DrawingsAsOne 1 of 5.pdf
PDF 5 MB Posted
- Attached to
- Repairs to BEQ 4313
- Solicitation number
- N400856970752
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DrawingsAsOne 2 of 5.pdf | ||
| DrawingsAsOne 5 of 5.pdf | ||
| SpecsAsOne 1 of 2.pdf | ||
| DrawingsAsOne 3 of 5.pdf | ||
| RFP 690752 Repairs to BEQ 4313.pdf | ||
| SpecsAsOne 2 of 2.pdf | ||
| DrawingsAsOne 4 of 5.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SLOCUM
GATE
MAIN GATE
PASS & ID BUILDING
U S
H W
Y
HWY 101
BLDG 163
ROICC FED
SLOCUM RD.
2N D
AV
E
E S
TR
E E T
4TH
AVE3R
D
AV
E
5TH
AV
E
1S T A
VE
C S
TR
EE
T C U
R T
IS
R
D
B E
A C
H Y
R D
L A
N G
L E
Y R
D
W R
IG
H
T R
D
C U
N N
IN
G
H A
M R
D
R O
O S
E V
E L T
B L V
D
ROOSEVELT BLVD.
A S
TR
E E T
MONROE RD
S K E E T R
A N
G E R
D
ACCESS RD
D U
F F
Y
R
D
6TH
AV
E
F STREET
R O
O S
E V
E L T
B L V
D
ROOSEVELT BLVD.
GI001
A3
4TH AVE
2ND AVE
3RD AVE
E S T
E S T
4TH AVE
EQUIPMENT
ENCLOSURE
BUILDING 4311
BUILDING 4313
EQUIPMENT
ENCLOSURE
NTRUE
NORTH
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
A R C H I T E C T U R E
EST. 1915
E N G I N E E R I N G
I N T E R I O R S
P L A N N I N G
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/1
/2
:5
:1
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
REPAIRS TO BEQ - 4313
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
GI001
C O
V E
R S
H E
E T
A N
D S
H E
E T
I N
D E
X
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
MARINE CORPS AIR STATION
CHERRY POINT, NC, 28533
12798469
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
KSVNP EJD
SCALE:1" = 3000'-0"
A1
LOCATION PLAN
SCALE: 1" = 200'-0"
A3
VICINITY MAP
N
SHEET INDEX
NAVFAC
DWG NO.
SHEET
COUNT
SHEET
NO. SHEET NAME
PLUMBING
12798526 058 P-001 PLUMBING SYMBOLS LEGEND
12798527 059 PD101 PLUMBING DEMOLITION PLAN - FIRST FLOOR
12798528 060 PD102 PLUMBING DEMOLITION PLAN - SECOND FLOOR
12798529 061 PD103 PLUMBING DEMOLITION PLAN - THIRD FLOOR
12798530 062 PP101 SOIL, WASTE AND VENT PIPING PLAN - FIRST FLOOR
12798531 063 PP102 SOIL, WASTE AND VENT PIPING PLAN - SECOND FLOOR
12798532 064 PP103 SOIL, WASTE AND VENT PIPING PLAN - THIRD FLOOR
12798533 065 PP111 DOMESTIC WATER PIPING PLAN - FIRST FLOOR
12798534 066 PP112 DOMESTIC WATER PIPING PLAN - SECOND FLOOR
12798535 067 PP113 DOMESTIC WATER PIPING PLAN - THIRD FLOOR
12798536 068 PP401 ENLARGED PLAN - S.W.&V. PIPING - FIRST FLOOR CENTRAL CORE & MECH RM 148
12798537 069 PP402 ENLARGED PLAN - S.W.&V. PIPING - SECOND FLOOR CENTRAL CORE
12798538 070 PP403 ENLARGED PLAN - S.W.&V. PIPING - THIRD FLOOR CENTRAL CORE
12798539 071 PP404 ENLARGED PLAN - S.W.&V. PIPING - TYP SLEEPING SUITE
12798540 072 PP405 ENLARGED PLAN - WATER PIPING - FIRST FLOOR CENTRAL CORE & MECH RM 148
12798541 073 PP406 ENLARGED PLAN - WATER PIPING - SECOND FLOOR CENTRAL CORE
12798542 074 PP407 ENLARGED PLAN - WATER PIPING - THIRD FLOOR CENTRAL CORE
12798543 075 PP408 ENLARGED PLAN - WATER PIPING - TYP SLEEPING SUITE
12798544 076 PP501 PLUMBING DETAILS
12798545 077 PP601 PLUMBING SCHEDULES
12798546 078 PP602 SOIL, WASTE AND VENT RISERS
12798547 079 PP603 DOMESTIC WATER RISERS
MECHANICAL
12798548 080 M-001 MECHANICAL SYMBOLS AND ABBREVIATIONS
12798549 081 M-002 MECHANICAL GENERAL NOTES
12798550 082 MD101 MECHANICAL DEMOLITION PLAN - FIRST FLOOR
12798551 083 MD102 MECHANICAL DEMOLITION PLAN - SECOND FLOOR
12798552 084 MD103 MECHANICAL DEMOLITION PLAN - THIRD FLOOR
12798553 085 MD401 HVAC DEMOLITION ENLARGED PLANS
12798554 086 MD402 HVAC DEMOLITION ENLARGED PLANS
12798555 087 MH101 HVAC PLAN - FIRST FLOOR
12798556 088 MH102 HVAC PLAN - SECOND FLOOR
12798557 089 MH103 HVAC PLAN - THIRD FLOOR
12798558 090 MH104 HVAC PLAN - ATTIC
12798559 091 MH301 MECHANICAL SECTIONS
12798560 092 MH302 MECHANICAL SECTIONS
12798561 093 MH303 MECHANICAL SECTIONS
12798562 094 MH401 HVAC ENLARGED PLANS
12798563 095 MH402 HVAC ENLARGED PLANS
12798564 096 MH403 HVAC ENLARGED PLANS
12798565 097 MH501 MECHANICAL DETAILS
12798566 098 MH502 MECHANICAL DETAILS
12798567 099 MH503 MECHANICAL DETAILS
12798568 100 MH601 MECHANICAL SCHEDULES
12798569 101 MH701 CHILLED WATER FLOW DIAGRAM
12798570 102 MH702 HOT WATER FLOW DIAGRAM
12798571 103 MI601 MECHANICAL CONTROLS
12798572 104 MI602 MECHANICAL CONTROLS
12798573 105 MP101 HVAC PIPING PLAN - FIRST FLOOR
12798574 106 MP102 HVAC PIPING PLAN - SECOND FLOOR
12798575 107 MP103 HVAC PIPING PLAN - THIRD FLOOR
ELECTRICAL
12798576 108 E-001 ELECTRICAL SYMBOLS LEGEND AND ABBREVIATIONS
12798577 109 ES101 ELECTRICAL SITE PLAN
12798578 110 ED101 ELECTRICAL DEMOLITION PLAN - FIRST FLOOR
12798579 111 ED102 ELECTRICAL DEMOLITION PLAN - SECOND FLOOR
12798580 112 ED103 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR
12798581 113 ED601 ELECTRICAL DEMOLITION DIAGRAM
12798582 114 EL101 ELECTRICAL LIGHTING PLAN - FIRST FLOOR
12798583 115 EL102 ELECTRICAL LIGHTING PLAN - SECOND FLOOR
12798584 116 EL103 ELECTRICAL LIGHTING PLAN - THIRD FLOOR
12798585 117 EL104 ELECTRICAL LIGHTING PLAN - ATTIC
12798586 118 EL501 LIGHTING FIXTURE SCHEDULE AND DETAILS
12798587 119 EL502 LIGHTING DETAILS
12798588 120 EP101 ELECTRICAL POWER PLAN - FIRST FLOOR
12798589 121 EP102 ELECTRICAL POWER PLAN - SECOND FLOOR
12798590 122 EP103 ELECTRICAL POWER PLAN - THIRD FLOOR
12798591 123 EP201 ELECTRICAL EQUIPMENT PLAN - FIRST FLOOR
12798592 124 EP202 ELECTRICAL EQUIPMENT PLAN - SECOND FLOOR
12798593 125 EP203 ELECTRICAL EQUIPMENT PLAN - THIRD FLOOR
12798594 126 EP401 ENLARGED ELECTRICAL POWER PLAN
12798595 127 EP501 ELECTRICAL DETAILS
12798596 128 EP502 ELECTRICAL DETAILS
12798597 129 EP601 ELECTRICAL DIAGRAMS
12798598 130 EP602 ELECTRICAL SCHEDULES
12798599 131 EP603 ELECTRICAL SCHEDULES
12798600 132 EP604 ELECTRICAL SCHEDULES
12798601 133 EP605 MECHANICAL EQUIPMENT CONNECTION SCHEDULE
SHEET INDEX
NAVFAC
DWG NO.
