This solicitation package outlines requirements for a construction project to replace doors in an intensive care unit at a Department of Veterans Affairs medical center. The contractor will provide all labor, materials, equipment, logistics, and supervision to replace primary entrance and patient room doors in the unit with new doors and access control features, in accordance with project specifications and drawings. Work includes infection control measures at BioSafety Level 4 and phasing to allow continued unit operation. Bids must be submitted electronically by the specified due date. The solicitation provides bidding instructions and an overview of the scope of work, which involves replacing doors to meet new accessibility and security standards while minimizing patient disruption.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAG
A101
SIM
X
E 1 0th
S t.
E. M arke t S t.
S pring
S t.
M ockingbird
V alley R d.
Z orn A ve.River R d.
B lanke nba ker L n.
D
r. M
.L .K
Jr. E xp y
Frankfort Ave.
Brownsboro R d.
C henow eth Ln.
W estport R d.
E. Main St.
Story Ave.
E. Broadway
Shelbyville Rd.
B axte r A ve.
VAMC
800 Zorn Ave.
Ohio R ive r
Kosair Children's Hospital
Cave Hill Cemetery
Thurm an
Hutc hin
P ark
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Department of Veterans Affairs Medical Center
HEAPY ENGINEERING
MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
ARCHITECTURE PLANNING INTERIOR DESIGN
524 FERNWOOD AVENUE
ALTAMONTE SPRINGS, FLORIDA 32701
407.830.6522 P
937.461.0260 F
RDC / JOHN POE ARCHITECTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:3
:2
P
M
VA Louisville Replace 6N Patient Room Doors
6/15/2021
COVER SHEET
G001
ACMD
603-21-201
VA Louisville Replace 6N Patient Room Doors 800 Zorn Avenue Louisville, KY 40206 PROJECT #: 603-21-201
100% CD
21001.00
G001 COVER SHEET
A101 PLANS & DETAILS
ET001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS
ET106 PARTIAL SIXTH FLOOR PLANS - REMOVALS & NEW WORK
GENERAL CONSTRUCTION NOTES
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO
ORDERING, FABRICATING OR INSTALLING NEW MATERIALS.
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO BE INSTALLED AS
PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE SPECIAL PROVISIONS TO INSTALL
EQUIPMENT THAT IS TOO LARGE TO FIT THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AS INDICATED IN THE CONTRACT DOCUMENTS
AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL WOOD BLOCKING SHALL BE FIRE
RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS SPECIFICALLY NOTED
OTHERWISE. IF NO FINISH IS INDICATED AT A PARTICULAR SURFACE, CONTRACTOR SHALL
PROVIDE FINISH(S) AS INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS WHICH COMPLY
WITH STATED CODES AND REGULATIONS. WHERE THE OMISSION OF A PART OR ELEMENT OF A
SYSTEM WOULD RESULT IN THE NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM,
CONTRACTOR SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED WALLS SHALL BE
SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF THE WALL.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE CONTRACTING OFFICER'S
REPRESENTATIVE (C.O.R.).
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE, INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF
VETERAN AFFAIRS, TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST ARCHITECTURAL BARRIERS
ACT ACCESSIBILITY STANDARD (ABAAS) AND DEPARTMENT OF VETERANS AFFAIRS BARRIER
FREE DESIGN GUIDE PG-18-13 WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS
AFFAIRS TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT EXISTING
CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH ADJACENT EXISTING
SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED DURING THE COURSE
OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF NEW WORK,
CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO REMAIN OR PROVIDE NEW
CONSTRUCTION TO MATCH EXISTING ADJACENT SURFACES TO REMAIN.
DRAWING INDEX
N N.T.S.Scale:
VICINITY MAP
Revisions Date
Locker
A-677A
Toilet
A-677B
Kitchen
A-677
Locker
A-677C
HAC
A-676 Electrical
Room
A675
Storage
A-674
Patient Bed Room
A-673
Dirty Utility
A-666
Ante Room
A-663
Isolation Room
A-662
Patient Bed Room
A-661
Patient Bed Room
A-660
Patient Bed Room
A-659
Patient Bed Room
A-658
Patient Bed Room
A-657 Patient Bed
Room
A-656
Patient Bed Room
A-655
Patient Bed Room
A-654
Stair-6
A-653 Clean Linen
A-652
Supply Room
A-651
Nurse MGR Office
A-650
Conference Room
Multi-Purpose
A-649Toilet
A-648B
On-Call Room
A-648A
On-Call Room
A-648
On-Call Room
A-648C
Storage
A-647A
Break Room
A-643B Restroom
A-643A
Toilet
A-678A
Waiting
A-678
Medicine Prep
A-664
Nurse Station
A-665
Elevator Lobby
A-647
Pipe Chase
A-643C
A-640
A-654 A-655
A-656 A-657
A-658
A-659
A-660A-661A-662
Corridor
A-640
Corridor
A-641
1.071.07
1.071.07 1.071.07
1.071.071.071.07
10'-0"
1.05 2.04
1.06 8.10 8.10
8.108.10
8.108.10
8.10
8.10
8.10
Locker
A-677A
Toilet
A-677B
Kitchen
A-677
Locker
A-677C
HAC
A-676 Electrical
Room
A675
Storage
A-674
Patient Bed Room
A-673
Dirty Utility
A-666
Ante Room
A-663
Isolation Room
A-662
Patient Bed Room
A-661
Patient Bed Room
A-660
Patient Bed Room
A-659
Patient Bed Room
A-658
Patient Bed Room
A-657
Patient Bed Room
A-656
Patient Bed Room
A-655
Patient Bed Room
A-654
Stair-6
A-653 Clean Linen
A-652
Supply Room
A-651
Nurse MGR Office
A-650
Conference Room
Multi-Purpose
A-649Toilet
A-648B
On-Call Room
A-648A
On-Call Room
A-648
On-Call Room
A-648C
Storage
A-647A
Break Room
A-643B Restroom
A-643A
Toilet
A-678A
Waiting
A-678
Medicine Prep
A-664
Nurse Station
A-665
Elevator Lobby
A-647
Pipe Chase
A-643C
1.03
1.03 1.03
1.03
1.03
1.03
1.03
1.03
1.03
1.03
2.51
2.52
M in
M in
M in
M in
M in
1.04
1.041.04 1.041.04
1.041.04
1.04
8" 8"
SEE SCHED.
S E
E S
C H
E D
U L E
NS
SEE SCHEDULE
S E
E S
C H
E D
U L E
/4
4'-0" wide sliding door
3 1/4" SEE SCHEDULE 3 1/4"
/4
S E
E S
C H
E D
U L E
SEE PLAN
H1
J1
9.21
9.80
9.09
9.21
9.80
H2
J2
9.08
7.83
7.83
SEE PLAN
9.21
9.80
9.08
7.83
8.10
9.09
9.21
9.80
6.07
7.83
8.10
8.08
8.08
1/2" 1/2"
LEGEND
Wall/Door to be Demolished
Existing to Remain
New Wall
ST
A
T E O F F L O R
I D A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:3
:2
P
M
VA Louisville Replace 6N Patient Room Doors
6/15/2021
PLANS & DETAILS
A101
ACMD
603-21-201
100% CD
21001.00
Scale: 1/8" = 1'-0"1 Sixth Floor New Work Plan
NOTES
Key Plan
Scale: 1/8" = 1'-0"2 Sixth Floor Demolition Plan
Scale: 1/4" = 1'-0"
Door Types Scale: 1/4" = 1'-0"
Frame Types
Scale: 1 1/2" = 1'-0"
Door Details
1.03 Remove existing door and harware. Existing frame to remain. Patch and prep frame as required to receive new doors and hardware.
1.04 Temporary partition per ICRA requirements.
1.05 New Keypad.
1.06 New door actuator.
1.07 Negative pressure room.
2.04 Existing intercom to remain.
2.51 Remove existing keypad.
2.52 Remove existing door actuator, patch wall & paint to match existing.
6.07 2" x 4" fire retardant treated blocking.
7.83 Cont. sealant each side.
8.08 Double egress hollow metal frame.
8.10 Anodized aluminum ICU door frame
9.08 Metal framing box header.
9.09 Double metal framing at jambs, typ.
9.21 5/8" Type X gypsum board.
9.80 Acoustic insulation
DOOR SCHEDULE
DOOR
BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION
FIRE
RATING
HDWE
SET REMARKSRM RM TYPE MAT'L
SIZE
TYPE MAT'L HEAD JAMB# W H T
A-640 A-641 A-640 N WD 2 3'-6" 7'-0" 1 3/4" 3 HM H1 J1 20 MIN 1.0 Existing frame to remain.
A-654 A-640 A-654 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-655 A-655 A-640 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-656 A-656 A-640 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-657 A-640 A-657 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-658 A-640 A-658 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-659 A-640 A-659 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-660 A-640 A-660 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-661 A-640 A-661 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
A-662 A-662 A-640 S AL/GL 1 8'-0" 7'-4" 1 3/4" - AL H2 J2 -- --
GENERAL NOTES
A. All dimensions are taken to face of gypsum wallboard or unit masonry.
B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.
C. All wood blocking to be fire retardent treated.
D. Remove all doors where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner. Deliver boxed hardware to the VA Maintenance Shop, B016 Basement Floor.
E. See Electrical Drawings for removal work associated with those trades.
F. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.R.
G. Repair existing walls to match adjacent undisturbed wall where disturbed by new work.
H. Phase project so only one patient bed room may be inoperable at any point in time. Fully complete each door, including punchlist and COR approval prior to beginning next door.
* ALL NEW DOORS TO FIT IN EXISITNG OPENING. CONTRACTOR TO FIELD VERIFY EXISTING OPENING SIZE & MANUFACTURE DOOR TO FIT EXISTING OPENING.
Revisions Date
Addendum 1
Addendum 1
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE
REQUIRED.
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
IC
WALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.
HD
AUTOMATIC DOOR OPERATOR MOTOR ASSEMBLY. 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND
DOOR ACTUATOR BUTTONS. REFER TO SECURITY ROUGH-IN DETAILS.
K WALL MOUNTED SECURITY KEYSWITCH (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYSWITCH AND CABLING PER DIV 28.
PB W
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL TRADES (DIVISION 01)
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY (DIVISION 28)
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTOR
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
F
F
F
F
F
S F
KF
S
H
C
D
FS
V
R W
SD
FT
PS
AM
C/I
PIV
K S
H
S S/R
S/R
FACP
FIRE ALARM SYMBOLS
FIRE ALARM BELL & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM CHIME & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM HORN & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
FIRE ALARM SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
CEILING MOUNTED FIRE ALARM SPEAKER.
FIRE ALARM CONTROL PANEL.
CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.
WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER
LOCATIONS.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
CEILING MOUNTED HEAT DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRIC RELEASE DOOR CLOSER.
ELECTRO-MAGNETIC DOOR HOLDER.
WATER FLOW SWITCH.
VALVE SUPERVISORY SWITCH.
CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES
WALL MOUNTED.
SMOKE DAMPER.
FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).
PRESSURE SWITCH.
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
POST INDICATOR VALVE.
KNOX BOX (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "S" INDICATES SUPERVISED UNIT.
FIRE ALARM BELL (88" AFF UNLESS NOTED OTHERWISE). SUBSCRIPT "W" INDICATES EXTERIOR WEATHERPROOF UNIT.
BEAM DETECTOR. SUBSCRIPT "T" INDICATES TRANSMITTER FUNCTION. SUBSCRIPT "R" INDICATES RECEIVER FUNCTION.
AIR SAMPLING SMOKE DETECTOR SAMPLING PORT.
REMOTE ANNUNCIATOR PANEL.
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.
AIR SAMPLING SMOKE DETECTOR BASE UNIT.
SURFACE MOUNTED FIRE ALARM SPEAKER (88" AFF). SUBSCRIPT "R" INDICATES RECESSED MOUNTING.
RAP
NAC
ASSD
F W
S F
S R
A
B T/R
E2
B
E2
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES
CIRCUIT(S).
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CONDUIT FOR DATA CIRCUITRY.DAT
WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA
WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL
CONDUIT FOR PHONE CIRCUITRY.PHO
WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC
WIRE RUN IN SURFACE WIREWAY.W
CABLE MANAGEMENT SYSTEM PATHWAY.CM
X - 1,2
WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM
WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S
WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I
WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV
CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
4"
4"
4"
T2 1 ELEVATION: 1 = ELEVATION DESIGNATION
T2 = SHEET WHERE ELEVATION IS LOCATED
CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
F
EDC
X ELECTRONIC DOOR CONTROL. SUPERSCRIPT "X" INDICATES SPECIFIC DOOR. REFER TO ELECTRONIC DOOR CONTROL
SCHEDULE FOR REQUIREMENTS.
LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS
SCHEDULE FOR ROOM CONTROL.
3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.
KC
WALL MOUNTED COMBINATION PROX READER/KEYPAD (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75"
CONDUIT TO ABOVE ACCESSIBLE CEILING. KEYPAD AND CABLING PER DIV 28.
RX
WALL MOUNTED REQUEST TO EXIT WAVE SENSOR (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75"
CONDUIT TO ABOVE ACCESSIBLE CEILING. WAVE SENSOR AND CABLING PER DIV 28.
K
WALL MOUNTED KEYPAD ENTRY STATION..
K
DESK MOUNTED PUSH BUTTON WITH WIRING FOR LOCAL DOOR LOCK-DOWN. CONNECT TO NEW PACS DOOR
CONTROLLER AND PROGRAM INTO SYSTEM.
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities ManagementPROJECT NO.
STATE COA FIRM NO.
Consultant:
/1
/2
:4
:0
A
M
VA Louisville Replace 6N Patient Room Doors
06/16/2021
ABBREVIATIONS, SYMBOLS &
INDEX OF DRAWINGS
ET001
PABJDK
603-21-201
LOUISVILLE, KY.
100% CONSTRUCTION
DOCUMENTS
21001.00
2021-05026.01
HEAPY
1400 W. DOROTHY LN
DAYTON, OHIO 45409
937.224.0862
INDEX OF DRAWINGS
SHEET NUMBER SHEET NAME
ET001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS
ET106 PARTIAL SIXTH FLOOR PLANS - REMOVALS & NEW WORK
NOTES:
ELECTRONIC DOOR CONTROLS SCHEDULE
E D
C N
U M
B E
R
D O
O R
O P
E N
IN
G
N U
M B
E R
CONTROL LOCKS REQUEST TO EXIT DOOR MONITOR
AUTOMATIC DOOR
OPERATOR
S P
E C
IA
L
D O
O R
N O
T E
SEAC INTERFACE POWER TYPE
Q T
Y
FUNCTION LOCATION POSITION SWITCH L BOLT
BOND
SENSOR MOTOR PUSHPLATE
R E
A D
E R
T O
D
F
IR
E A
L A
R M
I N
T E
R C
O M
P U
S H
B U
T T
O N
I N
T R
U S
IO
N
A L
A R
M
P O
E P
O E
V O
L T
A G
E
L O
C A
L
R E
M O
T E
L O
C A
T
IO
N
N O
T E
EP EL ES ML
W L A
L A
R M
S H
U N
T
U N
L O
C K
N O
T E
H A
R D
W A
R E
M O
T
IO
N
W A
L L
S W
IT
C
H
N O
T E
QTY #
P
T
B A
L A
N C
E D
H
IG
H S
E C
U R
IT
Y
R E
C E
S S
E D
S U
R F
A C
E
QTY QTY QTY E
A
C I
N T
E R
F A
C E
QTY W
IR
E L
E S
S
1 ● ● ● ● ● 24 ● ● 3 ● ● ● ● ● 2 DPDT ● ● 0 2 2 ● 0
IC
K
RX
K
EDC
HD
HD
IM
EDC
HD
HD
IM
IC
K
RX
KC
PB W
L M N O P Q R S T U
Patient Bed Room
A-657
Patient Bed Room
A-658
Patient Bed Room
A-659
Corridor A-640
Patient Bed Room
A-660
Patient Bed Room
A-661
Isolation Room
A-662
Patient Bed Room
A-656
Patient Bed Room
A-655
Patient Bed Room
A-654
Stair-6 A-653
Ante Room
A-663
Medicine Prep
A-664
Nurse Station
A-665
Clean Linen
A-652
Supply Room
A-651
Nurse MGR Office
A-650A-649
Conference Room
Multi-Purpose
Toilet
A-648B
On-Call Room
A-648
On-Call Room
A-648C
Toilet
A-678A
Locker
A-677A
Toilet
A-677B
Locker
A-677C
HAC
A-676
Kitchen
A-677
Electrical Room
A675
Storage
A-674
Patient Bed Room
A-673
Dirty Utility
A-666
Storage A-647A
On-Call Room
A-648A
7 8
5 14
16 16 16 16
161616
17302CA-640
K
L M N O P Q R S T U
Patient Bed Room
A-657
Patient Bed Room
A-658
Patient Bed Room
A-659
Corridor A-640
Patient Bed Room
A-660
Patient Bed Room
A-661
Isolation Room
A-662
Patient Bed Room
A-656
Patient Bed Room
A-655
Patient Bed Room
A-654
Stair-6 A-653
Ante Room
A-663
Medicine Prep
A-664
Nurse Station
A-665
Clean Linen
A-652
Supply Room
A-651
Nurse MGR Office
A-650A-649
Conference Room
Multi-Purpose
Toilet
A-648B
On-Call Room
A-648
On-Call Room
A-648C
Toilet
A-678A
Locker
A-677A
Toilet
A-677B
Locker
A-677C
HAC
A-676
Kitchen
A-677
Electrical Room
A675
Storage
A-674
Patient Bed Room
A-673
Dirty Utility
A-666
Storage A-647A
On-Call Room
A-648A
16 16 16 16
161616
A-640
1. NEW DOOR POSITION SWITCH, RECESSED.
2. NEW DOOR OPERATOR WITH CONTROL INTERFACES FROM DOOR
FRAME TO COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF
DOOR.
3. COMMON SECURITY JUNCTION BOX ON SECURE SIDE OF DOOR.
(12"X12"X4" WITH SECURITY SCREW COVER).
4. NEW POWER SUPPLY FOR NEW MAG LOCKS.
5. REPLACE EXISTING PUSH PLATE WITH NEW WAVE SENSOR, REFER
TO DRAWINGS FOR REVISED LOCATION.
6. PROVIDE NEW KEYSWITCH IN EXISTING BOX. WIRE TO ACCESS
CONTROL SYSTEM AS LOCAL DOOR LOCK OVERRIDE.
7. PRESENCE SENSOR AND REQUEST TO EXIT MOTION SENSOR AT
HEAD OF DOOR. INTEGRATED WITH DOOR OPENER..
8. NEW CARD READER SYSTEM COMBO KEYPAD/PROX READER, RE-
USE EXISTING BACKBOX. PROGRAM FOR KEYPAD OPERATION ONLY.
9. NEW WALL MOUNTED DOOR AUDIO/VIDEO INTERCOM, MOUNT ON
EXISTING BACKBOX.
10. EXTEND LOW VOLTAGE SECURITY/ CONTROL WIRING TO NEW ISTAR
EDGE CONTROLLER FOR COMPLETE INTERFACE AT DOOR.
11. NEW MAG LOCK.
FINISH FLOOR
CEILING
NON-SECURE SIDESECURE SIDE
MAG LOCK DOUBLE DOOR WITH CARD
READER ACCESS/INTERCOM ENTRY/EXIT AND
AUTO OPEN
HD
KC
46" MH
PS
K
46" MH
IC
RX
POWER
SUPPLY
120V
FIRE
ALARM
RELAY
DOOR DETAIL NOTES
1 1
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities ManagementPROJECT NO.
STATE COA FIRM NO.
Consultant:
/1
/2
:4
:0
A
M
VA Louisville Replace 6N Patient Room Doors
06/16/2021
PARTIAL SIXTH FLOOR PLANS -
REMOVALS & NEW WORK
ET106
PABJDK
603-21-201
LOUISVILLE, KY.
100% CONSTRUCTION
DOCUMENTS
21001.00
2021-05026.01
HEAPY
1400 W. DOROTHY LN
DAYTON, OHIO 45409
937.224.0862
Scale: 1/8" = 1'-0"2
PARTIAL SIXTH FLOOR PLAN - REMOVALS
Scale: 1/8" = 1'-0"1
PARTIAL SIXTH FLOOR PLAN - NEW WORK
KEYPLAN
N
PLAN NOTES
1. DISCONNECT AND REMOVE 120V WIRING FROM EXISTING DOOR CONTROL COMPONENTS BACK
TO THE ABOVE CEILING CONTROL BOX. THE EXISTING 120V CIRCUIT SHALL REMAIN FOR REUSE
WITH NEW DOOR OPENERS. ANY CONDUITS CONNECTED INTO DOOR FRAME SHALL REMAIN.
