DRAWINGS BP12 20200519.pdf
PDF 46 MB Posted
- Attached to
- Barracks Restoration Project #12 - Bid Abstract Added Federal contract opportunity
- Solicitation number
- W912L9-20-B-0005
- Issued by
- Department of the Army National Guard
About this file
This solicitation notice seeks bids for a barracks restoration project at an Indiana National Guard facility. The project includes selective demolition and renovation of Buildings 216 and 217, including installation of a new geothermal well system, facility controls, fire suppression system, and structural expansion of the mechanical room. The scope of work also encompasses preparation and finishing of surfaces, site work, and environmental protections. The fixed-price contract has a performance period of 240 days from notice to proceed. The solicitation is set aside entirely for small businesses with a NAICS code of 236220. The estimated value ranges from $1-5 million. The bid opening is September 9, 2020. Interested offerors must register on SAM.gov and beta.sam.gov to access solicitation documents. The contracting agency is the Department of the Army National Guard. Funding is anticipated but not yet available.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| BID OPENING ABSTRACT.pdf | ||
| Solicitation Amendment 3 W912L920B00050003.pdf | ||
| Questions and Answers UPDATED 9-2-2020.pdf | ||
| Questions and Answers.pdf | ||
| Solicitation Amendment 2 W912L920B00050002.pdf | ||
| Phase 2 Addendum No 01 BP12.pdf | ||
| 20200819 SITE VISIT PREPROPOSAL CONFERENCE MEETING MINUTES COMBINED.pdf | ||
| 102113.19 FL - Plastic Toilet Compartments.pdf | ||
| Solicitation Amendment 1 W912L9-20-B-0005.pdf | ||
| CAMP ATTERBURY BARRACKS AND BOQ RENOVATION -BP12 - 2020.0820.pdf | ||
| Sign In Sheet Site Visit.pdf | ||
| W912L9-20-B-0005 PROJECT 12.pdf | ||
| Barracks Statement of Work 05-21-2020 BP-12.pdf | ||
| 007_APNDX-B_CD-REPORT_Pkg 12_216-217.pdf | ||
| eCMRAMemo.pdf | ||
| 003_Phase 2_Project Manual Vol 1of 2_19May20.pdf | ||
| 004_Phase 2_Project Manual Vol 2 of 2_19May20.pdf | ||
| AF-66 Submittals_BP12.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DLZ Indiana, LLC
157 E. Maryland St.
Indianapolis, IN 46204 Office: 317.633.4120 Fax: 317.633.4177
ARCHITECT/ENGINEER:
ELECTRICALMECHANICAL / PLUMBING STRUCTURAL
EACH SEAL APPLIES TO ITS DESIGNATED DISCIPLINE.
SITE DEVELOPMENTPRINCIPAL ARCHITECT
CONSTRUCTION DOCUMENTS - BID PACKAGE
MAY 19, 2020
PO BOX 5000, BLDG #232 EGGLESTON STREET EDINBURGH, IN 46124
BASIC OFFICER QUARTERS AND BARRACKS RENOVATION
CAMP ATTERBURY JOINT MANEUVER TRAINING CENTER
DLZ PROJECT NO. 1963-1020-90
MARVIN L. HITCHCOCKERIC S. ACKERELLIOTT ALLENERIC B. RATTS, AIA JAMIE L. POCZEKAY
12 - Buildings 216 & 217
Project 2020-008-12 80 Man Barracks
507 508
504 503
607 608
404 405 407 408
410 411
217 216 214 213
211 210
104 105
107 108
111 110
117 116
114 113
NORTH
BUILDINGS
INCLUDED
IN PROJECT
BUILDINGS
INCLUDED IN
BID PACKAGE 9
BUILDINGS
INCLUDED IN
BID PACKAGE 8
BUILDINGS
INCLUDED IN
BID PACKAGE 12
BUILDINGS
INCLUDED IN
BID PACKAGE 11
BUILDINGS
INCLUDED IN
BID PACKAGE 10
BUILDINGS
INCLUDED IN
BID PACKAGE 3
A5.1
KEYNOTE TARGET
DRAWING TITLE
SYMBOL
ROOM
NAME ROOM NAME
ROOM NUMBER
DESCRIPTION
X WALL TYPE TARGET
BUILDING SECTION TARGET
SECTION NUMBER
SHEET NUMBER
VERTICAL ELEVATION BUBBLE
NORTH ARROW
DOOR MARK TARGET X
SHT DETAIL TARGET
X X
X X
XXXX
SHEET NUMBER
DETAIL NUMBER
X
SHT
SHEET NUMBER
SECTION NUMBER
WALL SECTION TARGET
INTERIOR ELEVATION TARGET
WINDOW TARGETX
EXTERIOR ELEVATION TARGET
ELEVATION NUMBER
SHEET NUMBER
DRAWING SCALE
XXX
SCALE:
XXX DRAWING NAME
DETAIL NUMBER
X
SHT
X
SHT
NORTH
X
SHEET
NUMBER
NUMBER
ELEVATION X
SHT
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
WINDOW
DESIGNATIONF2
CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SUBMITTING A BID OR BEGINNING ANY WORK. CONDITIONS FOUND TO BE IN VARIANCE FROM THE INFORMATION IN THE DRAWINGS OR PROJECT MANUAL SHALL BE SUBMITTED
TO THE ARCHITECT IN WRITING FOR CLARIFICATION.
KEYNOTES ARE MEANT AS A GENERAL GUIDE FOR TYPICAL LOCATIONS. CONTRACTOR TO PERFORM FULL EXTENT OF WORK REQUIRED TO ACCOMPLISH DESIGN INTENT. THE ABSENCE OF A KEYNOTE DOES NOT ABSOLVE THE CONTRACTOR FROM PROVIDING THE FEATURE
GRAPHICALLY INDICATED ON THE DRAWINGS.
SPECIFIC WORK ITEMS SHALL BE COORDINATED AND INTERFACED WITH ALL OTHER TRADES TO ALLOW FOR NEW CONSTRUCTION AND
COMPLETE INSTALLATION AS REQUIRED TO ACCOMPLISH DESIGN INTENT.
REFER TO DRAWINGS OF EACH TRADE OR DISCIPLINE FOR ADDITIONAL GENERAL NOTES AND INFORMATION, INCLUDING CIVIL/SITE DEVELOPMENT, ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL.
CONTRACTOR IS RESPONSIBLE FOR ALL WORK IDENTIFIED ON ALL DRAWINGS AND INFORMATION IN THE PROJECT MANUAL, AS A COMPLETE PROJECT. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE SPECIFIC SCOPE OF WORK FOR ANY SUBCONTRACTORS
FOR THIS PROJECT.
FIELD VERIFY ACTUAL LOCATIONS OF EXISTING UNDERGROUND UTILITIES, STRUCTURES, WATER LINES, STORM AND SANITARY LINES, GAS LINES, ELECTRICAL CONDUIT, AND OTHER UNDERGROUND UTILITIES PRIOR TO PERFORMING EARTHWORK, EXCAVATION, OR UTILITY WORK.
ENGAGE THE SERVICES OF A PRIVATE UTILITY LOCATE COMPANY TO COMPLETELY LOCATE EXISTING UNDERGROUND UTILITIES AND
STRUCTURES.
LOCATION OF ALL TEMPORARY FACILITIES SHALL BE COORDINATED WITH OWNER AND ARCHITECT PRIOR TO MOBILIZATION ON-SITE, INCLUDING BUT NOT LIMITED TO TEMPORARY STAGING AREA, MATERIAL STORAGE AREA, ACCESS DRIVE(S), PARKING AREA, TOPSOIL STOCKPILE AREA, WASTE DISPOSAL AREA, FIELD OFFICES AND TEMPORARY FACILITIES, JOB SIGN, AND TEMPORARY FENCING.
CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL MISCELLANEOUS BLOCKING REQUIRED FOR INSTALLATION OF ALL BUILDING COMPONENTS, INCLUDING BUT NOT LIMITED TO FURNISHINGS, FIXTURES, EQUIPMENT, HARDWARE, BRACKETS, AND OWNER-PROVIDED EQUIPMENT.
CONTRACTOR SHALL COORDINATE SPECIFIC REQUIREMENTS ASSOCIATED WITH EACH TRADE AND WITH OWNER'S REPRESENTATIVE.
CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL MISCELLANEOUS WOOD AND METAL TRIM, FLASHING, CLIP ANGLES, ANCHORS, SUPPORTS, AND CLOSURE TRIM REQUIRED TO PROVIDE A COMPLETE, UNIFORM, AND WEATHERTIGHT ASSEMBLY AS REQUIRED TO ACCOMPLISH THE
DESIGN INTENT.
ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS. CONTRACTOR SHALL PROVIDE AND INSTALL ALL ACCESSORY COMPONENTS AS REQUIRED TO FULLY COMPLY WITH MANUFACTURER'S RECOMMENDATIONS. IF PLANS CONFLICT WITH THE MANUFACTURER'S INSTRUCTION, CONSULT THE ARCHITECT FOR FURTHER INSTRUCTION BEFORE PROCEEDING.
CONTRACTOR SHALL PROVIDE ACCESS DOORS IN ALL WALLS AND CEILINGS WHERE SERVICE OR ADJUSTMENT TO MECHANICAL, PLUMBING, FIRE PROTECTION OR ELECTRICAL ITEMS MAY BE REQUIRED. ACCESS DOORS SHALL BE OF AN APPROPRIATE SIZE REQUIRED FOR EACH APPLICATION. WHERE APPLICABLE, ACCESS DOORS SHALL MATCH THE FIRE RATING OF THE WALL ASSEMBLY.
WHERE DISCREPANCIES EXIST IN THE CONTRACT DOCUMENTS INCLUDING DISCREPANCIES BETWEEN DRAWINGS AND PROJECT MANUAL, CONTRACTOR SHALL REQUEST CLARIFICATION IN WRITING FROM ARCHITECT. THE CONTRACTOR SHALL NOT ASSUME ANY ITEM TAKES PRECEDENCE OVER THE OTHER. ANY ACTION THE CONTRACTOR MAKES PRIOR TO NOTIFICATION IN WRITING SHALL BE SOLELY AT THE
CONTRACTOR'S RISK.
CONTRACTOR SHALL SEAL ALL PENETRATIONS IN EXTERIOR WALL AND ROOF ASSEMBLIES WITH APPROPRIATE JOINT SEALANT(S) AND FLASHING(S) TO MAINTAIN A WEATHERTIGHT AND AIRTIGHT BUILDING ENVELOPE. ALL JOINTS AND PENETRATIONS SHALL BE SEALED, GASKETED, OR WEATHER-STRIPPED TO MINIMIZE AIR LEAKAGE, INCLUDING THE FOLLOWING:
1. JOINTS AROUND FENESTRATION AND DOOR FRAMES.
2. JUNCTIONS BETWEEN WALLS AND FOUNDATIONS, BETWEEN WALLS AT BUILDING CORNERS, BETWEEN WALLS AND FLOORS OR ROOFS, AND BETWEEN WALLS AND ROOF OR WALL PANELS.
3. OPENINGS AT PENETRATIONS OF UTILITY SERVICES THROUGH ROOFS, WALLS, AND FLOORS.
4. JOINTS, SEAMS, AND PENETRATIONS OF VAPOR RETARDERS.
5. ALL OTHER OPENINGS IN THE BUILDING ENVELOPE.
COORDINATE WITH OTHER CONSTRUCTION ACTIVITIES AND CONSTRUCTION SEQUENCING WITH OTHER PROJECT(S) AND WORK BEING
PERFORMED CONCURRENTLY ON-SITE.
