Drawings 621-23-109 Install Lightning Protection and Grounding Systems _Part3.pdf

PDF 3 MB Posted

Attached to
Z1DA--621-23-2-5620-0001 - 621-23-109 - Install Lightning Protection & Grounding Systems
Solicitation number
36C24923B0002
Issued by

About this file

This document package includes construction drawings and specifications for installing new lightning protection and grounding systems at multiple buildings on the James H. Quillen VA Medical Center campus in Mountain Home, Tennessee. The scope of work involves installing surge protection devices and upgrading grounding systems at main electrical panels in Buildings 69, 77, 200, 204, 205, and 208 of the campus. It also specifies installing air terminals, down conductors, ground rods, and bonding details to provide complete lightning protection for the building roofs. The solicitation number for this opportunity is 36C24923B0002 and is seeking offers for the work defined in drawings E-305 through E-502 by June 2022. The Department of Veterans Affairs is the contracting agency.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELECTRICAL PANEL MAPS (200 Complex – 69, 77 & 200)

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (69-0-A, 208 VOLTS, 400 AMPS). PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (69-0-B, 208 VOLTS, 400 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. UTILIZE THE JUNCTION NEXT TO THE MAIN PANELS AND MOUNT ON WALL. IN THE EVENT THAT ONE PANEL IS FED FROM THE OTHER, PROVIDE THE SECOND SPD AS SPARE

PARTS TO COR. SEE GENERAL NOTE 10 & 12.

2. NO GROUND BUS BAR WILL BE PROVIDED FOR THIS BUILDING SINCE THE PANELS FOR B69 ARE FED FROM B77.

SCALE:SCALE:

BUILDING 77 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-305

1. PROVIDE 2 NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (M77A, 480 VOLTS, 1600 AMPS & M77B, 480 VOLTS, 1600 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE

GENERAL NOTE 10 & 12.

2. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 AND 12.

3. THE SWITCHGEAR FEEDING B77 IS LOCATED IN THE BASEMENT OF B204.

4. SEE GENERAL NOTE 13.

1. PROVIDE NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MSG-200, 480 VOLTS, 3200 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

3. PROVIDE A NEW TYPE 1, 240 KA SPD FOR GENERATOR #1 BREAKER (480 VOLTS, 1800 AMPS). CONNECT TERMINALS OF SPD ON GENERATOR FEED TO BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

4. PROVIDE A NEW TYPE 1, 240 KA SPD FOR GENERATOR #2 BREAKER (480 VOLTS, 1800 AMPS). CONNECT TERMINALS OF SPD ON GENERATOR FEED TO BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

5. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 & 12.

6. SEE GENERAL NOTE 13

SCALE:SCALE:

BUILDING 69 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-305

SCALE:SCALE:

BUILDING 200 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-305

GENERAL NOTES

GENERATORS MSG-200

MSBA PANEL

PANELS 69-0-A & 69-0-B

69-0-A 69-0-B

PANEL

MSG-200

PANELS

E-305

CAS

N

N

N

29 33

NOTE: LOOK AT B204 FOR LOCATION

RLSEPT. 2022

Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELECTRICAL PANEL MAPS (200 Complex – 204 & 205, 208)

GENERAL NOTES

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (SWBD 204-XSB, 480 VOLTS, 2000 AMPS).

CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. PROVIDE A NEW TYPE 1, 240 KA SPD FOR EQUIPMENT PANEL (480 VOLTS, 400 AMPS). CONNECT TERMINALS OF

SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

3. PROVIDE A NEW TYPE 1, 240 KA SPD FOR LIFE SAFETY PANEL (480 VOLTS, 400 AMPS). CONNECT TERMINALS OF

SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

4. PROVIDE A NEW TYPE 1, 240 KA SPD FOR CRITICAL SERVICES PANEL (480 VOLTS, 400 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

5. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 & 12.

6. SEE GENERAL NOTE 13.

N

SCALE:SCALE:

BUILDING 204 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-306

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MDP-205, 480 VOLTS, 1200 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 & 12.

3. SEE GENERAL NOTE 13

N

SCALE:SCALE:

BUILDING 205 - B200 COMPLEX - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-306

MDP

B77 CRITICAL

PANEL,

EQUIPMENT

PANEL, LIFE

SAFETY PANEL

PANEL MDP &

GENERATOR

PANEL

CRITICAL PANEL

EQUIPMENT PANEL

LIFE SAFETY PANEL

N

SCALE:SCALE:

BUILDING 208 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-306

1. PROVIDE 2 NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (SIDE A, 480 VOLTS, 1200 AMPS (MAIN LUGS ONLY) & SIDE B, 480 VOLTS, 1200 AMPS (MAIN LUGS ONLY)). CONNECT TERMINALS OF SPD ON SERVICE FEED TO

MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

SIDE BSIDE A

MAIN SWITCHBOARD

SIDE A & B

MAIN PANEL

E-306

CAS 30 33

SWDB 204-XSB

CRITICAL PANEL,

EQUIPMENT

PANEL, LIFE

SAFETY PANEL

RLSEPT. 2022

VHAMOULapoiL Rectangle

VHAMOULapoiL Text Box

NOT IN CONTRACT

MATCH LINE

B77 B69

B205

B204

B200

Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELETRICAL PANEL MAPS (Interconnection of Buss Bars)

COMPLEX 200

E-307

CAS 31 33

SCALE:SCALE:

B200 COMPLEX - GROUND BUS BAR INTERCONNECTIONS

N.T.S. E-307

FOR THE B200 COMPLEX PROVIDE A 4/0 BAR COPPER WIRE IN RIGID CONDUIT BETWEEN EACH NEW GROUND BUS.

1. CONTRACTOR SHALL DETERMINE ROUTE OF 4/0 WIRE TO NEW GROUND BUS (ABOVE CEILING) WITH COR'S APPROVAL. SUGGESTED ROUTE IS FROM THE SWITCHGEAR IN THE BASEMENT OF 204 (SWITCHGEAR FOR B77) UP TO THE SWITCHGEAR ON THE FIRST FLOOR OF 204, OVER TO THE MAIN DISTRIBUTION PANEL IN 205 AND

THEN DOWN THE HALL TO THE SWITCHGEAR IN 200.

2. IF RUN OF 4/0 CABLE IS OVER 250 FEET AND/OR MORE THAN 4(90-DEGREE) BENDS, INSTALL A JUNCTION BOX.

CONTRACTOR MUST ENSURE CONTINUITY OF THE CONDUIT FROM ONE END TO THE OTHER. PROVIDE GROUNDING TYPE TERMINATIONS FOR BOTH END AND OUT CONDUITS. PROVIDE A CONNECTION PER DETAIL 20 FOR EACH INSTANCE OF ENTRANCE AND EXIT FROM PULL BOX. INSTALL COVER WITHOUT CASKETS FOR A

GOOD METAL-TO-METAL CONNECTION.

3. AT THE GROUND BUS BARS, STOP RIGID CONDUIT WITHIN 1-FOOT OF THE BUS BAR. EXTEND CABLE WITH

2-HOLE CONNECTOR TO BUS BAR.

4. AT BOTH ENDS OF RIGID CONDUIT, INSTALL DEVICE THAT WILL BOND THE CABLE TO THE END OF THE RIGID

CONDUIT PER DETAIL 20.

GENERAL NOTES

N

B77 GROUND BUS

(BASEMENT)

B204 GROUND

BUS (FIRST

FLOOR)

B205 GROUND BUS

- GROUND FLOOR

B200 GROUND BUS

- GROUND FLOOR

PULL BOX

PULL BOX

SCALE:SCALE:

ROOF DRAIN GROUNDING

N.T.S. E-501

SCALE:SCALE: N.T.S. E-501

GROUND

ROD INSPECTION WELL DETAIL

SCALE:SCALE: N.T.S. E-501

5AIR TERMINAL PARAPET

SCALE:SCALE: N.T.S. E-501

3DOWNLEAD ROUTING DETAIL

SCALE:SCALE: N.T.S. E-501

4TYPICAL BONDING / SPLICING DETAILS

Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

E-501

CAS

ROOF

1" PVC PROTECTOR PIPE. ONE

REQUIRED PER EACH DOWNLEAD

TO EXTEND FROM 6'-0" ABOVE

GRADE TO BELOW GRADE. SEAL

ENDS OF PROTECTOR

PERMANENTLY WATER TIGHT

WITH DUCT SEAL.

LOOP TYPE PROTECTOR

PIPE ANCHOR SPACE

EVENLY IN A SIMILAR

MANNER AS SHOWN.

TRANSITION FROM ROOF

CONDUCTOR TO BARE COPPER

WIRE

"TURN" CONDUIT TO EXIT

BUILDING A MINIMUM OF

24" BELOW FINISHED

GRADE

COPPER DOWNLEAD CABLE.

COURSE CABLE BELOW GRADE.

CADWELD TO GROUND RING.

SEE LAYOUT FOR LOCATIONS.

