This solicitation is for renovation services at the Fayetteville Veteran Affairs Medical Center in Fayetteville, North Carolina. The scope of work includes renovating the basement and first floor of the Halls and Walls building to update finishes, fixtures, equipment and systems. Services required include architectural, mechanical, electrical and plumbing work. The solicitation is open to small businesses with a response due date of August 15, 2022 and period of performance of 365 days. The award amount is undetermined with funding provided by the Department of Veterans Affairs.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T T
11 11 11
11 11 11 11
EXISTING KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING AIR TERMINAL TO BE REMOVED, REINSTALLED AND RELOCATED AS
NECESSARY TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. SEE NEW
WORK PLANS.
EXISTING THERMOSTAT TO BE REMOVED, REINSTALLED AND RELOCATED AS
NECESSARY TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. SEE NEW
WORK PLANS.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:0
P
M
MD101C
MECHANICAL - FIRST LEVEL DEMOLITION
PLAN - D WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - FIRST LEVEL DEMOLITION PLAN - D WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
8 84 16 32
Revisions: Date:
T
1 1 1
NEW WORK KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING AIR TERMINAL TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE NEW ARCHITECTURAL RENOVATIONS. CLEAN AIR TERMINAL
TO LIKE NEW FINISH BEFORE REINSTALLING.
EXISTING THERMOSTAT TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE NEW ARCHITECTURAL RENOVATIONS. CLEAN THERMOSTAT
TO LIKE NEW FINISH BEFORE REINSTALLING.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:0
P
M
MH100A
MECHANICAL - BASEMENT RENOVATION
PLAN - A WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - BASEMENT RENOVATION PLAN - A WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
PM
PM
NEW WORK KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING PRESSURE MONITOR TO BE REINSTALLED AND RELOCATED AS
NECESSARY TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN
DEVICE TO LIKE NEW FINISH BEFORE REINSTALLING.
EXISTING AIR TERMINAL TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN AIR TERMINAL TO
LIKE NEW FINISH BEFORE REINSTALLING.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:1
P
M
MH100B
MECHANICAL - BASEMENT RENOVATION
PLAN - B & C WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - BASEMENT RENOVATION PLAN - B & C WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
TT
T
T T
1 1
NEW WORK KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING AIR TERMINAL TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN AIR TERMINAL TO
LIKE NEW FINISH BEFORE REINSTALLING.
EXISTING THERMOSTAT TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN THERMOSTAT TO
LIKE NEW FINISH BEFORE REINSTALLING.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:1
P
M
MH100C
MECHANICAL - BASEMENT RENOVATION
PLAN - D WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - BASEMENT RENOVATION PLAN - D WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
JT
NEW WORK KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING AIR TERMINAL TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN AIR TERMINAL TO
LIKE NEW FINISH BEFORE REINSTALLING.
EXISTING IT COMPONENTS TO BE REINSTALLED AND RELOCATED AS
NECESSARY TO ACCOMMODATE NEW ARCHITECTURAL RENOCATIONS.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:1
P
M
MH101A
MECHANICAL - FIRST LEVEL
RENOVATION PLAN - A WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - FIRST LEVEL RENOVATION PLAN - A WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
NEW WORK KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING AIR TERMINAL TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN AIR TERMINAL TO
LIKE NEW FINISH BEFORE REINSTALLING.
EXISTING IT COMPONENTS TO BE REINSTALLED AND RELOCATED AS
NECESSARY TO ACCOMMODATE NEW ARCHITECTURAL RENOCATIONS.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:2
P
M
MH101B
MECHANICAL - FIRST LEVEL
RENOVATION PLAN - B & C WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - FIRST LEVEL RENOVATION PLAN - B & C WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
DN
T T
1 1 1
1 1
1 1
NEW WORK KEYED NOTES
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED, IS INTENDED FOR GENERAL REFERENCE ONLY.
B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS
TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND
SHALL BE AT THE OWNERS DISCRETION.
C. ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING
CONSTRUCTION SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO
MATCH ADJACENT INSULATION AND COVERING.
D. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
E. MECHANICAL CONTRACTOR SHALL RELOCATE ANY EXISTING EQUIPMENT TO
REMAIN AS REQUIRED TO COORDINATE INSTALLATION OF NEW WORK.
