Addendum 3 Summary
This is Addendum 3 to the contract documents for HVAC & Plumbing Upgrades at Alice Coachman Elementary School, issued by the Dougherty County Board of Education in Albany, Georgia on June 15, 2022. The addendum modifies the original specifications and drawings dated May 20, 2022, and requires all bidders to acknowledge receipt on the Bid Price Form to avoid disqualification. Key modifications include substantial changes to Section 015000 regarding temporary modular classrooms, which must measure a minimum of 68' x 28' and accommodate two standard classrooms (600-700 square feet each) plus two ADA-accessible restrooms. The modular classroom specifications require comprehensive mechanical, electrical, and technology infrastructure, including fire alarm systems, HVAC equipment to maintain 70-75 degrees Fahrenheit, wireless internet connectivity, intercom systems, lighting fixtures capable of 50 foot-candles at desk height, ADA-accessible ramps and steps, and above-ground septic tanks with weekly pumping service. Two modular classroom distributors are identified: Wilscot in Tallahassee, Florida and Mobile Modular in Arcade, Georgia. Additional specification changes include deletion and replacement of Section 095113 (Acoustical Panel Ceilings) with a revised June 15, 2022 version, addition of CaptiveAire as an approved manufacturer in Section 233423, and modification of Section 234100 to specify Global Plasma Solutions as the approved manufacturer for bi-polar ionization units.
The addendum also replaces multiple mechanical and electrical drawing sheets, including Sheets MD101, MD102, and MD103 (Mechanical Demo Plans for Sectors A, B, and C/D/E respectively) and Sheets E001 and E801 (Electrical Overall Plan and Electrical Schedules and Legend), all revised to June 15, 2022. The acoustical panel ceiling specifications detail requirements for both wet and dry areas, with approved manufacturers including Armstrong World Industries, CertainTeed Corp., and USG Interiors. Specifications include comprehensive installation requirements, product performance standards complying with ASTM E 84 and E 1264, maintenance material submittals of 100 full-size panels of APC #1 and 25 full-size panels of APC #2, and 100 lineal feet of suspension system components. The addendum includes detailed mechanical demolition notes identifying existing equipment to be removed, retained, or salvaged, including GPS Needlepoint Bipolar Ionization Devices that must be labeled, safely stored, and reinstalled in new HVAC units in the same locations.
Text of this file
Alice Coachman Elementary School May 20, 2022 HVAC & Plumbing Upgrades Dougherty County Board of Education Albany, Georgia
Addendum No. 3- Page 1 of 3
ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210
ADDENDUM NUMBER: THREE DATED: June 15, 2022
To: All contract bidders of record.
This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings dated May 20, 2022, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Price Form; failure to do so may subject bidder to disqualification.
CHANGES TO SPECIFICATIONS
1. SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS
A. On page 015000-3, delete paragraph 2.2.C. in its entirety and replace with the following:
“C. Modular Classrooms: Of sufficient size (68’ x 28’ minimum) to accommodate two
(2) standard size classrooms (600-700 s.f.) and two (2) restrooms with ADA access. Furnish and equip modular classrooms as follows:
1. Fire Alarm Pull Station at door (one in each classroom). Connect pull station to the main building Fire Alarm Panel.
2. Fire Alarm Horn/Strobe (one in each classroom). Connect fire alarm to the main building Fire Alarm Panel.
3. Exit Light/Emergency Light (one in each classroom at egress).
4. Computer Hub/Switch. Connect to nearest IDF in the main building.
5. Wireless internet access, associated with main building. Connect portable classroom hub/switch to nearest IDF in the main building.
6. Wireless Access Point (one in each classroom). Connect to hub/switch.
7. Intercom Speaker (one in each classroom). Bogen model number
MB8TSL(VR) or approved equal.
8. Relay Board/s and Analog Card to Main Intercom Head End to support the additional temporary classroom intercom speakers.
