This file contains technical drawings related to a federal solicitation for renovation services. The solicitation number 36C25523R0115 was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 to renovate building 4E for a Primary Care Unit at an unspecified VA medical center. The solicitation is seeking general construction services to complete renovations as detailed in the 37-page drawing package, with a response due date not provided. The awarded contract is expected to support renovations to improve primary care services for veterans.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING

MECHANICAL

ELECTRICAL

COMMISSIONING

Enviros 220 Ramsey Street Hastings, MN 55033 Phone: 651-319-0170 Contact: Mike Lavoie E-mail: mlavoie@enviros.com

DESIGNER LIST AND STAMPS

IMEG

1600 Baltimore, suite 300 Kansas City, MO 64108 Phone: 816-842-8437 Contact: Bruce Hart E-mail: bruce.e.hart@imegcorp.com

IMEG

1600 Baltimore, suite 300 Kansas City, MO 64108 Phone: 314-257-0632 Contact: Mason Ryan E-mail: Mason.J.Ryan@imegcorp.com

IMEG

1600 Baltimore, suite 300 Kansas City, MO 64108 Phone: 314-257-0632 Contact: Lindsay Robertson E-mail: lindsay.robertson@imegcorp.com

STRUCTURAL

Calibre Engineering 9090 S Ridgeline Blvd. suite 105 Highlands Ranch, CO 80129 Phone: 303-730-0434 Contact: Ed Sabia E-mail: esabia@calibre-engineering.com

ESTIMATING

MCC Consaulting & Contracting W279N7090 Mill Pond Way Merton, WI 53056 Phone: 608-960-9444 Contact: Tom Middleton E-mail: tmiddleton@middleton-cc.com

ENVIRONMENTAL

SCI Engineering, INC.

130 Point West Boulevard St. Charles, MO 63301 Phone: 618-779-1445 Contact: Glen Grissom E-mail: GGrissom@sciengineering.com

ARCHITECT

NAGEL Architects + Engineers 13890 Bishops Dr, suite 250 Brookfield, WI 53005 Phone: 262.641.0746 Contact: Joe Heinowski E-mail: joe.heinowski@nagel.us

Kansas City VAMC 4801 Linwood Blvd, Kansas City, MO, 64128

CONTACT:

James Hidgon james.hidgon@va.gov 816-672-9747

NORTH

SIGNATURE BLOCK

APPROVED: PAULA ROYCHAUDHURI

ASSOCIATE DIRECTOR

DATE

APPROVED: CHARLES M. RONE

FACILITY PLANNER

DATE

APPROVED: MARCUS STEVENSON

PROJECT MANAGER

DATE

APPROVED: JESSICA FLANERY

INPATIENT CHIEF NURSE

DATE

APPROVED: JEFF HERNBLOOM

CHIEF OF FMS

DATE

APPROVED: PRESTON WHITE III

PROJECTS SUPERVISOR

DATE

APPROVED: JAMIE MILLER

M&O SUPERVISOR

DATE

APPROVED: ARTURO DELFIN

BIOMED

DATE

APPROVED: PARINYA SUKAROMYA

OI&T

DATE

APPROVED: DOMINIQUE HENDERSON

CHIEF OF EMS

DATE

APPROVED: MATHEW JOHNSON

INFECTION CONTROL

DATE

APPROVED: MATTHEW STEWART

SAFETY MANAGER

DATE

APPROVED: ANA MARIA CORCORAN

PATIENT SAFETY

DATE

APPROVED: KELLY FLANDERS

INTERIOR DESIGN

DATE

APPROVED: BRETT TWADDLE

ENERGY ENGINEER

DATE

APPROVED: JOHN REINERT

BOS

DATE

APPROVED: JOHN ARMSTEAD

KCVA POLICE

DATE

APPROVED: RANDALL LIVENGOOD

LOGISTICS

DATE

SHEET # SHEET NAME

00 - GENERAL - G

G001 COVER SHEET

G002 ARCHITECTURAL ABBREVIATIONS AND SYMBOLS

G003 BUILDING CODE REVIEW

G104 FOURTH FLOOR LIFE SAFETY PLAN

01 - ABATEMENT - H

H104 FOURTH FLOOR ASBESTOS ABATEMENT PLAN - FLOORING

H204 FOURTH FLOOR ASBESTOS ABATEMENT PLAN- MISCELLANEOUS

H304 FOURTH FLOOR ASBESTOS ABATEMENT PLAN - TSI

H404 FOURTH FLOOR ASBESTOS ABATEMENT PLAN - LBP

H405 THIRD FLOOR ABATEMENT PLAN

06 - STRUCTURAL

S001 GENERAL STRUCTURAL NOTES, DESIGN LOADS & ABBREVIATIONS

S002 QA NOTES AND TABLES

S104 FOURTH FLOOR FRAMING PLAN

S501 TYPICAL STRUCTURAL DETAILS

07 - ARCHITECTURAL - A

AD104 FOURTH FLOOR ARCHITECTURAL DEMOLITION PLAN

AD114 FOURTH FLOOR DEMOLITION REFLECTED CEILING PLAN

A104 FOURTH FLOOR ARCHITECTURAL PLAN

A114 FOURTH FLOOR REFLECTED CEILING PLAN

A124 FOURTH FLOOR WALL PROTECTION PLAN

A134 FOURTH FLOOR WAYFINDING PLAN

A201 INTERIOR ELEVATIONS

A202 INTERIOR ELEVATIONS

A203 INTERIOR ELEVATIONS

A204 INTERIOR ELEVATIONS

A205 INTERIOR VIEWS

A301 BUILDING SECTIONS

A404 FOURTH FLOOR ENLARGED ARCHITECTURAL PLAN

A405 ENLARGED PARTIAL ARCHITECTURAL FLOOR PLANS

A414 ENLARGED REFLECTED CEILING PLANS

A501 WALL AND PARTITION TYPES

A601 DOOR AND FRAME SCHEDULE & DETAILS

A701 TYPICAL DETAILS

A702 TYPICAL DETAILS

A703 TYPICAL DETAILS

AF104 FOURTH FLOOR FINISH PLAN

Q804 P-TUBE FLOOR PLAN COORDINATION

09 - EQUIPMENT - Q

Q104 FOURTH FLOOR EQUIPMENT PLAN

Q601 EQUIPMENT SCHEDULE

10 - FIRE PROTECTION - F

F000 FIRE PROTECTION COVERSHEET

F204 FOURTH FLOOR FIRE PROTECTION PLAN

11 - PLUMBING

P000 PLUMBING + MEDICAL GAS COVERSHEET

P103 THIRD FLOOR PLUMBING DEMOLITION PLAN

P104 FOURTH FLOOR PLUMBING DEMOLITION

P203 THIRD FLOOR PLUMBING PLAN

P204 FOURTH FLOOR PLUMBING PLAN

P214 FOURTH FLOOR MED GAS PLAN

P300 PLUMBING RISER DIAGRAMS

P301 PLUMBING RISER DIAGRAMS

P600 PLUMBING & MED GAS MATERIALS LIST

12 - MECHANICAL

M000 MECHANICAL COVERSHEET

M204 MECHANICAL PIPING

M214 MECHANICAL VENTILATION

M400 MECHANICAL DETAILS

M401 MECHANICAL DETAILS

M403 MECHANICAL DETAILS

M500 MECHANICAL CONTROL DIAGRAMS

M501 MECHANICAL CONTROL DIAGRAMS

M502 MECHANICAL CONTROL DIAGRAMS

M600 MECHANICAL SCHEDULES

M601 MECHANICAL SCHEDULES

13 - ELECTRICAL

E000 ELECTRICAL COVERSHEET

E001 ELECTRICAL SYSTEMS COVERSHEET

EL204 LEVEL -04 PLAN - ELECTRICAL LIGHTING

EP304 LEVEL -04 PLAN - ELECTRICAL POWER

ES404 LEVEL -04 PLAN - ELECTRICAL SYSTEM

E500 ELECTRICAL SCHEDULES

14 - TECHNOLOGY

T000 TECHNOLOGY COVERSHEET

T104 FOURTH FLOOR TECHNOLOGY DEMOLITION

T204 FOURTH FLOOR TECHNOLOGY PLAN

T214 FOURTH FLOOR NURSE CALL PLAN

T301 TECHNOLOGY DETAILS

T401 TECHNOLOGY RISER DIAGRAMS

T501 TECHNOLOGY SCHEDULES

13890 bishops drive, suite 250 brookfield, wi 53005

DEPARTMENT OF VETERANS AFFAIRS

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

NAGEL A+E PROJECT NUMBER:VA PROJECT NUMBER:

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Project NumberProject TitleDrawing Title Phase

NAGEL

project number:

C :\U se rs

\r ya nb \D oc um en ts

\2

-K an sa s C ity P

C U

_I S

S U

E F

O R

B

ID

_R ya n.

bo ur la nd .r vt 7/

/2

4:

:4

P M

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

22014589-22-420

G001

COVER SHEET Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

07/11/2023 JH RF,RB

FULLY SPRINKLERED

ISSUE FOR BID

22014

SHEET INDEX

PROJECT SITE MAP

PROJECT LOCATION MAP

STATION INFORMATION

PERSPECTIVE

BUILDING 1

Revisions: Date:

1-SCHEMATIC DESIGN 35% 07/29/2022

2-DESIGN DEVELOPMENT 65% 09/16/2022

3-CONSTRUCTION DOCUMENTS 95% 11/22/2022

4-CONSTRUCTION DOCUMENTS 95% R 12/16/2022

5-CONSTRUCTION DOCUMENTS 100% 01/30/2023

6-CONSTRUCTION DOCUMENTS 100%R 03/20/2023

7-CONSTRUCTION DOCUMENTS 100%R2 04/28/2023

SCOPE OF WORK INFORMATION

THIS PROJECT WILL BE PERFORMED BY

MULTIPLE ENTITIES DEFINED IN THE

DOCUMENT NAMED ATTACHMENT #01.

THE PURPOSE OF THIS DOCUMENT IS TO

DEFINE THE WORK SCOPE TO BE

PERFORMED BY THESE ENTITIES AND

PROVIDE CLEAR DIRECTION ON WHAT

PARTS OF THIS PROJECT WILL BE

COMPLETED BY EACH ENTITY.

