This file summary describes a federal contract solicitation for renovation services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is soliciting proposals under solicitation number 36C25523R0115 to renovate Building 4E for a Primary Care Unit at an estimated price of $5-10 million. Responses are due by October 11, 2023 and the contract is expected to be awarded by November 15, 2023. The scope of work involves renovating approximately 15,000 square feet of space to accommodate new primary care exam rooms, offices, waiting areas, and support spaces. Interested contractors should review the attached 35 page drawings file for detailed renovation plans and specifications.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION SYMBOL LIST
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
FIRE PROTECTION - DRY SYSTEMFPD
SERVICE WATER - POTABLEW
AIR PRESSURE MAINTENANCE DEVICE
AIR SUPERVISORY SWITCH
ANGLE VALVE
BUTTERFLY VALVE WITH MONITOR SWITCH
OS&Y GATE VALVE
OS&Y GATE VALVE WITH MONITOR SWITCH
PRESSURE SWITCH
P
NO HATCH LIGHT HAZARD
ORDINARY GROUP 1
ORDINARY GROUP 2
EXTRA GROUP 1
EXTRA GROUP 2
SPRINKLER - QUICK RESPONSE
SPRINKLER - CONCEALED QUICK RESPONSE
INSPECTOR TEST AND DRAIN VALVE
MONITOR SWITCH
COMPRESSED AIR - FIRE PROTECTIONCAF
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
SHUTOFF VALVE NORMALLY OPEN
DEMOLITION
DRAINDFP
NOT ALL SYMBOLS MAY APPLY.
AUTOMATIC DRAIN VALVE
UNION/FLANGE
DIRECTION OF FLOW IN PIPE
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
CHECK VALVE
FLOW SWITCH
F
ROUTE TO DRAIN
AREA BOUNDARY
BACKFLOW PREVENTER
NOT IN SCOPE
FIRE PROTECTION ABBREVIATION KEY
AD ACCESS DOOR
BFP BACKFLOW PREVENTER
N.C. NORMALLY CLOSED
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTESUON
I.E. INVERT ELEVATION
SHORT CIRCUIT CURRENT RATINGSCCR
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
NURSE CALL CONTRACTORN.C.C.
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE
CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS
REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID
TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND
IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL
TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE
BASIS OF DESIGN.
3. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS
WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.
SPRINKLER HEADS SHALL BE ALIGNED WITH OTHER SPRINKLER HEADS, LIGHTING,
DIFFUSERS, AND ANY OTHER FEATURES IN THE CEILING.
4. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK
RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.
5. PROVIDE COVERAGE ABOVE AND BELOW ALL DUCTWORK GREATER THAN 48" WIDE.
6. PROVIDE COVERAGE ABOVE (IF APPLICABLE) AND BELOW FLOATING CEILINGS, REFER
TO ARCHITECTURAL PLANS.
7. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT
NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.
8. THE FIRE PROTECTION SYSTEM SHALL BE DESIGNED TO MEET OWNER'S INSURANCE
COMPANY STANDARDS WHERE APPLICABLE. THE MORE STRINGENT OF THE OWNER'S
INSURANCE UNDERWRITER'S DESIGN CRITERIA AND THE NFPA STANDARDS SHALL BE
USED.
9. ALL BUILDING AREA SHALL BE FULLY SPRINKLERED INCLUDING CANOPIES, WALKWAYS,
OVERHANGS, SOFFITS, AND BUILDING PROJECTIONS. ALL ACCESSIBLE COMBUSTIBLE
CONCEALED SPACES SHALL BE FULLY PROTECTED BY THE SPRINKLER SYSTEM.
10. EACH ASSEMBLY SHALL INCLUDE BUTTERFLY CONTROL VALVE INDICATING "OPEN" OR
"CLOSED" POSITION, TEST INSPECTION VALVE, FLOW SWITCH AND PRESSURE GAUGES.
11. PROVIDE RISER ROOM IDENTIFICATION SIGNAGE OUTSIDE THE FIRE RISER ROOM.
COORDINATE EXACT SIGN LANGUAGE WITH AHJ.
12. WHERE FEASIBLE INSTALL PIPES HIGH AS POSSIBLE TO AVOID CONFLICT WITH OTHER
DISCIPLINES,
13. INSTALL SYSTEM DRAINS AT LOW POCKET AREAS CONTAINING FIVE GALLONS OF
WATER OR MORE, PROVIDE WITH ISOLATION VALVE AND THREADED HOSE
CONNECTION.
14. MAIN PIPING PASSING BELOW SKYLIGHTS OR CLERESTORIES ARE NOT PERMITTED.
15. FOLLOW STRUCTURAL DETAILS WHEN PENETRATING OR PASSING THROUGH
STRUCTURAL ELEMENTS. ALTERNATE DESIGNS WILL NEED TO BE APPROVED THROUGH
THE STRUCTURAL ENGINEER.
16. PROVIDE INTERMEDIATE TEMPERATURE SPRINKLER HEADS WHERE REQUIRED BY NFPA
13 UNLESS OTHERWISE NOTED.
17. FINAL HEAD LOCATION, TYPE AND FINISH SHALL BE REVIEWED AND APPROVED BY THE
ARCHITECT.
18. A GRAPHIC ANNUNCIATOR PANEL SHALL BE PROVIDED TO INCLUDE AREAS BEING
PROVIDED WITH A PRE-ACTION OR CLEAN AGENT SYSTEM WHICH HAVE CONCEALED
AREAS.
19. EXACT LOCATION OF THE ALL PANELS SHALL BE VERIFIED ON SITE AND COORDINATED
WITH THE ELECTRICAL CONTRACTOR.
20. PAINT ALL EXPOSED PIPING TO MATCH BACKGROUND OR AS DIRECTED BY THE
ARCHITECT.
21. THE OWNER MUST BE NOTIFIED PRIOR TO EACH AND EVERY DRAINING OR RECHARGING
OF THE SPRINKLER SYSTEM.
22. THE CONTRACTOR SHALL PREPARE A COORDINATED SET OF SHOP DRAWINGS AND
SHALL OBTAIN APPROVAL FROM THE AUTHORITIES HAVING JURISDICTION AND THE
LOCAL FIRE DEPARTMENT PRIOR TO ANY INSTALLATION.
23. DRAWINGS SHOW LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT,
ETC. AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
24. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW
ALL DRAWINGS. INCLUDING THOSE OF OTHER TRADES.
25. SPRINKLER LOCATIONS ARE DIAGRAMATIC AND DO NOT PRESCRIBE EXACT NUMBER
AND LOCATION OF SPRINKLER HEADS. CONTRACTOR SHALL DESIGN THE SYSTEM TO
SPRINKLER AREA PER NFPA 13 REQUIREMENTS
FIRE PROTECTION GENERAL NOTES:
FIRE PROTECTION SHEET INDEX
F000 FIRE PROTECTION COVERSHEET
F204 FOURTH FLOOR FIRE PROTECTION PLAN
GRAND TOTAL: 2
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:1
P
M
F000
FIRE PROTECTION COVERSHEET Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
NOTES:
1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS.
2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT.
3. ALL SPRINKLERS SHALL BE UL ----AND FM---- LISTED.
4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13
REQUIREMENTS.
5. TAG NAME IS PRIMARILY FOR IDENTIFIYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS.
CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED.
6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES.
7. NON-FERROUS SPRINKLER FOR USE IN MAGNETIC AND CORROSIVE ENVIROMENTS.
8. SPRINKLER FOR USE IN DUST-FREE ENVIRONMENTS.
9. SPRINKLER SHALL BE UL LISTED FOR 2-HR FIRE SEPARATION EQUIVALENCE.
10. SPRINKLERS SHALL HAVE A 3mm QUICK RESPONSE BULB.
11. SPRINKLERS SPECIFIED WITHIN FIRE SPRINKLER USAGE SCHEDULE ARE STANDARD COVERAGE TYPE. EXTENDED COVERAGE...
FIRE SPRINKLER USAGE SCHEDULE
AREA TYPE
(NOTE 1 & 6)
AREA
HAZARD
SPRINKLER
TEMPERATURE RATING MANUFACTURER & MODEL NOTES
TAG NAME
(NOTE 4 & 5)
SPRINKLER
TYPE
RESPONSE
CATEGORY FINISH
AREAS WITHOUT CEILINGS SEE PLANS SPR-1 PENDENT QUICK ROUGH
BRASS
PER NFPA VIKING VK, RELIABLE F1FR, TYCO TY-FRB, VICTAULIC
V2708
NOTE 3
AREAS WITH CEILINGS SEE PLANS SPR-4 CONCEALED QUICK WHITE PER NFPA VIKING VK, RELIABLE G4A, TYCO RFII, VICTAULIC V3802 NOTES 3
Revisions: Date:
4a
N1M1L2L1J2J
HGF
EDCBA2A
8a
6a
J1H1
EXISTING 6" FP
STANDPIPE UP
AND DOWN
F
EXTEND AND SPRINKLER
RENOVATED AREA
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:1
P
M
F204
FOURTH FLOOR FIRE PROTECTION
PLAN
Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
SHEET NOTES:
1. SEE SHEET FP000 FOR SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES.
N O R
HT
1/8" = 1'-0"
LEVEL 04 PLAN - FIRE PROTECTION CEILING PLAN
PLUMBING ABBREVIATION KEY
BATHTUBBT
CO CLEANOUT
CLINICAL SINKCS
DRINKING FOUNTAINDF
EMERGENCY EYEWASHEE
FLOOR CLEANOUTFCO
FLOOR DRAINFD
FLOOR SINKFS
GARBAGE DISPOSERGD
GREASE INTERCEPTORGI
HOSE BIBBHB
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYLAV
MOP BASINMB
MH MANHOLE
MIXING VALVEMV
NEUTRALIZATION TANKNT
OIL SEPARATOROS
ROOF DRAINRD
SHOWERSH
SINKSK
SERVICE SINKSS
TRENCH DRAINTD
TRAP PRIMERTP
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
WASH FOUNTAINWF
WATER HEATERWH
WASHING MACHINE FIXTUREWMF
YARD CLEANOUTYCO
EMERGENCY SHOWERES
EMERGENCY SHOWER/EYEWASHESE
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTESUON
EXISTINGE
FLOW METERFM
WATER SOFTENERWS
WATER METERWM
DIALYSIS BOXDB
CATCH BASINCB
CAST IRONCI
DUCTILE IRONDI
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
UTILITY BOXUB
SHORT CIRCUIT CURRENT RATINGSCCR
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE
(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-1
6"(1000)
ROOF DRAIN PROPERTIES SYMBOL
SIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
ALIGNMENT GUIDE
PIPE ANCHOR
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
COLD WATER - POTABLECW
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
SANITARY DRAINAGESAN
SOFT COLD WATERSCW
SOFT HOT WATERSHW
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTV
WASTE ANETHESIA GAS DISPOSALWAGD
COMPRESSED AIRCA
DRAIND
NOT ALL SYMBOLS MAY APPLY.
PRESSURE REDUCING VALVE (LIQUID/GAS)
LAB VACUUMVAC
SOLENOID VALVE
SAFETY/RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
PUMP
INSTRUMENT AIRIA
MEDICAL AIRMA
MEDICAL VACUUMMV
NITROGENN
NITROUS OXIDENO
OXYGENO
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE
AND HOSE CONNECTION WITH CAP
FLEXIBLE CONNECTION
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
EA MEDICAL EQUIPMENT AIR
VALVE BOX
MEDICAL GAS OUTLET (MGO)
ALARM PANEL
HEADWALL
SINGLE GAS OUTLET (AIR)A
SINGLE GAS OUTLET (OXYGEN)O
SINGLE GAS OUTLET (VACUUM)V
NITROGEN PRESSURE CONTROL CABINET
PRESSURE TRANSDUCER WITH ALARM WIRING
CO2 CARBON DIOXIDE
DRAIN - MEDICAL GASDMG
BACKFLOW PREVENTER
MEDIUM PRESSURE GASMPG
EXPANSION JOINT
#.#" IS THE EXPANSION TRAVEL INCHESEJ-#
AIR ADMITTANCE VALVE
TS
FT
TEMPERARURE SENSOR FOR LEGIONELLA MONITORING
TEMPERARURE SENSOR AND FLOW SENSOR FOR LEGIONELLA MONITORING
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO
THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN
THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE
BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL
APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
5. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY
ALL ELEVATIONS BEFORE BEGINNING WORK.
6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO
BEGINNING ANY WORK.
7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.
8. FOR CLARITY, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN
DOMESTIC WATER PIPING SERVING EACH ROOM WITH FIXTURES. ANGLE STOPS SHALL NOT
BE CONSIDERED SHUTOFF VALVES.
9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL
SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR
ADDITIONAL DEMOLITION INFORMATION.
10. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK
UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL
INFORMATION.
PLUMBING GENERAL NOTES:
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO
THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN
THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF
DESIGN.
3. INSTALL WALL MOUNTED OUTLETS 60" AFF UNLESS NOTED OTHERWISE. COORDINATE
ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
4. REFER TO MEDICAL GAS MATERIAL LIST FOR PIPE SIZES TO INDIVIDUAL OUTLETS.
MEDICAL GAS GENERAL NOTES:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS
PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS SHALL BE SEALED AIRTIGHT WITH
WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING; DUCTWORK, PIPING, ETC.
17. PROVIDE STRUCTURAL STEEL BASE FOR AIR HANDLING UNIT AS DETAILED ON
STRUCTURAL DRAWINGS.
18. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED. ALL SYTEM SHUTDOWNS ARE TO BE COORDINATED WITH
OWNER AT LEAST TWO WEEKS AHEAD OF PLANNED SHUTDOWN.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
12. THIS IS A 24 HOUR WORKING FACILITY THUS WORK MAY HAVE TO BE DONE OUTSIDE OF
REGULAR WORKING HOURS AT NO ADDITIONAL COST TO THE OWNER.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
PLUMBING SLOPE REQUIREMENTS:
INTERIOR:
SANITARY WASTE: ≤2-1/2”ø=1/4” PER FOOT ≥3”ø = 1/8” PER FOOT ≥8”ø = 1/16” PER FOOT
GREASE WASTE: 1/4” PER FOOT
STORM (GRAVITY): 1/8” PER FOOT
CONDENSATE AND INDIRECT DRAINAGE: 1/8” PER FOOT
SANITARY AND GREASE VENT: NO SPECIFIC PITCH, PITCH TO FIXTURES
DOMESTIC WATER: NO SPECIFIC PITCH, PITCH TO FIXTURES
BASED ON PLUMBING CODE: IPC-2018
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:1
P
M
P000
PLUMBING + MEDICAL GAS
COVERSHEET
Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
PLUMBING + MEDICAL GAS SHEET INDEX
P000 PLUMBING + MEDICAL GAS COVERSHEET
P103 THIRD FLOOR PLUMBING DEMOLITION PLAN
P104 FOURTH FLOOR PLUMBING DEMOLITION
P203 THIRD FLOOR PLUMBING PLAN
P204 FOURTH FLOOR PLUMBING PLAN
P300 PLUMBING RISER DIAGRAMS
P301 PLUMBING RISER DIAGRAMS
P600 PLUMBING & MED GAS MATERIALS LISTS
GRAND TOTAL: 8
NOTES: (APPLIES TO ALL PLUMBING FIXTURES LISTED BELOW)
1) SIZES SHOWN ARE MINIMUMS. LARGER SIZES SHOWN ON THE DRAWING SHALL DICTATE THE
ROUGH-IN SIZE. 2) SANITARY RISERS UP IN WALL TO FIXTURES SHALL BE A MINUMUM OF 2". 3) DOMESTIC WATER BRANCH PIPING OUTSIDE OF THE WALL/CHASE SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. ONLY THE FINAL RISE-DROP SHALL BE SMALLER. 4) FINAL SANITARY
SIZE SHALL MATCH P-TRAP SIZE (REFER TO MATERIAL LIST).
PLUMBING ROUGH-IN SCHEDULE
TAG NAME DESCRIPTION
COLD
WATER
HOT
WATER SANITARY VENT
FD-C FLOOR DRAIN 2" 1 1/2"
FD-H FLOOR SINK 3" 1 1/2"
P-102 WATER CLOSET 1 1/2" - 4" 2"
P-103 WATER CLOSET 1 1/2" - 4" 2"
P-104 WATER CLOSET (ACCESSIBLE) 1 1/2" - 4" 2"
P-413 LAVATORY (ACCESSIBLE) 1/2" 1/2" 1 1/2" 1 1/2"
P-418 LAVATORY (ACCESSIBLE) 1/2" 1/2" 1 1/2" 1 1/2"
P-420 LAVATORY 1/2" 1/2" 1 1/2" 1 1/2"
P-502 MOP BASIN 3/4" 3/4" 3" 1 1/2"
P-524 SINK 1/2" 1/2" 1 1/2" 1 1/2"
P-528 SINK 1/2" 1/2" 1 1/2" 1 1/2"
P-609 ELECTRIC WATER COOLER 1/2" - 1 1/2" 1 1/2"
P-701 SHOWER 1/2" 1/2" 2" 1 1/2"
P-812 UTILITY BOX (DRAIN) - - 2" 1 1/4"
P-6150 SINK 1/2" 1/2" 1 1/2" 1 1/2"
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06Revisions: Date:
7 7
8 8
4a
N1M1L2L1J2
J
J
H
H
G
G
F
F
EDCBA2A
8a
6a
J1H1
1 1
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:2
P
M
P103
THIRD FLOOR PLUMBING
DEMOLITION PLAN
Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
N O R
HT
1/8" = 1'-0"
LEVEL 03 DEMOLITION PLAN - PLUMBING
KEYED NOTES:
1. DEMO EXISTING PIPING SHOWN DARK AND DASHED
BACK TO RISER.
2. EXISTING PLUMBING RISER TO REMAIN.
3. DEMOLISH 4" SAN AND 4" V PLUMBING RISERS ABOVE
3RD FLOOR CEILNG AS REQUIRED TO OFFSET RISERS.
SEE NEW PLANS FOR ROUTING.
SHEET NOTES:
1. SEE SHEET P000 FOR SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES.
2. PLUMBING FIXTURES AND ARCHITECTURAL FLOOR PLAN
ON THIS SHEET ARE FOR THE FOURTH FLOOR AND ARE
FOR REFERENCE.
8 8
4a
N1M1L2L1J2
J
J
H
H
G
G
F
F
EDCBA2A
8a
6a
J1H1
1 1
1 1
3 3
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:2
P
M
P104
FOURTH FLOOR PLUMBING
DEMOLITION
Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
N O R
HT
1/8" = 1'-0"
LEVEL 04 DEMOLITION PLAN - PLUMBING
KEYED NOTES:
1. DISCONNECT AND REMOVE EXISTING PLUMBING
FIXTURE. DEMO ANY ASSOCIATED HOT AND COLD
WATER, SANITARY AND VENT PIPING, BACK TO MAINS
WHETHER SHOWN ON PLAN OR NOT ALONG WITH ALL
ASSOCIATED HANGERS AND ACCESSORIES. CAP PIPING
AT MAINS.
2. EXISTING PLUMBING RISER TO REMAIN.
3. DEMO EXISTING PIPING SHOWN DARK AND DASHED
BACK TO RISER.
4. DEMOLISH 4" SAN AND 4" V PLUMBING RISERS AS
REQUIRED TO OFFSET RISERS. SEE NEW PLANS FOR
ROUTING.
5. DEMOLISH EXISTING VALVE BOX AND ASSOCIATED
ACCESSORIES.
SHEET NOTES:
1. SEE SHEET P000 FOR SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES.
8 8
4a
N1M1L2L1J2
J
J
H
H
G
G
F
F
EDCBA2A
8a
6a
J1H1
NURSE MNG. OFFICE
M4-357
PATIENT TOILET/SHOWER
M4-355A
OFFICE DOCUMENTATION
M4-360
STAFF TOILET
M4-358
PATIENT TOILET/SHOWER
M4-356A
ISO PATIENT BEDROOM
M4-356
ANTE ROOM
M4-354
ISO PATIENT BEDROOM
M4-352
ISO PATIENT BEDROOM
M4-355
ISO PATIENT BEDROOM
M4-351
ANTE ROOM
M4-353
PATIENT TOILET/SHOWER
M4-351A
SOILED UTILITY
M4-349
H.A.C.
M4-362
CORRIDOR
C4-34
STAIRWELL NO. 1
S1
ELEC. CLOSET
M4-347
ELEC. CLOSET
M4-345
STERILE SUPPLY ROOM
M4-350
NOURISHMENT STATION
M4-348
PATIENT TOILET/SHOWER
M4-352A
WORK AREA 1
WA-1
HAND WASH 1
HW-1
MSA STATION
M4-342
CLEAN UTILITY ROOM
M4-332
PATIENT BEDROOM
M4-337
PATIENT TOILET/SHOWER
M4-337A
PATIENT TOILET/SHOWER
M4-335A
PATIENT BEDROOM
M4-335
CORRIDOR
C4-32
MECHANICAL ROOM
M4-333
LINEN CHUTE
M4-311
ELEC. CLOSET
M4-331
CORRIDOR
C4-30
HALLWAY
M4-305
OIT DATA CLOSET
M4-305A
BIOMED NETWORK CLOSET
M4-303
MEDICATION ROOM
M4-306
SERVICE ELEVATOR
E16
SERVICE ELEVATOR
E17
ELEVATOR
E1
ELEVATOR
E2
ELEVATOR
E3
ELEVATOR
E4
WAITING ROOM
M4-302
LOBBY
M4-300
PATIENT TOILET/SHOWER
M4-319A
PATIENT BEDROOM
M4-319
PATIENT BEDROOM
M4-317
PATIENT TOILET/SHOWER
M4-317A
PATIENT BEDROOM
M4-315
PATIENT TOILET/SHOWER
M4-315A
CORRIDOR
C4-31
CORRIDOR
M4-330
RRC-1
RRC-1
WORK AREA 3
WA-3
EQUIPMENT STORAGE
M4-359
CRASH CART
CC-1
HAND WASH 3
HW-3
PATIENT BEDROOM
M4-320
PATIENT TOILET/SHOWER
M4-320A
PATIENT TOILET/SHOWER
M4-318A
PUBLIC TOILET
M4-302A
PUBLIC TOILET
M4-302B
MED GAS STORAGE
M4-343
PORTABLE X-RAY ALCOVE
C4-34B
PATIENT BEDROOM
M4-316
PATIENT TOILET/SHOWER
M4-316A
PATIENT BEDROOM
M4-318
LINEN CLOSET
M4-309
WHEELCHAIR STORAGE
M4-307
STAFF LOUNGE
M4-304
MECHANICAL
M4-334
HAND WASH 2
HW-2
CORRIDOR
C4-33
WORK AREA 2
WA-2 4
"S
A N
WC
FD
LAV
FD
WCO
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
LAV
WCOFD
FD
FD
FD
WC
WC
LAV
LAV
WC WC
4"SAN
WCO
FD
WCO
LAV
FD
WC
LAV
WCO
LAV
WC
WCO
WC
LAV
WCO
WCO
LAV
LAV
LAV
LAV
LAV
WCO
WC
LAV
WCO
WCO
LAV
WCWCO
MB
FD
WCO
LAV
FD
WC
IM
WCO
SK
4"SAN
4"SAN
4"SAN
4"SAN
4"SAN
4"SAN
4"SAN
4"SAN
SK
4"SAN
4"SAN
4"SAN
2"SAN
4"SAN
3"SAN
3"SAN
4"SAN 4"SAN
4"SAN
4"SAN
4"SAN 4"SAN
4"SAN
1-1/2" V UP
1-1/2" V UP1-1/2" V UP
2" V UP
1-1/2" V UP
2" V UP1-1/2" V UP
1-1/2" V UP
1-1/2" V UP 1-1/2" V UP
1-1/2" V UP
1-1/2" V UP
2" V UP
2" V UP
1-1/2" V UP
1-1/2" V UP 1-1/2" V UP
1-1/2" V UP
1-1/2" V UP
1-1/2" V UP
1-1/2" V UP
1 1
SK
1-1/2" V UP
1-1/2" V UP
1-1/2" V UP
LAV
LAV
LAV LAV
LAV
1-1/2" V UP
LAV
4"SAN
LAVLAV
EWC
WC WC
4" SAN UP
2"SAN
LAV
LAV
LAV
LAV
4"SAN
RRC-1
RRC-1
2"SAN
4"SAN
4"SAN
4"SAN
4"V
FD
FD 1-1/2" V UP
1-1/2" V UP
"S
A N
4"SAN
4"SAN
LAV
FD FD
WCO
LAV
WCWC
SK
FS
FS
FCO
LAV
4"SAN
2"SAN
4"SAN
1-1/2" V UP
2"SAN
LAV
4"SAN
4"SAN
"S
A N
"S
A N
2"S
AN
2"S
AN
4"SAN
4"SAN
2" S
AN
4"SAN
FD
FD
1 1/2"V
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:3
P
M
P203
THIRD FLOOR PLUMBING PLAN Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
N O R
HT
1/8" = 1'-0"
LEVEL 03 PLAN - PLUMBING
SHEET NOTES:
1. SEE SHEET P000 FOR SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES.
2. PLUMBING FIXTURES AND ARCHITECTURAL FLOOR PLAN
ON THIS SHEET ARE FOR THE FOURTH FLOOR AND ARE
FOR REFERENCE.
KEYED NOTES:
1. EXISTING 4" SAN AND VENT RISER.
2. CONNECT TO EXISTIN 4" SAN AND VENT RISER DOWN
AND OFFSET UP TO 4TH FLOOR.
8 8
4a
N1M1L2L1J2
J
J
H
H
G
G
F
F
EDCBA2A
8a
6a
J1H1
NURSE MNG. OFFICE
M4-357
PATIENT TOILET/SHOWER
M4-355A
OFFICE DOCUMENTATION
M4-360
STAFF TOILET
M4-358
PATIENT TOILET/SHOWER
M4-356A
ISO PATIENT BEDROOM
M4-356
ANTE ROOM
M4-354
ISO PATIENT BEDROOM
M4-352
ISO PATIENT BEDROOM
M4-355
ISO PATIENT BEDROOM
M4-351
ANTE ROOM
M4-353
PATIENT TOILET/SHOWER
M4-351A
SOILED UTILITY
M4-349
H.A.C.
M4-362
CORRIDOR
C4-34
STAIRWELL NO. 1
S1
ELEC. CLOSET
M4-347
ELEC. CLOSET
M4-345
STERILE SUPPLY ROOM
M4-350
NOURISHMENT STATION
M4-348
PATIENT TOILET/SHOWER
M4-352A
WORK AREA 1
WA-1
HAND WASH 1
HW-1
MSA STATION
M4-342
CLEAN UTILITY ROOM
M4-332
PATIENT BEDROOM
M4-337
PATIENT TOILET/SHOWER
M4-337A
PATIENT TOILET/SHOWER
M4-335A
PATIENT BEDROOM
M4-335
CORRIDOR
C4-32
MECHANICAL ROOM
M4-333
LINEN CHUTE
M4-311
ELEC. CLOSET
M4-331
CORRIDOR
C4-30
HALLWAY
M4-305
OIT DATA CLOSET
M4-305A
BIOMED NETWORK CLOSET
M4-303
MEDICATION ROOM
M4-306
SERVICE ELEVATOR
E16
SERVICE ELEVATOR
E17
ELEVATOR
E1
ELEVATOR
E2
ELEVATOR
E3
ELEVATOR
E4
WAITING ROOM
M4-302
LOBBY
M4-300
PATIENT TOILET/SHOWER
M4-319A
PATIENT BEDROOM
M4-319
PATIENT BEDROOM
M4-317
PATIENT TOILET/SHOWER
M4-317A
PATIENT BEDROOM
M4-315
PATIENT TOILET/SHOWER
M4-315A
CORRIDOR
C4-31
CORRIDOR
M4-330
RRC-1
RRC-1
WORK AREA 3
WA-3
EQUIPMENT STORAGE
M4-359
CRASH CART
CC-1
HAND WASH 3
HW-3
PATIENT BEDROOM
M4-320
PATIENT TOILET/SHOWER
M4-320A
PATIENT TOILET/SHOWER
M4-318A
PUBLIC TOILET
M4-302A
PUBLIC TOILET
M4-302B
MED GAS STORAGE
M4-343
PORTABLE X-RAY ALCOVE
C4-34B
PATIENT BEDROOM
M4-316
PATIENT TOILET/SHOWER
M4-316A
PATIENT BEDROOM
M4-318
LINEN CLOSET
M4-309
WHEELCHAIR STORAGE
M4-307
STAFF LOUNGE
M4-304
MECHANICAL
M4-334
HAND WASH 2
HW-2
CORRIDOR
C4-33
WORK AREA 2
WA-2
P-413
FD-C P-701
P-701
P-102
P-413
P-701
P-102
P-413
1 1/2"CW1 1/2"CW2"CW
P-104 P-104
P-104
FD-CFD-C
FD-C
FD-C
FD-C
FD-C
FD-C
FD-C
P-413
P-104
P-418
P-104
P-413
P-413
P-701
"C
W
/2 "H
W
2 1/2"CW
2"CW
P-701
WCO-1
FD-C
FD-C
FD-C
FD-C
FD-C
/2 "V
P-812
1 1/2"V
"V
2"V
2"CW 2"CW 2"CW
/2 "C
W
"V
FD-C
FD-C
"V
2"V
"V
2"V
1 1/2"CW 1 1/2"CW
1 1/2"CW
WCO-1
/4 "H
W
2"V
"V
1 1/2"HW
P-6150
P-701
P-413
FD-C
FD-C
"V
P-502
P-524
P-413
P-413
P-413
1"HW
0.5 GPM
"H
W1
/4 "H
W
1 1/4"HW 1 1/4"HW
1 1/4"HW
1 1/4"HW 1"HW 1.2 GPM
P-413
P-104
P-420
WCO-1
WCO-1
P-420
P-420 P-420
P-420
P-420
P-420
WCO-1
1 1/2"V
2"V
"C
W P-104
1 1/2"V
1 1/2"V
1 1/2"V
WCO-1
FD-C
WCO-1
P-413 P-413
P-103 P-103
P-609
/2 "C
W
/4 "H
W
/4 "H
W
P-701
WCO-1
WCO-1
WCO-1
WCO-1
CONNECT NEW 3/4"
HWC LINE TO
EXISTING LINE ON
FIFTH FLOOR.
FD-C
WCO-1
1 1/2"1 1/2"
2"V
2"V
2"V
2"V1 /2
"C W
1/2"CW
3/4"HW3/4"HW
3/4"HW
P600
1 1/2"HW
2"V
FT
FT
FLOW AND TEMP SENSORS
WITH CHLORINATION PORT
FOR LEGIONELLA MONITORING
AND CONTROL (TYP.)