SHEET
COUNT
SHEET
NO. SHEET NAME
GENERAL
12798469 001 GI001 COVER SHEET AND SHEET INDEX
12798470 002 GI002 GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
12798471 003 GI003 CODE/LIFE SAFETY ANALYSIS
12798472 004 GI004 LIFE SAFETY - FLOOR PLANS
12798473 005 GI101 SITE PLAN
12798474 006 GI401 ENLARGED PLAN - EQUIPMENT ENCLOSURE
STRUCTURAL
12798475 007 S-001 GENERAL STRUCTURAL NOTES
12798476 008 S-002 GENERAL STRUCTURAL NOTES
12798477 009 SB101 PARTIAL FOUNDATION AND FLOOR FRAMING PLAN
12798478 010 SB102 PARTIAL ATTIC FRAMING PLANS
12798479 011 SB501 STRUCTURAL DETAILS
ARCHITECTURAL
12798480 012 AD101 DEMOLITION FLOOR PLANS
12798481 013 AD102 DEMOLITION ROOF PLAN
12798482 014 AD401 DEMOLITION ENLARGED PLAN
12798483 015 AE101 FLOOR PLANS
12798484 016 AE131 ROOF PLAN
12798485 017 AE201 EXTERIOR ELEVATIONS
12798486 018 AE401 PARTITION TYPES, TYP MOUNTING HT AND CLEAR FLOOR SPACES
12798487 019 AE402 ENLARGED PLAN - FIRST FLOOR CENTRAL CORE
12798488 020 AE403 ENLARGED PLAN - SECOND FLOOR CENTRAL CORE
12798489 021 AE404 ENLARGED PLANS - THIRD FLOOR CORE AND TYP SLEEPING SUITE
12798490 022 AE405 ENLARGED PLANS - FIRST FLOOR MECHANICAL
12798491 023 AE406 ENLARGED PLANS - SECOND FLOOR MECHANICAL
12798492 024 AE407 ENLARGED PLANS - THIRD FLOOR MECHANICAL
12798493 025 AE408 ENLARGED PLANS - ATTIC FLOOR AND MECHANICAL SHAFT WALL SECTION
12798494 026 AE411 ENLARGED RCP - FIRST FLOOR CENTRAL CORE
12798495 027 AE412 ENLARGED RCP - SECOND FLOOR CENTRAL CORE
12798496 028 AE413 ENLARGED RCP - THIRD FLOOR CORE AND TYP SLEEPING SUITE
12798497 029 AE421 INTERIOR ELEVATIONS
12798498 030 AE422 INTERIOR ELEVATIONS
12798499 031 AE501 MILLWORK DETAILS
12798500 032 AE502 DETAILS
12798501 033 AE503 DETAILS
12798502 034 AE601 DOOR SCHEDULE
12798503 035 AE602 DOOR DETAILS, WINDOW AND LOUVER TYPES
INTERIORS
12798504 036 IN101 FINISH PLANS - OVERALL
12798505 037 IN401 ENLARGED PLANS - FINISHES
12798506 038 IN402 ENLARGED PLANS - FINISHES
12798507 039 IN501 INTERIOR DESIGN DETAILS
12798508 040 IN502 SIGNAGE DETAILS
12798509 041 IN503 SIGNAGE DETAILS
12798510 042 IN601 ROOM FINISH SCHEDULE
12798511 043 IN602 ROOM FINISH SCHEDULE
12798512 044 IN603 SIGNAGE SCHEDULE
12798513 045 IN604 SIGNAGE SCHEDULE
12798514 046 IN605 SIGNAGE SCHEDULE
12798515 047 IF101 FF&E PLANS - OVERALL
12798516 048 IF401 ENLARGED PLANS - FF&E
12798517 049 IF402 ENLARGED PLANS - FF&E
FIRE PROTECTION
12798518 050 FA001 FIRE ALARM GENERAL NOTES
12798519 051 FA101 FIRE ALARM-FIRST FLOOR PLAN
12798520 052 FA102 FIRE ALARM-SECOND FLOOR PLAN
12798521 053 FA103 FIRE ALARM-THIRD FLOOR PLAN
12798522 054 FX001 FIRE PROTECTION GENERAL NOTES
12798523 055 FX101 FIRE PROTECTION-FIRST FLOOR PLAN
12798524 056 FX102 FIRE PROTECTION-SECOND FLOOR PLAN
12798525 057 FX103 FIRE PROTECTION-THIRD FLOOR PLAN
SHEET REMOVED FROM SET
R
O O
F N
I C
/0 7/
SEALSEALSEALSEAL
GENERAL SYMBOLS
SCALE:
B2
VIEW NAME
1/8" = 1'-0"
A4
EARTH
EARTH GRAVEL
CONCRETE
METALS
BRICK
CMU
TILE
STONE
WOOD
GYPSUM
GLASS
INSULATION
REGULAR
STEEL ALUMINUM
FACE COMMON
CMU
CERAMIC
MARBLE LIMESTONE
FINISH BLOCKING
PLASTER OR GWB
LARGE SCALE SMALL SCALE
BATT OR
LOOSE
RIGID
SURFACE
DETAIL TITLE
BUILDING
SECTION
WALL SECTION
EXTERIOR /
INTERIOR
ELEVATION
INTERIOR
MULTI-VIEW
ELEVATION
MATERIALS REFERENCE
DETAIL
SECTION
AE402
C4
AE201
A1
AE305
A1
AE305
A1
AE305
AE505
C3
A3
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
NORTH ARROW
N
PLAN NORTH
TRUE NORTH
S
B
5E
ACTUAL SQ. FT.
PROGRAMMED SQ. FT.
ROOM NUMBER
DOOR NUMBER
KEYNOTE
WALL TYPE
REVISION NUMBER
ELEVATION INDICATION
COLUMN GRID
IDENTIFICATION
WINDOW TYPE
?A1
ROOM NAME
A505B
200 SF / 150 SF
W1
XXX FURNITURE AND EQUIPMENT TAG
D
MATCHLINE
FINISH , FINISH
MATERIAL FINISH EXTENTS
LOUVER TYPEL1
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/2
/2
:2
:4
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
GI002
G E
N E
R A
L N
O T
E S
S
Y M
B O
L S
A N
D A
B B
R E
V
IA
T
IO
N S
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
12798470
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
KSVNP EJD
STOR STORAGE
STR STRUCTURAL
SUSP SUSPENDED
SW SWITCH
SWGR SWITCHGEAR
SYM SYMMETRICAL
T
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TC TOP OF CURB
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TERR TERRAZZO
TLT TOILET
TOPO TOPOGRAPHY
TOS TOP OF STEEL
TOW TOP OF WALL
TP TOP OF PAVEMENT
TRANS TRANSVERSE
TS TRANSITION STRIP
TYP TYPICAL
U
UC UNDERCUT
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UR URINAL
UV UNIT VENTILATOR
V
V VOLT
VAV VARIABLE AIR VOLUME
VC VERTICAL CURVE
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W
W WATT / WATER
W/ WITH
W/O WITHOUT
WAGD WASTE ANESTHESIA GAS DISPOSAL
WC WATER CLOSET
WD WOOD
WDW WINDOW
WH WATER HEATER / WALL HYDRANT
WP WEATHERPROOF
WPFG WATERPROOFING
WS WATER STOP
WT WEIGHT / WINDOW TREATMENT
WWF WELDED WIRE FABRIC
X
XFMR TRANSFORMER
Y
YD YARD
YH YARD HYDRANT
PLAS PLASTER
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PROJ PROJECTION
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT OF TANGENCY
PTVC POINT OF VERTICAL CURVATURE
PVC POLYVINYL CHLORIDE
PVI POINT OF VERTICAL INTERSECTION
PVT POINT OF VERTICAL TANGENCY
Q
QT QUARRY TILE
R
R RADIUS / REGISTER
RA RETURN AIR
RB RESILIENT BASE
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REFL REFLECTED
REG REGISTER
REINF REINFORCED
REQD REQUIRED
REV REVERSE / REVISION
RF RETURN FAN
RGS RIGID GALVANIZED STEEL
RH ROOF HOOD / RELATIVE HUMIDITY / REHEAT
RHC REHEAT COIL
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RS RESILIENT SHEET
RT RESILIENT TILE
S
S STAIR / STAIN / SURFACE / SANITARY
SA SUPPLY AIR / SOUND ATTENUATOR
SAN SANITARY
SCH SCHEDULE
SD SMOKE DAMPER / SUB DRAIN / STORM SEWER
SECT SECTION
SF SUPPLY FAN
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SP SUMP PUMP
SPEC SPECIFICATIONS
SQ SQUARE
SS SERVICE SINK / SANITARY SEWER
SSO STORM SEWER OVERFLOW
SSTL STAINLESS STEEL
STA STATION
STD STANDARD
STE STANDARD TAPERED END
STIFF STIFFENER
STIR STIRRUP
STL STEEL
M
M METER
M2 SQUARE METER
M3 CUBIC METER
MA MEDICAL AIR
MAINT MAINTENANCE
MAR MARBLE
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MBH 1000 BTUH
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MET METAL
MFR MANUFACTURER
MG MOTOR GENERATOR / MEDICAL GAS
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MILLIMETER
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
MULL MULLION
MV MEDICAL VACUUM
N
N NITROGEN
N2O NITROUS OXIDE
NEC NATIONAL ELECTRICAL CODE
NFPA NATIONAL FIRE PROTECTION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