CONTRACTOR TO PROTECT ALL ITEMS WITHIN THE CONSTRUCTION LIMITS (INCLUDING SITE ELEMENTS) THAT ARE DESIGNATED TO REMAIN;
ITEMS DAMAGED AS A RESULT OF WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED TO ORIGINAL CONDITION.
THESE DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS. IF THE DIMENSIONS CANNOT BE DETERMINED BY THE INFORMATION GIVEN, CONTRACTOR SHALL REQUEST CLARIFICATION FROM THE ARCHITECT. ALL DIMENSIONS ARE TO FACE OF GYPSUM BOARD, FACE OF CMU, OR FACE OF CONCRETE, UNLESS NOTED OTHERWISE. CEILING HEIGHT DIMENSIONS ARE FROM FINISHED FLOOR TO FACE OF FINISHED
CEILING MATERIALS, UNLESS NOTED OTHERWISE.
THESE DRAWINGS ARE REPRESENTATIVE OF TYPICAL BUILDINGS OF EACH TYPE. THERE MAY BE MINOR VARIATIONS AND DIFFERENCES BETWEEN THE DRAWINGS AND ACTUAL FIELD CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR PERFORMING ALL WORK NECESSARY TO
MEET THE DESIGN INTENT.
EXISTING CONDITIONS DEPICTED ARE BASED ON THE DESIGN OF RECORD AND INFORMATION FURNISHED BY THE OWNER TO THE ARCHITECT. THE ARCHITECT IS NOT RESPONSIBLE FOR THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED AND DOES
NOT REPRESENT THAT RECORD DRAWINGS ACCURATELY DEPICT ACTUAL CONDITIONS.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
D L Z
I N
D
IA
N A
L L C
D R
A W
IN
G
N U
M B
E R
P R
O J
E C
T N
U M
B E
R
D A
T E
A P
P R
V 'D
D E
S
IG
N E
D
D R
A W
N
C H
K 'D
/1
/2
:1
:0
P M
C R e v it B a c k u p s \2
\1
-A
T T
E R
B U
R Y
-B O
Q k k e rs ti e n s W
L R
A .r v t
G
2-
-1
-9
R W
H P
O A
E B
R
H W
S
M A
Y
P O
A
G E
N E
R A
L N
O T
E S
A N
D
IN
F O
R M
A T
IO
N
G E
N E
R A
L
E D
IN
B
U R
G H
IN
B A
S
IC
O F
F
IC
E R
Q U
A R
T E
R S
A N
D B
A R
R A
C K
S R
E N
O V
A T
IO
N
C A
M P
A T
T E
R B
U R
Y J
O
IN
T M
A N
E U
V E
R T
R A
IN
IN
G C
E N
T E
R
SYMBOLS
LOCATION MAP SHEET INDEX
GENERAL NOTES
MECHANICAL
M001 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
MD110 80 MAN BARRACKS - MECHANICAL, FLOOR AND UNDERSLAB
PLUMBING REMOVAL PLANS
M110 80 MAN BARRACKS - FIRE PROTECTION, MECHANICAL, AND
COMBINED PLUMBING INSTALLATION PLANS
M111 80 MAN BARRACKS - COMBINED SECTIONS AND RISER
DIAGRAMS
M500 MECHANICAL DETAILS
M501 MECHANICAL DETAILS
M600 MECHANICAL AND PLUMBING SCHEDULES
M700 CONTROL POINTS, SEQUENCES, AND SCHEMATICS
ELECTRICAL
E001 GENERAL NOTES, SYMBOLS, ABBREVIATIONS & DETAILS
ED110 80 MAN BARRACKS - ELECTRICAL, LIGHTING AND SYSTEMS
REMOVAL PLAN
ED111 80 MAN BARRACKS - EXISTING COMMUNICATIONS EQUIPMENT
PHOTOS AND REMOVAL TYPICAL PHOTOS
ED112 80 MAN BARRACKS - EXISTING COMMUNICATIONS EQUIPMENT
PHOTOS AND REMOVAL TYPICAL PHOTOS
E110 80 MAN BARRACKS - ELECTRICAL, LIGHTING AND SYSTEMS
INSTALLATION PLAN
E111 80 MAN BARRACKS - SCHEDULES AND DETAILS
E112 80 MAN BARRACKS - PANELBOARD SCHEDULES
GENERAL
G001-12 TITLE SHEET - BID PACKAGE 12
G002-12 GENERAL NOTES AND INFORMATION
G003 ABBREVIATIONS, MOUNTING HEIGHTS, AND PARTITION
SCHEDULE
G005 CODE ANALYSIS AND COMPLIANCE PLANS
SITE DEVELOPMENT
C100 SITE LOCATION PLAN
C102 EXISTING CONDITIONS AND REMOVALS PLAN
C201 ENLARGED SITE UTILITY PLAN
C301 EROSION CONTROL AND RESTORATION PLAN
C400 STANDARD DETAILS
C401 STANDARD DETAILS
STRUCTURAL
S001 STRUCTURAL GENERAL NOTES
S101 80 MAN BARRACKS - STRUCTURAL PLANS
S300 FOUNDATION DETAILS - 1
S301 FOUNDATION DETAILS - 2
S400 MASONRY TYPICAL DETAILS - 1
S401 MASONRY TYPICAL DETAILS - 2
S500 FRAMING DETAILS
ARCHITECTURE
AD110 80 MAN BARRACKS - REMOVAL CEILING AND FLOOR PLAN
A110 80 MAN BARRACKS - FLOOR PLANS & REFLECTED CEILING PLAN
A111 80 MAN BARRACKS - ROOF PLAN & ELEVATIONS
A112 80 MAN BARRACKS - SECTIONS, DETAILS, ROOM FINISH & DOOR
SCHEDULES
A200 COMMON SECTIONS & DETAILS
N O
R
E V
IS
IO
N D
A T
E
ANCHOR BOLT
AIR CONDITIONING
ACOUSTICAL CEILING TILE
AREA DRAIN
ADDENDUM
ABOVE FINISHED FLOOR
ABOVE GRADE
ACCESS PANEL
ACOUSTICAL PLASTER CEILING
AUDIO VISUAL
ADMINISTRATION
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATE
ARCHITECT (ARCHITECTURAL)
ASPHALT
ASSOCIATE
AVERAGE
BOTTOM
BOND BEAM
BOTTOM OF CURB
BARRIER FREE
BACK FLOW PREVENTER
BUILDING LINE
BENCH MARK
BRITISH THERMAL UNIT
BUILT UP
BOARD
BETWEEN
BUILDING
BLOCK
BLOCKING
BASIC OFFICER'S QUARTERS
BEAM
BULLET RESISTANT
BEARING
BRONZE
BASEMENT
CONDUIT
CABINET
CATCH BASIN
CORNER BAR
CENTER TO CENTER
CEMENT
CERAMIC
CUBIC FEET PER MINUTE
CORNER GUARD
CAST IRON
CAST IRON PIPE
CIRCLE OR CIRCULAR
CONTROL JOINT
CHALKBOARD
CENTERLINE
CONSTRUCTION LINE
CEILING
CLOSET
CLEAR
CONCRETE MASONRY UNIT
CLEAN OUT
COLUMN
COMPACTED
CONCRETE
CONDENSATE
CONSTRUCTION
CONTINUOUS
CONTRACTOR
COORDINATE
CORRIDOR
CORRUGATED
CARPETING
CONSTRUCTION JOINT
CAULKING SEAM
CERAMIC TILE BASE
CERAMIC TILE FLOOR
CERAMIC TILE WALL
CENTER OR CENTERING
CUBIC
COLD WATER
DEEP
DRINKING FOUNTAIN
DEAD LOAD
DOWN SPOUT
DOUBLE
DEGREE
DEMOLISH (ED)
DEPARTMENT
DIAMETER
DIMENSION
DOOR
DRAWING
DETAIL
EAST
EXHAUST AIR
ELECTRICAL CONTRACTOR
EXHAUST FAN
EXT. INSULATION FINISH SYSTEM
EXPANSION JOINT
EMERGENCY
ELECTRICAL PANEL
EACH WAY
ELECTRIC WATER COOLER
ELEVATION
ELECTRICAL OR ELECTRIC
ELEVATOR
ENGINEER OR ENGINEERING
EQUAL
EXPOSED STRUCTURE
EQUIPMENT
ENTERING ROOM TEMPERATURE
EXISTING TO REMAIN
EXISTING
EXPANSION
EXTERIOR
FIRE ALARM CONTROL PANEL
FRESH AIR INTAKE
FURNACE
FLOOR DRAIN
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FIRE HOSE CABINET
FLOOR MOUNTED
FIN RADIATION
FOOD SERVICE
FIELD VERIFY
A.B.
A.C.
A.C.T A.D.
ADD.
A.F.F.
A.F.G.
A.P.
A.P.C.
A.V.
ADMIN.
AGGR.
ALT.
ALUM.
APPROX.
ARCH.
ASPH.
ASSOC.
AVG.
B.(BOTT.)
BB
B.C.
B.F.
B.F.P.
B.L.
B.M.
B.T.U.
B.U.
BD.
BTWN
BLDG.
BLK.
BLKG.
BOQ
BM.
BR
BRG.
BRZ.
BSMT.
C.
CAB.
C.B.
CB.
C.C.
CEM.
CER.
C.F.M.
CG
C.I.
C.I.P.
CIR.
CJ
CKBD.
CL
C.L.
CLG.
CLOS.
CLR.
C.M.U.
C.O.
COL.
COMP.
CONC.
COND.
CONST.
CONT.
CONTR.
COORD.
CORR.
CORG.
CPT.
CSJ
C.S.
CTB
CTF
CTW
CTR.
CU.
CW
D.
D.F.
D.L.
D.S.
DBL.
DEG.
DEMO
DEPT.
DIA.
DIM.
DR.
DWG.
DTL.
E.
E.A.
E.C.
E.F.
E.I.F.S.
EJ
EMER.
E.PAN.
E.W.
E.W.C.
EL.
ELEC.
ELEV.
ENG.
EQ.
E.S.
EQUIP.
ETR.
ETR
EXIST.
EXP.
EXT.
F.A.C.P.
F.A.I.
F.C.
F.D.
F.E.
F.E.C.
F.H.C.
F.M.
F.R.
F.S.
F.V.
F.W.C.
FIN.
FLR.
FT.
FTG.
G.A.
G.C.
G.R.V.
GL.
GND.
GR.
GYP.BD.
H.
H.B.
H.M.
H.O.A.
H.V.A.C.
HW
HWS
HWR
HDWD.
HDWR.
HT.(HGT.)
H.D.P.
HORIZ.
HR.
HYD.
I.D.
I.F.
I.R.
IN.
INFO.
INSUL.
INT.
INV.
JAN.
J.B.
JCT.
JT.
K.D.
KIT.
K.O.
KP.
L.
LAM.
LAV.
LBS.
LG.
LGTH
L.H.
LFT.(LF.)
L.H.R.
L.L.
L.O.A.
LIN.
LTG.
M.C.
M.D.P.
M.H.
M.O.
MATL.
MAX.
MECH.
MEMB.
MEZZ.
MFR.
MIN.
MISC.
MIX.
MK.
M.O.
MSRY.
MTD.
MTL.
MTG.
N.
NA(N/A)
N.I.C.
NF
N.O.P.
NO.
NOM.
N.T.S.
OA.
O.A.
O.A.I.
O.C.
O.D.
O. TO O.
OF
O.R.
OL.
OFC.
OH
OPNG.
OPP.
OR.
ORIG.
OZ.
P.A.
P.C.
P.D.
P.J.F.
P.R.V.
PASS.
PAT.
PERP.
P.LAM.
PLAS.
PLBG.
PLYWD.
PNEU.
PNL.
PREFAB.
PROJ.
PT.
P.CONC.
PTN.
PV.
PVC.
QCV
Q.T.
QUAL.
FABRIC WALL COVERING
FINISH
FLOOR
FOOT OR FEET
FOOTING
GAUGE
GENERAL CONTRACTOR
GRAVITY ROOF VENTILATOR
GLASS
GROUND
GRADE
GYPSUM BOARD
HIGH
HOSE BIBB
HOLLOW METAL
HAND-OFF-AUTOMATIC
HEATING VENTILATING & AIR-CONDITIONING
HOT WATER
HOT WATER SUPPLY
HOT WATER RETURN
HARDWOOD
HARDWARE
HEIGHT
HIGH DENSITY PARTICLE BOARD
HORIZONTAL
HOUR
HYDRAULIC
INSIDE DIAMETER
INSIDE FACE
INSIDE RADIUS
INCH
INFORMATION
INSULATION
INTERIOR
INVERT
JANITOR OR JANITORIAL
JUNCTION BOX
JUNCTION
JOINT
KILN-DRIED
KITCHEN
KNOCKOUT
KICK PLATE
LEFT
LAMINATED
LAVATORY
POUNDS
LARGE
LENGTH
LEFT HAND
LINEAR FEET
LEFT HAND REVERSE
LIVE LOAD
LENGTH OVER ALL
LINEAR
LIGHTING
MECHANICAL CONTRACTOR
MAIN DISTRIBUTION PANEL
MAN HOLE
MASONRY OPENING
MATERIAL
MAXIMUM
MECHANICAL
MEMBRANE
MEZZANINE
MANUFACTURER
MINIMUM
MISCELLANEOUS
MIXTURE
MARK
MASONRY OPENING
MASONRY
MOUNTED
METAL
MOUNTING
NORTH
NOT APPLICABLE
NOT IN CONTRACT
NEAR FACE
NOT OTHERWISE PROVIDED
NUMBER
NOMINAL
NOT TO SCALE
OVERALL
OUTSIDE AIR
OUTSIDE AIR INTAKE
ON CENTER
OUTSIDE DIAMETER
OUT TO OUT
OUTSIDE FACE
OUTSIDE RADIUS
OVERLOAD
OFFICE
OVERHEAD
OPENING
OPPOSITE
OUTSIDE RADIUS
ORIGINAL
OUNCE
PIPE ANCHOR
PLUMBING CONTRACTOR
PRESSURE DROP
PRE MOLDED JOINT FILLER
PRESSURE REDUCING VALVE
PASSENGER
PATTERN
PERPENDICULAR
PLASTIC LAMINATE
PLASTIC
PLUMBING
PLYWOOD
PNEUMATIC
PANEL
PREFABRICATED
PROJECT
PAINT
PRECAST CONCRETE SLAB
PARTITION
PAVERS
POLYVINYL CHLORIDE
QUICK COUPLER VALVE
QUARRY TILE
QUALITY
QTY.
R R.
RAD.(R.)
R.A.
R.B.
RBR
RD.
R.D.
REC.
REF.
REV.
REM.
R.H.
R.H.R.
RCP
RE:
RECPT.
RECT.
REFR.
REINF.
REQD.
REV.
RFG.
R.H.
RHR
RLG.
RM.
R.R.
RT.
ROW (R/W)
RVS.
RWC.
RWL
S.A.
S.A.T.
S.C.
S.F.S.
S.P. S.
S.
S.S.
S. TO S.
SHM.
S.V.
SAN.
SCHED.
SECT.
SEW.
SHT.
SHWR.
SIM.
S.O.
SP
SPECS.
SPKR.
SQ.
ST.
STD.
STOR.
STRUCT.
SUSP.
SW.
T T.&B.
T.&G.
T.C.
T.C.C.
T.C.P.
T.P.
T.W.C.
TBB
TEL.
TEMP.
TERR.
THRU.
TKBD.
TLT.
TOL.
TYP.
U U.F.D.
U.L.
UNO
U.V.
UR.
UTIL.
VYL
VAP.
VAR.
VCB
V.C.P.
VCT
VERT.
VEST.
VENT.
VIF
VOL.
V.P.
V.S.
VWC
W.
W.C.
WD.
W.F.
WH
W.H.
W.I.
WP
W.P.
W.L.
W.M.
WS
W.S.
W.W.F.
WT.
XFMR
XFR
YD.
YCO
Ø
P x W/
QUANTITY
THERMAL RESISTANCE
RISER OR RIGHT
RADIUS
RETURN AIR
RUBBER BASE
RUBBER
ROAD
ROOF DRAIN
RECESSED
REFERENCE
REVISION
REMOVABLE
RIGHT HAND
RIGHT HAND REVERSE
REINFORCED CONCRETE PIPE
REFER TO:
RECEPTACLE
RECTANGLE OR RECTANGULAR
REFRIGERATOR
REINFORCE (D) (ING) (MENT)
REQUIRED
REVERSE
ROOFING
RIGHT HAND
RIGHT HAND REVERSE
RAILING
ROOM
RAIL ROAD
RIGHT
RIGHT OF WAY
REVERSE
MAIN WATER COLLECTOR
RAIN WATER LEADER
SUPPLY AIR
SUSPENDED ACOUSTICAL TILE
SEALED CONCRETE
STORE FRONT SYSTEM
STAND PIPE
SOUTH
STAINLESS STEEL
STUD TO STUD
SECURITY HOLLOW METAL
SHEET VINYL
SANITARY
SCHEDULE
SECTION
SEWER
SHEET
SHOWER
SIMILAR
SECTIONAL OVERHEAD
STATIC PRESSURE
SPECIFICATIONS
SPEAKER
SQUARE
STEEL
STANDARD
STORAGE
STRUCTURAL
SUSPENDED
SWITCH
TEMPERED
TOP AND BOTTOM
TONGUE AND GROOVE
TOP CURB
TEMP. CONTROL CONTRACTOR
TEMP. CONTROL PANEL
TEPID WATER
TEPID WATER CONTROLLER
TILE BACKER BOARD
TELEPHONE
TEMPERATURE
TERRAZZO
THROUGH
TACK BOARD
TOILET
TOLERANCE
TYPICAL
HEAT TRANSFER COEFFICIENT
UNDER FLOOR DUCT
UNDERWRITER'S LABORATORIES
UNLESS NOTED OTHERWISE
UNIT VENTILATOR
URINAL
UTILITY
VINYL
VAPOR
VARIES
VINYL COVE BASE
VITRIFIED CLAY PIPE
VINYL COMPOSITION TILE
VERTICAL
VESTIBULE
VENTILATE
VERIFY IN FIELD
VOLUME
VENT PIPE
VENT STACK
VINYL WALL COVERING
WEST
WATER CLOSET
WOOD
WASH FOUNTAIN
WALL HUNG
WATER HEATER
WROUGHT IRON
WORKING POINT
WATERPROOFING
WIND LOAD
WALK OFF MAT
WEATHER STRIP
WORK SINK
WELDED WIRE FABRIC
WEIGHT
TRANSFORMER
TRANSFER
YARD
YARD CLEAN OUT
DEGREE
PLUS OR MINUS
DIAMETER
CENTERLINE
PLATE
AND
BY
AT
NUMBER
WITH
ABBREVIATIONS:
BOTTOM OF
LIGHT FIXTURE
GRAB BARS AND
TOILET TISSUE
DISPENSER OR
HOLDER
WATER
CLOSET
STD.
URINAL
COAT
HOOKS
MIRROR AND
LAVATORY
1' - 0" 3' - 6"
3' - 4"
1' - 6"
M
A X
M
IN
1' - 0" 2' - 0"
T /R
IM
M A
X
M
IN
S U
R F
A C
E
T O
B /R
E F
L E
C T
IV
E
2' - 0"
M
IN
T O
B /G
F C
I
NOTE:
INSULATE SUPPLY AND
DRAIN PIPES BELOW
LAVATORIES AND SINK.
BARRIER
FREE LAV &
COUNTER
" 11"
T O
R
IM
O F
S
IN
K
3" MAX.
MIN.
1' - 5"
S
IN
K D
E P
T H
M A
X
8"
FIRE ALARM
HORN OR
STROBE
SHELF
M
IN
M
A X
FIRE HOSE,
EXTINGUISHER OR
COMBINATION CABINET
ELECTRIC OR
PANEL
CABINET
POWER
PANEL
ELECTRIC,
TELEPHONE OR TV
OUTLET
S W
IT
C
H
P U
S H
B U
T T
O N
F
IR
E A
L A
R M
B O
X
T H
E R
M O
S T
A T
C A
R D
R E
A D
E R
M E
C H
A N
IC
A
L
P
N E
L S
I N
F
IN
IS
H E
D S
P A
C E
S
M A
X T
O H
A N
D L E
M
IN
" 4
M
A X
W A
L L
B U
T T
O N
S
M A
X
S
DOOR
FRAME
DOOR
FRAME
EXIT
TYPICAL
LIGHT
SWITCH
LOCATION
EXIT LIGHTS
ABOVE DOORS
DOOR
M A
X
3"
TACTILE
SIGNAGE OR
PLAQUE
M
IN
M
A X
LOCATE ON LATCH SIDE
OF DOOR W/ 18" x 18"
CLEAR FLOOR SPACE.
WALL HUNG
LAV.
CONTRACTOR IS RESPONSIBLE TO
CONFIRM ALL MOUNTING HEIGHTS.
GENERAL NOTES:
A. REFER TO G002 FOR ADDITIONAL GENERAL NOTES AND
INFORMATION.
B. REFER TO STRUCTURAL DRAWINGS FOR APPLICABLE WALL
REINFORCEMENT AND ADDITIONAL REQUIREMENTS.
C. REFERENCE FLOOR PLANS FOR LOCATION OF PARTITION
TYPE.
WALL TYPE - A
"Z" FURRING AT 24" O.C.
2" RIGID INSULATION
5/8" GYP. BD.
3 1/8"
• TAKE TO UNDERSIDE OF EXISTING CEILING
12" CMU
WALL TYPE - H
• TAKE TO UNDERSIDE OF STRUCTURE
• REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL REQUIREMENTS
11 5/8"
VAPOR BARRIER
FACE OF EXISTING WALL
D L Z
I N
D
IA
N A
L L C
D R
A W
IN
G
N U
M B
E R
P R
O J
E C
T N
U M
B E
R
D A
T E
A P
P R
V 'D
D E
S
IG
N E
D
D R
A W
N
C H
K 'D
/1
/2
:2
:2
P M
C R e v it B a c k u p s \2
\1
-A
T T
E R
B U
R Y
-B O
Q k k e rs ti e n s W
L R
A .r v t
G
-1
-9
R W
H P
O A
E B
R
H W
S
M A
Y
P O
A
A B
B R
E V
IA
T
IO
N
S , M
O U
N T
IN
G
H E
IG
H
T S
, A N
D P
A R
T
IT
IO
N
S C
H E
D U
LE
G
E N
E R
A L
E D
IN
B
U R
G H
IN
B A
S
IC
O F
F
IC
E R
Q U
A R
T E
R S
A N
D B
A R
R A
C K
S R
E N
O V
A T
IO
N
C A
M P
A T
T E
R B
U R
Y J
O
IN
T M
A N
E U
V E
R T
R A
IN
IN
G C
E N
T E
R
ABBREVIATIONSPARTITION SCHEDULE
STANDARD MOUNTING HEIGHTS
N O
R
E V
IS
IO
N D
A
Path 3
Path 4
D L Z
I N
D
IA
N A
L L C
D R
A W
IN
G
N U
M B
E R
P R
O J
E C
T N
U M
B E
R
D A
T E
A P
P R
V 'D
D E
S
IG
N E
D
D R
A W
N
C H
K 'D
/1
/2
:2
:3
P M
C R e v it B a c k u p s \2
\1
-A
T T
E R
B U
R Y
-B O
Q k k e rs ti e n s W
L R
A .r v t
G
-1
-9
H W
S
E B
R
H W
S
M A
Y
P O
A
C O
D E
A N
A
LY
S
IS
A N
D C
O M
P
LI
A N
C E
P
LA
N S
G E
N E
R A
L
E D
IN
B
U R
G H
IN
B A
S
IC
O F
F
IC
E R
Q U
A R
T E
R S
A N
D B
A R
R A
C K
S R
E N
O V
A T
IO
N
C A
M P
A T
T E
R B
U R
Y J
O
IN
T M
A N
E U
V E
R T
R A
IN
IN
G C
E N
T E
R
TRAVEL DISTANCE- 60 MAN BARRACKS
Travel Path Travel Distance
Path 3 39' - 5"
Path 4 49' - 10"
USE
GROUP
ALLOWABLE
HEIGHT
ALLOWABLE
AREA
ACTUAL
AREA
(*SELECT DLZ STATE FOR APPLICABLE CODE REQUIREMENTS)
BUILDING CODE SUMMARY
A. PROJECT SUMMARY
1. RENOVATION OF EXISTING 60 AND 80 MAN BARRACKS. CMU MECHANICAL
ROOM ADDITIONS FOR NEW HVAC AND PLUMBING.