P-420
P-418
P-418
P-420 P-420
CO
4"V
CO
4"V
4"SAN2"V
1 1/2"V
P-104
WCO-1
2"V
2"V
WCO-1
WCO-1WCO-1
WCO-1
WCO-1
WCO-1WCO-1
WCO-1
WCO-1 P-418
/2 "V
/4
"C W
/2 "H
W
P-701
P-413
FD-C
FD-C
"V
WCO-1
P-528
P-524
P-413
FD-C
"V
FD-C
P-104
ROUTE PIPING DOWN AND
OFFSET BELOW WINDOW
TO CONNECT TO SINK
/2 "V
1 1/2"V
FD-H
FD-H
FCO-1
P-420P-420
1 1/2"V
WCO-1
P-418
P-104
/4 "H
W
3/4"HW1 1/4"HW 1 1/4"HW 1 1/4"HW
WCO-1
1/2"CW
/2
"C W
1/2"CW
1/2"CW
0.5 GPM
CP-1
/2
"C W
P-804
P-804
0.5 GPM
P-701
1 1/2"CW
1 1/2"CW
1/2"CW
1/2"CW
1/2"CW
/2
"C W
FD-CFD-C
SEE ENLARGED
PLAN FOR TYPICAL
PATIENT ROOM
FTFT
TS
TS
TS
TS
TS TS
TSTS
TS
TS
LEGIONELLA
CONTROL TEMP
SENSOR (TYP.)
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:4
P
M
P204
FOURTH FLOOR PLUMBING PLAN Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
N O R
HT
1/8" = 1'-0"
LEVEL 04 PLAN - PLUMBING
SHEET NOTES:
1. SEE SHEET P000 FOR SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES.
2. SEE ENLARGED PLAN, DETAIL 1 ON SHEET P600 FOR
TYPICAL PATIENT ROOM.
KEYED NOTES:
1. EXISTING 4" SAN AND VENT RISER.
2. OFFESET AND CONNECT NEW 4" SAN AND VENT TO
EXISTING RISER UP.
3. 1/2" CW FROM CIRCULATING PUMP. CONNECT TO MAIN
8 8
4a
N1M1L2L1J2
J
J
H
H
G
G
F
F
EDCBA2A
8a
6a
J1H1
NURSE MNG. OFFICE
M4-357
PATIENT TOILET/SHOWER
M4-355A
OFFICE DOCUMENTATION
M4-360
STAFF TOILET
M4-358
PATIENT TOILET/SHOWER
M4-356A
ISO PATIENT BEDROOM
M4-356
ANTE ROOM
M4-354
ISO PATIENT BEDROOM
M4-352
ISO PATIENT BEDROOM
M4-355
ISO PATIENT BEDROOM
M4-351
ANTE ROOM
M4-353
PATIENT TOILET/SHOWER
M4-351A
SOILED UTILITY
M4-349
H.A.C.
M4-362
CORRIDOR
C4-34
STAIRWELL NO. 1
S1
ELEC. CLOSET
M4-347
ELEC. CLOSET
M4-345
STERILE SUPPLY ROOM
M4-350
NOURISHMENT STATION
M4-348
PATIENT TOILET/SHOWER
M4-352A
WORK AREA 1
WA-1
HAND WASH 1
HW-1
MSA STATION
M4-342
CLEAN UTILITY ROOM
M4-332
PATIENT BEDROOM
M4-337
PATIENT TOILET/SHOWER
M4-337A
PATIENT TOILET/SHOWER
M4-335A
PATIENT BEDROOM
M4-335
CORRIDOR
C4-32
MECHANICAL ROOM
M4-333
LINEN CHUTE
M4-311
ELEC. CLOSET
M4-331
CORRIDOR
C4-30
HALLWAY
M4-305
OIT DATA CLOSET
M4-305A
BIOMED NETWORK CLOSET
M4-303
MEDICATION ROOM
M4-306
SERVICE ELEVATOR
E16
SERVICE ELEVATOR
E17
ELEVATOR
E1
ELEVATOR
E2
ELEVATOR
E3
ELEVATOR
E4
WAITING ROOM
M4-302
LOBBY
M4-300
PATIENT TOILET/SHOWER
M4-319A
PATIENT BEDROOM
M4-319
PATIENT BEDROOM
M4-317
PATIENT TOILET/SHOWER
M4-317A
PATIENT BEDROOM
M4-315
PATIENT TOILET/SHOWER
M4-315A
CORRIDOR
C4-31
CORRIDOR
M4-330
RRC-1
RRC-1
WORK AREA 3
WA-3
EQUIPMENT STORAGE
M4-359
CRASH CART
CC-1
HAND WASH 3
HW-3
PATIENT BEDROOM
M4-320
PATIENT TOILET/SHOWER
M4-320A
PATIENT TOILET/SHOWER
M4-318A
PUBLIC TOILET
M4-302A
PUBLIC TOILET
M4-302B
MED GAS STORAGE
M4-343
PORTABLE X-RAY ALCOVE
C4-34B
PATIENT BEDROOM
M4-316
PATIENT TOILET/SHOWER
M4-316A
PATIENT BEDROOM
M4-318
LINEN CLOSET
M4-309
WHEELCHAIR STORAGE
M4-307
STAFF LOUNGE
M4-304
MECHANICAL
M4-334
HAND WASH 2
HW-2
CORRIDOR
C4-33
WORK AREA 2
WA-2
/4 "M
V /4
"M A
/4
"O
3/4"O
3/4"MA
1"MV1"MV
3/4"MA
3/4"O
1 1/4"MV
3/4"MA
3/4"O 3/4"O
3/4"MA
1"MV
/4
"O /4
"M A
"M
V
1"MV
3/4"MA
3/4"O
/4
"O /4
"M A
"M
V
3/4"O
3/4"MA
1"MV
VB-1
1"MV
3/4"MA
3/4"O
1"MV
3/4"MA
3/4"O
3/4"O
3/4"MA
1"MV
3/4"O
3/4"MA
1"MV
1"MV
3/4"MA
3/4"O
1"MV
3/4"MA
3/4"O
3/4"O
3/4"MA
1"MV
1 1
AAP-1
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:5
P
M
P214
FOURTH FLOOR MED GAS PLAN Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
N O R
HT
1/8" = 1'-0"
LEVEL 04 PLAN - MEDICAL GAS
KEYED NOTES:
1. 3/4" OXYGEN AND MEDICAL AIR, AND 1" VACUUM DOWN
IN WALL. CONNECT TO OUTLETS IN OWNER PROVIDED
PRE-MANUFACTURED HEADWALL.
SHEET NOTES:
1. SEE SHEET P000 FOR SYMBOLS, ABBREVIATIONS AND
GENERAL NOTES.
FD-C
P-413P-413
FD-C
FD-C
2"SAN
FD-C
P-104
P-104
4"SAN
2"V
1 1/2"V
2"V
2"V
2"V
/2 "V
WCO-1
4"SAN
2"SAN
2"SAN
P-420
1 1/2"V
1 1/2"V
P-420
2"SAN
2"SAN
4"SAN
"V
"S A N
"S A N
"V
"S A N
"V
4"SAN
4"V
3"SAN
FD-H
FD-H
3"SAN
3"SAN
/2 "V 1
/2
"V
1 1/2"V
1 1/2"V
P-418
FD-C
P-104
P-413
FD-C
P-502
4"SAN
"V
2"V
1 1/2"V
WCO-1
WCO-1
"V
"S A N
"V
"S A N
"V
"S A N
"S A N
"V
"S A N
"V
4"SAN
2"S
AN
4"SAN
WCO-1
P-413
P-418
WCO-1
FD-C
FD-C
P-104P-413
P-413
P-104
FD-C
P-6150
4"SAN
4"SAN
/2 "V
2"V
WCO-1
P-104
FD-C
P-420
FD-C
P-413
WCO-1
P-420
P-420
P-420
WCO-1
1 1/2"V
1 1/2"V
P-418
2"SAN
2"V
2"V
2"V
1 1/2"V 2"V
P-418
FD-C
WCO-1
WCO-1
WCO-1
WCO-1
WCO-1
WCO-1
WCO-1
3"S
AN
3"S
AN
4"SAN
4"SAN
2"SAN
"S
A N
4"SAN
4"SAN
"V
"S A N
4"S
AN
2"SAN
P-103
P-103
P-413
P-413
WCO-1
P-609
/2 "V
1 1/2"V
2"V
2"SAN
2"SAN
4"SAN
WCO-1
FD-C
FD-C
/2 "V
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:0
P
M
P300
PLUMBING RISER DIAGRAMS Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
NO SCALE
RISER DIAGRAM EAST
NO SCALE
RISER DIAGRAM NORTH
NO SCALE
RISER DIAGRAM WEST
4"SAN
2"V
1 1/2"V
2"SAN
4"SAN
4"S
AN
4"S
AN
4"SAN
4"S
AN
FD-C
P-413
FD-C
P-413
P-102
FD-C
P-418
WCO-1
P-413
P-104
FD-C
FD-C
4"S
AN
P-420
4"S
AN
FD-C
P-413
2"SAN
/2 "V
4"SAN
"S A N
"V
"V
"S A N
"V
"S A N
"S A N
4"V
WCO-1
P-812
P-524
2"SAN
2"S
AN 2"SAN
"S
A N
4"S
AN
2"V
2"V
2"V
2"V
1 1/2"V
1 1/2"V
2"V
2"V
2"V
2"V
2"V
2"V
4"V
P-420
FD-C
/2 "V
FD-C
P-102
P-102
P-104
4"SAN
4"SAN
/2 "V
/2 "V
1 1/2"V
1 1/2"V
1 1/2"V
1 1/2"V
P-420
P-420
WCO-1
WCO-1
4"SAN
4"V
WCO-1WCO-1
4"V
4"SAN
"V
CO
"S A N
"V
4"V
4"SAN
4"V
"S A N
4"SAN
WCO-1
4"S
AN
2"SAN
2"SAN
2"SAN
4"SAN
4"SAN
"S
A N
"V
1 1/2"V
2"V
2"V
2"V
4"S
AN
4"SAN
2"SAN
/2 "V
/2 "V
P-420
/2 "V
2"V
2"V
4"SAN
4"SAN
4"SAN
P-524
P-528
WCO-1
FD-C
P-413
P-104
FD-C
FD-C
FD-C
P-413
P-104
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:1
P
M
P301
PLUMBING RISER DIAGRAMS Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
NO SCALE
RISER DIAGRAM SOUTH
M1L2
PATIENT TOILET/SHOWER
M4-319A
PATIENT BEDROOM
M4-319
"V
"V
/2 "C
W
"V
/2
"H W
/2
"H W
FD-C P-701
3/4"HW
1 1/2"CW1 1/2"CW
3/4"HW
1/2"CW 1/2"HW
1 1/2"V
"V
1/2"CW
1/2"HW
1-1/2" V DN
2" V DN
FD-C
1/2"HW
1/2"CW
P-104
P-413
WCO-1
1-1/2" V DN
P-420
STRAP-ON FLOW SENSOR BY M.C.
REFER TO MECH. DRAWINGS
WIRING BY EC. REFER
TO ELECTRICAL DRAWING
NOTES:
1. INSTALL SENSOR(S) PER MANUFACTURER'S REQUIREMENTS; CONFIRM ALL CLEARANCE AND SPACING REQUIREMENTS AND
VERIFY ON-SITE CONDITIONS ARE ACCEPTABLE.
2. THE ONICON F4300 SENSOR AND TEMPERATURE SENSOR SHOULD BE ABLE TO BE INSTALLED SIDE BY SIDE AT MOST
LOCATIONS. WHERE SPACE WILL NOT ALLOW THIS TO HAPPEN THE TEMPERATURE SENSOR CAN BE MOUNTED IN CLOSE
PROXIMITY TO THE FLOW SENSOR.
DIRECTION OF FLOW
NOTE 2NOTE 2
3/4" VALVE & CAP FOR CHLORINATION
CONNECTION. CONFIRM EXACT
CONNECTION REQUIREMENTS WITH
COR PRIOR TO INSTALLATION.
TO F4300
SYSTEM 10
TRANSDUCER
REMOTE MOUNTED
F4300
NOTES:
1. INSTALL SENSOR(S) PER MANUFACTURER'S REQUIREMENTS; CONFIRM ALL CLEARANCE AND SPACING REQUIREMENTS AND
VERIFY ON-SITE CONDITIONS ARE ACCEPTABLE. NOTIFY ENGINEER IF SENSOR LOCATION DOES NOT PROVIDE SUFFICIENT
SPACE FOR INSTALLATION.