F. ALL EXISTING CONTROLS COMPONENTS AND CONTROLS WIRING WITHIN THE
LIMITS OF CONSTRUCTION SHALL REMAIN. IF COMPONENTS NEED TO BE
REMOVED DURING CONSTRUCTION IN THIS AREA TO FACILITATE THE
INSTALLATION OF NEW WORK, THEN THE COMPONENTS SHALL BE REINSTALLED
TO A FUNCTIONAL CONDITION BEFORE PROJECT COMPLETION.
GENERAL NOTES
EXISTING AIR TERMINAL TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN AIR TERMINAL TO
LIKE NEW FINISH BEFORE REINSTALLING.
EXISTING THERMOSTAT TO BE REINSTALLED AND RELOCATED AS NECESSARY
TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. CLEAN THERMOSTAT TO
LIKE NEW FINISH BEFORE REINSTALLING.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:2
P
M
MH101C
MECHANICAL - FIRST LEVEL
RENOVATION PLAN - D WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
MECHANICAL - FIRST LEVEL RENOVATION PLAN - D WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
PLUMBING SYMBOLS
GENERAL
PLUMBING ABBREVIATIONS
WASTE
WALL CLEANOUT
VENT THROUGH ROOF
HOT WATER RETURN
HOT WATER
FLOOR CLEANOUT
EXISTING
DOWN
COLD WATER
CLEANOUT
BELOW FINISHED FLOOR
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
W
WCO
VTR
HWR
HW
FCO
(E)
DN
CW
CO
BFF
AFG
AFF
BALL VALVE
DEMOLISH TO EXSITING
CONNECT TO EXISTING
PIPE CONTINUES
ELBOW UP
ELBOW DOWN
SANITARY WASTER BELOW FINISHED FLOOR
SANITARY VENT ABOVE FINISHED CEILING
COLD WATER ABOVE FINISHED CEILING
HOT WATER ABOVE FINISHED CEILING
EXISTING SANITARY WASTE BELOW FINISHED FLOOR
EXISTING SANITARY VENT ABOVE FINISHED CEILING
EXISTING COLD WATER ABOVE FINSHED CEILING
EXISTING HOT WATER ABOVE FINISHED CEILING
EXISTING SYSTEM TO BE DEMOLISHED
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE THE INSTALLATION OF THE PLUMBING
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:2
P
M
P001
PLUMBING - NOTES, LEGEND AND
DRAWING INDEX
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
PLUMBING - DRAWING INDEX
Sheet
Number Sheet Name
P001 PLUMBING - NOTES, LEGEND AND DRAWING INDEX
PD100A PLUMBING - BASEMENT DEMOLITION PLAN - A WING
PD100B PLUMBING - BASEMENT DEMOLITION PLAN - B & C WING
PD101B PLUMBING - FIRST LEVEL DEMOLITION PLAN - B & C WING
PP100B PLUMBING - BASEMENT RENOVATION PLAN - B & C WING
PP101B PLUMBING - FIRST LEVEL RENOVATION PLAN - B & C WING
PP101C PLUMBING - FIRST FLOOR RENOVATION PLAN - D WING
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE THE INSTALLATION OF THE PLUMBING
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
WATERCOOLER AND ALL ASSOCIATED PIPING TO BE
DEMOLISHED IN ITS ENTIRETY. PC TO CAP SANITARY WASTE
LINE AND WATER PIPING IN WALL.
DEMOLITION KEYED NOTES
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:3
P
M
PD100A
PLUMBING - BASEMENT DEMOLITION
PLAN - A WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
PLUMBING - BASEMENT DEMOLITION PLAN - A WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
REMOVE AND REINSTALL WATERCOOLER AT ADA HEIGHT AND
TO ACCOMMODATE NEW AESTHETIC UPDATES. SEE NEW
WORK.
EXISTING KEYED NOTES
DEMOLITION KEYED NOTES
1 DEMOLISH EXISTING MEDICAL GAS ZONE VALVE BOX AND ALL
ASSOCIATED PIPING COMPLETE.
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:3
P
M
PD100B
PLUMBING - BASEMENT DEMOLITION
PLAN - B & C WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
PLUMBING - BASEMENT DEMOLITON PLAN - B & C WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
11 11
REMOVE AND REINSTALL WATERCOOLER AT ADA HEIGHT AND
TO ACCOMMODATE NEW AESTHETIC UPDATES. SEE NEW
WORK.