3. STRUCTURAL FRAMING SYSTEM
a. FIRST FLOOR: CMU LOAD BEARING WALLS.
4. FLOOR SYSTEM
a. FIRST FLOOR: CAST-IN-PLACE CONCRETE SLAB ON GRADE.
5. FOUNDATION SYSTEM
a. CAST-IN-PLACE CONCRETE.
6. ROOFING SYSTEM
a. PREFABRICATED WOOD TRUSSES WITH PLYWOOD SHEATING.
B. GOVERNING BUILDING STANDARDS
C. OCCUPANCY CLASSIFICATION
1. USE GROUP R-1
D. OCCUPANCY SEPARATION
1. NA
(TABLE 508.3.3)
E. CONSTRUCTION CLASSIFICATION
1. II-B
F. FIRE RESISTIVE REQUIREMENTS
1. BEARING WALLS - EXTERIOR
2. BEARING WALLS - INTERIOR
3. NON-BEARING WALLS - EXTERIOR
4. STRUCTURAL FRAME
5. PARTITIONS - PERMANENT
6. SHAFT ENCLOSURES
7. FLOORS AND ASSOCIATED SECONDARY MEMBERS
8. ROOFS AND ASSOCIATED SECONDARY MEMBERS
9. STAIRWAYS CONSTRUCTION
(TABLE 601, 602)
H. FIRE SPRINKLER SYSTEM
THE BUILDING SHALL BE PROVIDED WITH AN AUTOMATIC FIRE SUPPRESSION
SYSTEM THROUGHOUT.
I. FIRE ALARM SYSTEM
THE BUILDING SHALL BE PROVIDED WITH A FULLY ADDRESSABLE FIRE ALARM SYSTEM
THROUGHOUT.
J. THERMAL VALUES
1. CLIMATE ZONE B (ASHRAE 90.1 - 2007, TABLE 5.5-5)
2. OVERALL BUILDING CONSTRUCTION SHALL MEET OR EXCEED INDIANA ENERGY CONSERVATION CODE REQUIREMENTS
a. WALLS: MINIMUM R-11.4 c.i.
b. (*CONTINUE WALL TYPES AS NECESSARY)
c. ROOFS: MINIMUM R-38.0
d. OPAQUE DOORS: U-0.700 MAX.
e. FENESTRATION: U-0.55 MAX.
G. ALLOWABLE HEIGHT AND AREA (TABLE 503)
1. BUILDING CODE: 2014 INDIANA BUILDING CODE (2012 INTERNATIONAL BUILDING CODE WITH INDIANA AMENDMENTS)
2. PLUMBING CODE: 2012 INDIANA PLUMBING CODE (UNIFORM PLUMBING CODE, 2006 EDITION WITH INDIANA AMENDMENTS)
3. ELECTRICAL CODE: 2009 INDIANA ELECTRICAL CODE (NATIONAL ELECTRICAL CODE, 2008 EDITION WITH INDIANA AMENDMENTS)
4. MECHANICAL CODE: 2014 INDIANA MECHANICAL CODE (2012 INTERNATIONAL MECHANICAL CODE WITH INDIANA AMENDMENTS)
5. ENERGY CODE: 2010 INDIANA ENERGY CONSERVATION CODE (ASHRAE 90.1-2007 WITH INDIANA AMENDMENTS)
6. FIRE CODE: 2014 INDIANA FIRE CODE (2012 INTERNATIONAL FIRE CODE WITH INDIANA AMENDMENTS)
II-B 4 STORIES 16,000 S.F. BOQ'S = 3,839 S.F.
60 MAN = 5,227 S.F.
80 MAN = 6,326 S.F.
SCALE: 1/16" = 1'-0"
CODE COMPLIANCE PLAN - 80 MAN BARRACKS
N O
R
E V
IS
IO
N D
A
C
J L
P
J L P
J L
P
J N
J
S I T
E
L O
C A
T I O
N
P
L A
N
D R
A W
I N
G
N
U M
B E
R
A
P R
O J
E C
T
N
U M
B E
R
D A
T E
A P
P R
V D
D E
S I G
N E
D
D R
A W
N
C H
K D
M A
Y
C I V
I L
E D
I N
B U
R G
H
N O
R
E V
I S
I O
N D
A T
E
PLAN
NORTH
KEYPLAN
C A
M
T
E R
B U
R Y
J O
I N
T
M
A N
E U
V E
R
T
R A
I N
I N
G
C
E N
T E
R
B O
Q
B
A R
R A
C K
S
R
E N
O V
A T
I O
N
P
H A
S
DL
Z
IN
DI
AN
A, L
LC
BID PACKAGE 8
PROJECT AREA
SEE SHEET C201
FOR ENLARGED VIEW
BID PACKAGE 12
PROJECT AREA
SEE SHEET C201
FOR ENLARGED VIEW
BID PACKAGE 11
PROJECT AREA
SEE SHEET C201
FOR ENLARGED VIEW
BID PACKAGE 10
PROJECT AREA
SEE SHEET C202
FOR ENLARGED VIEW
BID PACKAGE 9
PROJECT AREA
SEE SHEET C202
FOR ENLARGED VIEW
BID PACKAGE 3
PROJECT AREA
SEE SHEET C200
FOR ENLARGED VIEW
I R B A N
K S
S T
THIRD STREET
F
O
U
R
H
R
E
E
T
BUILDING WALL
BUILDING WALL
BUILDING WALL
BUILDING WALL
BUILDING WALL
BUILDING WALL
SAN
SAN
S A N
S A N
S
A
N
S
A
N
S
A
N
C
J L
P
J L P
J L
P
J N
J
E X
I S
T I N
G
C
O N
D I T
I O
D
M
O V
A
A
N
A. UTILITIES SHOWN ARE APPROXIMATE, FIELD VERIFY PRIOR TO
CONSTRUCTION.
B. PROJECT LIMITS SHOWN ARE APPROXIMATE. ADJUSTMENTS TO THE
LIMITS INCIDENTAL TO CONSTRUCTION ACTIVITIES MAY BE
PERMITTED WITH THE APPROVAL OF THE ARCHITECT. CONTRACTOR
SHALL FIELD MARK ANY PROPOSED CHANGES TO THE PROJECT LIMITS
FOR ARCHITECT APPROVAL PRIOR TO BEGINNING CONSTRUCTION.
C. CONTRACTOR IS RESPONSIBLE FOR ALL NECESSARY TRAFFIC
MAINTENANCE PLANS, PERMITS, AND COORDINATION WITH
APPROPRIATE JURISDICTIONS REGARDING PUBLIC R.O.W. WORK.
D. SEE SITE CONSTRUCTION MANAGEMENT PLAN FOR STOCKPILE AND
STAGING LOCATIONS AND OTHER SITE REQUIREMENTS.
E. EROSION CONTROL MEASURES ARE TO BE INSTALLED PRIOR TO ANY
SITE DISTURBANCE. SEE SHEET NO. C400.
F. CONTRACTOR SHALL PROVIDE STABILIZED CONSTRUCTION ENTRANCE
PER THE REQUIREMENTS OF THE INDIANA STORMWATER QUALITY
MANUAL AND DETAIL ON SD5.2. SEE SITE CONSTRUCTION
MANAGEMENT PLAN FOR LOCATIONS.
G. EROSION CONTROL MEASURES FOR STOCKPILE PROTECTION SHALL BE
PLACED AS REQUIRED BY THE INDIANA STORMWATER QUALITY
MANUAL, INCLUDING, BUT NOT LIMITED TO, SILT FENCE ON
DOWNSLOPE AREAS OF STOCKPILE (10' MIN. FROM TOE OF SLOPE)
AND CONTAINMENT MEASURES TO AVOID WIND EROSION AND DUST
GENERATION. FINAL LOCATION BY CONTRACTOR.
H. REUSE OF ON-SITE TOPSOIL IS ANTICIPATED. CONTRACTOR SHALL
CONFIRM SUITABILITY OF ON-SITE TOPSOIL FOR REUSE PER
SPECIFICATIONS. IF UNSUITABLE OR INSUFFICIENT IN QUANTITY,
CONTRACTOR SHALL PROVIDE ADDITIONAL TOPSOIL TO MEET SITE
NEEDS AS SPECIFIED.
I. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND PROPERLY
DISPOSING OF ANY UNSUITABLE FILL ENCOUNTERED AS DEFINED IN
SPECIFICATIONS.
GENERAL NOTES
STRIP TURF AND TOPSOIL. STOCKPILE TOPSOIL FOR REUSE.
SITE REMOVAL KEY
PROTECTION KEY
PROTECT EXISTING UTILITY
DO NOT DISTURB EX. PAVEMENT
REMOVE SIDEWALK. SAW CUT AS REQUIRED AT JOINT.
REMOVE STONE MULCH AS NEEDED FOR UTILITY INSTALLATION.
REMOVE TREE.
REMOVE ASPHALT PAVEMENT.
TBM '1A' ELEV = 717.09' (NAVD88)
MAG SPIKE SET SOUTHWEST FACE OF POWER POLE W/NO NUMBER NORTH
OF THE SECOND BUILDING EAST OF THE INTERSECTION OF 1ST STREET AND
FAIRBANKS STREET ON THE SOUTH SIDE OF 1ST STREET.
TBM '1B' ELEV = 718.97' (NAVD88)
MAG SPIKE SET NORTH FACE OF POWER/LIGHT POLE #816-363 BETWEEN
THE THIRD AND FOURTH BUILDINGS EAST OF THE INTERSECTION OF 1ST
STREET AND EGGLESTON STREET ON THE NORTH SIDE OF 1ST STREET.
TBM '1C' ELEV = 715.11' (NAVD88)
MAG SPIKE SET SOUTHWEST FACE OF POWER/LIGHT POLE WITH NO
NUMBER, NORTH OF THE FIRST BUILDING WEST OF THE INTERSECTION OF
2ND STREET AND EGGLESTON STREET ON THE SOUTH SIDE OF 2ND STREET.
