Drawings_Vol-7_817CM3025_Marion NC.pdf
PDF 7 MB Posted
- Solicitation number
- 36C78625B0035
About this file
The provided file contains a comprehensive set of structural engineering drawings for the Marion National Cemetery New Land Expansion project (Project Number 817CM3025). The drawings include detailed structural plans and specifications for multiple buildings and structures, specifically:
- PIC Administration Building (structural plans for foundation, framing, roof, and details)
- Maintenance Building (structural plans with mezzanine floor and roof framing)
- Committal Shelter (foundation and framing plans)
- Columbarium (foundation and wall details)
- Entrance Wall and Flagpole Foundations
The drawings provide technical specifications for concrete foundations, reinforcement requirements, structural steel connections, wood framing, and engineered wood members. They are prepared for 100% construction documents and include detailed notes on construction methods, material specifications, load calculations, and compliance with building codes such as the 2012 International Building Code. The structural designs account for specific site conditions, including soil bearing pressures, wind loads, and seismic considerations for Marion, Indiana.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL CONSTRUCTION NOTES:
1. ALL WORK SHALL COMPLY WITH THE 2012 INTERNATIONAL BUILDING CODE, AS
APPROVED BY THE STATE OF INDIANA / CITY OF MARION.
2. REFERENCE STANDARDS: UNLESS OTHERWISE NOTED (U.O.N.), ALL
STANDARDS SHALL BE CURRENT EDITION, WITH LATEST ADDENDA, IF
APPLICABLE.
3. THE CONTRACTOR SHALL VERIFY ALL CONTRACT DOCUMENTS, SITE
ELEVATIONS, DIMENSIONS AND CONDITIONS PRIOR TO STARTING WORK AND
SHALL NOTIFY THE ARCHITECT/ ENGINEER OF ANY DISCREPANCIES OR
INCONSISTENCIES.
4. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES.
5. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT
THE FINISHED STRUCTURE. UNLESS OTHERWISE INDICATED, THEY DO NOT
INDICATE THE MEANS OR METHOD OF CONSTRUCTION. TEMPORARY BRACING
AND SHORING AGAINST WIND AND ERECTION CONDITIONS DURING
CONSTRUCTION OF THE BUILDING, SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE
PROTECTION OF THE STRUCTURE DURING ALL PHASES OF DEMOLITION,
CONSTRUCTION, AND INSTALLATION.
6. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
7. VERIFY LOCATION OF BOX OUTS AND OPENINGS WITH MECHANICAL
CONTRACTORS. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES, DUCTS
ETC. ARE FOR GENERAL INFORMATION ONLY AND SHALL BE VERIFIED WITH THE
MECHANICAL CONTRACTOR BEFORE COMMENCING THE WORK.
8. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS
DO NOT COINCIDE WITH EQUIPMENT SHOWN ON PLANS, COORDINATE
ADJUSTMENTS WITH THE STRUCTURAL ENGINEER.
9. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
APPROVED BY THE STRUCTURAL ENGINEER BEFORE PLACEMENT THROUGH
STRUCTURAL MEMBERS.
10. CONTRACTOR SHALL PROVIDE A CAST-IN SLEEVE FOR ALL HORIZONTAL
ELEMENTS THAT EXTEND THROUGH FOOTING. IE: DRAIN TILE, ELECTRICAL
CONDUIT, MECHANICAL PIPING, ETC. ALL SLEEVES SHALL BE COORDINATED
WITH ARCHITECT/ENGINEER.
11. SHOP DRAWINGS PREPARED BY SUPPLIERS, SUBCONTRACTORS, ETC., SHALL
BE DIMENSIONED, REVIEWED, COORDINATED, AND SIGNED/ STAMPED BY THE
GENERAL CONTRACTOR PRIOR TO SUBMITTING TO THE STRUCTURAL
ENGINEER.
12. FABRICATOR SHALL CLEARLY NOTE CHANGES MADE IN THE SHOP DRAWINGS
WHICH DO NOT COMPLY WITH THE CONTRACT DOCUMENTS. REVIEWED
APPROVAL SHOP DRAWINGS SHOWING ENGINEERS COMMENTS ACCOMPANIED
WITH RECORD SET SHOP SHOP DRAWINGS, SHALL BE AVAILABLE FOR
REFERENCE AT THE CONSTRUCTION SITE.
13. CONCRETE ANCHORS SHALL BE SIMPSON 'TITEN HD" SCREW ANCHORS OR
EQUIVALENT (U.O.N.). INSTALL ANCHORS USING THE MANUFACTURER'S
RECOMMENDATIONS.
FOUNDATION NOTES:
1. FOOTING ELEVATIONS ARE TO TOP OF FOOTING (T.O. FTG.), UNLESS
OTHERWISE NOTED.
2. FOOTINGS ARE DESIGNED FOR A MINIMUM NET ALLOWABLE SOIL BEARING
PRESSURE OF 2500 psf FOR CONTINUOUS AND 2500 psf FOR PAD FOOTINGS.
FOUNDATION DESIGN COMPLIES W/ GEOTECHNICAL REPORT DATED: AUGUST 5,
2024 BY TERRACON.
3. FOOTINGS SHALL BEAR ON NATURAL UNDISTURBED SOIL OR ENGINEERED FILL.
SOILS SHALL BE OBSERVED AND APPROVED BY A GEOTECHNICAL ENGINEER
PRIOR TO PLACEMENT OF FOOTING CONCRETE. IF NATURAL UNDISTURBED
SOILS ARE NOT ENCOUNTERED AND/OR INADEQUATE SOILS ARE NOTED AT
FOOTING BEARING LEVEL, ARCHITECT/ENGINEER SHALL BE NOTIFIED PRIOR TO
PROCEEDING WITH FURTHER WORK AT THOSE FOOTING LOCATIONS.
4. PROTECT FOOTINGS FROM THE ACTION OF WATER OR FREEZING.
5. FOOTINGS ARE CENTERED UNDER WALLS ABOVE - UNLESS OTHERWISE
NOTED.
6. PRIOR TO PLACEMENT OF FOOTING CONCRETE, CLEAN FOOTING EXCAVATIONS
OF SNOW, WATER AND DEBRIS.
7. FOOTINGS MAY NOT BE EARTH FORMED.
EXCAVATION & BACKFILL NOTES:
1. EXCAVATION AND BACKFILL SHALL BE EXECUTED IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS.
2. BACKFILL, & COMPACTION SHALL BE INSPECTED AND CERTIFIED BY A LICENSED
GEOTECHNICAL ENGINEER. REPORTS ARE TO BE SUBMITTED TO THE
ARCHITECT/ ENGINEER.
3. FOOTING EXCAVATIONS SHALL BE EXCAVATED TO PROPER LINE AND LEVEL TO
ENSURE MINIMUM CONCRETE COVER OF FOOTING REINFORCEMENT FOR
FOOTING DEPTH.
4. BACKFILL SHALL BE COMPACTED BY MECHANICAL MEANS. FLOODING OR
WATER INUNDATION SHALL NOT BE PERMITTED.
5. BACKFILL SHALL BE PLACED IN ALTERNATING LIFTS ON EACH SIDE OF THE
FOUNDATION WALLS TO MAINTAIN STABILITY OF THE FOUNDATION WALLS.
6. BACKFILL SHALL NOT BE PLACED AGAINST BASEMENT FOUNDATION WALLS
UNLESS WALLS ARE ADEQUATELY BRACED TOP AND BOTTOM. FINAL WALL
BRACING IS BASEMENT SLAB OR ENGINEERED BACKFILL AND 1ST FLOOR
STRUCTURE. IF THESE ELEMENTS ARE NOT IN PLACE AT TIME OF BACKFILL,
CONTRACTOR SHALL PROVIDE AN ENGINEERED, TEMPORARY BRACING
SYSTEM. THE TEMPORARY BRACING SYSTEM PROPOSED SHALL BE SUBMITTED
TO THE ARCHITECT/ ENGINEER FOR REVIEW PRIOR TO BACKFILLING.
CONCRETE NOTES:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE
INSTITUTE (ACI) CODES AND SPECIFICATIONS, LATEST EDITION. ACI 301
"SPECIFICATIONS FOR STRUCTURAL CONCRETE" ACI 315 "DETAILS &
DETAILING OF CONCRETE REINFORCEMENT" ACI 318 "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE".
2. CONCRETE MIX DESIGN SHALL BE BY AN INDEPENDENT TESTING
LABORATORY.
3. CAST-IN-PLACE CONCRETE SHALL BE SUBJECT TO TESTING BY AN
INDEPENDENT TESTING LABORATORY. SEE PROJECT SPECIFICATIONS
FOR REQUIREMENTS.
4. NON WELDED REINFORCING STEEL SHALL BE GRADE 60 DEFORMED,
BILLET-STEEL, ASTM A615, U.O.N. ALL WELDED WIRE FABRIC (WWF)
SHALL BE PLAIN, ASTM A185.
5. WELDED REINFORCING STEEL SHALL BE GRADE 60, LOW CARBON, ASTM
A706.
6. PROVIDE EXTRA REINFORCEMENT AROUND ALL OPENINGS GREATER
THAN 12" SQUARE OR 12" IN DIAMETER, INCLUDING DOOR OPENINGS, IN
CONCRETE WALLS & SLABS. PROVIDE 2 - #5 BARS @ 3" O.C., ON EACH
SIDE OF THE OPENING EXTENDING 24" BEYOND THE CORNER OF THE
OPENING & 2 - #5 BARS AT 3" O.C. BY 3'-0" LONG DIAGONAL BARS AT EACH
CORNER. PLACE DIAGONAL BARS CENTERED ON CORNER @ 2" CLEAR
OF CORNER. ADDITIONAL REINFORCEMENT SHALL BE PROVIDED AT EACH
LAYER OF REINFORCING.
7. REINFORCING STEEL SHALL BE BENT, SPLICED, AND PLACED IN
ACCORDANCE WITH THE ACI 301 (LATEST EDITION).
8. PROVIDE ADEQUATE SUPPORT BARS AND ACCESSORIES TO HOLD
REINFORCING BARS FIRMLY IN PLACE TO SPECIFIED COVERAGES.