9. Intrusion Alarm on Exterior Doors. Connect to main building alarm panel.
10. ADA Accessible Rest Room (one in each classroom).
11. Cooling and heating equipment necessary to maintain a uniform indoor temperature of 70-75 deg. F.
12. Lighting fixtures capable of maintaining average illumination of 50fc at desk height
13. One Set of Steps and One ADA Ramp.
14. Above ground septic tank, which will include weekly pumping service.
15. Exterior Light (Hubbell Model # LMC-30LU-4K-3-1-BZ or equal (one each portable).
16. Above ground septic tank, which will include weekly pumping service.
Addendum No. 3- Page 2 of 3
17. Modular Classroom Distributers:
a. Wilscot, 4742 Blountstown Hwy., Tallahassee, FL 3204;
(850) 574-9222, Contact Person; Rusty Young (850) 228-6575.
b. Mobile Modular, 530 Etheridge Rd., Arcade GA 30549,
(770) 366-3356, wendy.grenske@mobilemodular.com”
2. SECTION 095113 - ACOUSTICAL PANEL CEILINGS
A. Delete Section 095113 - Acoustical Panel Ceilings dated May 20, 2022, in its entirety and replace with Section 095113 - Acoustical Panel Ceilings, revised June 15, 2022, included herewith.
3. SECTION 233423 - HVAC POWER VENTILATORS
A. On page 233423-6, paragraph 2.12.B., add “CaptiveAire” as an approved manufacturer.
4. SECTION 234100 - PARTICULATE AIR FILTRATION AND BI-POLAR IONIZATION
UNITS
A. On page 234100-3, paragraph 2.3.A, delete the last sentence of this paragraph in its entirety and replace with the following:
“Bi-polar ionization unit shall be manufactured by Global Plasma Solutions or prior approved equal.”
CHANGES TO DRAWINGS
1. SHEET MD101 - MECHANICAL DEMO PLAN - SECTOR A
A. Delete Sheet MD101 in its entirety and replace with Sheet MD101, revised 06/15/2022, included herewith.
2. SHEET MD102 - MECHANICAL DEMO PLAN - SECTOR B
A. Delete Sheet MD102 in its entirety and replace with Sheet MD102, revised 06/15/2022, included herewith.
3. SHEET MD103 - MECHANICAL DEMO PLAN - SECTORS C, D & E
A. Delete Sheet MD103 in its entirety and replace with Sheet MD103, revised 06/15/2022, included herewith.
4. SHEET E001- ELECTRICAL OVERALL PLAN
A. Delete Sheet E001 in its entirety and replace with Sheet E001, revised 06/15/2022, included herewith.
Addendum No. 3- Page 3 of 3
5. SHEET E801- ELECTRICAL SCHEDULES AND LEGEND
A. Delete Sheet E801 in its entirety and replace with Sheet E801, revised06/15/2022, included herewith.
END OF ADDENDUM #3
Alice Coachman Elementary School Revised June 15, 2022
ACOUSTICAL PANEL CEILINGS 095113 - 1
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for ceilings.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.
2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
ACOUSTICAL PANEL CEILINGS 095113 - 2
B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed.
Do not proceed with installation of ceilings until deficiencies have been corrected.
1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.
2. Before notifying Architect, complete the following in areas to receive ceilings:
a. Installation of lighting fixtures, powered for operation.
b. Installation, insulation, and leak and pressure testing of water piping systems.
c. Installation of air-duct systems.
d. Installation of air devices.
e. Installation of mechanical system control-air tubing.
f. Installation of ceiling support framing.
C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.
2. Smoke-Developed Index: 450 or less.
2.2 ACOUSTICAL PANELS, GENERAL
A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.
B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.
C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.
2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)
A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.
ACOUSTICAL PANEL CEILINGS 095113 - 3
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.
2. Pattern: E.
C. Color: White.
D. LR: Not less than 0.90.
E. NRC: Not less than 0.95.
F. Humidity/Sag Resistance: Humiguard Plus.
G. Edge/Joint Detail: Square edge.
H. Thickness: 5/8 inch.
I. Modular Size: 24 by 24 inches.
2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Clean Room VL
2. CertainTeed Corp.; Performa, Vinyrock
3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.