TBM '2A' ELEV = 715.49' (NAVD88)
MAG SPIKE SET SOUTH FACE OF POWER POLE #816-533, BETWEEN
BUILDINGS 218 AND 219 DIRECTLY WEST OF THE INTERSECTION OF
FAIRBANKS STREET AND 4TH STREET.
TBM '3A' ELEV = 718.90' (NAVD88)
MAG SPIKE SET SOUTH FACE OF POWER/LIGHT POLE #276-051 BETWEEN
BUILDINGS 318 AND 319 NORTH AND WEST OF THE INTERSECTION OF
FAIRBANKS STREET AND 6TH STREET.
TBM '4A' ELEV = 727.97 (NAVD88)
MAG SPIKE SET NORTH FACE OF POWER/LIGHT POLE #816-724, BETWEEN
BUILDINGS 419 AND 420 ON THE SOUTH AND WEST SIDES OF THE
INTERSECTION OF HEADQUARTERS ROAD AND FAIRBANKS STREET.
TBM '5A' ELEV = 733.71' (NAVD88)
MAG SPIKE SET SOUTH FACE OF LIGHT POLE #366-843, BETWEEN BUILDINGS
512 AND 513 ON THE SOUTH AND EAST SIDES OF THE INTERSECTION OF
HEADQUARTERS ROAD AND GATLING STREET.
BENCHMARKS
D R
A W
I N
G
N
U M
B E
R
A
P R
O J
E C
T
N
U M
B E
R
D A
T E
A P
P R
V D
D E
S I G
N E
D
D R
A W
N
C H
K D
M A
Y
C I V
I L
E D
I N
B U
R G
H
N O
R
E V
I S
I O
N D
A T
E
PLAN
NORTH
KEYPLAN
C A
T
E R
B U
I N
T
M
A N
E U
V E
R
T
R A
I N
I N
G
C
E N
T E
R
B O
Q
B
A R
R A
C K
S
R
E N
O V
A T
I O
N
P
H A
Z
IN
DI
AN
A, L
LC
BID PACKAGE #8
PROJECT AREA
BID PACKAGE #11
PROJECT AREA
BID PACKAGE #12
PROJECT AREA
S E E
S H
E E T
C
I R B A N
K S
S T
THIRD STREET
F
O
U
R
R
E
E
T
T
Y
P
T
Y
P
25'
TYP.
25'
TYP.
25'
TYP.
25'
TYP.
W
W
W
W
W W W
W
W
W
W
W
W
W
W
C
J L
P
J L P
J L
P
J N
J
E N
L A
R G
T
E
U
T I L I T
Y
P
L A
N
EXISTING 8" WATER MAIN.
CONNECT PROPOSED 6" FIRE SERVICE LINE TO EXISTING 8" WATER
MAIN WITH TAPPING SLEEVE AND VALVE.
PROPOSED 6" WATER MAIN AT 4'-6" MINIMUM COVER. (PROVIDE
BENDS AND DEFLECTIONS REQUIRED TO MAINTAIN REQUIRED
CLEARANCE WITH EXISTING UTILITIES). RESTRAIN ALL WATER
MAIN JOINTS.
PAVEMENT PATCH REQUIRED. (SEE DETAIL 01/C400).
SIDEWALK REPLACEMENT. (SEE DETAIL 02/C400)
REPLACE STONE AND FABRIC WITH NEW MATERIALS THROUGH
EXCAVATED AREA.
CONTRACTOR SHALL BE PREPARED TO COMPLETELY REMOVE
SIDEWALK BETWEEN BUILDING PAIRS. IF REMOVED, REPLACE IN
KIND TO EXISTING GRADES.
GEOTHERMAL SYSTEM (SEE MECHANICAL PLANS FOR DETAILS).
BUILDING ADDITION (SEE ARCHITECTURAL PLANS).
RELOCATE GAS METER/GAS SERVICE.
ABANDON EXISTING WATER SERVICE AND WATER SERVICE PIT.
PROPOSED 6" X 6" X 6" WATER MAIN TEE
DETAILED INFORMATION REGARDING THE LOCATION OF EXISTING
UTILITIES/SERVICE LINES BETWEEN THE BUILDINGS IS NOT
AVAILABLE. CONTRACTOR TO OBTAIN UTILITY LOCATES AND/OR
POT HOLING TO DETERMINE VIABLE ROUTE FOR INSTALLATION OF
FIRE SERVICE LINES TO EACH BUILDING PAIR.
KEY NOTES
EXISTING ELECTRIC LINE
EXISTING FIBER OPTIC
EXISTING GAS MAIN
EXISTING TELEPHONE
EXISTING WATER MAIN
EXISTING SANITARY SEWER
LEGEND
E
FO
T
W
SAN
PROPOSED WATER MAINW
EXISTING UTILITY INFORMATION WAS COMPLIED FROM FIELD
SURVEY OF VISIBLE UTILITY APPURTENANCES AND AS-BUILT DATA
PROVIDED BY CAMP ATTERBURY. CONTRACTOR TO FIELD VERIFY
ALL UTILITIES PRIOR TO EXCAVATION.
G
D R
A W
I N
G
N
U M
B E
R
A
P R
O J
E C
T
N
U M
B E
R
D A
T E
A P
P R
V D
D E
S I G
N E
D
D R
A W
N
C H
K D
M A
Y
C I V
I L
E D
I N
B U
R G
H
N O
R
E V
I S
I O
N D
A T
E
PLAN
NORTH
KEYPLAN
C A
T
E R
B U
I N
T
M
A N
E U
V E
R
T
R A
I N
I N
G
C
E N
T E
R
B O
Q
B
A R
R A
C K
S
R
E N
O V
A T
I O
N
P
H A
Z
IN
DI
AN
A, L
LC
1. LOCATION OF EXISTING UTILITIES SHOWN ARE APPROXIMATE.
CONTRACTOR SHALL VERIFY LOCATIONS PRIOR TO EXCAVATION.
2. UTILITIES ARE NOT SHOWN TO SCALE AND ARE PROVIDED IN
DIAGRAMMATIC FORMAT ONLY. NO ACCURATE DESCRIPTION OF
SERVICING UTILITIES IS AVAILABLE. CONTRACTOR TO FIELD LOCATE
ALL PRIVATE SERVICE LINES AND DETERMINE AVAILABLE ALIGNMENT
FOR WATER MAIN INSTALLATION PRIOR TO MAKING FIRE SERVICE
WATER MAIN TAP TO EXISTING WATER MAIN.
3. COORDINATE UTILITY DRAWINGS WITH
ARCHITECTURAL/PLUMBING/MECHANICAL/ELECTRICAL PLANS FOR
EXACT BUILDING ENTRANCE LOCATIONS.
4. COORDINATE WATER SERVICE CONNECTIONS TO WATER MAINS WITH
THE LOCAL WATER UTILITY.
5. ALL NEW WATER MAINS SHALL HAVE A MINIMUM OF 4'-6” COVER TO
TOP OF PIPE.
6. ALL JOINTS SHALL BE RESTRAINED ON NEW WATER MAIN.
7. MAINTAIN A MINIMUM OF 10-FEET HORIZONTAL SPACING AND 18"
VERTICAL SPACING BETWEEN ALL WATER MAINS AND SEWERS.
8. ALL SITE IMPROVEMENTS THAT ARE REQUIRED TO BE REMOVED FOR
THE INSTALLATION OF THE FIRE SERVICE WATER MAIN, SHALL BE
REPLACED IN KIND TO SAME ELEVATION, IN ACCORDANCE WITH THE
DETAILS PROVIDED HEREIN.
9. ALL DISTURBED AREAS SHALL BE FINE GRADED AND SEEDED AS PER
SPECIFICATIONS.
GENERAL NOTES
S E E
S H
E E T
C
BID PACKAGE #8
PROJECT AREA
BID PACKAGE #12
PROJECT AREA
BID PACKAGE #11
PROJECT AREA
C
O
N
S
T
R
U
C
T
I
M
I
I R B A N
K S
S T
THIRD STREET
F
O
U
R
R
E
E
T
C
J L
P
J L P
J L
P
J N
J
D R
A W
I N
G
N
U M
B E
R
A
P R
O J
E C
T
N
U M
B E
R
D A
T E
A P
P R
V D
D E
S I G
N E
D
D R
A W
N
C H
K D
M A
Y
C I V
I L
E D
I N
B U
R G
H
N O
R
E V
I S
I O
N D
A T
E
PLAN
NORTH
KEYPLAN
C A
T
E R
B U
I N
T
M
A N
E U
V E
R
T
R A
I N
I N
G
C
E N
T E
R
B O
Q
B
A R
R A
C K
S
R
E N
O V
A T
I O
N
P
H A
Z
IN
DI
AN
A, L
LC
S E E
S H
E E T
C
BID PACKAGE #8
PROJECT AREA
BID PACKAGE #12
PROJECT AREA
BID PACKAGE #11
PROJECT AREA
GENERAL NOTES
A. PROPOSED GRADES AND SLOPES SHALL MATCH EXISTING GRADES AND
SLOPES AT CONSTRUCTION LIMITS OR AS SHOWN ON DRAWINGS,
TYP. WHERE INTERSECTING SLOPE ELEVATIONS VARY, PROVIDE
SMOOTH TRANSITIONAL EDGE, TYPICAL.
B. UTILITIES AND UNDERGROUND OBSTACLES SHOWN ARE
APPROXIMATE, FIELD VERIFY UTILITY LOCATION PRIOR TO
COMMENCEMENT OF EARTHWORK AND/OR UTILITY ACTIVITIES. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO
OBSTRUCTIONS AND UTILITY LINES ENCOUNTERED DURING
CONSTRUCTION. CONTRACTOR SHALL NOTIFY AND HAVE THE
UTILITIES LOCATED AT LEAST 48 HOURS IN ADVANCE PRIOR TO
EXCAVATING.
C. PROPOSED FINISHED GRADES SHALL PROVIDE FOR POSITIVE
DRAINAGE TO A DRAINAGE STRUCTURE, OR TO MATCH EXISTING
GRADES. INFORM ENGINEER OF ANY DISCREPANCIES PRIOR TO
CONSTRUCTION.
D. CONTRACTOR SHALL FILL LOW/DEPRESSIONAL GRADES WHICH MAY
OCCUR THROUGH REQUIRED DEMOLITION, AS WELL AS, ANY AREA
WITHIN THE GRADING LIMITS, SO AS TO PROVIDE CONSTANT
UNIFORM SLOPES FOR POSITIVE DRAINAGE.
E. NO OPEN TRENCHES WILL BE ALLOWED IN THE EVENING AFTER DAILY
CONSTRUCTION OPERATIONS, CONTRACTOR TO PROVIDE
CONSTRUCTION FENCING AROUND ANY TRENCHING AREA FOR PUBLIC
SAFETY.
F. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DEWATERING
NECESSARY. WATER REMOVED BY DEWATERING EQUIPMENT SHALL
NOT BE DISPOSED OF INTO EXISTING SANITARY SEWERS. PROVIDE
SEDIMENT CONTROL MEASURES AS INDICATED ON SD5.2.
G. CONTRACTOR TO FIELD LOCATE (STAKE AND MARK) PLANT
LOCATIONS FOR REVIEW BY ENGINEER PRIOR TO INSTALLATION. THE
ENGINEER RESERVES THE RIGHT TO FIELD ADJUST ALL PLANT
LOCATIONS AS MAY BE NECESSARY.
H. SEED ALL AREAS NOT IDENTIFIED ON THESE DRAWINGS DISTURBED
BY CONSTRUCTION/ INSTALLATION ACTIVITIES IN ACCORDANCE WITH
SPEC. SECTION 329200.
