Drawings 621-23-109 Install Lightning Protection and Grounding Systems _Part3.pdf
PDF 3 MB Posted
- Attached to
- Z1DA--621-23-2-5620-0001 - 621-23-109 - Install Lightning Protection & Grounding Systems
- Solicitation number
- 36C24923B0002
About this file
This document package includes construction drawings and specifications for installing new lightning protection and grounding systems at multiple buildings on the James H. Quillen VA Medical Center campus in Mountain Home, Tennessee. The scope of work involves installing surge protection devices and upgrading grounding systems at main electrical panels in Buildings 69, 77, 200, 204, 205, and 208 of the campus. It also specifies installing air terminals, down conductors, ground rods, and bonding details to provide complete lightning protection for the building roofs. The solicitation number for this opportunity is 36C24923B0002 and is seeking offers for the work defined in drawings E-305 through E-502 by June 2022. The Department of Veterans Affairs is the contracting agency.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs
621-22-117
JUNE 2022
LIGHTNING PROTECTION &
GROUNDING STUDY
BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,
200 COMPLEX (69, 77, 200, 204, 205) 201, 208
JAMES H. QUILLEN VA MEDICAL CENTER
MOUNTAIN HOME, TN
Office of Construction and Facilities Management
MAIN ELECTRICAL PANEL MAPS (200 Complex – 69, 77 & 200)
1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (69-0-A, 208 VOLTS, 400 AMPS). PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (69-0-B, 208 VOLTS, 400 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. UTILIZE THE JUNCTION NEXT TO THE MAIN PANELS AND MOUNT ON WALL. IN THE EVENT THAT ONE PANEL IS FED FROM THE OTHER, PROVIDE THE SECOND SPD AS SPARE
PARTS TO COR. SEE GENERAL NOTE 10 & 12.
2. NO GROUND BUS BAR WILL BE PROVIDED FOR THIS BUILDING SINCE THE PANELS FOR B69 ARE FED FROM B77.
SCALE:SCALE:
BUILDING 77 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS
N.T.S. E-305
1. PROVIDE 2 NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (M77A, 480 VOLTS, 1600 AMPS & M77B, 480 VOLTS, 1600 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE
GENERAL NOTE 10 & 12.
2. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 AND 12.
3. THE SWITCHGEAR FEEDING B77 IS LOCATED IN THE BASEMENT OF B204.
4. SEE GENERAL NOTE 13.
1. PROVIDE NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MSG-200, 480 VOLTS, 3200 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
3. PROVIDE A NEW TYPE 1, 240 KA SPD FOR GENERATOR #1 BREAKER (480 VOLTS, 1800 AMPS). CONNECT TERMINALS OF SPD ON GENERATOR FEED TO BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
4. PROVIDE A NEW TYPE 1, 240 KA SPD FOR GENERATOR #2 BREAKER (480 VOLTS, 1800 AMPS). CONNECT TERMINALS OF SPD ON GENERATOR FEED TO BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
5. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 & 12.
6. SEE GENERAL NOTE 13
SCALE:SCALE:
BUILDING 69 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS
N.T.S. E-305
SCALE:SCALE:
BUILDING 200 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS
N.T.S. E-305
GENERAL NOTES
GENERATORS MSG-200
MSBA PANEL
PANELS 69-0-A & 69-0-B
69-0-A 69-0-B
PANEL
MSG-200
PANELS
E-305
CAS
N
N
N
29 33
NOTE: LOOK AT B204 FOR LOCATION
RLSEPT. 2022
Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs
621-22-117
JUNE 2022
LIGHTNING PROTECTION &
GROUNDING STUDY
BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,
200 COMPLEX (69, 77, 200, 204, 205) 201, 208
JAMES H. QUILLEN VA MEDICAL CENTER
MOUNTAIN HOME, TN
Office of Construction and Facilities Management
MAIN ELECTRICAL PANEL MAPS (200 Complex – 204 & 205, 208)
GENERAL NOTES
1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (SWBD 204-XSB, 480 VOLTS, 2000 AMPS).
CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
2. PROVIDE A NEW TYPE 1, 240 KA SPD FOR EQUIPMENT PANEL (480 VOLTS, 400 AMPS). CONNECT TERMINALS OF
SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
3. PROVIDE A NEW TYPE 1, 240 KA SPD FOR LIFE SAFETY PANEL (480 VOLTS, 400 AMPS). CONNECT TERMINALS OF
SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
4. PROVIDE A NEW TYPE 1, 240 KA SPD FOR CRITICAL SERVICES PANEL (480 VOLTS, 400 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
5. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 & 12.
6. SEE GENERAL NOTE 13.
N
SCALE:SCALE:
BUILDING 204 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS
N.T.S. E-306
1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MDP-205, 480 VOLTS, 1200 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.
2. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 & 12.
3. SEE GENERAL NOTE 13
N
SCALE:SCALE:
BUILDING 205 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS
N.T.S. E-306
MDP
B77 CRITICAL
PANEL,
EQUIPMENT
PANEL, LIFE
SAFETY PANEL
PANEL MDP &
GENERATOR
PANEL
CRITICAL PANEL
EQUIPMENT PANEL
LIFE SAFETY PANEL
N
SCALE:SCALE:
BUILDING 208 - MAIN ELECTRICAL PANEL MAPS
N.T.S. E-306
1. PROVIDE 2 NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (SIDE A, 480 VOLTS, 1200 AMPS (MAIN LUGS ONLY) & SIDE B, 480 VOLTS, 1200 AMPS (MAIN LUGS ONLY)). CONNECT TERMINALS OF SPD ON SERVICE FEED TO
MAIN LUGS. SEE GENERAL NOTE 10 & 12.
2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL
NOTE 11 & 12.
SIDE BSIDE A
MAIN SWITCHBOARD
SIDE A & B
MAIN PANEL
E-306
CAS 30 33
SWDB 204-XSB
CRITICAL PANEL,
EQUIPMENT
PANEL, LIFE
SAFETY PANEL
RLSEPT. 2022
VHAMOULapoiL Rectangle
VHAMOULapoiL Text Box
NOT IN CONTRACT
MATCH LINE
B77 B69
B205
B204
B200
Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs
621-22-117
JUNE 2022
LIGHTNING PROTECTION &
GROUNDING STUDY
BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,
200 COMPLEX (69, 77, 200, 204, 205) 201, 208
JAMES H. QUILLEN VA MEDICAL CENTER
MOUNTAIN HOME, TN
Office of Construction and Facilities Management
MAIN ELETRICAL PANEL MAPS (Interconnection of Buss Bars)
COMPLEX 200
E-307
CAS 31 33
SCALE:SCALE:
B200 COMPLEX - GROUND BUS BAR INTERCONNECTIONS
N.T.S. E-307
FOR THE B200 COMPLEX PROVIDE A 4/0 BAR COPPER WIRE IN RIGID CONDUIT BETWEEN EACH NEW GROUND BUS.
1. CONTRACTOR SHALL DETERMINE ROUTE OF 4/0 WIRE TO NEW GROUND BUS (ABOVE CEILING) WITH COR'S APPROVAL. SUGGESTED ROUTE IS FROM THE SWITCHGEAR IN THE BASEMENT OF 204 (SWITCHGEAR FOR B77) UP TO THE SWITCHGEAR ON THE FIRST FLOOR OF 204, OVER TO THE MAIN DISTRIBUTION PANEL IN 205 AND
THEN DOWN THE HALL TO THE SWITCHGEAR IN 200.
2. IF RUN OF 4/0 CABLE IS OVER 250 FEET AND/OR MORE THAN 4(90-DEGREE) BENDS, INSTALL A JUNCTION BOX.
CONTRACTOR MUST ENSURE CONTINUITY OF THE CONDUIT FROM ONE END TO THE OTHER. PROVIDE GROUNDING TYPE TERMINATIONS FOR BOTH END AND OUT CONDUITS. PROVIDE A CONNECTION PER DETAIL 20 FOR EACH INSTANCE OF ENTRANCE AND EXIT FROM PULL BOX. INSTALL COVER WITHOUT CASKETS FOR A
GOOD METAL-TO-METAL CONNECTION.
3. AT THE GROUND BUS BARS, STOP RIGID CONDUIT WITHIN 1-FOOT OF THE BUS BAR. EXTEND CABLE WITH
2-HOLE CONNECTOR TO BUS BAR.
4. AT BOTH ENDS OF RIGID CONDUIT, INSTALL DEVICE THAT WILL BOND THE CABLE TO THE END OF THE RIGID
CONDUIT PER DETAIL 20.
GENERAL NOTES
N
B77 GROUND BUS
(BASEMENT)
B204 GROUND
BUS (FIRST
FLOOR)
B205 GROUND BUS
- GROUND FLOOR
B200 GROUND BUS
- GROUND FLOOR
PULL BOX
PULL BOX
SCALE:SCALE:
ROOF DRAIN GROUNDING
N.T.S. E-501
SCALE:SCALE: N.T.S. E-501
GROUND
ROD INSPECTION WELL DETAIL
SCALE:SCALE: N.T.S. E-501
5AIR TERMINAL PARAPET
SCALE:SCALE: N.T.S. E-501
3DOWNLEAD ROUTING DETAIL
SCALE:SCALE: N.T.S. E-501
4TYPICAL BONDING / SPLICING DETAILS
Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs
621-22-117
JUNE 2022
LIGHTNING PROTECTION &
GROUNDING STUDY
BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,
200 COMPLEX (69, 77, 200, 204, 205) 201, 208
JAMES H. QUILLEN VA MEDICAL CENTER
MOUNTAIN HOME, TN
Office of Construction and Facilities Management
E-501
CAS
ROOF
1" PVC PROTECTOR PIPE. ONE
REQUIRED PER EACH DOWNLEAD
TO EXTEND FROM 6'-0" ABOVE
GRADE TO BELOW GRADE. SEAL
ENDS OF PROTECTOR
PERMANENTLY WATER TIGHT
WITH DUCT SEAL.
LOOP TYPE PROTECTOR
PIPE ANCHOR SPACE
EVENLY IN A SIMILAR
MANNER AS SHOWN.
TRANSITION FROM ROOF
CONDUCTOR TO BARE COPPER
WIRE
"TURN" CONDUIT TO EXIT
BUILDING A MINIMUM OF
24" BELOW FINISHED
GRADE
COPPER DOWNLEAD CABLE.
COURSE CABLE BELOW GRADE.
CADWELD TO GROUND RING.
SEE LAYOUT FOR LOCATIONS.
SLAB ON
GRADE
1 BOLT PARALLEL
CLAMP
CROSS RUN
CONNECTOR
CABLE TO FLAT
METAL CLAMP
BONDING
PLATE
SECONDARY
BONDING LUG
IN-LINE
CONNECTOR
STRAP TYPE
PIPE CLAMP PIPE
GREATER THAN
3"Ø
U-BOLT TYPE
PIPE CLAMP
LESS THAN 3"Ø
CONDUCTOR
" M
IN
AIR TERMINAL
2'-0"
2" - 4"
RECOMMENDED
8" MAX.
PRIMARY BONDING CONDUCTOR
DRILL AND TAP ROOF DRAIN
FLANGE AND CONNECT BONDING
CONNECTOR TO DRAIN FLANGE
WITH STAINLESS STEEL BOLT
DOME ROOF DRAIN
THOMPSON #551
BONDING LUG WITH
3/8" BOLT HOLE
24"
12" MIN
TEST WELL AND COVER
#2 AWG BCW TINNED PIGTAIL
CADWELD TYPE GT
CLEAN SAND FILL
1"x4" SLOT IN
12" PVC PIPE
GROUND CONDUCTOR, SIZE
AS NOTED ON PLANS
DRIVEN COPPER CLAD
GROUND ROD 5/8" x 10'
(SEE NOTE)
NOTE:
TO IMPROVE SYSTEM RESISTANCE, ERICO GEM MAY BE USED
AS A BACKFILL MATERIAL IN AN AUGURED HOLE. PROVIDE
GROUND RODS TO ACHIEVE MAXIMUM 5 OHMS RESISTANCE.
2"
2"
2'-0" MIN
AIR TERMINAL
ADHESIVE BASE
ADHESIVE CABLE
FASTENER
SCALE:SCALE: N.T.S. E-501
LPS - ADHESIVE
BASE FOR HORIZONTAL SURFACE
SCALE:SCALE: N.T.S. E-501
8"
>8"
8"
ACCEPTABLE
NOT ACCEPTABLE
NOT ACCEPTABLE
.00
.00
>90.00°
CABLE BENDING DETAIL
2"
STAINLESS STEEL HARDWARE
5/16" DIAMETER HOLE PAIR
(TYP)
7/16" DIAMETER HOLE PAIR (TYP)
1 1/8" TYP
1"
5/8"
5/8"
TYPICAL TMGB DRILLED HOLE DIMENSIONS
COMPRESSION CONNECTOR W/
VIEWING WINDOW
1 1/2"
NOMINAL
INSULATOR
STAINLESS STEEL STANDOFF
BRACKET
ELECTRO-TIN PLATED
COPPER GROUND BAR
SCALE:SCALE: N.T.S. E-501
8MAIN GROUND BUS BAR
32 33
TYPICAL DETAILS
VARIES
5' - 8'
'Y' CONNECTOR
IN-LINE CONNECTOR
FROM ROOF
CONDUCTOR
TO ROOF
CONDUCTOR
2' AIR
TERMINAL
HEIGHT
INDICATED
ON
DRAWING
4 BOLT IN-LINE CONNECTOR (FOR
EASE OF MAINTENANCE ON
VENTILATOR)
PLACE FLAT BAR ACROSS
TOP IF NO SOLID OBJECT TO
MOUNT AIR TERMINAL ON
ROOF
CONDUCTOR
ROOF
CONDUCTOR
AIR TERMINAL
1. USE AIR TERMINAL BRACING DETAIL TO MOUNT AN AIR TERMINAL
NEXT TO THE ROTATING VENTILATOR.
2. TOP OF AIR TERMINAL MUST BE MINIMUM OF 18 INCHES ABOVE
TOP OF VENTILATOR.
3. AIR TERMINAL WILL BE HEIGHT OF ROTATING VENTILATOR PLUS 18
INCHES (IF 8 FEET HIGH PLUS 18 INCHES EQUALS 9 FEET 6 INCHES)
2'-0" AIR TERMINAL
'Y'
CONNECTOR
IN-LINE CONNECTOR
FROM ROOF
CONDUCTOR
TO ROOF
CONDUCTOR
2'-0"
AIR
TERMINAL
Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs
621-22-117
JUNE 2022
LIGHTNING PROTECTION &
GROUNDING STUDY
BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,
200 COMPLEX (69, 77, 200, 204, 205) 201, 208
JAMES H. QUILLEN VA MEDICAL CENTER
MOUNTAIN HOME, TN
Office of Construction and Facilities Management
TYPICAL DETAILS
SCALE:SCALE: N.T.S. E-502
9AIR TERMINAL STANDING SEAM MOUNT
SCALE:SCALE: N.T.S. E-502
LPS - AIR TERMINAL MOUNT
ROOF PEAK
SWIVEL
ADAPTER
CONDUCTOR
CLIP CABLE HOLDER
SWIVEL
ADAPTER
STANDING
SEAM POINT
BASE
STANDING
SEAM POINT
BASE
AIR
TERMINAL
2'-0"
AIR
TERMINAL
2'-0"
CONDUCTOR
CLIP CABLE
HOLDER
AIR TERMINAL
2'-0"
CABLE
FASTENER
SADDLE BASE
CONDUCTOR
E-502
CAS
SCALE:SCALE: N.T.S. E-502
21VENTILATOR DETAIL
2"
4" PVC
ROOF
CONDUCTOR
A SECTION
SCALE:SCALE: N.T.S. E-502
SUPPORT FOR ROOF
CONDUCTOR IN FREE AIR
SCALE:SCALE: N.T.S. E-502
AIR TERMINALS ON LARGE
MECHANICAL EQUIPMENT
BLOUNT TIP AIR
TERMINAL (TYPICAL)
MAIN SIZE COPPER
CONDUCTOR TO
ROOF CONDUCTOR
NOTE: TYPICAL FOR ROOFTOP AHU AND ERU EQUIPMENT.
EXOTHERMIC WELD TO
STRUCTURAL STEEL
MEMBERS FOR CREATE OF
NEW DOWN CONDUCTOR
PARALLEL EXOTHERMIC
SPLICE TO DOWN LEADERS
TO DOWN CONDUCTORS
AT BOTH LOCATIONS
TEE SPLICE FOR
CONNECTION OF DOWN
CONDUCTORS
SPLICE TO GROUND
ROD
PARAPET WALL
EXOTHERMIC WELDS
EXISTING DOWN CONDUCTOR.
TRIM OR EXPAND w/ AN INLINE
BARE COPPER WIRE EXOTHERMIC
WELD TO PROVIDE @ LEAST 4"
FOR USE OF A CLAM-ON OHMIC
METER FOR TESTING
EXIST. PVC, CUT BACK TO A
LENGTH OF 6" FROM PARAPET
WALL
EXIST. ROOF TOP BOX w/
DOWN CONDUCTOR
2 POSSIBLE CONNECTIONS:
EXOTHERMIC TEE CONNECTION OR
EXOTHERMIC IN-LINE CONNECTION
FOR TEE CONNECTION, MAKE
SURE THERE IS A MIN. 4" FOR
USE OF CLAMP-ON OHM METER
SCALE:SCALE: N.T.S. E-502
18EXOTHERMIC CONNECTIONS
SCALE:SCALE: N.T.S. E-502
EXIST. PARAPET WALL DOWN
CONDUCTOR CONNECTION
SCALE:SCALE: N.T.S. E-502
16AIR TERMINAL BRACING
CROSS SPLICE CONNECTOR
PARALLEL CONNECTOR
PLACED BETWEEN 1' AND 2'
FROM DOWN CONDUCTOR
CONNECTION POINT
ROOF LEVEL
EXIST. DOWN CONDUCTOR OUT OF PARAPET
TOP OF PARAPET
AIR TERMINAL
SCALE:SCALE: N.T.S. E-502
20BONDING OF CONDUCTOR
SCALE:SCALE: N.T.S. E-502
19CONDUCTOR @ PARAPET
VARIES
(IF OVER 6'-0" PROVIDE 12" ANGLE IRON
SUPPORT)
WALL OR
OTHER OBJECT
WALL OR
OTHER OBJECT
STEEL STRAPS
34" O.C.
FABRICATE
MOUNTING
BRACKET
FABRICATE
MOUNTING
BRACKET
A
A
COPPER
UNIVERSAL
BASE
NO. 82, GALVANIZED
STEEL TRIPOD BRACE
HIGH
COPPER AIR
TERMINAL
2' MAX
AS
REQ'D
SCALE:SCALE: N.T.S. E-502
15CONDUCTOR @ ROOF TOP BOX
EXISTING. BARE COPPER WIRE
SCALE:SCALE: N.T.S. E-502
17ROTATING VENTILATOR DETAIL
SCALE:SCALE: N.T.S. E-502
12DOOR BONDING DETAIL
GROUNDING
CONDUCTOR
EXIST. BARE
COPPER WIRE
MOUNT STRAP ON
SWING SIDE OF DOOR
BOND TO DOOR FRAME
TEE (ROUTE OVER &
BOND TO STEEL STEP)STEPS
SCALE:SCALE: N.T.S. E-502
22VENTILATOR DETAIL
NOTE:
1. IF VENTILATOR IS ALUMINUM, USE
B-METALIC INLINE CONNECTOR
2. ROUTE ALUMINUM CONDUCTOR
UP AND OVER VENTILATOR
3. USE ALUMINUM AIR TERMINAL.
33 33RLSEPT. 2022
| Sheets and Views |
| E-305 MAIN ELECTRICAL PANEL MAPS |
| E-306 MAIN ELECTRICAL PANEL MAPS |
| E-307 MAIN ELETRICAL PANEL MAPS (Interconnection of Buss Bars) |
| E-501 TYPICAL DETAILS |
| E-502 TYPICAL DETAILS |