O/S OFFSET
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OX OXYGEN
OZ OUNCE
P
P PAINT / PUMP / PENDANT
PA PASCAL
PART PARTITION
PAVT PAVEMENT
PC POINT OF CURVATURE
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERP PERPENDICULAR
PHC PREHEAT COIL
PHVAC PLUMBING, HEATING, VENTILATING AND AIR
CONDITIONING
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PKG PARKING
PL PLASTIC LAMINATE / PROPERTY LINE / PLATE
HK2E HOOK TWO ENDS
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HT HEIGHT
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HOT WATER
HWC HOT WATER CIRCULATING
HZ HERTZ
I
IA INSTRUMENT AIR
IC INTERCOM
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IN INCH
INSUL INSULATION
INT INTERIOR
J
JAN JANITOR
JB JUNCTION BOX
JP JOCKEY PUMP
JST JOIST
JT JOINT
K
KC MIL THOUSAND CIRCULAR MILS
KCJ KEYED CONSTRUCTION JOINT
KIT KITCHEN
KPA KILOPASCALS
KS KITCHEN SINK
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATTS
L
L LITER
LA LABORATORY AIR
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LIN LINEAR
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMU LIGHTWEIGHT MASONRY UNITS
LONG LONGITUDINAL
LPM LITERS PER MINUTE
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LV LABORATORY VACUUM
LVL LEVEL
LVT LUXURY VINYL TILE
EQ EQUAL
EQUIP EQUIPMENT
ET EXPANSION TANK
EVAC MEDICAL GAS EVACUATION
EW EACH WAY
EWC ELECTRICAL WATER COOLER
EWH ELECTRICAL WATER HEATER
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPN EXPANSION
EXT EXTERIOR
F
F FIRE MAIN
FA FIRE ALARM
FCU FAN COIL UNIT
FD FLOOR DRAIN / FIRE DAMPER
FD / SD COMBINATION FIRE AND SMOKE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDR FEEDER
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FL FLOOR
FM FORCE MAIN / FACTORY MUTUAL
FP FIREPROOFING / FIRE PUMP
FPM FEET PER MINUTE
FR FIRE RATED
FRP FIBERGLASS REINFORCED PLASTIC
FS FLOW SWITCH
FT FEET
FTG FOOTING
FVC FIRE VALVE CABINET
G
G GAS / GRILLE
GA GAGE
GALV GALVANIZED
GB GRAB BAR
GBD GRAVITY BACKDRAFT DAMPER
GEN GENERATOR
GFRC GLASS FIBER REINFORCED CONCRETE
GI GALVANIZED IRON
GL GLASS
GLB GLASS BLOCK
GP GLAZED PAINT
GPM GALLONS PER MINUTE
GR GRADE
GRV GRAVITY ROOF VENTILATOR
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HB HOSE BIBB
HC HEATING COIL
HDNR HARDENER
HDW HARDWARE
HDWD HARDWOOD
HK1E HOOK ONE END
CMP CORRUGATED METAL PIPE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT / CARBON MONOXIDE
CO2 CARBON DIOXIDE
COL COLUMN
COMB COMBINATION / COMBINE
COMP COMPRESSIBLE
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS / CONTINUATION
CONTR CONTRACTOR
CORR CORRIDOR
CP CEMENT PIPE
CPT CARPET
CS CONCRETE SEALER
CSF CUBIC FEET PER SECOND
CT CERAMIC TILE / COOLING TOWER
CTR CENTER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CUYD CUBIC YARD
CW COLD WATER
D
D DRAIN / DIFFUSER
DA DENTAL AIR
DBL DOUBLE
DEPR DEPRESSED
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DISP DISPENSER
DIST DISTRIBUTION
DK DECK
DL DEAD LOAD
DN DOWN
DO DITTO
DPR DAMPER
DR DOOR
DS DOWNSPOUT
DV DENTAL VACUUM
DWG DRAWING
DWL DOWEL
DWP DOMESTIC WATER PUMP
E
EA EACH / EXHAUST AIR
EF EACH FACE / EXHAUST FAN
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMBED EMBEDMENT
EMD ESTIMATED MAXIMUM DEMAND
EMT ELECTRICAL METAL TUBING
EP EPOXY PAINT
A
A/C AIR CONDITIONING
AB ANCHOR BOLT / AIR BLENDER
ABS ACRYLONITRILE-BUTADIENE-STYRENE
AC ALTERNATING CURRENT / AIR COMPRESSOR
ACP ASBESTOS CEMENT PIPE
ACU AIR CONDITIONING UNIT
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJACENT / ADJUSTABLE
ADR ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATELY
APT APARTMENT
ARCH ARCHITECT(URAL)
ASPH ASPHALT
ATB AIR TERMINAL BOX
ATC ACOUSTICAL TILE CEILING
ATD AIR TRANSFER DUCT
ATU AIR TERMINAL UNIT
AUX AUXILIARY
AVG AVERAGE
AZ AZIMUTH
B
BB BALLED AND BURLAPPED
BD BOARD
BDD BACK DRAFT DAMPER
BE BOTTOM ELEVATION
BL BUILDING LINE
BLDG BUILDING
BLKG BLOCKING
BM BENCH MARK / BEAM
BR BARE ROOT
BRG BEARING
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C/C CENTER TO CENTER
CAB CABINET
CB CIRCUIT BREAKER / CATCH BASIN
CC COOLING UNIT
CE COVER ELEVATION
CEM CEMENT
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
CH CHILLER
CI CURB INLET / CAST IRON
CIP CAST IRON PIPE
CJ CONTROL JOINT OR CONTRACTION JOINT
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CM CENTIMETER
CMH CUBIC METER PER HOUR
ABBREVIATIONS
GENERAL NOTES ARCHITECTURAL
A. PARTITION AND WALLS
1 DIMENSIONS ARE TO FINISH FACE OF PARTITIONS, FACE OF CMU, FACE OF
EXISTING FINISH OR CENTER LINE OF COLUMNS UNLESS SHOWN OR NOTED
OTHERWISE.
2 PARTITIONS SHALL BE 3-5/8 INCH METAL STUDS AT 16 INCHES ON CENTER WITH
5/8" GYPSUM WALLBOARD EACH SIDE, UNLESS NOTED OTHERWISE.
3 THICKNESS OF CONCRETE MASONRY UNITS (CMU) AND LIGHT WEIGHT MASONRY
UNITS (LMU) PARTITIONS ARE NOMINAL UNLESS NOTED OTHERWISE.
4 EXTERNAL CORNERS OF BLOCK WALLS AND PARTITIONS SHALL BE BULLNOSE.
5 ALL PARTITIOINS SHALL EXTEND FROM FLOOR TO UNDER SIDE OF DECK ABOVE
EXCEPT WHERE NOTED OR SHOWN OTHERWISE.
6 EXTEND ALL SOUND RATED PARTITIONS TO THE UNDER SIDE OF DECK ABOVE TO
PREVENT SOUND TRANSMISSION. FURNISH 4-1/4 POUNDS DENSITY GLASS FIBER
INSULATION SHAPED TO FIT THE VOID ABOVE THE PARTITION WHERE AIR-BORNE
SOUND CAN PENETRATE SPACES.
7 FOR LOCATIONS OF FIRE-RATED PARTITIONS SEE CODE PLANS IN THE G SERIES.
8 CONTROL JOINTS SHALL BE PROVIDED ABOVE DOORS AT EACH SIDE IN STUD
AND GWB PARTITIONS.
9 EXPANSION JOINTS AT ALL FLOORS, CEILINGS AND WALLS THAT ARE EXPOSED
TO VIEW SHALL BE COVERED WITH EXPANSION JOINT COVERS APPROPRIATE
FOR FINISHED SURFACES.
10 ALL COLUMNS WITHIN FINISHED SPACES SHALL BE FINISHED WITH SAME
MATERIALS SCHEDULED AT WALLS UNLESS OTHERWISE SHOWN OR DETAILED.
11 PROVIDE ALL WALL AND FLOOR OPENINGS FOR MECHANICAL AND ELECTRICAL
ITEMS. ALL OPENINGS MORE THAN 16 INCHES WIDE IN MASONRY PARTITIONS
SHALL HAVE LINTELS AS SCHEDULED ON THE STRUCTURAL DRAWINGS.
12 FOR WALL PARTITION TYPES, SEE SHEET AE401.
13 EXTERIOR FACE BRICK SHALL EXTEND A MINIMUM OF 8 INCHES BELOW GRADE.
14 EXTERIOR CAST-IN-PLACE CONCRETE WALLS ABOVE FINISH GRADE SHALL BE
PAINTED.
15 WHEREVER GWB IS CALLED FOR, USE HIGH IMPACT GWB.
16 PROVIDE AND INSTALL 50 SQUARE FEET OF EIFS.
17 USE THIN-SET TILE APPLICATION AS INDICATED AND SPECIFIED.
B. DOORS AND FRAMES
1 PROVIDE LABELS ON DOORS AND FRAMES WHERE SCHEDULED.
2 INSTALL CONTINUOUS CAULKING AROUND METAL FRAMES UNLESS NOTED
OTHERWISE.
3 HOLLOW METAL FRAMES SHALL BE ANCHORED TO THE STRUCTURAL FLOOR
WITH A MINIMUM OF TWO (2) ANCHOR BOLTS.
4 HOLLOW METAL FRAMES IN MASONRY WALLS SHALL BE FILLED WITH GROUT.
5 HOLLOW METAL FRAMES IN STUD PARTITIONS SHALL BE FILLED WITH GROUT TO
THE DEPTH OF THE FRAME ANCHOR FULL HEIGHT FOR SOUND DAMPENING
BEFORE SETTING IN PLACE.
6 INSTALL CASING BEADS AND CAULK WHERE PLASTER ABUTS METAL FRAMES.
7 DOOR TYPES AND SIZES ARE SHOWN ON SHEET AE601.
C. MISCELLANEOUS
1 PRESSURE WASH ALL EXTERIOR MASONRY AND CONCRETE SURFACES.
2 ALL WALL HUNG CASEWORK, GRAB BARS, DOOR HARDWARE AND EQUIPEMENT
ATTACHED TO WALLS SHALL BE ANCHORED TO 2x6 FIRE RATED WOOD BLOCKING
ANCHORED BETWEEN STUDS UNLESS OTHERWISE NOTED. BLOCKING SHALL BE
CONTINUOUS AND LOCATED BOTH AT BOTTOM AND TOP OF EQUIPMENT.
3 REMOVE AND REPLACE ALL EXTERIOR SEALANT AND BACKER RODS / FILLER
STRIPS.
A
M E
N D
M E
N T
/1
8/
SEALSEALSEAL
CODE ANALYIS LEGEND
OCCUPANCY
B
AREA NAME
150 SF 00
00 OCC.
1 HOUR FIRE BARRIER PER IBC SECTION 706. OPENINGS
FIRE RATED FOR 45 MINUTES UNLESS SHAFT, EXIT
ENCLOSURE, OR EXIT PASSAGEWAY WALLS WHICH
REQUIRE 1 HOUR RATED OPENINGS.
EGRESS PATH WITH NAME, SEGMENT LENGTH, AND
DIRECTION INDICATED
EXIT INDICATOR BASIC: WITH NAME OF EXIT AND TOTAL
OCCUPANTS EXITING INDICATED
IBC OCCUPANCY GROUP
ROOM (NET) AND AREA (GROSS) TAGS INDICATING SQUARE
FOOTAGE / OCCUPANCY LOAD FACTOR, AND RESULTING
OCCUPANCY BELOW
1/2 HOUR FIRE PARTITION PER NFPA 101 SECTION 28.7.2.
OPENINGS FIRE RATED FOR 20 MINUTES AND SHALL NOT
BE REQUIRED TO BE SELF-CLOSING UNLESS OPENING TO
EXTERIOR EXIT ACCESS BALCONIES, WHICH SHALL BE
SELF-CLOSING AND SELF-LATCHING
FB
FB
PATH A
165 EXIT EXIT F
0.2 X 165 = 33" MIN
ACTUAL = 34.25"
EXIT INDICATOR ADVANCED: WITH NAME OF EXIT, TOTAL
OCCUPANTS EXITING INDICATED, SIZE OF OPENING VS
ACUTAL OPENING WIDTH
165 EXIT EXIT F
SEMI-RECESSED TYPE FIRE EXTINGUISHER CABINETFEC-1
SURFACE MOUNT TYPE FIRE EXTINGUISHER CABINETFEC-2
CODE DATA
1.1 APPLICABLE CODES & STANDARDS
1.1.1 UFC 1-200-01 20 JUNE 2016, INCLUDING CHANGE 1, 1 FEBRUARY 2018
1.1.3 UFC 3-600-01, 8 AUGUST 2016, INCLUDING CHANGE 2, 25 MARCH 2018
1.1.4 UFC 4-510-01, 1 MAY 2016, INLCUDING CHANGE 2, NOVEMBER 2017
1.1.5 INTERNATIONAL BUILDING CODE, 2015 (IBC)
1.1.6 ARCHITECTURAL BARRIERS ACT (ABA) ACCESSIBILITY STANDARDS
1.1.7 NFPA 101, LIFE SAFETY CODE, 2018
1.1.8 NFPA 80, FIRE DOORS AND FIRE WINDOWS, 2019
1.1.9 NFPA 13R, INSTALLATION OF SPRINKLER SYSTEMS, 2019
1.1.10 NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2019
1.2 OCCUPANCY CLASSIFICATION
IBC CHAPTER 3
1.2.1 GROUP R-2 - RESIDENTIAL
NFPA 101 CHAPTER 6
1.2.4 HOTELS AND DORMITORIES
1.3 FIRE PROTECTION SYSTEMS
1.3.1 NFPA 13R AUTOMATIC SPRINKLER SYSTEM (UFC 3600-01, 4-2.2 & UFC
3-600-01, 6-1.1)
1.3.2 FIRE ALARM EVACUATION SYSTEM (UFC 3-600-01, 5-3.1)
1.3.3 MASS NOTIFICATION SYSTEM (UFC 4-010-01 & 4-021-01)
1.4 BUILDING HEIGHT & AREA LIMITATIONS - IBC CHAPTER 5
1.4.1 SECTION 508.3 RESIDENTIAL OCCUPANCIES: MIXED NON-SEPARATED
1.4.2 IBC TABLE 504.3 ALLOWABLE HEIGHT = 60'-0", ACTUAL = 35'-0"
1.4.3 IBC TABLE 504.4 ALLOWABLE STORIES = 4, ACTUAL = 3
1.4.4 IBC TABLE 506.2 ALLOWABLE AREA (AT) = 16,000 SF
AREA INCREASE DUE TO OPEN FRONTAGE (AF) = 12,000 SF
ALLOWABLE AREA PER FLOOR (AA) = AT + AF = 28,000
ACTUAL = 12,733 SF
1.5 EXISTING CONSTRUCTION TYPE - IBC CHAPTER 6 (NFPA 101)
1.5.1 TYPE III-B (332)
1.6 FIRE RESISTIVE REQUIREMENTS - IBC CHAPTER 6
1.6.1 PRIMARY STRUCTURAL FRAME = 0-HOUR RATING
1.6.2 BEARING WALLS, EXTERIOR =2-HOUR RATING
1.6.3 BEARING WALLS, INTERIOR = 0-HOUR RATING
1.6.4 NON-BEARING WALLS & PARTITIONS, EXTERIOR = 0-HOUR RATING
1.6.5 NON-BEARING WALLS & PARTITIONS, INTERIOR = 0-HOUR RATING
1.6.6 FLOOR CONSTRUCTION = 0-HOUR RATING
1.6.7 ROOF CONSTRUCTION = 0-HOUR RATING
1.7 MEANS OF EGRESS - NFPA 101, CHAPTER 7, 28
1.7.1 EGRESS CAPACITY CORRIDORS - NFPA 101 TABLE 7.3.3.1 = 0.2" PER
OCCUPANT
1.7.2 EGRESS CAPACITY STAIRWAYS - NFPA 101 TABLE 7.3.3.1 = 0.3" PER
OCCUPANT
1.7.3 MINIMUM NUMBER OF EXITS - NFPA 101 7.4.1.2 = 2 REQUIRED, 2 PROVIDED
1.7.4 MINIMUM WIDTH OF DOORS - NFPA 101 7.2.1.2.3.2 = 32" MINIMUM, 34"
PROVIDED
1.7.5 COMMON PATH OF TRAVEL NFPA 101 28.2.5.4 (HOTELS & DORMITORIES) =
50' MAXIMUM
1.7.6 TRAVEL DISTANCE - NFPA 101 28.2.6 (HOTELS & DORMITORIES) = 125'
MAXIMUM WITHIN A GUEST ROOM TO CORRIDOR DOOR. 200' MAXIMUM
FROM GUEST ROOM DOOR TO EXIT
1.7.7 ARRANGEMENT OF MEANS OF EGRESS - NFPA 101 7.5.1.3.3 & 7.5.1.3.6 =
MINIMUM SEPERATION BETWEEN AT LEAST TWO EXITS TO BE NOT LESS
THAN ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
DIMENSION
1.7.8 DEAD END CORRIDOR - NFPA 101 28.2.5.6 (HOTELS & DORMITORIES) = 30'
MAXIMUM
1.8 SEPARATION REQUIREMENTS
1.8.1 EACH SLEEPING ROOM SHALL BE SEPARATED FROM OTHER SLEEPING ROOMS
BY WALLS AND FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A FIRE
RESISTANCE RATING OF NOT LESS THAN ½ HOUR - NFPA 101 28.3.7.2
1.8.2 DOORS THAT OPEN ONTO EXTERIOR EXIT ACCESS BALCONIES SHALL BE SELF-
CLOSING AND SELF-LATCHING - NFPA 101 28.3.6.2.3
1.8.3 EXTERIOR WAYS OF EXIT ACCESS: EXTERIOR EXIT ACCESS BALCONIES REQUIRE
NO SEPARATION FROM THE INTERIOR OF THE BUILDING WHEN DEAD ENDS ON
THE EXTERIOR EXIT ACCESS DO NOT EXCEED 20 FT. - NFPA 101 7.5.3.3
1.8.4 OUTSIDE STAIR SERVING AN EXIT ACCESS BALCONY THAT HAS TWO REMOTE
OUTSIDE STAIRWAYS SHALL BE PERMITTED TO EB UNPROTECTED - NFPA 101
7.2.2.6.3.1 EXCEPTION (1)
1.8.5 HAZARDOUS AREAS: LAUNDRY ROOMS OVER 100 SQ FT AND BOILER & FUEL-
FIRED EQUIPMENT ROOMS WILL BE SEPARATED FROM OTHER AREAS BY 1-HOUR
FIRE-RATED PARTITIONS AND SPRINKLERS - NFPA 101 TABLE 28.3.2.2.2. STORAGE
ROOMS OVER 24 SQ FT WILL BE SEPARATED FROM OTHER AREAS BY
PARTITIONS THAT RESIST PASSAGE OF SMOKE - NFPA 101 TABLE 28.3.2.2.2
1.9 FIRE DEPARTMENT (EMERGENCY) VEHICLE ACCESS
1.9.1 RESIDENTIAL BUILDING SHALL BE PROVIDED WITH ALL-WEATHER GROUND
ACCESS TO 3 SIDES OF THE BUILDING WITH A MINIMUM OF 2 SIDES HAVING
ACCESS TO SLEEPING ROOMS TO ALLOW EMERGENCY VEHICLES UNIMPEDED
ACCESS TO THE BUILDING. ALL-WEATHER GROUND ACCESS MUST BE PAVED,
START FROM THE ROAD, AND TERMINATE NO FARTHER THAN 33 FT FROM THE
BUIDING - UFC 3-600-01 2-10.1
1.9.2 ALL FORCE PROTECTION EQUIPMENT, SUCH AS BOLLARD OR GATES, MUST NOT
REQUIRE MORE THAN ONE PERSON TO REMOVE OR OPEN. ACCESS MAY
REQUIRE FIRE APPARATUS TO DRIVE OVER A CURB. ANY LOCKING DEVICE
CONTROLLING VEHICLE ACCESS MUST BE UNDER CONTROL OF THE FIRE
DEPARTMENT OR 24-HOUR SECURITY PERSONNEL LOCATED AT THE FACITILIY.
DIMENSIONS OF FIRE LANES AND TURNAROUNDS SHALL COMPLY WITH NFPA 1,
UNIFORM FIRE CODE. - UFC 3-600-01 2-10.2
1.9.3 ALL FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH SUITABLE ALL-
WEATHER GROUND ACCESS SURFACE FOR PUMPER APPARATUS WITHIN 150 FT -
UFC 3-600-01 2-10.4
1.9.4 FIRE DEPARTMENT ACCESS ROADS SHALL BE PROVIDED SUCH THAT ANY
PORTION OF THE FACILITY OR ANY PORTION OF THE EXTERIOR WALL OF THE
FIRST STORY OF THE BUILDING IS LOCATED NOT MORE THAN 450 FT FROM THE
FIRE DEPARTMENT ACCESS ROADS AS MEASURED BY AN APPROVED ROUTE
AROUND THE EXTERIOR OF THE BUILDING - NFPA 1 18.2.3.2.2.1
1.10 ADDITIONAL LIFE SAFETY CRITERIA
1.10.1 EMERGENCY LIGHTING SYSTEMS SHALL BE PROVDED IN ACCORDANCE WITH
NFPA 101 7.9
1.10.2 MEANS OF EGRESS SHALL BE PROVDED WITH SIGNS IN ACCORDANCE WITH
NFPA 101 7.10. SIGNS MUST HAVE LETTERING ON AN OPAQUE BACKGROUND.
INTERNALLY ILLUMINATED SIGNS MUST BE LIGHT EMITTING DIODE (LED) TYPE,
ELECTROLUMINESCENCE (LEC), OR COLD CATHODE TYPE. INCANDESCENT
FIXTURES ARE NOT PERMITTED. RADIOLUMINOUS EXIT SIGNS ARE NOT
PERMITTED - UFC 3-600-01 2-5.2
1.10.3 PORTABLE FIRE EXTINGUISHERS ARE NOT REQUIRED IN SPRINKLERED HOTEL
AND DORMITORIES OCCUPANCIES, PROVIDED IN LAUNDRY AND OTHER
HAZARDOUS AREAS - NFPA 101 28.3.5.8
PLAN
NORTH
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/1
/2
:5
:0
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
GI003
C O
D E
/L
IF
E S
A F
E T
Y A
N A
L Y
S
IS
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
12798471
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
MARMAR NSJ
LIFE SAFETY ANALYSIS - AREA SCHEDULE
NAME AREA USE CLASSIFICATION (2015 IBC, TABLE 1004.1.2)
DESIGN OCCUPANT LOAD
LOAD
FACTOR
GROSS OR
NET
OCCUPANTS
FIRST FLOOR
Mechanical 1648 SF Accessory Storage Areas, Mechanical Equipment Room 300 SF Gross 6
Assembly 405 SF Assembly w/o Fixed Seats - Unconcentrated (Tables and Chairs) 15 SF Net 27
Business 1399 SF Business Areas 100 SF Gross 15
SECOND FLOOR
Mechanical 1629 SF Accessory Storage Areas, Mechanical Equipment Room 300 SF Gross 6
Residential 1236 SF Residential 200 SF Gross 7
THIRD FLOOR
Mechanical 1624 SF Accessory Storage Areas, Mechanical Equipment Room 300 SF Gross 6
Assembly 618 SF Assembly w/o Fixed Seats - Unconcentrated (Tables and Chairs) 15 SF Net 42
Residential 659 SF Residential 200 SF Gross 5
Grand total 9219 SF 114
SLEEPING ROOMS ARE APPROX. 250 SQ FT PER ROOM WITH 2 PERSONS PER ROOM.
FIRST FLOOR = 46 SLEEPING ROOMS X 2 PERSONS = 76 PERSONS OCCUPANT LOAD + 24 = 116 TOTAL OCCUPANTS SECOND FLOOR = 48 SLEEPING ROOMS X 2 PERSONS = 96 PERSONS OCCUPANT LOAD + 13 = 109 TOTAL OCCUPANTS THIRD FLOOR = 48 SLEEPING ROOMS X 2 PERSONS = 96 PERSONS OCCUPANT LOAD + 13 = 109 TOTAL OCCUPANTS 334 TOTAL OCCUPANTS
SCALE: NTS
A1
CODE SITE PLAN
824 SF
Mechanical
1236 SF
Residential805 SF
Mechanical
OCCUPANCY
R2 F
E C
-2
F E
C -2
0.
X
M
IN
A C
T U
A L
6"
0.2 X 35 = 7" MIN
ACTUAL = 32"
0.2 X 35 = 7" MIN
ACTUAL = 32"
FEC-1
PATH 1 - SECOND
FL
NFPA 101 Use Classification (Ch. 7)
Accessory Storage Areas, Mechanical Equipment Room
Residential
FEC-1
1358 SF
Business
820 SF
Mechanical
827 SF
Mechanical
OCCUPANCY
R2
F E
C -2
F E
C -2
0.
X
.4
M
IN
A C
T U
6"
0.
X
.4
M
IN
A C
T U
6"
COMMON PATH
NFPA 101 Use Classification (Ch. 7)
Accessory Storage Areas, Mechanical Equipment Room
Assembly w/o Fixed Seats - Unconcentrated (Tables and Chairs)
Business Areas
405 SF
Assembly
FEC-1
618 SF
Assembly
822 SF
Mechanical
802 SF
Mechanical
OCCUPANCY
R2
F E
C -2
F E
C -2
0.
X
M
IN
A C
T U
6"
0.2 X 35 = 7" MIN
ACTUAL = 32"
0.2 X 35 = 7" MIN
ACTUAL = 32"
FEC-1
PATH 2 - THIRD
FL
NFPA 101 Use Classification (Ch. 7)
Accessory Storage Areas, Mechanical Equipment Room
Assembly w/o Fixed Seats - Unconcentrated (Tables and Chairs)
Residential
614 SF
Residential
N
TRUE
NORTH
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/1
/2
:5
:1
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
GI004
L
IF
E S
A F
E T
Y
F L O
O R
P L A
N S
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
12798472
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
EWMMAR NSJ
SCALE: 1/16" = 1'-0"
B1
SECOND FLOOR LIFE SAFETY PLAN
SCALE: 1/16" = 1'-0"
A1
FIRST FLOOR LIFE SAFETY PLAN
SCALE: 1/16" = 1'-0"
D1
THIRD FLOOR LIFE SAFETY PLAN
EGRESS PATH SCHEDULE
PATH NAME TRAVEL DISTANCE
MAXIMUM
ALLOWABLE
COMMON PATH 37'-1" 50'
PATH 1 - SECOND FL 181'-1" 200'
PATH 2 - THIRD FL 181'-1" 200'
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
E S
T
BUILDING 4311
BUILDING 4313
EQUIPMENT
ENCLOSURE
GI401
B1
AS01
EQUIPMENT
ENCLOSURE
AS04 AS04
GENERAL SITE NOTES
1. TRIM BRANCHES OF TREES DIRECTLY ADJACENT TO THE BUILDING. ALL
BRANCHES 2 INCHES AND SMALLER WILL BE TRIMMED TO A HEIGHT OF 8’-0”.
2. REMOVE ROOTS OF DEAD TREES.
3. REMOVE AND REPLACE DAMAGED SIDEWALKS DIRECTLY ADJACENT TO THE
BUILDING.
FIRE HYDRANT
SITE LEGEND
N
TRUE
NORTH
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/1
/2
:5
:1
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
GI101
S
IT
E P
L A
N
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
12798473
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
KSVNP EJD
SCALE: 1" = 50'-0"
C1
SITE PLAN
SCALE : 1" = 50'-0"
0 50' 100'
KEYNOTE LEGEND
KEY DESCRIPTION
AS01 SCOPE OF WORK BOUNDARY/CONTRACTOR FENCE
AS04 REMOVE EXISTING TREE AND ROOTS. RESTORE GRADE TO MATCH ADJACENT
GRADE.
SEALSEAL
EQUIPMENT ENCLOSURE GENERAL NOTES
1. REPAIR DAMAGE TO ENCLOSURE WALL.
2. PROVIDE METAL COPING TO TOP OF THE ENCLOSURE WALL.
3. REPLACE METAL GATES AND HARDWARE.
4. REPOINT WALL FOR AREAS WITH CRACKED MORTAR JOINTS OR WALL EROSION
GREATER THAN 1/4"
5. REMOVE THE MORTAR TO A MINIMUM OF 3/4" DEEP. REPACK THE JOINTS AND
TOOL TO MATCH EXISTING CONSTRUCTION.
6. REMOVE AND REPLACE ANY CRACKED BRICKS AND BRICKS DAMAGED FROM
MORTAR REMOVAL± 8'-0"
GI401A1
GI401A2
AS02
D1
GI401
1"
M
IN
EXISTING BRICK MASONRY WALL
24 GAUGE ALUMINUM-ZINC
COPING WITH KYNAR
COATING AND 24 GAUGE
ALUMINUM-ZINC CONTINUOUS
CLEAT OF EACH SIDE. COLOR
SHALL MATCH ROOF COLOR
OF THE BUILDING SERVED
M
IN
/2
NEW 2X8 PRESERVATIVE
TREATED WOOD BLOCKING
ANCHOR TO EXISTING
CONCRETE CAP BLOCK
WITH 1/2" ⌀ EPOXY
ANCHOR AT 32" ON CENTER
EXISTING CONCRETE
CAP BLOCK
EXISTING PILASTER BEYOND
PROVIDE SELF-ADHERING
MEMBRANE BETWEEN
PRESERVATIVE TREATED
LUMBER AND ALL METAL
COMPONENTS, TYP
N
TRUE
NORTH
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/1
/2
:5
:1
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
GI401
E N
L A
R G
E D
P L A
N
E Q
U
IP
M E
N T
E N
C L O
S U
R E
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
12798474
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
KSVNP EJD
SCALE : 1" = 50'-0"
0 50' 100'
KEYNOTE LEGEND
KEY DESCRIPTION
AS02 EXISTING GATE AND HARDWARE: POWER TOOL CLEAN IN ACCORDANCE WITH
SSPC-SP3, PRIME AND PAINT IN ACCORDANCE WITH SPECIFICATION SECTION 09 90
00.
SCALE: 1/4" = 1'-0"
B1
ENLARGED PLAN OF EQUIPMENT ENCLOSURE
1/2'
SCALE : 1 1/2" = 1'-0"
0 1' 1 1/2'
SCALE: 12" = 1'-0"
A1
PHOTO
SCALE: 12" = 1'-0"
A2
PHOTO
SCALE: 1 1/2" = 1'-0"
D1
SCREEN WALL METAL CAP
IF SHEET MEASURES LESS THAN 22" X 34" IT IS A
REDUCED PRINT. REDUCE SCALE ACCORDINGLY
D
C
B
A
DES DRW CHK
SHEET OF
2 3 4 5
1 2 3 4 5
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D
C
B
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
APPROVED
FOR COMMANDER NAVFAC
ACTIVITY
SATISFACTORY TO DATE
A/E INFO
SEAL
AS NOTED
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
/1
/2
:5
:3
A M
C
U s e rs \k s h e n
\D o c u m e n ts
\A u to d e s k \R e v it
P ro je c ts
\B E
Q
-A
IS
k s h e n .r v t
100% CD - SEPTEMBER 2019
L A
D J o b N o -1
-0
S-001
G E
N E
R A
L S
T R
U C
T U
R A
L N
O T
E S
R E
P A
IR
S
T O
B E
Q
10 Tenth Street N.E., Suite 200 Atlanta, GA 30309 Tel 404.874.8333 Fax 404.874.8330
6970752
C H
E R
R Y
P O
IN
T
N
C
12798475
N A
V F
A C
M
ID
-A T
L A
N T
IC
M a ri n e C o rp s A ir S ta ti o n
M C
A S
ERGERG QTL
30. REINFORCEMENT EMBEDDED IN GROUT SHALL HAVE A THICKNESS OF GROUT BETWEEN THE REINFORCEMENT AND MASONRY UNITS NOT LESS THAN 1/2 INCH.
29. CLEAR COVER FROM THE EXTERIOR MASONRY SURFACE TO THE OUTERMOST SURFACE OF THE REINFORCEMENT SHALL BE 2 INCHES.
28. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF CONTROL JOINTS, MASONRY OPENINGS AND EMBEDDED ANCHORS FOR DOORS, EXTEND CONTROL JOINTS
FULL HEIGHT OF CMU WALL.
27. ALL BEARING PLATES SHALL BE CENTERED ON WALLS UNLESS NOTED OTHERWISE, SEE DETAILS.
26. FILL ALL BLOCK LINTELS AND BOND BEAMS SOLID WITH CMU GROUT CORE-FILL.
25. ALL STEEL LINTELS LOCATED IN EXTERIOR WALLS SHALL BE HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A123, PREPARED, AND FIELD PAINTED AS SPECIFIED. REPAIR GALVANIZED SURFACES THAT ARE DAMAGED BY WELDING IN ACCORDANCE WITH ASTM A780.
H. ANALYSIS PROCEDURE USED EQUIVALENT LATERAL FORCE
G. LONG-PERIOD TRANSITION 8 SECOND PERIOD, TL 24. ALL MASONRY LINTELS SHALL BEAR A MINIMUM OF 2’-0" ON SOLID MASONRY. FILL BLOCK CORES UNDER ALL BEARINGS WITH CONCRETE CMU VERTICAL CORE-FILL A MINIMUM OF 3 COURSES DOWN FOR A 2’-0" LENGTH OF WALL UNLESS NOTED OTHERWISE.
F. SEISMIC IMPORTANCE FACTOR 1.00 (UFC 3-301-01, TABLE 2-2
E. SEISMIC DESIGN CATEGORY C (IBC TABLE 1613.5.6 (1) & (2)) 23. ALL STEEL LINTELS SHALL BEAR A MINIMUM OF 8" ON SOLID MASONRY. FILL BLOCK CORES UNDER ALL BEARINGS WITH CONCRETE CMU VERTICAL CORE-FILL A
MINIMUM OF 3 COURSES DOWN FOR A 2’-0" LENGTH OF WALL UNLESS NOTED OTHERWISE.
D. SITE CLASSIFICATION E (PER GEOTECH REPORT) C. 6'-8" < OPENINGS ≤ 8'-0": 12"x32" BOND BEAM W/ 2-#5 CONT EACH COURSE (4 COURSES)
VI. SD1 0.140 B. 3'-4" < OPENINGS ≤ 6'-8": 12"x24" BOND BEAM W/ 2-#5 CONT EACH COURSE (3 COURSES)
V. SDS 0.200 A. OPENINGS ≤ 3'-4": 12"x16" BOND BEAM W/ 2-#5 CONT EACH COURSE (2 COURSES)
IV. Fv 3.500
III. Fa 2.500 22. FOR ALL OPENINGS, THROUGH EXTERIOR MASONRY WALLS INCLUDING MECHANICAL AND ELECTRICAL OPENINGS, PROVIDE ONE OF THE FOLLOWING UNLESS
NOTED OTHERWISE.
II. S1 0.060 (UFC 3-301-01, TABLE E-3) (2) - #5 BOT (2) - #5 BOT (1) - #5 BOT
I. SS 0.120 (UFC 3-301-01, TABLE E-3) 12" BLOCK 8" BLOCK 6" BLOCK
C. MAPPED SPECTRAL RESPONSE ACCELERATIONS: D. BLOCK LINTELS FOR INTERIOR NON-BEARING WALLS UP TO 8'-0" SPAN: (16" HIGH UNLESS NOTED OTHERWISE)
B. RISK CATEGORY II (UFC 3-301-01, TABLE 2-2) (2) - #4 BOT (2) - #4 BOT (1) - #4 BOT
A. ALL LOADS BASED ON IBC / ASCE 7 / UFC / VA SEISMIC DESIGN REQUIREMENTS H-18-8 12" BLOCK 8" BLOCK 6" BLOCK
6. DESIGN SEISMIC LOADS: C. BLOCK LINTELS FOR INTERIOR NON-BEARING WALLS UP TO 4'-0" SPAN: (8" HIGH UNLESS NOTED OTHERWISE)
(2) - 6"x 3 1/2" x 5/16" (LLV) INTERIOR NON-BEARING WALL FOR SPANS UP TO 6'-0”
(2) - 5"x 3 1/2" x 5/16" (LLV) INTERIOR NON-BEARING WALL FOR SPANS UP TO 5'-0”
(2) - 3 1/2"x 3 1/2" x 1/4" INTERIOR NON-BEARING WALL FOR SPANS UP TO 4'-0”
J. PROJECT IS LOCATED IN WIND-BORNE DEBRIS REGION. GLAZED OPENINGS SHALL BE PROTECTED WITH AN IMPACT-PROTECTIVE SYSTEM OR SHALL BE IMPACT-RESISTANT GLAZING SUBJECTED TO MISSILE TEST AND CYCLIC PRESSURE DIFFERENTIAL TESTS IN ACCORDANCE WITH ASTM E1996.
5. CUTTING OF EXISTING STRUCTURAL STEEL IS PROHIBITED WITHOUT APPROVAL FROM THE ENGINEER B. STEEL ANGLE LINTELS FOR 8" WIDE CMU:
I. INTERIOR WALLS SHALL HAVE 5 PSF LATERAL LOAD APPLIED IN THE ABSENCE OF ANY WIND LOAD EFFECTS. (1) - 6"x 3 1/2" x 5/16" (LLV) INTERIOR NON-BEARING WALL FOR SPANS UP TO 6'-0”
H. COMPONENT AND CLADDING LOADING AS INDICATED ON DRAWINGS (1) - 5"x 3 1/2" x 5/16" (LLV) INTERIOR NON-BEARING WALL FOR SPANS UP TO 5'-0”
G. WIND IMPORTANCE FACTOR, Iw 1.00 (ASCE 7-10, TABLE 1.5-2) 4. WHEN CUTTING A NEW OPENING IN EXISTING CONCRETE OR MASONRY, THE CONTRACTOR SHALL NOT OVER CUT AT CORNERS. CORE-DRILL, CHIP AND GRIND AS REQUIRED AT CORNERS. A LAYOUT OF ALL PROPOSED OPENINGS SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER PRIOR TO SAWCUTTING.
(1) - 3 1/2"x 3 1/2" x 1/4" INTERIOR NON-BEARING WALL FOR SPANS UP TO 4'-0”
F. INTERNAL PRESSURE COEFFICIENT, GPi +/- 0.18 A. STEEL ANGLE LINTELS FOR 4" WIDE CMU:
E. ENCLOSURE CLASSIFICATION ENCLOSED 3. PROVIDE ALL SHORING, BRACING, ETC., AS REQUIRED TO TEMPORARILY SUPPORT THE EXISTING STRUCTURE DURING REMOVAL OF EXISTING STRUCTURAL
ELEMENTS.
D. WIND EXPOSURE C 2. CONTRACTOR IS SOLELY RESPONSIBLE FOR PROTECTION OF EXISTING BUILDING DURING ALL PHASES OF CONSTRUCTION. 21. FOR ALL OPENINGS, THROUGH INTERIOR MASONRY WALLS INCLUDING MECHANICAL AND ELECTRICAL OPENINGS, PROVIDE ONE OF THE FOLLOWING UNLESS
NOTED OTHERWISE.
C. RISK CATEGORY II (UFC 3-301-01, TABLE 2-2)
B. NOMINAL DESIGN WIND SPEED (3-SECOND GUST) Vasd = 108 MPH 1. BEFORE FABRICATION AND ERECTION OF ANY MATERIALS, FIELD VERIFY ALL EXISTING ELEVATIONS, DIMENSIONS AND CONDITIONS AS SHOWN ON THE
DRAWINGS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT AT ONCE.
20. BOND BEAM REINFORCEMENT SHALL BE CONTINUOUS AT CONTROL JOINTS, CORNERS, AND STEPPED BOND BEAMS - LAP REINFORCEMENT PER MASONRY LAP
SPLICE LENGTH SCHEDULE.
A. ULTIMATE DESIGN WIND SPEED (3-SECOND GUST) Vult = 138 MPH C. EXISTING CONSTRUCTION: C. OPENINGS > 8’-8”: 4 CORES
5. WIND CRITERIA: B. 4'-0" < OPENINGS < 8'-8": 3 CORES
A. OPENINGS < 4'-0": 2 CORES
G. THERMAL FACTOR, Ct 1.00 (ASCE 7-10, TABLE 7-3) 19. JAMB REINFORCING UNO: REINFORCE NUMBER OF CORES SHOWN BELOW WITH 2-#5 BARS (1 EACH FACE, FULL HEIGHT) EACH SIDE OF OPENING.
F. EXPOSURE FACTOR, Ce 1.00 (ASCE 7-10, TABLE 7-2)
E. SNOW IMPORTANCE FACTOR, Is 1.00 (ASCE 7-10, TABLE 1.5-2) 11. COORDINATION WITH OTHER TRADES: THE CONTRACTOR SHALL COORDINATE ALL DEPRESSIONS, DIMENSIONS, ELEVATIONS, SLEEVES, CHASES, HANGERS, OPENINGS, INSERTS, ANCHORS, EQUIPMENT SUPPORTS, AND DETAILS WITH THE ENTIRE CONTRACT DOCUMENT PACKAGE, INCLUDING SPECIFICATIONS AND ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. FOR CONCRETE AND MASONRY CONSTRUCTION THE INSERTS, EMBEDDED PLATES, ETC. SHALL NOT INTERFERE WITH REINFORCEMENT LOCATIONS.
18. WHERE NOTED ON THE DRAWINGS, PROVIDE STANDARD HOOKS IN CONFORMANCE WITH LAP SPLICE SCHEDULE, UNLESS OTHERWISE INDICATED.
D. RISK CATEGORY II (UFC 3-301-01, TABLE 2-2) 17. LAP ALL HORIZONTAL REINFORCEMENT PER MASONRY LAP SPLICE LENGTH SCHEDULE, UNLESS OTHERWISE DETAILED.
C. FLAT ROOF SNOW LOAD, Pf 10 PSF 10. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY SHOWN, SIMILAR DETAILS OF
CONSTRUCTION SHALL BE USED, SUBJECT TO APPROVAL BY THE ENGINEER.
16. LAP ALL VERTICAL REINFORCEMENT PER MASONRY LAP SPLICE LENGTH SCHEDULE, UNLESS OTHERWISE DETAILED.
B. GROUND SNOW LOAD, Pg 10 PSF 15. PROVIDE VERTICAL REINFORCEMENT FULL HEIGHT OF WALL (FOOTING TO TOP OF WALL) - DOWEL TO FOOTING.
A. ROOF SNOW LOADS, APPLIED IN ACCORDANCE WITH THE BUILDING CODE INDICATED HEREIN.
4. SNOW LOADS: 14. PLACE BOND BEAMS AT BOTTOM COURSE, TOP COURSE, AND 4’-0” OC MAX, OR AS CALLED OUT ON PLANS, WHICHEVER IS THE LEAST SPACING, REINFORCED
WITH (2)-#5 BARS (1 EACH FACE, CONTINUOUS).
G. ROOF LIVE LOAD 20 PSF
9. THE STRUCTURAL DRAWINGS HEREIN REPRESENT THE FINISHED STRUCTURE. DURING CONSTRUCTION, THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR TEMPORARY GUYING, SHORING, BRACING, FORMING, ETC. TO HOLD THE STRUCTURE IN PROPER ALIGNMENT AND TO WITHSTAND ALL LOADS TO WHICH THE STRUCTURE MAY BE SUBJECTED, INCLUDING LATERAL LOADS, TEMPERATURE DIFFERENTIALS, STOCKPILES OF MATERIAL AND EQUIPMENT. SUCH MEASURES SHALL BE LEFT IN PLACE AS LONG AS REQUIRED FOR SAFETY AND UNTIL ALL FRAMING AND CONNECTIONS INCLUDING ROOF DECK ARE IN PLACE.
THE INVESTIGATION, DESIGN, SAFETY, ADEQUACY AND INSPECTION OF SUCH TEMPORARY MEASURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
13. ALL MASONRY WALLS SHALL BE REINFORCED WITH THE FOLLOWING HORIZONTAL REINFORCEMENT AT A MINIMUM: AT LEAST TWO LONGITUDINAL WIRES OF W1.7 (LADDER TYPE) BED JOINT REINFORCEMENT SPACED NOT MORE THAN 1'-4" OC MAX, OR AS CALLED OUT ON PLANS, WHICHEVER IS THE LEAST SPACING.
F. (**) AT SERVER ROOM, THE CONCENTRATED LOAD INDICATED SHALL BE DISTRIBUTED OVER AN AREA OF 4.5 INCHES BY 4.5 INCHES, AND LOCATED AS TO
PROVIDE THE MAXIMUM LOAD EFFECTS IN THE STRUCTURAL MEMBERS.
12. ALL MASONRY WALLS SHALL BE REINFORCED WITH THE FOLLOWING HORIZONTAL REINFORCEMENT AT A MINIMUM: (2) #5 HORIZONTALS PER CELL (1 EACH FACE, CONTINUOUS) AT 4’-0” OC MAX, OR AS CALLED OUT ON PLANS, WHICHEVER IS THE LEAST SPACING.
E. (*) UNLESS OTHERWISE INDICATED, THE CONCENTRATED LOAD INDICATED WAS DISTRIBUTED OVER AN AREA OF 2.5 FEET BY 2.5 FEET (6.25 SQUARE FEET), AND LOCATED AS TO PROVIDE THE MAXIMUM LOAD EFFECTS IN THE STRUCTURAL MEMBERS.
8. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE MEANS AND MANNER OF CONSTRUCTION AND FOR THE SAFETY OF PERSONS AND PROPERTY.
CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL SAFETY PRECAUTIONS AND REGULATIONS DURING THE WORK. THE ENGINEER WILL NOT
ADVISE ON NOR ISSUE DIRECTION AS TO SAFETY PRECAUTIONS AND PROGRAMS.
11. ALL MASONRY WALLS SHALL BE REINFORCED WITH THE FOLLOWING VERTICAL REINFORCEMENT AT A MINIMUM: (2) #5 VERTICALS PER CELL (1 EACH FACE, FULL HEIGHT) AT 4’-0” OC MAX FOR 12" WALLS, OR AS CALLED OUT ON PLANS, WHICHEVER IS THE LEAST SPACING.
OFFICES 50 2,000
WALKWAYS AND ELEVATED PLATFORMS 60 - 7. CONTRACTOR SHALL ENSURE NO STRUCTURAL MEMBERS OR ELEMENTS ARE DAMAGED OR ALTERED BY OTHER TRADES. ANY SUCH DAMAGE THAT DOES OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
10. ALL MASONRY WALLS SHALL BE REINFORCED WITH THE FOLLOWING VERTICAL REINFORCEMENT AT A MINIMUM: (1) #5 VERTICALS PER CELL (CENTERED, FULL HEIGHT) AT 4’-0” OC MAX FOR 8" WALLS, OR AS CALLED OUT ON PLANS, WHICHEVER IS THE LEAST SPACING.
CORRIDORS ABOVE FIRST FLOOR 80 2,000 6. ALL WALL FOOTINGS SHALL BE CENTERED ON WALLS UNLESS NOTED OTHERWISE.
STAIRS AND EXIT WAYS 100 - 5. ALL COLUMN FOOTINGS SHALL BE CENTERED ON COLUMNS UNLESS NOTED OTHERWISE. 9. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING NECESSARY TO LATERALLY SUPPORT ALL CONCRETE MASONRY WALLS AS REQUIRED.
RESTROOMS 100 1,000 4. ALL COLUMNS SHALL BE CENTERED ON GRID LINES UNLESS NOTED OTHERWISE.
LOBBIES AND FIRST FLOOR CORRIDORS 100 2,000 D. USING SELF-CONSOLIDATING FINE GROUT MIX DESIGN, LIFTS ARE NOT TO EXCEED 24’-0” IN HEIGHT AND CLEAN-OUTS ARE TO BE PROVIDED AT THE
BOTTOM OF EACH LIFT HIGHER THAN 4’-0”, EACH CELL, PER ACI 530, LATEST EDITION.
MECHANICAL / ELECTRICAL ROOM 150 2,000 3. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING AND BRACING OF ALL THE NEW (AND/OR EXISTING) STRUCTURES FOR ALL
LOADS THAT MAY BE IMPOSED DURING CONSTRUCTION.
C. USING SELF-CONSOLIDATING COARSE GROUT MIX DESIGN, LIFTS ARE NOT TO EXCEED 12’-8” IN HEIGHT AND CLEAN-OUTS ARE TO BE PROVIDED AT THE
BOTTOM OF EACH LIFT HIGHER THAN 4’-0”, EACH CELL, PER ACI 530, LATEST EDITION.
OCCUPANCY UNIFORMLY DISTRIBUTED LOAD
(PSF)
CONCENTRATED LOAD * (LBS) A. OPENINGS THROUGH FLOORS AND ROOFS, WHICH MEASURE 12 INCHES OR LESS IN ALL DIRECTIONS, MAY BE CORED DRILLED (AT CONCRETE FILL) OR
CUT (AT ROOF DECK).
B. USING STANDARD GROUT MIX DESIGN, AS SPECIFIED, LIFTS ARE NOT TO EXCEED 8’-0” IN HEIGHT AND CLEAN-OUTS ARE TO BE PROVIDED AT THE BOTTOM
OF EACH LIFT HIGHER THAN 4’-0”, EACH CELL, PER ACI 530, LATEST EDITION.
CODE SPECIFIED MINIMUM FLOOR LIVE LOAD
2. SEE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF WALL, ROOF AND FLOOR OPENINGS AND SLEEVES, AND CONCRETE PADS UNDER EQUIPMENT. THE CONTRACTOR SHALL VERIFY EXACT SIZE AND LOCATION WITH EQUIPMENT FURNISHED. OPENINGS IN STRUCTURE
TO BE HANDLED AS FOLLOW:
A. PROVIDE CLEANOUTS IN THE BOTTOM COURSE OF MASONRY FOR EACH GROUT POUR WHEN THE GROUT POUR HEIGHT EXCEEDS 4’-0”, PER ACI 530, LATEST EDITION.
D. TYPICAL MINIMUM LIVE LOAD USED FOR DESIGN = 100 PSF AND 1,000 LBS CONCENTRATED LOAD. 8. GROUT USED IN MASONRY WALLS:
C. LIVE LOAD REDUCTIONS APPLIED AS PER BUILDING CODE. 7. ALL MASONRY SHALL BE LAID IN RUNNING BOND. STACK BOND CONSTRUCTION IS NOT PERMITTED.
6. LINTEL UNITS SHALL NOT BE USED IN LIEU OF BOND BEAM UNITS.
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS (INCLUDING FIELD VERIFICATIONS OF EXISTING CONDITIONS AND DIMENSIONS) BEFORE STARTING WORK OR FABRICATING ANY REINFORCING STEEL, STRUCTURAL STEEL, COLD-FORMED STEEL ELEMENTS, OR OTHER STRUCTURAL ELEMENTS. THE ARCHITECT, CONTRACTING OFFICER AND ENGINEER OF RECORD SHALL BE NOTIFIED OF ANY DISCREPANCIES FOUND.
5. GROUT FOR REINFORCED CONCRETE MASONRY SHALL CONFORM TO ASTM C476.
B. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL AND INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF, SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES.
B. CONTRACTOR RESPONSIBILITIES: 4. GROUT COMPRESSIVE STRENGTH OF CONCRETE MASONRY, f'g = 2,000 PSI
3. NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY, f'm = 2,000 PSI.
I. ANCHOR RODS (ASTM F1554, GRADE 36) Fy = 36,000 PSI 2. MORTAR SHALL CONFORM TO ASTM C270, TYPE M OR S.
IV. OTHERWISE, ASTM A706, GRADE 60 Fy = 60,000 PSI 1. HOLLOW CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90.
A. THE "TYPICAL MINIMUM LIVE LOAD USED FOR DESIGN" INDICATED BELOW WAS USED FOR ALL OCCUPANCY OR USE TYPES, EXCEPT THOSE WHERE THE "CODE-SPECIFIED MINIMUM LIVE LOADS" ARE GREATER, IN WHICH CASE THE ASSOCIATED LIVE LOAD INDICATED IN THE TABLE WAS USED FOR DESIGN.
SEE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR THE DEFINITION OF SPACES.
F. CONCRETE MASONRY:
3. DESIGN LIVE LOADS: III. MINIMUM ELONGATION IN 8 INCHES SHALL BE AT LEAST 14 PERCENT FOR BAR SIZES NO. 3 THROUGH NO. 6, AT LEAST 12 PERCENT FOR BAR SIZES
NO. 7 THROUGH NO. 11, AND AT LEAST 10 PERCENT FOR BAR SIZES NO. 14 AND NO. 18
II. THE RATIO OF THE TESTED TENSILE STRENGTH TO THE TESTED YIELD STRENGTH IS NOT LESS THAN 1.25.
A. ROOF DEAD LOAD 20 PSF I. THE TESTED YIELD STRENGTH BASED ON MILL TESTS DOES NOT EXCEED Fy BY MORE THAN 18,000 PSI 11. CONDUITS, PIPES, AND SLEEVES SHALL NOT BE LARGER IN OUTSIDE DIMENSION THAN 1/3 THE OVERALL THICKNESS OF THE CONCRETE ELEMENT IN WHICH
THEY ARE EMBEDDED.
2. DESIGN ROOF DEAD LOADS: IF THE FOLLOWING CONDITIONS ARE MET:
H. TYPICAL BARS (ASTM A615, GRADE 60) Fy = 60,000 PSI 10. CONDUITS, PIPES, AND SLEEVES IN CONCRETE SHALL BE NO CLOSER THAN (3) DIAMETERS ON CENTER. MINIMUM SPACING OF CONDUITS, PIPES OR SLEEVES
OF DIFFERENT DIAMETERS SHALL BE DETERMINED USING THE LARGER DIAMETER.
9. REINFORCING STEEL:
9. NO PENETRATIONS (SUCH AS PIPE SLEEVES, ELECTRICAL CONDUITS, ETC.) THROUGH ANY STRUCTURAL MEMBER, SHALL BE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .