DRAWINGS
21 MB Posted
- Attached to
- Alice Coachman Elem. HVAC and Plumbing Upgrades
- Solicitation number
- 22-FAC-012
- Issued by
- Douglas County, Georgia
About this file
This is a drawings file for the State of Georgia Department of Education containing detailed mechanical, plumbing, and architectural plans for the HVAC and plumbing upgrades at Alice Coachman Elementary School located at 1425 W Oakridge Drive, Albany, Georgia 31707. The project involves comprehensive replacement and upgrades of heating, ventilation, air conditioning systems, and plumbing fixtures throughout the school facility. The scope includes demolition of existing equipment, installation of new wall-hung heat pumps (37 units), rooftop units (2 units), packaged terminal heat pumps (4 units), ductless heat pumps (4 units), fan coil units (4 units), outside air handling units (2 units), exhaust fans (38 units), and associated ductwork, piping, and controls. The project is organized into six construction phases to maintain school operations with temporary classroom relocations. Work will require coordination with existing building systems, including provisions for protecting occupied areas, maintaining exit access, and restroom availability during construction.
The drawings package includes comprehensive mechanical specifications with equipment schedules detailing model numbers, cooling and heating capacities in MBH, CFM ratings, motor specifications, and installation requirements. All HVAC equipment utilizes R-410a refrigerant with variable speed technology. The project incorporates VRF (Variable Refrigerant Flow) systems, hot gas reheat capabilities, and needlepoint bipolar ionization units for air quality enhancement. Ducting specifications include detailed insulation requirements, fire damper installations, and condensate drain provisions. The mechanical contractor is responsible for recovering all R-22 refrigerant from existing systems during demolition. Installation details address equipment supports, vibration isolation, condensate management, and integration with existing building infrastructure. All new duct penetrations require lintels to maintain fire ratings, and the project necessitates careful coordination around limited mezzanine access, existing structural members, and the school's occupied spaces during phased construction.
Text of this file
D A
D E
BLECKLEY LAURENS
CHATHAM
EFFINGHAM
IRWIN
BERRIEN
LOWNDESGRADY
SE
M
IN
OL
E
DECATUR
EARLY
MILLER
BAKER
THOMAS
BROOKS
COLQUITT
MITCHELL
COOK
TIFT
SCHLEY
TERRELL
DOUGHERTY
WEBSTER
RANDOLPH
QUITMAN
CLAY
CALHOUN
CHATTAHOOCHEE
STEWART
MARION
WILCOX
CRISP
WORTH
LEE
TURNER
DOOLY
MACON
SUMTER
HOUSTON
PULASKI
McINTOSH
PIERCE
CHARLTON
LA
NI
ER
CLINCH
ECHOLS
ATKINSON
WARE
CAMDEN
BRANTLEY
GLYNN
TOOMBS
APPLING
COFFEE
BEN HILL
TELFAIR
DAVIS
JEFF
WHEELER
DODGE
TREUTLEN
M
ON
TG
OM
ER
Y
LONG
WAYNE
LIBERTY
BULLOCH
EVANS
CANDLER
TATTNALL
BRYAN
DAWSON FRANKLIN
CLARKE
OCONEE
PUTNAM
BALDWIN
TWIGGS
HENRY
FA
YE
TT
E
PIKE
UPSON
SPALDING
M
ER
IW
ET
HER
HARRIS
MUSCOGEE
TALBOT
COWETA
HEARD
TROUP
PEACH
CRAWFORD
TAYLOR
BIBB
MONROE
LAMAR
BUTTS
JASPER
JONES
CHEROKEE
FULTON
PAULDING
HARALSON
CARROLL
DOUGLAS
BARTOWFLOYD
POLK
COBB
NEWTON
DEKALB
CL
AY
TO
N
ROCKD
AL
E
WALTON
MORGAN
GWINNETT
FORSYTH
JACKSON
HALL BANKS
BARROW
M cD
U F
F
IE
JEFFERSON
EMANUEL
WASHINGTON
WILKINSON
JOHNSON
HANCOCK
WARREN
GLASCOCK
JENKINS
SCREVEN
RICHMOND
BURKE
COLUMBIA
OGLETHORPE
WILKES
TALIAFERROGREENE
LINCOLN
ELBERT
HART
MADISON
RABUN
STEPHENS
FANNIN
PICKENS
GILMER
WHITF
IELD
GORDON
C H
AT
TO
O G
A
WALKER M
U
R R
A Y
CATOOSA
UNION
LUMPKIN
WHITE
HABERSHAM
TOWNS
BACON
DOUGHERTY
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION
T100
TITLE SHEET
2021191
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
ALICE COACHMAN ELEMENTARY SCHOOL -
HVAC & PLUMBING UPGRADES
1425 W OAKRIDGE DR, ALBANY, GA 31707
T100 TITLE SHEET
C101 SITE PLAN
A100 CONSTRUCTION PHASING PLAN
A200 ARCHITECTURAL CEILING PLAN
A300 ARCHITECTURAL CHASE PLAN & DETAILS
MD100 MECHANICAL DEMO PLAN - OVERALL
MD101 MECHANICAL DEMO PLAN - SECTOR A
MD102 MECHANICAL DEMO PLAN - SECTOR B
MD103 MECHANICAL DEMO PLAN - SECTORS C, D & E
M100 MECHANICAL NEW WORK PLAN - OVERALL
M101 MECHANICAL NEW WORK PLAN - SECTOR A
M102 MECHANICAL NEW WORK PLAN - SECTOR B
M103 MECHANICAL NEW WORK PLAN - SECTORS C, D & E
M301 MECHANICAL DIAGRAMS
M302 MECHANICAL DIAGRAMS
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL SCHEDULES
M603 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES
P101 PLUMBING FLOOR PLAN - SECTOR A
P102 PLUMBING FLOOR PLAN - SECTOR B
P103 PLUMBING FLOOR PLAN - SECTORS C, D, & E
E001 ELECTRICAL OVERALL PLAN
ED101 ELECTRICAL DEMO PLAN - SECTOR A
ED102 ELECTRICAL DEMO PLAN - SECTOR B
ED103 ELECTRICAL DEMO PLAN - SECTORS C, D, & E
E101 ELECTRICAL NEW WORK PLAN - SECTOR A
E102 ELECTRICAL NEW WORK PLAN - SECTOR B
E103 ELECTRICAL NEW WORK PLAN - SECTORS C, D, & E
E801 ELECTRICAL SCHEDULES AND LEGEND
No. Description Date
GA DOE ID#: 0299
EXISTING
PLAYGROUND
EXISTING
FENCED
PLAYGROUND
EXISTING STORM DRAIN
EXISTING
FENCED
MECHANCIAL YARD
PAVED DRIVE
PAVED DRIVE
TEMPORARY PORTABLE
CLASSROOM
TEMPORARY PORTABLE
CLASSROOM
TEMPORARY PORTABLE
CLASSROOM
SIDEWALK SIDEWALK
SID
EW
ALK
SIDEW
ALK
EXISTING STORM DRAIN
1 1/2" DCW 2" DCW
/2
D C
W
/2
D C
W
2" DCW
2" D C W
D C
W
2" D C W
D C
W
CONTRACTOR SHALL COORDINATE WITH
OWNER FOR TEMPORARY CONNECTION OF 2"
DOMESTIC COLD WATER PIPING TO EXISTING IN
THIS APPROXIMATE LOCATION BELOW GRADE.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
C101
SITE PLAN
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1/16" = 1'-0"
1 SITE PLAN
GENERAL NOTE: LOCATIONS OF CLASSROOM TRAILERS IS APPROXIMATE.
CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF EXISTING STORM
DRAINS, FENCING, SIDEWALKS, PLAYGROUNDS, DRIVES, ETC. AND
CAREFULLY COORDINATE PLACEMENT OF CLASSROOMS TO AVOID
CONFLICT AND MAINTAIN REQUIRED CLEARANCES.
1 1
2 2
PHASE 1 PHASE 2 PHASE 3 PHASE 4
PHASE 5 PHASE 6
PHASE 1
PHASE 2
PHASE 3
PHASE 4
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
A100
CONSTRUCTION PHASING
PLAN
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1/16" = 1'-0"
1 CONSTRUCTION PHASING PLAN
NOTES: (THIS SHEET ONLY)
1 . ADJUST TEMPORARY WALLS AS REQUIRED TO MAINTAIN SEPARATION FROM
WORK AREAS AND OCCUPIED STUDENT AREAS. ACCESS TO EXIT DOORS
SHALL BE MAINTAINED AT ALL TIMES.
2 . ADJUST TEMPORARY WALLS AS REQUIRED TO ALLOW ACCESS TO
RESTROOMS WHILE MAINTAINING SEPARATION OF WORK AREAS FROM
OCCUPIED STUDENT AREAS. (TYPICAL)
3 . PROVIDE TEMPORARY WALL (MIN 6' TALL) TO SEPARATE WORK AREAS FROM
OCCUPIED AREAS BASED ON PHASING. PROVIDE DOORS AS REQUIRED FOR
ACCESS TO WORK AREA. PROVIDE PROTECTION FOR EXISTING FLOORING,
WALLS, ETC. TO PREVENT DAMAGE TO EXISTING ITEMS DURING
INSTALLATION / REMOVAL OF TEMPORARY WALL.
GENERAL NOTE: PRIOR TO CONSTRUCTION, CONTRACTOR SHALL COORDINATE WITH OWNER
TO REMOVE ALL PERSONAL ITEMS FROM SPACES AFFECTED BY DEMOLITION. CONTRACTOR
SHALL PROTECT EXISTING CASEWORK, FURNITURE, FLOORING, WALLS, CEILINGS, ETC. NOT
ABLE TO BE REMOVED. AT THE END OF CONSTRUCTION, CONTRACTOR SHALL REMOVE ALL
PROTECTIVE COVERS AND WIPE DOWN AND CLEAN ALL SURFACES AFFECTED BY DUST, DIRT,
CONSTRUCTION DEBRIS, ETC.
GENERAL NOTE: THERE WILL BE 3 MODULAR CLASSROOM BUILDINGS WITH (2) CLASSROOMS
PER MODULAR UNIT ON THIS SITE PROVIDED BY THE CONTRACTOR. NO MORE THAN 6
CLASSROOMS MAY BE MOVED TO MODULAR UNITS FOR EACH PHASE. PHASES SHOWN
HEREIN ARE SUGGESTED PHASES AND MAY BE CHANGED DUE TO CONSTRUCTION
TIMELINES, CONSTRUCTION SCHEDULES, EQUIPMENT LEAD TIMES, UNFORESEEN
CIRCUMSTANCES ENCOUNTERED DURING THE CONSTRUCTION PROCESS OR FURTHER
COORDINATION WITH OWNER. VERIFY ALL PHASING, TEMPORARY WALL/PARTITION
INSTALLATION AND/OR SCHEDULING PRIOR TO COMMENCEMENT OF WORK.
1 1 1
2 2
2 2
3 3
DEMO EXISTING CEILING TILE & GRID AS
REQUIRED AND REPLACE WITH NEW
CEILING TILE & GRID
DEMO EXISTING CEILING TILE &
REPLACE WITH NEW CEILING TILE
CEILING HATCH LEGEND
(NO HATCH) EXISTING CEILING TILE
& GRID TO REMAIN
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
A200
ARCHITECTURAL CEILING
PLAN - OVERALL
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1/16" = 1'-0"
1 ARCHITECURAL CEILING PLAN - OVERALL
1 . REMOVE EXISTING CEILING TILE & GRID AS REQUIRED FOR REMOVAL OF
EXISTING LINSETS AND DUCT. SEE MECHANICAL DRAWINGS FOR EXACT
LOCATIONS OF REMOVED & NEW LINESETS, DUCT, ETC. REPLACE EXISTING
CEILING TILE AND GRID REMOVED DURING DEMOLITION.
2 . PROVIDE NEW BORDER AROUND NEW CHASE AND INTEGRATE WITH
EXISTING CEILING GRID.
3 . REMOVE GRID AS REQUIRED FOR INSTALLATION OF NEW LINESETS,
DUCTWORK, CONDENSATE DRAINS, ETC. EXISTING GRID "MAINS" AND
BORDER TO REMAIN TO MAINTAIN EXISTING LIGHTING, SPEAKER, ETC.
LAYOUT. SEE MECHANICAL DRAWINGS FOR ALL NEW ABOVE CEILING ITEMS.
(TYPICAL FOR ADMIN & MEDIA SPACES)
NOTES: (THIS SHEET ONLY)
GENERAL NOTE: REMOVAL OF CEILINGS REQUIRED FOR REMOVAL OF
EXISTING EXHAUST FANS LOCATED ABOVE RESTROOMS NOT SHOWN. SEE
MECHANICAL DRAWINGS FOR LOCATIONS OF ITEMS LOCATED ABOVE
CEILINGS THAT MAY REQUIRE REMOVAL OF CEILING TILES.
1 1
1 1
2 2
A300
1 LAYER ABUSE RESISTANT 5/8" GYPSUM BOARD (ONE SIDE).
ACOUSTICAL TILE T-BAR CEILING
EXTEND WALL 0'-6" (MAXIMUM) PAST CEILING - OR AS DICTATED BY
EXITING STRUCTURAL CONDITIONS, SUPPLY DUCT, ETC.
3" BATTS INSULATION BETWEEN STUD FOR SOUND ATTENUATION.
CONTINUOUS SEALANT AT CEILING INTERFACE OF 5/8" GYP.
MTL. RUNNER - DO NOT FASTEN TO STUD.
HEAD
PLAN
BASE
OVERALL DIMENSION = 4-1/4"
'C' SHAPED MTL. STUD. DO NOT FASTEN TO RUNNER ABOVE.
FASTENERS @ 2'-0" O.C. MAX WITHIN 1" OF ENDS.
TOP OF STRUCTURAL SLAB.
CONTINUOUS SEALANT.
CONTINUOUS C'SHAPED METAL RUNNER.
BASEBOARD.
CLASSROOMCHASE
METAL STUD SIZE - 3-5/8"
WHHP
PROVIDE STEEL CORNER BEAD AT 90
DEG GYP. BOARD OUTSIDE CORNERS.
PROVIDE FRAMED OPENING FOR
SUPPLY DUCT AND RETURN GRILLE
AND DUCT. SEE MECHANICAL
DRAWINGS FOR EXACT SIZE.
SEE MECHANICAL DRAWINGS FOR
SUPPLY & RETURN DUCT SIZES.
EXTERIOR WALL
24" MAXIMUM
48" MAXIMUM
EXTERIOR
FLOOR
MODIFY EXISTING UPPER CABINET AS
SHOWN TO ACCOMODATE NEW CHASE.
REMOVE EXISTING LOWER CABINET AS
SHOWN TO ACCOMODATE NEW CHASE.
CEILING
EXTERIOR
FLOOR
NEW METAL STUD & GYP BOARD CHASE.
SEE CHASE WALL DETAIL THIS SHEET.
CEILING
DEMO PLAN NEW WORK PLAN
MODIFY/SHORTEN
EXISTING LAMINATE
COUNTERTOP AND
BACKSPLASH TO
TERMINATE FLUSH WITH
NEW CHASE WALL.
PROVIDE COVE MOLDING AT INTERFACE
OF EXISTING TO REMAIN BASE AND UPPER
CABINETS, PAINTED TO MATCH EXISTING.
MODIFY/SHORTEN
EXISTING 2 X 4 BASE AND
RUBBER ALONG TOE KICK
TO TERMINATE FLUSH
WITH NEW CHASE WALL.
TERMINATE COUNTERTOP AT NEW METAL STUD &
GYP BOARD CHASE WALL. SEE CHASE WALL
DETAIL THIS SHEET. FACE OF CHASE FLUSH WITH
EXISTING BASE CABINETS.
PROVIDE NEW LAMINATE PLASTIC
BACKSPLASH ON PRESSURE TREATED 3/4"
X 4" SOFTWOOD ALONG NEW CHASE WALL
TO MATCH EXISTNG BACKSPLASH. CAULK
WATERTIGHT AT COUNTER INTERFACE
AND CHASE WALL INTERFACE.
NEW OUTSIDE AIR DUCT
RISES IN CHASE. SEE
MECHANICAL FOR DETAILS.
3' - 3"
CHASE WALL FINAL/INSTALLED
DIMENSION IS DICTATED BY WIDTH OF
REMOVED BASE AND UPPER WALL
CABINETS. CONTRACTOR FIELD VERIFY
DIMENSIONS OF CABINETS.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
A300
ARCHITECTURAL CHASE
PLAN & DETAILS
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1/16" = 1'-0"
1 ARCHITECURAL CHASE PLAN
NOTES: (THIS SHEET ONLY)
1 . CONSTRUCT CHASE WALL FOR WALL HUNG UNIT DUCTWORK ACCORDING TO
CHASE WALL DETAIL, THIS SHEET.
2 . CONSTRUCT CHASE WALL FOR 100% OUTSIDE AIR UNIT DUCTWORK SIMILAR
TO CHASE WALL DETAIL, THIS SHEET. SEE MECHANICAL DRAWINGS FOR
OUTSIDE AIR DUCT DIMENSIONS. COORDINATE CHASE DIMENSIONS WITH
OUTSIDE AIR DUCT.
NOT TO SCALE
CHASE WALL DETAIL
NOT TO SCALE
WHHP CHASE WALL DETAIL
NOT TO SCALE
2 WORK ROOM CABINET ELEVATION NOT TO SCALE
3 WORK ROOM CABINET FLOOR PLAN
MD101
MD102
MD103
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD100
MECHANICAL DEMO PLAN -
OVERALL
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1/16" = 1'-0"1 MECHANICAL DEMO PLAN - OVERALL
44 4 4
MD101
MD101
MD101
11 12
9 9
CORRIDOR
A114
OFFICE
A104
WORK ROOM
A119
COUNSELOR
A118
TEST
A122
A123
BOOK KEEPING
A124
PRINCIPAL
A108
RR
A107
RR
A106
RR
A105
RR
A115
ELEC
A110
CLINIC
A116
ART
A111
STOR.
A113
MEDIA
A127
LOBBY
CONF.
A136
A.V. STOR.
A135
MEDIA PRODUCTION
A134
MDF
A133
COMPUTER LAB
A131
MUSIC
A132
21 21
19 19
19 19
7 7
7 7
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD101
MECHANICAL DEMO PLAN -
SECTOR A
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . REMOVE EXISTING INLINE EXHAUST FAN MOUNTED ABOVE
CEILING.
2 . REMOVE EXISTING FAN COIL UNIT AND ASSOCIATED DUCTWORK
UP TO LOCATION SHOWN. REMOVE EXISTING GPS BIPOLAR
IONIZATION UNIT AND STORE FOR REUSE IN NEW FAN COIL UNIT
SAME LOCATION.
3 . REMOVE EXISTING VVT BOX, SUPPORTS, ASSOCIATED
DUCTWORK, INSULATION, ETC. (TYPICAL)
4 . REMOVE EXISTING HEAT PUMP, ASSOCIATED PIPING, ETC.
5 . EXISTING DUCT PENETRATES FLOOR SLAB AT THIS APPROXIMATE
LOCATION. LEAVE EXISTING DUCTWORK TO APPROX. 8" ABOVE
SLAB. SEE NEW WORK PLAN FOR CONNECTION OF NEW DUCT.
6 . EXISTING DUCTWORK AND FIRE DAMPER TO REMAIN. CAP
DUCTWORK ON BOTH SIDES OF WALL AND SEAL AIR TIGHT.
PROVIDE ACCESS PANEL TO ALLOW ACCESS TO FIRE DAMPER.
7 . DUCTWORK CONTINUES ABOVE CEILING. SEE MECHANICAL DEMO
PLAN - SECTOR A
8 . EXISTING DIFFUSER MOUNTE BELOW MEZZANINE TO REMAIN. SEE
MECHNICAL DEMO MEZZANINE PLAN - ADMIN AREA FOR MORE
INFORMATION.
9 . EXISTING DUCTWORK TO REMAIN. CLEAN DUCTWORK IN
ACCORDANCE WITH DUCT CLEANING SPEC.
10 . REMOVE EXISTING OUTSIDE AIR DUCT UP TO LOCATION SHOWN.
CAP AND SEAL DUCT AIR AND WATER TIGHT.
11 . REMOVE EXISTING DUCTWORK, SUPPORTS, ETC. ROUTED BELOW
MEZZANINE.
12 . SEE MECHANICAL DEMO MEZZANINE PLAN - MEDIA AREA FOR
ITEMS REMOVED IN MEZZANINE AREA ABOVE.
13 . SEE MECHANICAL DEMO MEZZANINE PLAN - ADMIN AREA FOR
ITEMS REMOVED IN MEZZANINE AREA ABOVE.
14 . SEE MECHANICAL DEMO MEZZANINE PLAN - ART AREA FOR ITEMS
REMOVED IN MEZZANINE AREA ABOVE.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A
1/4" = 1'-0"3 MECHANICAL DEMO MEZZANINE PLAN - ADMIN AREA
1/4" = 1'-0"4 MECHANICAL DEMO MEZZANINE PLAN - MEDIA AREA
1/4" = 1'-0"2 MECHANICAL DEMO MEZZANINE PLAN - ART AREA
NOTES: (THIS SHEET ONLY)
15 . REMOVE EXISTING EXHAUST FAN MOUNTED BELOW MEZZANINE.
DUCTWORK TO REMAIN. SEE NEW WORK PLAN FOR INSTALLATION
OF NEW EXHAUST FAN.
16 . EXISTING INLINE EXHAUST FAN IN ATTIC TO REMAIN.
17 . REMOVE EXISTING ELECTRIC DUCT HEATER AT THIS
APPROXIMATE LOCATION. PATCH DUCT WHERE HEATER WAS
REMOVED.
18 . EXISTING PIPING CONTINUES TO ASSOCIATED AIR HANDLING UNIT.
FIELD VERIFY EXACT ROUTING. REMOVE ALL EXISTING PIPING.
SEE NEW WORK PLAN FOR ROUTING OF NEW PIPING IN SAME
LOCATION.
19 . REMOVE EXISTING PIPING IN CHASE. SEE NEW WORK PLAN FOR
ROUTING OF NEW PIPING IN EXISTING CHASE.
20 . EXISTING 44" X 16" RETURN DUCT IN CHASE AND ASSOCIATED
SIDEWALL RETURN GRILLE TO REMAIN. SEE NEW WORK PLAN FOR
CONNECTION OF NEW RETURN DUCT.
21 . REMOVE EXISTING OUTSIDE AIR DUCT. SEAL OPENING AIR TIGHT.
22 . EXISTING RELIEF OPENING AND FIRE DAMPER TO REMAIN.
GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF
WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL
UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING
WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).
CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT
REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY
CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS
HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR
PROCESSING.
10 10
STAGE
B116
DRY STORAGE
B104
FREEZER
B103
COOLER
B102
KITCHEN
B111
OFFICE
B108
TOILET
B106
CAN WASH
B105LOCKERS
B107
JAN
B110
SERVING
B112
GYM
B120
MECH.
B124
ELEC.
B126
STORAGE
B123
OFFICE
B122
STORAGE
B121
CORR.
B101
BOYS RR
B117
GIRLS RR
B118
CUSTODIAL
B119
CAFETORIUM
B115
DISH WASH
B114
13 13
MM
20 13
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD102
MECHANICAL DEMO PLAN -
SECTOR B
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . COMPLETELY REMOVE EXISTING CEILING HEATER, DISCONNECT,
THERMOSTAT, ASSOCIATED WIRING, ETC. REPAIR ANY DAMAGED
CEILING GRID/TILE CAUSE BY DEMOLITION. PROVIDE NEW CEILING
TILE TO MATCH EXISTING TILE WHERE CEILING HEATER WAS
REMOVED.
2 . REMOVE EXISTING ROOF MOUNTED EXHAUST FAN. SEE NEW
WORK PLAN FOR INSTALLATION OF NEW EXHAUST FAN IN SAME
LOCATION.
3 . REMOVE EXISTING PAD MOUNTED PACKAGED HEAT PUMP,
ASSOCIATED DUCTWORK, AND DUCT COVER UP TO LOCATION
SHOWN. REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT AND
STORE FOR REINSTALLATION IN NEW PACKAGED HEAT PUMP
SAME LOCATION.
4 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SEE NEW
WORK PLAN FOR INSTALLATION OF NEW PTHP IN SAME LOCATION.
5 . REMOVE EXISTING INTAKE VENTILATOR ON ROOF. EXISTING ROOF
CURB TO REMAIN. CAP EXISTING CURB AND PROVIDE SUPPORTS
AS REQUIRED FOR INSTALLATION OF NEW DUCTLESS HEAT PUMP.
SEE NEW WORK PLAN FOR INSTALLATION OF NEW DUCTLESS
HEAT PUMP ON EXISTING CURB THIS LOCATION.
6 . REMOVE EXISTING FAN COIL UNIT MOUNTED ABOVE CEILING,
ASSOCIATED DUCTWORK, SUPPORTS, PIPING, GRILLES, ETC.
REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT AND STORE
FOR REUSE IN NEW DUCTLESS FAN COIL UNIT SAME LOCATION.
EXISTING CONDENSATE PIPE TO REMAIN FOR REUSE, SEE NEW
WORK PLAN.
7 . REMOVE EXISTING HEAT PUMP MOUNTED ATOP EQUIPMENT
SUPPORT PLATFORM ON ROOF, AND ASSOCIATED PIPING.
EXISTING EQUIPMENT SUPPORT TO BE REUSED. SEE NEW WORK
PLAN FOR INSTALLATION OF NEW DUCTLESS HEAT PUMP.
8 . REMOVE EXISTING AIR HANDLING UNIT AND ASSOCIDATED PIPING
COMPLETELY. REMOVE DUCTWORK UP TO LOCATION SHOWN. SEE
SHEET M102 FOR NEW AIR HANDLING UNIT.
9 . COMPLETELY REMOVE EXISTING HEAT PUMP, ASSOCIATED
PIPING, ETC. SEE NEW WORK PLAN FOR INSTALLATION OF NEW
HEAT PUMP SAME LOCATION.
10 . REMOVE EXISTING CEILING HEATER. SEE NEW WORK PLAN FOR
INSTALLATION OF NEW CEILING HEATER.
11 . EXISTING INLINE FAN MOUNTED IN ATTIC TO REMAIN.
12 . REMOVE EXISTING ROOF MOUNTED EXHAUST FAN. EXISTING
ROOF CURB TO REMAIN. CAP EXISTING CURB AND PROVIDE
SUPPORTS AS REQUIRED FOR INSTALLATION OF NEW DUCTLESS
HEAT PUMP. SEE NEW WORK PLAN FOR INSTALLATION OF NEW
DUCTLESS HEAT PUMP ATOP EXISTING CURB THIS LOCATION.
13 . EXISTING DUCTWORK TO REMAIN. CLEAN DUCTWORK IN
ACCORDANCE WITH DUCT CLEANING SPEC.
14 . EXISTING ROOF MOUNTED EXHAUST FAN, ASSOCIATED
DUCTWORK, SUPPORTS, ETC. SERVING DISHWASHER TO REMAIN.
15 . REMOVE EXISTING DOOR AIR CURTAIN. SEE NEW WORK PLAN FOR
INSTALLATION OF NEW DOOR AIR CURTAIN SAME LOCATION.
16 . REMOVE EXISTING KITCHEN UPBLAST EXHAUST FAN ON ROOF.
SEE NEW WORK PLAN FOR INSTALLATION OF NEW FAN SAME
LOCATION.
17 . REMOVE EXISTING KITCHEN MAKE-UP AIR UNIT. SEE NEW WORK
PLAN FOR INSTALLATION OF NEW KITCHEN MAKE-UP AIR UNIT
SAME LOCATION.
18 . EXISTING LOUVER, ACTUATOR, SCREEN, ASSOCIATED DUCTWORK
AND GRILLES TO REMAIN.
19 . EXISTING MOTOR ACTUATOR TO REMAIN. MAINTAIN EXISTING
START/STOP SIGNAL FOR EXISTING LOUVER ACTUATOR MOTOR.
20 . CAP EXISTING OUTSIDE AIR DUCT AND SEAL AIR AND WATER
TIGHT.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B
GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF
WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL
UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING
WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).
CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT
REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY
CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS
HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR
1 1
1 1
1 1
2 2 2
3 3 3 3
5 5 5
4TH GRADE CR
C102
4TH GRADE CR
C123
4TH GRADE CR
C122
5TH GRADE CR
C113
4TH GRADE CR
C104
4TH GRADE CR
C103
2ND GRADE CR
D102
2ND GRADE CR
D123
2ND GRADE CR
D122
2ND GRADE CR
D103
2ND GRADE CR
D104
EIP
D112
3RD GRADE CR
D111
3RD GRADE CR
D110
3RD GRADE CR
D109
3RD GRADE CR
D108
P.F.
D107
BOYS TOILET
D105
ELEC
D114
JAN
D106
VESTIBULE
D118
WORK ROOM
D119
BOOK STOR.
D120
IDF
D121
5TH GRADE CR
C109
5TH GRADE CR
C110
5TH GRADE CR
C111
5TH GRADE CR
C112
KINDERGARTEN CR
E102
KINDERGARTEN
CLASSROOM
E106
KINDERGARTEN
CLASSROOM
E131
KINDERGARTEN CR
E135
1ST GRADE CR
E121
1ST GRADE CR
E120
1ST GRADE CR
E111
MOID
E110
PID CR
E107
WORK ROOM
E128
JAN
E122
GIRLS TLT
E123
BOYS TLT
E124
VESTIBULE
E127
WOMEN
E125
MEN
E126
IDF
E130
ELEC
E129
BATHROOM
E108
KITCHEN/LAUND
E109
RECEPTION/WAITING
E116
BOOK STOR.
E117
GIRLS TLT
E118
BOYS TLT
E119
BOOK STOR.
E112
GIRLS TLT
E113
BOYS TLT
E114
RECEPTION/WAITING
E115
SPEECH CR
C108
RESOURCE CR
C107
JAN
C106
BOYS TOILET
C105
BOOK STOR.
C120
IDF
C121
WORK ROOM
C119
VESTIBULE
C118
WOMEN
C116
MEN
C117
ELEC
C114
MEN
D117
WOMEN
D116
BOYS TLT
E134
GIRLS TLT
E133
BOOK STOR.
E132
BOOK STOR.
E103
GIRLS TLT
E104
BOYS TLT
E105
CORRIDOR
E101
CORRIDOR
C101
GIRLS TOILET
C115
CORRIDOR
D101
GIRLS TOILET
D115
9 9
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD103
MECHANICAL DEMO PLAN -
SECTORS C, D & E
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . REMOVE EXISTING WALL HUNG HEAT PUMP. REMOVE EXISTING
GPS BIPOLAR IONIZATION UNIT AND STORE FOR INSTALLATION IN
NEW WALL HUNG HEAT PUMP SAME LOCATION. SEE NEW WORK
PLAN.
2 . REMOVE EXISTING INLINE EXHAUST FAN MOUNTED ABOVE
CEILING. FIELD VERIFY EXACT LOCATION. REMOVE PORTION OF
DUCTWORK AS REQUIRED FOR INSTALLATION OF NEW EXHAUST
FAN IN SAME LOCATION. REPAIR / REPLACE ANY CEILING TILE OR
GRID DAMAGED DURING DEMOLITION.
3 . REMOVE EXISTING CEILING HEATER. FIELD VERIFY EXACT
LOCATION. CAREFULLY REMOVE CEILING TILE / GRID AS
REQUIRED FOR REMOVAL AND INSTALLATION OF NEW CEILING
HEATER IN SAME LOCATION. REPAIR / REPLACE CEILING TILE /
GRID DAMAGED DURING DEMOLITION.
4 . COMPLETELY REMOVE EXISTING DEHUMIDFIER IN BOOK STORAGE
ROOM.
5 . EXISTING PROPELLER FAN MOUNTED IN ATTIC TO REMAIN.
6 . REMOVE EXISTING WALL HUNG HEAT PUMP. EXISTING DUCTWORK
TO REMAIN. REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT
AND STORE FOR REINSTALLATION IN NEW WALL HUNG HEAT PUMP
SAME LOCATION.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTORS C, D, & ENOTES: (THIS SHEET ONLY)
7 . REMOVE EXISTING WALL HUNG HEAT PUMP. EXISTING DUCTWORK
AND SIDEWALL GRILLES TO REMAIN. CLEAN GRILLES TO REMOVE
DIRT AND DEBRIS IN ACCORDANCE WITH DUCT CLEAN
SPECIFICATION. SALVAGE EXISTING GPS BIPOLAR IONIZATION
UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME
LOCATION.
8 . EXISTING EXHAUST DUCTWORK & GRILLES TO REMAIN. CLEAN
FACE OF GRILLES TO REMOVE DIRT, DUST, & DEBRIS.
9 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SEE NEW
WORK PLAN FOR INSTALLATION OF NEW PTHP IN SAME LOCATION.
GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF
WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL
UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING
WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).
CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT
REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY
CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS
HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR
M101
M102
M103
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
M100
MECHANICAL NEW WORK
PLAN - OVERALL
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1/16" = 1'-0"1 MECHANICAL NEW WORK PLAN - OVERALL
IU-1.1
IU-1.9 IU-1.11IU-1.8
IU-1.6
IU-1.5
IU-1.4
IU-1.3
IU-2.1
IU-2.2
IU-2.3
IU-2.6
IU-2.7
IU-2.8
HRU-1
HRU-2
EF-9
EF-8
EF-10
EF-7
CORRIDOR
A114
IU-1.2
A1
A1
A1
A1
A1
A1
IU-1.7
"ø
MUSIC
A132
COMPUTER LAB
A131
COUNSELOR
A118
TEST
A122
BOOK KEEPING
A124
OFFICE
A104
PRINCIPAL
A108
ASSIST. PRINCIPAL
A109
M101
M101
A2
A2
A2
A2
A2
A2
A3
A3
A3
A3
A3
"x
LOBBY
MDF
A133
OFFICE
A128
RR
A130
A.V. STOR.
A135
CONF.
A136
MEDIA
A127
2461.7 SF
M101
HP-2
HP-3HP-1 OAU-CU-1
R RR
R R
A2
A1
SS
EF-10
CC
CC
SS
RR
A107
RR
A106
RR
A105
RR
A115
ELEC
A110
ART
A111
KILN
A112
STOR.
A113
OAU-CU-2
R
TT
F.D.
TT
10"ø 12"ø 14"x14"
8"ø 8"ø 8"ø 8"ø 8"ø 8"ø
8"ø 8"ø 8"ø
14"x14"10"ø 12"ø
8"ø 8"ø 8"ø 8"ø8"ø
14"x14" 14"x14"
8"ø ø16"
16"ø
IU-2.2
IU-2.1
TT
IU-2.4
IU-2.5
12 8"ø
"x
"x
16"x14"29
D R
1 1/2" D
D
D D
/2
D
/2
D
TT
TT
TT
TT
TT TT
FCU-2
FCU-3
TT
TT TT
TT
TT
TT
TT
TT
A2
A2
A2
A2
A1
16"x12"
IU-1.6
TT
IU-1.1
8"ø
8"ø8"ø
"x ø8"
6"ø
6"ø
4"ø 10"ø
G1
G1
G1
A1
6"ø
6"ø 6"ø
12"ø
10"ø8"ø ø6"
6"ø ø6"
4"ø8"ø
8"ø
18"ø
8"ø
8"ø
6"ø
12"x12"
16"x12"
4"ø
4"ø 6"ø
A1
4"ø
6"ø
10"ø 10"ø
18"ø
265 130
4"ø4"ø
4"ø
4"ø
G1
A1
A1
6"ø
G1
B1 ø18"31
323232
R
R
1 1/2" D
D
D
D
1 1/2" D R
R
R
R
DR
R(TYP)
D D D
D
R
R
R D
R
TT
TT
38 38 38 38
39 39
40 40 40
40 40 40
265 265
265 265
270 265 265
245 245
215 215
42 42
TT
TT
47 47
D
D
DHP-1
R
R
R
DFCU-1D
R
R
R
RR
R
R
IU-1.12
MDC-1
IU-1.10
OAU-1
6"ø
"ø
D
1 1/2" D D
R
R
R
14"x16"
R(TYP)
410"ø
R R
R
RR
FCU-2
FCU-3
IU-2.5IU-2.4
OAU-2
F.D. F.D.
16 17
8"ø
12"ø 12"ø
"ø
8"ø 8"ø
8"ø
11"x20"
16"x14"14"x14"
"x
D
D
D
D
D
D
R
R
R R
MDC-2
F.D.
F.D.
14"x8" 7
GENERAL NOTES:
ALL EXISTING OPENINGS NOT REUSED,
AND ALL NEW OPENINGS SHALL BE
PATCHED TO MATCH EXISTING
WALL/CEILING/FLOOR CONSTRUCTION TO
MAINTAIN FIRE RATING.
ALL EXISTING AND NEW EQUIPMENT MUST
FIT THROUGH EXISTING 4' X 3' MEZZANINE
DOOR. SPACE IS EXTREMELY LIMITED.
FIELD COORDINATE WITH EXISTING
TRANSFORMER, CONDUIT, WIRING,
PANELS, ETC. IN ELECTRICAL ROOM.
51 51 51
FCU-1
14"x24"
GENERAL NOTES:
ALL EXISTING OPENINGS NOT REUSED,
AND ALL NEW OPENINGS SHALL BE
PATCHED TO MATCH EXISTING
WALL/CEILING/FLOOR CONSTRUCTION TO
MAINTAIN FIRE RATING.
ALL EXISTING AND NEW EQUIPMENT MUST
FIT THROUGH EXISTING 4' X 3' MEZZANINE
DOOR. SPACE IS EXTREMELY LIMITED.
R D
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
M101
MECHANICAL NEW WORK
PLAN - SECTOR A
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . OVERHEAD STRUCTURE AT APPROXIMATELE 6'-0" ABOVE
MEZZANINE FLOOR INDICATED BY DASHED LINE. COORDINATE ALL
DUCT, PIPING, ETC. WITH OVERHEAD STRUCTURE (TYPICAL)
2 . VRF COMPACT CEILING CASSETTE SUSPENDED FROM DROP RODS
(MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH
SUPPLEMENTAL 2" X 2" X 1/4" ANGLE IRON.
3 . VRF DUCTED FAN COIL MOUNTED ABOVE CEILING, SUSPENDED
FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD
STRUCTURE. CONNECT SUPPLY DUCT TO EXISTING SUPPLY
DUCTWORK AS SHOWN. FIELD VERIFY EXACT LOCATION. PROVIDE
FITTINGS & TRANSITIONS AS REQUIRED TO MAKE CONNECTION.
4 . 10"Ø 100% OUTSIDE AIR SUPPLY DUCT ROUTED BETWEEN
EXISTING STRUCTURAL MEMBERS AS SHOWN.
5 . DUCT OF INDICATED SIZE ELBOWS DOWN FOR CONNECTION TO
PLENUM STAND BENEATH UNIT. SEE VERTICAL FCU DETAIL.
6 . NEW EXHAUST FAN LOCATED IN SAME LOCATION AS FAN
REMOVED DURING DEMOLITION. PROVIDE TRANSITIONS AS
REQUIRED TO INSTALL NEW FAN.
7 . 8" X 12" SUPPLY DUCT RISES AND TRANSITIONS TO 12"Ø IN RISE
AND ROUTED AS SHOWN. SPACE IS EXTREMELY LIMITED, HOLD
DUCTWORK AS TIGHT AS POSSIBLE TO ALLOW MEZZANINE DOOR
TO OPEN FULLY. COORDINATED DUCTWORK WITH EXISTING
CONDENSATE DRAIN AND NEW PIPING TO PREVENT CONFLICT.
8 . LINE SIZE CONDENSATE DRAIN RISES TO MEZZANINE ABOVE AND
ELBOWS DOWN AT EXISTING FLOOR DRAIN.
9 . SEE LARGE SCALE MEZZANINE PLAN - ADMIN AREA THIS SHEET
FOR EQUIPMENT LOCATED IN MEZZANINE.
10 . SEE LARGE SCALE MEZZANINE PLAN - ART AREA THIS SHEET FOR
EQUIPMENT LOCATED IN MEZZANINE.
11 . SEE LARGE SCALE MEZZANINE PLAN - MEDIA AREA THIS SHEET
FOR EQUIPMENT LOCATED IN MEZZANINE.
12 . NEW DUCTWORK TRANSITIONS AS REQUIRED TO CONNECT TO
EXISTING SUPPLY DUCTWORK AT THIS APPROXIMATE LOCATION.
FIELD VERIFY EXACT LOCATION OF EXISTING DUCTWORK AND
SHIFT UNIT/ OFFSET DUCTWORK AS REQUIRED TO MAKE
CONNECTION.
13 . 12" Ø OUTSIDE AIR DUCT TAPS IN TO EXISTING 22" X 42" OUTSIDE
AIR DUCT. BALANCE DAMPER FOR AMOUNT OF OUTSIDE AIR
SCHEDULED.
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR A
1/4" = 1'-0"3 MECHANICAL NEW WORK MEZZANINE PLAN - ADMIN AREA
1/4" = 1'-0"4 MECHANICAL NEW WORK MEZZANINE PLAN - MEDIA AREA1/4" = 1'-0"2 MECHANICAL NEW WORK MEZZANINE PLAN - ART AREA
14 . SPACE IN MEZZANINE IS EXTREMELY LIMITED. ROUTE RETURN
DUCT AS CLOSE TO WALL AS POSSIBLE TO ALLOW INSTALLATION
OF OAU-1 AND MAINTAIN PROPER CLEARANCES.
15 . 8"Ø OUTSIDE AIR DUCT TAPS INTO TOP OF RETURN PLENUM.
BALANCE FOR 150 CFM OF OUTSIDE AIR.
16 . OUTSIDE AIR DUCT ELBOWS UNDER EXISTING STRUCTURE AT
THIS APPROXIMATE LOCATION.
17 . 8"Ø OUTSIDE AIR DUCT TAPS OFF BOTTOM OF 12"Ø OUTSIDE AIR
DUCT AND IS ROUTED BELOW FCU-3 TO RETURN OF FCU-2.
BALANCE FOR 150 CFM OF OUTSIDE AIR.
18 . 8"Ø OUTSIDE AIR DUCT TAPS INTO EXISTING RETURN AIR PLENUM.
BALANCE FOR 150 CFM OF OUTSIDE AIR.
19 . APPROXIMATE LOCATION OF EXISTING 54" X 18" DUCT
PENETRATION. REUSE PORTION OF EXISTING OPENING WHERE
FEASIBLE AND PATCH REMAINING OPENING TO MATCH EXISTING
WALL COMPOSITION AND RATING.
20 . APPROXIMATE LOCATION OF EXISTING 24" X 46" DUCT
PENETRATION. REUSE PORTION OF EXISTING OPENING WHERE
FEASIBLE AND PATCH REMAINING OPENING TO MATCH EXISTING
WALL COMPOSITION AND RATING. PROVIDE FIRE DAMPER AT
DUCT PENETRATION OF RATED WALL.
21 . PROVIDE FIRE DAMPERS AT DUCT PENETRATIONS OF EXISTING
RATED WALL.
22 . NEW 16" X 16" SUPPLY DUCTWORK TAPS INTO CAPPED 24" X 40"
EXISTING SUPPLY DUCTWORK.
23 . CONNECTION SIZE SUPPLY DUCTWORK TAPS INTO CAPPED 24" X
40" CAPPED SUPPLY DUCTWORK. PROVIDE FITTINGS AND
OFFSETS AS REQUIRED TO MAKE CONNECTION.
24 . CONNECTION SIZE RETURN DUCT CONNECTS TO EXISTING 18" X
26" RETURN DUCT. PROVIDE FITTINGS AND OFFSETS AS
REQUIRED TO MAKE CONNECTION.
25 . TRAPPED, SLOPED (1/4" PER FOOT) CONDENSATE DRAIN ROUTED
FROM FCU TO EXISTING FLOOR DRAIN. DO NOT BLOCK ACCESS
PANELS.
26 . HORIZONTAL SUSPENDED FAN COIL UNIT MOUNTED IN SAME
LOCATION AS UNIT REMOVED DURING DEMOLITION. PROVIDE
AUXILIARY CONDENSATE DRAIN PAN BENEATH UNIT. SEE
AUXILIARY CONDENSATE DRAIN PAN DETAIL AND HORIZONTAL DX
FAN COIL UNIT DETAIL.
27 . HORIZONTAL FLOOR MOUNTED FAN COIL UNIT. PROVIDE
SUPPORTS AS REQUIRED TO ELEVATE UNIT TO ALLOW FOR
PROPER INSTALLATION OF CONDENSATE TRAP. PROVIDE
AUXILIARY CONDENSATE DRAIN PAN BENEATH UNIT. SEE
AUXILIARY CONDENSATE DRAIN PAN DETAIL.
28 . CONDENSATE DRAIN ELBOWS DOWN INTO FLOOR DRAIN AT THIS
APPROXIMATE LOCATION. (TYPICAL)
29 . 16" X 14" RETURN DUCTS CONNECT TO EXISTING 44" X 16" IN
CHASE. PROVIDE OFFSETS AND TRANSITIONS AS REQUIRED TO
MAKE CONNECTION.
30 . REFRIGERANT PIPING RISES THROUGH CEILING AND IS ROUTED
THROUGH SAME LOCATION AS PIPING REMOVED DURING
DEMOLITION. MAINTAIN FIRE RATING AT ALL PENETRATIONS
THROUGH RATED CEILINGS..
31 . PROVIDE 1½" ELBOW UP AND MINIMUM 8" TALL VERTICAL OPEN
STAND PIPE AT THIS APPROXIMATE LOCATION.
32 . PROVIDE FULL SIZE, SLOPED, INSULATED PVC VINYL TUBE FOR
DRAIN PIPING FROM UNIT DRAIN PORT AND TRANSITION TO RIGID
DRAIN PIPE AS DETAILED IN VRF CONDENSATE DRAIN
CONNECTION DETAIL. PROVIDE FITTINGS AS REQUIRED TO
CONNECT DRAIN PIPE.
33 . PROVIDE FULL SIZE, TRAPPED, SLOPED, INSULATED PVC FOR
DRAIN PIPING FROM UNIT DRAIN PORT TO CONDENSATE MAIN AS
SHOWN. SEE CONDENSATE DRAIN TRAP DETAIL.
34 . DISTRIBUTION CONTROLLER SUSPENDED WITH DROP RODS (MIN
3/8") AND CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4"
ANGLE IRON. PROVIDE DRAIN PAN BENEATH DISTRIBUTION
CONTROLLER. SEE VRF CONDENSATE DRAIN PAN DETAIL. MOUNT
UNIT AS TIGHT TO STRUCTURE AS POSSIBLE WHILE MAINTAINING
MANUFACTURER'S REQUIRED CLEARANCES.
35 . DISTRIBUTION CONTROLLER SUSPENDED WITH DROP RODS (MIN
3/8") AND CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4"
ANGLE IRON. PROVIDE DRAIN PAN BENEATH DISTRIBUTION
CONTROLLER. SEE VRF CONDENSATE DRAIN PAN DETAIL. MOUNT
UNIT AS TIGHT TO STRUCTURE AS POSSIBLE WHILE MAINTAINING
MANUFACTURER'S REQUIRED CLEARANCES.
36 . REFRIGERANT DISTRIBUTION PIPING ROUTED FROM DISTRIBUTION
CONTROLLER TO INDOOR UNIT. ROUTE REFRIGERANT PIPING
OVER MEZZANINE TIGHT TO STRUCTURE. (TYPICAL)
NOTES: (THIS SHEET ONLY) NOTES: (THIS SHEET ONLY)
37 . NEW 6"Ø CONNECTS TO EXISTING DUCT PENETRATION THROUGH
FLOOR SLAB. PROVIDE TRANSITIONS AS REQUIRED TO CONNECT
TO EXISTING DUCT.
38 . NEW REFRIGERANT PIPING ROUTED IN SAME LOCATION AS PIPING
REMOVED DURING DEMOLITION. FIELD VERIFY EXISTING ROUTING.
39 . REUSE EXISTING PIPE CHASE FOR ROUTING OF NEW PIPING.
40 . MOUNT UNIT ATOP EXISTING CONCRETE EQUIPMENT PAD.
EXTEND EXISTING CONCRETE EQUIPMENT PAD AS SHOWN TO
ALLOW INSTALLATION OF NEW EQUIPMENT.
41 . CONNECTION SIZE SUPPLY DUCT TRANSITIONS AND CONNECTS
TO EXISTING APPROXIMATELY 10" X 36" SUPPLY DUCT. PROVIDE
FITTINGS AND TRANSITIONS AS REQUIRED TO MAKE CONNECTION.
FIELD VERIFY EXISTING DUCT SIZE.
42 . NEW THERMOSTAT LOCATED IN SAME LOCATION AS THERMOSTAT
REMOVED DURING DEMOLITION. FIELD VERIFY EXACT LOCATION.
43 . NEW FACTORY WALL MOUNTED VRF WIRED UNIT
THERMOSTAT/CONTROLLER. MOUNT B.E. 4'-6" A.F.F.
44 . CONNECTION SIZE RETURN DUCT TAPS INTO 14" X 24" RETURN
DUCT.
45 . 14" X 24" RETURN DUCT TRANSITIONS AS REQUIRE TO CONNECT
TO EXISTING APPROX. 24" X 24" RETURN DUCT. PROVIDE FITTINGS
AND TRANSITIONS AS REQUIRED TO MAKE CONNECTION. FIELD
VERIFY EXITING DUCT SIZE.
46 . CONDENSATE PIPE CONTINUES TO SAME LOCATION AS
CONDENSATE PIPE REMOVED DURING DEMOLITION. FIELD VERIFY
EXACT LOCATION.
47 . 4"Ø OUTSIDE AIR DUCT CONNECTS TO CEILING CASSETTE
OUTSIDE AIR KNOCKOUT. PROVIDE FITTINGS AND TRANSITONS AS
REQUIRED TO MAKE CONNECTION. BALANCE FOR 20 CFM OF
OUTSIDE AIR.
48 . OAU-1 POSITIONED BETWEEEN STRUCTURAL MEMBERS TO ALLOW
INSTALLATION. OAU-1 BASIS OF DESIGN IS APPROX 73" TALL AND
WILL EXTEND ABOVE BOTTOM OF STRUCTURAL MEMBERS. ROUTE
NEW OUTSIDE AIR DUCT THROUGH STRUCTURE AS REQUIRED TO
ROUTE AS SHOWN ON DRAWINGS.
49 . REFRIGERANT PIPING RISES TO ABOVE. SEE MECHANICAL NEW
WORK MEZZANINE PLAN - MEDIA AREA THIS SHEET FOR
CONTINUATION.
NOTES: (THIS SHEET ONLY)
50 . DFCU/DCU REFRIGERANT PIPING DROPS TO BELOW MEZZANINE
FLOOR FOR ROUTING TO DFCU. SEE MECHANICAL NEW WORK
PLAN - SECTOR A THIS SHEET FOR CONTINUATION.
51 . REFRIGERANT PIPING ROUTED ABOVE MEZZANINE CEILING, AND
DROPS THROUGH MEZZANINE CEILING IN LOCATION SHOWN.
52 . MAIN DDC PANEL ON 3/4" PLYWOOD BACKBOARD. COORDINATE
EXACT LOCATION WITH EXISTING SERVER RACK AND SHELVING.
53 . VRF CENTRALIZED CONTROLLER MOUNTED ON WALL WITH B.E.
4'-6" A.F.F. PROVIDE BACNET INTERFACE TO ALLOW VRF SYSTEM
TO COMMUNICATE WITH DDC SYSTEM.
54 . DDC CONTACTOR.
NOTES: (THIS SHEET ONLY)
GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS
THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.
2 2
GYM
B120
CH-1
CH-2
CH-4 CH-3
EF-5
EF-31
EF-6
PTHP-1
RTU-1 RTU-2
MECH.
B124
ELEC.
B126
STORAGE
B123
OFFICE
B122
STORAGE
B121
STAGE
B116
KITCHEN
B111 COOLER
B102
FREEZER
B103
DRY STORAGE
B104
OFFICE
B108
TOILET
B106
CAN WASH
B105
SERVING
B112
CORR.
B101
BOYS RR
B117
CUSTODIAL
B119
GIRLS RR
B118
DFCU-2
DHP-2
DISH WASH
B114
CAFETORIUM
B115
KMUAU-1
CC
CC
T
JAN
B110
LOCKERS
B107
TT TT
TT
TT
TT
EF-1
HP-4
FCU-4
DAC-1
S
TT TT
R
D
R
R
R
DFCU-3
DFCU-4
R
D
/2
D
1 1/2" D
R
D
DHP-3
DHP-4
KEF-1
B1 B1
B1 B1
24"x8"
24"x8"
S S
24 24
25 25
NOTES: (THIS SHEET ONLY)
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
M102
MECHANICAL NEW WORK
PLAN - SECTOR B
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
1 . EXISTING ROOF MOUNTED DISHWASHER CENTRIFUGAL FAN TO
REMAIN.
2 . NEW ROOFTOP UNIT MOUNTED ATOP EXISTING CONCRETE PAD.
PROVIDE OFFSETS AND FITTINGS AS REQUIRED TO CONNECT
NEW DUCTWORK TO EXISTING DUCTWORK AT LOCATION SHOWN.
3 . NEW PACKAGED TERMINAL HEAT PUMP MOUNTED IN SAME
LOCATION AS PTHP REMOVED DURING DEMOLITION
4 . HEAT PUMP MOUNTED ATOP CONCRETE PAD.
5 . EXTEND EXISTING CONCRETE PADS TO ALLOW FOR MOUNTING OF
NEW HEAT PUMP. SEE CONCRETE EQUIPMENT PAD DETAIL.
6 . SUPPLY DUCT RISES AND TRANSITIONS TO EXISTING SUPPLY
DUCT CONNECTION SIZE (APPROX 22" X 32" FIELD VERIFY EXACT
DIMENSION) . PROVIDE DUCT OFFSETS AS REQUIRED TO MAKE
CONNECTION.
7 . 30" X 36" RETURN DUCT FROM FCU-4 RISES FROM MIXING BOX FOR
CONNECTION TO EXISTING RETURN DUCT. PROVIDE TRANSITIONS
/ OFFSETS AS REQUIRED TO MAKE CONNECTION.
8 . 16" X 16" OUTSIDE AIR DUCT TAPS INTO BACK OF LOUVER PLENUM
AND IS ROUTED TO FCU-4 MIXING BOX. TRANSITION AS REQUIRED
FOR CONNECTION TO FCU-4.
9 . CENTRIFUGAL ROOF MOUNTED EXHAUST FAN MOUNTED ATOP
EXISTING ROOF CURB.
10 . DUCT MOUNTED SMOKE DETECTOR SHALL BE PROVIDED AND
WIRED BY ELECTRICAL AND INSTALLED BY MECHANICAL.
11 . FIELD VERIFY LOCATION OF EXISTING DUCT MOUNTED SMOKE
DETECTOR. NEW DUCT MOUNTED SMOKE DETECTOR LOCATED IN
SAME LOCATION AS EXISTING. DUCT MOUNTED SMOKE DETECTOR
PROVIDED AND WIRED BY ELECTRICAL AND INSTALLED BY
MECHANICAL. REMOTE TEST STATION, LED, AND AUDIBLE
SOUNDER PORTION OF SMOKE DETECTOR SYSTEM WHICH
REQUIRED SERVICING AND PERIODIC MAINTENANCE IS SEPARATE
FROM TUBE AND ELECTRONIC SENSING COMPONENT AND SHALL
BE MOUNTED IN AN ACCESSIBLE LOCATION ADJACENT TO
THERMOSTAT.
12 . CONDENSATE DRAIN ELBOWS DOWN TO EXISTING FLOOR DRAIN
AT THIS APPROXIMATE LOCATION.
13 . DUCTLESS HEAT PUMP MOUNTED ATOP EXISTING EQUIPMENT
SUPPORT PLATFORM ON ROOF THIS APPROXIMATE LOCATION.
14 . DFCU CONDENSATE ROUTED TO SAME LOCATION AS
CONDENSATE PIPING REMOVED DURING DEMOLITION. FIELD
VERIFY EXACT LOCATION.
15 . NEW KITCHEN MAKE UP AIR UNIT MOUNTED ATOP EXISTING ROOF
CURB. PROVIDE ADAPTER AS REQUIRED.
16 . UTILIZE EXISTING ROOF CURB FOR EQUIPMENT SUPPORT
PLATFORM FOR NEW DUCTLESS HEAT PUMP. SEE EQUIPMENT
SUPPORT PLATFORM DETAIL.
17 . REFRIGERANT PIPING RISES IN NEW PIPE BOX ON ROOF. SEE PIPE
BOX/HOOD ASSEMBLY DETAIL.
18 . PROVIDE 1½" ELBOW UP AND MINIMUM 8" TALL VERTICAL OPEN
STAND PIPE AT THIS APPROXIMATE LOCATION.
19 . NEW CONDENSATE DRAIN CONNECTS TO EXISTING CONDENSATE
DRAIN AT THIS APPROXIMATE LOCATION. FIELD VERIFY EXACT
LOCATION AND DIMENSIONS. PROVIDE FITTINGS AS REQUIRED TO
MAKE CONNECTION.
20 . NEW KITCHEN EXHAUST FAN MOUTNED ATOP EXISTING ROOF
CURB. PROVIDE ADAPTER AS REQUIRED.
21 . DDC CONTACTOR.
22 . WALL MOUNTED CEILING HEATER THERMOSTAT MOUNTED IN
SAME LOCATION AS EXISTING THERMOSTAT. FIELD VERIFY EXACT
LOCATION.
23 . METAL DUCT HOOD BETWEEN HVAC UNIT AND EXTERIOR WALL.
SEE METAL DUCT HOOD DETAIL FOR MORE INFORMATION.
CONSTRUCT HOOD TO COMPLETLY COVER EXISTING WALL
OPENING. FIELD VERIFY EXACT DIMENSIONS.
24 . NEW DUCT TRANSITIONS FROM UNIT CONNECTION SIZE TO
EXISTING DUCT SIZE. PROVIDE OFFSETS AND TRANSITIONS AS
REQUIRED. EXTERIOR DUCTWORK SHALL HAVE ONE LAYER OF 2"
THICK ARMAFLEX CLOSED CELL ELASTOMERIC INSULATION ON
EXTERIOR OF DUCT. COVER INSULATION WITH EMBOSSED
ALUMINUM COVER. PROVIDE DUCT SUPPORTS AS NECESSARY TO
ADEQUATELY SUPPORT DUCT.
25 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC
CONDENSATE DRAIN PIPING FROM RTU TO LOCATION SHOWN.
BASIS OF DESIGN CONDENSATE DRAIN CONNECTION IS IN A
DIFFICULT TO ACCESS LOCATION, INSTALL TRAP IN AN
ACCESSIBLE LOCATION OUTSIDE OF DUCT HOOD AS SHOWN. DO
NOT INSTALL TRAP UNDER DUCT HOOD. ENSURE DRAIN PIPING
DOES NOT BLOCK ACCESS PANELS. SEE CONDENSATE DRAIN
TRAP DETAIL.
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR B
GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS
1 1
1 1
2 2
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
A3
A3
A3
A3
WHHP-1
WHHP-13
WHHP-2
WHHP-12
WHHP-3
WHHP-4
WHHP-5
WHHP-6
WHHP-7
WHHP-8
WHHP-9
WHHP-10
WHHP-11
EF-11
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
C1
C1
C1
C1
A2
A2
A2
A2
A1
A1
A2
A2
A2
A2
A2
A2
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø
10"ø
C1
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
20"x10"
A3
A3
A3
A3
10"ø
10"ø
10"ø
12"x10"
30"x10"
C1
10"ø
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
A3
A3
A3
A3
12"x10" 20"x10"
10"ø 10"ø
10"ø 10"ø
C1
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
20"x10"
A3
A3
A3
A3
10"ø
10"ø10"ø
12"x10"
30"x10"
C1
10"ø
A2
A2
WHHP-16
WHHP-15
WHHP-14
WHHP-17
WHHP-18
WHHP-19 WHHP-20
WHHP-21
WHHP-22
WHHP-23
WHHP-24
WHHP-25
WHHP-26
WHHP-27
WHHP-28
WHHP-29
WHHP-30
WHHP-31 WHHP-32
WHHP-33
WHHP-34
WHHP-35
WHHP-36
WHHP-37
EF-15
EF-16
EF-12
EF-13
EF-23
EF-20
EF-19
EF-22
EF-21
4TH GRADE CR
C102
4TH GRADE CR
C123
4TH GRADE CR
C122
5TH GRADE CR
C113
4TH GRADE CR
C104
4TH GRADE CR
C103
2ND GRADE CR
D102
2ND GRADE CR
D123
2ND GRADE CR
D122
2ND GRADE CR
D103
2ND GRADE CR
D104
EIP
D112
3RD GRADE CR
D111
3RD GRADE CR
D110
3RD GRADE CR
D109
3RD GRADE CR
D108
P.F.
D107
BOYS TOILET
D105
ELEC
D114
JAN
D106
VESTIBULE
D118
WORK ROOM
D119
BOOK STOR.
D120
IDF
D121
5TH GRADE CR
C109
5TH GRADE CR
C110
5TH GRADE CR
C111
5TH GRADE CR
C112
KINDERGARTEN CR
E102
KINDERGARTEN
CLASSROOM
E106
KINDERGARTEN
CLASSROOM
E131
KINDERGARTEN CR
E135
1ST GRADE CR
E121
1ST GRADE CR
E120
1ST GRADE CR
E111
MOID
E110
PID CR
E107
WORK ROOM
E128
JAN
E122
VESTIBULE
E127
WOMEN
E125
MEN
E126
IDF
E130
ELEC
E129
BATHROOM
E108
KITCHEN/LAUND
E109
RECEPTION/WAITING
E116
BOOK STOR.
E117
GIRLS TLT
E118
BOYS TLT
E119
BOOK STOR.
E112
GIRLS TLT
E113
BOYS TLT
E114
RECEPTION/WAITING
E115
SPEECH CR
C108
RESOURCE CR
C107
JAN
C106
BOYS TOILET
C105
BOOK STOR.
C120
IDF
C121
WORK ROOM
C119
VESTIBULE
C118
WOMEN
C116
MEN
C117
ELEC
C114
MEN
D117
WOMEN
D116
BOYS TLT
E134
GIRLS TLT
E133
BOOK STOR.
E132
BOOK STOR.
E103
GIRLS TLT
E104
BOYS TLT
E105
CORRIDOR
E101
A4
A4 ø12" ø12"
12"x12"
A4 ø12" ø12"
12"x12"
A4
EF-38
A1
EF-17
EF-18
6"ø
A1
A1
A1
A1
EF-14
CH-5
CH-6
CH-7
CH-8
PTHP-2 PTHP-3
A1
A1
A2
A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
EF-36 EF-37
6 6
6 6
CORRIDOR
C101
GIRLS TOILET
C115
CORRIDOR
D101
GIRLS TOILET
D115
LAB
E116.4
LAB
E115.4
ER 3
E115.3
ER 2
E115.2
ER 1
E115.1 ER 3
E116.3
ER 2
E116.2
ER 1
E116.1
T
CC
CC
CC CC
CC
CC
T
CC
CC
T
CC
CC
CC
CC
CC
GIRLS TLT
E123
BOYS TLT
E124
EF-25 EF-27 EF-29
OAU-4OAU-3
OAU-5
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
6"ø
6"ø
6"ø
6"ø
8"ø
8"ø
6"ø
6"ø
8"ø
8"ø
8"ø
6"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
"ø
20"x14" 20"x14" A2
8"ø
6"ø
8"ø
8"ø
"ø
"ø
"ø
"ø
A2
A2
A2
A2
1508"ø
6"ø
6"ø
6"ø ø8" ø8"
8"ø ø8" ø8"
C1
750 90 450 750 90 450
7575 75
TT
TT
TT
TT
75 75
DHP-1
16"x14"
A1
6"ø 6"ø
A1
A1
6"ø
TT
TT
TTTT
TT
TT
TT
TT
TT
TT TT
TTTT
C1
C1
TT TT
TTTT
TT
TT
TT TT
TT
TT
TT TT
TTTT
TT TT
TT TT
TTTT
TT TT
20"x14"20"x14"
10 10
4 4
4 4
4 4
4 4
PTHP-4
12 12
14 14
15 15
16 16
17 17
TT
TT
TT
22 22
24 24
6"ø
6"ø
6"ø
6"ø
A1
6"ø
6"ø
6"ø
A1
6"ø
6"ø
A1
"ø
"ø
6"ø
6"ø
A1
A1
6"ø
6"ø
4 4
6 6
A1
6"ø
8"ø ø8"
8"ø ø8"6"ø
6"ø
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
M103
MECHANICAL NEW WORK
PLAN - SECTORS C, D & E
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS
WALL HUNG HEAT PUMP REMOVED DURING DEMOLITION. PROVIDE
ADAPTER CURB AS REQUIRED FOR NEW INSTALLATION OF WHHP.
SEE WALL HUNG HEAT PUMP DUCTED DETAIL.
2 . CENTRIFUGAL INLINE EXHAUST FAN MOUNTED ABOVE CEILING.
3 . OUTSIDE AIR DUCT OF INDICATED SIZE RISES UP IN NEW DUCT
CHASE TO ABOVE CEILING LEVEL. SEE OAU DUCT ROUTING
DETAIL.
4 . DUCT ROUTED OVER FIRE RATED MEZZANINE. NO FIRE DAMPER
REQUIRED. DO NOT PENETRATE CORRIDOR FIRE RATED WALL.
5 . NEW OUTSIDE AIR DUCT ROUTED ABOVE CHICKEN WIRE
INSULATION SYSTEM.
6 . DUCT ROUTED OVER FIRE RATED MEZZANINE TURNS DOWN AND
PENETRATES MEZZANINE FOR CONNECTION TO CEILING
DIFFUSER IN CORRIDOR. PROVIDE FIRE DAMPER AT DUCT
PENETRATION OF FIRE RATED MEZZANINE. PROVIDE FLEX DUCT
OF INDICATED SIZE AT CONNECTION TO GRILLE.
7 . DUCT TAPS INTO TOP OF INDICATED DUCT, RISES TO ABOVE
SUSPENDED INSULATION SYSTEM AND IS ROUTED AS SHOWN.
PROVIDE R-8 INSULATION FOR DUCTWORK ROUTED IN ATTIC.
8 . OUTSIDE AIR DUCT OF SIZE INDICATED PENETRATES CHICKEN
WIRE INSULATION SYSTEM FOR CONNECTION TO GRILLE. SEE
OUTSIDE AIR DUCT GRILLE CONNECTION DETAIL.
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTORS C, D, & E9 . 100% OUTSIDE AIR UNIT MOUNTED ATOP CONCRETE EQUIPMENT
PAD. COORDINATE CONCRETE PAD WITH EXISTING GUTTERS,
CLEANOUTS, ETC. SEE CONCRETE EQUIPMENT PAD DETAIL.
EXTEND EDGE OF PAD TO INCLUDE ALL FENCE POSTS AND
FENCING.
10 . 100% OUTSIDE AIR DUCT TRANSITIONS FROM UNIT CONNECTION
SIZE TO SIZE SHOWN, PENETRATES EXTERIOR WALL, AND TURNS
VERTICAL IN NEW DUCT CHASE AS SHOWN. EXTERIOR DUCTWORK
SHALL HAVE ONE LAYER OF 2" THICK ARMAFLEX CLOSED CELL
ELASTOMERIC INSULATION ON INTERIOR OF DUCT. SEE EXTERIOR
DUCT PENETRATION THRU WALL DETAIL.
11 . COORDINATE NEW CONCRETE PAD WITH EXISTING GUTTER AT
THIS APPROXIMATE LOCATION. FIELD VERIFY EXACT LOCATION.
MODIFY EXISTING GUTTER TO OFFSET AROUND NEW DUCT AS
REQUIRED. CONDENSATE DRAIN ROUTED TO EXISTING GUTTER
AS SHOWN.
12 . NEW PACKAGED TERMINAL HEAT PUMP MOUNTED IN SAME
LOCATION AS PTHP REMOVED DURING DEMOLITION
13 . OUTSIDE AIR DUCT OF INDICATED SIZE RISES UP IN NEW DUCT
CHASE TO ABOVE CEILING LEVEL. SEE OAU DUCT ROUTING
DETAIL. COORDINATE DUCT CHASE TO NOT INTERFERE WITH
EXISTING WINDOW. SEE ARCHITECTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
NOTES: (THIS SHEET ONLY) NOTES: (THIS SHEET ONLY)
14 . PROVIDE NEW 6' TALL CHAINLINK FENCE AROUND OUTSIDE AIR
UNIT. MAINTAIN REQUIRED CLEARANCES AROUND UNIT FOR
PROPER OPERATION AND SERVICE. MAINTAIN MINMUM 3' AROUND
EACH SIDE OF THE OAU THAT REQUIRES CLEARANCE.
15 . APPROXIMATE LOCATION OF EXISTING CLEANOUT. EXTEND
EXISTING CLEANOUT ABOVE NEW CONCRETE EQUIPMENT PAD.
FIELD VERIFY EXISTING LOCATION AND PIPE SIZE.
16 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED,
SCHEDULE 40 PVC PIPING TO DISCHARGE AS SHOWN ON
DRAWINGS. SEE CONDENSATE DRAIN TRAP DETAIL. COORDINATE
CONDENSATE ROUTING WITH DUCT COVER. CONDENSATE TRAP
SHALL BE LOCATED OUTSIDE OF DUCT COVER.
17 . METAL DUCT HOOD BETWEEN HVAC UNIT AND EXTERIOR WALL.
SEE METAL DUCT HOOD DETAIL FOR MORE INFORMATION.
18 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE
TEMPERATURE. MOUNT B.E. 4' 6" A.F.F.
19 . WALL MOUNTED DDC SPACE TEMPERATURE SENSOR. MOUNT B.E.
OF SENSOR AT 4'-6" A.F.F.
20 . WALL MOUNTED DDC SPACE TEMPERATURE SENSOR MOUNTED IN
SAME LOCATION AS EXISTING. FIELD VERIFY EXACT LOCATION.
NOTES: (THIS SHEET ONLY)
21 . WALL MOUNTED CEILING HEATER THERMOSTAT MOUNTED IN
SAME LOCATION AS EXISTING THERMOSTAT. FIELD VERIFY EXACT
LOCATION.
22 . WALL MOUNTED SNAP ACTION THERMOSTAT LOCATED IN SAME
LOCATION AS EXISTING THERMOSTAT. FIELD VERIFY EXACT
LOCATION.
23 . DDC CONTACTOR.
24 . PROVIDE NEW 3' WIDE CHAINLINK FENCE GATE WITH LOCKABLE
HANDLE IN LOCATION SHOWN.
GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS
GENERAL NOTES:
1. EQUIPMENT MODEL NUMBERS INDICATED ARE FOR BASIS-OF-DESIGN
MANUFACTURER, CARRIER, UNLESS NOTED OTHERWISE.
2. REFRIGERANT PIPING SIZES INDICATED ARE APPROXIMATE AND SHALL BE
VERIFIED / COORDINATED WITH EQUIPMENT SUPPLIER BASED ON REQUIRED
LENGTHS, SYSTEM LAYOUT / INSTALLATION, SYSTEM CAPACITY, AND OTHER
FACTORS AS REQUIRED BY MANUFACTURER.
GENERAL NOTES:
1. EQUIPMENT MODEL NUMBERS INDICATED ARE FOR BASIS-OF-DESIGN
MANUFACTURER, CARRIER, UNLESS NOTED OTHERWISE.
2. REFRIGERANT PIPING SIZES INDICATED ARE APPROXIMATE AND SHALL BE
VERIFIED / COORDINATED WITH EQUIPMENT SUPPLIER BASED ON REQUIRED
LENGTHS, SYSTEM LAYOUT / INSTALLATION, SYSTEM CAPACITY, AND OTHER
FACTORS AS REQUIRED BY MANUFACTURER.
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
2021191
05/20/2022
GA DOE ID #: 0299
M301
MECHANICAL DIAGRAMS
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOT TO SCALE
HRU-1 PIPING DIAGRAM
NOT TO SCALE
HRU-1 WIRING DIAGRAM
NOT TO SCALE
HRU-2 PIPING DIAGRAM
NOT TO SCALE
HRU-2 WIRING DIAGRAM
NOT TO SCALE
VRF CENTRAL CONTROLLER DIAGRAM
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
2021191
05/20/2022
GA DOE ID #: 0299
M302
MECHANICAL DIAGRAMS
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOT TO SCALE
FCU-4 HOT GAS BYPASS DIAGRAM
NOT TO SCALE
FCU-4 MODULATING HOT GAS REHEAT DIAGRAM
No. Description Date
NOT TO SCALE
OAU-1, OAU-2 HOT GAS REHEAT PIPING DIAGRAM
J
POWER WIRING AND CONDUIT BY ELECTRICAL
EXISTING ROOF CURB.
POWER CABLE BY ELECTRICAL
REMOVABLE ACCESS COVER FOR MOTOR
COMPARTMENT
INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT
SWITCH UNLESS SCHEDULED OTHERWISE
SEE SCHEDULE FOR DRIVE TYPE.
FACTORY WIRED FROM MOTOR TO
DISCONNECT SWITCH.
UPBLAST EXHAUST FAN
EXISTING EXHAUST DUCT UP FROM
BELOW
FACTORY INSTALLED, MINIMUM 1/2"
DIA. CONDUIT CHASE GALVANIZED BIRD SCREEN
SECURE CURB CAP TO CURB WITH ANCHORS ON
MAXIMUM 12" CENTERS (MINIMUM 2 ANCHORS
EACH SIDE)
GRADE
WELDED WIRE MESH
AT MID DEPTH OF SLAB
6" X 6" 10/10 WWF
3000 PSI CONCRETE
1" CHAMFER
SEE SPECIFICATIONS FOR
PAD HEIGHT ABOVE
ADJACENT GRADE
2" MINIMUM
EXTERIOR CONCRETE PAD
FLOOR
1" CHAMFER
ANCHOR (TYPICAL OF 4)
INTERIOR CONCRETE PAD
WELDED WIRE MESH
AT MID DEPTH OF SLAB
6" X 6" 10/10 WWF
SEE SPECIFICATIONS FOR
PAD HEIGHT ABOVE
ADJACENT GRADE
2"
3000 PSI CONCRETE
1½"
3"
UNION
AC UNIT
DRAIN CONNECTION
DRAIN PIPE SHALL BE AT LEAST
THE SAME DIAMETER AS THE NIPPLE
ON THE DRAIN PAN CONNECTION
OPEN END NIPPLE
SEE DRAWINGS FOR
PIPE REQUIRED MATERIAL
SLOPE AS REQUIRED
IN SPECIFICATIONS
PIPE NIPPLE
J
POWER WIRING AND CONDUIT BY ELECTRICAL
EXISTING ROOF CURB.
POWER CABLE BY ELECTRICAL
REMOVABLE ACCESS COVER FOR MOTOR
COMPARTMENT
INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT
SWITCH UNLESS SCHEDULED OTHERWISE
SEE SCHEDULE FOR DRIVE TYPE. (PROVIDE
ADJUSTABLE SHEAVE FOR ALL BELT DRIVE)
FACTORY WIRED FROM MOTOR TO
DISCONNECT SWITCH.
EXHAUST FAN
EXHAUST DUCT UP FROM BELOW
FACTORY INSTALLED, MINIMUM 1/2"
DIA. CONDUIT CHASE
CEILING, BY ARCHITECTURAL
SQUARE TO ROUND TRANSITION (WHERE ELBOW CONNECTS TO SQUARE
NECK DIFFUSERS). PROVIDE ROUND TO ROUND TRANSITION WHERE GRILLE
NECK SIZE DIFFERS FROM CONNECTING DUCT SIZE (EITHER LARGER OR
SMALLER). INSULATE ON SUPPLY DUCTS.
3 GORE ADJUSTABLE ELBOW. INSULATE
ON SUPPLY DUCTS.
NYLON ZIP STRIP ON OUTER VAPOR BARRIER.
ENSURE INSULATION IS PULLED DOWN WITH
VAPOR BARRIER SO NO DUCTWORK IS
UNINSULATED.
NOTE: DETAIL IS TYPICAL FOR ALL FLEX DUCT RUNOUTS TO DIFFUSERS
STAINLESS STEEL DRAWBAND
ON INNER DUCT
FLEX DUCT
INSULATION BLANKET ON TOP
OF SUPPLY DIFFUSERS
CEILING DIFFUSER
HEX NUTS SECURELY TIGHTENED
HVAC EQUIPMENT
EQUIPMENT MOUNTING RAIL
OR MOUNTING BRACKETS
LOWER SUPPORT WITH RAIL LOWER SUPPORT WITH INTEGRAL TAPPING UPPER SUPPORT
EQUPIMENT WITH INTEGRAL
THREADED TAPPING
DOUBLE HEX NUTS TIGHTLL
SECURED. CONTRACTOR MAY
USE HEXNUT AND LOCK WASHER,
HEXNUT AND JAMNUT OR
LOCKNUT.
WELD OR CLAMP ANGLE IRON TO
STRUCTURE (BAR JOISTS, BEAMS, ETC.)
THREADED ROD. SEE
SPECIFICATIONS FOR SIZE.
HEX NUTS SECURELY
TIGHTENED
GENERAL: PROVIDE VIBRATION ISOLATION WHERE
SPECIFIED, PROVIDE DOUBLE NUTS AT EACH
CONNECTION POINT TO VIBRATION ISOLATOR
(4 NUTS TOTAL PER ISOLATOR)
NOTE: UPPER SUPPORT DETAIL
IS ALSO APPLICABLE TO PIPE
HANGER SUPPORTS.
BASIS OF DESIGN GUIDELINES, CONNECTION AT INDOOR
UNIT MAY VARY BASE ON MANUFACTURER'S INSTRUCTIONS
TRANSPARENT CLEAR PVC DRAIN PIPE SHALL
TRANSITION AS REQUIRED TO CONNECT TO
STANDARD RIGID DRAIN PIPE
INSULATION AS SPECIFIED
TRANSITION TO PVC OR COPPER
AT THIS APPROXIMATE LOCATION
MAIN 1 ½" DRAIN PIPE
DRAIN PIPE
DRAIN PIPE
D O
N O
T E
X C
E E
D M
A N
U F
A C
T U
R E
R 'S
M
A X
IM
U
M L
IF
T
C A
P A
B
IL
IT
Y
6" MAX.
DRAIN PIPE
LARGE S.S. WORM GEAR.
SECURE WORM GEAR AROUND
INSULATION AND PIPING.
DRAIN SOCKET,
PROVIDED WITH VRF
EQUIPMENT
TRANSPARENT PVC DRAIN PIPE PROVIDED
WITH VRF EQUIPMENT. SEE INDOOR UNIT
SCHEDULE FOR DRAIN CONNECTION SIZE.
SMALL S.S. WORM GEAR. SECURE
WORM GEAR AROUND DRAIN SOCKET
AND DRAIN CONNECTION PIPE
S
GENERAL: ENSURE ALL ACCESS DOORS FOR FAN, MOTOR, ELECTRICAL, ETC.,
ARE FREE TO OPEN FULLY AND ARE NOT OBSTRUCTED BY WALLS, PIPING,
CONDUIT, ETC. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE
CLEARANCES AROUND FAN COIL UNIT.
D
R S
R L
THREADED DROP ROD SUPPORT
(TYP OF 4). SEE UPPER SUPPORT
DETAIL. PROVIDE SUFFICIENT
DISTANCE FROM ACCESS PANEL
TO ALLOW OPENING. FAN COIL UNIT
(FCU)
TRANSITION FROM UNIT CONNECTION SIZE
TO DUCT SIZE SHOWN ON PLANS
FLEXIBLE DUCT CONNECTION
(TYPICAL SUPPLY AND RETURN)
INSULATED (2" DUCTWRAP) SUPPLY DUCT.
ADDITIONALLY, PROVIDE DUCT LINER
DOWNSTREAM OF FCU AS SHOWN ON FLOOR PLANS.
DOUBLE DEFLECTION NEOPRENE
VIBRATION ISOLATOR (TYP OF 4)
DUCT MOUNTED SMOKE DETECTOR ON UNITS
2000 CFM AND OVER. DETECTOR PROVIDED
AND WIRED BY DIVISION 16 AND INSTALLED BY
MECHANICAL AND INCORPORATED INTO HVAC
CONTROLS AS SPECIFIED BY DIVISION 15.
WHERE SHOWN ON THE DRAWINGS, PROVIDE
1/2" DRAIN PIPE ROUTED TO DISCHARGE IN
CONSPICUOUS LOCATION AS SHOWN ON FLOOR PLANS
2 X 2 X 1/4 UPPER AND LOWER ANGLE OR
CHANNEL SUPPORT. SEE DETAIL. (TYP OF
2, MIN.) ONE SUPPORT SERVES FCU,
SECOND SUPPORT SERVES DRAIN PAN.
FULL SIZED SLOPED,…
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| Bid tab | — | |
| Addendum 3 | — | |
| Addendum 4 | — | |
| Bid Invitation | — | |
| Award Information | — | |
| Addendum 2 | — | |
| Addendum 1 | — |