Drawings 603-21-201 6N Patient Room Doors CD.pdf

PDF 971 KB Posted

Attached to
Z2DA--36C249-23-AP-0088 - 603-21-201 - Replace 6-N Patient Room Doors
Solicitation number
36C24923B0016
Issued by

About this file

This solicitation package outlines requirements for a construction project to replace doors in an intensive care unit at a Department of Veterans Affairs medical center. The contractor will provide all labor, materials, equipment, logistics, and supervision to replace primary entrance and patient room doors in the unit with new doors and access control features, in accordance with project specifications and drawings. Work includes infection control measures at BioSafety Level 4 and phasing to allow continued unit operation. Bids must be submitted electronically by the specified due date. The solicitation provides bidding instructions and an overview of the scope of work, which involves replacing doors to meet new accessibility and security standards while minimizing patient disruption.

View the file

Other files

File Type Posted
36C24923B0016 0005.docx DOCX document
Attachment 1 - 1999 Door Project Image.jpg JPG image
36C24923B0016 0004.docx DOCX document
Attachment 5 - ADDENDUM 001 603-21-201 Replace 6-North Patient Room Doors 078400 FIRESTOPPING.pdf PDF
36C24923B0016 0003.docx DOCX document
Attachment 2 - ADDENDUM 001 603-21-201 Replace 6-North Patient Room Doors A654 DOOR FRAME.pdf PDF
Attachment 4 - ADDENDUM 001 603-21-201 Replace 6-North Patient Room Doors ICRA.pdf PDF
Attachment 3 - ADDENDUM 001 603-21-201 Replace 6-North Patient Room Doors SOC-8_6th Floor.pdf PDF
Attachment 1 - RFI Questions - 603-21-201 - Replace 6N Patient Room Doors VA.pdf PDF
36C24923B0016 0002.docx DOCX document
36C24923B0016 0001.docx DOCX document
Price Schedule-36C24923B0016.xlsx XLSX spreadsheet
ADDENDUM 001 INDEX 603-21-201 Replace 6 floor-North Patient Room Doors.pdf PDF
Drawing_A102-A654 FR_603-21-201 Replace 6-North Patient Room Doors.pdf PDF
Bidder Declaration-36C24923B0016.docx DOCX document
RFI_Form-36C24923B0016.pdf PDF
CalcofSelfPerformedWork-36C24923B0016.xlsx XLSX spreadsheet
ContractorEMR_Certification.docx DOCX document
SPEC_078400_Firestopping-603-21-201 Replace 6-North Patient Room Doors.pdf PDF
Original Specs 603-21-201 6N Patient Room Doors VA.pdf PDF
IFB-36C24923B0016-Replace 6N Patient Room Doors.pdf PDF
WAGE-RATES.docx DOCX document
DRAWING_SOC-8- Replace 6-North Patient Room Doors-603-21-201.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXTERIOR ELEVATION

INTERIOR ELEVATION

SECTION/DETAIL NUMBER

DRAWING NUMBER

EQUIPMENT TAG

COLUMN GRID

NOTE

WINDOW OPENING

DOOR OPENING

ROOM NAME

ROOM NUMBER

WALL TYPE

CEILING HEIGHT

FINISH DESIGNATION

X

10'-8"

X

X

XX.X-X

XX

X

1/A101

X

A101

XX

TOILET ACCESSORY TAGX SIGNAGE TAG

A101

SIM

X

E 1 0th

S t.

E. M arke t S t.

S pring

S t.

M ockingbird

V alley R d.

Z orn A ve.River R d.

B lanke nba ker L n.

D

r. M

.L .K

Jr. E xp y

Frankfort Ave.

Brownsboro R d.

C henow eth Ln.

W estport R d.

E. Main St.

Story Ave.

E. Broadway

Shelbyville Rd.

B axte r A ve.

VAMC

800 Zorn Ave.

Ohio R ive r

Kosair Children's Hospital

Cave Hill Cemetery

Thurm an

Hutc hin

P ark

ST

A

T E O F F L O R

ID

A

RE

G

IS

T E R E D A R C H

IT

EC

T

ROGE

R A R E P

ST

IEN

A R

VA Project No.

RDC/JPA Project No.

Department of Veterans Affairs Medical Center

HEAPY ENGINEERING

MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY

1400 WEST DOROTHY LANE

DAYTON, OH 45409

937.224.0861 P

937.224.5777 F

ARCHITECTURE PLANNING INTERIOR DESIGN

524 FERNWOOD AVENUE

ALTAMONTE SPRINGS, FLORIDA 32701

407.830.6522 P

937.461.0260 F

RDC / JOHN POE ARCHITECTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

/1

/2

:3

:2

P

M

VA Louisville Replace 6N Patient Room Doors

6/15/2021

COVER SHEET

G001

ACMD

603-21-201

VA Louisville Replace 6N Patient Room Doors 800 Zorn Avenue Louisville, KY 40206 PROJECT #: 603-21-201

100% CD

21001.00

G001 COVER SHEET

A101 PLANS & DETAILS

ET001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS

ET106 PARTIAL SIXTH FLOOR PLANS - REMOVALS & NEW WORK

GENERAL CONSTRUCTION NOTES

6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO

ORDERING, FABRICATING OR INSTALLING NEW MATERIALS.

7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO BE INSTALLED AS

PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE SPECIAL PROVISIONS TO INSTALL

EQUIPMENT THAT IS TOO LARGE TO FIT THROUGH FINISHED OPENINGS.

8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AS INDICATED IN THE CONTRACT DOCUMENTS

AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL WOOD BLOCKING SHALL BE FIRE

RETARDANT TREATED.

9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS SPECIFICALLY NOTED

OTHERWISE. IF NO FINISH IS INDICATED AT A PARTICULAR SURFACE, CONTRACTOR SHALL

PROVIDE FINISH(S) AS INDICATED AT SIMILAR CONDITIONS.

10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS WHICH COMPLY

WITH STATED CODES AND REGULATIONS. WHERE THE OMISSION OF A PART OR ELEMENT OF A

SYSTEM WOULD RESULT IN THE NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM,

CONTRACTOR SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.

11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED WALLS SHALL BE

SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF THE WALL.

* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE CONTRACTING OFFICER'S

REPRESENTATIVE (C.O.R.).

1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE, INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF

VETERAN AFFAIRS, TECHNICAL INFORMATION LIBRRARY WEBSITE.

2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST ARCHITECTURAL BARRIERS

ACT ACCESSIBILITY STANDARD (ABAAS) AND DEPARTMENT OF VETERANS AFFAIRS BARRIER

FREE DESIGN GUIDE PG-18-13 WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS

AFFAIRS TECHNICAL INFORMATION LIBRARY WEBSITE.

3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT EXISTING

CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED WITH THE CONTRACTING

OFFICER'S REPRESENTATIVE.

4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH ADJACENT EXISTING

SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED DURING THE COURSE

OF DEMOLITION OR NEW WORK.

5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF NEW WORK,

CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO REMAIN OR PROVIDE NEW

CONSTRUCTION TO MATCH EXISTING ADJACENT SURFACES TO REMAIN.

DRAWING INDEX

N N.T.S.Scale:

VICINITY MAP

Revisions Date

Locker

A-677A

Toilet

A-677B

Kitchen

A-677

Locker

A-677C

HAC

A-676 Electrical

Room

A675

Storage

A-674

Patient Bed Room

A-673

Dirty Utility

A-666

Ante Room

A-663

Isolation Room

A-662

Patient Bed Room

A-661

Patient Bed Room

A-660

Patient Bed Room

A-659

Patient Bed Room

A-658

Patient Bed Room

A-657 Patient Bed

Room

A-656

Patient Bed Room

A-655

Patient Bed Room

A-654

Stair-6

A-653 Clean Linen

A-652

Supply Room

A-651

Nurse MGR Office

A-650

Conference Room

Multi-Purpose

A-649Toilet

A-648B

On-Call Room

A-648A

On-Call Room

A-648

On-Call Room

A-648C

Storage

A-647A

Break Room

A-643B Restroom

A-643A

Toilet

A-678A

Waiting

A-678

Medicine Prep

A-664

Nurse Station

A-665

Elevator Lobby

A-647

Pipe Chase

A-643C

A-640

A-654 A-655

A-656 A-657

A-658

A-659

A-660A-661A-662

Corridor

A-640

Corridor

A-641

1.071.07

1.071.07 1.071.07

1.071.071.071.07

10'-0"

1.05 2.04

1.06 8.10 8.10

8.108.10

8.108.10

8.10

8.10

8.10

Locker

A-677A

Toilet

A-677B

Kitchen

A-677

Locker

A-677C

HAC

A-676 Electrical

Room

A675

Storage

A-674

Patient Bed Room

A-673

Dirty Utility

A-666

Ante Room

A-663

Isolation Room

A-662

Patient Bed Room

A-661

Patient Bed Room

A-660

Patient Bed Room

A-659

Patient Bed Room

A-658

Patient Bed Room

A-657

Patient Bed Room

A-656

Patient Bed Room

A-655

Patient Bed Room

A-654

Stair-6

A-653 Clean Linen

A-652

Supply Room

A-651

Nurse MGR Office

A-650

Conference Room

Multi-Purpose

A-649Toilet

A-648B

On-Call Room

A-648A

On-Call Room

A-648

On-Call Room

A-648C

Storage

A-647A

Break Room

A-643B Restroom

A-643A

Toilet

A-678A

Waiting

A-678

Medicine Prep

A-664

Nurse Station

A-665

Elevator Lobby

A-647

Pipe Chase

A-643C

1.03

1.03 1.03

1.03

1.03

1.03

1.03

1.03

1.03

1.03

2.51

2.52

M in

M in

M in

M in

M in

1.04

1.041.04 1.041.04

1.041.04

1.04

8" 8"

SEE SCHED.

S E

E S

C H

E D

U L E

NS

SEE SCHEDULE

S E

E S

C H

E D

U L E

/4

4'-0" wide sliding door

3 1/4" SEE SCHEDULE 3 1/4"

/4

S E

E S

C H

E D

U L E

SEE PLAN

H1

J1

9.21

9.80

9.09

9.21

9.80

H2

J2

9.08

7.83

7.83

SEE PLAN

9.21

9.80

9.08

7.83

8.10

9.09

9.21

9.80

6.07

7.83

8.10

8.08

8.08

1/2" 1/2"

LEGEND

Wall/Door to be Demolished

Existing to Remain

New Wall

ST

A

T E O F F L O R

I D A

RE

G

IS

T E R E D A R C H

IT

EC

T

ROGE

R A R E P

ST

IEN

A R

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

/1

/2

:3

:2

P

M

VA Louisville Replace 6N Patient Room Doors

6/15/2021

PLANS & DETAILS

A101

ACMD

603-21-201

100% CD

21001.00

Scale: 1/8" = 1'-0"1 Sixth Floor New Work Plan

NOTES

Key Plan

Scale: 1/8" = 1'-0"2 Sixth Floor Demolition Plan

Scale: 1/4" = 1'-0"

Door Types Scale: 1/4" = 1'-0"

Frame Types

Scale: 1 1/2" = 1'-0"

Door Details

1.03 Remove existing door and harware. Existing frame to remain. Patch and prep frame as required to receive new doors and hardware.

1.04 Temporary partition per ICRA requirements.

1.05 New Keypad.

1.06 New door actuator.

1.07 Negative pressure room.

2.04 Existing intercom to remain.

2.51 Remove existing keypad.

2.52 Remove existing door actuator, patch wall & paint to match existing.

6.07 2" x 4" fire retardant treated blocking.

7.83 Cont. sealant each side.

8.08 Double egress hollow metal frame.

8.10 Anodized aluminum ICU door frame

9.08 Metal framing box header.

9.09 Double metal framing at jambs, typ.

9.21 5/8" Type X gypsum board.

9.80 Acoustic insulation

DOOR SCHEDULE

DOOR

BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION

FIRE

RATING

HDWE

SET REMARKSRM RM TYPE MAT'L

SIZE

TYPE MAT'L HEAD JAMB# W H T

A-640 A-641 A-640 N WD 2 3'-6" 7'-0" 1 3/4" 3 HM H1 J1 20 MIN 1.0 Existing frame to remain.

A-654 A-640 A-654 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-655 A-655 A-640 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-656 A-656 A-640 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-657 A-640 A-657 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-658 A-640 A-658 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-659 A-640 A-659 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-660 A-640 A-660 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-661 A-640 A-661 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

A-662 A-662 A-640 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --

GENERAL NOTES

A. All dimensions are taken to face of gypsum wallboard or unit masonry.

B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.

C. All wood blocking to be fire retardent treated.

D. Remove all doors where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner. Deliver boxed hardware to the VA Maintenance Shop, B016 Basement Floor.

E. See Electrical Drawings for removal work associated with those trades.

F. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.R.

G. Repair existing walls to match adjacent undisturbed wall where disturbed by new work.

H. Phase project so only one patient bed room may be inoperable at any point in time. Fully complete each door, including punchlist and COR approval prior to beginning next door.

* ALL NEW DOORS TO FIT IN EXISITNG OPENING. CONTRACTOR TO FIELD VERIFY EXISTING OPENING SIZE & MANUFACTURE DOOR TO FIT EXISTING OPENING.

Revisions Date

Addendum 1

Addendum 1

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS

IC

WALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO

ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.

HD

AUTOMATIC DOOR OPERATOR MOTOR ASSEMBLY. 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND

DOOR ACTUATOR BUTTONS. REFER TO SECURITY ROUGH-IN DETAILS.

K WALL MOUNTED SECURITY KEYSWITCH (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYSWITCH AND CABLING PER DIV 28.

PB W

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL TRADES (DIVISION 01)

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY (DIVISION 28)

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY CONTRACTOR

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

F

F

F

F

F

S F

KF

S

H

C

D

FS

V

R W

SD

FT

PS

AM

C/I

PIV

K S

H

S S/R

S/R

FACP

FIRE ALARM SYMBOLS

FIRE ALARM BELL & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM CHIME & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM HORN & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

CEILING MOUNTED FIRE ALARM SPEAKER.

FIRE ALARM CONTROL PANEL.

CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.

WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER

LOCATIONS.

FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.

CEILING MOUNTED SMOKE DETECTOR.

CEILING MOUNTED HEAT DETECTOR.

DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

ELECTRIC RELEASE DOOR CLOSER.

ELECTRO-MAGNETIC DOOR HOLDER.

WATER FLOW SWITCH.

VALVE SUPERVISORY SWITCH.

CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES

WALL MOUNTED.

SMOKE DAMPER.

FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).

PRESSURE SWITCH.

ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.

POST INDICATOR VALVE.

KNOX BOX (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "S" INDICATES SUPERVISED UNIT.

FIRE ALARM BELL (88" AFF UNLESS NOTED OTHERWISE). SUBSCRIPT "W" INDICATES EXTERIOR WEATHERPROOF UNIT.

BEAM DETECTOR. SUBSCRIPT "T" INDICATES TRANSMITTER FUNCTION. SUBSCRIPT "R" INDICATES RECEIVER FUNCTION.

AIR SAMPLING SMOKE DETECTOR SAMPLING PORT.

REMOTE ANNUNCIATOR PANEL.

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.

AIR SAMPLING SMOKE DETECTOR BASE UNIT.

SURFACE MOUNTED FIRE ALARM SPEAKER (88" AFF). SUBSCRIPT "R" INDICATES RECESSED MOUNTING.

RAP

NAC

ASSD

F W

S F

S R

A

B T/R

E2

B

E2

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES

CIRCUIT(S).

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

CONDUIT FOR DATA CIRCUITRY.DAT

WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA

WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL

CONDUIT FOR PHONE CIRCUITRY.PHO

WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC

WIRE RUN IN SURFACE WIREWAY.W

CABLE MANAGEMENT SYSTEM PATHWAY.CM

X - 1,2

WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM

WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S

WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I

WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV

CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

4"

4"

4"

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

F

EDC

X ELECTRONIC DOOR CONTROL. SUPERSCRIPT "X" INDICATES SPECIFIC DOOR. REFER TO ELECTRONIC DOOR CONTROL

SCHEDULE FOR REQUIREMENTS.

LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS

SCHEDULE FOR ROOM CONTROL.

