Drawings II.pdf

PDF 26 MB Posted

Attached to
Z1DA--MINOR-CONST 528-811 CONSOLIDATE PRIMARY CARE 1st FLOOR PHASE 1
Solicitation number
36C24224R0080
Issued by

About this file

The provided document is a set of drawings, titled "Drawings II.pdf", related to a federal contract opportunity with Solicitation Number 36C24224R0080, titled "Z1DA--MINOR-CONST 528-811 CONSOLIDATE PRIMARY CARE 1st FLOOR PHASE 1". The contract opportunity is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 (VISN 2), a civilian federal agency. The contract involves minor construction work to consolidate primary care on the first floor, Phase 1. The document does not provide detailed information about the required products or services, response dates, award dates, pricing terms, set asides, incumbents, or other salient details. It appears to be a set of technical drawings that would be used as part of the solicitation package for this contract opportunity.

View the file

Other files

File Type Posted
528-811_ASPC_Addendum_1_20240530.pdf PDF
36C24224R0080 0004.docx DOCX document
528-811_TripleC-CA-SubmittalLOG and Cutsheet Index.xlsx XLSX spreadsheet
00 41 13.10 - Construction Estimate Breakdown Template.xlsx XLSX spreadsheet
Past Performace Questionaire_PPQ.pdf PDF
PROCEDURES FOR SUBMITTAL OF OFFERS AND PROPOSAL EVALUATION CRITERIA.docx DOCX document
36C24224R0080 0003.docx DOCX document
36C24224R0080 0002.docx DOCX document
36C24224R0080 0001.docx DOCX document
36C24222R0080 Project RFI Questions with Responses 6-07-2024.pdf PDF
Wage Determination.txt TXT text file
Past Performace Questionaire.pdf PDF
Drawings I.pdf PDF
FAR 52.225-2 Buy American Certification.pdf PDF
Specifications.pdf PDF
852.219-77 VA Notice of Limitations on Subcontracting.docx DOCX document
36C24224R0080_1.docx DOCX document
Contractor Projects Form.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXAM 13

157157

EXAM 2

115115

EXAM 11

155155

CLEAN

LINENS

142142

EXAM 8

138138

EXAM 12

156156

EXAM 9

137137

EXAM 3

114114

EXAM 6 SDA

143143

PAT TOILET

116116

MEDICATION

141141

TEAM WORK

D

147147

WORKROOM

169169

STAFF TLT

153153

CIRCULATION

127127

CIRCULATION

154154

CIRCULATION

146146

CIRCULATION

110110

TEAM WORK -

STAFF

165165

HUDDLE

167167

TEAM WORK -

RESIDENTS

168168

CIRCULATION

139139

CIRCULATION

140140

EXAM 7 SDA

144144

PROCEDURE/

BARIATRIC/

SPI/

TELEHEALTH

EXAM

117117

CONSULT 1

152152

CONSULT 2

151151

SOILED

UTILITY

124124

CONSULT 4

149149

CONSULT 3

150150

CONSULT 5

148148

CLEAN LINEN

123123

CIRCULATION

134134

M A

T C

H

LI

N E

S E

E : F

1/ Q

-1

C

110A

5A

7A12

7 15

7A

6A

5A

2A

1A

0A

9A

8A

167166

7A 13

8A

3A 14

4A

A-401

D8

A-401

C4

A-402

E8

A-401

A8

A-401

C8

HT WT

STATION

110C110C

4A

A5145

2 2

ELEC.

126126

ELEC.

125125

ED WAITING

172172

VESTIBULE

145145

ED

RECEPTION

170170

110B

A-401

F3

DED ALT #5

5'-0"

2' -0

A5180

CT020

A5080M

CS010

A5075

A5225M

A5145

A1132 5

C04Q0 C04F0

3' -7

A5180

4'-7"

5'-0"

2' -0

A1132

A5180

A5180 A5145

A5225M

C04F0 A5075 C04Q0

CS010

A5080M

CT020 4

CT020M

C02C0 R6200

A5075A5080M

C04Q0

CS090

A5145

A5180

5'-0"

2' -0

A1132

A5180

A5225M

CT020

A5080M

CS010

A5075

C04Q0 C04F0

3' -2

4'-2"4'-2"

A5180

CT020

A5080M C04Q0

CS010

A5075

A5225M

A1132

2' -0

5'-0"

A5180

A1203

C04F0

P3100 A1067

A5075

A5080M P9051

A5200M

P3100 A5080M

A5075 P2000

A5212

A5075

CS010

A5080M

CT020M

C04Q0

A5212

A5075

CS010

A5080M

CT020M

C04Q0

A52126

A5075

CS010

A5080M

CT020M

C04Q0

A5075

CS010

A5080M

CT020M

C04Q0

CS010

A5080M

CT020M

C04Q0

A5212A5212

A5080M P3100

A5075

P9051

A5200M

A1067

CA021M

CT020

R6200

CA041M

CT020

CA021M

CA021M

F0102M

A1132

A5180

5'-0"

2' -0

A5145

A5180

4'-2"

3' -3

4 4

A5180 A5180

A5180

A1132

CT020

C04Q0

A5080M

CS010

A5075 C04F0

A5225M

A5180

3' -3

4'-2" A5145

5'-0"

4'-3"

3' -3

"A5145

CT020

C04Q0

A5080M

CS010

A5075

C04F0

A5225M

CT020

C04Q0 A5080M

CS010

A5075 C04F0

A5225M

EQ. STOR. -

FUTURE

EXAM 4

113113

A1132

A5180

4'-3"

5'-0"

2' -0

"A5180

A5145

CT020

C04Q0

A5080M

CS010

A5075 C04F0

A5225M

A5180

A1132

5'-0" A5145

CT020

C04Q0

A5080M

CS010

A5075 C04F0

A5225M

A5180 A5180

4'-3" 4'-3"

CT020

C04Q0

A5080M

CS010

A5075 C04F0

A5225M

A5145

A5180

A1132

CT020

C04Q0

A5080M

CS010

A5075 C04F0

A5225M

TEAM WORK

D

147147

U0002

U0002 U0002

U0002

U0002

U0002U0002U0002

F2000

FEC

A5109

A5109

127A 120

FURNITURE, FIXTURE, & EQUIPMENT INDICATORA1000

EQUIPMENT / FURNITURE LEGEND

SHEET NOTES

ARCHITECTURAL SYMBOL LEGEND

PARTITION RATING GRAPHICS:

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE

SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

2 HR FIRE BARRIER

1 HR FIRE BARRIER

SMOKE BARRIER (NON RATED)