9. CONTROL JOINTS SHALL BE PLACED IN A SQUARE PATTERN WITH A
MAXIMUM SPACING OF 10' - 0" O.C. FOR 4" THICK SLAB, 12' - 0" O.C. FOR 5"
THICK SLAB, 15' - 0" O.C. FOR 6" THICK SLAB. WHERE A SQUARE PATTERN
IS NOT POSSIBLE, THE MAXIMUM LONG SIDE TO SHORT SIDE OF THE
JOINT PATTERN SHALL NOT EXCEED A RATIO OF 1.5:1. CONSTRUCTION
JOINTS SHALL BE LOCATED BY THE CONTRACTOR AS REQUIRED FOR
CONSTRUCTION WITH A MAXIMUM OF 3,000 SQUARE FEET.
10. CAST DOWELS, WITH STD 90 DEGREE HOOK, IN FOOTINGS FOR
CONCRETE PIERS AND WALLS ABOVE. DOWELS SHALL BE THE SAME SIZE
AND NUMBER AS THE VERTICAL REINFORCING. (U.O.N.)
11 CONCRETE MIX DESIGNS REQUIREMENTS: - AGGREGATES SHALL
CONFORM TO ASTM C33. - CONCRETE EXPOSED TO FREEZE THAW SHALL
HAVE 4.5%-7.5% AIR. - WATER/CEMENT RATIO 0.55 MAX. FOR FOOTINGS
AND WALLS, 0.5 MAX. FOR SLABS - NO FLY ASH IN EXPOSED SLABS, 0.25
MAX. FLY/ASH/CEMENT RATIO IN ALL OTHER APPLICATIONS - WATER
PROOFING ADMIXTURE ADD FOR EXTERIOR EXPOSED CONCRETE.
12 INJECTION ADHESIVE ANCHORS SHALL BE SIMPSON "SET-3G" USING
STANDARD 36 KSI THREADED RODS (U.O.N.). SEE SPECIFICATIONS FOR
USAGE. INSTALL ANCHORS IN STRUCTURAL CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
CAST-IN-PLACE CONCRETE COMPRESSIVE STREGNTHS
FOOTINGS 4000 psi.
EXTERIOR FOUNDATION WALLS 4000 psi.
PIERS 4000 psi.
INTERIOR SLABS ON GRADE 4000 psi.
EXTERIOR SLABS ON GRADE (AIR ENTRAINED) 4000 psi.
EXTERIOR SLABS ON DECK (AIR ENTRAINED) 4000 psi.
REINFORCING CLEAR CONCRETE COVER
CONCRETE ON SOIL 3"
SLABS ON GRADE MIDHEIGHT
FORMED WALLS & STRUCTURAL SLABS EXPOSED TO EARTH OR
WEATHER: #6 THRU #18
2"
FORMED WALLS & STRUCTURAL SLABS EXPOSED TO EARTH OR
WEATHER: #5 OR SMALLER
1 1/2"
FORMED WALLS & STRUCTURAL SLABS NOT EXPOSED TO EARTH OR
WEATHER: #11 AND SMALLER
3/4"
BEAMS AND COLUMNS (COVER TO STIRRUPS OR TIES) 1 1/2"
CONC. REINFORCING BAR LAP SPLICE
SCHEDULE
BAR SIZE
f'c = 3000 psi.
f'c = 4000 psi.
f'c = 5000 psi.
CLASS
"B"
CLASS
"B"
CLASS
"B"
#3 22" 20" 18"
#4 30" 26" 22"
#5 36" 32" 28"
#6 44" 38" 34"
#7 64" 54" 50"
#8 72" 62" 56"
#9 82" 70" 64"
#10 92" 80" 70"
#11 102" 88" 78"
BAR LAP SCHEDULE NOTES:
A. REINFORCING BAR LAP SPLICE SCHEDULE APPLIES TO UNCOATED, GRADE 60
REINFORCING BAR NORMAL WEIGHT CONCRETE.
B. PROVIDE CLASS "B" LAP UNLESS OTHERWISE NOTED.
C. FOR EPOXY COATED BAR, MULTIPLY THE NOTED LENGTHS BY 1.5.
D. FOR LIGHT WEIGHT CONCRETE, MULTIPLY THE NOTED LENGTHS BY 1.3.
E. MAXIMUM SPACING OF BARS BEING LAPPED IS ONE FIFTH THE LAP SPLICE
LENGTH, NOT TO EXCEED 6".
F. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12" OF CONCRETE PLACED
BELOW THEM. NORMAL WEIGHT CONCRETE.
STRUCTURAL STEEL NOTES:
1. WELDED CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THE LATEST
RECOMMENDATIONS OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(AISC) AND THE AMERICAN WELDING SOCIETY (AWS).
2. COLUMN BASE AND CAP PLATES TO BE WELDED AROUND ALL SIDES.
3. WELDS NOT SPECIFIED SHALL BE A FILLET WELD, CONTINUOUS AND/OR ALL
AROUND WITH MINIMUM THROAT DIMENSION AS REQUIRED FOR MATERIAL
THICKNESS PER AWS.
4. STRUCTURAL FABRICATORS SHALL SHOW ALL FIELD WELDING REQUIREMENTS
ON SHOP DRAWINGS SUBMITTED TO THE ENGINEER.
5. BEFORE ENCASING STEEL COLUMNS IN CONCRETE OR MASONRY, COAT
COLUMN BASES AND TOPS OF ANCHOR BOLTS WITH ASPHALTIC ROOF CEMENT.
6. BEAMS AND COLUMNS SHALL BE ERECTED TRUE AND PLUMB WITHIN AISC
TOLERANCE. PROVIDE TEMPORARY BRACING AS REQUIRED.
7. BEARING PLATES FOR STEEL SHALL BE DRY PACKED WITH A NON-SHRINK,
NON-METALLIC GROUT AS SPECIFIED.
8. PROVIDE DOUBLE ANGLE CONNECTIONS AS DESCRIBED IN PART 10 OF THE AISC
MANUAL OF STEEL CONSTRUCTION (15TH ED-ASD). CONNECTIONS SHALL BE
SELECTED TO SUPPORT BEAM END REACTIONS INDICATED ON THE CONTRACT
DRAWINGS. IF BEAM END REACTIONS ARE NOT INDICATED, CONNECTIONS
MUST BE SELECTED ACCORDING TO THE STANDARD DETAILS OF THE
CONTRACT DRAWINGS. IF BEAM IS NOT ABLE TO SATISFY THE CONDITIONS OF
THE STANDARD DETAILS CONTACT ENGINEER OF RECORD FOR SPECIFIC
DETAILING.
9. FRAMED STEEL BEAM CONNECTIONS SHALL BE "BEARING TYPE", (U.O.N.).
10. DO NOT PAINT STEEL TO BE FIELD WELDED.
AISC MATERIAL SPECIFICATION (13TH EDITION)
"W", "S" AND "M" SHAPES ASTM A992 Fy = 50 ksi.
GRADE "B" STANDARD PIPES ASTM A53 Fy = 35 ksi.
GRADE "C" HSS PIPES ASTM A500 Fy = 46 ksi.
GRADE "C" HSS TUBES ASTM A500 Fy = 50 ksi.
PLATES, BARS, CHANNELS, RODS, ANGLES AND
MISC. SHAPES
ASTM A36 Fy = 36 ksi.
GRADE 36 ANCHOR BOLTS ASTM F1554-99 Fy = 36 ksi.
CONNECTION BOLTS ASTM A325 Fv = 120 ksi.
CONNECTION BOLTS ASTM A490 Fv = 150 ksi.
CONNECTION NUTS ASTM A563
WASHERS ASTM F436
ELECTRODES E70XX
ENGINEERED WOOD NOTES:
1. LAMINATED WOOD FABRICATOR SHALL BE AN "AITC" MEMBER AND SHALL
FABRICATE ACCORDING TO "AITC" SPECIFICATIONS.
2. LAMINATED WOOD SUPPLIER SHALL FURNISH ALL HANGERS, HARDWARE &
ACCESSORIES FOR ALL CONNECTIONS ASSOCIATED W/ LAMINATE WOOD
MEMBERS (U.O.N.).
3. SEE ARCHITECTURAL DETAILS AND SPECIFICATIONS FOR MATERIAL TYPE
AND FINISHES, UNLESS OTHERWISE NOTED.
4. ALL LAMINATED FRAMING MEMBERS ARE SPECIFIED AS DOUG-FIR
COMBINATION 24FV4, - SOUTHERN-PINE COMBINATION 24FV3 MAY BE USED
WITH EQUIVALENT DESIGN VALUES & SECTION PROPERTIES.
5. STRUCTURAL STEEL SUPPLIER SHALL FURNISH ALL REMAINING WOOD TO
STEEL CONNECTIONS, HANGERS AND HARDWARE WHICH ARE REQUIRED TO
COMPLETE THE ERECTION OF THE LAMINATED WOOD.
6. LAMINATED WOOD MANUFACTURER AND STRUCTURAL STEEL SUPPLIER
SHALL COORDINATE ALL CONNECTION DETAILS PRIOR TO FABRICATION.
7. PROVIDE STANDARD CAMBER AT ALL ROOF BEAMS AND PURLINS.
ENGINEERED WOOD MEMBER DESIGN PROPERTIES:
GLU-LAM MEMBERS BENDING Fb = 2400 psi.
SHEAR Fv = 265 psi.
COMPRESSION PARALLEL TO GRAIN Fc = 1650 psi.
COMPRESSION PERPENDICULAR TO GRAIN Fc = 650 psi.
MODULUS OF ELASTICITY E = 1800 ksi.
LIGHT GAUGE FRAMING NOTES:
1. LIGHT GAUGE STEEL CONSTRUCTION SHALL CONFORM TO THE FOLLOWING
STANDARDS: AMERICAN IRON & STEEL INSTITUTE (AISI) - "SPECIFICATION
FOR THE DESIGN OF COLD FORMED STRUCTURAL MEMBERS". ASTM C-955 -
"STANDARD SPECIFICATION FOR LOAD BEARING STEEL STUDS, TRACKS, &
BRIDGING." ASTM C-1007 - "STANDARD SPECIFICATION FOR INSTALLATION
OF LOAD BEARING STEEL STUDS & RELATED ACCESSORIES"
2. LIGHT GAUGE FRAMING MEMBERS SHALL BE SIZED AS SHOWN ON THE
CONTRACT DOCUMENTS. STUDS SHALL BE A MINIMUM 1 5/8" x 3 1/2" WITH A
3/8" RETURN LIP.