2. PROVIDE NEW 120V WIRING FROM ABOVE CEILING CONTROL BOX TO NEW DOOR OPENERS.
3. EXTEND EXISTING CONDUITS FOR PROX READER/KEYPAD, INTERCOM, REQUEST TO EXIT AND
KEYWAY FOR DOOR SECURITY OVERRIDE TO ABOVE CEILING CONTROL BOX AS REQUIRED.
4. EXISTING WALL MOUNTED KEYPAD ENTRY STATION TO BE REMOVED. EXISTING BOX/CONDUIT
TO REMAIN FOR RE-USE. REMOVE EXISTING WIRING.
5. EXISTING WALL MOUNTED INTERCOM DOOR STATION TO BE REMOVED. EXISTING BOX/CONDUIT
TO REMAIN FOR RE-USE. REMOVE EXISTING WIRING.
6. EXISTING WALL MOUNTED KEYSWITCH TO BE REMOVED. EXISTING BOX/CONDUIT TO REMAIN
FOR RE-USE. REMOVE EXISTING WIRING.
7. EXISTING MAG LOCK TO BE REMOVED. REMOVE EXISTING WIRING.
8. EXISTING WALL MOUNTED PUSH TO EXIT STATION TO BE REMOVED. REMOVE EXISTING WIRING.
9. PROVIDE NEW WALL MOUNTED KEYPAD ENTRY STATION. UTILIZE EXISTING BOX/CONDUIT FOR
NEW WIRING. PROVIDE NEW WIRING TO NEW DOOR OPERATOR.
10. PROVIDE NEW WALL MOUNTED AIPHONE VIDEO INTERCOM DOOR STATION . UTILIZE EXISTING
BOX/CONDUIT FOR NEW WIRING. EXTEND NEW WIRING TO REPLACED DOOR INTERCOM
MASTER STATION AND TO DOOR OPERATOR FOR DOOR CONTROL.
11. PROVIDE NEW WALL MOUNTED KEYSWITCH. UTILIZE EXISTING BOX/CONDUIT FOR NEW WIRING.
PROVIDE NEW WIRING TO NEW MAG LOCKS FOR REMOTE OVERRIDE.
12. PROVIDE NEW MAG LOCKS. PROVIDE NEW WIRING TO KEYSWITCH, INTERCOM AND DOOR
OPERATOR.
13. PROVIDE NEW WALL MOUNTED PUSH TO EXIT STATION INCLUDING 1- GANG BOX, 0.75" CONDUIT
AND WIRING TO NEW DOOR OPERATOR..
14. EXISTING AIPHONE MASTER STATION TO BE REPLACED, INCLUDING WIRING.
15. NEW AIPHONE MASTER STATION INCLUDING WIRING.
16. EXISTING DOOR SENSORS WHICH CONNECT INTO ROOM PRESSURE ALARM SYSTEM ARE TO BE
REMOVED AND REPLACED WITH NEW. COORDINATE WITH MANUFACTURER (TSI) FOR SPECIFIC
SENSOR TO BE USED AND PLACEMENT ON NEW DOOR. PROVIDE NEW WIRING BETWEEN
SENSOR AND ALARM SYSTEM.
17. PROVIDE FIRE ALARM CONNECTION FOR DOORWAY AS REQUIRED.
18. PROVIDE NEW SOFTWARE HOUSE ISTAR 2 EDGE 2-DOOR CONTROLLER AND POWER SUPPLY
TO SERVE RE-CONFIGURED CORRIDOR DOOR. PROVIDE NEW DATA DROP FOR PANEL
CONNECTIVITY.
19. PROVIDE NEW PUSHBUTTON AT DESK TO INITIATE EMERGENCY LOCKDOWN OF CORRIDOR
DOOR. WIRE INTO NEW ISTAR DOOR CONTROLLER AND PROVIDE ADDITIONAL PROGRAMMING
AS REQUIRED.
SECURITY DOOR DETAILS
GENERAL NOTES
A. WALL MOUNTED KEY SWITCH, MAG LOCKS, WALL MOUNTED KEYPAD,
DOOR HARDWARE, WALL MOUNTED INTERCOM AND RETURN TO VA MAINTENANCE.
File details come from the government source that posted it. Updated .