NON RATED

VV ITEM - VA SUPPLIED & INSTALLED

VC ITEM - VA SUPPLIED & CONTRACTOR INSTALLED

CC ITEM - CONTRACTOR SUPPLIED & INSTALLED

MATCHLINE

EXISTING WALL OR LOW HEIGHT WALL TO REMAIN

NEW WALL. SEE WALL TYPES

EXISTING GRID

EXISTING DOOR TO REMAIN

NEW GRID15.A

XX WALL TAG XX WINDOW TAG

NEW DOOR AND DOOR TAG

X X

X

AREA OF BID ALTERNATE, ADDITIVE OR DEDUCTIVE

EXISTING DOOR TO REMAIN

SLOPE (ARROW

POINTS DOWN)

X" / 12"

1 : XX

MILLWORK LOCK LOCATION

N

N

FIRST FLOOR

KEY PLAN

D WING

PLAN

NORTH

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536

MES Group 550 North Reo Street Tampa, FL 33609

(813) 289-4700

TRIPLE C THE A&E GROUP

201 E. Jefferson St, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

A u to d e s k D o c s /5

-8

C o n s o lid a te

P ri m a ry

C a re s t

F lo o r

S tr a tt o n V

A M

C /5

-8

.1

-A .r v t

/1

/2

:0

:0

A

M

Q-101D

EQUIPMENT PLAN - FIRST FLOOR - D WING 528-811

BLDG 1

08/10/2023 M .PERKINS K.MACAULAY

ISSUED FOR BIDDING CONSOLIDATE PRIMARY CARE ON

FIRST FLOOR

113 Holland Ave, Albany, NY 12208

1/4" = 1'-0" F1

EQUIPMENT PLAN - FIRST FLOOR - D WING

1 SPACE NOT RENOVATED. REFER TO MEP FOR ADJUSTMENTS TO

INFRASTRUCTURE.

2 REFER TO IF101C AND IF101D FOR FURNITURE INFORMATION. ITEMS SHOWN HERE

ARE CONTRACTOR PROVIDED, CONTRACTOR INSTALLED.

3 ITEM TAGGED IS VV SUPPLIED AND CC INSTALLED, ITEM IS SHOWN ON BOTH

FURNITURE AND EQUIPMENT FOR CLARITY AND COORDINATION.

4 CUBICLE CURTAIN TRACK PROVIDED & INSTALLED BY CONTRACTOR. CURTAINS

ARE PART OF ACTIVATIONS TO BE PROVIDED AND INSTALLED BY THE VA.

5 COORDINATE HEIGHT OF ACCESSORY RAIL WITH OWNER.

6 COORDINATE WITH OWNER FOR TV BRACKET INSTALLATION HEIGHT.

EQUIPMENT KEY - CC/VC ONLY

JSN NAME ACQ/INS

A1030 Locker, 2 Person, Over/Under CC

A1067 Mirror, Float Glass, ADA Accessible CC

A1132 Rail, Accessory Mounting, Length As Required VC

A1203 Lift System, Overhead, Bariatric CC

A4995 Table, Diaper Changing, Wall Mounted CC

A5075 Dispenser, Soap, Disposable CC

A5080M Dispenser, Paper Towel, Plastic, Surface Mounted VC

A5109 Grab Bar, ABA Compliant, SS, 2-Wall, W/C Accessible CC

A5145 Hook, Garment, Double, SS, Surface Mounted CC

A5200M Dispenser, Toilet Tissue, Plastic, 2-Roll, Surface Mntd VC

A5225M Bracket, Dual Computer Monitor, Wall-Mounted VC

C02C0 Cabinet, U/C/B, 1 Shelf, 1 Drawer, 1 DO CC

C04F0 Cabinet, U/C/B, 1 Shelf, 2 Half DR, 2 DO CC

C04Q0 Cabinet, ADA Sink, Wall-Mounted CC

CA021M Cabinet, W/H, 2 Shelf, 1 DO, Non-Sloping Top CC

CA041M Cabinet, W/H, 2 Shelf, 1 DO, Non-Sloping Top CC

CS010 Sink, SS, Single Compartment, 7.5x12x12 ID CC

CS090 Sink, SS, Single Compartment, 7.5x19x16 ID CC

CT020 Countertop, Solid Surface CC

CT020M Countertop, Solid Surface CC

F0102M Cabinet, Distribution, Mail CC

L1200 Cabinet, Specimen, Pass Thru, CRS CC

P1965 Eyewash, Eye/Face, Sink Mounted, Hands-free CC

P2000 Eyewash, Wall Mounted, Hands-Free CC

P3100 Lavatory, Vitreous China, Slab Type CC

P4700 Sink, Mop, Molded Stone CC

P9051 Toilet, Floor Mounted, Siphon Jet CC

R6200 Refrigerator, U/C or F/S, 5 Cu Ft VC

U0002 Recessed PPE Organizer CC

THE ABOVE EQUIPMENT LIST SHOWS ONLY CONTRACTOR

SUPPLIED/CONTRACTOR INSTALLED AND VA SUPPLIED/CONTRACTOR

INSTALLED ITEMS. REFER TO IF SERIES FURNITURE PLANS FOR VA

SUPPLIED/VA INSTALLED ITEMS.

DEDUCTIVE ALTERNATES:

DEDUCT ALTERNATE #1 - DO NOT REFINISH EXISTING ROOF AREAS.

(1,442 SF OF ROOFING)

DEDUCT ALTERNATE #2 - DO NOT EXTEND PNEUMATIC TUBE SYSTEM.

(50LF OF PNEUMATIC TUBE)

DEDUCT ALTERNATE #3 - REDUCE 392 SF - NO RENOVATION OFFICES

NORTH SIDE OF CORRIDOR -- TAKES OUT 1/2 OF BLOOD DRAW AREA

DEDUCT ALTERNATE #4 - REDUCE 340 SF - NO RENOVATION OFFICES

SOUTH SIDE OF CORRIDOR -- TAKES OUT OVERFLOW WAITING

DEDUCT ALTERNATE #5 - REDUCE 500 SF - NO RENOVATION AT

BENEFICIARY TRAVEL -- TAKES OUT 1 PROCEDURE ROOM, 1 EXAM ROOM

ON THIS SHEET: #5

# Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536

MES Group 550 North Reo Street Tampa, FL 33609

(813) 289-4700

TRIPLE C THE A&E GROUP

201 E. Jefferson St, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

A u to d e s k D o c s /5

-8

C o n s o lid a te

P ri m a ry

C a re s t

F lo o r

S tr a tt o n V

A M

C /5

-8

.1

-A .r v t

/1

/2

:0

:1

A

M

Q-601

EQUIPMENT SCHEDULE 528-811

BLDG 1

08/10/2023 M .PERKINS K.MACAULAY

ISSUED FOR BIDDING CONSOLIDATE PRIMARY CARE ON

FIRST FLOOR

113 Holland Ave, Albany, NY 12208

EQUIPMENT LIST (MILSTD 1691)

JSN NAME QTY ACQ/INS

SECTION

NUMBER DESCRIPTION P

LU

M

B

IN

G

E

LE

C

TR

IC

A

L

M E

D

IC

A L

G A

S (N

FP

A

9)

M

IS

C E

LL

A

N E

O U

S G

A S

N O

N -M

E D

IC

A

L G

A S

M

IS

C E

LL

A

N E

O U

S

A1012 Telephone, Wall Mounted, 1 Line 13 VV Telephone, wall mounted, 1 line. - - - - - -

A1014 Telephone, Wall Mounted, 1 Line, With Speaker

1 VV Telephone, wall mounted, 1 line, with speaker. - - - - - -

A1015 Telephone, Desk, Multiple Line 39 VV Telephone, desk, multiple line. - - - - - -

A1030 Locker, 2 Person, Over/Under 20 CC 10 51 00 Two person locker, double tier, 72Hx12Wx15D. This unit includes hooks for coats and hats. Door equipped with safety guard handles. Designed for storage of coats, hats, and other personal belongings. Other width and depths are available.

A1067 Mirror, Float Glass, ADA Accessible 4 CC 10 28 00 A high quality 1/4" polished float glass mirror with a stainless steel frame. Frame holds mirror in a tilted position for accessibility and compliance with ADA requirements. Mirror has a galvanized steel back secured to frame with concealed screws with integral horizontal hanging brackets. Mirror shall be approximately 18" wide and 36" high. Other sizes are available.

A1132 Rail, Accessory Mounting, Length As Required

24 VC 10 28 00 Horizontal equipment mounting rail with lock mounting devices capable of; supporting up to 75 pounds each, being repositioned, and mounting and dismounting of equipment without the use of tools (special tools may be required to unlock adapter that was previously locked to the rail). The rail must be capable of supporting medical equipment and accessories normally found in exam or patient rooms. The rail system must be capable of mounting and dismounting equipment without leaving or creating new holes in the finished surface of the wall. The rail system utilizes a series of mounting plates and adapters specific to the device being mounted to the rail. The plate and adapter rail mounting kit must be specified to match the equipment being mounted to the equipment rail. Contractor shall provide in-wall blocking at all rail locations.

A1203 Lift System, Overhead, Bariatric 1 CC 11 73 00 An overhead ceiling mounted rail system specifically designed for bariatric patient lifting and movement within a patient room. The system will consist of recessed or ceiling mounted primary and secondary rails, lift motor with carriage, patient harness or seat, and a hand controller or control box with charger (other charging options may be available). System will facilitate lifting and movement of patient to and from bed, to stretcher, chair, bathroom or other requirements. Lifting capacity is 1000 pounds. Custom design of track layout by manufacturer is essential to meet individual facility requirements.

- F - - - -

A4995 Table, Diaper Changing, Wall Mounted 1 CC 10 28 00 Wall mounted diaper changing table for use in public restrooms. Unit is a fold down system that folds upward when not in use for minimal intrusion into the room. Changing surface is contoured and has safety belt to insure that an infant will not fall from the table. Table is designed to hold no less than 250 pounds static weight. Closed dimensions are approximately 21" H x 36" W x 5" D. Open dimensions vary according to style.

One system's open dimensions are 15 " high, 32" wide and 19" deep.

A5075 Dispenser, Soap, Disposable 27 CC 10 28 00 Disposable soap dispenser. One-handed dispensing operation. Designed to accommodate disposable soap cartridge and valve.

A5077 Dispenser, Hand Sanitizer, Hands-Free 50 VV A touch free wall-mounted hand sanitizer dispenser. For use throughout a healthcare facility. Unit does not include the sanitizing liquid. Units are battery operated.

A5080M Dispenser, Paper Towel, Plastic, Surface Mounted

27 VC 10 28 00 A surface mounted, plastic, single-fold, paper towel dispenser. Dispenser features: tumbler lock; front hinged at bottom; and refill indicator slot. Minimum capacity 400 single-fold paper towels. For general purpose use throughout the facility.

A surface mounted, satin finish stainless steel, single-fold, paper towel dispenser. Dispenser features: tumbler lock; front hinged at bottom; and refill indicator slot. Minimum capacity 400 single-fold paper towels. For general purpose use throughout the facility.

A5107M Dispenser, Glove, Surgical-Examination 28 VV Examination four glove dispenser box for wall mounting. Fabricated of clear PETG plastic. Hardware not included, A5108 Waste Disposal Unit, Sharps 19 VV A container for collecting and transporting syringes and other sharps for decontamination and disposal.

Available in 2 gallon and 8 gallon with locking rotor. Complies with OSHA regulations for handling sharps.

A5109 Grab Bar, ABA Compliant, SS, 2-Wall, W/C Accessible

4 CC 10 28 00 2-wall toilet stall/room grab bar with concealed mounting flanges and a satin finish stainless steel peened gripping surface.. Snap over flanges are provided to conceal mounting screws. A selection of mounting kits and concealed anchor devices are available from the manufacturers for different types of installations. Grab bar shall comply with all barrier-free accessibility guidelines for design, sizing, positioning, installation, and structural strength. For typical water closet applications in toilet stalls and rooms where Architectural Barriers Act grab bar requirements must be met.

A5145 Hook, Garment, Double, SS, Surface Mounted

43 CC 10 28 00 A surface mounted, satin finish stainless steel, double garment hook. Equipped with a concealed mounting bracket that is secured to a concealed wall plate. For general purpose use throughout the facility to hang various items of apparel.

A5180 Track, Cubicle, Surface Mounted, With Curtain

31 VV 10 21 23 Surface mounted cubicle track, with curtain. Track constructed of thick extruded aluminum. Equipped with self lubricating carriers, beaded drop chain hooks, and flame resistant curtain. To include removable end caps.

Designed to be suspended around patient areas where privacy is needed. Price listed is per foot of the track, curtains to be priced per quote. Track to be provided and installed by contractor. Curtains are part of activations to be provided and installed by the VA.

A5200M Dispenser, Toilet Tissue, Plastic, 2-Roll, Surface Mntd

4 VC 10 28 00 A concealed surface mounted, double roll, plastic, toilet tissue dispenser. Unit accommodates two standard-core toilet tissue rolls through 6" in diameter. Spindles are chrome plated plastic with a heavy-duty internal spring and turn freely for non-controlled delivery. For general purpose use in restrooms.

A5212 Bracket, Television, Wall-Mounted, Tilt/Angle

6 VV A wall mounted, tilt/angled TV bracket for 37" to 80" TVs. Mount will be a universal and VESA compliant unit with a load capacity of up to 130 lbs. Contractor shall provide in wall blocking at all TV mounting bracket locations.

A5225M Bracket, Dual Computer Monitor, Wall-Mounted

14 VC Wall-mounted bracket that supports two LCD computer monitors, or laptop and monitor configuration.

Extends LCD's or labtop up to 25" with an adjustment range of 18". Desk clamp attaches to edge up to 2.6" thick. Maximum combined weight supported not to exceed 50 lbs. Contractor shall provide in-wall blocking at all monitor mounting brackets. Contractor to coordinate installation with VA.

C02C0 Cabinet, U/C/B, 1 Shelf, 1 Drawer, 1 DO 2 CC 12 32 00 Standing height under counter base cabinet with an adjustable shelf and a full width drawer above a solid right or left-hinged door (appropriate door hinge configuration to be indicated on equipment elevation drawings). Also referred to as a combination cabinet or a drawer and cupboard cabinet. For general purpose use throughout the facility.

C04F0 Cabinet, U/C/B, 1 Shelf, 2 Half DR, 2 DO 21 CC 12 32 00 Standing height under counter base cabinet with an adjustable shelf and two half width drawers above solid hinged doors. Also referred to as a combination cabinet or a drawer and cupboard cabinet. For general purpose use throughout the facility.

C04Q0 Cabinet, ADA Sink, Wall-Mounted 23 CC 12 32 00 Wall mounted sink support cabinet for drop-in sink with vertical fascia and angled ADA profile, also referred to as ADA sink cabinet. Removable front panel to permit access to plumbing. Medium density M-3 particle board core construction faced with high pressure vertical grade decorative plastic laminate on exposed surfaces and melamine on semi-exposed and concealed surfaces; plastic laminate edge banding. Includes all attaching hardware including support rail.

CA021M Cabinet, W/H, 2 Shelf, 1 DO, Non-Sloping Top

3 CC 12 32 00 Wall hung cabinet with two adjustable shelves, solid right or left-hinged door (appropriate door hinge configuration to be indicated on equipment elevation drawings).

CA041M Cabinet, W/H, 2 Shelf, 1 DO, Non-Sloping Top

1 CC 12 32 00 Wall hung cabinet with two adjustable shelves, solid right or left-hinged door (appropriate door hinge configuration to be indicated on equipment elevation drawings).

CS010 Sink, SS, Single Compartment, 7.5x12x12 ID

20 CC 22 40 00 Single compartment stainless steel sink, drop-in, self-rimming, ledge-type, connected with a drain and provided with a mixing faucet. It shall also be provided with pre-punched fixture holes on 4" center, integral back ledge to accommodate deck-mounted fixtures, brushed/polished interior and top surfaces, and sound deadened. Recommended for use in suspended or U/C/B sink cabinets having a high plastic laminate or Chemsurf laminate countertop/work surface. For general purpose use throughout the facility.

B - - - - -

CS090 Sink, SS, Single Compartment, 7.5x19x16 ID

2 CC 22 40 00 Single compartment stainless steel sink, drop-in, self-rimming, ledge-type, connected with a drain and provided with a mixing faucet. It shall also be provided with pre-punched fixture holes on 4" center, integral back ledge to accommodate deck-mounted fixtures, brushed/polished interior and top surfaces, and sound deadened. Recommended for use in suspended or U/C/B sink cabinets having a high plastic laminate or Chemsurf laminate countertop/work surface. Coordinate actual outside sink dimensions with the actual clear dimension of cabinet specified to ensure that they are compatible. For general purpose use throughout the facility.

D - - - - -

CT020 Countertop, Solid Surface 32 CC 12 36 00 A solid, nonporous countertop with a smooth seamless appearance. Easy to clean and maintain and with proper cleaning does not support the growth of mold. An acrylic-based solid surface product. Standard thickness of 1", and a 4" butt backsplash/curb. Also referred to as a work surface or work top. Available in a choice of colors and depths. Used in lab and other hospital areas requiring optimum physical and chemical resisting properties.

CT020M Countertop, Solid Surface 8 CC 12 36 00 A solid, nonporous countertop with a smooth seamless appearance. Easy to clean and maintain and with proper cleaning does not support the growth of mold. An acrylic-based solid surface product. Standard thickness of 1", and a 4" butt backsplash/curb. Also referred to as a work surface or work top. Available in a choice of colors and depths. Used in lab and other hospital areas requiring optimum physical and chemical resisting properties.

E0045 Workcenter, Computer, Free Standing, 60" W

34 VV THIS TYPICAL INCLUDES: 1 Tool Rail 2 Paper Tray 1 Diagonal Tray 1 Freestanding Work Surface 1 Mobile Pedestal, Box/File 1 Adjustable Keyboard Tray

E0063 Workstation, L-Shaped w/Peninsula, Wall Mtd, 72x72

5 VV THIS TYPICAL INCLUDES: 3 Vertical Hanging Strips 2 Lockable Flipper Units 2 Shelves, Storage/Display 2 Lights 1 Tackboard 2 Tool Rails 2 Paper Trays 1 Diagonal Tray 1 Cantilevered Work Surface 1 Peninsula Work Surface 1 Adjustable Keyboard Tray 1 Mobile Pedestal, Box/File 1 Pencil Drawer 1 Cpu Holder

- A - - - -

E0915 Locker, Supply, Medication, Wall Mtd, 23"W x 20"D

1 VV THIS TYPICAL INCLUDES: 1 Wall Mounted Rail 1 Locked Storage Container 2 Tray/Shelves 1 Locked Drawer w/Locked Lid, 6"H 5 Drawers, 3"H 3 Drawers, 6"H 2 Tray/Shelves Divider Drawer Organizer Bins Consider the need for an E0921 to transport the locker from place to place.

E0948 Cart, General Storage, Mobile, 42"H x 32"W x 22"D

18 VV THIS TYPICAL INCLUDES: 1 Cart Body, Style-A Narrow, w/Raised Edge Top 2 Drawers, 3" H 4 Drawers, 6" H 1 Accessory Rail, Side Drawer Organizer Bins

F0102M Cabinet, Distribution, Mail 1 CC 12 32 00 Custom millwork mail distribution cabinet. Horizontal style distribution boxes. Unit consists of adjustable horizontal dividers and/or adjustable shelves. Unit can be customized to fit the client needs. Used for mail distribution.

F0205 Chair, Side With Arms 1 VV Upholstered side chair, 32" high X 21" wide X 23" deep with arms, padded seats and padded backs. Seat height is a minimum of 17". Available with or without sled base.

Acquisition Code Responsibility Description CC CFCI Contractor Furnished Contractor Installed.

Equipment purchased and installed by the contractor.

VC GFCI VA Furnished Contractor Installed. Equipment is provided by the Government and installed by the Contractor (used for major imaging and OR equipment).

VV GFGI VA Furnished VA Installed. Equipment purchased and installed by the Government.

L_RE Leased or Rented Other. Equipment leased or rented and installed by the Government.

R GFGI Reuse. These are existing equipment assets that will be transferred and reused and may be a relocation cost associated with them.

RESPONSIBILITY: PLUMBING:

Code Description A Hot and cold water B Cold water and drain C Hot water and drain D Cold and hot water and drain E Treated water and drain F Cold, hot and treated water and drain G Cold and treated water and drain H Hot and treated water and drain I Drain only J Cold water only

ELECTRICAL:

Code Description A 120 volt, conventional outlet B 120 volt, special outlet C 208/220 volt D 120 and 208/220 volt E 440 volt, 3 phase F Special electrical requirements

(includes, but is not limited to emergency power, multiple power connections, etc.)

G 208/220 volt, 3 phase

MEDICAL GAS:

Code Description A Oxygen B Vacuum C Air, low pressure D Air, high pressure E Oxygen and medical air H Oxygen, vacuum and medical air J Vacuum and HP air K Medical air

MISCELLANEOUS GAS:

Code Description A Steam B Nitrogen gas C Nitrous oxide D Nitrogen and nitrous oxide gas E Carbon dioxide gas F Liquid carbon dioxide G Liquid nitrogen H Instrument Air

NON-MEDICAL GAS:

Code Description A Natural gas B Liquid propane gas C Methane D Butane E Propane F Hydrogen gas G Reserved H Acetylene gas

MISCELLANEOUS:

Code Description A Earth ground B Lead lined walls C Remote alarm ground D Empty conduit with pull cord E Vent to atmosphere F Special gas requirements G Liquid gas requirements H RF/Magnetic shielding J Wall/ceiling support required K Empty conduit/pull cord & wall/ceiling support required M Earth ground and wall/ceiling support required P Lead lined walls and wall/ceiling support required T CAT 6 wire to nearest

Telecommunications Room

EQUIPMENT LIST (MILSTD 1691)

JSN NAME QTY ACQ/INS

SECTION

NUMBER DESCRIPTION P

LU

M

B

IN

G

E

LE

C

TR

IC

A

L

M E

D

IC

A L

G A

S (N

FP

A

9)

M

IS

C E

LL

A

N E

O U

S G

A S

N O

N -M

E D

IC

A

L G

A S

M

IS

C E

LL

A

N E

O U

S

F0205 Chair, Side With Arms 37 VV Upholstered side chair, 32" high X 21" wide X 23" deep with arms, padded seats and padded backs. Seat height is a minimum of 17". Available with or without sled base.

F0206 Chair, Side, Bariatric, With Arms 3 VV A bariatric side chair with arms for use in a waiting room, lobby or other patient area. Chair will have a padded seat and back and have a capacity of 800 pounds.

F0220 Chair, Conference 4 VV Conference chair designed to complement the executive furniture package selected. Foam rubber cushioned seats and backs covered with either woven fabric or vinyl. Base with 5 (five) swivel casters.

F0275 Chair, Swivel, High Back 37 VV Highback contemporary swivel chair, 41" high X 23" wide X 23" deep with five (5) caster swivel base and arms. Chair may be used at desks or in conference rooms. Back and seat are foam padded and upholstered with either woven textile fabric or vinyl.

F0300 Chair, Task, Swivel, With Arms 5 VV Task chair, approximately 34" H X 26" W X 22" D with adjustable arms and a five caster adjustable swivel base. Seat and back are foam padded and upholstered in woven fabric or vinyl.

F0340 Stool, Self Adjusting 18 VV Self adjusting stool. Consists of a foam padded upholstered seat with attached foot rest for added comfort.

Mounted on swivel casters. Designed for doctor's use during examinations.

F0421 Pedestal File, Mobile 39 VV A steel mobile pedestal file with three drawers and casters. Choice of finishes, handle style and with or without locking mechanism.

F0515 Cart, Supply, Linen 6 VV Closed linen supply cart. Equipped with four (4) non-marking rubber tire roller bearing casters and heavy duty cover. May be used for the delivery and user storage of clean linen as well as the return of soiled linen.

F0535 Cart, Utility 2 VV Utility cart, 32-39" high X 36" wide X 24" deep, with 4 (four) heavy duty caster wheels. - - - - - -

F0740 Table, Occasional, Lamp 4 VV Occasional lamp table (end table) approximately 20" high X 27" wide X 27" deep with choice of finishes (wood, oak veneer, or high pressure laminate).

F0765 Table, Folding / Nesting 2 VV Mobile table. The unit provides mobile or isolated freestanding work surface. Characteristics and components include 3-1/2 inch casters and attached drawer bearers. Unit is used for general work applications, primarily in dry areas.

F2000 Basket, Wastepaper, Fire Resistant 9 VV Wastepaper basket, fire resistant, approximately 40 quart capacity. This unit is used to collect and temporarily store small quantities of paper refuse in patient rooms, administrative areas and nursing stations. Size and shape varies depending on the application and manufacturer selected.

F2010 Basket, Wastepaper, Step-On 22 VV "Step-on" wastepaper basket with inner liner and foot petal activated flip top. - - - - - -

F2020 Can, Trash, 44 Gallon 2 VV Forty four (44) gallon trash can, 32" high X 24" diameter, with lid. Used to collect and transport refuse from a point of origin to point of disposal (example: from soiled utility or a nursing unit to the trash compactor at housekeeping).

F2310 Rack, Pamphlet, Wall Mounted 12 VV Wall mounted pamphlet rack up to 12 (twelve) pamphlet holding pockets. Unit is used to store and display educational pamphlets.

F3065 Whiteboard/Bulletin Board, Combination 5 VV A combination whiteboard and bulletin board, half LCS and half cork. Available with either aluminum or wood frame. It can be used in patient rooms or in any appropriate space in the facility.

F3200 Clock, Battery, 12" Diameter 13 VV Clock, 12" diameter. Round surface, easy to read numbers with sweep second hand. Wall mounted unit for use when impractical to install a fully synchronized clock system. Battery operated, (batteries not included).

L1200 Cabinet, Specimen, Pass Thru, CRS 2 CC 10 28 00 Pass-through specimen cabinet. The unit has a sight-proof interlocking door that permits only one door to open at a time. It also includes a removable spill tray, corrosion resistant stainless steel welded construction with seamless corners and burr-free edges and is able to adjust to wall thickness between 3-6 inches. Used for passage of specimens from patient area to laboratory.

M0506 Television, Flat Screen 2 VV Flat screen television with approximately 32'" to 40' diagonal screen size. The TV will have built-in speakers, NTSC tuner, a 16:9 wide screen aspect ratio, a minimum of 1280 x 768 resolution and a remote control.

- A - - - -

M1410 Chair, Laboratory, Blood Drawing, w/Storage

5 VV Laboratory blood drawing chair with storage. Chair has built-in storage cabinet(s) and locking arm assembly that may be positioned on either side of the fiberglass chair.

M1801 Computer, Microprocessing, w/Flat Panel Monitor

40 VV Desk top microprocessing computer. The unit shall consist of a central processing mini tower, flat panel monitor, keyboard, mouse and speakers. The system shall have the following minimum characteristics: a 2.8 GHz Pentium processor; 512 MB memory; 80GB hard drive; 32/48x CD-ROMDVD combo; 1.44MB network interface card; video 32 MB NVIDIA; a 18 inch flat panel monitor. The computer is used throughout the facility to input, manipulate and retrieve information.

- A - - - -

M1803 Workstation, Computer, Wall Mounted, Adjustable

1 VV A wall mounted computer workstation with height adjustable monitor and keyboard arms. Keyboard and monitor can be stored within 8" to 10" of wall. Fingertip adjustability for keyboard and monitor enable frequent position changes. Unit contains an integrated cable management system to hide wires. A separate wall-mounted CPU holder is included.

- A - - - -

M1810 Copier, Floor Standing, Digital 1 VV Floor standing copier. Unit features automatic paper size selection, automatic document feeder and sorter.

The system also has zoom capabilities and automatic two-sided copying. For use where medium volume reproduction is required in the range of 30 to 40 copies per minute.

- A - - - -

M1830 Printer, Label, Pharmacy 3 VV Label printer for use in pharmacy applications. The printer shall be bench top standing. It shall be flexible enough to accommodate label sizes up to 4 inches, with a minimum print speed of 6 inches per second and a minimum resolution of 203 dpi.

- A - - - -

M3070 Hamper, Linen, Mobile, w/Lid 2 VV Mobile linen hamper with hand or foot operated lid. Made of heavy tubular stainless steel with heavy gauge welded steel platform. Holds 25" hamper bags. Mounted on ball bearing casters. For linen transport in hospitals and clinics.

M3072 Frame, Infectious Waste Bag w/Lid 4 VV Frame for an infectious waste collection bag. Made of heavy tubular stainless steel with heavy gauge welded steel platform. Adjust to hold 18" or 25" trash bags. Mounted on ball bearing casters and includes permanently mounted hinged lid. Provides means of bagging infectious waste at point of waste generation.

M3150 Distribution System, Medication, Automatic

1 VV An automated dispensing system that provides controlled dispensing, inventory, and security. Size and cost will vary dependent on number of modules selected.

B A - - - -

M4020 Scale, Person Weighing, High Capacity 1 VV High capacity, person weighing scale. Large digital readout displays weight in pounds, or kilograms. Hand rails. Shall be supported by fixed heavy-duty legs in stationary position. Capacity up to 800 pounds. Optional equipment: battery pack with rechargeable batteries and built-in recharger. Designed to weigh large ambulatory patients.

- A - - - -

M4100 Sphygmomanometer, Aneroid, Wall Mounted

13 VV Aneroid sphygmomanometer. Unit is wall mounted and has large graphic dial display for easy reading from all angles. It has a 90 degree (angle) swivel and 10 degree (angle) forward tilt to reduce glare. Unit accuracy is within 1% of reading. Sturdy impact-resistant construction.

M4116 Monitor, Vital Signs 13 VV Electronic sphygmomanometer. LCD displays non-invasive blood pressure, pulse rate and temperature. Used in hospitals and clinics. Includes an optional mobile stand.

- A - - - -

M4200 Otoscope/Ophthalmoscope, Wall Mounted

13 VV Wall mounted otoscope and ophthalmoscope. Includes 6 foot line cord and plug and accepts and includes two handles. Contains head turn-on/turn-off, built-in speculum tray and 8 foot coiled cords. Unit is designed for use in patient exam rooms.

- A - - - -

M4255 Stand, IV, Adjustable 1 VV Adjustable IV stand with 4-hook arrangement. Stand has stainless steel construction with heavy weight base.

It adjusts from 66 inches to 100 inches and is mounted on conductive rubber, ball bearing, swivel casters.

Stand is used for administering intravenous solutions.

M4655 Stretcher, Mobile, CRS, 9 Position 1 VV Mobile stretcher. All corrosion resistant stainless steel construction. It consists of a tubular frame with side rails, a 9-position hydraulic base with pneumatic fowler adjustment, and a 2" pad. Unit is mounted on 8" conductive casters. Designed for patient transport as well as for minor surgical procedures.

M4925 Chair, Exam/Treatment, With Motor 12 VV Exam/treatment chair with motor. Chair is electrically powered and can be positioned for a wide range of procedures. Unit is mounted on a 24"(approx) iron casting base with foot controls on both sides of the chair.

Chair is equipped with footrests and fully adjustable headrest and armrests. It is used in hospitals, clinics, or office settings for examinations, treatments, and minor procedures.

- A - - - -

M7710 Electrocardiograph, 12 Lead, Portable 1 VV Used to detect the electrical signals associated with cardiac activity, diagnose cardiac abnormalities, determine a patients response to drug therapy and reveal trends or changes in heart function. Capable of recording two or more leads simultaneously, recording an entire 12 lead ECG in about 10 seconds. Includes of a 3.5 inch, high density, floppy disk drive for test storage. Portable.

- A - - - -

M8810 Stand, Mayo 1 VV Adjustable instrument table. Table is corrosion resistant stainless steel construction and is mounted on two casters with two skid rails. It has telescopic upright adjusts from 39 inches to 60 inches with automatic locking device, and removable 13"x19" instrument tray. Designed for use in operating and procedure rooms.

P1965 Eyewash, Eye/Face, Sink Mounted, Hands-free

1 CC 22 40 00 A sink mounted eyewash station. The unit is designed for emergency eye and face rinsing from soft flow dual spray-heads. The Flow must be activated by the single momentary action and remain on until terminated.

P2000 Eyewash, Wall Mounted, Hands-Free 1 CC 22 40 00 Wall mounted emergency eye wash station. The flow of water from the unit is activated by hand. Upon initiation of water flow the unit will operate hands free to provide streams of water to clear foreign particles or dilute caustic liquids from the eyes in emergency situations. Used in laboratories and areas of the hospital where employees are subject to foreign bodies or liquid material to the eyes.

B - - - - -

P3100 Lavatory, Vitreous China, Slab Type 5 CC 22 40 00 Wall mounted, slab type, vitreous china, lavatory (approximate bowl size 7"x15"x10") with: faucet holes on 4" centers; gooseneck spout; wrist blade handles; and grid strainer. It shall be suitable for use in clinics, offices, washrooms or patient care area.

D - - - - -

P4700 Sink, Mop, Molded Stone 1 CC 22 40 00 Mop service sink approximately 10"H x 36"W x 24"D. Also called a mop service basin and a mop receptor.