2. Pattern: As indicated by manufacturer’s designation.
C. Color: White.
D. LR: Not less than 0.78.
E. CAC: Not less than 38.
F. Edge/Joint Detail: Square.
G. Thickness: 1/2 inch.
H. Modular Size: 24 by 24 inches.
ACOUSTICAL PANEL CEILINGS 095113 - 4
2.5 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.
1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.
B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.
2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>
A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation
B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating designation; with prefinished 15/16-inch-wide metal caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. End Condition of Cross Runners: Override (stepped) type.
3. Face Design: Flat, flush.
4. Cap Material: Steel cold-rolled sheet.
5. Cap Finish: Painted white.
2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard
2. CertainTeed Corp.; Classic Environmental Stab
3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA
ACOUSTICAL PANEL CEILINGS 095113 - 5
B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System:
Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-rolled, 15/16-inch-wide aluminum caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. Face Design: Flat, flush.
3. Face Finish: Painted white.
2.8 METAL EDGE MOLDINGS AND TRIM
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation.
B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.
1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated.
2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member.
3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.
B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
ACOUSTICAL PANEL CEILINGS 095113 - 6
3.2 PREPARATION
A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.
3.3 INSTALLATION
A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."
B. Suspend ceiling hangers from building's structural members and as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.
2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.
3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.
4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.
5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.
6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.
7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.
8. Do not attach hangers to steel deck tabs.
9. Do not attach hangers to steel roof deck. Attach hangers to structural members.
10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.
11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.
ACOUSTICAL PANEL CEILINGS 095113 - 7
C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or post installed anchors.
D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.
1. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.
2. Do not use exposed fasteners, including pop rivets, on moldings and trim.
E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.
F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.
1. Arrange directionally patterned acoustical panels as follows:
a. Install panels in a basket-weave pattern.
2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.
3. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.
3.4 CLEANING
A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.
END OF SECTION 095113
ACOUSTICAL PANEL CEILINGS 095113 - 8
THIS PAGE INTENTIONALLY LEFT BLANK
44 4 4
MD101
MD101
MD101
11 12
9 9
CORRIDOR
A114
OFFICE
A104
WORK ROOM
A119
COUNSELOR
A118
TEST
A122
A123
BOOK KEEPING
A124
PRINCIPAL
A108
RR
A107
RR
A106
RR
A105
RR
A115
ELEC
A110
CLINIC
A116
ART
A111
STOR.
A113
MEDIA
A127
LOBBY
CONF.
A136
A.V. STOR.
A135
MEDIA PRODUCTION
A134
MDF
A133
COMPUTER LAB
A131
MUSIC
A132
21 21
19 19
19 19
7 7
7 7
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD101
MECHANICAL DEMO PLAN -
SECTOR A
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . REMOVE EXISTING INLINE EXHAUST FAN MOUNTED ABOVE
CEILING.
2 . REMOVE EXISTING FAN COIL UNIT AND ASSOCIATED DUCTWORK
UP TO LOCATION SHOWN. REMOVE EXISTING GPS BIPOLAR
IONIZATION UNIT AND STORE FOR REUSE IN NEW FAN COIL UNIT
SAME LOCATION.
3 . REMOVE EXISTING VVT BOX, SUPPORTS, ASSOCIATED
DUCTWORK, INSULATION, ETC. (TYPICAL)
4 . REMOVE EXISTING HEAT PUMP, ASSOCIATED PIPING, ETC.
5 . EXISTING DUCT PENETRATES FLOOR SLAB AT THIS APPROXIMATE
LOCATION. LEAVE EXISTING DUCTWORK TO APPROX. 8" ABOVE
SLAB. SEE NEW WORK PLAN FOR CONNECTION OF NEW DUCT.
6 . EXISTING DUCTWORK AND FIRE DAMPER TO REMAIN. CAP
DUCTWORK ON BOTH SIDES OF WALL AND SEAL AIR TIGHT.