7/11/23

NORTH ARROW

ELEVATION REFERENCE

SYMBOL

ELEVATION REFERENCE

SYMBOL

SECTION REFERENCE

SYMBOL

ENLARGED AREA

REFERENCE SYMBOL

DOOR TAG

REVISION TAG

WINDOW TAG

ROOM TAG

COLUMN REFERENCE

SYMBOL

Name Elevation

A101

A101

SIM

A101

SIM

NORTH

PARTITION TAG

A36C G11C

ARCHITECTURAL SYMBOLS___

ROOM NAME

111A

EQUIPMENT TAGX####

A101

SIM DETAIL REFERENCE

SYMBOL

AD101.1 MATCH LINE

AREA NOT IN CONTRACT

A ALIGN FINISH

SURFACES FLUSH

WALL TAG1iEX1

FINISH WOOD

CONCRETE MASONRY UNIT (CMU)

CONCRETE, CAST-IN-PLACE

CONCRETE, PRE-CAST

FILL - PER NOTE

INTERMITTENT BLOCKING

CONT. ROUGH FRAMING

STEEL

EARTH

RIGID INSULATION

BATT INSULATION

GYPSUM BOARD

MARBLE/GRANITE/STONE

TILE/TERRAZZO

GLASS

LARGE SCALE

SECTIONS

BRICK

PLYWOOD

MATERIAL

MATERIAL LEGEND_________

EARTH, COMPACT

ALUMINUM

FILL, POROUS

EXISTING DOOR TO

REMAIN

EXISTING DOOR TO BE

REMOVED

180 DEGREE SWING

DOOR

SINGLE DOOR PAIR OF DOORS

DOOR WITH EMERGENCY

RELEASE HARDWARE

DOUBLE-ACTING DOOR CASED OPENINGPAIR OF DOUBLE EGRESS

DOORS

ASYMMETRIC DOORS

FRONT APPROACH

PULL SIDE

M

IN

DOOR & FIXTURE CLEARANCES

ALL ITEMS SHOWN ARE FOR REFERENCE ONLY - DOES NOT INDICATE EQUIPMENT OR FIXTURES TO BE PROVIDED

MIN

18"

FRONT APPROACH

PUSH SIDE

M

IN

HINGE APPROACH

PULL SIDE

M

IN

MIN

36"

FRONT APPROACH

PUSH SIDE

M

IN

MIN

12"

* IF BOTH CLOSER &

LATCH ARE PROVIDED

HINGE APPROACH

PUSH SIDE

M

IN

HINGE APPROACH

PULL SIDE

M

IN

MIN

42"

LATCH APPROACH

PUSH SIDE

M

IN

MIN

24"

MIN

22"

** 48" MIN IF BOTH CLOSER

& LATCH ARE PROVIDED

* 48" IF CLOSER IS

PROVIDED

LATCH APPROACH

PULL SIDE

*4

M

IN

MIN

24"

12"

24"

M A

X

M

IN

CLEAR FLOOR SPACE

@ WATER CLOSET

60"

2'-6"

CLEAR FLOOR SPACE

@ ADA LAVATORY

2'-6"

CLEAR FLOOR SPACE @

ADA DRINKING FOUNTAIN

VA TOILET ROOM

TURNING RADIUS

ø 5'-6" ø 6'-0"

VA BARIATRIC TOILET

ROOM TURNING RADIUS

MIN

18"

MIN

18"

* 54" MIN IF CLOSER

IS PROVIDED

ø 5'-0"

ADA TOILET ROOM

TURNING RADIUS

ALL ITEMS SHOWN ARE FOR REFERENCE ONLY - DOES NOT INDICATE EQUIPMENT OR FIXTURES TO BE PROVIDED

DOOR SIGN ON LATCH

SIDE OF DOOR (ADA)

4" MAX

>2

M

A X

T

O P

O F

F E

(I F

LB

O

R L

E S

S

M

A X

T O

F E

H A

N D

LE

3' -6

"M A

X

FEC

EXTINGUISHER

WEIGHT> 40 LBS

FEC

EXTINGUISHER

WEIGHT< 40 LBS

4'

M A

X

FE

FIRE

EXTINGUISHER

(2

(8

M A

X

-2

5" R

E A

C H

(2

(6

M

A X

M

A X

6)

(2

M

A X

6)

(2

(1

(9

(1)

(1

(1)

(1

(1)

(1

(9

(1) (1)

(1

(1

(1)

M

A X

5)

4M

IN

M

A X

6)

M A

X

L

A V

M A

X

M A

X

M A

X

LA

V T

O

M A

X

M A

X

-2

5" R

E A

C H

12"

24"

18"

T /O

B A

R

B /O

B A

R

18"

M

IN40"

"1 1/

2" C

LR

M

IN

(1

(2

M A

X

M

IN

18" 12

M A

X

M

IN

SIDE ELEVATION

FRONT ELEVATIONPLAN

M

IN

M A

X

7"-9"

7"-9"

M

IN

C

LE

A R

1/

2M

IN

C

LE

A R

SIDE ELEVATION

SIDE ELEVATION SIDE ELEVATION

M A

X

17"-19"

8" MIN

15"

M A

X

30" MIN CLR

M A

X

M

IN

17"

MIN

M

IN

18" UNO

SIDE ELEVATION SIDE ELEVATION

PLAN PLAN

SIDE ELEVATION

M

IN

25" MAX

M

IN

C

LE

A R

17" MIN

9" M

IN

6" MAX 11" MIN

8" MIN

R E

C O

M M

E N

D E

D

15"-16"

2 1/2MAX

22"-23"

1/

2M A

X

15 M A

X

S T

A

LL

D E

P T

H

3M A

X

15"-16"

2 1/2MAX

1/

2M A

X

S T

A

LL

D E

P T

H

3M A

X

M A

X

8)

4"

MAX

SIDE ELEVATION SIDE ELEVATION

A F

F

A S

S C

H E

D

AS SCHED

FIRE EXTINGUISHERS

HAND DRYER HAND DRYER FACIAL TISSUE

DISPENSER

SEAT COVER

DISPENSER

SOAP

DISPENSER

PAPER TOWEL

DISPENSER (FOLDED)

SINGLE ROLL

DISPENSER

DOUBLE ROLL

DISPENSER

MULTI-ROLL DISP

(SURFACE)

SNGL JUMBO

DISP(SURFACE)

DBL JUMBO DISP

(SURFACE)

DBL ROLL DISP

(PARTITION)

WASTE RECEPTACLE

(TALL & SHORT)

NAPKIN

DISPOSAL

PAPER TOWEL DISPENSERS

WITH WASTE (TALL & SHORT)

MIRROR

FRAMELESS

MIRROR

FRAME

MIRROR

WITH SHELF

R E

F

LE

C T

IV

E

S U

R F

A C

E

HAND DRYERS DISPOSAL

MIRRORS

PAPER TOWEL

DISPENSER (ROLL)

DISPENSERS

TYPICAL

@ RECESSED

LAVATORY

WATER CLOSET

34"

WATER CLOSETWATER CLOSET

BELOW GRAB BAR

ABOVE GRAB BAR

WATER CLOSET

NON-ACCESSIBLE

URINAL TOILET PAPER DISPENSER

ADA TOILETS & GRAB BARS

NOTES

MIN & MAX DIMENSIONS ARE TO THE BOTTOM OF THE DISPENSER

(1) CLEAR DIMENSION IS FROM BOTTOM OF GRAB BAR TO ANY PLUMBING

COMPONENT.

(2) TO TOP OF SEAT

SEE KNEE AND TOE

CLEARANCE DIAGRAM

INSULATED HOT

WATER & DRAIN PIPES

IN SHADED AREA. NO

SHARP OR ABRASIVE

SURFACES.

T O

S P

O U

T

T O

S P

O U

T

MIN TO SPOUT

MIN TO SPOUT

SEE KNEE AND TOE

CLEARANCE DIAGRAM

RIM OR COUNTER

SURFACE OF LAVATORY

MINIMUM CLEARANCE

AFF TO B.O. APRON

(ADAAG ONLY)

WALL MOUNT

ADAAG ONLY

PLAN

DRINKING FOUNTAINS

FREE-STANDING ADA FREE-STANDING

NON-ACCESSIBLE

FREE-STANDING ADA RECESSED

LAVATORIES

ADA LAVATORY

ADAAG & ANSI

MINIMUM TOE EXTENSION

UNDER AN ELEMENT

MAXIMUM KNEE AND TOE

EXTENSION UNDER AN

ELEMENT

KNEE CLEARANCE

TOE CLEARANCE

MINIMUM TOE EXTENSION

UNDER AN ELEMENT

KNEE & TOE CLEARANCES (NTS)

SIDE SIDE

PLAN PLAN

CHILDCARE

BABY CHANGING

STATION

DIMENSION NOTES

(1) SEE TP DISPENSER DIAGRAM FOR ADDITIONAL MOUNTING INFORMATION

(2) NON-ACCESSIBLE

(3) TOP OF SHELF

(4) TOP OF BAR OR PIN

(5) TOP OF WASTE OPENING

(6) TOP OF DISPENSER OPENING

(7) TOP OF HOOK

(8) TOP OF OPERABLE PART

(9) BOTTOM ROLL

(10) TOP OF CHANGING BED

SHOWER ACCESSORIES

SHOWER SEAT

(L-SHAPE)

SHOWER

CURTAIN ROD SHOWER SEAT

(RECTANGLE)

OUTLETS / RECEPTACLES

FLOOR

RECEPTACLE

COUNTER

RECEPTACLE

THERMOSTAT

(FORWARD REACH)

44" TYP

PROJECTION SCREEN

(WALL)

DOOR

SIGN

ADA DOOR

CONTROL

PROJECTION SCREEN DOOR SIGNAGE & CONTROL

42" MIN

12"

MAX

13.5" MIN

8" MIN

M

IN 9

M

IN

11"

MIN

"M

A X

-1 5"

M

IN

8)

"M

A X

-3 6"

M

IN

8)

4' -0

"M

IN

B /O

LO

W

E S

T T

E X

T

5' -0

B

/O

H

IG

H E

S T

T E

X T

"M

A X

-3 4"

M

IN

8)

44" TYP

M A

X

LA

V T

O

R E

F

LE

C T

IV

E

S U

R F

A C

E

SHARPS DISPOSAL UNIT

WITH GLOVE DISPENSER

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

n a g e l-d c \C o m p a n y \P ro je c ts

\2

-K a n s a s C it y P

C U

\4

D e s ig n D o c u m e n ts \4

D

M o d e lin g \2

-K a n s a s C it y P

C U

IS

S U

E F

O R

B

ID

.r v t

/2

/2

:2 :4

A

M

G002

ARCHITECTURAL ABBREVIATIONS

AND SYMBOLS

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

07/11/2023 JH RF,RB

ISSUE FOR BID

FULLY SPRINKLERED

22014

1/4" = 1'-0" D6

TYPICAL DOOR CONVENTIONS

UTIL UTILITY

V

VA VETERAN'S AFFAIRS, DEPARTMENT OF

VAR VARNISH

VCT VINYL COMPOSITION TILE

VEH VEHICLE

VERT VERTICAL

VF VINYL FABRIC

VG VERTICAL GRAIN

VIN VINYL

VJ V-JOINT(ED)

VNR VENEER

VT VINYL TILE

W

W WEST

W WIDTH, WIDE

W/ WITH

W/D WASHER & DRYER

W/O WITHOUT

WB WOOD BASE

WC WATER CLOSET

WD WOOD

WDW WINDOW

WG WIRED GLASS

WH WALL HUNG

WHS WHEEL STOP

WI WROUGHT IRON

WM WIRE MESH

WP WATER PROOFING

WPT WORKING POINT

WR WATER REPELLANT

WSCT WAINSCOT

WT WEIGHT

WTW WALL-TO-WALL

WWF WELDED WIRE FABRIC

WWM WELDED WIRE MESH

SL SLEEVE

SNT SEALANT

SP STANDPIPE

SP SOUNDPROOF

SPEC SPECIFICATION

SPK SPEAKER

SPKLR SPRINKLER

SPL SPECIAL

SQ SQUARE

SS STAINLESS STEEL

SSEW SANITARY SEWER

STA STATION

STC SOUND TRANSMISSION CLAS

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUS SUSPENDED

SUSP SUSPENSION

SYM SYMMETRICAL, SYMMETRY

SYN SYNTHETIC

SYS SYSTEM

T

T&G TONGUE & GROOVE

T/O(T.O.) TOP OF

TB TOWEL BAR

TC TERRA COTTA

TEL TELEPHONE

TEMP TEMPORARY

THK THICKNESS

THR THRESHOLD

THRU THROUGH

TOL TOLERANCE

TOT TOTAL

TOW(T.O.W.) TOP OF WALL

TPD TOILET PAPER DISPENSER

TR TREAD

TRM TRANSOM

TV TELEVISION

TYP TYPICAL

TZ TERRAZZO

U

UC UNDERCUT

UNFIN UNFINISHED

UNO(U.N.O) UNLESS NOTED OTHERWISE

UR URINAL

QT QUARTZ TILE

QTY QUANTITY

R

RA RETURN AIR

RAD RADIUS

RB RUBBER BASE

RBT RABBET, REBATE

RC RESILIENT CHANNEL

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RE REINFORCE(D)(ING)

REF REFERENCE

REFR REFRIGERATOR

REG REGISTER

REINF REINFORCED

REM REMOVE

REQ'D REQUIRED

RESIL RESILIENT

REV REVISION

RFG ROOFING

RFH ROOF HATCH

RFL REFLECT(ED)(IVE)(OR)

RH RIGHT HAND

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RS RISER

RT RETURN

RWC RAINWATER CONDUCTOR

S

S SOUTH

SC SOLID CORE

SCHED SCHEDULE

SCN SCREEN

SD STORM DRAIN

SEC SECTION

SF SQUARE FEET

SFG SAFETY GLASS

SH SHELF, SHELVING

SHR SHEER

SHT SHEET

SHTG SHEATHING

SHV SHELVES

SI SQUARE INCHES

SIM SIMILAR

OFCI OWNER FURNISHED CONTRACTOR

INSTALLED

OPER OPERABLE

OPNG OPENING

OPP OPPOSITE

OPPHD OPPOSITE HAND

OVHD OVERHEAD

OWJ OPEN-WEB JOIST

P

P, PT PAINT

PAR PARALLEL

PB PANIC BAR

PBD PARTICLE BOARD

PCF POUNDS PER CUBIC FOOT

PED PEDESTAL

PERF PERFORATED

PERIM PERIMETER

PERM PERMANENT

PERP PERPENDICULAR

PFN PREFINISHED

PG PLATE GLASS

PKG PARKING

PL PROPERTY LINE

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLF POUNDS PER LINEAR FOOT

PNL PANEL

PR PAIR

PRCST PRECAST

PREFAB PREFABRICATED

PRELIM PRELIMINARY

PRF PREFORMED

PROJ PROJECT

PRT PROPERTY

PSC PRESTRESSED CONCRETE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PTC POST-TENSIONED CONCRETE

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PTR PAPER TOWEL RECEPTACLE

PWD PLYWOOD

Q

QRT QUARRY TILE

LMS LIMESTONE

LP LIGHT PROOF

LPT LOW POINT

LT LIGHT

LTG LIGHTING

LTL LINTEL

LVR LOUVER

LW LIGHTWEIGHT

M

M.O. MASONRY OPENING

M.R. MOISTURE RESISTANT

MAS MASONRY

MAX MAXIMUM

MBR MEMBER

MC MEDICINE CABINET

MECH MECHANIC(AL)

MED MEDIUM

MEMB MEMBRANE

MET METAL

MEZZ MEZZANINE

MFR MANUFACTURER

MH MANHOLE

MIN MINUTE, MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

MLD MO(U)LDING

MOD MODULAR

MOV MOVABLE

MT MOUNT(ED)(ING)

MTL MATERIAL

MULL MULLION

MWK MILLWORK

N

N NORTH

N/A NOT APPLICABLE

NAT NATURAL

NI NICKEL

NIC NOT IN CONTRACT

NO. NUMBER

NOM NOMINAL

NR NOISE REDUCTION

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER

GST GLAZED STRUCTURAL TILE

GT GROUT

GWB GYPSUM WALL BOARD

GYP GYPSUM

H

HB HOSE BIBB

HBD HARDBOARD

HC HANDICAPPED

HDR HEADER

HDWD HARDWOOD

HDWR HARDWARE

HGT HEIGHT

HJT HEAD JOINT

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HTG HEATING

HTR HEATER

HVAC HEAT, VENTILATION, & AIR CONDITIONING

HWH HOT WATER HEATER

I

ICRA INFECTION CONTROL RISK ASSESSMENT

ID INSIDE DIAMETER

IN INCH

INC INCLUDING

INSUL INSULATE(D)(ION)

INT INTERIOR

INV INVERT

J

JC JANITOR'S CLOSET

JT JOINT

K

KIT KITCHEN

KO KNOCKOUT

KP KICK PLATE

L

LAB LABORATORY

LAD LADDER

LAV LAVATORY

LB POUND

LB LAG BOLT

LBL LABEL

LH LEFT HAND

LL LIVE LOAD

FBO FURNISHED BY OTHERS

FD FLOOR DRAIN

FDN FIRE DEPARTMENT

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FACTORY FINISH

FG FIBERGLASS

FIN FINISH(ED)

FLR FLOOR

FN FENCE

FOB FACE OF BRICK

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FPL FIREPLACE

FR FRAME(D)(ING)

FRA FRESH AIR

FRC FIRE-RESISTANT COATING

FRT FIRE-RETARDANT

FRTW FIRE RETARDANT TREATED WOOD

FT FOOT

FTG FOOTING

FUR FURRED(ING)

FURN FURNITURE

FUT FUTURE

G

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACT(OR)

GCMU GLAZED CONC. MASONRY UNITS

GEN GENERAL

GF GROUND FACE

GKT GASKET(ED)

GL GLASS

GLU LAM GLUE LAMINATED

GOVT GOVERNMENT

GP GALVANIZED PIPE

GPL GYPSUM LATH

GPPL GYPSUM PLASTER

GPT GYPSUM TILE

GRN GRANITE

GS(S) GALVANIZED STEEL (SHEET)

DF DRINKING FOUNTAIN

DH DOUBLE HUNG

DIA DIAMETER

DIM DIMENSION

DL DEAD LOAD

DMT DEMOUNTABLE

DN DOWN

DP DAMP PROOFING

DPR DAMPER

DR DOOR

DRW DRYWALL

DS DOWNSPOUT

DT DRAIN TILE

DTL DETAIL

DW DUMBWAITER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRAWER

E

E EAST

EA. EACH

EF EXHAUST FAN

EIFS EXTERIOR INSULATION & FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSE

EP ELECTRICAL PANELBOARD

EQ EQUAL

EQUIP EQUIPMENT

ESC ESCALATOR

ESMT EASEMENT

EST ESTIMATE

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

F

F/O FACE OF

FAS FASTEN(ER)

FBD FIBERBOARD

CALC CALCULATION

CB CATCH BASIN

CEM CEMENT

CFL COUNTER FLASH(ING)

CFT CUBIC FOOT

CHAM CHAMFER

CI CAST IRON

CIP CAST-IN-PLACE CONCRETE

CIR CIRCLE

CIRC CIRCUMFERENCE

CJ CONTROL JOINT

CK CAULK(ING)

CL CENTER LINE

CLG CEILING

CLR CLEAR

CLS CLOSURE

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

COMPO COMPOSITION

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACT

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CORR CORRIDOR

CPT CARPET

CRS COURSE(S)

CS COUNTERSINK

CSMT CASEMENT

CST CAST STONE

CT CERAMIC TILE

CTRL(S) CONTROL(S)

CYD CUBIC YARD

D

D DRAIN

DA DOUBLE ACTING

DEG DEGREE

DEMO DEMOLISH, DEMOLITION

DEP DEPRESSED

DEPT DEPARTMENT

A/C AIR CONDITIONING

AB ANCHOR BOLT

ABV ABOVE

AC ACOUSTICAL

ACC ACCESS

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADDL ADDITIONAL

ADH ADHESIVE

ADJ ADJUSTABLE, ADJACENT

AFF(A.F.F.) ABOVE FINISH FLOOR

AGG AGGREGATE

ALT ALTERNATE

ANC ANCHOR, ANCHORAGE

ANOD ANODIZED

AP ACCESS PANEL

APX APPROXIMATE

ARCH ARCHITECT(URAL)

ASB ASBESTOS

ASC ABOVE SUSPENDED CEILING

AUTO AUTOMATIC

B

B/O(B.O.) BOTTOM OF

BD BOARD

BELOW BEL

BET BETWEEN

BITUM BITUMINOUS

BLDG BUILDING

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BRG BEARING

BRK BRICK

BS BOTH SIDES

BSMT BASEMENT

BUR BUILT-UP ROOFING

BVL BEVELED

BW BOTH WAYS

C

C-C CENTER TO CENTER

CAB CABINET

ARCHITECTURAL ABBREVIATIONS

1/4" = 1'-0" D5

DOORS & FIXTURES CLEARANCES

1/4" = 1'-0" C1

MOUNTING HEIGHTS

Revisions: Date:

1-SCHEMATIC DESIGN 35% 07/29/2022

2-DESIGN DEVELOPMENT 65% 09/16/2022

3-CONSTRUCTION DOCUMENTS 95% 11/22/2022

4-CONSTRUCTION DOCUMENTS 95% R 12/16/2022

5-CONSTRUCTION DOCUMENTS 100% 01/30/2023

6-CONSTRUCTION DOCUMENTS 100%R 03/20/2023

7-CONSTRUCTION DOCUMENTS 100%R2 04/28/2023

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

n a g e l-d c \C o m p a n y \P ro je c ts

\2

-K a n s a s C it y P

C U

\4

D e s ig n D o c u m e n ts \4

D

M o d e lin g \2

-K a n s a s C it y P

C U

IS

S U

E F

O R

B

ID

.r v t

/2

/2

:2 :4

A

M

G003

BUILDING CODE REVIEW Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

07/11/2023 JH RF,RB

ISSUE FOR BID

FULLY SPRINKLERED

22014

BUILDING CODE REVIEW

hide this column IBC CODE SECTION REQUIRED PROVIDED NFPA 101 SECTION

1 OCCUPANCY OR USE CLASSIFICATION

2 Single Institutional I2 Institutional I2 CHAPTER 6.1 - HEALTHCARE

3 Accessory Occupancy [508.4] N/A N/A N/A

4 Incidental Uses [Table 509] STORAGE - 1HR FIRE BARRIER STORAGE - 1HR FIRE BARRIER [6.1.14.4.1(a)] 1 HR (w/Sprinkler System)

6 SPECIAL DETAIL REQUIREMENTS PER OCCUPANCY

7 Special Applications [Ch 4] N/A N/A CHAPTER 11

8 Occupancy Separations Needed? [Table 508.4] N/A N/A CHAPTER 6.1.14.4

9 High Hazard Class [Section 414] N/A N/A CHAPTER 6.2.2

11 TYPE OF CONSTRUCTION & LIMITS [TABLE 503]

12 Construction Class EXISTING TYPE 1B EXISTING TYPE 1B NFPA 220

13 Allowable Area 33,000 SF 8917 SF N/A

14 Area Increase: Sprinkler N/A N/A N/A

15 Area Increase; Frontage N/A N/A N/A

16 Total Area w/ increases N/A N/A N/A

16.1 Allowable Height EXISTING EXISTING N/A

17 Height Modifications N/A N/A N/A

18 Allowable # of Stories EXISTING EXISTING N/A

20 POSITIONING ON PROPERTY [TABLE 602]

21 Distance to property lines (N, E, S, W) N/A N/A N/A

22 Distance to other buildings N/A N/A N/A

23 Distance to same building N/A N/A N/A

24 Allowable Exterior Wall Openings [705] N/A N/A N/A

26 FIRE SUPPRESSION SYSTEMS

27 Sprinkler Requirement REQUIRED AS REQ'D N/A

28 Alarm & Detection System Requirement REQUIRED AS REQ'D N/A

29 Monitoring Services

30 Standpipe systems Class I in every stairway Per NFPA 14

31 Portable fire extinguishers <75' travel Class A Per NFPA 10 NFPA 10

32 Smoke control systems 909.5.3 Auto closing doors

34 MEANS OF EGRESS PARAMETERS

35 Occupant Load [Table 1004.1.2] - BUSINESS USE 240 GROSS 240 GROSS [Table 7.3.1.2]

36 Required Exit Capacities

37 # of exits required [1006.2.2.1] 2 4

38 Exit width 96" min. SEE PROVIDED EGRESS CHART G101 CHAPTER 7.3.4

39 Exit discharge 1028.2 Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade or shall provide a direct path of egress travel to grade. The exit discharge shall not reenter a building. The combined use of Exceptions 1 and 2 shall not exceed 50 percent of the number and minimum width or required capacity of the required exits.

SEE PROVIDED EGRESS CHART G101 CHAPTER 7.7

40 Door Hardware Requirements Close and fail closed on horizontal exits AS REQ'D CHAPTER 7.2

41 Misc & Special Requirements N/A N/A PER CHAPTER, 11-43

42 Stair Width 44" min. 46" CHAPTER 7.2.2

43 Common path of travel 75' min. SEE COMMON PATH CHART SHEET G101

PER CHAPTER, 11-43

44 Travel distance to Exits 200' sprinklered SEE TRAVEL DISTANCE CHART

SHEET G101

PER CHAPTER, 11-43

45 Stair enclosure EXISTING 2HR EXISTING 2HR CHAPTER 7.2.2.5

46 Vertical openings EXISTING EXISTING

47 Accessible means of egress 50% AS REQ'D CHAPTER 7.5.4

48 Emergency lighting PER NFPA 101 CH.7 SEE ELECTRICAL DWGS CHAPTER 7.8-9

49 Equipment platform [505] N/A N/A

50 Mezzanine w/o sprinkler N/A N/A CHAPTER 8.6.10

52 OTHER ARCHITECTURAL ELEMENTS

53 Roof requirements

54 -Access N/A N/A CHAPTER 7.2.1.5.9

55 -Rails N/A N/A

57 FIRE PERFORMANCE REQUIREMENTS [TABLE 601] NFPA 220 [Table 4.1.1]

58 Columns EXISTING 2 HR EXISTING 2 HR

59 Floor EXISTING 2 HR EXISTING 2 HR

60 Roof N/A N/A

61 Roof Covering N/A N/A

62 Exterior Walls EXISTING 2 HR EXISTING 2 HR

63 Interior Bearing Walls N/A N/A

64 Fire Walls EXISTING 2 HR EXISTING 2 HR

65 Other partitions 0 HR EXISITNG/AS REQ'D

66 Corridors [1020.1] 0 HR 0 HR PER CHAPTER, 11-43

67 Exit passageways 0 HR 0 HR

68 Vertical exit enclosures EXISTING 2 HR EXISTING 2 HR

69 Vertical shafts EXISTING 2 HR EXISTING 2 HR

70 Penthouse Walls N/A N/A

71 Penthouse Roof N/A N/A

72 Storage Rooms 1 HR, SF>100SF /SPRINKLERS 1 HR, SF>100SF /SPRINKLERS

73 Occupancy separations N/A N/A [Table 6.1.14.4.1]

74 Hazardous areas N/A N/A CHAPTER 6.2

75 Accessible means of egress [1009.1.2] REQUIRED / EXISTING REQUIRED / EXISTING

77 SMOKE COMPARTMENT

78 ATTIC REQUIREMENTS N/A N/A

79 -Access N/A N/A

80 -Smoke separations N/A N/A

82 CONSTRUCTION MATERIALS - FINISHES

83 Exit Enclosures & Passageways [Table 803.11] B EXISTING/AS REQ'D

84 Corridors B EXISTING/AS REQ'D

85 Rooms & Enclosed spaces B EXISTING/AS REQ'D

86.1 ENERGY EFFICIENCY REQUIREMENTS

86.1 Energy Conservation: Roof R20ci; Walls R13.3 ci Slab R-10 for 24in below Table 502.2(1)

EXISTING

86.1 Insulation Above Deck N/A N/A N/A

86.1 Walls Above Grade, Wood Framed N/A N/A N/A

86.1 Walls Below Grade N/A N/A N/A

86.1 Floors, Mass EXISTING EXISTING N/A

86.2 Slab-on-grade Floors, Heated N/A N/A N/A

86.3 Opaque Doors N/A N/A N/A

86.4 Vertical Fenestration, Fixed EXISTING EXISTING N/A

86.4 Vertical Fenestration, Operable N/A N/A N/A

86.5 Vertical Fenestration, Entrance Doors N/A N/A N/A

86.5 Skylights N/A N/A N/A

86.5

87 MEP REQUIREMENTS

88 Lighting NATURAL: 8% OF FLOOR SERVED -OR- ARTIFICIAL:

10 FOOT CANDLES OVER AREA AT 30" AFF

AS REQ'D N/A

89 Water Closets 1 PER ROOM 1 PER ROOM N/A

90 Lavatories 1 PER ROOM AS REQ'D N/A

91 Bathtubs/Showers 1 PER 15 1 PER ROOM N/A

92 Drinking Fountains 1 PER 100 1 N/A

93 Other (mop basin) 1 SERVICE SINK 1 N/A

Revisions: Date:

1-SCHEMATIC DESIGN 35% 07/29/2022

2-DESIGN DEVELOPMENT 65% 09/16/2022

3-CONSTRUCTION DOCUMENTS 95% 11/22/2022

4-CONSTRUCTION DOCUMENTS 95% R 12/16/2022

5-CONSTRUCTION DOCUMENTS 100% 01/30/2023

FIRE BARRIER, 1 HR

FIRE BARRIER, 2 HR

SMOKE BARRIER PER IBC 709 & NFPA 101 8.5

BUILDING EXIT

COMMON PATH OF EGRESS TRAVEL

EXISTING EGRESS WIDTH TAG

EXIT ACCESS CORRIDOR

LEGEND - LIFE SAFETY PLAN

EXIT ACCESS TRAVEL DISTANCE

ROOM TAG WITH OCCUPANT LOAD

GROSS AREA BOUNDARY

ROOM NAME

AREA

OCCU TYPE - LOAD

42"

SMOKE COMPARTMENT OR SUITE, AS NOTED

SMOKE PARTITION PER IBC 710 & NFPA 101 8.4

AREA ABOVE OCCUPANCY HAZARD

AREA NOT IN CONTRACT

FE

FIRE EXTINGUISHER CABINET

EXISTING

KEY PLAN - NOT TO SCALE

N O

R T

H

4a4a

7 7

8 8

6a

8a

A

A

B

B

C

C

D

D

E

E

F

F

G

G

H

H H1 J1

J

J

J2

J2

A2

A2

L1

L1

L2

L2

M1

M1

N1

N1

123 SF

NURSE MNG.

OFFICE

M4-357

77 SF

PATIENT

TOILET/SHOWER

M4-355A

149 SF

OFFICE

DOCUMENTATION

M4-360

73 SF

PATIENT

TOILET/SHOWER

M4-356A

164 SF

ISO PATIENT

BEDROOM

M4-356

64 SF

ANTE

ROOM

M4-354

163 SF

ISO PATIENT

BEDROOM

M4-352

164 SF

ISO PATIENT

BEDROOM

M4-355

162 SF

ISO PATIENT

BEDROOM

M4-351

64 SF

ANTE

ROOM

M4-353

77 SF

PATIENT

TOILET/SHOWER

M4-351A

95 SF

SOILED

UTILITY

M4-349

85 SF

H.A.C.

M4-362

899 SF

CORRIDOR

C4-34

206 SF

STERILE

SUPPLY

ROOM

M4-350

98 SF

NOURISHMENT

STATION

M4-348

77 SF

PATIENT

TOILET/SHOWER

M4-352A

194 SF

MSA STATION

M4-342

158 SF

CLEAN

UTILITY ROOM

M4-332

161 SF

PATIENT

BEDROOM

M4-337

158 SF

PATIENT

BEDROOM

M4-335

453 SF

CORRIDOR

C4-32

98 SF

MECHANICAL

ROOM

M4-333

50 SF

LINEN CHUTE

M4-311

333 SF

CORRIDOR

C4-30

64 SF

BIOMED

NETWORK

CLOSET

M4-303

142 SF

MEDICATION

ROOM

M4-306

164 SF

WAITING

ROOM

M4-302

91 SF

PATIENT

TOILET/SHOWER

M4-319A

196 SF

PATIENT

BEDROOM

M4-319

183 SF

PATIENT

BEDROOM

M4-317

91 SF

PATIENT

TOILET/SHOWER

M4-317A

188 SF

PATIENT

BEDROOM

M4-315

91 SF

PATIENT

TOILET/SHOWER

M4-315A

598 SF

CORRIDOR

C4-31

193 SF

EQUIPMENT

STORAGE

M4-359

STAIRWELL

NO. 23

S23

ELEC. CLOSET

M4-331

CORRIDOR

M4-330

MECH. ROOM

M4-303

STAIRWELL

NO. 22

S22

STAIRWELL

NO. 1

S1

ELEC. CLOSET

M4-347

ELEC. CLOSET

M4-345

CORRIDOR

C4-34A

HALLWAY

M4-305

OIT DATA

CLOSET

M4-305A

LOBBY

M4-300

ELEVATOR

E1

ELEVATOR

E2

ELEVATOR

E3

ELEVATOR

E4

STAIRWELL

NO. 2

S2

FREIGHT

ELEVATOR

E5

OFFICE

M4-274

SERVICE

ELEVATOR

E18

INTERIOR

DESIGN

M4-267

CORRIDOR

C4-22

SERVICE

ELEVATOR

E16

SERVICE

ELEVATOR

E17

STAIRWELL

NO. 16

S16

F.E. CLOSET

WORK AREA 1

WORK AREA 3

CRASH

CART RRC-1

HAND WASH 1

68 SF

STAFF TOILET

M4-358

86 SF

PATIENT

TOILET/SHOWER

M4-335A

86 SF

PATIENT

TOILET/SHOWER

M4-337A

42"

42"

42"

42"

46"

FE

FE

FE

FE

FE

PATH 4

P A

T H

PATH 1

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

PATH A

PATH C

P A

T H

D

HAND WASH 3

WORK AREA 2

232 SF

PATIENT

BEDROOM

M4-320

91 SF

PATIENT

TOILET/SHOWER

M4-320A

91 SF

PATIENT

TOILET/SHOWER

M4-318A

185 SF

PATIENT

BEDROOM

M4-318

185 SF

PATIENT

BEDROOM

M4-316

94 SF

PATIENT

TOILET/SHOWER

M4-316A

19 SF

LINEN CLOSET

M4-309

37 SF

WHEELCHAIR

STORAGE

M4-307

277 SF

STAFF

LOUNGE

M4-304

529 SF

MECHANICAL

M4-334

53 SF

PUBLIC

TOILET

M4-302A

54 SF

PUBLIC

TOILET

M4-302B

11 SF

PORTABLE

X-RAY

ALCOVE

C4-34B

S22

S23

S16

S2

9903 SF

MED SURG UNIT

LEGEND - OCCUPANCY TYPE

I2 - HOSPITAL

Calculating...

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

n a g e l-d c \C o m p a n y \P ro je c ts

\2

-K a n s a s C it y P

C U

\4

D e s ig n D o c u m e n ts \4

D

M o d e lin g \2

-K a n s a s C it y P

C U

IS

S U

E F

O R

B

ID

.r v t

/2

/2

:2 :0

A

M

G104

FOURTH FLOOR LIFE SAFETY

PLAN

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

07/11/2023 JH RF,RB,OW

ISSUE FOR BID

FULLY SPRINKLERED

22014

OCCUPANCY BY AREA PER IBC TABLE 1014.1.2 / NFPA 101 TABLE 7.3.1.2

AREA OCCUPANCY

PERSONS

NAME SF TYPE FUNCTION LOAD FACTOR

INST INPATIENT

MED SURG UNIT 9903 SF I2 - HOSPITAL INST INPATIENT 240 42

9903 SF 42

COMMON PATH OF TRAVEL

PATH A

27'-8"

PATH B

20'-4"

PATH C

23'-3"

PATH D

28'-11"

EXIT DISTANCE

PATH 1

74'-9"

PATH 2

113'-0"

PATH 3

47'-6"

PATH 4

124'-3"

PROVIDED EGRESS WIDTH

DOOR NO. EGRESS WIDTH

S2 42"

S16 42"

S22 46"

S23 42"

1/8" = 1'-0" F1

FOURTH FLOOR LIFE SAFETY PLAN 0' 4' 8' 16'

NORTH

1" = 30'-0" E7

FOURTH FLOOR OCCUPANCY PLAN

EXISTING EGRESS DOOR WIDTHS

Revisions: Date:

1-SCHEMATIC DESIGN 35% 07/29/2022

2-DESIGN DEVELOPMENT 65% 09/16/2022

3-CONSTRUCTION DOCUMENTS 95% 11/22/2022

4-CONSTRUCTION DOCUMENTS 95% R 12/16/2022

5-CONSTRUCTION DOCUMENTS 100% 01/30/2023

ACM FLOOR TILE MASTIC

ACM FLOOR TILE

ACM FLOOR TILE & MASTIC

LEGEND - ASBESTOS ABATEMENT PLAN

ACM TERRAZZO

STAIRWELL

NO. 23

S23

W10 EXAM

ROOM

M4-339

TOILET

M4-335A

W8 EXAM

ROOM

M4-335

W11 EXAM

ROOM

M4-338

SHOWER

M4-336A

W0 EXAM

ROOM

M4-336

OFFICE

M4-334TOILET, STAFF

M4-340 HALLWAY

C4-33A

PANTRY

M4-341

MECH. ROOM

M4-333

SOILED

UTILITY

M4-311

ELEC. CLOSET

M4-331

F.E. CLOSET

TOILET

M4-313

R2 EXAM

ROOM

M4-315

STORAGE

M4-314A

R1

TREATMENT

ROOM

M4-314

R4 EXAM

ROOM

M4-317

R3 EXAM

ROOM

M4-316 R5 EXAM

ROOM

M4-318

R6 EXAM

ROOM

M4-319

TOILET

M4-319B

CLOSET

M4-321A

CLOSET

M4-319A

TOILET

M4-321B

CLOSET

M4-318A

TOILET

M4-318B

CLEAN

UTILITY

M4-320

CLOSET

M4-320A

R7 EXAM

ROOM

M4-321

CORRIDOR

M4-330

MECH. ROOM

M4-303 STAIRWELL

NO. 22

S22

CHECK OUT

M4-342

STAFF ONLY

M4-308

STAIRWELL

NO. 1

S1

ELEC. CLOSET

M4-347

ELEC. CLOSET

M4-345

R12 EXAM

ROOM

M4-348

CLOSET

M4-348A

SOILED LINEN

M4-350

R13 EXAM

ROOM

M4-351

R14 EXAM

ROOM

M4-352

TOILET

M4-351A

TOILET

M4-353A

R15 EXAM

ROOM

M4-353

OFFICE

M4-354

R17 EXAM

ROOM

M4-357

R16 EXAM

ROOM

M4-358

TOILET

M4-359A

TOILET

M4-357A

TOILET

M4-358A

TOILET

M4-360A

R18 EXAM

ROOM

M4-360

R19 EXAM

ROOM

M4-359

R21 EXAM

ROOM

M4-363

R20 EXAM

ROOM

M4-362

TOILET

M4-362A

TOILET

M4-364A

TOILET

M4-365A

TOILET

M4-363A

R23 EXAM

ROOM

M4-365

R22 EXAM

ROOM

M4-364

STAIRWELL

NO. 16

S16

CORRIDOR

C4-34A

CORRIDOR

C4-33

CORRIDOR

C4-34

BREAK ROOM

M4-309

HALLWAY

M4-305

BIOMED

NETWORK

CLOSET

M4-305A

CORRIDOR

C4-30

CORRIDOR

C4-32

LOBBY

M4-300

ELEVATOR

E1

ELEVATOR

E2

ELEVATOR

E3

ELEVATOR

E4

STAIRWELL

NO. 2

S2

FREIGHT

ELEVATOR

E5

CLOSET

M4-301

BIOMEDICAL

EQUIPMENT

M4-271

F.E. CLOSET

OFFICE

M4-274

TOILET

M4-252

VESTIBULE

M4-273

SERVICE

ELEVATOR

E18INTERIOR

DESIGN

M4-267

SERVICE

ELEVATOR

E16

SERVICE

ELEVATOR

E17

SERVICE

ELEVATOR

LOBBY

M4-303

CORRIDOR

C4-31F.E. CLOSET

22222

2 2 2 2 2 2

1 1 1 1

1 1 1 1

1 1

3 3

KEY PLAN - NOT TO SCALE

N O

R T

H

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

NOT FOR CONSTRUCTION

H104

FOURTH FLOOR ASBESTOS

ABATEMENT PLAN - FLOORING

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

GAG

FULLY SPRINKLERED

22014

1/8" = 1'-0"

F1

FOURTH FLOOR ASBESTOS ABATEMENT PLAN - FLOORING 0' 4' 8' 16'

NORTH

Revisions: Date:

NOTES

1 ABATE ASBESTOS CONTAINING FLOOR TILE AND/OR MASTIC PER

028211.

2 ABATE ASBESTOS CONTAINING TERRAZZO FLOORING PER 028211.

3 ABATE ASBESTOS CONTAINING TERRAZZO COVE BASE PER 028211

11 JUN 2023

ISSUE FOR BID

RCVCONSTRUCTION DOCUMENTS 95%

CONSTRUCTION DOCUMENTS 95% R

CONSTRUCTION DOCUMENTS 100%

CONSTRUCTION DOCUMENTS 100% R

CONSTRUCTION DOCUMENTS 100% R2

11/22/2022

12/16/2022

01/30/2023

03/20/2023

04/28/2023

130 Pierce Blvd

St. Charles, MO 63301

STAIRWELL

NO. 23

S23

W10 EXAM

ROOM

M4-339

TOILET

M4-335A

W8 EXAM

ROOM

M4-335

W11 EXAM

ROOM

M4-338

SHOWER

M4-336A

W0 EXAM

ROOM

M4-336

OFFICE

M4-334TOILET, STAFF

M4-340 HALLWAY

C4-33A

PANTRY

M4-341

MECH. ROOM

M4-333

SOILED

UTILITY

M4-311

ELEC. CLOSET

M4-331

F.E. CLOSET

TOILET

M4-313

R2 EXAM

ROOM

M4-315

STORAGE

M4-314A

R1

TREATMENT

ROOM

M4-314

R4 EXAM

ROOM

M4-317

R3 EXAM

ROOM

M4-316 R5 EXAM

ROOM

M4-318

R6 EXAM

ROOM

M4-319

TOILET

M4-319B

CLOSET

M4-321A

CLOSET

M4-319A

TOILET

M4-321B

CLOSET

M4-318A

TOILET

M4-318B

CLEAN

UTILITY

M4-320

CLOSET

M4-320A

R7 EXAM

ROOM

M4-321

CORRIDOR

M4-330

MECH. ROOM

M4-303 STAIRWELL

NO. 22

S22

CHECK OUT

M4-342

STAFF ONLY

M4-308

STAIRWELL

NO. 1

S1

ELEC. CLOSET

M4-347

ELEC. CLOSET

M4-345

R12 EXAM

ROOM

M4-348

CLOSET

M4-348A

SOILED LINEN

M4-350

R13 EXAM

ROOM

M4-351

R14 EXAM

ROOM

M4-352

TOILET

M4-351A

TOILET

M4-353A

R15 EXAM

ROOM

M4-353

OFFICE

M4-354

R17 EXAM

ROOM

M4-357

R16 EXAM

ROOM

M4-358

TOILET

M4-359A

TOILET

M4-357A

TOILET

M4-358A

TOILET

M4-360A

R18 EXAM

ROOM

M4-360

R19 EXAM

ROOM

M4-359

R21 EXAM

ROOM

M4-363

R20 EXAM

ROOM

M4-362

TOILET

M4-362A

TOILET

M4-364A

TOILET

M4-365A

TOILET

M4-363A

R23 EXAM

ROOM

M4-365

R22 EXAM

ROOM

M4-364

STAIRWELL

NO. 16

S16

CORRIDOR

C4-34A

CORRIDOR

C4-33

CORRIDOR

C4-34

BREAK ROOM

M4-309

HALLWAY

M4-305

BIOMED

NETWORK

CLOSET

M4-305A

CORRIDOR

C4-30

CORRIDOR

C4-32

LOBBY

M4-300

ELEVATOR

E1

ELEVATOR

E2

ELEVATOR

E3

ELEVATOR

E4

STAIRWELL

NO. 2

S2

FREIGHT

ELEVATOR

E5

CLOSET

M4-301

BIOMEDICAL

EQUIPMENT

M4-271

F.E. CLOSET

OFFICE

M4-274

TOILET

M4-252

VESTIBULE

M4-273

SERVICE

ELEVATOR

E18INTERIOR

DESIGN

M4-267

SERVICE

ELEVATOR

E16

SERVICE

ELEVATOR

E17

SERVICE

ELEVATOR

LOBBY

M4-303

CORRIDOR

C4-31F.E. CLOSET

2 2 2

2 2

2 2 2 2

5 6

5 6

5 6

5 6

5 6 5 6

5 6

5 6 5 6

5 6

5 6

5 6

5 6 5 6

5 6 5 6

5 6 5 6

5 6 5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

5 6

1 4

KEY PLAN - NOT TO SCALE

N O

R T

H

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

NOT FOR CONSTRUCTION

H204

FOURTH FLOOR ASBESTOS

ABATEMENT PLAN - MISCELLANEOUS

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

11 JUN 2023 GAG

FULLY SPRINKLERED

22014

1/8" = 1'-0"

F1

FOURTH FLOOR ASBESTOS ABATEMENT PLAN - MISCELLANEOUS 0' 4' 8' 16'

NORTH

Revisions: Date:

NOTES

1 ABATE PRESUMED ACM FIRE DOOR PER 028211

2 ABATE ACM STEAM CONVECTOR TRANSITE PANEL AND

PRESUMED ACM GASKET PER 028211

3 ABATE SINK SOUNDPROOFING PER 028211

4 ABATE STAIRWELL DOOR CAULK PER 028211

5 ABATE PLASTER TO GLAZE BLOCK STRUCTURAL CAULK PER

028211

6 TAR COATING ON EXTERIOR CONCRETE WALLS TO REMAIN

ISSUE FOR BID

RCVCONSTRUCTION DOCUMENTS 95%

CONSTRUCTION DOCUMENTS 95% R

CONSTRUCTION DOCUMENTS 100%

CONSTRUCTION DOCUMENTS 100% R

CONSTRUCTION DOCUMENTS 100% R2

11/22/2022

12/16/2022

01/30/2023

03/20/2023

04/28/2023

LEGEND - ASBESTOS ABATEMENT PLAN

ACM - TSI

ACM VERTICAL TSI

KEY PLAN - NOT TO SCALE

N O

R T

H

STAIRWELL

NO. 23

S23

W10 EXAM

ROOM

M4-339

TOILET

M4-335A

W8 EXAM

ROOM

M4-335

W11 EXAM

ROOM

M4-338

SHOWER

M4-336A

W0 EXAM

ROOM

M4-336

OFFICE

M4-334TOILET, STAFF

M4-340 HALLWAY

C4-33A

PANTRY

M4-341

MECH. ROOM

M4-333

SOILED

UTILITY

M4-311

ELEC. CLOSET

M4-331

F.E. CLOSET

TOILET

M4-313

R2 EXAM

ROOM

M4-315

STORAGE

M4-314A

R1

TREATMENT

ROOM

M4-314

R4 EXAM

ROOM

M4-317

R3 EXAM

ROOM

M4-316 R5 EXAM

ROOM

M4-318

R6 EXAM

ROOM

M4-319

TOILET

M4-319B

CLOSET

M4-321A

CLOSET

M4-319A

TOILET

M4-321B

CLOSET

M4-318A

TOILET

M4-318B

CLEAN

UTILITY

M4-320

CLOSET

M4-320A

R7 EXAM

ROOM

M4-321

CORRIDOR

M4-330

MECH. ROOM

M4-303 STAIRWELL

NO. 22

S22

CHECK OUT

M4-342

STAFF ONLY

M4-308

STAIRWELL

NO. 1

S1

ELEC. CLOSET

M4-347

ELEC. CLOSET

M4-345

R12 EXAM

ROOM

M4-348

CLOSET

M4-348A

SOILED LINEN

M4-350

R13 EXAM

ROOM

M4-351

R14 EXAM

ROOM

M4-352

TOILET

M4-351A

TOILET

M4-353A

R15 EXAM

ROOM

M4-353

OFFICE

M4-354

R17 EXAM

ROOM

M4-357

R16 EXAM

ROOM

M4-358

TOILET

M4-359A

TOILET

M4-357A

TOILET

M4-358A

TOILET

M4-360A

R18 EXAM

ROOM

M4-360

R19 EXAM

ROOM

M4-359

R21 EXAM

ROOM

M4-363

R20 EXAM

ROOM

M4-362

TOILET

M4-362A

TOILET

M4-364A

TOILET

M4-365A

TOILET

M4-363A

R23 EXAM

ROOM

M4-365

R22 EXAM

ROOM

M4-364

STAIRWELL

NO. 16

S16

CORRIDOR

C4-34A

CORRIDOR

C4-33

CORRIDOR

C4-34

BREAK ROOM

M4-309

HALLWAY

M4-305

BIOMED

NETWORK

CLOSET

M4-305A

CORRIDOR

C4-30

CORRIDOR

C4-32

LOBBY

M4-300

ELEVATOR

E1

ELEVATOR

E2

ELEVATOR

E3

ELEVATOR

E4

STAIRWELL

NO. 2

S2

FREIGHT

ELEVATOR

E5

CLOSET

M4-301

BIOMEDICAL

EQUIPMENT

M4-271

F.E. CLOSET

OFFICE

M4-274

TOILET

M4-252

VESTIBULE

M4-273

SERVICE

ELEVATOR

E18INTERIOR

DESIGN

M4-267

SERVICE

ELEVATOR

E16

SERVICE

ELEVATOR

E17

SERVICE

ELEVATOR

LOBBY

M4-303

CORRIDOR

C4-31F.E. CLOSET

1 2 3

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

NOT FOR CONSTRUCTION

H304

FOURTH FLOOR ASBESTOS

ABATEMENT PLAN - TSI

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

GAG RCV

FULLY SPRINKLERED

22014

1/8" = 1'-0"

F1

FOURTH FLOOR ASBESTOS ABATEMENT PLAN - TSI 0' 4' 8' 16'

NORTH

Revisions: Date:

NOTES

1 ABATE ASBESTOS CONTAINING PIPE INSULATION AND FITTINGS

USING GLOVEBAG METHODS PER 028213.13

2 ABATE ASBESTOS CONTAINING MASTIC ON METAL PIPES AND CONDUIT

USING GLOVEBAG METHODS PER 028213.13

3 ABATE ASBESTOS CONTAINING DUCT SEAM SEALANT USING

GLOVEBAG METHODS PER 028213.13

11 JUN 2023

ISSUE FOR BID

CONSTRUCTION DOCUMENTS 95% 11/22/2022

CONSTRUCTION DOCUMENTS 95% R 12/16/2022

CONSTRUCTION DOCUMENTS 100% 01/30/2023

03/20/2023

04/28/2023

CONSTRUCTION DOCUMENTS 100% R

CONSTRUCTION DOCUMENTS 100% R2

S23

W10 EXAM

ROOM

M4-339

TOILET

M4-335A

W8 EXAM

ROOM

M4-335

W11 EXAM

ROOM

M4-338

SHOWER

M4-336A

W0 EXAM

ROOM

M4-336

OFFICE

M4-334TOILET, STAFF

M4-340 HALLWAY

C4-33A

PANTRY

M4-341

MECH. ROOM

M4-333

SOILED

UTILITY

M4-311

ELEC. CLOSET

M4-331

F.E. CLOSET

TOILET

M4-313

R2 EXAM

ROOM

M4-315

STORAGE

M4-314A

R1

TREATMENT

ROOM

M4-314

R4 EXAM

ROOM

M4-317

R3 EXAM

ROOM

M4-316 R5 EXAM

ROOM

M4-318

R6 EXAM

ROOM

M4-319

TOILET

M4-319B

CLOSET

M4-321A

CLOSET

M4-319A

TOILET

M4-321B

CLOSET

M4-318A

TOILET

M4-318B

CLEAN

UTILITY

M4-320

CLOSET

M4-320A

R7 EXAM

ROOM

M4-321

CORRIDOR

M4-330

MECH. ROOM

M4-303 STAIRWELL

NO. 22

S22

CHECK OUT

M4-342

STAFF ONLY

M4-308

STAIRWELL

NO. 1

S1

ELEC. CLOSET

M4-347

ELEC. CLOSET

M4-345

R12 EXAM

ROOM

M4-348

CLOSET

M4-348A

SOILED LINEN

M4-350

R13 EXAM

ROOM

M4-351

R14 EXAM

ROOM

M4-352

TOILET

M4-351A

TOILET

M4-353A

R15 EXAM

ROOM

M4-353

OFFICE

M4-354

R17 EXAM

ROOM

M4-357

R16 EXAM

ROOM

M4-358

TOILET

M4-359A

TOILET

M4-357A

TOILET

M4-358A

TOILET

M4-360A

R18 EXAM

ROOM

M4-360

R19 EXAM

ROOM

M4-359

R21 EXAM

ROOM

M4-363

R20 EXAM

ROOM

M4-362

TOILET

M4-362A

TOILET

M4-364A

TOILET

M4-365A

TOILET

M4-363A

R23 EXAM

ROOM

M4-365

R22 EXAM

ROOM

M4-364

STAIRWELL

NO. 16

S16

CORRIDOR

C4-34A

CORRIDOR

C4-33

CORRIDOR

C4-34

BREAK ROOM

M4-309

HALLWAY

M4-305

BIOMED

NETWORK

CLOSET

M4-305A

CORRIDOR

C4-30

CORRIDOR

C4-32

LOBBY

M4-300

ELEVATOR

E1

ELEVATOR

E2

ELEVATOR

E3

ELEVATOR

E4

STAIRWELL

NO. 2

S2

FREIGHT

ELEVATOR

E5

CLOSET

M4-301

BIOMEDICAL

EQUIPMENT

M4-271

F.E. CLOSET

OFFICE

M4-274

TOILET

M4-252

VESTIBULE

M4-273

SERVICE

ELEVATOR

E18INTERIOR

DESIGN

M4-267

SERVICE

ELEVATOR

E16

SERVICE

ELEVATOR

E17

SERVICE

ELEVATOR

LOBBY

M4-303

CORRIDOR

C4-31F.E. CLOSET

LEGEND - MOLD ABATEMENT PLAN

TAN CERAMIC WALL TILE

WHITE GLAZED TUB

GREEN GLAZED CERAMIC WALL BLOCK

KEY PLAN - NOT TO SCALE

N O

R T

H

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

NOT FOR CONSTRUCTIONC

U s e r s r y a n b D o c u m e n t s K a n s a s

C i t y

P

C U

R y a n b o u r l a n d r v t

P

M

H404

FOURTH FLOOR ASBESTOS

ABATEMENT PLAN - LBP

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

RCV

FULLY SPRINKLERED

22014

1/8" = 1'-0"

F1

FOURTH FLOOR ASBESTOS ABATEMENT PLAN - LBP 0' 4' 8' 16'

NORTH

Revisions: Date:

11 JUN 2023

ISSUE FOR BID

CONSTRUCTION DOCUMENTS 95%

CONSTRUCTION DOCUMENTS 95% R

CONSTRUCTION DOCUMENTS 100%

CONSTRUCTION DOCUMENTS 100% R

CONSTRUCTION DOCUMENTS 100% R2

11/22/2022

12/16/2022

01/30/2023

03/20/2023

04/28/2023

130 Pierce Blvd

GAG

7 7

8 8

4a

N1M1L2L1J2

J

J

H

H

G

G

F

F

EDCBA2A

8a

6a

J1H1

1 1

13890 bishops drive, suite 250 brookfield, wi 53005

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NAGEL

project number:

NOT FOR CONSTRUCTIONB

IM

/1

.0

V A

K C

R e n o v a te

E f o r P

C U

/M E

P

.0 V

A K

C R e n o v a te

E f o r P

C U

C

.r v t

/7

/2

:4

:2

P

M

P103

THIRD FLOOR PLUMBING

DEMOLITION PLAN

Renovate 4E for Progressive Care Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

June 11, 2023 BEH CSB

ISSUE FOR BID

589-22-420

1600 BALTIMORE

SUITE 300

KANSAS CITY, MO 64108

P: 816.842.8437 www.imegcorp.com

Missouri Certificate of Authority #F001325536

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2022 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #18001588.06

KEYED NOTES:

1.

SHEET NOTES:

1. SEE SHEET P000 FOR SYMBOLS, ABBREVIATIONS AND

GENERAL NOTES.

2. PLUMBING FIXTURES AND ARCHITECTURAL FLOOR PLAN

ON THIS SHEET ARE FOR THE FOURTH FLOOR AND ARE

FOR REFERENCE.

Revisions: Date:

ABATE ASBESTOS CONTAINING PIPE INSULATION AND

FITTINGS USING GLOVEBAG METHODS PER 028213.13

AS REQUIRED TO FACILITATE FOURTH FLOOR

DEMOLITION. QUANTITIES SHOWN IN SPECIFICATION.

1/8" = 1'-0"

F1

THIRD FLOOR ABATEMENT PLAN

0' 4' 8' 16'

NORTH

130 Pierce Blvd

St. Charles, MO 63301

H4045

ABATEMENT PLAN

KEY PLAN - NOT TO SCALE

N O

R T

H

FULLY SPRINKLERED

13100 watertown plank road suite 200 elm grove, wi 53122

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Nagel Architects + Engineers project number:

NOT FOR CONSTRUCTION

Calibre Engineering, Inc.

9090 South Ridgeline Boulevard, Suite 105 Highlands Ranch, CO 80129 (303) 730−0434 www.calibre−engineering.com Civil | Structural | Security

B

IM

/K

C V

A M

C

E R e n o v a tio n /K

C

E R

E N

O V

A T

IO

N

V

S

T R

U C

T U

R A

L C

E N

T R

A L

.r v t

/1

/2

:4

:3

A

M

S001

GENERAL STRUCTURAL NOTES,

DESIGN LOADS & ABBREVIATIONS

Renovate 4E for Progressive Care

Unit

4801 Linwood Blvd, Kansas City, MO, 64128

589-22-420

ES EM

FULLY SPRINKLERED

22014Revisions: Date:

INT INTERIOR

JST JOIST

JT JOINT

K, KIPS THOUSAND POUNDS

KLF KIPS PER LINEAR FOOT

KSF KIPS PER SQUARE FOOT

L LENGTH, ANGLE

LB POUND

LF LINEAR FOOT

LG LONG, LIGHT GUAGE

LL LIVE LOAD

LLH LONG LEG HORIZONTAL

LLR ROOF LIVE LOAD

LLV LONG LEG VERTICAL

LOC LOCATE, LOCATION

LONG LONGITUDINAL

LW LIGHT WEIGHT

MAS MASONRY

MAX MAXIMUM

MB MACHINE BOLT

MBR MEMBER

MECH MECHANICAL

MED MEDIUM

MEZZ MEZZANINE

MF MOMENT FRAM

MFG MANUFACTURING

MID MIDDLE

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY, MODIFIED

MPH MILES PER HOUR

MRF MANUFACTURER

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NS NEAR SIDE

NTS NOT TO SCALE

NW NORMAL WEIGHT

OC ON CENTER

OD OUTSIDE DIAMETER

OH OPPOSITE HAND, OVERHEAD

OPP OPPOSITE

OSB ORIENTED STRAND BOARD

OWSJ OPEN WEB STEEL JOIST

P/C PIN CONNECTED

PAF POWDER ACCUATED FASTENER

PAR PARALLEL

PCC PRECAST CONCRETE

PCF POUNDS PER CUBIC FOOT

PERIM PERIMETER

PL PLATE

PLUMB PLUMBING

PLYWD PLYWOOD

PNL PANEL

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED, POINT, PRETENSIONED

REINF REINFORCING, REINFORCED

REQ REQUIRED

RET RETURN, RETAINING

REV REVISION, REVISED

RF ROOF

RFT RAFTERS

RS ROUGH SAWN

RT ROOF TRUSS

S SECTION MODULUS

SC SLIP CRITICAL

SCHED SCHEDULE

SDC SEISMIC DESIGN CATEGORY

SDI STEEL DECK INSTITUTE

SECT SECTION

SEIS SEISMIC

SEOR STRUCTURAL ENGINEER OF RECORD

SEP SEPARATION

SF SQUARE FEET

SHT SHEET

SIM SIMILAR

SJI STEEL JOIST INSTITUTE

SL SNOW LOAD

SMS SHEET METAL SCREW

SPEC(S) SPECIFICATION(S)