3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.

KC

WALL MOUNTED COMBINATION PROX READER/KEYPAD (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75"

CONDUIT TO ABOVE ACCESSIBLE CEILING. KEYPAD AND CABLING PER DIV 28.

RX

WALL MOUNTED REQUEST TO EXIT WAVE SENSOR (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75"

CONDUIT TO ABOVE ACCESSIBLE CEILING. WAVE SENSOR AND CABLING PER DIV 28.

K

WALL MOUNTED KEYPAD ENTRY STATION..

K

DESK MOUNTED PUSH BUTTON WITH WIRING FOR LOCAL DOOR LOCK-DOWN. CONNECT TO NEW PACS DOOR

CONTROLLER AND PROGRAM INTO SYSTEM.

P: 937-224-0861 www.heapy.com

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities ManagementPROJECT NO.

STATE COA FIRM NO.

Consultant:

/1

/2

:4

:0

A

M

VA Louisville Replace 6N Patient Room Doors

06/16/2021

ABBREVIATIONS, SYMBOLS &

INDEX OF DRAWINGS

ET001

PABJDK

603-21-201

LOUISVILLE, KY.

100% CONSTRUCTION

DOCUMENTS

21001.00

2021-05026.01

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

937.224.0862

INDEX OF DRAWINGS

SHEET NUMBER SHEET NAME

ET001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS

ET106 PARTIAL SIXTH FLOOR PLANS - REMOVALS & NEW WORK

NOTES:

ELECTRONIC DOOR CONTROLS SCHEDULE

E D

C N

U M

B E

R

D O

O R

O P

E N

IN

G

N U

M B

E R

CONTROL LOCKS REQUEST TO EXIT DOOR MONITOR

AUTOMATIC DOOR

OPERATOR

S P

E C

IA

L

D O

O R

N O

T E

SEAC INTERFACE POWER TYPE

Q T

Y

FUNCTION LOCATION POSITION SWITCH L BOLT

BOND

SENSOR MOTOR PUSHPLATE

R E

A D

E R

T O

D

F

IR

E A

L A

R M

I N

T E

R C

O M

P U

S H

B U

T T

O N

I N

T R

U S

IO

N

A L

A R

M

P O

E P

O E

V O

L T

A G

E

L O

C A

L

R E

M O

T E

L O

C A

T

IO

N

N O

T E

EP EL ES ML

W L A

L A

R M

S H

U N

T

U N

L O

C K

N O

T E

H A

R D

W A

R E

M O

T

IO

N

W A

L L

S W

IT

C

H

N O

T E

QTY #

P

T

B A

L A

N C

E D

H

IG

H S

E C

U R

IT

Y

R E

C E

S S

E D

S U

R F

A C

E

QTY QTY QTY E

A

C I

N T

E R

F A

C E

QTY W

IR

E L

E S

S

1 ● ● ● ● ● 24 ● ● 3 ● ● ● ● ● 2 DPDT ● ● 0 2 2 ● 0

IC

K

RX

K

EDC

HD

HD

IM

EDC

HD

HD

IM

IC

K

RX

KC

PB W

L M N O P Q R S T U

Patient Bed Room

A-657

Patient Bed Room

A-658

Patient Bed Room

A-659

Corridor A-640

Patient Bed Room

A-660

Patient Bed Room

A-661

Isolation Room

A-662

Patient Bed Room

A-656

Patient Bed Room

A-655

Patient Bed Room

A-654

Stair-6 A-653

Ante Room

A-663

Medicine Prep

A-664

Nurse Station

A-665

Clean Linen

A-652

Supply Room

A-651

Nurse MGR Office

A-650A-649

Conference Room

Multi-Purpose

Toilet

A-648B

On-Call Room

A-648

On-Call Room

A-648C

Toilet

A-678A

Locker

A-677A

Toilet

A-677B

Locker

A-677C

HAC

A-676

Kitchen

A-677

Electrical Room

A675

Storage

A-674

Patient Bed Room

A-673

Dirty Utility

A-666

Storage A-647A

On-Call Room

A-648A

7 8

5 14

16 16 16 16

161616

17302CA-640

K

L M N O P Q R S T U

Patient Bed Room

A-657

Patient Bed Room

A-658

Patient Bed Room

A-659

Corridor A-640

Patient Bed Room

A-660

Patient Bed Room

A-661

Isolation Room

A-662

Patient Bed Room

A-656

Patient Bed Room

A-655

Patient Bed Room

A-654

Stair-6 A-653

Ante Room

A-663

Medicine Prep

A-664

Nurse Station

A-665

Clean Linen

A-652

Supply Room

A-651

Nurse MGR Office

A-650A-649

Conference Room

Multi-Purpose

Toilet

A-648B

On-Call Room

A-648

On-Call Room

A-648C

Toilet

A-678A

Locker

A-677A

Toilet

A-677B

Locker

A-677C

HAC

A-676

Kitchen

A-677

Electrical Room

A675

Storage

A-674

Patient Bed Room

A-673

Dirty Utility

A-666

Storage A-647A

On-Call Room

A-648A

16 16 16 16

161616

A-640

1. NEW DOOR POSITION SWITCH, RECESSED.

2. NEW DOOR OPERATOR WITH CONTROL INTERFACES FROM DOOR

FRAME TO COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF

DOOR.

3. COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF DOOR.

(12"X12"X4" WITH SECURITY SCREW COVER).

4. NEW POWER SUPPLY FOR NEW MAG LOCKS.

5. REPLACE EXISTING PUSH PLATE WITH NEW WAVE SENSOR, REFER

TO DRAWINGS FOR REVISED LOCATION.

6. PROVIDE NEW KEYSWITCH IN EXISTING BOX. WIRE TO ACCESS

CONTROL SYSTEM AS LOCAL DOOR LOCK OVERRIDE.

7. PRESENCE SENSOR AND REQUEST TO EXIT MOTION SENSOR AT

HEAD OF DOOR. INTEGRATED WITH DOOR OPENER..

8. NEW CARD READER SYSTEM COMBO KEYPAD/PROX READER, RE-

USE EXISTING BACKBOX. PROGRAM FOR KEYPAD OPERATION ONLY.

9. NEW WALL MOUNTED DOOR AUDIO/VIDEO INTERCOM, MOUNT ON

EXISTING BACKBOX.

10. EXTEND LOW VOLTAGE SECURITY/ CONTROL WIRING TO NEW ISTAR

EDGE CONTROLLER FOR COMPLETE INTERFACE AT DOOR.

11. NEW MAG LOCK.

FINISH FLOOR

CEILING

NON-SECURE SIDESECURE SIDE

MAG LOCK DOUBLE DOOR WITH CARD

READER ACCESS/INTERCOM ENTRY/EXIT AND

AUTO OPEN

HD

KC

46" MH

PS

K

46" MH

IC

RX

POWER

SUPPLY

120V

FIRE

ALARM

RELAY

DOOR DETAIL NOTES

1 1

P: 937-224-0861 www.heapy.com

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities ManagementPROJECT NO.

STATE COA FIRM NO.

Consultant:

/1

/2

:4

:0

A

M

VA Louisville Replace 6N Patient Room Doors

06/16/2021

PARTIAL SIXTH FLOOR PLANS -

REMOVALS & NEW WORK

ET106

PABJDK

603-21-201

LOUISVILLE, KY.

100% CONSTRUCTION

DOCUMENTS

21001.00

2021-05026.01

HEAPY

1400 W. DOROTHY LN

DAYTON, OHIO 45409

937.224.0862

Scale: 1/8" = 1'-0"2

PARTIAL SIXTH FLOOR PLAN - REMOVALS

Scale: 1/8" = 1'-0"1

PARTIAL SIXTH FLOOR PLAN - NEW WORK

KEYPLAN

N

PLAN NOTES

1. DISCONNECT AND REMOVE 120V WIRING FROM EXISTING DOOR CONTROL COMPONENTS BACK

TO THE ABOVE CEILING CONTROL BOX. THE EXISTING 120V CIRCUIT SHALL REMAIN FOR REUSE

WITH NEW DOOR OPENERS. ANY CONDUITS CONNECTED INTO DOOR FRAME SHALL REMAIN.

2. PROVIDE NEW 120V WIRING FROM ABOVE CEILING CONTROL BOX TO NEW DOOR OPENERS.

3. EXTEND EXISTING CONDUITS FOR PROX READER/KEYPAD, INTERCOM, REQUEST TO EXIT AND

KEYWAY FOR DOOR SECURITY OVERRIDE TO ABOVE CEILING CONTROL BOX AS REQUIRED.

4. EXISTING WALL MOUNTED KEYPAD ENTRY STATION TO BE REMOVED. EXISTING BOX/CONDUIT

TO REMAIN FOR RE-USE. REMOVE EXISTING WIRING.

5. EXISTING WALL MOUNTED INTERCOM DOOR STATION TO BE REMOVED. EXISTING BOX/CONDUIT

TO REMAIN FOR RE-USE. REMOVE EXISTING WIRING.

6. EXISTING WALL MOUNTED KEYSWITCH TO BE REMOVED. EXISTING BOX/CONDUIT TO REMAIN

FOR RE-USE. REMOVE EXISTING WIRING.

7. EXISTING MAG LOCK TO BE REMOVED. REMOVE EXISTING WIRING.

8. EXISTING WALL MOUNTED PUSH TO EXIT STATION TO BE REMOVED. REMOVE EXISTING WIRING.

9. PROVIDE NEW WALL MOUNTED KEYPAD ENTRY STATION. UTILIZE EXISTING BOX/CONDUIT FOR

NEW WIRING. PROVIDE NEW WIRING TO NEW DOOR OPERATOR.

10. PROVIDE NEW WALL MOUNTED AIPHONE VIDEO INTERCOM DOOR STATION . UTILIZE EXISTING

BOX/CONDUIT FOR NEW WIRING. EXTEND NEW WIRING TO REPLACED DOOR INTERCOM

MASTER STATION AND TO DOOR OPERATOR FOR DOOR CONTROL.

11. PROVIDE NEW WALL MOUNTED KEYSWITCH. UTILIZE EXISTING BOX/CONDUIT FOR NEW WIRING.

PROVIDE NEW WIRING TO NEW MAG LOCKS FOR REMOTE OVERRIDE.

12. PROVIDE NEW MAG LOCKS. PROVIDE NEW WIRING TO KEYSWITCH, INTERCOM AND DOOR

OPERATOR.

13. PROVIDE NEW WALL MOUNTED PUSH TO EXIT STATION INCLUDING 1- GANG BOX, 0.75" CONDUIT

AND WIRING TO NEW DOOR OPERATOR..

14. EXISTING AIPHONE MASTER STATION TO BE REPLACED, INCLUDING WIRING.

15. NEW AIPHONE MASTER STATION INCLUDING WIRING.

16. EXISTING DOOR SENSORS WHICH CONNECT INTO ROOM PRESSURE ALARM SYSTEM ARE TO BE

REMOVED AND REPLACED WITH NEW. COORDINATE WITH MANUFACTURER (TSI) FOR SPECIFIC

SENSOR TO BE USED AND PLACEMENT ON NEW DOOR. PROVIDE NEW WIRING BETWEEN

SENSOR AND ALARM SYSTEM.

17. PROVIDE FIRE ALARM CONNECTION FOR DOORWAY AS REQUIRED.

18. PROVIDE NEW SOFTWARE HOUSE ISTAR 2 EDGE 2-DOOR CONTROLLER AND POWER SUPPLY

TO SERVE RE-CONFIGURED CORRIDOR DOOR. PROVIDE NEW DATA DROP FOR PANEL

CONNECTIVITY.

19. PROVIDE NEW PUSHBUTTON AT DESK TO INITIATE EMERGENCY LOCKDOWN OF CORRIDOR

DOOR. WIRE INTO NEW ISTAR DOOR CONTROLLER AND PROVIDE ADDITIONAL PROGRAMMING

AS REQUIRED.

SECURITY DOOR DETAILS

GENERAL NOTES

A. WALL MOUNTED KEY SWITCH, MAG LOCKS, WALL MOUNTED KEYPAD,

DOOR HARDWARE, WALL MOUNTED INTERCOM AND RETURN TO VA MAINTENANCE.

File details come from the government source that posted it. Updated .