I. CLEAR AND GRUB ALL AREAS DESIGNATED FOR PROPOSED
PLANTING/IMPROVEMENTS AS NECESSARY TO INSTALL PROPOSED
LAWN AND/OR PLANTINGS.
J. UTILITIES SHOWN ARE APPROXIMATE, FIELD VERIFY LOCATIONS
PRIOR TO COMMENCEMENT OF LANDSCAPING ACTIVITIES.
K. DECIDUOUS TREES WILL HAVE UNIFORM CROWN AND FORM AND BE
EVENLY LIMBED TO A MINIMUM HEIGHT ABOVE GRADE OF 5'-0",
UNLESS OTHERWISE SPECIFIED. TREES WITHIN LAWN AREAS TO HAVE
MIN. 5' DIAMETER SHREDDED HARDWOOD MULCH TREE RING.
L. ALL PLANTING BEDS TO RECEIVE 3" MINERAL MULCH AND STEEL EDGE
PER SPEC SECTION 329300.
A. THIS EROSION CONTROL PLAN SHALL BE CONSIDERED A MINIMUM
APPLICATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROMPTLY AND PROPERLY ADDRESSING UNFORESEEN EROSION IN
ACCORDANCE WITH THE INDIANA STORM WATER QUALITY MANUAL.
CONTRACTOR SHALL KEEP AN UP-TO-DATE RECORD ONSITE OF ANY
ALTERATIONS TO THE STORM WATER POLLUTION PREVENTION PLAN.
B. CONTRACTOR SHALL NOTIFY THE JOHNSON COUNTY SOIL AND WATER
CONSERVATION DISTRICT AT LEAST 48 HOURS TO BEGINNING OF
CONSTRUCTION.
C. THE CONTRACTOR HAS FULL RESPONSIBILITY OF INSPECTING AND
MAINTAINING THE EROSION CONTROL MEASURES ON A DAILY BASIS.
AT A MINIMUM, PRACTICES NEED TO BE INSPECTED WEEKLY, WITHIN
24 HOURS AFTER EACH STORM EVENT OVER ½ INCH AND DAILY
DURING PROLONGED STORM EVENTS. FAILING PRACTICES SHALL BE
REPAIRED OR REPLACED IMMEDIATELY.
D. ANY SEDIMENT TRACKED OUT OF PROJECT AREA ONTO PUBLIC
STREETS MUST BE CLEANED UP THE SAME DAY IT OCCURS.
E. CONTRACTOR SHALL SUBMIT CONSTRUCTION STAGING PLAN
DETAILING ALL VEHICLE AND EQUIPMENT PARKING AREAS, FUELING
LOCATIONS, CONSTRUCTION TRAILER PLACEMENT, AND DESIGNATED
CONCRETE TRUCK WASHOUT AREAS.
F. IF CONSTRUCTION WINDOW EXTENDS THROUGH WINTER, TEMPORARY
MULCHING AS SPECIFIED IN CHAPTER 7 OF THE INDIANA
STORMWATER QUALITY MANUAL SHALL BE REQUIRED.
G. TEMPORARY SEEDING SHALL BE INSTALLED ON ANY CLEARED AREA
THAT WILL BE UNDISTURBED FOR 7 DAYS OR MORE.
H. THE CONTRACTOR SHALL CONTROL DUST ON SITE WHEN NECESSARY
USING METHODS WHICH COMPLY WITH THE INDIANA STORM WATER
QUALITY MANUAL.
I. CONTRACT RESPONSIBILITY CORRESPONDS TO BID PACKAGE
INDICATED IN SILT FENCE CALLOUT. IF DAMAGED, SILT FENCE SHALL
BE REPAIRED/REPLACED BY CONTRACTOR RESPONSIBLE FOR DAMAGE
AND SHALL NOT BE SUBMITTED FOR PAYMENT. IF RESPONSIBLE
CONTRACTOR HAS COMPLETED WORK AND COMPLETELY REMOVED
FROM THE SITE, RESPONSIBILITY OF PROVIDING AND MAINTAINING
NEW SILT FENCE SHALL FALL ON ADJACENT CONTRACTOR.
GENERAL EROSION CONTROL NOTES
1. TEMPORARY CONSTRUCTION ENTRANCES SHALL BE PLACED PRIOR TO
EARTH DISTURBANCE AND SHALL REMAIN IN PLACE UNTIL PERMANENT
PAVEMENT IS INSTALLED.
2. SILT FENCE SHALL BE SET IN PLACE BEFORE ANY OF THE SOIL TO BE
CONTAINED BY THE FENCE IS DISTURBED. FENCE IS TO REMAIN AND
BE MAINTAINED UNTIL THE SITE IS STABILIZED WITH FINAL GROUND
COVER.
3. CHECK DAMS SHALL BE SET IN PLACE AT COMPLETION OF GRADING OF
DITCH. CHECK DAMS ARE TO REMAIN AND BE MAINTAINED UNTIL THE
CONTRIBUTING AREA IS STABILIZED.
4. CATCH BASIN PROTECTION SHALL BE PLACED IMMEDIATELY UPON
INSTALLATION OF STRUCTURE. PROTECTION IS TO REMAIN AND BE
MAINTAINED UNTIL PAVEMENT, CURB AND PLANTING AREA ARE
RESTORED.
5. SOIL STABILIZATION MEASURES (PERMANENT SEEDING AND EROSION
CONTROL BLANKET) SHALL BE INSTALLED IMMEDIATELY FOLLOWING
FINISH GRADING AND TOP SOIL PLACEMENT TO MINIMIZE EROSION
AND SHALL OCCUR IN STAGES AS ANY GIVEN AREA IS COMPLETED.
6. TEMPORARY MEASURES CAN BE REMOVED ONCE 70% DENSITY OF
PERMANENT VEGETATION IS ESTABLISHED OR ANOTHER STABILIZATION
MEASURE SUCH AS PAVEMENT IS IN PLACE. ALL TEMPORARY MEASURES
SHALL BE REMOVED AND RESTORED FOLLOWING STABILIZATION PER
THE DETAILS ON C5.2 AND THE INDIANA STORMWATER QUALITY
MANUAL.
SOIL EROSION & SEDIMENTATION
CONTROL TIMELINE
LEGEND
TEMPORARY PERIMETER PROTECTION - SILT FENCE
EXISTING CONTOUR
HYDROSEED TURF - SEE
SPECIFICATION SECTION 329200 FOR
ADDITIONAL INFORMATION.
STONE MULCH - SEE DETAIL SHEET C400
AND SPECIFICATION SECTION 329200
FOR ADDITIONAL INFORMATION.
# INDICATES BID PACKAGE, SEE GENERAL EROSION CONTROL NOTE I
E R
O S
I O
N
C
O N
T R
O L
A
S
T O
R A
T I O
N
P
L A
N
A. SEED ALL AREAS NOT IDENTIFIED ON THESE DRAWINGS DISTURBED BY
CONSTRUCTION/INSTALLATION ACTIVITIES IN ACCORDANCE WITH
SPECIFICATION SECTION 329200.
B. CLEAR AND GRUB ALL AREAS DESIGNATED FOR PROPOSED
PLANTING/IMPROVEMENTS AS NECESSARY TO INSTALL PROPOSED
LAWN AND/OR PLANTINGS.
C. REPLACE/REPAIR STONE MULCH AREAS DISTURBED BY CONSTRUCTION.
GENERAL PLANTING NOTES
J L
P
J L P
J L
P
J N
J
S T
A N
D A
T
A I L S
BROOM FINISH AS SPECIFIED
TRANSVERSE JOINT
1/2" PJF
PLAN
SEE NOTES BELOW
S E E
D
R A W
I N
G S
COMPACTED SUBGRADE
CONCRETE PAVEMENT
NOTES:
1. CONTRACTOR TO PLACE FORM WORK, COMPACT SUBGRADE MECHANICALLY TO A MINIMUM OF 100%
STANDARD PROCTOR, PLACE AND COMPACT BASE MEETING INDOT NO. 53 STONE SPECIFICATIONS TO
A MINIMUM OF 100% STANDARD PROCTOR, DEPOSIT CONCRETE INTO FORMS, LEVEL, AND TAMP
SUFFICIENTLY TO BRING MORTAR TO SURFACE, BEFORE FINISHING WITH A WOOD FLOAT. MEDIUM
BROOM FINISH. EDGES TO BE ROUNDED WITH APPROVED EDGER. SCORE (SAW CUT) CONTRACTION
JOINTS 1/4 THICKNESS OF PAVEMENT. LAYOUT JOINTING AT INTERVALS AS SHOWN ON PLANS AND
PER SPECIFICATIONS.
2. PROVIDE PREFORMED EXPANSION JOINT FILLER 1/2" THICK, BETWEEN CONCRETE AND ANY FIXED
STRUCTURE, INCLUDING CURBS, PAVEMENT, AND BUILDINGS, OR WHERE INDICATED, AS WELL AS
BETWEEN RADIUS POINTS, SEPARATE POURS, AND WHERE BREAK IS 30° OR MORE. PJF SHALL BE
HOMEX 300, HOMASOTE, OR OTHER CONFORMING TO AASHTO M-33 OR M-213. RECESS JOINT AND
CAULK WITH SEALANT FOR ALL EXPANSION JOINTS. SEE SPECIFICATION SECTIONS 321313 AND
321373.
3. UNIFORMLY DISPERSE FIBRILLATED POLYPROPYLENE FIBER AT 1.5 LB/CU. YD. PER THE REQUIREMENTS
OF SPEC SECTION 321313.
4" COMPACTED AGGREGATE
BASE COURSE
SIDEWALK SECTION
3 1/2" (385#/SQ. YD.) HMA BASE, TYPE B
1 1/2" (165#/SQ YD.) HMA SURFACE, TYPE B
SUBGRADE -
COMPACTED PER
SPECS.
2" COMPACTED INDOT NO. 53
AGGREGATE BASE COURSE
6" COMPACTED INDOT NO. 2
AGGREGATE BASE COURSE
NOTES:
1. CONTRACTOR TO COMPACT SUBGRADE MECHANICALLY TO A
MINIMUM OF 100% STANDARD PROCTOR, PLACE AND
COMPACT BASE MEETING INDOT NO. 53 STONE
SPECIFICATIONS TO A MINIMUM OF 100% STANDARD
PROCTOR.
2. SEE SPECIFICATION SECTION 321216.
3. SEE 9/SD3.2 FOR EDGE TREATMENT.
COMPACTED SUBGRADE
6" COMPACTED INDOT #53 AGGREGATE
3" COMPACTED INDOT #11 AGGREGATE
STRAW BALE
BINDING WIRE
10 MIL PLASTIC LINING
STAPLES (2 PER BALE)
" DIA. STEEL WIRE IN U 2"X4".
WOOD OR METAL STAKES (2 PER BALE)
STRAW BALE, TYP.
STAKE, TYP.
10 MIL PLASTIC
LINING TYP.
NOTES:
1. INSTALL CONCRETE WASHOUT SIGN WITHIN 30' OF TEMPORARY WASHOUT
FACILITY.
2. LAYOUT OF WASHOUT FACILITY MAY VARY DEPENDING ON SPACE AVAILABLE
WITHIN CONSTRUCTION STAGING AREA. WASHOUT FACILITIES SHALL BE
DESIGNATED BY THE PERMIT HOLDER BEFORE WORK BEGINS AND SHALL BE
LOCATED IN AN APPROPRIATE AREA WHERE THE WASTE RESULTING FROM
THE WASHOUT CANNOT ENTER SEWER SYSTEMS OR LOCAL WATERWAYS.
3. INSPECT DAILY AND AFTER EACH STORM EVENT FOR INTEGRITY OF OVERALL
SYSTEM, LEAKS, SPILLS, TRACKING BY EQUIPMENT AND TEARS OR
PUNCTURES OF LINING.
4. REMOVE WASTE WHEN SYSTEM REACHES 50% CAPACITY. WASTE FROM THE
WASHOUT FACILITIES SHALL BE DISPOSED OF IN AN APPROVED MANNER
ACCORDING TO STATE LAWS. REINSPECT SYSTEM PRIOR TO NEXT USE.
REPLACE LINER AFTER EVERY CLEANING.
5. ENFORCE USE OF WASHOUT BY ALL SITE PERSONNEL AND SUPPLIERS.
GEOTEXTILE FABRIC
N
N
8" MIN. INDOT NO. 2 AGGREGATE
P
U
B
L
A
D
NOTES:
1. FOR ADDITIONAL INSTALLATION, AND MAINTENANCE REQUIREMENTS, SEE INDIANA STORMWATER
QUALITY MANUAL, CHAPTER 7, SITE ACCESS AND PREPARATION.
2. CONTRACTOR SHALL INSPECT DAILY. RESHAPE AND TOP DRESS WITH CLEAN AGGREGATE AS NEEDED.
3. IMMEDIATELY REMOVE ANY MUD OR SEDIMENT TRACKED OR WASHED ONTO PUBLIC ROADS.
6"
4"-6"
6"
12"
NOTES:
1. PREPARE SOIL BEFORE INSTALLING BLANKETS, INCLUDING ANY NECESSARY APPLICATION OF LIME, FERTILIZER, AND SEED.
2. BEGIN AT THE TOP OF THE SLOPE BY ANCHORING THE BLANKET IN A 6" DEEP X 6" WIDE TRENCH WITH APPROXIMATELY
12" OF BLANKET EXTENDED BEYOND THE UP-SLOPE PORTION OF THE TRENCH. ANCHOR THE BLANKET WITH A ROW OF
STAPLES/STAKES APPROXIMATELY 12" APART IN THE BOTTOM OF THE TRENCH. BACKFILL AND COMPACT THE TRENCH
AFTER STAPLING. APPLY SEED TO COMPACTED SOIL AND FOLD REMAINING 12" PORTION OF BLANKET BACK OVER SEED
AND COMPACTED SOIL. SECURE BLANKET OVER COMPACTED SOIL WITH A ROW OF STAPLES/STAKES SPACED
APPROXIMATELY 12" APART ACROSS THE WIDTH OF THE BLANKET.
3. ROLL THE BLANKETS (A.) DOWN OR (B.) HORIZONTALLY ACROSS THE SLOPE. BLANKETS WILL UNROLL WITH APPROPRIATE
SIDE AGAINST THE SOIL SURFACE. ALL BLANKETS MUST BE SECURELY FASTENED TO SOIL SURFACE BY PLACING
STAPLES/STAKES IN APPROPRIATE LOCATIONS AS PER BY MANUFACTURER'S RECOMMENDATION.
4. THE EDGES OF PARALLEL BLANKETS MUST BE STAPLED WITH APPROXIMATELY 3"-5" OVERLAP. ON BLANKET TYPE. TO
ENSURE PROPER SEAM ALIGNMENT, PLACE THE EDGE OF THE OVERLAPPING BLANKET (BLANKET BEING INSTALLED ON
TOP) EVEN WITH THE COLORED SEAM STITCH ON THE PREVIOUSLY INSTALLED BLANKET.
5. SPLICING CONSECUTIVE BLANKETS DOWN THE SLOPE SHALL BE DONE IN A SHINGLE STYLE WITH THE UP-SLOPE BLANKET
OVERLAPPING THE DOWN-SLOPE BLANKET 3" MINIMUM. STAPLE THROUGH OVERLAPPED AREA, APPROXIMATELY 12"
APART ACROSS ENTIRE BLANKET WIDTH.
6. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
7. IN LOOSE SOIL CONDITIONS THE USE OF STAPLE OR STAKE LENGTHS GREATER THAN 6" MAY BE NECESSARY TO PROPERLY
SECURE THE BLANKETS.
8. MANUFACTURER: NORTH AMERICAN GREEN MODEL: S150 OR EQUAL.
PERIMETER CONTROL
WATER FLOW
JOINING FENCES
STAKE INSTALLATION
G
R
A
D
E
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
2. INSTALL FENCING BY DIGGING A 6" DEEP TRENCH ALONG PROPOSED FENCE LINE. POUND STAKES IN TRENCH 6"- 8"
OR UNTIL SECURE. BE SURE TO STRETCH FABRIC TAUT WHEN POUNDING STAKES. DRAPE LOOSE END OF GEOTEXTILE
FABRIC INTO TRENCH. BACKFILL AND COMPACT SOIL ON BOTH SIDES.
3. JOIN FENCES BY PLACING THE END POST OF THE SECOND FENCE INSIDE THE END POST OF THE FIRST FENCE.
ROTATE BOTH POSTS AT LEAST 180° IN A CLOCKWISE DIRECTION TO CREATE A TIGHT SEAL WITH THE FABRIC
MATERIAL. DRIVE BOTH POSTS ABOUT 10" INTO THE GROUND AND BURY FLAP.
4. INSPECT WITHIN 24 HOURS OF A RAIN EVENT AND ATLEAST ONCE EVERY SEVEN DAYS. IF FENCE FABRIC TEARS, STARTS TO DECOMPOSE, OR IN ANYWAY BECOMES INEFFECTIVE, REPLACE THE AFFECTED PORTION IMMEDIATELY.
5. REMOVE DEPOSITED SEDIMENT WHEN IT IS CAUSING THE FILTER FABRIC TO BULGE OR WHEN IT REACHES ONE-HALF
THE HEIGHT OF THE FENCE AT IT'S LOWEST POINT. WHEN THE CONTRIBUTING DRAINAGE AREA HAS BEEN
STABILIZED, REMOVE THE FENCE AND SEDIMENT DEPOSITS, GRADE THE SITE TO BLEND WITH THE SURROUNDING
AREA AND STABILIZE.
FABRIC
STAKE
6"X6" TRENCH
WITH BACKFILL
FABRIC
EXTENDS
INTO
TRENCH
UNDISTURBED
AREA OF SITE
POST
FABRIC
POST
FABRIC
GRADE
INSTALLATION INSTRUCTIONS:
1. REMOVE THE GRATE FROM THE CASTING OR CONCRETE
DRAINAGE STRUCTURE.
2. CLEAN THE LEDGE OF THE CASTING FRAME OR DRAINAGE
STRUCTURE TO ENSURE IT IS FREE OF STONE AND DIRT.
3. DROP INLET FILTER THROUGH THE CLEAR OPENING AND BE
SURE THE SUSPENSION HANGERS REST FIRMLY ON THE INSIDE
LEDGE OF THE CASTING.
4. REPLACE THE GRATE AND CONFIRM IT IS ELEVATED NO MORE
THAN 1/8”, WHICH IS THE THICKNESS OF THE STEEL HANGERS.
MAINTENANCE GUIDELINES:
1. CONSTRUCTION SITE INSPECTION SHOULD OCCUR FOLLOWING
EACH ½” OR MORE RAIN EVENT.
2. EMPTY THE SEDIMENT BAG IF MORE THAN HALF FILLED WITH
SEDIMENT AND DEBRIS.
3. REMOVE THE GRATE, ENGAGE THE LIFTING BARS OR HANDLES
AND LIFT FROM THE DRAINAGE STRUCTURE.
4. DISPOSE OF THE SEDIMENT OR DEBRIS AS DIRECTED BY THE
ENGINEER OR MAINTENANCE CONTRACT IN ACCORDANCE WITH
EPA GUIDELINES.
5. REMOVE ANY CAKED ON SILT FROM THE SEDIMENT BAG AND
REVERSE FLUSH THE BAG WITH MEDIUM SPRAY FOR OPTIMAL
FILTRATION.
6. REPLACE THE BAG IF TORN OR PUNCTURED TO ½” DIAMETER
OR GREATER ON THE LOWER HALF OF THE BAG.
7. DISPOSE OF ALL OIL CONTAMINATED PRODUCTS IN
ACCORDANCE WITH EPA GUIDELINES.
INLET GRATE
INLET FILTER -
PRODUCT TO BE
FLEXSTORM INLET
FILTER BY INLET &
PIPE PROTECTION, INC.
OR APPROVED EQUAL.
CASTING LEDGE
D R
A W
I N
G
N
U M
B E
R
A
P R
O J
E C
T
N
U M
B E
R
D A
T E
A P
P R
V D
D E
S I G
N E
D
D R
A W
N
C H
K D
M A
Y
C I V
I L
E D
I N
B U
R G
H
N O
R
E V
I S
I O
N D
A T
E
C A
T
E R
B U
I N
T
M
A N
E U
V E
R
T
R A
I N
I N
G
C
E N
T E
R
B O
Q
B
A R
R A
C K
S
R
E N
O V
A T
I O
N
P
H A
Z
IN
DI
AN
A, LC
J L
P
J L P
J L
P
J N
J
S T
A N
D A
T
A I L S
M
I N
O.D.
5' OR LESS
M
I N
O.D.
GREATER
THAN 5'
NOTES:
ALL BEDDING AND INITIAL
BACKFILL SHALL BE
INSTALLED IN 6" TO 12"
BALANCED LIFTS.
A MINIMUM OF 9" OF
CLEARANCE SHALL BE
PROVIDED ON EACH SIDE
OF THE INSTALLED PIPE.
BEDDING AND BACKFILL
FOR WATER MAINS SHALL
BE SAND IN LIEU OF #8
CRUSHED STONE.
WITHIN 5' OF EDGE OF PAVEMENT GREATER THAN 5' FROM EDGE OF
PAVEMENT
'B' BORROW OR EQUIV. GRANULAR
MATERIAL COMPACTED TO 95%
STANDARD PROCTOR MAX.
DENSITY
MINIMUM TRENCH WIDTH
1.25X(O.D.) + 12"
# 8 CRUSHED STONE OR
APPROVED EQUIVALENT.
CLASS 1 BEDDING MATERIAL
HAND TAMPED OR WALKED
INTO PLACE.
PIPE, SEE SITE PLAN
FOR TYPE AND SIZE
MIN. 6" TOPSOIL TO ENSURE GRASS
GROWTH IF NOT UNDER PAVEMENT
E.O.P., CURB, GUTTER
OR SIMILAR STRUCTURE
E.O.P., CURB, GUTTER, OR
SIMILAR STRUCTURE
MIN. 6" TOPSOIL TO ENSURE
GRASS GROWTH
REGULAR
BACKFILL
MINIMUM TRENCH WIDTH
1.25X(O.D.) + 12"
#8 CRUSHED STONE OR
APPROVED EQUIVALENT.
CLASS 1 BEDDING MATERIAL
HAND TAMPED OR WALKED
INTO PLACE.
PIPE, SEE SITE PLAN
FOR TYPE AND SIZE
THRUST BLOCKING, AS REQUIRED
AS REQ'D
FINISH GRADE
PROPOSED SEWER PIPE
CROSSING
CENTER 20' LENGTH OF
WATER MAIN
WATER
MAIN
M
I N
C L E A R
WATER MAIN
WATER MAIN
SAND BACKFILL
WATER MAIN ON PROPOSED STORM CROSSING
3' MAXIMUM
SAME SIZE AS SEWER SERVICE
45° "WYE" BRANCH
NOTES:
1. LOCATE CLEAN-OUT SUCH THAT PLUG IS NOT LOCATED
IN SIDEWALK UNLESS DIRECTED OTHERWISE.
2. IN NON-TRAFFIC AREAS, TOP OF CLEAN-OUT SHALL
REQUIRE AN ADAPTER AND A THREADED PLUG.
3. IN CONCRETE OR ASPHALT ROADWAYS OR SIDEWALKS,
CLEANOUT AND PLUG TO BE LOCATED WITHIN A
CASTING. CASTING FRAME AND LID TO BE NEENAH
#R-1975 OR APPROVED EQUAL.
4. ALL SANITARY SEWERS SHALL BE DESIGNED AND
INSTALLED IN ACCORDANCE WITH THE RECOMMENDED
STANDARDS FOR WASTEWATER FACILITIES BY THE
GREAT LAKES-UPPER MISSISSIPPI RIVER BOARD OF
STATE AND PROVINCIAL PUBLIC HEALTH AND
ENVIRONMENTAL MANAGERS. SANITARY SEWERS
SHALL BE APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT.
5. THE CONTRACTOR OR DEVELOPER SHALL PROVIDE THE
OWNER WITH "AS BUILT" DRAWINGS OF ALL SANITARY
SEWER AND SERVICES.
6. ALL NEW SERVICE CONNECTIONS TO MAIN LINE
SEWERS SHALL REQUIRE A PERMIT AND TAPPING FEES.
B L D
G
W
A L L
CONC. PAD O.D.
SHALL EQUAL
JACKET O.D. PLUS
18" WITH AN 8" MIN.
THICKNESS
45° ELBOW
M
I N
GRADE
TARRED FELT DISK
8" MIN.
SANITARY/STORM
SEWER FROM
BUILDING
45°
1' MINIMUM
PVC CLEAN-OUT ADAPTER AND
THREADED PLUG UNLESS OTHERWISE
DIRECTED OR AS NOTED BELOW
D R
A W
I N
G
N
U M
B E
R
A
P R
O J
E C
T
N
U M
B E
R
D A
T E
A P
P R
V D
D E
S I G
N E
D
D R
A W
N
C H
K D
M A
Y
C I V
I L
E D
I N
B U
R G
H
N O
R
E V
I S
I O
N D
A T
E
C A
T
E R
B U
I N
T
M
A N
E U
V E
R
T
R A
I N
I N
G
C
E N
T E
R
B O
Q
B
A R
R A
C K
S
R
E N
O V
A T
I O
N
P
H A
Z
IN
DI
AN
A, L
LC
NOTE: THOROUGHLY CLEAN EXISTING MAIN AT PROPOSED
CONNECTION BEFORE ATTACHING TAPPING SLEEVE
EXISTING
WATER MAIN
TAPPING SLEEVE
JOINT FLANGE
MECHANICAL
JOINT FLANGE
MECHANICAL
NEW WATER MAIN
W/VALVE BOX
TAPPING VALVE
STAINLESS STEEL
EXISTING
WATER MAIN
1) LOAD TYPE UNIFORM (PSF) CONCENTRATED (POUNDS)
2) ROOF LIVE LOAD 20 300
3) FLOOR LIVE LOAD 100 2000
4) CORRIDORS AT FIRST FLOOR 100
5) MECHANICAL AREAS 125
6) LIVE LOAD REDUCTION NOT USED
1. GENERAL
A. THE INFORMATION ON THIS SHEET SHALL APPLY TO ALL CONSTRUCTION DOCUMENTS.
B. INFORMATION ON THIS SHEET SUPPLEMENTS THE PROJECT SPECIFICATIONS. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
C. NUMEROUS OPENINGS ARE REQUIRED THROUGH THE ROOF. SEE ALL OTHER TRADES' DRAWINGS FOR SIZE AND EXACT LOCATION OF ALL
PENETRATIONS. PENETRATIONS LESS THAN 12" MAY NOT ALL BE INDICATED ON STRUCTURAL DRAWINGS. PENETRATIONS LESS THAN 12" SHALL
HAVE AT LEAST 1'-0" CLEAR BETWEEN OPENINGS, UNLESS APPROVED IN WRITING BY THE SER.
D. UNLESS OTHERWISE NOTED, ALL DETAILS, SECTIONS AND NOTES ON THE DRAWINGS ARE INTENDED TO INDICATE DESIGN INTENT AND ARE TO BE
TYPICAL FOR SIMILAR SITUATIONS ELSEWHERE.
E. THESE DRAWINGS ARE NOT TO BE USED FOR SHOP DETAILING UNLESS SPECIFICALLY STAMPED BY THE STRUCTURAL ENGINEER ON THE
DRAWINGS “FOR DETAILING”. THESE DRAWINGS ARE NOT TO BE REPRODUCED FOR THE PURPOSE OF USING THEM AS SHOP DRAWINGS. ANY
SHOP DRAWINGS SUBMITTED WITH COPIES OF THESE DRAWINGS WITHOUT PRIOR APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD WILL
BE REJECTED AND RESUBMITTAL WILL BE REQUIRED.
F. THE INFORMATION CONTAINED ON THE STRUCTURAL DRAWINGS IS IN ITSELF INCOMPLETE AND VOID UNLESS USED IN CONJUNCTION WITH ALL
OTHER DISCIPLINE DRAWINGS, THE SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE STANDARDS, CODES, ETC.
G. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF SHOP DRAWINGS OR PERIODIC OBSERVATION OF
CONSTRUCTION, FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE CONFIRMED AND CORRELATED ON THE JOB SITE
AND BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR FABRICATION PROCESSES AND CONSTRUCTION TECHNIQUES (INCLUDING
EXCAVATION, SHORING, SCAFFOLDING, BRACING, ERECTION, FORMWORK, ETC.), FOR COORDINATION OF THE VARIOUS TRADES, AND FOR SAFE
CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD CONDITIONS RELATIVE TO THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE
ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT PROGRESS UNTIL WRITTEN PERMISSION FROM THE ENGINEER IS OBTAINED.
H. EXISTING FINISH ELEVATION IS SHOWN AS EQUAL TO 100'-0" AS USED IN THE STRUCTURAL DRAWINGS.
I. WHERE CONFLICTS OR DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS EXIST THE CONTRACTOR SHALL NOTIFY THE ENGINEER
IMMEDIATELY FOR CLARIFICATION. THE CONTRACTOR SHALL NOT ASSUME ANY ITEM TAKES PRECEDENCE OVER THE OTHER. ANY ACTION THE
CONTRACTOR MAKES PRIOR TO NOTIFICATION SHALL BE AT THE CONTRACTOR'S RISK.
J. THESE DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS. IF THE DIMENSIONS CANNOT BE DETERMINED BY THE INFORMATION GIVEN, CONTRACTOR SHALL CONTACT ENGINEER FOR REQUIRED INFORMATION.
K. SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN
ACCORDANCE WITH THE STRUCTURAL CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT BE CONSTRUED AS EXHAUSTIVE
OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE OWNER AGAINST
DEFECTS OR DEFICIENCIES IN THE WORK OF THE CONTRACTOR.
L. THE DRAWINGS, SPECIFICATIONS, BIM MODEL AND OTHER DOCUMENTS PREPARED BY DLZ INDIANA, LLC (DLZ) FOR THIS PROJECT ARE
INSTRUMENTS OF THE ENGINEER'S SERVICE, AND MAY BE USED SOLELY WITH RESPECT TO THE PROJECT AND, UNLESS OTHERWISE PROVIDED, THE ENGINEER SHALL BE DEEMED THE AUTHOR OF THESE PLANS AND RETAINS ALL COMMON LAW RIGHTS, TITLES AND INTEREST THEREIN. THE
OWNER SHALL BE PERMITTED TO RETAIN COPIES, INCLUDING REPRODUCIBLE COPIES, OF THE ENGINEER'S DRAWINGS, SPECIFICATIONS OTHER
DOCUMENTS FOR INFORMATION AND REFERENCE IN CONNECTION WITH THE OWNER'S USE AND OCCUPANCY OF THE PROJECT. DLZ SHALL NOT
BE LIABLE FOR ANY HARM OR DAMAGE SUFFERED BY ANY PARTY BY REASON OF THE UNAUTHORIZED USE OF THESE PLANS. DLZ EXPRESSLY
RESERVES ITS COPYRIGHTS IN THESE PLANS. THESE PLANS MAY NOT BE REPRODUCED, CHANGED, OR COPIED IN ANY FORM OR MANNER
WHATSOEVER, NOR MAY THEY BE ASSIGNED OR OTHERWISE MADE AVAILABLE TO ANY THIRD PARTY WITHOUT FIRST OBTAINING THE EXPRESS
WRITTEN CONSENT OF DLZ.
M. DO NOT INSTALL CONDUIT IN SLABS ON GRADE OR CONCRETE WALLS UNLESS EXPLICITLY SHOWN OR NOTED ON THE STRUCTURAL DRAWINGS.
N. DO NOT SUSPEND ANY ITEMS, SUCH AS DUCTWORK, MECHANICAL OR ELECTRICAL FIXTURES, CEILINGS, ETC. FROM WOOD ROOF SHEATHING.
O. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION, AND REMOVAL OF ALL TEMPORARY BRACING AND CONSTRUCTION
SUPPORTS, FOR NEW AND EXISTING STRUCTURES, AS NECESSARY TO COMPLETE THE PROJECT. NO PORTION OF THE PROJECT, WHILE UNDER
CONSTRUCTION, IS INTENDED TO BE STABLE IN THE ABSENCE OF THE CONTRACTOR'S TEMPORARY BRACES AND SUPPORTS UNTIL ALL OF THE
STRUCTURAL ELEMENTS, INCLUDING THE MASONRY/CONCRETE WALLS, WOOD ROOF DECK, AND SLABS-ON-GRADE ARE IN PLACE AND FULLY
CONNECTED AS INDICATED ON THESE DRAWINGS. CONTRACTOR SHALL RETAIN A LICENSED PROFESSIONAL ENGINEER TO DESIGN ALL
TEMPORARY BRACING AND CONSTRUCTION SUPPORTS.
2. DESIGN DATA
A. DESIGN CODE:
1) ALL DESIGN IS IN CONFORMANCE WITH THE 2016 UNIFIED FACILITIES CRITERIA (2015 INTERNATIONAL BUILDING CODE) (UFC). RISK CATEGORY
IS TYPE II.
B. DESIGN DEAD LOADS: WEIGHT OF ALL MATERIALS OF CONSTRUCTION INCORPORATED INTO THE BUILDING INCLUDING BUT NOT LIMITED TO
WALLS, FLOORS, ROOFS, CEILINGS, BUILT IN PARTITIONS, FINISHES, CLADDING, EQUIPMENT AND OTHER SIMILARLY INCORPORATED ITEMS AND
EQUIPMENT.
1) ROOF TOP CHORD - 15 PSF
2) ROOF BOTTOM CHORD - 10 PSF
C. DESIGN LIVE LOADS
D. WIND LOADING CRITERIA
1) ULTIMATE 3-SECOND WIND SPEED V=115 MPH
2) EXPOSURE B
3) GCPI=±0.18 (ENCLOSED STRUCTURES)
E. SNOW LOADING CRITERIA
1) PG=20 PSF
2) PF=16 PSF
3) I=1.0
4) CE=0.9
5) CT=1.2
F. SEISMIC DESIGN CRITERIA
1) I=1.0
2) SS =0.173
3) S1 =0.092
4) SDS=0.185
5) SD1=0.147
6) SITE CLASS D (ASSUMPTION MADE WITHOUT GEOTECHNICAL REPORT BASED ON ALLOWABLE SOIL PROPERTIES IN IBC 2015)
7) SEISMIC DESIGN CATEGORY B
8) BASIC SEISMIC FORCE RESISTING SYSTEM - ORDINARY REINFORCED MASONRY SHEAR…