SPRT SUPPORT

SQ SQUARE

SS STAINLESS STEEL

ST SNUG TIGHT

STD STANDARD

STIF/STIFF STIFFENER

STL STEEL

STRUCT STRUCTURAL, STRUCTURE

SUSP SUSPENDED

SYM SYMMETRICAL

T&B TOP AND BOTTOM

TGB TOP OF GRADE BEAM

THK THICK, THICKNESS

TL TOTAL LOAD

TN TOE NAIL

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOF TOP OF FOOTING

TOS TOP OF STEEL

TOW TOP OF WALL

TYP TYPICAL

UFC UNITED FACILITES CRITERIA

UON UNLESS OTHERWISE NOTED

V SHEAR

VB VAPOR BARRIER

VERT VERTICAL

VIF VIF

W WIDTH, WEST, WIDE FLANGE

W/ WITH

W/C WATER CONTENT

W/O WITHOUT

WL WIND LOAD

WPT WORKING POINT

WWF WELDED WIRE FABRIC

WWM WELDED WIRE MESH

x, * BY, TIMES

# NUMBER

& AND

@ AT

A/E ARCHITECT / ENGINEER

AB ANCHOR BOLT

ACI AMERICAN CONCRETE INSTITUTE

ADDL ADDITIONAL

ADJ ADJACENT

AFF ABOVE FINISEHD FLOOR

AGG AGGREGATE

AH, AHU AIR HANDLING UNIT

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

ALT ALTERNATE

APA AMERICAN PLYWOOD ASSOCIATION

APPROX APPROXIMATELY

ARCH ARCHITECTURAL

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

AT/FP ANTI-TERRORISM/ FORCE PROTECTION

AWS AMERICAN WELDING SOCIETY

BET BETWEEN

BLDG BUILDING

BLW BELOW

BM BEAM

BN BOUNDARY NAIL

BOF BOTTOM OF FOOTING

BOS BOTTOM OF STEEL

BOT BOTTOM

BRG BEARING

BTWN BETWEEN

C CHANNEL

CD CONSTRUCTION DOCUMENTS

CE CARBON EQUIVALENT

CENT CENTERED

CFMF COLD-FORMED METAL FRAMING

CFS COLD-FORMED STEEL

CIP CAST IN PLACE

CJ CONTROL JOINT/CEILING JOIST

CJP COMPLETE JOINT PENETRATION

CL CENTERLINE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

CONC CONCRETE

COND CONDITION

CONN CONNECT, CONNECTION

CONST CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CORNER, CONTRACTING OFFICER'S REPRESENTATIVE

CTR CENTER

CU FT CUBIC FEET

D DEEP, DEPTH

DAS DEFORMED ANCHOR STUD

DBL DOUBLE

DEG DEGREE

DEMO DEMOLISH, DEMOLITION

DEP DEPRESSED

DIA, Ø DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DIR DIRECTION

DL DEAD LOAD

DO DITTO

DT DRAG TRUSS

DTL DETAIL

DWG(S) DRAWINGS

DWL DOWEL

EA EACH

EF EACH FACE

ELEC ELECTRICAL

ELEV ELEVATION

EN EDGE NAIL

EOR ENGINEER OF RECORD

EQ, = EQUAL, EQUALS

EQN EQUATION

EQUIP EQUIPMENT

ES EACH SIDE

EW EACH WAY

EXIST, (E) EXISTING

EXP EXPANSION

EXT EXTERNAL, EXTERIOR

FF FAR FACE, FINISH FACE

FFE FINISH FLOOR ELEVATION

FG FINISH GRADE

FJ FLOOR JOIST

FN FIELD NAIL

FND FOUNDATION

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FOS FACE OF STUD

FRMG FRAMING

FS FAR SIDE

FT, ' FOOT

FTG FOOTING

Fy YIELD STRESS

GA GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GLB GLUED LAMINATED BEAM

GT GIRDER TRUSS

GUSS GUSSET

GYP BD GYPSUM BOARD

HAS HEADED ANCHOR STUD

HD HOLD DOWN

HDR HEADER

HGR HANGER

HK HOOK

HORIZ HORIZONTAL

HP HIGH POINT

HSS HOLLOW STRUCTURAL SECTION

HT HEIGHT

HVAC HEATNG/ VENTILATING/ AIR CONDITIONING

I MOMENT OF INERTIA

IBC INTERNATIONAL BUILDING CODE

ICF INSULATED CONCRETE FORM

ID INSIDE DIAMETER

IN, " INCH

INCL INCLUDE

INFO INFORMATION

INS INSULATED, INSULATION

STRUCTURAL ABBREVIATIONS

STRUCTURAL SHEET INDEX

SHEET

NUMBER SHEET NAME

S001 GENERAL STRUCTURAL NOTES, DESIGN LOADS &

ABBREVIATIONS

S002 QA NOTES AND TABLES

S104 FOURTH FLOOR FRAMING PLAN

S501 TYPICAL STRUCTURAL DETAILS

CODE AND DESIGN CRITERIA

1. BUILDING CODES:

a. LATEST EDITION OF U.S. DEPARTMENT OF VETERANS AFFAIRS DESIGN GUIDES, STANDARDS AND

MANUALS

b. INTERNATIONAL BUILDING CODE (IBC) - 2021

c. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC), STEEL CONSTRUCTION MANUAL - 15th

EDITION

d. AISC, SEISMIC DESIGN MANUAL - 3rd EDITION

e. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) 7, MINIMUM DESIGN LOADS AND ASSOCIATED

CRITERIA FOR BUILDINGS AND OTHER STRUCTURES - 2016

f. AMERICAN CONCRETE INSTITUTE (ACI) 318, BUILDING CODE REQUIREMENTS FOR STRUCTURAL

CONCRETE - 2019

2. DESIGN CRITERIA

a. RISK CATEGORY: IV

3. DESIGN LOADS

a. FLOOR

1. SUPERIMPOSED DEAD LOAD: 10 PSF

2. LIVE LOAD: MATCH EXISTING

4. WIND DESIGN DATA

a. BASIC WIND SPEED: 122 MPH (ULTIMATE) 95 MPH (ALLOWABLE)

b. EXPOSURE: B

c. SURFACE ROUGHNESS: B

d. INTERNAL PRESSURE COEFFICIENT (GCpi): ± 0.18

e. DESIGN WIND PRESSURES FOR COMPONENTS AND CLADDING DESIGNED BY THE CONTRACTOR:

1. LISTED PRESSURES ARE INCLUDED FOR REFERENCE ONLY BASED ON A TRIBUTARY AREA OF

10 SF. FINAL CALCULATIONS SHALL BE COMPLETED BY THE CONTRACTOR.

2. EDGE ZONE a = 10’

3. WALL PRESSURES

1. INTERIOR ZONE (4) = -33 PSF, +33 PSF

2. CORNER ZONE (5) = -61 PSF, +33 PSF

4. ROOF PRESSURES

1. POSITIVE ALL ZONES = 16 PSF

2. INTERIOR ZONE 1 = -48 PSF

3. EDGE ZONE 2 = -67 PSF

4. CORNER ZONE 3 = -92 PSF

5. SEISMIC DESIGN DATA

a. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE

b. SEISMIC IMPORTANCE FACTOR (Ie): 1.5

c. Ss: 0.096g

d. S1: 0.069g

e. SITE CLASS: D

f. Sds: 0.110g

g. Sd1: 0.110g

h. SEISMIC DESIGN CATEGORY: C

i. SEISMIC FORCE RESISTING SYSTEM: ORDINARY REINFORCED CONCRETE SHEAR WALLS

GENERAL NOTES

1. THE PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS.

2. THE CONTRACTOR SHALL EXAMINE THE STRUCTURAL DRAWINGS, ARCHITECTURAL DRAWINGS, AND

EXISTING CONDITIONS/DIMENSIONS. THE CONTRACTOR SHALL NOTIFY THE COR OF ANY

DISCREPANCIES BEFORE PROCEEDING WITH ANY WORK.

3. THE DRAWINGS AND SPECIFICATIONS REPRESENT THE COMPLETED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES AND

MEANS NECESSARY TO PROTECT PERSONS AND STRUCTURES DURING CONSTRUCTION. SUCH

MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING, ETC. OBSERVATION BY THE

ARCHITECT, ENGINEER OR COR DOES NOT INCLUDE REVIEW OF THESE MEASURES.

4. NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS TAKE PRECEDENCE OVER GENERAL NOTES.

TYPICAL DETAILS SHALL BE USED WHENEVER APPLICABLE. REFER TO SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

5. ALL WORK NOT DETAILED OR NOTED SHALL BE CONSTRUCTED IN ACCORDANCE WITH OTHER SIMILAR

WORK SHOWN ON THE DRAWINGS AND TYPICAL DETAILS.

6. DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES.

7. NO PIPES OR DUCTS SHALL BE PLACED IN OR PENETRATE STRUCTURAL MEMBERS UNLESS

SPECIFICALLY DESIGNED AND DETAILED.

8. STRUCTURAL DRAWINGS TO BE USED IN CONJUNCTION WITH ARCHITECTURAL, MECHANICAL,

PLUMBING, ELECTRICAL, AND CIVIL DRAWINGS HEREIN.

9. REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:

a. SIZE AND LOCATION OF DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED.

b. SIZE AND LOCATION OF INTERIOR AND EXTERIOR NONBEARING PARTITIONS.

c. SIZE AND LOCATION OF CURBS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, CHANGES IN LEVEL, RAMPS, CHAMFERS, GROOVES, INSERTS, ETC.

d. SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS, IF NOT DIMENSIONED ON THESE DRAWINGS.

e. FLOOR AND ROOF FINISHES.

f. STAIR FRAMING AND DETAILS, EXCEPT AS NOTED.

g. DIMENSIONS NOT SHOWN ON STRUCT DWGS.

10. REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:

a. PIPE RUNS, SLEEVES, HANGERS, EQUIPMENT, SLAB OPENINGS, NOT SHOWN OR NOTED ON

STRUCTURAL DRAWINGS

b. ELECTRICAL CONDUIT, BOXES, OUTLETS.

c. CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL, AND PLUMBING FIXTURES.

d. SIZE AND LOCATION OF MACHINE AND EQUIPMENT BASES. CONTRACTOR'S ENGINEER SHALL

DESIGN SEISMIC ANCHORAGE FOR MECHANICAL AND ELECTRICAL EQUIPMENT PER SPEC.

11. ASTM REFERENCES ARE FOR LATEST REVISIONS AND ISSUE, UON.

12. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON STRUCTURAL FRAME SUCH THAT THE

LOADING DOES NOT EXCEED THE DESIGN LIVE LOADS. PROVIDE SHORING AND BRACING WHERE

DESIGN STRENGTH HAS NOT BEEN ATTAINED OR STRUCTURE IS NOT COMPLETE.

13. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE RESPONSIBILITY FOR, CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, FOR THE ACT OF

OMISSIONS OF THE CONTRACTOR,…