Drawings_Vol-9_817CM3025_Marion NC.pdf
PDF 12 MB Posted
- Solicitation number
- 36C78625B0035
About this file
This file contains electrical design drawings for the Marion National Cemetery New Land Expansion project located in Marion, Indiana. The comprehensive electrical plans cover multiple buildings including an Administration Building, Maintenance Building, Committal Shelter, and site electrical infrastructure. Key electrical system components include:
The project involves installing new electrical services with 125kW and 230kW diesel generators for backup power, electrical distribution panels, site lighting, underground conduit systems, technology infrastructure, and comprehensive electrical systems for each building. Specific electrical designs include detailed power distribution plans, lighting layouts, technology rough-ins, security systems, and telecommunications infrastructure across approximately 4-5 buildings. The electrical systems are designed to support various facility functions with redundant power capabilities, integration of access control and video surveillance systems, and comprehensive technology backbone connectivity using fiber and copper infrastructure.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING TITLE
##" = 1'-0"
SPD
DRAWING/ DETAIL TITLE
NOTE:
DRAWING TITLE MAY
NOT APPEAR ON
LARGE SCALE DETAIL
DRAWINGS
DETAIL NUMBER
SECTION CUT SYMBOL
NORTH ARROW ENLARGED PLAN DETAIL
REFER TO THIS
SHEET FOR
ENLARGED
PLAN
ELECTRICAL LEGEND
NOTE: NOT ALL SYMBOLS ARE USED ON THIS PROJECT.
ELECTRICAL ABBREVIATIONS
ABBREVIATIONS USED ON DRAWINGS IN GENERAL ARE LISTED BELOW.
A AMPS
AC AIR CONDITIONING
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
A.I.C. AMPS INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
AT AMP TRIP
BRKR BREAKER
C CONDUIT
CATV CABLE ANTENNA TELEVISION
CKT CIRCUIT
CLG CEILING MOUNTED
CPT CONTROL POWER TRANSFORMER
CPU CENTRAL PROCESSING UNIT
CUH CABINET UNIT HEATER
Cu COPPER
DIA DIAMETER
DISTR DISTRIBUTION
E EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ELEC ELECTRICAL
EM
EMERGENCY LIGHTING WITH CONNECTION TO
EMERGENCY POWER SOURCE
EMT ELECTRICAL METALLIC TUBING
ER EXISTING TO BE REMOVED
EXP EXPLOSION PROOF
EWC ELECTRIC WATER COOLER
F FUSE
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
FCU FAN COIL UNIT
FIXT LIGHT FIXTURE
FLUOR FLUORESCENT
FS FUSIBLE SWITCH
G GROUND
GFI GROUND FAULT CIRCUIT INTERRUPTING PROTECTION
GRC GALVANIZED RIGID CONDUIT
HID HIGH INTENSITY DISCHARGE
HP HORSE POWER
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED GROUND
J JUNCTION BOX
KEC KITCHEN EQUIPMENT CONTRACTOR
KVA KILOVOLT AMPERE
KW KILOWATTS
LC LIGHTING CONTACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MLO MAIN LUG ONLY
MSB MAIN SWITCHBOARD
MTD MOUNTED
NAC NOTIFICATION APPLIANCE CIRCUIT
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
PH PHASE
P POLE
PB PULL BOX
PC PHOTOELECTRIC CONTROL
PE PNEUMATIC/ELECTRIC
PNL PANEL
PVC POLYVINYL CHLORIDE
QR QUARTZ RESTRIKE
R RELOCATED
SW SWITCH
TCP TEMPERATURE CONTROL PANEL
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VC VOLUME CONTROL
W WATTS OR WALL MOUNTED
WG WIRE GUARD
WP WEATHER PROOF TYPE DEVICE
XFMR TRANSFORMER
GENERAL SYMBOLS
CONDUIT CONCEALED ABOVE CEILING OR IN WALL WHEREVER POSSIBLE
CONDUIT CONCEALED BELOW SLAB OR GRADE
CONDUIT EXPOSED ON CEILING, WALL OR BAR JOIST FOR EXPOSED
HOME RUN TO PANELBOARD SHOWING CIRCUIT DESIGNATION,
INDICATING PANEL AND CIRCUIT BREAKER NUMBER WITHIN PANEL
POWER SYMBOLS
DUPLEX WALL RECEPTACLE
DUPLEX WALL RECEPTACLE ON BACKUP POWER
QUADRUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE LOCATED ABOVE COUNTER BACKSPLASH OR AS INDICATED.
ELECTRIC WATER COOLER GFCI RECEPTACLE. THE CONTRACTOR
SHALL VERIFY EXACT LOCATION OF WATER COOLER RECEPTACLE
WITH MANUFACTURERS DWGS.
DUPLEX RECEPTACLE WITH ISOLATED GROUND
SPECIAL PURPOSE OUTLET, AS NOTED ON PLANS OR SPECIFICATIONS
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE
FLOOR BOX/POKE THROUGH, REFER TO FLOOR BOX SCHEDULE FOR
ADDITIONAL INFORMATION.
LIGHTING/ RECEPTACLE PANEL
DISTRIBUTION/ POWER PANEL
SURGE PROTECTION DEVICE
TRANSFORMER
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD
PROTECTION AND PILOT LIGHT
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MAGNETIC MOTOR STARTER
MAGNETIC MOTOR STARTER COMBINED WITH DISCONNECT SWITCH
PUSH PLATE FOR DOOR OPERATOR
CIRCUIT BREAKER
FUSIBLE SWITCH
SWITCH PROVIDED W/ MOTORIZED PROJECTION SCREEN, INSTALLED
AND WIRED BY ELECTRICAL
EMERGENCY POWER OFF, REFER TO PLANS FOR WIRING DETAILS.
VARIABLE FREQUENCY DRIVE; FURNISHED BY OTHERS, INSTALLED
BY ELECTRICAL CONTRACTOR
A-1
LIGHTING SYMBOLS
2' x 4' LED LIGHT FIXTURE
2' x 4' LED LIGHT FIXTURE WITH CONNECTION TO
EMERGENCY POWER SOURCE
1' x 4' LED LIGHT FIXTURE
1' x 4' LED LIGHT FIXTURE WITH CONNECTION TO
EMERGENCY POWER SOURCE
LED DOWNLIGHT FIXTURE
LED DOWNLIGHT FIXTURE WITH
CONNECTION TO EMERGENCY POWER SOURCE
WALL MOUNTED LIGHT FIXTURE
4' LED STRIP FIXTURE
EXIT LIGHT FIXTURE. SHADED AREA DENOTES SINGLE OR DOUBLE
FACE. DIRECTIONAL ARROWS AS SHOWN ON PLANS
EMERGENCY BATTERY PACK FIXTURE
POLE MOUNTED SITE LIGHT FIXTURE. NUMBER OF HEADS AS PER
DRAWINGS. (NOTE THAT ARROWS INDICATE DIRECTION FOR WHICH
OPTIMUM PHOTOMETRIC PERFORMANCE IS DESIRED. FIELD ROTATE
REFLECTOR ASSEMBLY IF REQUIRED.
GENERAL PURPOSE, 120/277V SINGLE POLE SWITCH EQUAL TO HUBBELL CSL120
DOUBLE POLE TOGGLE SWITCH EQUAL HUBBELL TO CSL220
GENERAL PURPOSE, 120/277V 3-WAY SWITCH EQUAL TO HUBBELL CSL320
GENERAL PURPOSE, 120/277V 4-WAY SWITCH EQUAL TO HUBBELL CSL420
GENERAL PURPOSE KEY-OPERATED SWITCH
GENERAL PURPOSE 3-WAY KEY-OPERATED SWITCH
GENERAL PURPOSE 4-WAY KEY-OPERATED SWITCH
GENERAL PURPOSE SWITCH WITH PILOT LIGHT
CONTACTOR
TIME CLOCK
ENLARGED PLAN NUMBER
VFD
EWC
SECTION NUMBER
SHEET WHERE SECTION IS
DRAWN
T
PS
T
TC
C
H10
ELECTRICAL SYSTEM INDICATION
HEAVY LINE-
WEIGHT
INDICATES
NEW WORK
LIGHT LINE
WEIGHT-
INDICATES
EXISTING
EQUIPMENT OR
REFERENCED
INFORMATION
DASHED LINE-
EQUIPMENT OR
MATERIALS TO BE
DISCONNECTED
AND REMOVED
TEXT LEADER
NOTES BY SYMBOLDRAWING REVISION
SYMBOL
DRAWING REVISION
NUMBER
KEYED
NOTE NUMBER
INFORMATION TEXT
VAV-XX
EQUIPMENT TAG
IDENTIFICATION
REFERENCE E002 FOR
EQUIPMENT BRANCH CIRCUIT
REQUIREMENTS
DUPLEX RECEPTACLE WITH USB CONNECTION. USB TYPES A & C.
U
K
3K
4K
P
DUPLEX RECEPTACLE LOCATED ABOVE COUNTER BACKSPLASH OR AS INDICATED.