Unit is made of molded stone and is a one piece item. It shall include a service faucet hose, hose bracket and mop hanger. Used in utility rooms for cleaning mops and floor cleaning equipment.

D - - - - -

P9051 Toilet, Floor Mounted, Siphon Jet 4 CC 22 40 00 Siphon jet water closet/ toilet. This unit is floor mounted with an elongated bowl, top spud flushometer, seat with open front and check hinge, and carrier. Height does not include seat. Seat is not included with all vendors. See comments.

B - - - - -

R6200 Refrigerator, U/C or F/S, 5 Cu Ft 2 VC Utility refrigerator approximately 35" H x 24" W x 26" D. The unit has a two tray ice cube cooling system. The refrigerator fits standard architectural dimensions for undercounter installation. The unit is perfect for use in nurses' station, wards, and laboratories, pharmacies or wherever space is limited.

- A - - - -

U0001 Drip tray 44 VV Wall mounted drip plate for installation below soap dispenser and hand sanitizer dispensers - - - - - -

U0002 Recessed PPE Organizer 10 CC 10 28 00 Recessed PPE Organizer, ADA Compliant extends 1 1/4"; Powder Coated Steel featuring latch closure with lock; Approx. 24 3/8"W x 27 5/8"H x 4 3/4"D

# Revisions: Date:

SCALE:

SCALE:

SCALE:

SCALE:

SCALE:

m m

M A

X

NTS

NTS

NTS

NTS

NTS

RETURN BEND ASSEMBLY DETAIL

SPRINKLERS IN GRID CEILING SYSTEMS SHALL BE LOCATED AT THE

MIDPOINT OR QUARTERPOINT OF THE FOUR FOOT (4') DIMENSION AND THE

MIDPOINT OF THE TWO (2') DIMENSION AND SCRIBE CEILING MATERIALS FOR

A TIGHT FIT. WHERE A CONFLICT OCCURS, SYMMETRY ABOUT THE AXIS

SHALL BE MAINTAINED.

E Q

E

Q

EQ.EQ.EQ.EQ.

E Q

E

Q

E Q

E

Q

EQ.EQ.

E Q

E

Q

EQ. EQ.

E Q

E

Q

EQ. EQ.

SPRINKLER

SPEAKER OR

OTHER DEVICE

AIR DEVICE,

LIGHT FIXTURE,

SPEAKER,

OCCUPANCY

SENSOR, ETC.

CEILING LEGEND

SPRINKLER MOUNTING DETAIL

FOR HEAD TYPES,

SEE FLOOR PLANS

AND HEAD DETAILS

1" X 1/2" R.C.

DROP

90 EL.

ARMOVER (NOTE 1)

RISER NIPPLE

BRANCHLINE

SUSPENDED CEILING

NOTE:

1. PROVIDE HANGER FOR ALL ARMOVERS

REGARDLESS OF LENGTH.

NOTE:

1. APPLICABLE TO PENETRATIONS OF

ALL FIRE RATED MEMBRANES, IN

ACCORDANCE WITH NFPA 101. REFER

TO SPECIFICATIONS SECTION 07 84 00,

FIRE STOPPING SYSTEMS.

FLOOR

FIRESTOP MATERIAL

3/4" [19mm] APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

PIPE SLEEVE

WHERE SPECIFIED

1/4" [6.4mm]∅ ANCHOR

ROD FOR NEW

CONSTRUCTION

WELD

[2 m m

[1 m m

[1 m m

FLOOR OR DECK PENETRATION

PARTITION OR CHASE PENETRATION

[150mm] [150mm]

MASONRY

PARTITION

PARTITION SUPPORT

FIRESTOP

MATERIAL

[150mm] [150mm]

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER

DRYWALL PARTITION

6" 6"

6" 6"

SIDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000 LB.] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS

BAND

43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm

[2"X2"X1/4"] ANGLE

15mm [1/2"] DIA.

HANGER RODS WITH

900mm [36"] MAX.

SPACING ON EACH

CHANNEL

SADDLE

HANGER ROD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

NOTE:

SEE SPECIFICATIONS FOR DETAILED

HANGER REQUIREMENTS

mm

[IN]

mm

[FT]

mm

[FT]

THRU 20

[THRU 3/4]

[7]

[5]

[1]

[7]

[6]

[11/4]

[7]

[7]

[11/2]

[9]

[8]

[2]

[10]

[8]

[21/2]

[11]

[9]

[3]

[12]

[10]

[4]

[14]

[12]

[5]

[16]

[13]

[6]

[17]

[14]

[8]

[19]

[16]

[10]

[22]

[12]

[23]

[14]

[25]

[16]

[27]

[18]

[28]

[20]

[30]

[24]

[32]

PIPE HANGER DETAIL

PIPE PENETRATION DETAIL

UNION WITH CORROSION

RESISTANT ORIFICE GIVING FLOW

EQUIVALENT TO THE SMALLEST

SPRINKLER ORIFICE IN THE SYSTEM

TO DRAIN

SYSTEM RISER

AUXILIARY DRAIN

VALVE

SITE GLASS

INSPECTORS TEST VALVE

1" DRAIN LINE

PRESSURE GAUGE

WATER FLOW SWITCH

TO SPRINKLERS

INDICATING TYPE FLOOR

CONTROL VALVE WITH

SUPERVISORY SWITCH

EXISTING FIRE SPRINKLER ZONE

CONTROL VALVE PIPING DETAIL

A. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS

INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE

TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS

ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED

AND NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. CONTRACTOR

SHALL REVIEW COVERAGE OF TEMPORARY UPRIGHT SPRINKLERS AND ENSURE

THAT COVERAGE REQUIREMENTS OF NFPA 13 ARE MET, PROVIDE ADDITIONAL

UPRIGHT SPRINKLER HEADS WHERE COVERAGE IS NOT ADEQUATE. UNLESS

OTHERWISE INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT

ARE TO REMAIN. REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL

CONSTRUCTION.

B. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR

THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS

RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED

PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC

CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY

TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND

ALL APPLICABLE CODES AND CRITERIA.

C. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13,

14, AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING

CODE 2021, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES.

WHERE CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR,

THE MOST RESTRICTIVE REQUIREMENTS SHALL GOVERN.

D. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS

FOR REVIEW ACCORDING TO NFPA 1 (2021 EDITION), SECTION 1.14.

E. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN

ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S

REPRESENTATIVE.

F. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE

IN A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST

SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,

LATEST EDITION.

G. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE

CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING

SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR

BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY

COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.

H. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, BARRIERS,

CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED

ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS

TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS

FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION

DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED

ASSEMBLIES.

I. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE

REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL

WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO

ARE REGULARLY EMPLOYED TO DO SUCH WORK.

J. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,

CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE

SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF

THE BUILDING.

K. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.

L. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS

OTHERWISE NOTED.

M. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND

OBSTRUCTION REQUIREMENTS.

N. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL

FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,

AND STRUCTURAL COMPONENTS.

O. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL

SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE

REQUIREMENTS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION

DESIGN MANUAL.

P. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE.

PROVIDE RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD

ADJUSTMENT.

Q. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS

AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL

SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN

ACCORDANCE WITH NFPA.

R. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE

SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,

ELECTRICAL ROOMS, IT ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND

ON ALL SPRINKLERS INSTALLED BELOW 7'-0" AFF.

S. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND

FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS 1". THREADED JOINTS ARE

ALLOWED ON PIPING UP TO 2". GROOVED PIPING MAY BE USED ON PIPING 2-1/2"

AND LARGER. MECHANICAL TEES AND WELD-O-LETS ARE PERMITTED. DO NOT

THREAD THINWALL PIPE. SADDLE TAPS AND FLEXIBLE CONNECTIONS ARE NOT

PERMITTED.

T. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES

OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL

PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED

ADJUSTABLE HANGERS.

U. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT

WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND

NFPA REQUIREMENTS.

V. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT

WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS

PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH

NFPA 13.

W. SPRINKLERS SHALL HAVE A K FACTOR OF 5.6 UNLESS NOTED OTHERWISE.

X. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE

BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.

Y. ALL EXPOSED SPRINKLER PIPING SHALL BE RED IN COLOR AND LABELED EVERY

10 FEET IN THE DIRECTION OF FLOW.

TITLEFIRE PROTECTION NOTES

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE PROVIDED (FURNISHED AND

INSTALLED) UNDER THIS CONTRACT. DRAWINGS SHOULD NOT BE SCALED.

2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER WHICH THEY SHALL OPERATE

AND VERIFY THE EXTENT OF WORK REQUIRED TO COMPLETE THE WORK UNDER THIS CONTRACT.

3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO DETERMINE ANY

NECESSARY MODIFICATIONS.

4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE

ENGINEERING DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE REQUIREMENTS:

• VA FIRE PROTECTION DESIGN MANUAL (VA FPDM), 8TH EDITION (JUNE 2021)

• INTERNATIONAL BUILDING CODE (IBC) 2021

• INTERNATIONAL EXISTING BUILDING CODE 2021

• IBC MECHANICAL 2021

• IBC PLUMBING 2021

• IBC ENERGY CONSERVATION 2021

• ASHRAE 90.1-2019, ENERGY STANDARD FOR BUILDING EXCEPT LOW-RISE RESIDENTIAL BUILDINGS

• NFPA 1-2021, THE UNIFORM FIRE CODE

• NFPA 101-2021, THE LIFE SAFETY CODE

• NFPA 51B-2019, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING AND OTHER HOT WORK

• NFPA 13-2019, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

• NFPA 70-2020, NATIONAL ELECTRICAL CODE

• NFPA 90A-2021, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTING SYSTEMS.

• NFPA 99-2021, STANDARD FOR HEALTH CARE FACILITIES

• NFPA 241-2019, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS.

• VA ALBANY SAMUEL S. STRATTON VAMC STATION SPECIFIC SPECS - COORDINATE WITH COR

1. VA SOP 138-12HV - DHW TEMP LIMITS

2. VA SOP 138-13HV - HOT WORK PROCEDURES

3. VA SOP 138-22HV - CONSTRUCTION SOP'S FOR QA

4. VA SOP 138-60HV - ENGINEERING SERVICE IC POLICY

5. VA SOP 138-62HV - HOUSEKEEPING SAFETY ON CONSTRUCTION PROJECTS

6. VHA DIRECTIVE 1061 - LEGIONELLA PREVENTION AND ANTI-SCALD

6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND CONSTRUCTION WORK.

7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF WORK UNDER THIS CONTRACT.

DISMANTLE AND REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF

INSTALLATION.

8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.

9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART OF THE TOTAL PROJECT COST.

10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, BARRIERS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L.

REQUIREMENTS TO MAINTAIN THE ASSEMBLY RATING.

11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL

TIMES DURING CONSTRUCTION.

12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS FOR ALL PRODUCTS USED ON

PROJECT.

14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION IN EITHER HARD COPY OR ELECTRONIC FORM. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF

RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS OR HER SUBMITTAL DATA.

15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN THREE RING BINDERS AND ELECTRONIC MEDIA AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP

DRAWINGS, SPARE PARTS DATA, ETC. PROVIDE AN INDEX AND ASSOCIATED DIVIDERS.

16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION COMPLETION IN BOTH

HARD COPY AND ELECTRONIC MEDIA FORMS.

17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND MATERIALS. NO CHANGE ORDERS SHALL

BE ISSUED WITHOUT WRITTEN CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.

FIRE PROTECTION NOTESFIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA

SPACE TYPE

HAZARD

CLASSIFICATION

SYSTEM

TYPE

DISCHARGE

DENSITY

REMOTE

AREA

MAXIMUM

COVERAGE

AREA PER

SPRINKLER

MAXIMUM

SPACING

WATER

SUPPLY

DURATION

OUTSIDE

HOSE

ALLOWANCE TEMPERATURE

CLASSIFICATION

SPRINKLER TYPE NOTES

GPM/FT² FT² FT² FT. MINUTES GPM

GENERAL,

EXCEPT AS

LISTED BELOW

LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY

SEMI-RECESSED PENDENT, QUICK

RESPONSE, FACTORY MUTUAL

APPROVED, UL LISTED

STORAGE, LINEN

ORDINARY

HAZARD

GROUP 2

WET PIPE 0.2 1,500 130 15 60-90 250 ORDINARY

SEMI-RECESSED PENDENT OR

UPRIGHT, QUICK RESPONSE,

FACTORY MUTUAL APPROVED, UL

LISTED

EQUIPMENT

ROOM

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY

QUICK RESPONSE UPRIGHT,

FACTORY MUTUAL APPROVED, UL

LISTED

HOUSEKEEPING

CLOSET

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY

PENDENT OR UPRIGHT, QUICK

RESPONSE, FACTORY MUTUAL

APPROVED, UL LISTED

NO SPRINKLER

MODIFICATIONS IN

THIS AREA

N/A EXISTING N/A N/A N/A N/A N/A N/A N/A EXISTING 1

NOTES:

1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.

HAZARD

SYMBOL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536

MES Group 550 North Reo Street Tampa, FL 33609

(813) 289-4700

A u to d e s k D o c s

/5

-8

C o n s o lid a te

P ri m a ry

C a re s t F lo o r

S tr a tt o n V

A M

C /5

-8

.B

.M

E P

F .r v…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .