L YEAR BUILT:
ABUTMENT / PIER MAT'L: ... CONCRETE YEAR RECONSTRUCTED: .. 1993
PROJ./PLAN REF. NO: ......... 1A8,10,35,44 / 1254 SKEW ANGLE: ..................... 0 °
NPS ROAD CLASS: .............. 7 - URBAN PARKWAY FRACTURE CRITICAL: ........ YES
STRUCTURE HISTORY: ...... 1982-PAINTED. 1993-NEW CONCRETE DECK PANELS. 1994-RAILING AND STRUCTURAL
STEEL REPAINTED. 2009-SCOUR REPAIRS AT NORTH PIER.
LOCATION
GEORGE WASHINGTON MEMORIAL PARKWAY MILE POINT: ..................... 4.51 (KM PT 7.26)
STATE: ................................. VIRGINIA LOCATION: 4.6 MILES SOUTH OF I-495.
FACILITY CARRIED: ............ GWMP
FEATURE INTERSECTED: .. PIMMIT RUN
STRUCTURE EVALUATION SUMMARY
This fracture-critical steel girder bridge is in fair condition overall. The main problems include moderate to severe deterioration of the abutment breastwalls, which should be repaired. In addition, failure of the expansion joint compression seals has led to leakage through the joints and subsequent rusting of the structural steel superstructure.
This is also exacerbated by the configuration of the deck drains, which channel water directly onto the floor beams, gusset plates, and lateral bracing members in several locations. The expansion joints should be resealed, the drainage downspouts should be extended below the superstructure, and the structural steel should be cleaned and spot painted as necessary.
In addition, moderate rusting of the top flange of isolated stringers is indicative of water intrusion through the deck panel construction joints. The modified concrete wearing surface should be sealed to prevent further intrusion and slow the rate of deterioration.
Further problems include moderate spalling of the wearing surface along the expansion joints, rusting of the bridge railings, and deterioration of the approach pavement along the abutment backwalls. Repairs should be made as outlined in this report to prevent the possible development of more serious or costly problems in the future.
It should be noted that the lane markings have been repainted since the last inspection.
INSPECTION TEAM: M.D. HARLAN, R.E. ESTES (CLARK NEXSEN)
CONDITION ASSESSMENT:
MATTHEW D. HARLAN, P.E., FIELD TEAM LEADER
REPORT REVIEW:
GARY J. GOODLIN, FIELD TEAM LEADER 703-404-6253
REPORT APPROVAL: DATE: 8/17/11
MARCUS MILLER, P.E., LEAD STRUCTURAL ENGINEER 703-404-6252
RECOMMENDATIONS AND ESTIMATED COSTS STRUCTURE NO. 3300-005P
A (Critical) - Structure is closed, in imminent danger of collapse, or presents a critical safety hazard.
B (Major) - Structure is seriously deficient or presents a safety hazard, but can remain in service at reduced loads or with frequent inspections.
C (Moderate) - Structure is deficient, functionally obsolete, or requires substantial repairs to prevent a serious deficiency or unsafe condition.
D (Minor) - Structure is generally in good condition. Preventative maintenance may be required.
E (Special) - Structure is under construction or reconstruction.
C226 PRIORITY OF IMPROVEMENT
ITEM
NO.
MAINTENANCE RECOMMENDATIONS
(GENERALLY NOT FLHP ELIGIBLE)
QTY. UNIT COST
UNIT
ESTIMATE
COST
PRELIM.
58.7 EXTEND DECK DRAIN PIPES BELOW STRUCTURAL STEEL. 5 EA
58.2 REPLACE COMPRESSION SEAL AT BOTH EXPANSION JOINTS; RESEAL
LONGITUDINAL PORTION OF EXPANSION JOINTS.
141 LF
222.4 PATCH SPALLING OF APPROACH PAVEMENT ALONG ABUTMENT BACKWALLS. 50 SF
58.6 RESET OR REPLACE STONES IN MASONRY MEDIAN BARRIER. 1 CY
58.3 REPAIR WEARING SURFACE IN WEST SHOULDER OF SOUTHBOUND LANES
ALONG EXPANSION JOINTS AT BRIDGE ENDS.
8 SF
PRELIM. MAINTENANCE TOTAL :
ITEM
NO.
REHABILITATION/RECONSTRUCTION
(TYPICALLY NEEDED WITHIN 5 YEARS)
QTY. UNIT
UNIT
COST ESTIMATES
PRELIM. COST
REHAB. RECONSTR.
58.3 CLEAN AND SEAL MODIFIED CONCRETE WEARING SURFACE. 19,062 SF
58.6 CLEAN AND PAINT RAILINGS. 353 LF
60.1,3 REMOVE UNSOUND CONCRETE FROM ABUTMENT BREASTWALLS
AND BEARING SEATS, CLEAN REBAR, AND PLACE NEW CONCRETE
TO ORIGINAL DIMENSIONS.
200 SF
59.1,2,4,6,7 CLEAN AND SPOT PAINT STRUCTURAL STEEL UNDER DECK
DRAINS, AT ENDS OF STRUCTURE, AND AT ISOLATED LOCATIONS
ELSEWHERE AS NECESSARY.
1,500 SF
PRELIM. REHABILITATION/RECONSTRUCTION TOTAL :
COST ESTIMATE SUMMARY
PRELIM. MAINTENANCE TOTAL:
PRELIM. REHABILITATION TOTAL:
PRELIM. RECONSTRUCTION TOTAL: ..
TOTAL ITEMIZED COSTS:
PRELIMINARY ESTIMATE TOTAL* :
(*Includes typical contract costs for mobilization, traffic control, and design/construction engineering; but does not include detour bridges, work beyond the bridge limits, or work not listed above. Estimates are approximate and are for preliminary planning purposes only; they should not be used as a complete or final engineers estimate.)
REMARKS: Cost estimates assume that the recommended actions will be combined with similar work being performed on other structures.
FIELD INSPECTION REPORT STRUCTURE NO. 3300-005P
G = GOOD (CODES 7 - 9) F = FAIR (CODES 5 - 6) P = POOR (CODES 0 - 4)
CONDITION RATING CODE EQUIVALENTS FOR SUB-ELEMENTS
SERIOUS CONDITION - loss of section, deterioration, spalling, or scour have seriously affected primary structural components. Local failures are possible.
Fatigue cracks in steel or shear cracks in concrete may be present.
CRITICAL CONDITION - advanced deterioration of primary structural elements. Fatigue cracks in steel or shear cracks in concrete may be present or scour may have removed substructure support. Unless closely monitored it may be necessary to close the structure until corrective action can be taken.
“IMMINENT” FAILURE CONDITION - major deterioration or section loss present in critical structural components or obvious vertical or horizontal movement affecting structure stability. Structure is closed to traffic but corrective action may return structure to light service.
FAILED CONDITION - out of service; beyond corrective action.
CONDITION RATING CODES FOR ITEMS 58 - 62, 222, 223
NOT APPLICABLE
EXCELLENT CONDITION
VERY GOOD CONDITION - no problems noted.
GOOD CONDITION - some minor problems.
SATISFACTORY CONDITION - structural elements show some minor deterioration.
FAIR CONDITION - all primary structural elements are sound but may have minor section loss, cracking, spalling, or scour.
POOR CONDITION - advanced section loss, deterioration, spalling, or scour.
N
58. DECK
ITEM REFERENCE AND REMARKS
OTHER
ALIGNMENT
DEFLECTION AND/OR VIBRATION
FASCIA(E)
DIAPHRAGMS AND BRACING
TRUSSES
FLOOR BEAMS AND STRINGERS
ARCH(ES) OR SLAB(S)
GIRDERS OR BEAMS
BEARING DEVICES
59. SUPERSTRUCTURE
OTHER
DEFLECTION AND/OR VIBRATION
UTILITIES
DRAINS AND DRAINAGE
PARAPETS AND/OR RAILINGS
CURBS, SIDEWALKS, AND MEDIAN
RIDEABILITY
WEARING SURFACE
EXPANSION JOINTS
DECK SLAB
ABUTMENTS
60. SUBSTRUCTURE
1.
10.
2.
3.
4.
5.
6.
7.
8.
9.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
PAINT
11.
F F N F N F F N G
N G
F G G F F N
N
P
G
G
58.1 MINOR TRANSVERSE CRACKING OF DECK UNDERSIDE UNDER
MEDIAN AND UNDERSIDE OF OVERHANGS WITH EFFLORESCENCE.
POST-TENSIONING TENDONS EXPOSED ON DECK UNDERSIDE AT
PIERS. GROUT HAUNCHES BETWEEN DECK AND STRINGERS OR
GIRDERS INCOMPLETELY POURED AND BREAKING UP IN SEVERAL
LOCATIONS WITH WIDESPREAD SHRINKAGE CRACKING.
MODERATE DELAMINATION OF DECK UNDERSIDE AT SOUTH
ABUTMENT ADJACENT TO WEST GIRDER.
MINOR LONGITUDINAL CRACK (2'L) WITH EFFLORESCENCE ON
DECK UNDERSIDE UNDER MEDIAN, NORTH SPAN BETWEEN FLOOR
BEAMS #15 AND #16.
58.2 ACTIVE LEAKAGE AT TIME OF INSPECTION THROUGH EXPANSION
JOINTS. COMPRESSION SEAL AT SOUTH EXPANSION JOINT HAS
FAILED FOR APPROXIMATELY 27' (PREVIOUSLY 20') IN
NORTHBOUND LANES AND 25' IN SOUTHBOUND LANES.
COMPRESSION SEAL AT NORTH EXPANSION JOINT IS RECESSED
FOR 12' (PREVIOUSLY 5') IN NORTHBOUND LANES AND 16'
(PREVIOUSLY 6') IN SOUTHBOUND LANES. LONGITUDINAL PORTION
OF EXPANSION JOINTS SEALED SINCE LAST INSPECTION; SEALS
BEGINNING TO FAIL. MINOR ACCUMULATION OF DEBRIS IN BOTH
EXPANSION JOINTS.
58.3 MINOR TRANSVERSE CRACKING OF WEARING SURFACE IN SOME
LOCATIONS. MINOR SCALING WITH EXPOSED AGGREGATE
THROUGHOUT SOUTHBOUND LANES. WEARING SURFACE
BREAKING UP (UP TO 42"L X 1'W X 1"D) ALONG EXPANSION JOINTS
AT BOTH ENDS OF BRIDGE IN WEST SHOULDER OF SOUTHBOUND
LANES; MINOR CRACKING AT SOUTH END IN NORTHBOUND LANES.
LANE MARKINGS RESTRIPED SINCE LAST INSPECTION.
58.5 WIDESPREAD MINOR CRACKING OF CURBS.
BREASTWALLS OR COLUMNS1. F
PILE BENTS2. N
CAPS AND/OR BEARING SEATS3. F
BACKWALLS AND/OR BULKHEADS4. G
FOUNDATIONS5. N
WINGWALLS6. G
WEEP HOLES7. G
EXPANSION JOINTS8. N
EROSION AND/OR SCOUR9. G
SETTLEMENT OR DEFLECTION10. G
SLOPE PROTECTION11. G
OTHER (DRAINAGE TROUGHS) 12. F
PIER(S)
WALLS AND/OR COLUMNS 13. G
PILE BENTS14. N
CAPS AND/OR BEARING SEATS15. F
FOUNDATIONS16. (BURIED) N
EROSION AND/OR SCOUR17. G
SETTLEMENT OR DEFLECTION18. G
OTHER 19. N
ITEM REFERENCE AND REMARKS
STREAM BED COMPOSITION : 9.
AVERAGE CLEAR OPENING 8.
NORMAL VELOCITY 7.
ADEQUACY OF OPENING 6.
OTHER 5.
WATERWAY OBSTRUCTIONS 4.
CHANNEL PROTECTION3.
EROSION AND/OR SCOUR2.
ALIGNMENT1.
61. CHANNEL 7
G G G G N
MED
SUFF
65 FT.
SAND, GRAVEL
222. APPROACHES 6
OTHER 9.
ALIGNMENT 8.
SIGNS7.
SETTLEMENT 6.
EROSION5.
SURFACING4.
APPROACH GUARDRAIL 3.
2. RELIEF JOINTS
APPROACH SLABS1. N
N G F G G G G N
223. RETAINING WALL N
OTHER 6.
SETTLEMENT OR DEFLECTION5.
EROSION AND/OR SCOUR4.
FOUNDATION3.
WEEP HOLES2.
1. WALL
36. TRAFFIC AND SAFETY FEATURES
APPROACH GUARDRAIL ENDSD.
APPROACH GUARDRAILSC.
TRANSITIONSB.
BRIDGE RAILINGSA. 1
58.6 MINOR EFFLORESCENCE ON MASONRY MEDIAN BARRIER. ONE
STONE MISSING ON NORTHBOUND SIDE IN SOUTH SPAN, TWO
MISSING ON NORTHBOUND SIDE NEAR NORTH PIER, AND ONE
MISSING ON SOUTHBOUND SIDE IN SOUTH SPAN NEAR SOUTH
PIER.
MINOR TO MODERATE VEHICLE SCRAPES AND RUSTING OF
RAILINGS THROUGHOUT WITH SOME RUST SCALE. MOLD ON WEST
RAILING NEAR NORTH END. MODERATE VEGETATION GROWTH ON
EAST RAILING AT NORTH END.
58.7 MINOR ACCUMULATION OF GRAVEL IN SHOULDERS IN SOME
LOCATIONS NOT AFFECTING DRAINAGE.
CONFIGURATION OF DECK DRAINS AT FLOOR BEAMS #2, #8, #11,
#13, AND #15 CHANNEL WATER DIRECTLY ONTO GUSSET PLATES,
LATERAL BRACING MEMBERS, AND/OR FLOOR BEAMS;
ACCUMULATION OF DEBRIS ON GUSSET PLATES.
58.9, 59.9 MINOR VIBRATION FELT AT MEDIAN AT NORTH END OF STRUCTURE
UNDER LIVE LOAD. MINOR VIBRATION OF FLOOR BEAM #17 (AT
NORTH ABUTMENT) AND ADJACENT BRACING UNDER LIVE LOAD.
59, 60 WIDESPREAD GRAFFITI NEAR ENDS OF STRUCTURE AND ON
LOWER PORTION OF PIERS. NO UBIV ACCESS TO SOUTH SPAN
DUE TO OVERGROWTH OF TREES.
TRAFFIC SAFETY RATING CODES
N
Does not meet standards or a safety feature is required and none is provided.
Meets currently acceptable standards.
Not applicable or a safety feature is not required.
ADDITIONAL ITEM REFERENCE AND REMARKS
59.1,2,4,6,7 MINOR RUSTING THROUGHOUT STRUCTURAL STEEL (APPROXIMATELY 10%) WITH UP TO 1/8" DEEP PITTING PREDATING PAINT. MINOR TO MODERATE RUSTING OF BEARINGS AND ENDS OF GIRDERS AT ABUTMENTS;
RUST SCALE ON BEARINGS AND AT ISOLATED LOCATIONS ON GIRDER ENDS.
UP TO 1/2" PACK RUST BETWEEN GIRDER BOTTOM FLANGE COVER PLATES PREDATING PAINT, PRIMARILY OVER PIERS AND AT ISOLATED LOCATIONS ELSEWHERE. MODERATE SECTION LOSS ON GIRDER BOTTOM FLANGE, COVER PLATES, AND RIVET HEADS BEHIND BEARINGS AT ABUTMENTS PREDATING PAINT (3/8" SECTION REMAINING, 3/4" ORIGINAL SECTION). ONE RIVET TYPICALLY MISSING ON EXTERIOR SIDE OF GIRDERS IN UPPER ANGLE AT FLOOR BEAM CONNECTIONS. SMALL DRILLED HOLE IN MID-HEIGHT OF WEST GIRDER WEB AT
NORTH SIDE OF FLOOR BEAM #6 (SOUTH PIER).
BOTTOM FLANGE OF STRINGER #4 IN CENTER SPAN BETWEEN FLOOR BEAMS #8 AND #9 BENT DOWN APPROXIMATELY 1" FOR 3'L. MODERATE RUSTING OF TOP FLANGE OF STRINGER #4 IN CENTER AND NORTH SPANS OVER FLOOR BEAMS #9, #10, AND #15. MODERATE RUSTING OF STRINGERS AT NORTH ABUTMENT, END
UP TO 15'.
UP TO 1/16" PACK RUST BETWEEN FLOOR BEAM BOTTOM FLANGE COVER PLATES AT DRAIN LOCATIONS PREDATING PAINT. MODERATE SECTION LOSS ON NORTH SIDE OF BOTTOM FLANGE (1/2" SECTION REMAINING, 3/4" ORIGINAL SECTION) AND BOTTOM 4" OF WEB OF FLOOR BEAM #17 WITH UP TO 100% SECTION LOSS ON
RIVET HEADS AND STIFFENERS PREDATING PAINT.
MODERATE RUSTING OF GUSSET PLATES, LATERAL BRACING MEMBERS, AND/OR FLOOR BEAM FLANGES AT FLOOR BEAMS #2, #8, #11, AND #14 (ALL DRAIN LOCATIONS EXCEPT FLOOR BEAM #14); SEVERE SECTION LOSS ON NUTS AND BOLTS AT FLOOR BEAM #2. LONGITUDINAL BRACE IN SOUTH SPAN BETWEEN FLOOR BEAMS #3 AND #4 BENT DOWN APPROXIMATELY 6"; GUSSET PLATES AT FLOOR BEAMS #3 AND #4 DISTORTED AS A
RESULT.
60.1 WIDESPREAD MODERATE TO SEVERE DELAMINATION AND SPALLING OF ABUTMENT BREASTWALLS WITH UP TO
50% (20% PREVIOUSLY) SECTION LOSS ON EXPOSED REBAR.
60.3 MINOR ACCUMULATION OF DEBRIS ON ABUTMENT BEARING SEATS. SEVERE SPALLING OF FLUME CONCRETE ON TOP OF ABUTMENT BREASTWALLS IN SEVERAL LOCATIONS WITH WIDESPREAD MINOR DETERIORATION.
MODERATE DETERIORATION OF GROUT AROUND WEST BEARING AT SOUTH ABUTMENT. VEGETATION
GROWING ON TOP OF NORTH ABUTMENT BREASTWALL NEAR WEST GIRDER.
60.4 MINOR CRACKING OF ABUTMENT BACKWALLS WITH EFFLORESCENCE. MINOR SCALING AND EDGE SPALLING
ON TOP OF BACKWALLS.
60.6 MINOR VERTICAL CRACKING OF WINGWALLS WITH EFFLORESCENCE. MINOR VEGETATION GROWTH ON NORTHEAST WINGWALL. MINOR SPALL WITH EXPOSED REBAR ON NORTH FACE OF SOUTHWEST WINGWALL.
60.9,11 EROSION TRENCHES AT ABUTMENT SLOPES BELOW DECK DRAINS LINED WITH RIPRAP; MINOR EROSION
REMAINS.
60.12 ACCUMULATION OF DEBRIS IN CONCRETE DRAINAGE TROUGHS AT ABUTMENTS. MINOR SCALING AND COVER SPALLING OF TROUGHS. MODERATE SPALL (3'L X 8"H X FULL DEPTH) WITH EXPOSED REBAR AT TOP OF
TROUGH AT SOUTH ABUTMENT.
60.13 MINOR EFFLORESCENCE ON SOUTH SIDE OF SOUTH PIER STEM AND ON NORTH PIER STEM AT TOP. MODERATE
VEGETATION GROWTH ON NORTH PIER.
ADDITIONAL ITEM REFERENCE AND REMARKS
60.15 WIDESPREAD MINOR CRACKING OF PIER CAPS. MINOR DELAMINATION OF NORTH FACE OF SOUTH PIER CAP.
MINOR RUST SPOT ON SOUTH PIER CAP UNDERSIDE AT WEST END. MINOR DELAMINATION AND SPALLING WITH EXPOSED REBAR AND EFFLORESCENCE ON SOUTH FACE OF NORTH PIER CAP AT WEST END. MINOR
DELAMINATION WITH EFFLORESCENCE ON NORTH FACE OF NORTH PIER CAP AT WEST END.
MODERATE DETERIORATION OF GROUT AROUND BEARINGS AT SOUTH PIER.
61.3 RIPRAP CHANNEL BANK PROTECTION ALONG NORTH CHANNEL BANK FOR A SIGNIFICANT LENGTH UPSTREAM
AND DOWNSTREAM OF STRUCTURE.
222.3 WEATHERING STEEL APPROACH GUARDRAILS IN MEDIAN IN GOOD CONDITION.
222.4 MINOR CRACKING AND MODERATE SPALLING OF APPROACH PAVEMENT, PRIMARILY ALONG BACK OF
BACKWALLS; ISOLATED AREAS OF ASPHALT PATCHING.
222.7 "PIMMIT RUN" SIGNS AT EAST SIDE OF SOUTH APPROACH AND WEST SIDE OF NORTH APPROACH.
36.B,D MASONRY APPROACH PARAPETS NOT ATTACHED TO BRIDGE RAILINGS. END TREATMENTS DO NOT MEET
CURRENT AASHTO SPECIFICATIONS.
STRUCTURE LOAD RATING STRUCTURE NO. 3300-005P
TRUCK TYPE
INVENTORY RATING (NORMAL TRAFFIC) OPERATING RATING (MAXIMUM LOAD)
TONS METRIC TONS TONS METRIC TONS
H 20 18 33 30
HS 34 31 56 51
TYPE 3 33 30 55 50
TYPE 3S2 37 34 62 56
TYPE 3-3 40 36 67 61
DESIGN LOADING: H20 (M18)
X CAPACITY MEETS OR EXCEEDS DESIGN LOAD
CAPACITY IS LESS THAN DESIGN LOAD
ORIGINAL LOAD RATING CALCULATION APPLICABLE
ORIGINAL LOAD RATING CALCULATION REVISED
DATE OF LOAD RATING CALCULATION:
LOAD RATING CONTROLLED BY:
REMARKS: RATING IS BASED ON DESIGN LOAD OF STRUCTURE.
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 3300-005P
STRUCTURE IDENTIFICATION
(201) PARK: GEORGE WASHINGTON MEMORIAL PARKWAY
(202) STRUCTURE NAME: .......... PIMMIT RUN BRIDGE
(203) STRUCTURE KIND: ............ 1 - BRIDGE
(204) STRUCTURE NUMBER: ..... 3300-005P
(205) NPS REGION: .................... 2 - NATIONAL CAPITAL
(206) ROUTE CODE NUMBER: ... 1
(207) ROAD SECTION NO: .......... 005P
(208) NPS ROAD CLASS: ............ 7 - URBAN PARKWAY
(209) WITHIN NPS BNDRY?: ....... YES
(210) OPERATING UNIT: ............. PARK
(211) PROJECT NO(S): ................ 1A8,10,35,44
(212) DRAWING NUMBERS:
(21) MAINTAINED BY: ................. 66 - NATIONAL PARK SERVICE
(22) OWNER: ............................... 66 - NATIONAL PARK SERVICE
(1) STATE:
(2) STATE HWY. AGENCY DIST:
(3) COUNTY CODE:
(4) CITY/PLACE CODE:
(5) INVENTORY ROUTE:
(6) FEATURES INTERSECTED:
(7) FACILITY CARRIED:
(8) STATE STRUCTURE NO:
(9) LOCATION:
(10) INV. RTE. - MIN. VERT. CLR: ..
(11) MILE POINT:
(27) YEAR BUILT:
(106) YEAR RECONSTRUCTED:
(20) TOLL:
(37) HISTORICAL DESIGNATION: ..
513 - VIRGINIA (VA)
059 - FAIRFAX
161000010
PIMMIT RUN
GWMP
3300005P0000000
4.6 MILES SOUTH OF I-495.
99.99 FT (99.99 M)
4.51 (KM PT 7.26)
3 - FREE ROAD
5 - NOT ELIGIBLE
STRUCTURE DESCRIPTION, FOUNDATION, AND DECK TYPE
(43A) MAIN STR. MATERIAL: ..
(43B) MAIN STR. TYPE:
(45) NO. OF MAIN SPANS:
(48) MAX. SPAN LENGTH:
(49) STRUCTURE LENGTH:
(216A) ABUTMENT #1 FDN:
(216B) ABUTMENT #2 FDN:
(217A) PREDOM. PIER FDN.: ..
(217B) SECOND. PIER FDN: ...
(107) DECK TYPE:
4 - STEEL CONTINUOUS
03 - GIRDER & FLOOR BEAM SYSTEM
131.0 FT (39.9 M)
353.0 FT (107.6 M)
2 - SPREAD FTG ON BEARING MAT'L
2 - SPREAD FTG ON BEARING MAT'L
2 - SPREAD FTG ON BEARING MAT'L
2 - SPREAD FTG ON BEARING MAT'L
2 - CONCRETE PRECAST PANELS
(44A) APPR. STR. MATERIAL: ........ 0 - OTHER
(44B) APPR. STR. TYPE: ................ 00 - OTHER
(46) NO. OF APPROACH SPANS: .. 0
(108) WEAR SURFACE/PROTECT SYSTEM:
A) TYPE WEARING SURFACE: .. 3 - MODIFIED CONCRETE
B) TYPE MEMBRANE: ................. 0 - NONE
C) TYPE PROTECTION: .............. 0 - NONE
(218) IS SALT USED?: ..................... YES
LOAD RATING AND POSTING
(31) DESIGN LOAD: ................. 4 - H20 (M18) (41) LOAD RESTRICTION: ......... A - OPEN, NO RESTRICTION
(66) INVENTORY RATING: ...... 34.0 TONS (31.0 METRIC TONS) (70) BRIDGE POSTING: .............. 5 - NO POSTING REQUIRED
(64) OPERATING RATING: ...... 56.0 TONS (50.8 METRIC TONS)
INSPECTION DATES
(90) INSPECTION DATE: 4/11 (91) FREQ. OF INSP: 24 MONTHS (92 / 93) CRITICAL FEATURE INSPECTION (CFI):
(219) ADD. STUDIES NEEDED: N - 0 - NONE (A) FRACTURE CRITICAL: ... YES
INSP. EVERY: 24 MONTHS - LAST INSP. : 4/11 (220) SPECIAL STUDY TYPE: 0 - NONE
(B) UNDERWATER: .............. NO
(221) SPECIAL STUDY DATE: INSP. EVERY: MONTHS - LAST INSP. :
(C) SPECIAL INSPECTION: .. NO
INSP. EVERY: MONTHS - LAST INSP. :
o
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 3300-005P
GEOMETRY, TRAFFIC, AND NAVIGATIONAL DATA
(16) LATITUDE: ............................. 38°55'55.00"
(17) LONGITUDE: ......................... 77°07'26.80"
(19) DETOUR LENGTH: ............... 9 MI (14 KM)
(28A) LANES ON STRUCT:
(28B) LANES UNDER STRUCT: ... 00
(42A) SERVICE ON: ..................... 5 - HIGHWAY-PEDESTRIAN
(42B) SERVICE UNDER: .............. 5 - WATERWAY
(29) AVG. DAILY TRAFFIC:
(30) YEAR OF ADT:
(114) FUTURE ADT:
(115) YEAR OF FUTURE ADT:
(101) PARALLEL STRUCTURE: ... N - NONE
(38) NAVIGATION CONTROL?: ... 0
(39) VERTICAL CLEARANCE: ...... 0.0 FT (0.0 M)
(40) HORIZ. CLEARANCE: ........... 0.0 FT (0.0 M)
(111) ABUT. OR PIER PROT:
LATERAL UNDERCLEARANCE:
(55) RIGHT: ....................... 0.0 FT (0.0 M)
(56) LEFT: ......................... 0.0 FT (0.0 M)
(51) CURB TO CURB WIDTH: ........... 62.5 FT (19.1 M)
(52) DECK WIDTH: ............................ 68.0 FT (20.7 M)
(32) APPR. ROADWAY WIDTH: ........ 54.0 FT (16.5 M)
(213) APPR. PAVEMENT WIDTH: ..... 54.0 FT (16.5 M)
LEFT SHOULDER: .................. 0.0 FT (0.0 M)
RIGHT SHOULDER: ................ 0.0 FT (0.0 M)
(33) BRIDGE MEDIAN: ....................... 3 - CLOSED MEDIAN (non-moun
(34) SKEW ANGLE: ............................ 0 °
(35) DECK FLARE?: ........................... NO
(47) TOTAL HORIZ. CLEARANCE: .... 31.2 FT (9.5 M)
(50) SIDEWALKS:
LEFT : ...................................... 0.0 FT (0.0 M)
RIGHT : ................................... 0.0 FT (0.0 M)
(214) BRIDGE RAIL TYPE:
RAIL CONFIGURATION: ......... 1 - FULL HEIGHT (NO PARAPE
MATERIAL: .............................. 4 - STEEL
DESIGN TYPE: ........................ 1 - CONTINUOUS RAIL
(215) BRIDGE RAIL HEIGHT: ............ 3.67 FT (1.12 M)
(53) MIN. VRT. CLEAR. OVER DECK: 99.99 FT (99.99 M)
(54) MIN. VRT. UNDERCLEARANCE: 0.00 FT (0.00 M)
CONDITION AND APPRAISAL DATA, PROPOSED IMPROVEMENTS, AND COST
(58) DECK:
(59) SUPERSTRUCTURE:
(60) SUBSTRUCTURE:
(61) CHANNEL:
(62) CULVERT: ........................... N
(222) APPROACHES:
(223) RETAINING WALL: ........... N
(36) TRAFFIC SAFETY FEAT: ... 1010
(75A) TYPE OF WORK: .............. 35 - GENERAL REHAB
(75B) WORK DONE BY: ............. 1 - CONTRACT
(76) IMPROVEMENT LENGTH: .. 353.0 FT (107.6 M)
(67) STRUCTURAL EVALUATION:
(68) DECK GEOMETRY:
(69) UNDERCLEARANCES:
(71) WATERWAY ADEQUACY:
(72) APPROACH ALIGNMENT:
(113) SCOUR CRITICAL:
(225) PURPOSE OF IMPROVEMENT:
(226) PRIORITY OF IMPROVEMENT:
(227) MAINTENANCE COST:
(228) REHAB./RECONSTR. COST: ...
(229) CONSTRUCTION COST:
N
8 - Stable; scour above top of fo
2 - REHAB/RECONSTRUCTION
C - MODERATE
ADDITIONAL INFORMATION
(230) STRUCTURE HISTORY:
1982-PAINTED. 1993-NEW CONCRETE DECK PANELS. 1994-RAILING AND STRUCTURAL STEEL REPAINTED. 2009-SCOUR REPAIRS
AT NORTH PIER.
(231) ADDITIONAL CONSIDERATIONS:
(330) ADDITIONAL CONFIG. INFO.:
http:77�07'26.80 http:38�55'55.00
APPENDIX STRUCTURE NO. 3300-005P
PHOTOGRAPHS STRUCTURE NO. 3300-005P
PHOTO #1 - LOOKING SOUTHBOUND TOWARD MT. VERNON
FLOW
PHOTO #2 - EAST (DOWNSTREAM) SIDE
PHOTO #3 - GENERAL TOPSIDE VIEW
LOOKING NORTH, SOUTHBOUND LANES
PHOTO #4 - WEARING SURFACE BREAKING UP
ALONG NORTH EXPANSION JOINT IN WEST
SHOULDER OF SOUTHBOUND LANES
PHOTO #5 - FAILED COMPRESSION SEAL AT
SOUTH EXPANSION JOINT IN NORTHBOUND
LANES
PHOTO #6 - FAILED COMPRESSION SEAL AT
SOUTH EXPANSION JOINT IN SOUTHBOUND
LANES; ALSO NOTE TYPICAL CRACKING AND
SPALLING OF APPROACH PAVEMENT ALONG
BACK OF BACKWALLS
PHOTO #7 - TWO STONES MISSING ON NORTHBOUND SIDE OF MEDIAN
NEAR NORTH PIER
PHOTO #8 - TYPICAL RUSTING OF RAILINGS; WEST RAILING AT SOUTH
END SHOWN
PHOTO #9 - GENERAL UNDERSIDE VIEW LOOKING SOUTH, SOUTH
SPAN
PHOTO #10 - TYPICAL EXPOSED POST-TENSIONING TENDONS ON
DECK UNDERSIDE AT PIERS; BAY #6 IN NORTH SPAN AT NORTH PIER
SHOWN
PHOTO #11 - TYPICAL GROUT HAUNCH BETWEEN DECK AND GIRDER
INCOMPLETELY POURED; WEST GIRDER IN NORTH SPAN SHOWN
PHOTO #12 - TYPICAL GROUT HAUNCH BETWEEN DECK AND
STRINGER INCOMPLETELY POURED; STRINGER #6 NEAR FLOOR BEAM
#2 IN SOUTH SPAN SHOWN
PHOTO #13 - DELAMINATION OF DECK UNDERSIDE AT SOUTH
ABUTMENT ADJACENT TO WEST GIRDER; ALSO NOTE TYPICAL
RUSTING OF GIRDERS AT ABUTMENTS
PHOTO #14 - TYPICAL RUSTING THROUGHOUT STRUCTURAL STEEL;
WEST GIRDER IN NORTH SPAN SHOWN
PHOTO #15 - TYPICAL RUSTING OF BEARINGS; WEST BEARING AT
SOUTH ABUTMENT SHOWN; ALSO NOTE DETERIORATION OF GROUT
AROUND BEARING
PHOTO #16 - TYPICAL RUSTING OF GIRDERS AT ABUTMENTS; WEST
GIRDER AT SOUTH ABUTMENT SHOWN; ALSO NOTE TYPICAL SECTION
LOSS PREDATING PAINT
PHOTO #17 - TYPICAL PACK RUST BETWEEN GIRDER BOTTOM FLANGE
COVER PLATES PREDATING PAINT; WEST GIRDER IN CENTER SPAN
NEAR SOUTH PIER SHOWN
PHOTO #18 - TYPICAL PACK RUST BETWEEN GIRDER BOTTOM FLANGE
COVER PLATES PREDATING PAINT; EAST GIRDER IN CENTER SPAN
NEAR NORTH PIER SHOWN
PHOTO #19 - RUSTING OF STRINGER #4 IN CENTER SPAN OVER
FLOOR BEAM #10
PHOTO #20 - TYPICAL RUSTING OF STRINGERS AT NORTH ABUTMENT;
STRINGER #4 SHOWN
PHOTO #21 - BOTTOM FLANGE OF STRINGER #4 IN CENTER SPAN
BETWEEN FLOOR BEAMS #8 AND #9 BENT DOWN; ALSO NOTE DECK
DRAIN DIRECTLY ABOVE FLOOR BEAM
PHOTO #22 - TYPICAL CONDITION OF STRUCTURAL STEEL UNDER
DECK DRAINS; FLOOR BEAM #2 SHOWN
PHOTO #23 - RUSTING OF GUSSET PLATE, LATERAL BRACING, AND
FLOOR BEAM #11 UNDER DECK DRAIN (VIEW FROM BELOW)
PHOTO #24 - RUSTING OF GUSSET PLATE, LATERAL BRACING, AND
FLOOR BEAM #11 UNDER DECK DRAIN (VIEW FROM ABOVE)
PHOTO #25 - LONGITUDINAL BRACE IN SOUTH SPAN BETWEEN FLOOR
BEAMS #3 AND #4 BENT DOWN
PHOTO #26 - GENERAL VIEW OF SOUTH ABUTMENT
PHOTO #27 - TYPICAL DETERIORATION OF
ABUTMENT BREASTWALLS; WEST END OF
SOUTH ABUTMENT SHOWN
PHOTO #28 - TYPICAL DETERIORATION OF
ABUTMENT BREASTWALLS; EAST END OF
SOUTH ABUTMENT SHOWN
PHOTO #29 - TYPICAL DETERIORATION OF ABUTMENT BREASTWALLS;
CENTERLINE OF NORTH ABUTMENT SHOWN
PHOTO #30 - TYPICAL DETERIORATION OF FLUME CONCRETE ON TOP
OF ABUTMENT BREASTWALLS; WEST END OF SOUTH ABUTMENT
SHOWN
PHOTO #31 - GENERAL VIEW OF NORTH PIER,
SOUTH FACE; NOTE VEGETATION GROWTH
PHOTO #32 - DETERIORATION OF SOUTH
FACE OF NORTH PIER CAP AT WEST END
PHOTO #33 - LOOKING UPSTREAM THROUGH STRUCTURE, CENTER
SPAN
PHOTO #34 - LOOKING DOWNSTREAM THROUGH STRUCTURE,
CENTER SPAN