GFI DUPLEX WALL RECEPTACLE
GFIGFIGFI
DIGITAL OCCUPANCY SENSOR WALL SWITCH EQUAL TO
• SENSORSWITCH WSXA SERIES
SIMPLEX WALL RECEPTACLE
IG
QUADRUPLEX RECEPTACLE ON BACKUP POWER
SPECIAL PURPOSE OUTLET ON BACKUP POWER, AS NOTED ON PLANS OR SPECIFICATIONS
FB-# PT-#
F
EPO
SIMPLEX WALL RECEPTACLE ON BACKUP POWER
2' x 2' LED LIGHT FIXTURE
2' x 2' LED LIGHT FIXTURE WITH CONNECTION TO
EMERGENCY POWER SOURCE
JUNCTION BOX
MOTOR; REFER TO PLANS FOR CIRCUITING AND PHASE.
J
J
WIREMOLD/ PLUGMOLD W/ ENTRANCE FITTING AS SPECIFIED AND
RECEPTACLES/ DEVICES AS INDICATED ON PLAN
D 120V/277V, 0-10V DIMMING SWITCH EQUAL TO LUTRON DIVA
S
S
S
S
S
S
S
S
S
SWITCHES
(REFER TO SPECIFICATIONS AND LIGHTING SEQUENCE OF OPERATIONS FOR ADDITIONAL INFORMATION)
CONNECT TO EXISTING SYMBOL
DENOTING LIGHTING CONTROL ZONES. FIXTURES SHALL BE
CONTROLLED TOGETHER.
PLAN
NORTH
TRUE
NORTH
D 120V/277V, 0-10V, 3-WAY DIMMING SWITCH EQUAL TO LUTRON DIVA
FIRE ALARM SYMBOLS
F
FS
TS
FIRE ALARM PULL STATION
FIRE ALARM HORN/STROBE - WALL MOUNTED
FIRE ALARM STROBE - WALL MOUNTED
FIRE ALARM STROBE - CEILING MOUNTED
WATERFLOW SWITCH (SUPPLIED BY FIRE PROTECTION)
TAMPER SWITCH (SUPPLIED BY FIRE PROTECTION)
FIRE ALARM HORN/STROBE - CEILING MOUNTED
C
DD
DUCT SMOKE DETECTOR. COORDINATE WITH MECHANICAL
DRAWINGS. DETECTORS SHALL BE MOUNTED IN RETURN AND
SUPPLY DUCTS OF EACH AIR HANDLER UNIT UNLESS NOTED
OTHERWISE. MOUNT DUCT DETECTORS A MINIMUM OF SIX
WIDTHS FROM ANY BENDS, BRANCH CONNECTIONS OR TURNS
IN THE DUCT
SMOKE DETECTOR - CEILING MOUNTED
NAC
FAAP
FACP FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
NOTIFICATION APPLIANCE CIRCUIT
HEAT DETECTOR - FIXED TEMPERATURE
DH FIRE ALARM HOLD OPEN CONNECTION
EXR EXISTING TO BE RELOCATED
FIRE ALARM RELAY
R
W DIGITAL WALL SWITCH/STATION EQUAL TO
• SENSORSWITCH SPODMRA SERIES
DUAL TECHNOLOGY LOW VOLTAGE OCCUPANCY SENSOR EQUAL TO
• SENSORSWITCH CM SERIES
S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:5
P M
ELECTRICAL COVERSHEET MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E000
Revisions: Date:
OF 266216216 OF 266216
101.1
841.98
GA TE B
3 1 4 4 7 8
GA TE E
3 1 4 4 7 9
OH C E
3 1 8 3 9 0
NEW
SERVICE
POLE
E002
E004
E003
EV CHARGING PEDESTAL
GENERATOR
GENERATOR
SA SA SA SA
HH-1
HH-3
MH-1
HH-4
SB
SB
SB
SA
HH-2
PANEL C
(2) 2-1/2"C, PVC-80 (POWER)
(1) 1"C, PVC-80 (POWER)
(1) 1"C, PVC-80 (POWER)
(1) 1"C
(2) 2-1/2"C
PVC-80 (POWER)
(1) 1"C
(1) 1-1/4"C
(2) 2-1/2"C
PVC-80 (POWER)
(1) 1-1/4"C, PVC-80 (POWER)
(2) 1"C, PVC-80 (POWER)S10
S5
S5
S5
S5
S5
S5
S4
S3
S3
S3
S7
S6
S7
S6
SA
S7
S6
S7
S6
S7
S6
S7
S6
S8
S8
S8
S9
S5
(1) 1-1/4"C
(2) 2"C
(2) 2-1/2"C
PVC-80 (POWER)
S3
(3) 3"C
(1) 1-1/4"C
PVC-80 (POWER)
S10
GENERATOR QUICK
CONNECT CABINET
GENERATOR QUICK
CONNECT CABINET
S2
S6
S6
S6
S1
ER
ER
REMOVE FLAGPOLE
LIGHTING
S12
S13
EXISTING
SERVICE POLE
ES14
(1) 2 1/2" C
PVC-80 (POWER)
(1) 2 1/2" C
PVC-80 (POWER)
ES17
ES19
ES18
ES15
ES16
ES16
ES20
WPWP
F@400A
OHEOHE
OHEOHEOHEOHE
(3) 3"C
PVC-80 (POWER)
OHEOHEOHEOHEOHE
OHEOHE
EXISTING UTILITY POWER POLE
AND OVERHEAD LINES TO REMAIN
REFER TO CIVIL PLANS FOR
LOCATION AND ADDITIONAL
DETAILS
ELECTRICAL SITE
PLAN GENERAL NOTES
A. UTILITIES SHOWN ARE INDICATED SCHEMATICALLY. CONTRACTORS SHALL VERIFY
ALL DEPTHS AND ALL LOCATIONS/DIMENSIONS PRIOR TO EXCAVATING. ALL
UTILITIES MAY NOT BE SHOWN.
B. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING AND
NEW SITE CONDITIONS INCLUDING UTILITES.
C. ALL UNDERGROUND UTILITIES, PIPING, ETC. SHALL BE LOCATED EXACTLY BEFORE
DIGGING.
D. ANY BACKFILL SHALL BE TAMPED AND COMPACTED TO PREVENT FUTURE
SETTLING. ALL EXCESS DIRT SHALL BE CLEARED FROM THE AREA AND DISPOSED
OF.
E. MECHANICAL AND ELECTRICAL CONTRACTORS SHALL REPAIR ALL DISTRUBED
SURFACES SUCH AS SIDEWALKS, DRIVEWAYS, STREETS, GRASS, AND CONCRETE.
REPLACED SURFACES SHALL MATCH EXISTING.
F. COORDINATE ALL EXTERIOR SITE LIGHTING FIXTURES WITH DESIGN TEAM PRIOR
TO INSTALLATION.
G. CONTRACTOR IS RESPONSIBLE FOR DOING ALL WORK PER LOCAL RESPECTIVE
UTILITY REQUIREMENTS.
H. VERIFY EXACT LOCATIONS OF UTILITY CONNECTIONS, PRIOR TO START OF WORK.
OVERALL ELECTRICAL SITE PLAN KEYED
NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
S1
LOCATION OF 225KW DIESEL GENERATOR WITH SOUND ATTENUATING
ENCLOSURE. REFER TO SHEET 3005-E003 AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION. REFER TO SHEET 3005-E501 FOR GENERATOR
PAD DETAIL. REFER TO CIVIL PLANS FOR GENERATOR PAD EXTENTS.
S2
LOCATION OF 125KW DIESEL GENERATOR WITH SOUND ATTENUATING
ENCLOSURE. REFER TO SHEET 1001-E002 AND SPECIFCATIONS FOR
ADDITIONAL INFORMATION. REFER TO SHEET 1001-E501 FOR GENERATOR
PAD DETAIL. REFER TO CIVIL PLANS FOR GENERATOR PAD EXTENTS.
S3 REFER TO SHEET 1001-E501 FOR EXTERIOR HANDHOLE DETAIL.
S4 REFER TO SHEET 1001-E501 FOR MANHOLE DETAIL.
S5
REFER TO SHEET 1001-E501 FOR UNDERGROUND CONDUIT DETAIL. REFER
TO ONE-LINE DIAGRAM ON SHEET 1001-E301 FOR CONDUCTOR SIZES.
S6
CONTROL LIGHTING VIA ASTRONOMILCAL TIMECLOCK. LIGHTS SHALL TURN
ON 15 MINUTES BEFORE SUNSET AND TURN OFF 15 MINUTES AFTER
SUNRISE.
S7 SPACE IN-GRADE LIGHTING EVENLY ACROSS LENGTH OF MONUMENT SIGN.
S8 REFER TO SHEET 1001-E501 FOR FLAGPOLE LIGHT BASE DETAIL.
S9 REFER TO SHEET 1001-E501 FOR GENERATOR PAD DETAIL.
S10
REFER TO SHEET 3005-E501 FOR UNDERGROUND CONDUIT DETAIL. REFER
TO ONE-LINE DIAGRAM ON SHEET 3005-E301 FOR CONDUCTOR SIZES.
S11 REFER TO SHEET 3005-E501 FOR FLAGPOLE LIGHT BASE DETAIL.
