Drawings 621-23-109 Install Lightning Protection and Grounding Systems _Part2.pdf

PDF 15 MB Posted

Attached to
Z1DA--621-23-2-5620-0001 - 621-23-109 - Install Lightning Protection & Grounding Systems
Solicitation number
36C24923B0002
Issued by

About this file

This federal contract opportunity notice solicits bids to install new lightning protection and grounding systems at multiple buildings of the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 will award a contract to provide installation of lightning protection and grounding systems as defined in the contract documents. Bids are due by the date listed in the solicitation number 36C24923B0002. The selected contractor will be responsible for installing new lightning protection and grounding systems at the buildings on site to provide updated safety measures.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Raymond-Pond SDVOSB JV, LLC 1035 Green St. SE Suite A Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELECTRICAL PANEL MAPS (3, 5, & 8)

E-301

CAS

SCALE:SCALE:

BUILDING 3 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-301

SCALE:SCALE:

BUILDING 5 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-301

SCALE:SCALE:

BUILDING 8 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-301

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MDP3, 208 VOLTS, 1000 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. REMOVE EXISTING TVSS. SEE GENERAL

NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (5MPG, 208 VOLTS, 1600 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (M5B, 480 VOLTS, 1200 AMPS). CONNECT

TERMINALS OF SPD ON SERVICE FEED. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

5MDPG

SMDPG

MSB-BH2

GENERAL NOTES

MSB-BH2

PANEL

5MDPG

SMDPG

N

N

N

25 33RLSEPT. 2022

Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELECTRICAL PANEL MAPS (35, 36, & 37)

E-302

SCALE:SCALE:

BUILDING 35 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-302

SCALE:SCALE:

BUILDING 36 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-302

SCALE:SCALE:

BUILDING 37 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-302

GENERAL NOTES

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (35-SB-A, 208 VOLTS, 1200 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (36-0-A, 208 VOLTS, 225 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (SWITCHBOARD, 208 VOLTS, 1000 AMPS). THIS SWITCHBOARD IS OUTSIDE; PROVIDE SPD IN A NEMA 3R ENCLOSURE CONNECT TERMINALS OF SPD ON

SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

3. NEW GROUND BUS BAR SHALL BE INSTALLED IN A NEMA 3R BOX OF SUFFICIENT SIZE (MIN 3 FT X 3FT, 2 FT DEEP)

AND MOUNTED TO THE OUTSIDE SWITCHGEAR.

4. ROUTE 1/0 WIRE FROM GROUND GRID TO NEW GROUND BUS BAR IN PVC. START PVC AT LEAST 3-FEET FROM GROUND BUS BAR, ROUTE UP AND TO BOX. CONTINUE WIRE TO GROUND BUS AND CONNECT TO GROUND BUS

WITH A 2-HOLE CONNECTOR.

PANEL 35-BS-A

PANEL 36-0-A

MAIN SWITCHBOARD

PANEL 35-SB-A

IN BASEMENT

PANEL 36-0-A

IN BASEMENT

MAIN SWITCHBOARD

OUTSIDE

E-302

CAS

N

N

N

26 33

(208V, 1200A)

RLSEPT. 2022

VHAMOULapoiL Rectangle

VHAMOULapoiL Text Box

NOT IN CONTRACT

Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELECTRICAL PANEL MAPS (108, 115, &

160)

E-303

CAS

SCALE:SCALE:

BUILDING 108 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-303

SCALE:SCALE:

BUILDING 115 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-303

SCALE:SCALE:

BUILDING 160 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-303

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MCC DP-BH, 480 VOLTS, 800 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. PROVIDE A NEW TYPE 1, 240 KA SPD FOR THE ATS (480 VOLTS, 400 AMPS). CONNECT TO THE GENERATOR FEED

SIDE OF THE ATS. SEE GENERAL NOTE 10 & 12.

3. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (208 VOLTS, 150 AMPS). CONNECT TERMINALS

OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. PROVIDE A NEW TYPE 1, 240 KA SPD FOR THE PANEL (208 VOLTS, 225 AMPS) PROVIDING POWER TO CONTROLS FOR MEDIUM VOLTAGE BREAKERS. CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN

LUGS. SEE GENERAL NOTE 10 & 12.

3. GROUND BUS BAR IS EXISTING IN B115. LEAVE AS IS.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MSG-160, 480 VOLTS, 3200 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 AND 12.

ATS

MCC

MCCATS

RELAY

PANEL

MAIN

PANEL

MAIN PANEL

MAIN SWITCHGEAR

GENERAL NOTES

MAIN

SWITCHGEAR MSG

RELAY PANEL

N

N

N

27 33RLSEPT. 2022

VHAMOULapoiL Rectangle

VHAMOULapoiL Text Box

NOT IN CONTRACT

Conyers, GA 30012 770-483-9592 Art Warner U.S. Department of Veterans Affairs

621-22-117

JUNE 2022

LIGHTNING PROTECTION &

GROUNDING STUDY

BUILDINGS 3, 5, 8, 35, 36, 37, 108, 115, 116, 160, 161, 162,

200 COMPLEX (69, 77, 200, 204, 205) 201, 208

JAMES H. QUILLEN VA MEDICAL CENTER

MOUNTAIN HOME, TN

Office of Construction and Facilities Management

MAIN ELECTRICAL PANEL MAPS (161, 162, &

201)

SCALE:SCALE:

BUILDING 161 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-304

SCALE:SCALE:

BUILDING 162 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-304

SCALE:SCALE:

BUILDING 201 - MAIN ELECTRICAL PANEL MAPS

N.T.S. E-304

GENERAL NOTES

1. UTILIZE EXISTING SPD INSTALLED MAIN SERVICE PANEL (MAIN PANEL, 480 VOLTS, 2000 AMPS).

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MSB-162, 208 VOLTS, 1600 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. PROVIDE A NEW GROUND BUS FOR BUILDING. SEE GENERAL NOTE 11 AND 12.

1. PROVIDE A NEW TYPE 1, 240 KA SPD FOR MAIN SERVICE PANEL (MSG-201, 480 VOLTS, 1000 AMPS). CONNECT TERMINALS OF SPD ON SERVICE FEED TO MAIN BREAKER/MAIN LUGS. SEE GENERAL NOTE 10 & 12.

2. ROUTE A 1/0 COPPER WIRE FROM NEW GROUND GRID TO NEW GROUND BUS FOR BUILDING. SEE GENERAL

NOTE 11 & 12.

MSB-162

MSB-201

MSB-162

PANEL

MSB-201

PANEL

MAIN PANEL

E-304

CAS

N

N

N

28 33

MAIN PANEL

ATS

RLSEPT. 2022

Sheets and Views
E-301 MAIN ELECTRICAL PANEL MAPS
E-302 MAIN ELECTRICAL PANEL MAPS
E-303 MAIN ELECTRICAL PANEL MAPS
E-304 MAIN ELECTRICAL PANEL MAPS
E-305 MAIN ELECTRICAL PANEL MAPS
E-306 MAIN ELECTRICAL PANEL MAPS
E-307 MAIN ELETRICAL PANEL MAPS (Interconnection of Buss Bars)
E-501 TYPICAL DETAILS
E-502 TYPICAL DETAILS

File details come from the government source that posted it. Updated .