SLAB ON

GRADE

1 BOLT PARALLEL

CLAMP

CROSS RUN

CONNECTOR

CABLE TO FLAT

METAL CLAMP

BONDING

PLATE

SECONDARY

BONDING LUG

IN-LINE

CONNECTOR

STRAP TYPE

PIPE CLAMP PIPE

GREATER THAN

3"Ø

U-BOLT TYPE

PIPE CLAMP

LESS THAN 3"Ø

CONDUCTOR

" M

IN

AIR TERMINAL

2'-0"

2" - 4"

RECOMMENDED

8" MAX.

PRIMARY BONDING CONDUCTOR

DRILL AND TAP ROOF DRAIN

FLANGE AND CONNECT BONDING

CONNECTOR TO DRAIN FLANGE

WITH STAINLESS STEEL BOLT

DOME ROOF DRAIN

THOMPSON #551

BONDING LUG WITH

3/8" BOLT HOLE

24"

12" MIN

TEST WELL AND COVER

#2 AWG BCW TINNED PIGTAIL

CADWELD TYPE GT

CLEAN SAND FILL

1"x4" SLOT IN

12" PVC PIPE

GROUND CONDUCTOR, SIZE

AS NOTED ON PLANS

DRIVEN COPPER CLAD

GROUND ROD 5/8" x 10'

(SEE NOTE)

NOTE:

TO IMPROVE SYSTEM RESISTANCE, ERICO GEM MAY BE USED

AS A BACKFILL MATERIAL IN AN AUGURED HOLE. PROVIDE

GROUND RODS TO ACHIEVE MAXIMUM 5 OHMS RESISTANCE.

2"

2"

2'-0" MIN

AIR TERMINAL

ADHESIVE BASE

ADHESIVE CABLE

FASTENER

SCALE:SCALE: N.T.S. E-501

LPS - ADHESIVE

BASE FOR HORIZONTAL SURFACE

SCALE:SCALE: N.T.S. E-501

8"

>8"

8"

ACCEPTABLE

NOT ACCEPTABLE

NOT ACCEPTABLE

.00

.00

>90.00°

CABLE BENDING DETAIL

2"

STAINLESS STEEL HARDWARE

5/16" DIAMETER HOLE PAIR

(TYP)

7/16" DIAMETER HOLE PAIR (TYP)

1 1/8" TYP

1"

5/8"

5/8"

TYPICAL TMGB DRILLED HOLE DIMENSIONS

COMPRESSION CONNECTOR W/

VIEWING WINDOW

1 1/2"

NOMINAL

INSULATOR

STAINLESS STEEL STANDOFF

BRACKET

ELECTRO-TIN PLATED

COPPER GROUND BAR

SCALE:SCALE: N.T.S. E-501

8MAIN GROUND BUS BAR

32 33

TYPICAL DETAILS

VARIES

5' - 8'

'Y' CONNECTOR

IN-LINE CONNECTOR

FROM ROOF

CONDUCTOR

TO ROOF

CONDUCTOR

2' AIR

TERMINAL

HEIGHT

INDICATED

ON

DRAWING

4 BOLT IN-LINE CONNECTOR (FOR

EASE OF MAINTENANCE ON

VENTILATOR)

PLACE FLAT BAR ACROSS

TOP IF NO SOLID OBJECT TO

MOUNT AIR TERMINAL ON

ROOF

CONDUCTOR

ROOF

CONDUCTOR

AIR TERMINAL

1. USE AIR TERMINAL BRACING DETAIL TO MOUNT AN AIR TERMINAL

NEXT TO THE ROTATING VENTILATOR.

2. TOP OF AIR TERMINAL MUST BE MINIMUM OF 18 INCHES ABOVE

TOP OF VENTILATOR.

3. AIR TERMINAL WILL BE HEIGHT OF ROTATING VENTILATOR PLUS 18

INCHES (IF 8 FEET HIGH PLUS 18 INCHES EQUALS 9 FEET 6 INCHES)

2'-0" AIR TERMINAL

'Y'

CONNECTOR

IN-LINE CONNECTOR

FROM ROOF

CONDUCTOR

TO ROOF

CONDUCTOR

2'-0"

AIR

TERMINAL

Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

TYPICAL DETAILS

SCALE:SCALE: N.T.S. E-502

9AIR TERMINAL STANDING SEAM MOUNT

SCALE:SCALE: N.T.S. E-502

LPS - AIR TERMINAL MOUNT

ROOF PEAK

SWIVEL

ADAPTER

CONDUCTOR

CLIP CABLE HOLDER

SWIVEL

ADAPTER

STANDING

SEAM POINT

BASE

STANDING

SEAM POINT

BASE

AIR

TERMINAL

2'-0"

AIR

TERMINAL

2'-0"

CONDUCTOR

CLIP CABLE

HOLDER

AIR TERMINAL

2'-0"

CABLE

FASTENER

SADDLE BASE

CONDUCTOR

E-502

CAS

SCALE:SCALE: N.T.S. E-502

21VENTILATOR DETAIL

2"

4" PVC

ROOF

CONDUCTOR

A SECTION

SCALE:SCALE: N.T.S. E-502

SUPPORT FOR ROOF

CONDUCTOR IN FREE AIR

SCALE:SCALE: N.T.S. E-502

AIR TERMINALS ON LARGE

MECHANICAL EQUIPMENT

BLOUNT TIP AIR

TERMINAL (TYPICAL)

MAIN SIZE COPPER

CONDUCTOR TO

ROOF CONDUCTOR

NOTE: TYPICAL FOR ROOFTOP AHU AND ERU EQUIPMENT.

EXOTHERMIC WELD TO

STRUCTURAL STEEL

MEMBERS FOR CREATE OF

NEW DOWN CONDUCTOR

PARALLEL EXOTHERMIC

SPLICE TO DOWN LEADERS

TO DOWN CONDUCTORS

AT BOTH LOCATIONS

TEE SPLICE FOR

CONNECTION OF DOWN

CONDUCTORS

SPLICE TO GROUND

ROD

PARAPET WALL

EXOTHERMIC WELDS

EXISTING DOWN CONDUCTOR.

TRIM OR EXPAND w/ AN INLINE

BARE COPPER WIRE EXOTHERMIC

WELD TO PROVIDE @ LEAST 4"

FOR USE OF A CLAM-ON OHMIC

METER FOR TESTING

EXIST. PVC, CUT BACK TO A

LENGTH OF 6" FROM PARAPET

WALL

EXIST. ROOF TOP BOX w/

DOWN CONDUCTOR

2 POSSIBLE CONNECTIONS:

EXOTHERMIC TEE CONNECTION OR

EXOTHERMIC IN-LINE CONNECTION

FOR TEE CONNECTION, MAKE

SURE THERE IS A MIN. 4" FOR

USE OF CLAMP-ON OHM METER

SCALE:SCALE: N.T.S. E-502

18EXOTHERMIC CONNECTIONS

SCALE:SCALE: N.T.S. E-502

EXIST. PARAPET WALL DOWN

CONDUCTOR CONNECTION

SCALE:SCALE: N.T.S. E-502

16AIR TERMINAL BRACING

CROSS SPLICE CONNECTOR

PARALLEL CONNECTOR

PLACED BETWEEN 1' AND 2'

FROM DOWN CONDUCTOR

CONNECTION POINT

ROOF LEVEL

EXIST. DOWN CONDUCTOR OUT OF PARAPET

TOP OF PARAPET

AIR TERMINAL

SCALE:SCALE: N.T.S. E-502

20BONDING OF CONDUCTOR

SCALE:SCALE: N.T.S. E-502

19CONDUCTOR @ PARAPET

VARIES

(IF OVER 6'-0" PROVIDE 12" ANGLE IRON

SUPPORT)

WALL OR

OTHER OBJECT

WALL OR

OTHER OBJECT

STEEL STRAPS

34" O.C.

FABRICATE

MOUNTING

BRACKET

FABRICATE

MOUNTING

BRACKET

A

A

COPPER

UNIVERSAL

BASE

NO. 82, GALVANIZED

STEEL TRIPOD BRACE

HIGH

COPPER AIR

TERMINAL

2' MAX

AS

REQ'D

SCALE:SCALE: N.T.S. E-502

15CONDUCTOR @ ROOF TOP BOX

EXISTING. BARE COPPER WIRE

SCALE:SCALE: N.T.S. E-502

17ROTATING VENTILATOR DETAIL

SCALE:SCALE: N.T.S. E-502

12DOOR BONDING DETAIL

GROUNDING

CONDUCTOR

EXIST. BARE

COPPER WIRE

MOUNT STRAP ON

SWING SIDE OF DOOR

BOND TO DOOR FRAME

TEE (ROUTE OVER &

BOND TO STEEL STEP)STEPS

SCALE:SCALE: N.T.S. E-502

22VENTILATOR DETAIL

NOTE:

1. IF VENTILATOR IS ALUMINUM, USE

B-METALIC INLINE CONNECTOR

2. ROUTE ALUMINUM CONDUCTOR

UP AND OVER VENTILATOR

3. USE ALUMINUM AIR TERMINAL.

33 33RLSEPT. 2022

Sheets and Views
E-305 MAIN ELECTRICAL PANEL MAPS
E-306 MAIN ELECTRICAL PANEL MAPS
E-307 MAIN ELETRICAL PANEL MAPS (Interconnection of Buss Bars)
E-501 TYPICAL DETAILS
E-502 TYPICAL DETAILS

File details come from the government source that posted it. Updated .