S12
COORDINATE REMOVAL AND RELOCATION OF EXISTING UTILITY POLE WITH
INDIANA MICHIGAN POWER.
S13
COORDINATE LOCATION OF NEW UTIILTY POLE FOR ADMINISTRATION
BUILDING SERVICE WITH INDIANA MICHIGAE POWER PRIOR TO ROUTING
CONDUIT.
ES14
LOCATION OF EXISTING INDIANA MICHIGAN POWER SERVICE POLE.
COORDIANTE REPLACE OF EXISTING SERVICE TRNASFORMERS FROM
POLE WHEN SERVICE UPGRADE IS COMPLETED.
ES15
COORDINATE NEW UTILITY POWER POLE INSTALLATION WITH INDIANA
MICHIGAN POWER FOR SERVICE UPGRADE. REFER TO ONE-LINE DIAGRAM
FOR ADDITIONAL DETAILS.
ES16
COORDINATE REMOVAL OF EXISTING METER SOCKET AND CT CABINET
WITH INDIANA MICHIGAN POWER.
ES17
LOCATION OF NEW IRRIGATION PUMP CONTROL STATION AND IRRIGATION
PUMPS. REFER TO IRRIGATION PLANS FOR EXACT LOCATIONS. EXISTING
PUMPS TO BE DISCONNECTED AND REMOVED. DISCONNECT AND REMOVE
ALL ASSOCIATE WIRING BACK TO SOURCE EXISTING UNDERGROUND
CONDUIT MAY BE ABANDONED IF IT DOES NOT INTEREFER WITH NEW
CONSTRUCTION.
ES18
PROVIDE PAD MOUNTED 48"x48"x12" 1200A RATED, NEMA 3R ENCLOSURE
WITH WOOD BACK PANEL FOR CT MOUNTING PER INDIANA MICHIGAN
POWER SPECIFICATIONS. REFER TO ONE-LINE DIAGRAM ON SHEET
3005-E301 FOR ADDITIONAL INFORMATION.
ES19
PROVIDE 1200A, PAD MOUNTED, BOTTOM FED SWITCHBOARD WITH NEMA
3R ENCLOSURE AND STRIP HEATER WITH INTERNAL POWER. REFER TO
ONE-LINE DIAGRAM ON SHEET 3005-E501 FOR ADDITIONAL DETAILS.
ES20
PROVIDE 400A RATED, NEMA 3R METER SWITCH, NON FUSED LOAD BREAK
DISCONNECT, METER SOCKET PER UTILITY REQUIREMENTS, AND FUSIBLE
400A, NEMA 3R SERVICE DISCONNECT. PROVIDE (2) 4" GALVANIZED PIPE
WITH UNISTRUT FOR MOUNTING EQUIPMENT. REFER TO METER SWITCH
DETAIL WITH DISCONNECT ON SHEET 1001-E501 FOR ADDITIONAL DETAILS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:5
P M
OVERALL ELECTRICAL SITE PLAN MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E001
1" = 40'-0"
ELECTRICAL SITE PLAN
PLAN
NORTH
OF 266217217 OF 266217
A
B.2
ES2
ES1
EPO
WP
GENERATOR EMERGENCY
SHUTDOWN
125kW
GENERATOR
ES3
ES4 MH-1
HH-3
ES6
(1) 1"C
(1) 1-1/4"C
(2) 2-1/2"C
PVC-80 (POWER)
ES5
(1) 1-1/4"C, PVC-80 (POWER) ES5
(1) 1"C
(2) 2-1/2"C
PVC-80 (POWER)
ES5
ES5
(1) 1-1/4"C
(2) 2"C
(2) 2-1/2"C
PVC-80 (POWER)
GENERATOR QUICK
CONNECT CABINET
ES7
ELECTRICAL SITE
PLAN GENERAL NOTES
A. UTILITIES SHOWN ARE INDICATED SCHEMATICALLY. CONTRACTORS SHALL VERIFY
ALL DEPTHS AND ALL LOCATIONS/DIMENSIONS PRIOR TO EXCAVATING. ALL
UTILITIES MAY NOT BE SHOWN.
B. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING AND
NEW SITE CONDITIONS INCLUDING UTILITES.
C. ALL UNDERGROUND UTILITIES, PIPING, ETC. SHALL BE LOCATED EXACTLY BEFORE
DIGGING.
D. ANY BACKFILL SHALL BE TAMPED AND COMPACTED TO PREVENT FUTURE
SETTLING. ALL EXCESS DIRT SHALL BE CLEARED FROM THE AREA AND DISPOSED
OF.
E. MECHANICAL AND ELECTRICAL CONTRACTORS SHALL REPAIR ALL DISTRUBED
SURFACES SUCH AS SIDEWALKS, DRIVEWAYS, STREETS, GRASS, AND CONCRETE.
REPLACED SURFACES SHALL MATCH EXISTING.
F. COORDINATE ALL EXTERIOR SITE LIGHTING FIXTURES WITH DESIGN TEAM PRIOR
TO INSTALLATION.
G. CONTRACTOR IS RESPONSIBLE FOR DOING ALL WORK PER LOCAL RESPECTIVE
UTILITY REQUIREMENTS.
H. VERIFY EXACT LOCATIONS OF UTILITY CONNECTIONS, PRIOR TO START OF WORK.
ELECTRICAL SITE PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
ES1 MINIMUM SETBACK FROM STRUCTURE OF 3' SHALL BE MAINTAINED.
ES2
PROVIDE 125KW DIESEL GAS FUELED GENERATOR WITH SOUNDED
ATTENUATING ENCLOSURE. REFER TO SHEETS 1001-E3.1, 1001-E5.1, AND
SPECIFICATIONS FOR ADDITIONAL DETAILS.
ES3 REFER TO SHEET 1001-E501 FOR EXTERIOR HANDHOLE DETAIL.
ES4 REFER TO SHEET 1001-E501 FOR MANHOLE DETAIL.
ES5
REFER TO SHEET 1001-E501 FOR UNDERGROUND CONDUIT DETAIL. REFER
TO ONE-LINE DIAGRAM ON SHEET 1001-E301 FOR CONDUCTOR SIZES.
ES6 REFER TO SHEET 1001-E501 FOR GENERATOR PAD DETAIL.
ES7
PROVIDE 100A, 208Y/120V RATED WALL MOUNTED MANUAL TRANSFER
SWITCH WITH 100A CIRCUIT BREAKER EQUAL TO TRYSTAR TMTS-01.
MANUAL TRANSFER SWITH SHALL HAVE MALE CAM-LOCK CONNECTIONS
FOR MOBILE GENERATOR CONNECTION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:0
P M
PIC ADMIN. BLDG - ELECTRICAL SITE PLAN MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E002
1/8" = 1'-0"
ELECTRICAL SITE PLAN - ADMINSTRATION BUILDING
PLAN
NORTH
OF 266218218 OF 266218
ss s w w w s w w s s
S s w w
S w
S
S
S S
S
S S
S S
S
S
S
S
SS
S S
GENERAL
OFFICE
MEN'S
TOILET
WOMEN'S
TOILET
IT CLOSET &
STORAGE
MECHANICAL
ROOM
ELEC
CLOSET
MULTI
PURPOSE
ROOM
MEN'S
TOILET
WOMEN'S
TOILET
HALLWAY
WORK
ROOM
BREAKROOM
OFFICE
ASSISTANT
DIRECTOR
OFFICE
SECURE
STORAGE
ROOM
JANITOR
LR-1
RB
LR-1
RB
LR-1
RB
LR-1
RB
LR-3
WB
LR-3
WB
WA
WA
100A
VESTIBULE
EA
EA EA
EA
C
C
B
B B
E a,b
PA
A
A
F
B
B
RB RB RB
RBRB
C
C
LR-1
RB
RB
LR-1
RB
RB
LR-1
RB
RB
F
RB RB
RB
A
LR-1
RB
B
DD
a a a a a a a a b
LR-1
RB
LR-1
RB
LR-1
RB
LR-1
RB
C
EA
1 1.2 1.8 2 3 4
B
C
D
E
F
L2 L2
L2 L2
L2L2
L2
L2
L2
L2
L2L2
L2
L2
RA
RA
RB
RA
RA RA
RA
RB
RB
RBRB
RB
RB
RB
FA1
LR-1
FA1
FA1 FA1
FA1
LR-1
FA1
LR-1
DA
LR-1
DA
LR-1
DA
LR-1
DA
LR-1
DA
LR-1
DA
L2 L2
L2 L2
DA
DA
DA DA
DA DA DA DA
DA DA
DA DA
DA DA
DA DA
WA
WA
WA WA
OS-1-31
L2
L2
L2
L2
FA1
NORTH LIGHTING
OS-1-30
LR-1
RB
L2
LIGHTING GENERAL NOTES
1. REFER TO SPECIFICATION SECTION 26 0923 FOR ADDITIONAL DETAILS ASSOCIATED
WITH LIGHTING CONTROLS.
2. SURFACE RACEWAY SHALL NOT BE TWO DEVICES ON OPPOSITES SIDES OF THE
SAME WALL ARE WITHIN 6" OF EACH OTHER.
3. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE
SAME WALL ARE WITHIN 6" OF EACH OTHER.
4. COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.
5. ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE
ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE
NOTIFIED IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.
6. ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION
DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
7. THE ELECTRICAL CONTRACTOR SHALL EXTEND AN "UNSWITCHED" HOT
CONDUCTOR FROM THE NEAREST LIFE SAFETY CIRCUIT TO EXIT SIGNS REQUIRED
FOR EMERGENCY EGRESS OPERATION.
8. CONTRACTOR SHALL PROVIDE A UL924 RATED TRANSFER DEVICE IN ALL AREAS
WHERE EMERGENCY EGRESS LIGHTING IS REQUIRED PER NFPA 101. LIGHTING
CONTROLS MANUFACTURER SHALL DETERMINE EXACT QUANTITIES WITH
LIGHTING CONTROL ZONES AND LAYOUTS.
9. UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES,
SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.
10.REFER TO ARCHITECTURAL ELEVATION AND REFLECTED CEILING PLANS FOR THE
SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE
REVIEWED AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
LIGHTING PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
L1 NO LIGHTING SCOPE IN THIS AREA.
L2
CIRCUIT EMERGENCY FIXTURE TO LEGALLY REQUIRED PANEL LRH.
EMERGENCY LIGHT SHALL BE CONTROLLED WITH OTHER LIGHTS IN AREA
AND ACCORDING TO SEQUENCE OF OPERATION. FIXTURE SHALL TURN ON
TO FULL BRIGHTNESS IN THE EVENT OF POWER LOSS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:0
P M
PIC ADMIN. BLDG - LIGHTING PLAN MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E101
1/4" = 1'-0"
LIGHTING PLAN
F AUTO ON/OFF via PHOTOCELL AUTO ON/OFF via EXTERIOR PHOTOCELL INTEGRAL TO LIGHT FIXTURES OR PROVIDED EXTERNAL AS INDICATED ON DRAWINGS. N/A
E MANUAL ON/ AUTO OFF w/ DIMMING MANUAL ON/ AUTO OFF w/ MULTI ZONE WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL WITH ZONES INDICATED ON PLAN. 15 MINUTE TIMEOUT
D MANUAL ON/ AUTO OFF w/ DIMMING MANUAL ON/ AUTO OFF w/ WALL CONTROL, CEILING SENSOR(S), AND ROOM CONTROLLERS AS APPROPRIATE. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT
C AUTO ON/OFF w/ DIMMING AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. FIXTURES SHALL HAVE FULL DIMMING CONTROL. 15 MINUTE TIMEOUT
B AUTO ON/OFF AUTO ON/OFF w/ WALL MOUNTED AND/OR CEILING MOUNTED SENSOR(S) AS INDICATED ON PLANS. 15 MINUTE TIMEOUT
A MANUAL ON/OFF MANUAL LINE VOLTAGE TOGGLE SWITCH N/A
TAG ACTIVATION DECRIPTION SCHEDULE
LIGHTING CONTROL - SEQUENCE OF OPERATION
NOTES:
1. REFER TO SPECIFICATIONS 26 0923 FOR FURTHER INFORMATION.
2. OCCUPANCY SENSORS SHALL BE PROGRAMMED FOR 15 MINUTE TIME DELAY.
3. PROVIDE PROPER NUMBER OF POWER PACKS REQUIRED FOR A FULLY FUNCTIONAL SYSTEM.
4. EXACT DEVICE AND POWER PACK QUANTITIES SHALL BE DETERMINED DURING CONSTRUCTION BY THE LIGHTING CONTROLS MANUFACTURER.
5. PROVIDE UL924 RATED TRANSFER DEVICE(S) IN ALL AREAS WHERE EMERGENCY EGRESS LIGHTING IS REQUIRED PER NFPA 101 AND SHADED LIGHT FIXTURES INDICATED FOR EGRESS.
TRUE
NORTH
PLAN
NORTH
OF 266219219 OF 266219
EPO
C
F
F
J
JJ
J
C
CC
C
M S
1 2 3 4
B
C
D
E
F
1.2 1.8
B.2
LOBBY
GENERAL
OFFICE
OFFICE
ASSISTANT
DIRECTOR
OFFICE
SECURE
STORAGE
ROOM
WORK
ROOM
MULTI
PURPOSE
ROOM
MECHANICAL
ROOM
IT CLOSET &
STORAGE
WOMEN'S
TOILET
MEN'S
TOILET
ELEC
CLOSET 111
WOMEN'S
TOILET
MEN'S
TOILET
HALLWAY
BREAKROOM
JANITOR
100A
VESTIBULE
PNL LR
F A
A P
F A
C P
125KW DIESEL
GENERATOR
GFI GFI GFI
GFI
GFI
GFIGFI
GFI GFI
WP
GFI
E1
WP
WP
GFI
+24" +42"
WP
GFI
1 1.2 1.8 2 3 4
B
C
D
E
F
OS-1-4
OS-1-6
OS-1-7
OS-1-20
OS-1-23
OS-1-28
OS-1-21
OS-1-19
OS-1-18
OS-1-14
OS-1-29
OS-1-26
OS-1-16
OS-1-17
OS-1-13
OS-1-3
OS-1-1
OS-1-2
OS-1-5
GFI
MICROWAVE
OS-1-24
OS-1-25
FRIDGE
OS-1-27
GFI
EWC-1
OS-1-15
COPIER
OS-1-9
OS-1-8 SHREDDER
OS-1-11
OS-1-22
E2
E2
E2
E2 E2
IT RACK
OS-1-12
OS-1-10
E2E2
PNL OS-1
PNL OS-2
MDP
ATS-OS
ATS-LR
BATTERY CHARGER
LR-5
JACKET HEATER
208V-2P/20A
LR-2,4
FACP
LR-6
E4 E4 E4 E4
E4
E4
+60"
E3
FB-1
E11
E10 E7
E6
E9
E8
ELECTRICAL GENERAL NOTES
1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE
OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND
BOND PER NEC ARTICLE 250.
2. ELECTRICAL CONTRACTOR SHALL PROVIDE TAMPER RESISTANCE RECEPTACLES
PER NEC 406. 12.
3. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A
MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET
PRIOR TO ROUGH-IN.
4. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.
DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.
5. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT PRIOR
APPROVAL FROM THE DESIGN TEAM.
6. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.
7. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME
WALL ARE WITHIN 24" OF EACH OTHER.
8. PRIOR TO ROUGH-IN, COORDINATE ALL WALL DEVICES WITH FINAL CASEWORK
ELEVATIONS AND OTHER TRADES. CONFLICTS SHALL BE BROUGHT IMMEDIATELY
TO THE ATTENTION OF THE DESIGN TEAM.
9. ALL FLOOR BOXES SHALL HAVE THEIR EXACT ROUGH-IN LOCATIONS DETERMINED
BY THE DESIGN TEAM THROUGH DIMENSIONED DRAWINGS APPROVED BY THE
OWNER PRIOR TO ROUGH-IN. LOCATIONS SHOWN ARE FOR BIDDING PURPOSES
ONLY.
10.REFER TO TECH SHEETS FOR ADDITIONAL ROUGH-IN INFORMATION OF LOW
VOLTAGE DEVICES.
11.REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE
REVIEWED AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1
LOCATION OF NEW 125 KW DIESEL FUEL GENEATOR AND QUICK CONNECT
CABINET. REFER TO SPECIFICATIONS AND SHEETS 1001-E001, E002 AND
E501 FOR ADDITIONAL DETAILS.
E2
ACCESS CONTROL LOCATION. REFER TO LOW VOTAGE DETAILS AND
ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER
ROUGH-IN/BIDDING INFORMATION. COORDINATE ALL DOOR HOLDS, CARD
READERS, DOOR POSITION SWITCHES, AND OTHER ACCESSORIES WITH
DESIGN TEAM PRIOR TO ROUGH-IN.
E3
COORDINATE EXACT DEVICE LOCATION WITH OWNERS DESIRED
MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER
PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICE AND
CABLES ARE NEAT AND CONCEALED. REFER TO TECH DRAWINGS FOR
ADDITIONAL DEVICE ROUGH INS.
E4
COORDINATE EXACT DEVICE LOCATION WITH FURNITURE PRIOR TO
ROUGH-IN.
E6
PROVIDE 208Y/120V, 400A SERVICE ENTRANCE RATED PANELBOARD WITH
MAIN CIRCUIT BREAKER. COORDINATE BOTTOM FEED LOCATIONS WITH
INCOMING FEEDERS. REFER TO SHEETS 1001-E501 AND 1001-E601 FOR
ADDITIONAL PANEL INFORMATION.
E7
PROVIDE 208Y/120V, 400A RATED OPEN TRANSITION TRANSFER SWITCH.
COORDINATE BOTTOM FEED WITH EMERGENCY FEEDERS FROM
GENERATOR. REFER TO SHEET 1001-E301 AND SPECIFICATIONS FOR
ADDITIONAL DETAILS.
E8
PROVIDE 208Y/120V, 100A RATED OPEN TRANSITION TRANSFER SWITCH.
COORDINATE BOTTOM FEED WITH EMERGENCY FEEDERS FROM
GENERATOR. REFER TO SHEET 1001-E301 AND SPECIFICATIONS FOR
ADDITIONAL DETAILS.
E9
PROVIDE 208Y/120V, 225A RATED PANELBOARD WITH 100A MAIN CIRCUIT
BREAKER. REFER TO SHEETS 1001-E501 AND 1001-E601 FOR ADDITIONAL
PANEL INFORMATION.
E10
PROVIDE 208Y/120V, 400A RATED PANELBOARD WITH MAIN CIRCUIT
BREAKER AND FEED THROUGH LUGS. REFER TO SHEETS 1001-E501 AND
1001-E601 FOR ADDITIONAL PANEL INFORMATION.
E5
HVAC UNIT ABOVE 2000 CFM. FIRE ALARM CONTRACTOR SHALL PROVIDE
DUCT SMOKE DETECTION ON THE SUPPLY AND RETURN SIDE OF THIS UNIT.
CONNECT EACH DUCT SMOKE DETECTOR TO A FAN SHUTDOWN RELAY.
COORDINATE SHUT DOWN SEQUENCE WITH MECHANICAL CONTRACTOR.
FOLLOW NFPA 72 AND MANUFACTURER RECOMMENDATIONS FOR
INSTALLATION.
E11
PROVIDE 208Y/120V, 400A RATED PANELBOARD. REFER TO SHEETS
1001-E501 AND 1001-E601 FOR ADDITIONAL PANEL INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \A
W e b e r\
D o c u m e n ts
\1
P
IC
A
D M
IN
IS
T R
A T
IO
N
R
-M
E P a w e b e r9
S
.r v t
/1 /2
:3
:2
P M
PIC ADMIN. BLDG - POWER PLAN MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E201
1/4" = 1'-0"
POWER PLAN
OF 266220220 OF 266220
J
J
J
J
J
J
J
J
J
J
J
J
J
J
M S
J
R
1 2 3 4
B
C
D
E
F
1.2 1.8
B.2
1 1.2 1.8 2 3 4
B
C
D
E
F
EUH-1
208V-3P/30A
OS-2-74,76,78
EWH-1
208V-3P/110A
OS-2-65,67,69
PNL LR
VAV-01
208V-2P/20A
OS-2-43,45
VAV-10
208V-2P/20A
OS-2-68,70
VAV-09
208V-2P/20A
OS-2-61,63
VAV-08
208V-2P/20A
OS-2-64,66
VAV-02
208V-3P/25A
OS-2-44,46,48
VAV-03
208V-2P/20A
OS-2-47,49 VAV-04
208V-2P/20A
OS-2-50,52
VAV-05
208V-2P/20A
OS-2-51,53
VAV-06
208V-2P/25A
OS-2-54,56
VAV-07
208V-3P/20A
OS-2-55,57,59
ACCU-1
208V-3P/80A
OS-2-71,73,75
AHU-1
208V-3P/60A
OS-2-58,60,62
ERV-1
120V-1P/20A
OS-2-72
PNL OS-2 PNL OS-1
ATS-LR
MDP
ATS-OS
EF-1
208V-2P/20A
OS-2-77,79
125 KW DIESEL GENERATOR
GENERATOR QUICK
CONNECT CABINET
WP
DD
DD
E5
EF-1
(ON ROOF)
ELECTRICAL GENERAL NOTES
1. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE
OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND
BOND PER NEC ARTICLE 250.
2. ELECTRICAL CONTRACTOR SHALL PROVIDE TAMPER RESISTANCE RECEPTACLES
PER NEC 406. 12.
3. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH A
MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET
PRIOR TO ROUGH-IN.
4. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL EQUIPMENT.
DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.
5. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT PRIOR
APPROVAL FROM THE DESIGN TEAM.
6. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.
7. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE SAME
WALL ARE WITHIN 24" OF EACH OTHER.
8. PRIOR TO ROUGH-IN, COORDINATE ALL WALL DEVICES WITH FINAL CASEWORK
ELEVATIONS AND OTHER TRADES. CONFLICTS SHALL BE BROUGHT IMMEDIATELY
TO THE ATTENTION OF THE DESIGN TEAM.
9. ALL FLOOR BOXES SHALL HAVE THEIR EXACT ROUGH-IN LOCATIONS DETERMINED
BY THE DESIGN TEAM THROUGH DIMENSIONED DRAWINGS APPROVED BY THE
OWNER PRIOR TO ROUGH-IN. LOCATIONS SHOWN ARE FOR BIDDING PURPOSES
ONLY.
10.REFER TO TECH SHEETS FOR ADDITIONAL ROUGH-IN INFORMATION OF LOW
VOLTAGE DEVICES.
11.REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR THE
SPECIFIC ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE
REVIEWED AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.
ELECTRICAL PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
E1
LOCATION OF NEW 125 KW DIESEL FUEL GENEATOR AND QUICK CONNECT
CABINET. REFER TO SPECIFICATIONS AND SHEETS 1001-E001, E002 AND
E501 FOR ADDITIONAL DETAILS.
E2
ACCESS CONTROL LOCATION. REFER TO LOW VOTAGE DETAILS AND
ARCHITECTURAL SPECIFICATIONS FOR OPERATION AND FURTHER
ROUGH-IN/BIDDING INFORMATION. COORDINATE ALL DOOR HOLDS, CARD
READERS, DOOR POSITION SWITCHES, AND OTHER ACCESSORIES WITH
DESIGN TEAM PRIOR TO ROUGH-IN.
E3
COORDINATE EXACT DEVICE LOCATION WITH OWNERS DESIRED
MOUNTING HEIGHT PRIOR TO ROUGH-IN. COORDINATE WITH OWNER
PROVIDED TV/MONITOR AND MOUNTING SYSTEM SO THAT DEVICE AND
CABLES ARE NEAT AND CONCEALED. REFER TO TECH DRAWINGS FOR
ADDITIONAL DEVICE ROUGH INS.
E4
COORDINATE EXACT DEVICE LOCATION WITH FURNITURE PRIOR TO
ROUGH-IN.
E6
PROVIDE 208Y/120V, 400A SERVICE ENTRANCE RATED PANELBOARD WITH
MAIN CIRCUIT BREAKER. COORDINATE BOTTOM FEED LOCATIONS WITH
INCOMING FEEDERS. REFER TO SHEETS 1001-E501 AND 1001-E601 FOR
ADDITIONAL PANEL INFORMATION.
E7
PROVIDE 208Y/120V, 400A RATED OPEN TRANSITION TRANSFER SWITCH.
COORDINATE BOTTOM FEED WITH EMERGENCY FEEDERS FROM
GENERATOR. REFER TO SHEET 1001-E301 AND SPECIFICATIONS FOR
ADDITIONAL DETAILS.
E8
PROVIDE 208Y/120V, 100A RATED OPEN TRANSITION TRANSFER SWITCH.
COORDINATE BOTTOM FEED WITH EMERGENCY FEEDERS FROM
GENERATOR. REFER TO SHEET 1001-E301 AND SPECIFICATIONS FOR
ADDITIONAL DETAILS.
E9
PROVIDE 208Y/120V, 225A RATED PANELBOARD WITH 100A MAIN CIRCUIT
BREAKER. REFER TO SHEETS 1001-E501 AND 1001-E601 FOR ADDITIONAL
PANEL INFORMATION.
E10
PROVIDE 208Y/120V, 400A RATED PANELBOARD WITH MAIN CIRCUIT
BREAKER AND FEED THROUGH LUGS. REFER TO SHEETS 1001-E501 AND
1001-E601 FOR ADDITIONAL PANEL INFORMATION.
E5
HVAC UNIT ABOVE 2000 CFM. FIRE ALARM CONTRACTOR SHALL PROVIDE
DUCT SMOKE DETECTION ON THE SUPPLY AND RETURN SIDE OF THIS UNIT.
CONNECT EACH DUCT SMOKE DETECTOR TO A FAN SHUTDOWN RELAY.
COORDINATE SHUT DOWN SEQUENCE WITH MECHANICAL CONTRACTOR.
FOLLOW NFPA 72 AND MANUFACTURER RECOMMENDATIONS FOR
INSTALLATION.
E11
PROVIDE 208Y/120V, 400A RATED PANELBOARD. REFER TO SHEETS
1001-E501 AND 1001-E601 FOR ADDITIONAL PANEL INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \A
W e b e r\
D o c u m e n ts
\1
P
IC
A
D M
IN
IS
T R
A T
IO
N
R
-M
E P a w e b e r9
S
.r v t
/1 /2
:4
:5
P M
PIC ADMIN. BLDG - EQUIPMENT POWER PLAN MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 Checker Author17101
1001-E202
1/4" = 1'-0"
EQUIPMENT POWER PLAN
OF 266221221 OF 266221
ELECTRICAL RISER KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
ER1
REFER TO PANEL SCHEDULE FOR ADDITIONAL BREAKER AND PANEL
INFORMATION.
ER2
REFER TO PANEL SCHEDULE ON SHEET 4802-3501 FOR ADDITIONAL
BREAKER AND PANEL INFORMATION.
ELECTRICAL RISER GENERAL
NOTES
A. ELECTRICAL POWER OUTAGES, IF REQUIRED, SHOULD BE STRATEGICALLY
MINIMIZED AND SCHEDULED CLOSELY WITH OWNER. CHANGEOVERS COULD BE
REQUIRED TO OCCUR AT ANY HOUR.
B. MAINTAIN ALL SERVICE CLEARANCES REQUIRED BY THE UTILITY AND NEC.
COORDINATE INSTALLATION WITH UTILITY REQUIREMENTS PRIOR TO ROUGH-IN.
C. REFER TO SITE PLAN SHEETS FOR ADDITIONAL REQUIREMENTS AND
RESPONSIBILITIES.
D. INSTALL ALL CONDUCTORS AS PER MANUFACTURER'S RECOMMENDATIONS.
E. ELECTRICAL SERVICE ENTRANCE LAYOUT MAY VARY FROM WHAT IS SHOWN ON
PLANS BASED ON MANUFACTURER PROVIDING THE SYSTEM. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR FITTING SYSTEM PROVIDED IN THE SPACE
SHOWN ON PLANS.
F. EXTERNAL MOUNTED SURGE PROTECTION DEVICES SHALL BE INSTALLED PER
MANUFACTURER'S GUIDELINES. MINIMIZE DISTANCE FROM EQUIPMENT.
COPPER CONDUCTOR
AND CONDUIT SIZING CHART
CONDUCTORS (THWN-2) CONDUIT PARALLEL
RUNS
PHASE NEUTRAL GROUND EMT SCH 80
15/4 (3) #12 AWG #12 AWG #12 AWG 1/2" 3/4" 1
20/4 (3) #12 AWG #12 AWG #12 AWG 1/2" 3/4" 1
25/4 (3) #10 AWG #10 AWG #10 AWG 1/2" 3/4" 1
30/4 (3) #10 AWG #10 AWG #10 AWG 1/2" 3/4" 1
35/4 (3) #8 AWG #8 AWG #10 AWG 3/4" 1" 1
40/4 1
45/4 1
50/4 1
60/4 (3) #4 AWG #4 AWG #10 AWG 1
70/4 (3) #4 AWG #4 AWG #8 AWG 1-1/4" 1-1/4" 1
80/4 1
90/4 (3) #2 AWG #2 AWG #8 AWG 1
100/4 1
(3) #2 AWG #2 AWG #6 AWG 1
(3) #1 AWG #1 AWG #6 AWG 1-1/2" 2" 1
(3) 1/0 AWG 1/0 AWG #6 AWG 2" 1
(3) 2/0 AWG 2/0 AWG #6 AWG 1
(3) 3/0 AWG 3/0 AWG #6 AWG 1
(3) 4/0 AWG 4/0 AWG #4 AWG 1
(3) 250 MCM 250 MCM #4 AWG 3" 1
(3) 350 MCM 350 MCM #4 AWG 3" 1
(3) 500 MCM 500 MCM #3 AWG 3" 3-1/2" 1
(3) 3/0 AWG 3/0 AWG #3 AWG 2" 2-1/2" 2
3/4" 1"
1" 1"
1" 1"
(3) #8 AWG #8 AWG #10 AWG
(3) #6 AWG #6 AWG #10 AWG
(3) #6 AWG #6 AWG #10 AWG
(3) #3 AWG #3 AWG #8 AWG 1-1/4" 1-1/4"
1-1/4" 1-1/4"
1-1/4" 1-1/4"(3) #2 AWG #2 AWG #8 AWG
110/4
125/4
150/4
175/4
200/4
225/4
250/4
300/4
350/4
400/4
1-1/4" 1-1/2"
2"
2" 2"
2" 2-1/2"
2-1/2"2-1/2"
2-1/2"
3"
1-1/4" 1-1/4"
COPPER CONDUCTOR
AND CONDUIT SIZING CHART
CONDUCTORS (THWN-2) CONDUIT PARALLEL
RUNS
PHASE NEUTRAL GROUND EMT SCH 80
15/3 (3) #12 AWG #12 AWG 1/2" 3/4" 1
20/3 (3) #12 AWG #12 AWG 1/2" 3/4" 1
25/3 (3) #10 AWG #10 AWG 1/2" 3/4" 1
30/3 (3) #10 AWG #10 AWG 1/2" 3/4" 1
35/3 (3) #8 AWG #10 AWG 3/4" 1" 1
40/3 1
45/3 1
50/3 1
60/3 (3) #4 AWG #10 AWG 1
70/3 (3) #4 AWG #8 AWG 1-1/4" 1-1/4" 1
80/3 1
90/3 (3) #2 AWG #8 AWG 1
100/3 1
(3) #2 AWG #6 AWG 1
(3) #1 AWG #6 AWG 1-1/2" 2" 1
(3) 1/0 AWG #6 AWG 2" 1
(3) 2/0 AWG #6 AWG 1
(3) 3/0 AWG #6 AWG 1
(3) 4/0 AWG #4 AWG 1
(3) 250 MCM #4 AWG 3" 1
(3) 350 MCM #4 AWG 3" 1
(3) 500 MCM #3 AWG 3" 3-1/2" 1
(3) 3/0 AWG #3 AWG 2" 2-1/2" 2
3/4" 1"
1" 1"
1" 1"
(3) #8 AWG #10 AWG
(3) #6 AWG #10 AWG
(3) #6 AWG #10 AWG
(3) #3 AWG #8 AWG 1-1/4" 1-1/4"
1-1/4" 1-1/4"
1-1/4" 1-1/4"(3) #2 AWG #8 AWG
110/3
125/3
150/3
175/3
200/3
225/3
250/3
300/3
350/3
400/3
1-1/4" 1-1/2"
2"
2" 2"
2" 2-1/2"
2-1/2"2-1/2"
2-1/2"
3"
1-1/4" 1-1/4"
SERVICE ENTRANCE
COPPER CONDUCTOR
AND CONDUIT SIZING CHART
CONDUCTORS (THWN-2) CONDUIT PARALLEL
RUNS
PHASE NEUTRAL GROUND EMT SCH 80
(3) 3/0 AWG 3/0 AWG 1
(3) 4/0 AWG 4/0 AWG 1
(3) 250 MCM 250 MCM 3" 1
(3) 350 MCM 350 MCM 3" 1
(3) 500 MCM 500 MCM 3" 3-1/2" 1
(3) 3/0 AWG 3/0 AWG 2" 2-1/2" 2
200/N
225/N
250/N
300/N
350/N
400/N
2" 2-1/2"
2-1/2"2-1/2"
2-1/2"
3"
COORDINATE NEW UTILITY SERIVCE POLE
AND POLE MOUNTED TRANSFORMERS
WITH INDIANA MICHIGAN POWER
(REFER TO ES DRAWING FOR LOCATION)
400A-3P
[LSIG]
30A-3P
SPD
100A-3P
[LSI]
ATS-LR
100A 42kA WCR
3-POLE
400A-3P
[LSIG]
ATS-OS
400A 22kA SCCR
3-POLE
100A-3P
[LSI]
400A-3P
[LSIG]
125KW, STANDBY DIESEL
POWERED GAS
GENERATOR (120/208V, 3Ø,
4W) WITH SOUND ENCLOSURE.
SEE ELECTRICAL SPECIFICATIONS.MDP
400A, 208Y/120V
AVAILABLE SCCR: 3,994A
CALCULATED ON: 08/29/2024
N G PANEL LR
SPD
PANEL OS-1
SPD
400/N
100/4 400/4
ER1 ER1
400/4
100/4
400/4
100/4
DPM
N
L
E N
L
E
100A, 208/120V
GENERATOR QUICK
CONNECT CABINET AND
MANUAL TRANSFER SWITCH
E
T L
60A-3P
60/4 PANEL C
(COMMITTAL SHELTER)
400/4
FEED-THROUGH LUGS
PANEL OS-2
ER1
ER2
LOAD BREAK NON-FUSED
METER SWITCH
400A RATED
NEMA 3R
NEMA 3R DISCONNECT
FUSED @400A
EC SHALL PROVIDE METER SCOKET PER UTILITY
SPECIFICATIONS. PROVIDE MOUNTING STRUCTURE
PER UTILITY METER SWITCH MOUNTING DETAIL
400/4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:0
P M
PIC ADMIN. BLDG - ELECTRICAL ONE-LINE
DIAGRAM
MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E301
ELECTRICAL ONE LINE - NEW
OF 266222222 OF 266222
36" Ø
[3
M
IN
IM
U M
M
IN
IM
U
M
8' WIDE x 10' LONG]
MOUNT SWITCH IN
WEATHERPROOF
COVER, NEAR
ENTRANCE TO
MANHOLE
MOUNT LUMINARIES
TO CEILING
SIMPLEX RECEPTACLE,
FOR SUMP PUMP, IN
CAST BOX WITH IN-USE
COVER. +46" A.F.F.
24"Ø X 2' SUMP PIT WITH OPEN
GRATING COVER WITH SAND
BACKFILL ON 6" OF SIDES AND
6" CONCRETE AROUND BOTTOM
WATERSTOP
AT ALL JOINTS
18"Ø SUMP PIT
WITH MINIMUM 12" DRAIN
FIELD OF PEA GRAVEL
BOTTOM SECTION
PVC COATED
PULLING IRONS
LOCATED OPPOSITE
CONDUIT ENTRANCES
STANDARD PRECAST
OR CAST-IN-PLACE
CONCRETE MANHOLE
DOWEL DUCT BANK TO
MANHOLE WITH
MINIMUM (4) #4 DOWELS
CONDUITS
SLOPE TO
MANHOLE (TYP)
2500 PSI GROUT
MALLEABLE IRON
BELL END (TYP)
TOP SECTION
CAST-IN-PLACE OR
PRECAST CONCRETE TOP
PROVIDE ANCHORING FOR
CABLE SUPPORT BRACKETS
AT 2'-0" O.C. ON ALL MANHOLE
WALLS. PROVIDE NON-
METALLIC CABLE SUPPORT
ARMS AS REQUIRED
MANHOLE FRAME WITH SOLID
LID, MARKED "ELECTRICAL".
[NEENAH FOUNDRY R-1640,
OR EQUAL]
5/8" x 8'-0" COPPER CLAD
GROUND ROD, IN 2" PVC
SLEEVE. BOND ALL STEEL IN
MANHOLE TO GROUND ROD
FINISH GRADE
SECTION VIEW
PLAN VIEW
GROUND ROD SLEEVE
36"Ø CLEAR OPENING
18"Ø SUMP
1.
NOTES:
MANHOLE SHALL BE DESIGNED TO AASHTO HS-20 LIVE LOADS.
SUBMITTAL SHALL SHOW DESIGN LOADING AND MATERIAL SPECIFICATIONS
FOR SUPPLIED PRODUCTS.
/6
2 59/64" 0"
1 13/64"
/6
/6
PLAN VIEW
2'-0"
1" CHAMFER
FINISHED GRADE LINE
TRANSITION TO RIGID
GALVANIZED STEEL CONDUIT
FOR RISER FOR ALL
CONDUITS
CONCRETE BASE (3000 PSI)
4#4W/#3 TIES @12". MINIMUM
2" ON SIDES AND 3" AT
BOTTOM CONCRETE COVER
OF REINFORCING STEEL.
4#4W/#3 TIES @12". MINIMUM
2" ON SIDES AND 3" AT
BOTTOM CONCRETE COVER
OF REINFORCING STEEL.
EXTEND TO FIRM CLEAN
UNDISTURBED SOIL
SACK RUB FINISH ON ALL
EXPOSED CONCRETE
3 GANG CAST BOX, EQUAL TO CROUSE-HINDS
FSS23 OR PER FIXTURE MANUFACTURER'S
SPECIFICATIONS. INSTALL CONDUIT
REDUCERS AT BOX.
3/4" LIQUIDTIGHT FLEXIBLE CONDUIT
JJJ
GENERATOR PAD
SEE CIVIL PLANS FOR EXTENTS AND DIMENSIONS.
COORDINATE ALL CONDUIT PENTRATIONS REQUIRED.
BATTERY CHARGER
JACKET HEATER
AUTOMATIC TRANSFER SWITCH
EPO REMOTE SHUTDOWN PER NFPA 110.
COORDINATE EXACT MOUNTING
LOCATION WITH LOCAL AHJ.
1" CONDUIT TO REMOTE
GENERATOR ANNUNCIATOR
NON WALK-IN
REFERENCED NOTES:
1. PROVIDE CONDUCTORS TO AUTOMATIC TRANSFER SWITCH.
REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR CONDUIT
AND WIRE SIZE INFOMATION.
2. GENERATOR-MOUNTED BREAKER(S).
STAINLESS STEEL HEX
HEAD BOLT W/WASHER
PULL SLOT
SKID RESISTANT
SURFACE
EXTENSIONS AS REQUIRED
BY CONDUIT DEPTH
KNOCKOUTS - (8)
SLOPE GRADE AWAY FROM
COVER 1" IN 3'
MOUSEHOLES - (2)
STAINLESS STEEL 304 1/2" X 1/2" x .063
WOVEN METAL MESH ABOVE GRAVEL FOR
RODENT CONTROL.
GRAVEL DRAINAGE BED MINIMUM 12"
DEPTH EXTENDING 6" BEYOND ALL EDGES.
MINIMUM SIZE GRAVEL 1" (CA5 OR CA7).
CONDUITS LARGER THAN MOUSEHOLES
CAN ACCOMMODATE, SHALL ENTER
BOTTOM OF HANDHOLE WITH LONG
RADIUS SWEEPS.
8" E
XTENSION
NOTES:
1. ALL DIMENSIONS ARE NOMINAL.
2. ALL SPLICES OR DEVICES IN HANDHOLE SHALL BE SUBMERSIBLE.
FINISHED GRADE
MINIMUM 24" DEPTH
MAXIMUM 30" DEPTH
COMPACTED SAND BEDDING,
MINIMUM 3" BELOW AND TO
SIDES OF CONDUITS AND 6"
ABOVE CONDUIT.
UNDERGROUND CONDUIT(S)
SEE PLANS FOR QUANTITY,
SIZE AND TYPE.
MARKER TAPE WITH
METALLIC TRACER, 12"
ABOVE CONDUITS.
SERVICE
DISCONNECT
VOLTS
METER
SWITCH
NON FUSE
LOAD BREAK
DISCONNECT
6" MIN.
6" MIN.
X
FINAL GRADE
L
IN
E
(U N
D E
R G
R O
U N
D )X
UNISTRUT OR EQUAL
M
IN
M A
X
4" GALV.
PIPE
METER SOCKET
BY CUSTOMER
DISCONNECT
BY CUSTOMER
GROUND WIRE
BARE #6 CU.
MINIMUM
DISCONNECT
BY CUSTOMER
X6"
48"
' M
IN
D R
IV
E
N G
R O
U N
D R
O D
C
L A
M P
G R
O U
N D
W
IR
E B
A R
E
C
U M
IN
IM
U M x6' MIN.
12" TYP. 12" TYP.
x4
S P
D
SPD
ALTERNATE
MOUNTING
METHOD
CONDUCTORS SHALL
BE SLIGHTLY TWISTED
AND BUNDLED WITH
WIRE WRAPS.
LEAD LENGTH SHOULD
BE MINIMIZED,
PREFERABLE LEAD
LENGTH IS 6"
3POLE CIRCUIT
BREAKER SIZED PER
MANUFACTURER
REQUIREMENTS.
SURGE
PROTECTION
DEVICE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:1
P M
PIC ADMIN. BLDG - ELECTRICAL DETAILS MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E501
ELECTRICAL MANHOLE DETAIL
U.S. FLAG POLE LIGHT EXTENDED BASE DETAIL
GENERATOR ROUGH-IN DETAIL
EXTERIOR HANDHOLE DETAIL
UNDERGROUND CONDUIT DETAIL
UTILITY METER SWITCH DISCONNECT MOUNTING DETAIL
Revisions: Date:
TVSS INSTALLATION DETAIL
OF 266223223 OF 266223
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
C U s e rs \j c a lla h a n
\D o c u m e n ts
\1
P
IC
A D
M
IN
IS
T
R A
T
IO
N
R
-M
E P
J c a lla h a n X
F H
.r v t
/1 /2
:0
:1
P M
PIC ADMIN. BLDG - ELECTRICAL SCHEDULES MARION NATIONAL CEMETERY
NEW LAND EXPANSION
1700 E 38TH ST, MARION, IN 46953
817CM3023
10/30/2024 ATW JPC17101
1001-E601
TYPE LEGEND: A=ARC FAULT E=EXISTING G=GFI H=HANDLE LOCK ST=SHUNT TRIP
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 6.2 A
TOTAL CONNECTED AMPS: 6.18 A
Lighting - Dwelling Unit 0.136 kVA 100.00% 0.136 kVA TOTAL ESTIMATED DEMAND LOAD: 2.227 kVA
Power 1.5 kVA 100.00% 1.5 kVA TOTAL CONNECTED LOAD: 2.23 kVA
Lighting 0.598 kVA 100.00% 0.598 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
Total Amps: 8.86 2.25 9.22
Total Load: 0.96 kVA 0.27 kVA 1.00 kVA
29 0 -- -- -- 30
27 0 -- -- -- 28
25 0 3 30 A SPD 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 BATTERY CHARGER 20 A 1 0.5 0.5 1 20 A FACP 6
3 EXTERIOR LIGHTINGS 20 A 1 0.02 0.25 -- -- -- 4
1 EGRESS LIGHTING 20 A 1 0.71 0.25 2 20 A JACKET HEATER 2
CKT
NO. LOAD DESCRIPTION TYPE TRIP P
A B C
P TRIP TYPE LOAD DESCRIPTION
CKT
NO.
NOTES:
AVAILABLE Isc: 3,557A SCCR: 10,000 A
LOCATION: MECHANICAL ROOM 112 WIRES 4 SPD EXTERNAL
FED FROM: @ PHASES: 3 MCB RATING: 100 A
ENCLOSURE: Type 1 VOLTAGE: 208Y/120V MAINS RATING: 100 A
MOUNTING: Surface MAINS TYPE: MCB
PANEL LR LEGALLY REQUIRED
WB BEACON RWL1 48L-20 4K7 4F UNV XXX PC LED TRAPEZOIDAL WALL PACK. IP65 RATED HOUSING. INTEGRAL PHOTOCELL. ARCHITECT SHALL SELECT FINISH AT TIME OF SUBMITTAL. BAA COMPLIANT. LED/4000K
PHOTOCEL
L
2672 19.9 120-277 LITHONIA
WA LITHONIA FMVCSL 24IN MVOLT 30K 90CRI BN 24" LED SQUARE VANITY FIXTURE. BRUSHED NICKEL FINISH. COORDINATE INSTALLATION WITH MIRROR ELEVATION PRIOR TO INSTALLATION. BAA COMPLIANT. LED/3000K N/A 1300 18 120-277
ENGINEER
APPROVED
SB INSIGHT LIGHTING PS17 LOW TR 4 40K 120V 0-10V IP66 LED FLAG POLE LIGHT. DIE CAST ALUMINUM HOUSING. 4 DEGREE DSITRIBUTION. POLYESTER POWDER COAT FINISH. IP 66 RATED. ARCHITECT SHALL VERIFY FINISH AT TIME OF SUBMITTAL. BAA COMPLIANT. LED/4000K 0-10V 12413 100 120
ENGINEER
APPROVED
SA HK LIGHTING ZFL16 IR2 ABL UNV 08 40 MHJB LED DOUBLE HEAD FLOOD LIGHT. ALUMINUM BLACK HOUSING. GROUND MOUNTED. SPACE EVENLY AND COORDINATE AIMING WITH SIGNAGE. BAA COMPLIANT. LED/4000K/80 0-10V 1008 16 120-277
ENGINEER
APPROVED
RB LITHONIA
CPX 2X2 3200LM 80CRI 35K SWL MIN10
ZT MVOLT
2'x2' LED BACK-LIT FLAT PANEL WITH WHITE DIFFUSE LENS. BAA COMPLIANT. LED/3500K/80 0-10V, 10% 3669 30.1 120-277
METALUX
COLUMBIA
RA LITHONIA
CPX 2X4 3200LM 80CRI 35K SWL MIN10
ZT MVOLT
2'x4' LED BACK-LIT FLAT PANEL WITH WHITE DIFFUSE LENS. BAA COMPLIANT. LED/3500K/80 0-10V, 10% 3180 24.6 120-277
METALUX
COLUMBIA
PB OCL
TB5-P1FK-12-MW-WTP-LED2-35K-ND-UN
V-48-DIM1
5" DIAMETER LED PENDANT. 5.75" SURFACE MOUNT CANOPY, SINGLE CENTER AIRCRAFT CABLE AND WHITE POWER CORD. MATTE WHITE FINISH. MOUNT APPROXIMATELY 3' ABOVE TABLE. COORDINATE EXACT LOCATION
WITH FURNITURE PRIOR TO ROUGH-IN. BAA COMPLIANT.
LED/3500K 0-10V, 10% 1100 9 120-277
ENGINEER
APPROVED
PA FINELITE
HO4 P ID RO 8' S S 835 TG OPN 96LG
120 SC
8' LED LINEAR PENDANT WITH OPEN RECTLINEAR SHAPE. INDIRECT AND DIRECT OUTPUT. PROVIDE ACCESSORIES REQUIRED FOR SUSPENDED INSTALLATION APPROXIMATELY 3' ABOVE TABLE. BAA COMPLIANT. LED/3500K/80 0-10V, 10%
XXX LM/FT UP
XXX LM/FT
DOWN
XX
LM/FT
120-277 LITE CONTROL
FB COLUMBIA MPS 4 LW C W EDU 4' LED STRIP FIXTURE. CURVED, FROSTED ACRLYIC LENS. WIDE DISTRIBUTION. PROVIDE CHAIN HANGER ACCESSORIES REQUIRED FOR SUSPENDED INSTALLATION AT APPROXIMATELY 8' AFF. BAA COMPLIANT. LED/3500K/80 0-10V 3878 27.3 120-277
METALUX
LITHONIA
FA COLUMBIA MPS 4 LW C W EDU 4' LED STRIP FIXTURE. CURVED, FROSTED ACRLYIC LENS. WIDE DISTRIBUTION. PROVIDE ACCESSORIES REQUIRED FOR SURFACE MOUNTED INSTALLATION. BAA COMPLIANT. LED/3500K/80 0-10V 3878 27.3 120-277
METALUX
LITHONIA
EB LITHONIA LE S 2 R DIE CAST ALUMINUM EXIT SIGN. DOUBLE FACE. RED LETTERS. PROVIDE CHEVRONS AS INDICATED ON PLANS. BAA COMPLIANT. LED/RED N/A N/A 0.81 120-277
DUAL-LITE
EMERGI-LITE
EA LITHONIA LE S 1 R DIE CAST ALUMINUM EXIT SIGN. SINGLE FACE. RED LETTERS. PROVIDE CHEVRONS AS INDICATED ON PLANS. BAA COMPLIANT. LED/RED N/A N/A 0.81 120-277
DUAL-LITE
EMERGI-LITE
DC GOTHAM EV04SH 35/10 DFR SOL MVOLT EZ1 4" LED SHOWER DOWNLIGHT. REGRESSED WIPE DOWN LENS. NON-CONDUCTIVE DEAD-FRONT TRIM. MEDIUM WIDE DISTRIBUTION. IP66 RATED ROOM SIDE. BAA COMPLIANT. LED/3500K/85 0-10V, 1% 843 8.8 120-277
PRESCOLITE
PORTFOLIO
DB GOTHAM EV06 40/10 CL LSS WD MVOLT GZ10 6" LED OPEN DOWNLIGHT. CLEAR REFLECTOR WITH SEMI-SPECULAR FINISH. WIDE DISTRIBUTION. WET LOCATION RATED WITH COVERED CEILING. BAA COMPLIANT. LED/4000K/85 0-10V, 10% 994 9.6 120-277
PRESCOLITE
PORTFOLIO
DA GOTHAM EV06 35/15 CL LSS WD MVOLT GZ10 6" LED OPEN DOWNLIGHT. CLEAR REFLECTOR WITH SEMI-SPECULAR FINISH. WIDE DISTRIBUTION. BAA COMPLIANT. LED/3500K/85 0-10V, 10% 1,471 14.7 120-277
PRESCOLITE
PORTFOLIO
TYPE
BOD
MANUFACTURE
R
MODEL NUMBER DESCRIPTION
LAMP/CCT/CR
I
CONTRO
L
DELIVERED
LUMENS
WATTS VOLTS EQUALS
LIGHTING FIXTURE SCHEDULE
TYPE LEGEND: A=ARC FAULT E=EXISTING G=GFI H=HANDLE LOCK ST=SHUNT TRIP
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
Water Heater 30 kVA 100.00% 30 kVA
Heating 41.5 kVA 100.00% 41.5 kVA
Receptacle 15.03 kVA 83.27% 12.515 kVA
Cooling 15.264 kVA 100.00% 15.264 kVA
Lighting - Dwelling Unit 0.426 kVA 100.00% 0.426 kVA TOTAL ESTIMATED DEMAND AMPS: 326.7 A
Power 2.94 kVA 100.00% 2.94 kVA TOTAL CONNECTED AMPS: 333.69 A
Other 0 kVA 0.00% 0 kVA TOTAL ESTIMATED DEMAND LOAD: 117.703 kVA
Lighting 1.111 kVA 100.00% 1.111 kVA TOTAL CONNECTED LOAD: 120.22 kVA
HVAC 13.968 kVA 100.00% 13.968 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
Total Amps: 342.55 322.14 342.56
Total Load: 40.78 kVA 38.66 kVA 40.78 kVA
41 0 -- -- -- 42
39 0 -- -- -- 40
37 0 3 30 A SPD 38
35 36
33 Receptacle MULTI PURPOSE... 20 A 1 0.54 34
31 SOUTH LIGHTING 20 A 1 0.96 32
29 STORAGE 116 20 A 1 0.54 0.56 1 20 A NORTH LIGHTING 30
27 FRIDGE G 20 A 1 0.09 0.36 1 20 A EXTERIOR RECEPTACLES 28
25 BREAKROOM 107 20 A 1 0.18 0.54 1 20 A GENERAL OFFICE 101 26
23 BREAKROOM 107 20 A 1 1.08 0.18 1 20 A G MICROWAVE 24
21 HALLWAY 109 20 A 1 0.36 0.18 1 20 A COFFEE MAKER 22
19 WOMEN'S TOILET 112 20 A 1 0.36 0.36 1 20 A BREAK ROOM 108 20
17 MEN'S ROOM 119 20 A 1 0.9 1.08 1 20 A MECHANICAL ROOM 113 18
15 EWC-1 G 20 A 1 0.18 0.36 1 20 A MULTI PURPOSE ROOM 115 16
13 LOBBY 100 20 A 1 0.54 0.72 1 20 A MULTI…