3. TRACKS SHALL BE INSTALLED AT THE TOPS AND BOTTOMS OF ALL VERTICAL
STUDS AND SHALL BE THE SAME GAUGE AS THE WALL STUDS. TRACK SIZE
SHALL BE 1 1/4" x 3 1/2" MINIMUM. TRACKS SHALL BE CONNECTED TO THE
STUDS WITH 2 - #8 SCREWS (MIN.), ONE AT EACH FLANGE.
4. WELDED CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THE LATEST
RECOMMENDATION OF THE AMERICAN IRON AND STEEL INSTITUTE (AISI)
AND THE AMERICAN WELDING SOCIETY (AWS).
5. FOR LIGHT GAUGE EXTERIOR CURTAIN WALL DESIGN CRITERIA: SEE
"DESIGN LOADS" TABLE ON SHEET S0.01
6. LIGHT GAUGE YIELD STRENGTH: ASTM A653, A875, A792 OR A463 (G-60 GALV.
FINISH, MIN.); ALL DESIGN THICKNESSES - 33 ksi.; 16 GA. AND HEAVIER - 50 ksi.
BOTH STUDS AND TRACK SHALL BE A MINIMUM UNCOATED BASE METAL
THICKNESS OF 0.033 INCH (18 GAUGE).
7. ALL WALL STUDS SHALL BE BRACED WITH A COLD ROLLED CHANNEL RUN
THROUGH THE STUD PUNCH OUTS AND ATTACHED TO A CLIP ANGLE AT
EACH STUD. THE COLD ROLLED CHANNELS SHALL BE 1 1/2" x 1 1/2", 16 GA.
AND ATTACHED WITH 2 - SCREWS PER FLANGE. AT SPLICES, OVERLAP THE
CHANNEL BY 12". VERTICAL SPACING OF CHANNELS SHALL NOT EXCEED
4'-0" O.C.
8. STRUCTURAL FRAMING MEMBERS SHALL CONFORM TO ASTM C955 & HAVE
ENGINEERING PROPERTIES CALCULATED IN CONFORMANCE WITH AISI
"SPECIFICATION FOR THE DESIGN OF COLD - FORMED STEEL STRUCTURAL
MEMBERS".
9. NO NOTCHING OF STUDS, JOISTS, BEAMS OR TRUSS MEMBERS IS
PERMITTED WITHOUT THE ENGINEERS APPROVAL.
10. WEB PUNCH OUTS MUST BE LOCATED @ A MIN. 1'-0" CLEAR FROM ALL
BEARING LOCATIONS.
11. JOISTS MUST BE BRACED AGAINST ROTATION @ ALL BRG SUPPORTS BY
TRACK OR BLOCKING.
12. PROVIDE HORIZONTAL BRIDGING AT ALL JOIST MEMBERS AS
RECOMMENDED BY THE AISI "SPECIFICATION FOR THE DESIGN OF COLD
FORMED STRUCTURAL MEMBERS" WITH MINIMUM ROWS AS FOLLOWS
(U.O.N.): SPANS UP TO 14'-0" - 1 ROW AT MIDPOINT; 14'-0" UP TO 20'-0" - 2
ROWS @ THIRD POINTS; 20'-0" & GREATER - 1 ROW EVERY 6'-0" O.C.
BRIDGING MATERIALS SHALL BE SAME GRADE AND GAUGE AS JOIST
MEMBERS.
13. ALL JOISTS, BEAMS, GIRDERS AND TRUSSES SHALL HAVE FULL HORIZONTAL
BEARING OF THE MEMBER OVER SUPPORT UNLESS OTHERWISE SHOWN.
14. ROOF TRUSSES ARE TO BE ENGINEERED BY FABRICATOR AND ERECTED
ACCORDING TO MANUFACTURER'S SPECIFICATIONS. LIGHT GAUGE TRUSS
CONSTRUCTION AND FABRICATION SHALL FOLLOW GUIDELINES SET FORTH
BY THE LIGHT GAUGE STEEL ENGINEERS ASSOCIATION (LGSEA). SEE
PROJECT SPECIFICATIONS FOR ADDITIONAL TRUSS INFORMATION.
15. ALL FABRICATED LIGHT GAUGE TRUSSES SHALL BE FURNISHED IN
ACCORDANCE WITH DESIGNS PREPARED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE THE PROJECT IS LOCATED, USING THE DESIGN
LOADS AND SPAN CONDITIONS INDICATED ON THE CONTRACT DOCUMENTS.
NO DEVIATION OF TRUSS SHAPE, MEMBER SIZE, BEARING POINT LOCATION,
OR SUPERIMPOSED LOADS, FROM THE CONTRACT DOCUMENTS SHALL BE
PERMITTED WITHOUT THE APPROVAL OF THE ARCHITECT AND / OR THE
ENGINEER. SHOP DRAWINGS, INCLUDING AN OVERALL ERECTION PLAN
INDICATING EACH TYPE OF TRUSS, TRUSS BEARING POINT LOCATIONS,
REQUIRED LATERAL BRACING, EACH TRUSS MEMBERS SIZE AND STRESS
AND CONNECTION DETAILS, SHALL BE SUBMITTED FOR PRIOR APPROVAL TO
THE GENERAL CONTRACTOR.
16. THE LIGHT GAUGE TRUSS SUPPLIER SHALL PROVIDE THE LGSEA
PUBLICATION "FIELD INSTALLATION GUIDELINES" DATED OCT. 1999, WITH
THE TRUSS ERECTION DWGS. FOR REFERENCE BY THE TRUSS INSTALLER.
17. THE GUIDELINES SET FORTH BY THE LGSEA "FIELD INSTALLATION
GUIDELINES" SHALL BE FOLLOWED BY THE TRUSS INSTALLER.
18. PERMANENT BRACING OF LIGHT GAUGE TRUSSES SHALL BE INSTALLED BY
THE TRUSS INSTALLER, WHERE INDICATED BY THE TRUSS ERECTION DWGS.
MINIMUM BRACING REQUIREMENTS FOR TOP CHORD, BOTTOM CHORD, &
WEB MEMBER PLANES SHALL BE IN ACCORDANCE W/ THE LGSEA "FIELD
INSTALLATION GUIDELINES" UNLESS REQUIREMENTS NOTED ON THE PLAN
ARE MORE STRICT.
19. ERECTION BRACING OF LIGHT GAUGE TRUSSES IS THE RESPONSIBILITY OF
THE TRUSS INSTALLER. THE TRUSS INSTALLER SHALL PROVIDE
TEMPORARY DIAGONAL, LATERAL, & CROSS BRACING (PER LGSEA) UNTIL
ROOF SHEATHING, CEILING & PERMANENT BRACING CAN BE APPLIED &
SHEAR WALLS COMPLETED.
20. ROOF TRUSSES SHALL BE FASTENED TO THE SUPPORT WALLS WITH
SIMPSON "S/H3" TIES OR EQUAL (U.O.N.) AND SHALL BE FASTENED PER
MANUFACTURER'S RECOMMENDATIONS.
VERTICAL STRUCTURAL PANEL SHEATHING NOTES:
VERTICAL GENERAL:
1. FASTENERS SHALL NOT BE LOCATED LESS THAN 3/8" IN FROM THE EDGE OF
THE PANEL.
2. FASTENERS SHALL BE DRIVEN FLUSH WITH SURFACE OF SHEATHING.
3. FASTENERS SHALL BE OF SUFFICIENT LENGTH TO ENSURE PENETRATION INTO
FRAMING MEMBERS BY AT LEAST 1 1/2" INTO WOOD FRAMING OR AT LEAST 3
EXPOSED THREADS AT LIGHT GAUGE FRAMING.
4. NO PANEL LESS THAN 1'-0" WIDE SHALL BE USED.
5. PANEL EDGES SHALL BUTT ALONG THE CENTERLINE OF FRAMING MEMBERS.
6. IN THE PRE-FABRICATED WALL PANEL APPLICATION, ALL ADJACENT WALL
PANEL EDGES THAT DO NOT SHARE A COMMON FRAMING MEMBER OF
ADJOINED WALL PANELS FASTENED TOGETHER WITH ONE ROW OF STAGGERED
10D NAILS @ 6" ON CENTER FROM BOTH SIDES.
7. LIGHT GAUGE STUDS SHALL BE DOUBLED (BACK-TO-BACK) AT SHEAR WALL
ENDS.
8. ALL PANEL EDGES SHALL BE FULLY BLOCKED. WHERE HORIZONTAL STRAP
BLOCKING IS USED, IT SHALL BE A MINIMUM 1 1/2" WIDE & OF THE SAME
MATERIAL & THICKNESS AS THE TRACK & STUDS.
HORIZONTAL STRUCTURAL PANEL SHEATHING NOTES:
HORIZONTAL GENERAL:
1. FASTENERS SHALL NOT BE LOCATED LESS THAN 3/8" IN FROM THE EDGE OF
THE SHEATHING PANEL.
2. FASTENERS SHALL BE DRIVEN FLUSH WITH SURFACE OF SHEATHING.
3. FASTENERS SHALL BE OF SUFFICIENT LENGTH TO ENSURE PENETRATION
INTO FRAMING MEMBERS BY AT LEAST 1 1/2" INTO WOOD FRAMING OR AT
LEAST 3 EXPOSED THREADS AT LIGHT GAUGE FRAMING.
4. NO UNBLOCKED PANELS LESS THAN 1'-0" WIDE SHALL BE USED.
5. SHEATHING PANEL EDGES SHALL BUTT ALONG THE CENTERLINE OF A
COMMON FRAMING MEMBER.
HORIZONTAL WOOD SHEATHING:
1. PANEL ROOF SHEATHING SHALL BE 1/2" APA EXPOSURE 1, RATED
SHEATHING WITH A 32/16 SPAN RATING (U.O.N.).
2. PANEL FLOOR SHEATHING SHALL BE 3/4" APA EXPOSURE 1, RATED
PLYWOOD WITH A 48/24 SPAN RATING (U.O.N.).
3. WOOD FRAMING SHEATHING FASTENERS SHALL BE A MINIMUM 0.148" DIA. x
3" LONG COMMON NAILS. LIGHT GAUGE SHEATHING FASTENERS SHALL BE A
MINIMUM #8 FLAT HEAD W/ MINIMUM HEAD DIAMETER OF 0.292" IN
ACCORDANCE W/ SAE J78. SEE HORIZONTAL GENERAL NOTE #3 FOR
LENGTH.
4. FLOOR/ ROOF PANEL SHEATHING SHALL BE CONTINUOUS OVER 2 OR MORE
SUPPORTS (MINIMUM).
5. FLOOR/ ROOF PANEL SHEATHING SHALL BE ORIENTED WITH THE STRENGTH
AXIS PERPENDICULAR TO THE SUPPORTS.
6. TONGUE & GROOVE EDGES, PANEL EDGE CLIPS (1 - MIDWAY BETWEEN EACH
SUPPORT), OR BLOCKING SHALL BE USED @ ALL UNSUPPORTED EDGES.
7. SPACE FASTENERS @ 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS
(FIELD OFSHEATHING PANEL); SPACE FASTENERS @ 6" O.C. ALONG ALL
SHEATHING PANEL EDGE FRAMING MEMBERS (SUPPORTED EDGES) (U.O.N.).
8. EACH SHEATHING PANEL SHALL BE IDENTIFIED WITH THE GRADE
TRADEMARK OF THE AMERICAN PLYWOOD ASSOCIATION AND SHALL MEET
THE REQUIREMENTS OF PRODUCT STANDARD (psi). APPLICATION AND
NAILING OF PLYWOOD SHALL BE IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE AMERICAN PLYWOOD ASSOCIATION & TABLE
2304.10.1 "FASTENING SCHEDULE" OF THE INTERNATIONAL BUILDING CODE
UNLESS OTHER REQUIREMENTS NOTED ON THE PLAN ARE MORE STRICT.
VERTICAL WOOD SHEATHING:
1. BLOCK ALL SHEATHING PANEL EDGES.
2. PANEL SHEATHING SHALL BE_7/16" APA EXPOSURE 1, RATED SHEATHING
WITH A 32/16 SPAN RATING (U.O.N.).
3. FRAMING SPACING TO BE MAXIMUM 1'-4" O.C. UNLESS SPECIFIC NOTES AND /
OR DETAILS ARE MORE STRICT.
4. WOOD FRAMING SHEATHING FASTENERS SHALL BE A MINIMUM 0.131" DIA. x 2
1/2" LONG COMMON NAILS OR GALVANIZED BOX NAILS (GALVANIZED NAILS
SHALL BE HOT-DIPPED OR TUMBLED). LIGHT GAUGE SHEATHING
FASTENERS SHALL BE MINIMUM #8 FLAT HEAD W/ MINIMUM HEAD DIAMETER
OF 0.292" IN ACCORDANCE W/ SAE J78. SEE VERTICAL GENERAL NOTE #3
FOR LENGTH.
5. OFFSET SHEATHING PANEL JOINTS ON EACH SIDE OF WALL MINIMUM ONE
STUD BAY.
6. SHEATHING PANELS MAY BE INSTALLED EITHER PARALLEL OR
PERPENDICULAR TO FRAMING.
7. SPACE FASTENERS @ 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS
(FIELD OF PANEL); SPACE FASTENERS @ 6" O.C. ALONG ALL EDGE FRAMING
MEMBERS (SUPPORTED EDGES) (U.O.N.).
8. EACH SHEATHING PANEL SHALL BE IDENTIFIED WITH THE GRADE
TRADEMARK OF THE AMERICAN PLYWOOD ASSOCIATION AND SHALL MEET
THE REQUIREMENTS OF PRODUCT STANDARD (psi). APPLICATION AND
NAILING OF PLYWOOD SHALL BE IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE AMERICAN PLYWOOD ASSOCIATION & TABLE
2304.10.1 "FASTENING SCHEDULE" OF THE INTERNATIONAL BUILDING CODE
UNLESS OTHER REQUIREMENTS NOTED ON THE PLAN ARE MORE STRICT.
16. DESIGN LOADS:
ROOF LIVE LOADS:
ROOF SNOW Pf = 14 psf.
IMPORTANCE FACTOR Is = 1.0
EXPOSURE FACTOR Ce = 1.0
THERMAL FACTOR Ct = 1.0
GROUND SNOW LOAD Pg = 20 psf.
CONSTRUCTION LOADING 25 psf.
LIVE LOAD 20 psf.
DEAD LOADS
TYPICAL ROOF DL = 20 psf.
LATERAL LOADS (WIND -
MSFRS)
IMPORTANCE FACTOR 1.0 Iw
ULTIMATE WIND SPEED (3 SECOND GUST) 115 MPH.
NOMINAL WIND SPEED 89.1 MPH.
RISK CATEGORY II
WIND EXPOSURE "C"
INTERNAL PRESSURE COEFF +/- 0.18
COMPONENTS CLADDING BASE PRESSURE 24.7 psf.
LATERAL LOADS
(SEISMIC - MSFRS)
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR Ie = 1
MAPPED SPECTRAL RESPONSE Ss = 0.123
MAPPED SPECTRAL RESPONSE S1 = 0.069
DESIGN SPECTRAL RESPONSE Sds = 0.131
DESIGN SPECTRAL RESPONSE Sd1 = 0.110
SITE CLASS D
SEISMIC DESIGN CATEGORY B
SEISMIC FORCE RESISTING SYSTEM LIGHT FRAME (COLD-FORMED
STEEL) WALLS WITH WOOD
PANELS OR STEEL SHEETS
DESIGN BASE SHEAR V = 0.020W
SEISMIC RESPONCE COEFFICIENT Cs = 0.020
RESPONSE MODIFICATION FACTOR R = 6.5
ANALYSIS PROCEDURE ELFA
ABBREVIATIONS & SYMBOLS:
+/- PLUS OR MINUS
@ AT
A.B. ANCHOR BOLT
A.P.A. AMERICAN PLYWOOD
ASSOCIATION
A.S.T.M. AMERICAN SOCIETY OF TESTING
MATERIALS
ARCH. ARCHITECTURAL
B.B. BOND BEAM
B.O. BOTTOM OF
BLK. BLOCK
BM. BEAM
BOT. BOTTOM
BRG. BEARING
C CHANNEL
C.M.U. CONCRETE MASONRY UNIT
CCJ CONSTRUCTION CONTROL JOINT
CJ CONTROL JOINT
CL. CENTER LINE
CLR. CLEAR
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONT. CONTINUOUS
D.L. DEAD LOAD
D.T. DOUBLE TEE / DRAIN TILE
DBL. DOUBLE
DIA. DIAMETER
DIM. DIMENSION
DWL. DOWEL
E.F. EACH FACE
E.J. EXPANSION JOINT
E.W. EACH WAY
EA. EACH
EL. ELEVATION
ELEV. ELEVATOR
EQ. EQUAL
EX. EXISTING
EXC. EXCAVATION
EXP. EXPANSION
F.D. FLOOR DRAIN
FDN. FOUNDATION
FT. FEET
FTG. FOOTING
G.C. GENERAL CONTRACTOR
G.T. GIRDER TRUSS
GA. GAUGE
GALV. GALVANIZE
HC. HOLLOWCORE
HORIZ. HORIZONTAL
HSS HOLLOW STRUCTURAL SECTION
I.F. INSIDE FACE
INT. INTERIOR
JST. JOIST
KLF. KIPS PER LINEAR FOOT
KSI. KIPS PER SQUARE INCH
L ANGLE
LB LEDGER BEAM
LL LIVE LOAD / DOUBLE ANGLE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG. LONGITUDINAL
LWC LIGHT WEIGHT CONCRETE
M.C. MECHANICAL CONTRACTOR
MAS. MASONRY
MAX. MAXIMUM
MECH. MECHANICAL
MFG. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
MTL. METAL
N. NORTH
N.T.S. NOT TO SCALE
NS. NON-SHRINK
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F. OUTSIDE FACE
O.H. OVERHEAD
OPNG. OPENING
ORIG. ORIGINAL
P.A.F. POWDER ACTUATED FASTENER
P.C. PRECAST CONCRETE
PART. PARTITION
PL. PLATE
PLF POUNDS PER LINEAR FOOT
PNL. PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PW PLYWOOD
R. OR
RAD.
RADIUS
R.D. ROOF DRAIN
REINF. REINFORCING
REQD. REQUIRED
S.A. STUD ANCHOR
S.B. SOIL BORING
S.D. SEE DETAIL
S.D.L. SUPERIMPOSED DEAD LOAD
S.E.R. STRUCTURAL ENGINEER OF
RECORD
S.L. SNOW LOAD
S.L.L. SUPERIMPOSED LIVE LOAD
S.S. STAINLESS STEEL
SCHED. SCHEDULE
SHT. SHEET
SIM. SIMILAR
SPA. SPACING / SPACES
SPECS. SPECIFICATIONS
SQ. SQUARE
STD. STANDARD
STL. STEEL
T & B TOP & BOTTOM
T & G TONGUE & GROOVE
T.O. TOP OF
T.O.B. TOP OF BEAM
T.O.J. TOP OF JOIST
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
T.S.E. TOP OF STEEL ELEVATION
TEMP. TEMPORARY
THK. THICK / THICKENED
TRANS. TRANSVERSE
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
V. / VER. VERIFY
VERT. VERTICAL
W.L. WIND LOAD
W/ WITH
W/O WITH OUT
WD. WOOD
WTS. WEIGHTS
WWF WELDED WIRE FABRIC
DEFERRED SUBMITTAL SCHEDULE NOTES:
1. PREFABRICATED COMPONENTS OR SYSTEMS SPECIFIED ON THE STRUCTURAL
DRAWINGS TO BE DESIGNED BY OTHERS SHALL BE SUBMITTED BY THE
CONTRACTOR TO THE ARCHITECT OR ENGINEER OF RECORD FOR REVIEW AS A
DEFERRED SUBMITTAL. DEFERRED SUBMITTALS SHALL INCLUDE DRAWINGS
AND CALCULATIONS THAT HAVE BEEN STAMPED AND SIGNED BY AN ENGINEER
APPROPRIATELY LICENSED IN THE STATE OF CONSTRUCTION.
2. THE PURPOSE OF THE ENGINEER OF RECORD’S REVIEW SHALL BE
DETERMINING THAT THE DRAWINGS AND CALCULATIONS HAVE BEEN PROPERLY
SEALED, THAT THE LOAD CRITERIA IS IN GENERAL CONFORMANCE WITH THE
CONTRACT DOCUMENTS AND THE REFERENCED BUILDING CODE, AND THAT THE
CONNECTIONS TO THE PRIMARY STRUCTURE ARE APPROPRIATE FOR THE
STRUCTURE’S DESIGNED CAPABILITIES.
3. THE STRUCTURAL ENGINEER WILL RELY ON THE SPECIALTY ENGINEER’S SEAL
AS CERTIFICATION THAT THE ITEMS DESIGNED BY THE SPECIALTY ENGINEER
COMPLY WITH THE CRITERIA SET FORTH IN THE CONTRACT DOCUMENTS AND
APPLICABLE CODES AND STANDARDS. THE STRUCTURAL ENGINEER SHALL NOT
BE RESPONSIBLE FOR THE ADEQUACY OF DESIGNS PROVIDED BY OTHERS.
DEFERRED SUBMITTAL SCHEDULE:
PREFABRICATED LIGHT GAUGE ROOF TRUSSES
LIGHT GAUGE STUD WALLS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
17101
100% CONSTRUCTION
DOCUMENTS
C U s e rs \J
B u e rm a n n
\D o c u m e n ts
\1
P
IC
a m p A d m in is tr a ti o n
R V
T jb u e rm a n n S
R X
R
.r v t
/1 /2
:4
:0
P M
PIC ADMIN. BLDG - NOTE SHEET
OCTOBER 30, 2024 EW DW/JB
1001-S001
MARION NATIONAL CEMETERY
NEW LAND EXPANSION
817CM3025
1700 E. 38TH ST. MARION IN 46953
LAMINATED WOOD DECKING NOTES
1. LAMINATED WOOD DECKING SHALL BE 3" NOMINAL (2 3/16" ACTUAL MINIMUM)
SOLID DOUGLAS FIR / LARCH WITH THE FOLLOWING MINIMUM DESIGN VALUES:
E = 1800 ksi. - MODULUS OF ELASTICITY, Fb = 2500 psi. - BENDING, Fv = 165 psi. -
SHEAR.
2. ALL WOOD DECKING SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS W/ CONTINUOUS RANDOM LENGTH
LAYOUT.
3. PLACE DECK WITH TONGUE UP, BEGINNING AT THE LOW POINTS OF THE ROOF.
4. ALL WOOD DECKING SHALL BE NAILED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS WITH THE FOLLOWING MINIMUM
REQUIREMENTS: ATTACH EACH COURSE OF DECKING TO SUPPORT WITH 3 -
0.216" DIA. x 4 1/2" WOOD SCREWS. SECURE ADJACENT COURSES BY SLANT NAILING WITH 0.131" DIA. x 2 1/2" LONG NAILS AT A MAXIMUM 30" O.C., STAGGER
LOCATIONS IN ALTERNATE COURSES BY 15". DRIVE NAILS AT AN ANGLE OF 40
DEGREE TO 50 DEGREE STARTING WITHIN 12" OF EACH END JOINT.
Revisions: Date:
10/30/2024
OF 266162162 OF 266162
B
F
1 4
86' - 0"
4" CONC. SLAB, REINF. W/ #4 @ 1'-6" EACH WAY,
ON 12 MIL. (MIN.) VAPOR BARRIER ON 6" SAND FILL
T.O. SLAB EL. = 100'-0" U.O.N.
13' - 4"
5'
0"
10' - 0" 6' - 0"
5'
0"
1'
4"
1' - 4"
1'
4"
1' - 4"
FC2.5
FC2.5
FC2.5
FC1.7
FC1.7
FC2.5
C
FC2.5
FC1.7
8" 8"
2 3
3' - 0" 15' - 4" 3' - 0" 36' - 8" 28' - 0"
2'
0" 8'
0"
A
1.2 1.8
FS3.5FS3.5
P1 P1
S301
S301
S301
S301
S301
S301
S301
S301
S301
S301
D
E
HD1
HD1
HD1
HD1
BP1 BP1
B.2
FS3.5FS3.5
P1P1
BP1 BP1
1' - 0"1' - 0"
2' - 0"
2'
0"
5'
0"
SHEET NOTES:
1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
2. SEE SHEET 1001-S001 FOR GENERAL STRUCTURAL NOTES.
3. P# = PIER MARK - SEE PIER SCHEDULE ON THIS SHEET.
4. BP# = BASE PLATE MARK - SEE BASE PLATE SCHEDULE ON THIS SHEET.
5. FC/S/T# = FOOTING MARK - SEE FOOTING SCHEDULE ON THIS SHEET.
6. HD# = HOLDOWN MARK - SEE HOLDOWN SCHEDULE ON THIS SHEET.
KEYNOTES:
1 FOOTING CONNECTION DETAIL - S.D. 9/1001-S301
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
17101
100% CONSTRUCTION
DOCUMENTS
C U s e rs \J
B u e rm a n n
\D o c u m e n ts
\1
P
IC
a m p A d m in is tr a ti o n
R V
T jb u e rm a n n S
R X
R
.r v t
/1 /2
:4
:0
P M
PIC ADMIN. BLDG - FOOTING &
FOUNDATION PLAN
OCTOBER 30, 2024 EW DW/JB
1001-S101
MARION NATIONAL CEMETERY
NEW LAND EXPANSION
817CM3025
1700 E. 38TH ST. MARION IN 46953
1/4" = 1'-0"
FOOTING & FOUNDATION PLAN
T.O. EXT. FOOTING EL. = 97' - 0"
FOOTING SCHEDULE
MARK WIDTH DEPTH
REINFORCING
TRANSVERSE LONGITUDINAL
FC1.7 1'-8" CONT. 1'-0" --- 2 - #5
FC2.5 2'-6" CONT. 1'-0" #5 @ 6'-0" O.C. 2 - #5
FS3.5 3'-6" x 3'-6" 1'-0" 5 - #5 5 - #5
HOLDOWN SCHEDULE
MARK HOLDOWN TYPE
ANCHOR
POST SIZE
ANCHOR
BOLT SIZE
"E" MINIMUM
EMBED DEPTH
COMMENTS
HD1 1 - SIMPSON "S/HDU6" 2 - 6" x 18 GA. 5/8" DIA. 8" S.D. 12/S301
HOLDOWN SCHEDULE NOTES:
1. ALL ANCHOR POSTS TO BE 6" x 18 GA. U.O.N.
2. ALL "HD" HOLDOWN ANCHOR BOLTS MAY BE INJECTION ADHESIVE ANCHORS U.O.N.
3. ANCHOR BOLT NUTS TO BE SNUG TIGHT PLUS 1/2 TURN.
4. PROVIDE 3" x 3" x .229" WASHER BETWEEN SILL PLATE & NUT @ ALL HOLDOWN ANCHORS.
0 4' 8'2'
Revisions: Date:
OF 266163163 OF 266163
B
F
1 4
86' - 0"
2'
0"
2'
0"
8'
0"
H1
H1
H1H1H1
H1H1H1H1H1H1H1
H1 H1
H
H
H
H
H
H1
H
H1
C
H
H1
H1
H1H1H1
B1
2 3
3' - 0" 15' - 4" 3' - 0" 36' - 8" 28' - 0"
A
1.2 1.8
S401
S401
S401
S401
S401
S401
D
E
TYP. @
EXTERIOR
SW1
TYP. @
EXTERIOR
SW1
8 1/2"
8 1/2"
8 1/2"
TYP. @
EXTERIOR
SW1
8 1/2"
TYP. @
EXTERIOR
SW1
1/
8" x
1/ 2"
G
LU
-L A
M
1/
8" x
1/ 2"
G
LU
-L A
M
1/
8" x
1/ 2"
G
LU
-L A
M
5 1/8" x 10 1/2" GLU-LAMC2 C2
C1
DORMER TRUSSES
@ 2'-0" O.C.
S401
S401
TRUSSES @ 2'-0" O.C.
LIGHT GAUGE ROOF
S401
________________________________________________________________________________TYP.
@ C2
S401
S401
B.2
5 1/8" x 10 1/2" GLU-LAM
C2 C1 C2
3' - 0"
SHEET NOTES:
1. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
2. SEE SHEET 1001-S001 FOR GENERAL STRUCTURAL NOTES.
3. B# / H# - BEAM / HEADER MARK - SEE BEAM / HEADER SCHEDULE ON THIS SHEET.
4. SW# - SHEAR WALL TYPE MARK (BELOW) - SEE SHEARWALL SCHEDULE ON THIS SHEET.
5. C# - COLUMN MARK - SEE COLUMN SCHEDULE ON THIS SHEET.
6. ALL STRUCTURAL BEARING "EXTERIOR" & "INTERIOR" STUD WALLS SHALL BE 6" 16 GA. MIN. METAL STUDS @ 1'-4" O.C.
MAX. BY SUPPLIER.
7. ROOF SHEATHING TO BE 1/2" APA RATED SHEATHING WITH A 32/16 SPAN RATING.
8. ROOF TRUSS SUPPLIER TO PROVIDE ALL REQUIRED BRACING & BRIDGING.
9. ROOF DECK SHALL BE 3x6 TONGUE & GROOVE LAMINATED WOOD DECKING. SEE 1001-S001 FOR GENERAL DECKING
CRITERIA.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
17101
100% CONSTRUCTION
DOCUMENTS
C U s e rs \J
B u e rm a n n
\D o c u m e n ts
\1
P
IC
a m p A d m in is tr a ti o n
R V
T jb u e rm a n n S
R X
R
.r v t
/1 /2
:4
:0
P M
PIC ADMIN. BLDG - ROOF
FRAMING PLAN
OCTOBER 30, 2024 EW DW/JB
1001-S201
MARION NATIONAL CEMETERY
NEW LAND EXPANSION
817CM3025
1700 E. 38TH ST. MARION IN 46953
1/4" = 1'-0"
ROOF FRAMING PLAN
BEAM/HEADER SCHEDULE
MARK BEAM / HEADER SIZE
B1 BEAMS BY SUPPLIER
H1 HEADERS BY SUPPLIER
SHEARWALL SCHEDULE NOTES:
1. FASTENERS SHALL BE A MINIMUM #10 SCREWS.
2. BACK ALL PANEL EDGES WITH 2x BLOCKING MINIMUM.
3. GYPSUM & RATED SHEATHING PANEL EDGES TO BE FASTENED AS NOTED. INTERMEDIATE
SUPPORTS SHALL BE FASTENED @ 1'-0" O.C.
4. WHERE PANELS ARE APPLIED ON 2 - SIDES OF WALL PANEL JOISTS SHALL BE OFFSET TO FALL
ON DIFFERENT FRAMING MEMBERS. ALTERNATIVLEY WHERE PANEL JOINTS CAN NOT BE
STAGGERED THE WIDTH OF THE FACE OF FRAMING MEMBERS SHALL BE 3" NOMINAL OR
GREATER AT ADJOINING PANEL EDGES WITH PANEL EDGE NAILING STAGGERED.
5. 7/16" RATED SHEATHING SHALL BE EXPOSURE NO.1, WITH A 24/16 SPAN RATING. 19/32" RATED
SHEATHING SHALL BE EXPOSURE NO. 1, WITH A 40/20 SPAN RATING.
6. SHEATHING TO EXTEND FROM THE FLOOR TO THE FLOOR OR ROOF SHEATHING ABOVE.
7. ANCHOR BOLTS FOR SHEARWALLS SHALL BE SIMPSON "TITEN HD" SCREW ANCHORS WITH A
MINIMUM OF 3 1/4" EMBED U.O.N.
SHEARWALL SCHEDULE
MARK SHEATHING # OF SIDES PERIMETER NAILING SOLE PLATE FASTENING
SW1 7/16" RATED 1 #10 SCREWS @ 6" O.C. 1/2" DIA. ANCHOR BOLTS @ 2'-0" O.C.
COLUMN SCHEDULE
MARK COLUMN TYPE COMMENTS
C1 5 1/8" X 6" GLULAM S.D. 6/S401
C2 HSS6x6x1/4" S.D. 7/S401
0 4' 8'2'
Revisions: Date:
OF 266164164 OF 266164
T.O. PIER
EL. = 108'-8"
SLAB ON GRADE
EL. = SEE PLAN
T.O. PIER INSIDE
EL. = SEE ARCH
T.O. PIER OUTSIDE
EL. = SEE ARCH
3" CLR. - TYP.
SIZE & REINF.
SEE PLAN FOR
NOTE:
EXTEND ALL REINFORCING THRU CORNER - LAP & TIE.
NOTE:
IF WALL SURFACE IS SOIL LOADED EXTEND HORIZONTAL BARS TO OPPOSITE FACE & PROVIDE STANDARD HOOK.
SIZE & REINF.
SEE PLAN FOR
3 - 4 VERT. W/ DWL. TO
MATCH @ FOOTING.
CORNER BARS TO
MATCH SIZE &
SPACING OF HORIZ.
WALL REINF.
S E
E S
C H
E D
LA
P
S P
LI
C
E
1 1/2" CLR. - TYP.
SIZE & REINF.
SEE PLAN FOR
CORNER BARS
TO MATCH SIZE
& SPACING OF
HORIZ. WALL
REINF.
S E
E S
C H
E D
LA
P
S P
LI
C
E
1 1/2" CLR. - U.O.N.
SIZE & REINF.
SEE PLAN FOR
VERT. W/ DWL. TO
MATCH @ FOOTING.
CORNER BARS TO
MATCH SIZE &
SPACING OF HORIZ.
WALL REINF.
S E
E S
C H
E D
LA
P
S P
LI
C
E
1 1/2" CLR. - U.O.N.
NOTE:
CONST. JOINT SHOWN MAY BE OMITTED @ CONTRACTOR'S OPTION.
SIZE & REINF.
SEE PLAN FOR
2" x 4" x 6" LONG.
VERT. KEYWAY
EVENLY SPACED
BETWEEN HORIZ.
REINF. SPACING
DWL. W/ STANDARD
HOOK TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING2" CLR. - TYP.
S E
E S
C H
E D
LA
P
S P
LI
C
E
2" x 6" x 6" LONG.
VERT. KEYWAY
EVENLY SPACED
BETWEEN HORIZ.
REINF. SPACING
DWL. W/ STANDARD
HOOK TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING
SIZE & REINF.
SEE PLAN FOR
2" CLR. - TYP.
S E
E S
C H
E D
LA
P
S P
LI
C
E
NOTE:
JOINT MAXIMUM SPACING 40'-0". SPACING MAY BE INCREASED TO 80'-0"
IF WALL IS BACKFILLED INTERIOR SIDE FOR FULL HEIGHT OR 120'-0" IF
WALL IS BACKFILLED ON BOTH SIDES FOR FULL HEIGHT.
1"
1/2"
S
IZ
E
R E
IN
F
S E
E P
LA
N
F O
R
1 1/2"
6" 6"
SEE SCHED.
LAP SPLICE3" CLR.VERT. CAULK JOIST @
EACH FACE
2" x 6" x 6" LONG. VERT. KEYWAY (2" x 4" x 6" @ 8" WALL) EVENLY
SPACED BETWEEN HORIZ. REINF.
SPACING. KEYWAY CONT. WHERE
WATERSTOP IS REQUIRED
VERT. CAULK
VERT. ROD STOCK
WATERSTOP
WHERE
REQUIRED
6" 6"
SLAB ON GRADE
SEE PLAN "A"
3/16" SAW CUT OR TOOL JOINT
IN EXPOSED SLAB. FILL WITH
POURABLE SEALANT
4"
3/4" DIA. X 1'- 1" SMOOTH DOWEL
@ 1'-0" O.C. GREASE ONE END.
NOTE:
DIM. "A" = 1" FOR 4" SLABS, 1 1/4" FOR 5" SLABS, & 1 1/2" FOR 6" SLABS
NOTE:
SAW CUT SHALL BE EXECUTED AS SOON AS CONCRETE HAS HARDENED
SUFFICIENTLY TO PREVENT AGGREGATE DISLODGING BY SAW & PRIOR
TO SHRINKAGE STRESS CRACKING.
SLAB ON GRADE
SEE PLAN
1/4 SLAB DEPTH
3/16" SAW CUT OR TOOL
JOINT IN EXPOSED SLAB
OPENING
2 - 5 DWL. @ EACH LAYER OF
REINFORCING, TYP. @
PERIMETER
2 - 5 DWL. x 3'-0" @ EACH
LAYER OF REINFORCING,
TYP. @ CORNERS
1 1/2" CLR.
TYP.
1'
T Y
P
3" O.C.
TYP.
3" CLR.
TYP.
DWL. TO MATCH @
EACH VERT.
4 @ 1'-0" O.C. EACH
WAY
8" 4 DWL. 9" x 15" @
2'-0" O.C. TYP.
S.D. NOTES
CONC. SLAB OVER 1 1/2", TYPE "C", 20 GA.
(GALV.) DECK W/ 3" BRG. @ EACH END,
OVER 3" VOID. REINF. W/ 4 @ 1'-0" O.C.
EACH WAY. SLOPE SLAB 1/4"/FOOT
SEE PLAN
EQEQ
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV. TYP.
SEE PLAN FOR
WALL SIZE &
REINFORCING
BOND BREAK
SLAB ON GRADE
SEE PLAN
WALL BEYOND
SEE PLAN
5 1/2"
NOTES:
1. WHERE SLAB ON GRADE EXTENDS BEYOND STOOP SLAB HOLD STOOP SLAB
BACK 2" AND PROVIDE 3/4" DIA. x 1'-6" SMOOTH ROD @ 1'-0" O.C. PROVIDE
SLEEVE FOR ROD OR WRAP & TAPE WITH BUILDING FELT.
2. PROVIDE L4x4x1/4" W/ 1/2" DIA. SCREW ANCHORS @ 1'-0" O.C. (2 - ANCHORS
MIN.), EMBED 3 1/2" MIN. WHERE DECK IS UNSUPPROTED FOR MORE THAN 1'-0".
S.D. NOTE 2
METAL STUD
WALL SEE PLAN
SEE PLAN FOR
WALL SIZE &
REINFORCING
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
SLAB ON GRADE SEE
PLAN
INTERIOR FTG. - S.D. 11/1001-S301
#5 HORIZONTAL @ 1'-4" O.C.
2 - 5 VERT., DRILL & EPOXY
INTO FOOTING, 6" MINIMUM
EMBED
8" MIN. x FTG. WIDTH
1'
8"
NOTE:
CONTRACTORS OPTION: CONCRETE PIER MAY BE REPLACED
WITH C.M.U. W/ 5 DWL. @ EACH CORE, 6" MIN. EMBED INTO
FOOTING.
5 DWL. @ EACH VERT.
SEE ARCH.
BOND BREAK
CONT. TRACK W/ 1/2" DIA.
SIMPSON "TITEN-HD" SCREW
ANCHORS @ 2'-0" O.C.,
EMBED = 3 1/4" MINIMUM
SLAB ON GRADE SEE
PLAN
5 @ 1'-4" O.C.
EACH WAY,
EACH FACE
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
DWL. TO MATCH @
EACH VERT.
SEE ARCH.
METAL STUD WALL
SEE PLAN
5 1/2" VER.
8 1/2" VER.
1' - 4"
TYP.
1 1/2" CLR.
3" CLR. - TYP.
SLAB ON GRADE SEE
PLAN
1'-0" 1'-0"
CONT. TRACK W/ 1/2" DIA.
SIMPSON "TITEN-HD" SCREW
ANCHORS @ 2'-0" O.C., EMBED =
3 1/4" MINIMUM
METAL STUD WALL
SEE PLAN
BENT DWL. SEE
PLAN 3" CLR. - TYP.
8"
SEE PLAN FOR FOOTING SIZE,
REINF. & ELEV.
ANCHOR POST
SEE SCHEDULE
HOLDOWN SEE
PLAN AND
SCHEDULE
HOLD ANCHOR
SEE PLAN AND
SCHEDULE
CONT. TRACK
BOND BREAK
SLAB ON GRADE SEE
PLAN
SEE ARCH.
"E" - EMBED DEPTH
SEE PLAN AND SCHEDULESEE PLAN FOR
WALL SIZE &
REINF.
3/8" DIA.
ANCHOR BOLTS
HEAVY
HEX NUT
B.O. BASEPLATE
GRID
GRID
MARK BP1
PL. 3/4" x 10" x 10" W/
4 - 3/8" DIA. ANCHOR
BOLTS
3 1/2"3 1/2"
1/
2"
1/ 2"
1'
0"1 1/2" TYP.
3/16
1 1/2" NS. GROUT
STEEL COLUMN SEE
PLAN
BASE PLATE & ANCHOR
BOLT S.D. 13/1001-S301
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
DWL. TO MATCH @
EACH VERT. TYP.
MARK P1
4 - #6 VERTS. @
INSIDE W/ #3 TIES @
1'-0" O.C. U.O.N.
GRID
GRID
GRID
8" 8"
8" 8"
3" CLR. - TYP.
3 - #3 TIES
@ 3" O.C. 1'
4"
1' - 4"
BOND BREAK
1 1/2" CLR.
4 - #6 VERTS. @
OUTSIDE W/ #3 TIES
@ 1'-0" O.C. U.O.N.
3 - #3 TIES
@ 3" O.C. U.O.N.
SEE ARCH
2' - 0"
1' - 0" 1' - 0"
1'
0" 1'
0"
2'
0"
1 1/2" CLR. TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
17101
100% CONSTRUCTION
DOCUMENTS
C U s e rs \J
B u e rm a n n
\D o c u m e n ts
\1
P
IC
a m p A d m in is tr a ti o n
R V
T jb u e rm a n n S
R X
R
.r v t
/1 /2
:4
:0
P M
PIC ADMIN. BLDG - FOOTING &
FOUNDATION DETAILS
OCTOBER 30, 2024 EW DW/JB
1001-S301
MARION NATIONAL CEMETERY
NEW LAND EXPANSION
817CM3025
1700 E. 38TH ST. MARION IN 46953
1/2" = 1'-0"S301
1 FOOTING CORNER REINF. DETAIL
1/2" = 1'-0"S301
2 WALL CORNER REINF. DETAIL
1/2" = 1'-0"S301
3 WALL INTERSECTION DETAIL
1/2" = 1'-0"S301
4 WALL CONSTRUCTION JOINT DETAIL
1/2" = 1'-0"S301
5 FLOOR CONSTRUCTION JOINT DETAIL
1/2" = 1'-0"S301
6 FLOOR CONTROL JOINT DETAIL
1/2" = 1'-0"S301
7 ADDT. REINF. @ OPENING
1/2" = 1'-0"S301
8 STOOP DETAIL
1/2" = 1'-0"S301
9 INT. FTG. CONN. DETAIL
1/2" = 1'-0"S301
10 FOUNDATION WALL DETAIL
1/2" = 1'-0"S301
11 INTERIOR FOOTING DETAIL
1/2" = 1'-0"S301
12 TYPICAL HOLDOWN DETAIL
1/2" = 1'-0"S301
13 BASE PLATE/ANCHOR BOLT DETAIL
1/2" = 1'-0"S301
14 EXTERIOR PIER DETAIL
Revisions: Date:
OF 266165165 OF 266165
T.O. PIER
EL. = 108'-8"
T.O. STEEL
EL. = 111'-4"
T.O. STEEL
EL. = SEE ARCH
METAL STUD WALL
SEE PLAN
CONT. L6x4x5/16 (LLH) ATTACH TO TOP
TRACK W/ 2-ROWS OF #12 TEK SCREWS
@ 1'-0" O.C., ROWS STAGGERED
SIMPSON "H2.5" TIE
@ EACH TRUSS
EXTERIOR SHEATHING
RUN CONT. TO ROOF
SEE PLAN
SEE ARCH.
ROOF SHEATHING SEE
PLAN
LIGHT GAUGE BLOCKING
BETWEEN EA. ROOF
TRUSS BY SUPPLIER
METAL ROOF TRUSS
SEE PLAN
CONT. TOP TRACK
CONT. TRACK
SEE NOTE 1
SEE ARCH.
NOTE:
1. CONT. TRACK SHALL BE DESIGNED TO TAKE A NON-FACTORED
WIND LOAD TENSILE FORCE = 3500#. METAL STUD WALL
SEE PLAN
CONT. L6x4x5/16 (LLH) ATTACH TO TOP
TRACK W/ 2-ROWS OF #12 TEK SCREWS
@ 1'-0" O.C., ROWS STAGGERED
1-SIMPSON "H2.5" TIE
@ EACH TRUSS
EXTERIOR SHEATHING
RUN CONT. TO ROOF
SEE PLAN
ROOF SHEATHING SEE
PLAN
ROOF TRUSS SEE
PLAN
METAL STUD BLOCKING BTWN.
EA. JOIST, ATTACH TO TRUSS
W/ #12 TEK SCREWS @ 6" O.C.
16 GA. ROOF JOIST (MIN.) @
2'-0" O.C. BY TRUSS SUPPLIER
CONT. TOP TRACK
CONT. TRACK
SEE ARCH.
ANGLE CLIPS @ EA. JOIST
BY TRUSS SUPPLIER
CONT. C8X11.5 W/ 2-ROWS OF
#12 TEK SCREWS @ 6" O.C.
SEE ARCH.
UPLIFT CONNECTOR BY
SUPPLIER - TYP.
SEE ARCH.
ROOF SHEATHING SEE
PLAN
ROOF TRUSS
SEE PLAN
CONT. TOP TRACK
1/2"
ROOF TRUSS
SEE PLAN
METAL STUD WALL
SEE PLAN
WOOD ROOF DECK
SEE PLAN
CONT. WOOD WEDGE
TO MATCH GLU-LAM
GRADE & FINISH
GLU-LAM BEAM
SEE PLAN
BOUNDARY MEMBER
FASTENING PATTERN
SEE PLAN
CONT. 2x4 RIBBON
SEE ARCH
SEE ARCH
0.148" DIA. x 3" NAILS
@ 6" O.C. ROWS
STAGGERED
WOOD ROOF DECK
SEE PLAN
CONT. WOOD WEDGE
TO MATCH GLU-LAM
GRADE & FINISH
GLU-LAM BEAM
SEE PLAN
BOUNDARY MEMBER
FASTENING PATTERN
SEE PLAN
SEE ARCH
SIMPSON "CCQ" COLUMN CAP
GLU-LAM BEAM
SEE PLAN
GLU-LAM COL.
SEE PLAN
GLU-LAM BEAM
SEE PLAN
SIMPSON "CCQ" COLUMN CAP
1 1/2" NS. GROUT
STEEL COLUMN SEE
PLAN
BASE PLATE & ANCHOR
BOLT S.D. 13/1001-S301
4" 4"
PIER - SEE PLAN
SECTION "A"
1 1/2"
2 1/2"
1 1/2"1 1/2"
2 1/2"
1 1/2"
1 1/2"1 1/2" 2"
SEE ARCH
CAP PLATE 3/8"
SIDE PLATES
1/4" x 8" x 11"
GLU-LAM BEAM
SEE PLAN
GLU-LAM BEAM BEYOND
SEE PLAN
16 - 1/4" DIA. WOOD
SCREWS PRE-DRILLED
1/4
1/4
B S401
SIDE PLATES
1/4" x 8" x 8"
2" 1 1/2"1 1/2"
1 1/2"1 1/2"
2"
CAP PLATE 3/8"
SIDE PLATES
SEE A/S401
GLU-LAM BEAM
SEE PLAN16 - 1/4" DIA. WOOD
SCREWS PRE-DRILLED
1/4
SECTION "B"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
TECHNOLOGY:
IMEG
11044 RESERCH BLVD A-230
AUSTIN, TX 78759
309.786.5092
JAYSON STICKROD, PE
IRRIGATION:
EC DESIGN GROUP, LTD
400 5TH STREET
WEST DES MOINES, IA 50265
515.225.6365
GEOTECHNICAL:
TERRACON
7770 WEST NEW YORK ST.
INDIANAPOLIS, IN 46214
317.746.7925
RICHARD D. OLSON, PE
COST ESTIMATING:
CPMI
1001 GRAND AVE, SUITE 201
WEST DES MOINES, IA 50265
515.244.1166
BRYAN BERTRANDERIK CHRISTIANSEN, ASIC
BUILDING 1001
17101
100% CONSTRUCTION
DOCUMENTS
C U s e rs \J
B u e rm a n n
\D o c u m e n ts
\1
P
IC
a m p A d m in is tr a ti o n
R V
T jb u e rm a n n S
R X
R
.r v t
/1 /2
:4
:0
P M
PIC ADMIN. BLDG - FRAMING
DETAILS
OCTOBER 30, 2024 EW DW/JB
1001-S401
MARION NATIONAL CEMETERY
NEW LAND EXPANSION
817CM3025
1700 E. 38TH ST. MARION IN 46953
1" = 1'-0"S401
1 ROOF TRUSS BRG. DETAIL
1" = 1'-0"S401
2 ROOF END WALL DETAIL
1" = 1'-0"S401
3 ROOF TRUSS BRG. DETAIL
1" = 1'-0"S401
4 WOOD BEAM CONN. DETAIL
1" = 1'-0"S401
5 WOOD BEAM CONN. DETAIL
1" = 1'-0"S401
6 GLU-LAM COL. CONN.
1" = 1'-0"S401
7 COL. CONN. DETAIL
Revisions: Date:
OF 266166166 OF 266166
APPROVED BY THE STATE OF INDIANA / CITY OF MARION.
2. REFERENCE STANDARDS: UNLESS OTHERWISE NOTED (U.O.N.), ALL
STANDARDS SHALL BE CURRENT EDITION, WITH LATEST ADDENDA, IF
APPLICABLE.
3. THE CONTRACTOR SHALL VERIFY ALL CONTRACT DOCUMENTS, SITE
ELEVATIONS, DIMENSIONS AND CONDITIONS PRIOR TO STARTING WORK AND
SHALL NOTIFY THE ARCHITECT/ ENGINEER OF ANY DISCREPANCIES OR
INCONSISTENCIES.
4. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES.
5. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT
THE FINISHED STRUCTURE. UNLESS OTHERWISE INDICATED, THEY DO NOT
INDICATE THE MEANS OR METHOD OF CONSTRUCTION. TEMPORARY BRACING
AND SHORING AGAINST WIND AND ERECTION CONDITIONS DURING
CONSTRUCTION OF THE BUILDING, SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE
PROTECTION OF THE STRUCTURE DURING ALL PHASES OF DEMOLITION,
CONSTRUCTION, AND INSTALLATION.
6. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
7. VERIFY LOCATION OF BOX OUTS AND OPENINGS WITH MECHANICAL
CONTRACTORS. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES, DUCTS
ETC. ARE FOR GENERAL INFORMATION ONLY AND SHALL BE VERIFIED WITH THE
MECHANICAL CONTRACTOR BEFORE COMMENCING THE WORK.
8. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS
DO NOT COINCIDE WITH EQUIPMENT SHOWN ON PLANS, COORDINATE
ADJUSTMENTS WITH THE STRUCTURAL ENGINEER.
9. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
APPROVED BY THE STRUCTURAL ENGINEER BEFORE PLACEMENT THROUGH
STRUCTURAL MEMBERS.
10. CONTRACTOR SHALL PROVIDE A CAST-IN SLEEVE FOR ALL HORIZONTAL
ELEMENTS THAT EXTEND THROUGH FOOTING. IE: DRAIN TILE, ELECTRICAL
CONDUIT, MECHANICAL PIPING, ETC. ALL SLEEVES SHALL BE COORDINATED
WITH ARCHITECT/ENGINEER.
11. SHOP DRAWINGS PREPARED BY SUPPLIERS, SUBCONTRACTORS, ETC., SHALL
BE DIMENSIONED, REVIEWED, COORDINATED, AND SIGNED/ STAMPED BY THE
GENERAL CONTRACTOR PRIOR TO SUBMITTING TO THE STRUCTURAL
ENGINEER.
12. FABRICATOR SHALL CLEARLY NOTE CHANGES MADE IN THE SHOP DRAWINGS
WHICH DO NOT COMPLY WITH THE CONTRACT DOCUMENTS. REVIEWED
APPROVAL SHOP DRAWINGS SHOWING ENGINEERS COMMENTS ACCOMPANIED
WITH RECORD SET SHOP SHOP DRAWINGS, SHALL BE AVAILABLE FOR
REFERENCE AT THE CONSTRUCTION SITE.
13. CONCRETE ANCHORS SHALL BE SIMPSON 'TITEN HD" SCREW ANCHORS OR
EQUIVALENT (U.O.N.). INSTALL ANCHORS USING THE MANUFACTURER'S
RECOMMENDATIONS.
14 LINTELS SHALL HAVE A BEARING OF 1" PER FOOT OF SPAN AT
EACH END, 8" MIN. LINTEL ANGLES WHICH HAVE NOT BEEN SHOWN
OTHERWISE, TO BE AS FOLLOWS FOR EACH 4" OF WALL
THICKNESS:
FOUNDATION NOTES:
1. FOOTING ELEVATIONS ARE TO TOP OF FOOTING (T.O. FTG.), UNLESS
OTHERWISE NOTED.
2. FOOTINGS ARE DESIGNED FOR A MINIMUM NET ALLOWABLE SOIL BEARING
PRESSURE OF 2500 psf FOR CONTINUOUS AND 2500 psf FOR PAD FOOTINGS.
FOUNDATION DESIGN COMPLIES W/ GEOTECHNICAL REPORT DATED: AUGUST 5,
2024 BY TERRACON.
3. FOOTINGS SHALL BEAR ON NATURAL UNDISTURBED SOIL OR ENGINEERED FILL.
SOILS SHALL BE OBSERVED AND APPROVED BY A GEOTECHNICAL ENGINEER
PRIOR TO PLACEMENT OF FOOTING CONCRETE. IF NATURAL UNDISTURBED
SOILS ARE NOT ENCOUNTERED AND/OR INADEQUATE SOILS ARE NOTED AT
FOOTING BEARING LEVEL, ARCHITECT/ENGINEER SHALL BE NOTIFIED PRIOR TO
PROCEEDING WITH FURTHER WORK AT THOSE FOOTING LOCATIONS.
4. PROTECT FOOTINGS FROM THE ACTION OF WATER OR FREEZING.
5. FOOTINGS ARE CENTERED UNDER WALLS ABOVE - UNLESS OTHERWISE
NOTED.
6. PRIOR TO PLACEMENT OF FOOTING CONCRETE, CLEAN FOOTING EXCAVATIONS
OF SNOW, WATER AND DEBRIS.
7. FOOTINGS MAY NOT BE EARTH FORMED.
EXCAVATION & BACKFILL NOTES:
1. EXCAVATION AND BACKFILL SHALL BE EXECUTED IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS.
2. BACKFILL, & COMPACTION SHALL BE INSPECTED AND CERTIFIED BY A LICENSED
GEOTECHNICAL ENGINEER. REPORTS ARE TO BE SUBMITTED TO THE
ARCHITECT/ ENGINEER.
3. FOOTING EXCAVATIONS SHALL BE EXCAVATED TO PROPER LINE AND LEVEL TO
ENSURE MINIMUM CONCRETE COVER OF FOOTING REINFORCEMENT FOR
FOOTING DEPTH.
4. BACKFILL SHALL BE COMPACTED BY MECHANICAL MEANS. FLOODING OR
WATER INUNDATION SHALL NOT BE PERMITTED.
5. BACKFILL SHALL BE PLACED IN ALTERNATING LIFTS ON EACH SIDE OF THE
FOUNDATION WALLS TO MAINTAIN STABILITY OF THE FOUNDATION WALLS.
6. BACKFILL SHALL NOT BE PLACED AGAINST BASEMENT FOUNDATION WALLS
UNLESS WALLS ARE ADEQUATELY BRACED TOP AND BOTTOM. FINAL WALL
BRACING IS BASEMENT SLAB OR ENGINEERED BACKFILL AND 1ST FLOOR
STRUCTURE. IF THESE ELEMENTS ARE NOT IN PLACE AT TIME OF BACKFILL,
CONTRACTOR SHALL PROVIDE AN ENGINEERED, TEMPORARY BRACING
SYSTEM. THE TEMPORARY BRACING SYSTEM PROPOSED SHALL BE SUBMITTED
TO THE ARCHITECT/ ENGINEER FOR REVIEW PRIOR TO BACKFILLING.
MASONRY NOTES:
1. CONCRETE BLOCK MASONRY UNITS SHALL CONFORM TO GRADE
'N', MOISTURE CONTROLLED TYPE I REQUIREMENTS OF ASTM C90,
WITH AN ASSUMED COMPRESSIVE STRENGTH F'm - 2500 psi.
MORTAR SHALL CONFORM TO ASTM C270 AND SHALL BE TYPE 'M'
OR TYPE 'S', WITH TYPE 'M' BELOW GRADE.
2. BOND BEAMS SHALL HAVE TWO CONTINUOUS #5 REINFORCING
BARS. WHERE SHOWN ON PLAN OR IN A DETAIL, PROVIDE A BOND
BEAM AT THE TOP OF WALLS AND SPACED NOT MORE THAN 10' - 0"
ON CENTER VERTICALLY.
3. WIRE REINFORCING FOR CMU WALLS SHALL BE CORROSION
RESISTANT 9 GA. HORIZONTAL JOINT REINFORCING CONFORMING
TO ASTM A951. WHERE BOND BEAMS ARE REQUIRED TO BE
SPACED MORE THAN 10' - 0" ON CENTER WIRE REINFORCING SHALL
BE INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS
WITH MAXIMUM SPACING OF 16" O.C. (U.O.N.).
4. CONCRETE GROUT FOR UNIT MASONRY CORES AND BOND BEAMS
SHALL HAVE A 28 DAY COMPRESSIVE STRENGTH OF 3000 psi.
5. MASONRY WALLS ARE TO BE SUPPORTED LATERALLY UNTIL THE
ENTIRE ROOF AND/OR FLOOR IS IN PLACE AS DETAILED.
6. MASONRY REINFORCING SHALL BE LAPPED AS FOLLOWS: #3 BAR
= 18", #6 BAR = 36", #4 BAR = 24", #7 BAR = 42", #5 BAR = 30", #8
BAR = 48".
7. VERTICAL REINFORCING BARS SHALL BE HELD IN POSITION AT TOP
AND BOTTOM AND AT 192 (REINF.) DIAMETER INTERVALS MAXIMUM.
LENGTH OF REINFORCING BARS TO BE COORDINATED WITH
GENERAL CONTRACTOR AND MASONRY CONTRACTOR.
8. WHERE CELLS ARE TO BE FILLED W/ CONCRETE GROUT, PROVIDE
ADDITIONAL FULL MORTAR BED AT CROSS WEBS ENCLOSING
GROUTED CELL.
9. CONSOLIDATE ALL CONCRETE GROUT BY PUDDLING OR
VIBRATING.
10. BLOCK COURSING SHOWN ON STRUCTURAL PLANS MAY NOT BE
REPRESENTATIVE OF ACTUAL COURSING. SEE ARCHITECTURAL
PLANS AND SECTIONS FOR ACTUAL LAYOUT OF BLOCK COURSING.
11. MASONRY PIERS SHALL BE LAID UP SIMULTANEOUSLY WITH WALLS
AND SHALL BE INTERLOCKED WITH WALL BLOCKS.
12. FIRST COURSE OF ALL HOLLOW MASONRY SHALL BE PLACED ON A
FULL BED OF MORTAR.
13. CAST DOWELS, WITH STANDARD HOOKS, IN FOOTINGS FOR PIERS
AND WALLS ABOVE. DOWELS SHALL BE THE SAME SIZE AND
SPACING OF VERTICAL REINFORCING. (U.O.N.)
CONCRETE NOTES:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE
INSTITUTE (ACI) CODES AND SPECIFICATIONS, LATEST EDITION. ACI 301
"SPECIFICATIONS FOR STRUCTURAL CONCRETE" ACI 315 "DETAILS &
DETAILING OF CONCRETE REINFORCEMENT" ACI 318 "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE".
2. CONCRETE MIX DESIGN SHALL BE BY AN INDEPENDENT TESTING
LABORATORY.
3. CAST-IN-PLACE CONCRETE SHALL BE SUBJECT TO TESTING BY AN
INDEPENDENT TESTING LABORATORY. SEE PROJECT SPECIFICATIONS FOR
REQUIREMENTS.
4. NON WELDED REINFORCING STEEL SHALL BE GRADE 60 DEFORMED,
BILLET-STEEL, ASTM A615, U.O.N. ALL WELDED WIRE FABRIC (WWF) SHALL BE
PLAIN, ASTM A185.
5. WELDED REINFORCING STEEL SHALL BE GRADE 60, LOW CARBON, ASTM A706.
6. PROVIDE EXTRA REINFORCEMENT AROUND ALL OPENINGS GREATER THAN
12" SQUARE OR 12" IN DIAMETER, INCLUDING DOOR OPENINGS, IN CONCRETE
WALLS & SLABS. PROVIDE 2 - #5 BARS @ 3" O.C., ON EACH SIDE OF THE
OPENING EXTENDING 24" BEYOND THE CORNER OF THE OPENING & 2 - #5
BARS AT 3" O.C. BY 3'-0" LONG DIAGONAL BARS AT EACH CORNER. PLACE
DIAGONAL BARS CENTERED ON CORNER @ 2" CLEAR OF…
This is the start of the file's text. The full file is on GovTribe.