EXISTING KEYED NOTES
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:3
P
M
PD101B
PLUMBING - FIRST LEVEL DEMOLITION
PLAN - B & C WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
PLUMBING - FIRST LEVEL DEMOLITION PLAN - B & C WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
PF
COORDINATE THE INSTALLATION OF THE PLUMBING
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
EXISTING WATER COOLER TO BE REINSTALLED AT ADA
HEIGHT AND RELOCATED AS NECESSARY TO ACCOMMODATE
ARCHITECTURAL RENOVATIONS. CLEAN WATER COOLER TO
LIKE NEW FINISH BEFORE REINSTALLING.
NEW WORK KEYED NOTES
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:4
P
M
PP100B
PLUMBING - BASEMENT RENOVATION
PLAN - B & C WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
PLUMBING - BASEMENT RENOVATION PLAN - B & C WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE THE INSTALLATION OF THE PLUMBING
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
EXISTING WATER COOLER TO BE REINSTALLED AT ADA
HEIGHT AND RELOCATED AS NECESSARY TO ACCOMMODATE
ARCHITECTURAL RENOVATIONS. CLEAN WATER COOLER TO
LIKE NEW FINISH BEFORE REINSTALLING.
NEW WORK KEYED NOTES
1 1
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:4
P
M
PP101B
PLUMBING - FIRST LEVEL RENOVATION
PLAN - B & C WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
PLUMBING - FIRST FLOOR RENOVATION PLAN - B & C WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
DN
DN
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE THE INSTALLATION OF THE PLUMBING
SYSTEMS WITH OTHER TRADES PRIOR TO INSTALLATION TO
AVOID CONFLICTS ABOVE CEILING AND BELOW FLOORS.
THE PLUMBING CONTRACTOR SHALL VERIFY ALL WASTE
AND WATER REQUIREMENTS AND LOCATIONS FOR
CONNECTING OWNERS EQUIPMENT PRIOR TO
INSTALLATION. PROVIDE ALL NECESSARY MATERIALS AND
COMPONENTS. VERIFY AND INSTALL PER MANUFACTURES
WRITTEN SPECIFICATIONS, INSTRUCTIONS, AND ALL LOCAL
AND NATIONAL CODES.
PLUMBING CONTRACTOR SHALL COORDINATE WITH
ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED
BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL
NATIONAL CODES.
PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-OFF
VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS ARE TO
BE INSTALLED. WHERE VALVES DO OCCUR, A 2’X2’ ACCESS
PANEL SHALL BE INSTALLED. ARCHITECT SHALL BE
NOTIFIED BEFORE PANEL IS INSTALLED.
THE PLUMBING CONTRACTOR SHALL VERIFY AND
COORDINATE ALL PIPING INVERTS WITH EXISTING
CONDITIONS PRIOR TO NEW INSTALLATIONS.
PLUMBING DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT
INTENDED TO INCLUDE EVERY ASPECT OF THE REQUIRED
WORK. PLUMBING CONTRACTOR SHALL ENSURE A
COMPLETE AND WORKING SYSTEM IS INSTALLED.
FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE, VENT,
STORM, AND WATER PIPING RISERS PRIOR TO ANY
DEMOLITION AND RELOCATION. CONTACT ENGINEER ONCE
PIPING SYSTEMS HAVE BEEN UNCOVERED/EXPOSED.
ALL DRAWINGS ARE DIAGRAMATTIC. CONTRACTOR TO
PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE
WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS
REQUIRED DUE TO FIELD CONDITIONS ARE THE
RESPONSIBILITY OF THE CONTRACTOR
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
EXISTING WATER COOLER TO BE REINSTALLED AT ADA
HEIGHT AND RELOCATED AS NECESSARY TO ACCOMMODATE
ARCHITECTURAL RENOVATIONS. CLEAN WATER COOLER TO
LIKE NEW FINISH BEFORE REINSTALLING.
NEW WORK KEYED NOTES
A B & C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:1
:4
P
M
PP101C
PLUMBING - FIRST FLOOR RENOVATION
PLAN - D WING
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/2022 GAT CAC
100% BID DOCUMENTS
FULLY SPRINKLERED
317-800-6388
1/8" = 1'-0"
PLUMBING - FIRST FLOOR RENOVATION PLAN - D WING
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )ELECTRICAL SYMBOLS
DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.