WIRING BY EC. REFER TO
ELECTRICAL DRAWINGS
PIPE AND INSULATION
SIZE VARIES, REFER TO FLOOR
PLANS FOR SIZES.
STRAP-ON TEMPERATURE SENSOR BY
MC. REFER TO MECHANICAL DRAWINGS.
INSULATE COMPLETELY
AROUND SENSOR. SENSOR MUST
TOUCH BARE PIPE.
WORM GEAR
13890 bishops drive, suite 250 brookfield, wi 53005
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NAGEL
project number:
B
IM
/1
.0
V A
K C
R e n o v a te
E f o r P
C U
/M E
P
.0 V
A K
C R e n o v a te
E f o r P
C U
C
.r v t
/7
/2
:4
:2
P
M
P600
PLUMBING & MED GAS MATERIALS
LISTS
Renovate 4E for Progressive Care Unit
4801 Linwood Blvd, Kansas City, MO, 64128
589-22-420
June 09, 2023 BEH CSB
ISSUE FOR BID
589-22-420
1600 BALTIMORE
SUITE 300
KANSAS CITY, MO 64108
P: 816.842.8437 www.imegcorp.com
Missouri Certificate of Authority #F001325536
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #18001588.06
MEDICAL GAS MATERIAL LIST
TAG NAME DESCRIPTION MANUFACTURER AND MODEL
AAP-1 AREA ALARM PANEL - MODULAR IN DESIGN, DIGITAL TYPE, USED WITH REMOTE
OR LOCAL SELF CONTAINED LINE PRESSURE AND LINE VACUUM SENSORS. THE
MEDICAL GAS LINES TO BE MONITORED SHALL INCLUDE THE FOLLOWING:
OXYGEN
MEDICAL AIR
VACUUM
THE MODULE FOR MONITORING EACH GAS OR VACUUM LINE SHALL INCLUDE
THE FOLLOWING: AN AUDIBLE WARNING DEVICE THAT WILL SOUND IF THE
PRESSURE IN A MEDICAL GAS LINE IS 20% ABOVE OR BELOW ITS
NORMALSETTING AND AN "ABNORMAL" RED LIGHT THAT WILL COME ON. A
SWITCH SHALL BE PROVIDED TO SILENCE THE AUDIBLE WARNING DEVICE.
"ABNORMAL" RED LIGHT WILL REMAIN LIT UNTIL CONDITION HAS BEEN
CORRECTED. A BUILT-IN LCD (LIQUID CRYSTAL DISPLAY) WILL CONTINUOUSLY
INDICATE THE PRESSURE OR VACUUM AT ALL TIMES. A TEST SWITCH SHALL BE
SUPPLIED TO TEST INTERNAL CIRCUITS, LIGHTS ANDWARNING DEVICES. ALL
POWER WIRING TO THE ALARM PANEL AND SENSORS TO BE WIRED BY THE
ELECTRICAL CONTRACTOR. ALL ALARM WIRING TO THE PANEL IS THIS
CONTRACTORS RESPONSIBILITY. ALL WIRING TO COMPLY WITH THE
RECOMMENDATION OF THE ALARM PANEL MANUFACTURER AND SHALL BE RUN
IN CONDUIT. ALL WIRING SHALL COMPLY WITH THE LATEST EDITION OF THE
NATIONAL ELECTRICAL CODE. THIS CONTRACTOR SHALL PROVIDE WIRING
DIAGRAMS AND REQUIREMENTS TO THE ELECTRICAL CONTRACTOR.
BEACONMEDAES, ALLIED
HEALTHCARE, OHIO MEDICAL,
PATTON’S MEDICAL,
TRI-TECH, AMICO, POWEREX
VB-1 VALVE BOX - PAINTED GALVANIZED STEEL WITH PLASTER FRAME, TEMPORARY
PLASTER GUARD, IDENTIFICATION COVER AND SHIELD. THE FINISH FRAME
SHALL MOUNT TO BOX WITH CONCEALED MOUNTING SCREWS.
PLACEMENT OF VALVE HANDLE WITHIN THE BOX SHALL BE SUCH THAT THE
EMERGENCY PLASTIC PULL-OUT WINDOW CANNOT BE REPLACED WITH THE
VALVE HANDLE IN THE "OFF" POSITION.
FACTORY INSTALLED TUBING SHALL EXTEND AT LEAST 3" BEYOND THE BOX,
AND THE VALVE BODY SHALL BE SWUNG OUT OF LINE OF HEAT TRANSFER,
PERMITTING JOINT TO BE BRAZED WITHOUT OBSTRUCTION OR HEAT DAMAGE
TO VALVE. OPEN ENDS OF TUBING SHALL BE CAPPED TO AVOID
PREINSTALLATION CONTAMINATION.
A 1-1/2" DIAMETER LINE PRESSURE/VACUUM GAUGE SHALL BE SUPPLIED AND
INSTALLED DOWNSTREAM OF SHUTOFF VALVE.
ALL VALVES SHALL BE PREPARED FOR OXYGEN SERVICE AND SHALL CONFORM
TO NFPA #99. ALL VALVES SHALL BE OF BALL-TYPE, WITH DOUBLE O-RING STEM
SEAL AND TEFLON BALL SEATING, MINIMUM WORKING PRESSURE OF 400 PSIG,
ACTUATED FROM FULL "ON" TO FULL "OFF" BY 90 DEGREE TURN OF VALVE
HANDLE. IDENTIFY SERVICE ON EACH VALVE HANDLE.
VALVES SHALL BE THE SAME SIZE AS THE PIPING ENTERING THE VALVE.
VALVE BOX SHALL CONTAIN THE FOLLOWING VALVES:
OXYGEN, MEDICAL AIR, & VACUUM
BEACONMEDAES, ALLIED
HEALTHCARE, OHIO MEDICAL,
PATTON’S MEDICAL,
TRI-TECH, AMICO, POWEREX
PLUMBING MATERIAL LIST
TAG NAME DESCRIPTION MANUFACTURER AND MODEL
P-420 (P-420) Lavatory (Sensor…