ON CENTER.
ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.
TELEPHONE TERMINAL BOARD.
EMPTY CONDUIT.
ABBREVIATIONS
AFF
EC
OC
TTB
+60"
NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.NL
TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.
TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.
W = WALL MOUNTED STATION
INTERCOM OUTLET WALL MOUNTED 48" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION UNLESS
INTERCOM WALL MOUNTED 18" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION.
VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE. PROVIDE 1"C. FROM
MODIFIERS FOR INTERCOM:
S = SUB STATION
M = MASTER STATION
TELEPHONE OUTLET, WALL MOUNTED 48" AFF.
VOICE/DATA OUTLET, WALL MOUNTED 48" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH.
PROVIDE 1"C. FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.
OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.
TELEPHONE OUTLET WALL MOUNTED 48" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH,
PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR VOICE/DATA WIRING TO
PRE WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT
MODIFIERS FOR VOICE/DATA & TELEPHONE OUTLETS: (DEVICE AND CONDUCTORS BY TELECOM VENDOR) a = VOICE ONLY b = STANDARD (2 DATA / 1 VOICE SPLIT) c = 1 DATA ONLY d = 4 DATA / 1 VOICE SPLIT
COMMUNICATIONS
VOICE/DATA OUTLET, FLUSH FLOOR MOUNTED.
W
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.
LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,
POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).
DRAWINGS. SEE SCHEDULE FOR TYPE (*).
CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON
EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED
OTHERWISE. CONNECT UNSWITCHED.
LIGHTING
LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.
TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.
AMPACITY. SEE FEEDER SCHEDULE.
ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER
WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.
WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.
DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND OVERCURRENT BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC.
WIRING SYSTEM TURNED UP.
WIRING SYSTEM TURNED DOWN.
WIRING SYSTEM EXPOSED.
PROTECTION DEVICE NUMBER.
CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT
LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.
JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.
CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)
CONNECTION TO HEADWALL UNIT. ONE NORMAL POWER CIRCUIT. ONE CRITICAL POWER CIRCUIT, CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
AND ONE DEDICATED CRITICAL POWER CIRCUIT FOR VENTILATOR.
CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
PANELBOARD SURFACE MOUNTED.
REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.
GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.
N = NORMAL BRANCH
U = UNGROUNDED (ISOLATION) PANEL
Q = EQUIPMENT BRANCH
C = CRITICAL BRANCH
L = LIFE SAFETY BRANCH
M = MOTOR CONTROL CENTER
L = 120/208 VOLT
H = 277/480 VOLT
PANELBOARD FLUSH MOUNTED.
1,2,3 = FLOOR
A,B,C = LOCATION
PANELBOARD NAMING CONVENTION
JUNCTION OR PULL BOX. W = WEATHERPROOF.
CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.
HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.
POWER
SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 48" AFF OR 8" ABOVE COUNTER
TV = TELEVISION, SEE DETAIL.
G = GROUND FAULT CIRCUIT INTERRUPTER.
EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER
P = PEDESTAL
WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.
DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.
DUPLEX RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED.
SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF OUTLET
OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES
OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY
DUPLEX RECEPTACLE, MOUNTED 48" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH
DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED.
SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.
MODIFIERS FOR RECEPTACLES:
SPECIAL RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED. NEMA CONFIGURATION AS INDICATED.
LH2A-1
CH2A
POWER POLE. DEVICE CONFIGURATION AND COLOR AS INDICATED.
TR = TAMPER RESISTANT
3 = THREE WAY
MODIFIERS FOR SWITCHES:
SINGLE POLE SWITCH, MOUNTED 48" AFF TO CENTER OF DEVICE.
THREE SINGLE POLE SWITCHES IN A 3-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE.
PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.
SWITCHES
TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE.
PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.
4 = FOUR WAY
D = DIMMER
DT = DOUBLE THROW
LV = LOW VOLTAGE
TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE, TO COMPLY WITH ENERGY CODE. EITHER SWITCH INBOARD AND OUTBOARD LAMPS SEPARATELY OR STEP-DIM BOTH
PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.
OS = OCCUPANCY SENSOR
TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.
a,b,c = MULTIPLE SWITCH LEGS
T = TIMER
INDICATED.
INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT
LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).
SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.
LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
SEE SCHEDULE FOR TYPE (*).
SEE SCHEDULE FOR TYPE (*).
REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.
HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.
LAMPS TO 50%.
NOTED OTHERWISE.
SUPPLIER/INSTALLER.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).
HEADWALL. SEE PLAN FOR NUMBER.HW#
POWER COLUMN. SEE PLAN FOR NUMBER.PC#
OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.
POWER SYSTEM.
CONNECTED TO THE EMERGENCY POWER SYSTEM.
LED STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY
GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.
ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.
WALL MOUNTED LOCAL ALARM BUZZER, 85dBA.
PUSH BUTTON DOOR RELEASE WITH SOUNDER COVER.
MAGNETIC LOCK FOR DOOR.
REMOTE LINE ISOLATION MONITOR.
CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.
PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.
VARIABLE SPEED DRIVEVSD
EXPEDITOR SYSTEM
EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.
PNEUMATIC TUBE STATIONPTS
BUTTON RELEASE.
BADGE ACCESS.
NURSE LOCATOR.
EMERGENCY MANUAL OVERRIDE.
DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.
SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.
POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).
SYMBOL LOCATION LEADER
4/350
ERS
LIM
RA
GA
J
E
C
M
H
F
P
P P
J
PP
ES
CR
ES
AL
PB
HH
BR
BA
NL
EMO
C
TC
PE
SS
SSS
SS
S
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACHOS
SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
DEMOLITION NOTES
A. COORDINATE ALL DEMOLITION WORK WITH OWNER PRIOR TO BEGINNING WORK.
B. REMOVE ALL ELECTRICAL DEVICES, WIRING AND RACEWAYS IN WALLS AND
CEILINGS BEING DEMOLISHED UNLESS NOTED OTHERWISE. RECONNECT DEVICES
AND FIXTURES DOWNSTREAM OF REMOVED WORK. UNLESS OTHERWISE NOTED,
WIRING AND RACEWAYS ARE TO BE REMOVED BACK TO THEIR SOURCE.
C. RELOCATE EXISTING WORK TO REMAIN WHICH INTERFERES WITH RENOVATION.
ELECTRICAL DEMOLITION WORK SHALL BE PHASED IN ACCORDANCE WITH
PROJECT "GENERALCONDITIONS". ELECTRICAL CONTRACTOR SHALL DEVELOP A
PHASING SCHEME WHICH WILL WORK WITH THE ARCHITECT'S OVERALL PHASING
PLAN AND WITH WORK TO BE DONE BY OTHER TRADES.
D. CONTRACTOR SHALL PROVIDE TEMPORARY POWER WHERE NECESSARY AT NO
EXTRA COST TO THE COR IN ORDER TO KEEP THE BUILDING IN OPERATION
DURING EACH PHASE OF THE RENOVATION.
E. REMOVE EXISTING ELECTRICAL WORK AS INDICATED. TRANSFER OF FEEDERS AND
BRANCH CIRCUITS TO NEW PANELS SHALL BE DONE IN A MANNER THAT WILL KEEP
DOWNTIME TO AN ABSOLUTE MINIMUM.
F. ALL OUTAGES SHALL BE COORDINATED WITH THE COR AT LEAST 72 HOURS IN
ADVANCE. OUTAGES WHICH ARE ANTICIPATED TO LAST LONGER THAN 1 HOUR
SHALL BE COORDINATED WITH OWNER AT LEAST 1 WEEK IN ADVANCE.
G. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL WORK ASSOCIATED
WITH WORK INDICATED TO BE REMOVED ON THE ARCHITECTURAL, PLUMBING,
MECHANICAL AND FIRE PROTECTION DRAWINGS.
H. ELECTRICAL WORK SHOWN IS BASED ON FIELD OBSERVATIONS AND EXISTING
DRAWINGS AND IS PROVIDED TO CONVEY THE GENERAL SCOPE OF DEMOLITION
WORK TO BE ACCOMPLISHED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE
SITE AND OBSERVE EXISTING CONDITIONS PRIOR TO BIDDING.
RL = EXISTING DEVICE TO BE RELOCATED.
MODIFIERS FOR EXISTING DEVICES
RLD = RELOCATED DEVICE SHOWN IN FINAL LOCATION.
RM = EXISTING DEVICE TO REMAIN.
EXRV
RV = EXISTING DEVICE TO BE REMOVED.
RP = EXISTING DEVICE TO BE REPLACED WITH NEW DEVICE.
EX = EXISTING DEVICE
GENERAL PROJECT NOTES
1. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
2. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE COR
AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME LENGTH MAY
BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE
OWNER'S DISCRETION.
3. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
4. ALL FIXED ELECTRICAL EQUIPMENT FURNISHED BY ELECTRICAL CONTRACTOR
SHALL BE LISTED AND LABELED BY AN APPROVED TESTING AGENCY.
FACTORY ASSEMBLED LISTED COMPONENTS SHALL BE LISTED AND LABELED
AS AN ASSEMBLY. ANY ELECTRICAL EQUIPMENT NOT LISTED OR LABELED
MUST BE APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION AND
HAVE A THIRD PARTY TESTING LABEL.
5. FIRE ALARM APPLIANCES AND DEVICES SHOWN INDICATE TO PROVIDE
COVERAGE IN THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE
APPLIANCES AND DEVICES AS REQUIRED BY THE LATEST EDITION OF NFPA 72
AND THE BUILDING CODE. NO CHANGE ORDERS WILL BE ALLOWED FOR
APPLIANCES AND DEVICES REQUIRED BY NFPA 72 AND THE BUILDING CODE.
6. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL
OFFICER TO VERIFY THAT APPROPRIATE SAFEGUARDS ARE BEING TAKEN TO
PROTECT WORKERS INVOLVED IN DEMOLITION ACTIVITIES.
7. CONTRACTOR SHALL COORDINATE WITH FACILITY'S INFECTION CONTROL
OFFICER TO VERIFY THAT APPROPRIATE PRECAUTIONS ARE BEING TAKEN TO
PROTECT FACILITY STAFF AND PATIENTS DURING THE CONSTRUCTION
ACTIVITIES.
8. ASBESTOS CONTAINING MATERIALS (IF PRESENT) WILL BE IDENTIFIED BY THE
OWNER AND WILL BE REMOVED FROM AHU'S, PIPING INSULATION, DUCT
INSULATION, ETC. (IF REQUIRED) PRIOR TO CONTRACTOR BEGINNING ANY
WORK ON THE SITE. COORDINATE WITH OWNER.
9. COMPLETE EXISTING ELECTRICAL WORK AS INDICATED ON THE PLANS.
CONNECTIONS OF FEEDERS AND BRANCH CIRCUITS TO NEW PANELS SHALL
BE DONE TO KEEP DOWNTIME TO AN ABSOLUTE MINIMUM.
10. ALL TERMINATIONS, CONDUCTORS, AND DEVICES SHALL BE 75 DEGREE
RATED.
11. ELECTRICAL CONTRACTOR IS NOT PERMITTED TO ROUTE WIRING CONNECTED
TO THE LIFE SAFETY OR CRITICAL BRANCH SOURCES OF POWER IN FLEXIBLE
METAL RACEWAYS OR METAL SHEATHED CABLE ASSEMBLIES, WITH THE
EXCEPTIONS OF THE EXEMPTIONS LISTED IN NEC 517.31.C.1.
12. ELECTRICAL CONTRACTORS SHALL PROVIDE SEPARATE RACEWAY, JUNCTION
BOXES OR CABINETS THAT ROUTE LIFE SAFETY AND/OR CRITICAL BRANCH
CIRCUITS WIRING FROM ALL WIRING AND EQUIPMENT CONNECTED TO OTHER
BRANCHES OF POWER.
13. UNLESS NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL INSTALL ALL
RACEWAY, BOXES, AND CABLES. ALL MEDICAL EQUIPMENT CABLES, UNLESS
OTHERWISE NOTED, SHALL BE PROVIDED BY MEDICAL EQUIPMENT VENDOR.
14. ALL ELECTRICAL WORK MUST BE COMPLETED IN PHASES, AS ESTABLISHED IN
"GENERAL CONDITIONS".
15. PER NEC REQUIREMENTS, EQUIPMENT GROUNDING TERMINAL BUSES OF THE
NORMAL AND ESSENTIAL BRANCH-CIRCUIT PANELBOARDS SERVING THE SAME
INDIVIDUAL PATIENT CARE VICINITY SHALL BE CONNECTED TOGETHER WITH
AN INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10
AWG.
16. A MAXIMUM OF THREE 20A, 1 POLE BRANCH CIRCUITS MAY BE COMBINED IN A
COMMON HOMERUN SHARING A COMMON NEUTRAL OR WITH SEPARATE
NEUTRALS, FOR A TOTAL OF SIX CURRENT CARRYING CONDUCTORS. ALL
BRANCH CIRCUITS LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO
PANEL.
17. CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN 600 VOLTS.
MINIMUM SIZE SHALL BE NO. 12 AWG UNLESS OTHERWISE NOTED ON THE
DRAWINGS. ALL WIRE #8 AWG AND LARGER SHALL BE STRANDED. #10 THRU #
12 AWG CONDUCTORS SHALL BE SOLID. ALL INSULATION TYPES SHALL BE
THWN OR THHN.
18. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE BREAKERS FOR ALL
SHARED NEUTRALS OR PROVIDE SEPARATE NEUTRALS FOR EACH BRANCH
CIRCUIT. ADJUST PANEL SCHEDULES ACCORDINGLY TO MEET NEC 210.4.
19. ALL WORK ASSOCIATED WITH VOICE, DATA, CCTV, CATV, NURSE CALL, WI-FI,
PUBLIC ADDRESS, SECURITY ACCESS, TO BE PROVIDED BY THE OWNER. THE
CONTRACTOR TO PROVIDE BACK BOXES, CONDUIT STUB-UP AND PULL WIRE.
20. BRANCH CIRCUIT WIRE SIZING WILL BE IN ACCORD WITH THE FOLLOWING
TABLES:
VOLTS DISTANCE HOMERUN REMAINDER OF CIRCUIT
120/208 0' - 50' #12 #12
50' - 100' #10 #12 100' - 150' #8 #10
VOLTS DISTANCE HOMERUN REMAINDER OF CIRCUIT
277/480 0' - 125' #12 #12
125' - 220' #10 #12 220' - 330' #8 #10
21. A SHORT-CIRCUIT/ARC FLASH AND SELECTIVE COORDINATION STUDY SHALL
BE PREPARED FOR THE ELECTRICAL OVERCURRENT DEVICES TO BE
INSTALLED UNDER THIS PROJECT. FINAL FIELD SETTINGS AND MODIFICATIONS
OF THE OVERCURRENT PROTECTIVE DEVICES SHALL BE MADE TO CONFIRM
WITH THE STUDY, WITHOUT ADDITIONAL COST TO THE OWNER.
22. ALL BREAKERS 600 AMP AND ABOVE ARE TO BE SOLID-STATE TYPE. SELECT
ELECTRONIC TRIP FUNCTIONS FOR LOW-VOLTAGE CIRCUIT BREAKERS SO AS
TO ACHIEVE SELECTIVE COORDINATION.
23. LIGHTING LAYOUTS ARE BASED ON IES STANDARD RECOMMENDED LIGHTING
LEVELS. LIGHT LEVELS ARE AFFECTED BY ENVIRONMENTAL CONDITIONS SUCH
AS FINISH COLOR, WINDOW TREATMENTS, AND FINAL LUMINAIRE SELECTIONS.
FINAL INFORMATION IS NOT ALWAYS ESTABLISHED AT THE TIME OF
CALCULATION. DESIGN BASIS LIGHT LEVEL CALCULATIONS FOR SPECIFIC
AREAS CAN BE PROVIDED UPON REQUEST.
S
RM
PATIENT TRACKER.PT
SECURITY DEVICES
360° DOME CAMERA
SECURITY CAMERA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
.9
V A
F a y e tt e v ill e H a lls
W a lls
/2 .9
M E
P v
.r v t
/1
/2
:0
:1
P
M
E001
ELECTRICAL - ELECTRICAL NOTES &
DRAWING INDEX
CHARLOTTE ENGINEERS, LLP
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704-531-3000
MICHAEL EAVES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
HALLS & WALLS
FAYETTEVILLE, NC
565-21-101
BLDG 1
07/14/20…