PROVIDE ACCESS PANEL TO ALLOW ACCESS TO FIRE DAMPER.
7 . DUCTWORK CONTINUES ABOVE CEILING. SEE MECHANICAL DEMO
PLAN - SECTOR A
8 . EXISTING DIFFUSER MOUNTE BELOW MEZZANINE TO REMAIN. SEE
MECHNICAL DEMO MEZZANINE PLAN - ADMIN AREA FOR MORE
INFORMATION.
9 . EXISTING DUCTWORK TO REMAIN. CLEAN DUCTWORK IN
ACCORDANCE WITH DUCT CLEANING SPEC.
10 . REMOVE EXISTING OUTSIDE AIR DUCT UP TO LOCATION SHOWN.
CAP AND SEAL DUCT AIR AND WATER TIGHT.
11 . REMOVE EXISTING DUCTWORK, SUPPORTS, ETC. ROUTED BELOW
MEZZANINE.
12 . SEE MECHANICAL DEMO MEZZANINE PLAN - MEDIA AREA FOR
ITEMS REMOVED IN MEZZANINE AREA ABOVE.
13 . SEE MECHANICAL DEMO MEZZANINE PLAN - ADMIN AREA FOR
ITEMS REMOVED IN MEZZANINE AREA ABOVE.
14 . SEE MECHANICAL DEMO MEZZANINE PLAN - ART AREA FOR ITEMS
REMOVED IN MEZZANINE AREA ABOVE.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A
1/4" = 1'-0"3 MECHANICAL DEMO MEZZANINE PLAN - ADMIN AREA
1/4" = 1'-0"4 MECHANICAL DEMO MEZZANINE PLAN - MEDIA AREA
1/4" = 1'-0"2 MECHANICAL DEMO MEZZANINE PLAN - ART AREA
NOTES: (THIS SHEET ONLY)
15 . REMOVE EXISTING EXHAUST FAN MOUNTED BELOW MEZZANINE.
DUCTWORK TO REMAIN. SEE NEW WORK PLAN FOR INSTALLATION
OF NEW EXHAUST FAN.
16 . EXISTING INLINE EXHAUST FAN IN ATTIC TO REMAIN.
17 . REMOVE EXISTING ELECTRIC DUCT HEATER AT THIS
APPROXIMATE LOCATION. PATCH DUCT WHERE HEATER WAS
REMOVED.
18 . EXISTING PIPING CONTINUES TO ASSOCIATED AIR HANDLING UNIT.
FIELD VERIFY EXACT ROUTING. REMOVE ALL EXISTING PIPING.
SEE NEW WORK PLAN FOR ROUTING OF NEW PIPING IN SAME
LOCATION.
19 . REMOVE EXISTING PIPING IN CHASE. SEE NEW WORK PLAN FOR
ROUTING OF NEW PIPING IN EXISTING CHASE.
20 . EXISTING 44" X 16" RETURN DUCT IN CHASE AND ASSOCIATED
SIDEWALL RETURN GRILLE TO REMAIN. SEE NEW WORK PLAN FOR
CONNECTION OF NEW RETURN DUCT.
21 . REMOVE EXISTING OUTSIDE AIR DUCT. SEAL OPENING AIR TIGHT.
22 . EXISTING RELIEF OPENING AND FIRE DAMPER TO REMAIN.
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
2 ADDENDUM #3 06/15/22
10 10
STAGE
B116
DRY STORAGE
B104
FREEZER
B103
COOLER
B102
KITCHEN
B111
OFFICE
B108
TOILET
B106
CAN WASH
B105LOCKERS
B107
JAN
B110
SERVING
B112
GYM
B120
MECH.
B124
ELEC.
B126
STORAGE
B123
OFFICE
B122
STORAGE
B121
CORR.
B101
BOYS RR
B117
GIRLS RR
B118
CUSTODIAL
B119
CAFETORIUM
B115
DISH WASH
B114
13 13
MM
20 13
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD102
MECHANICAL DEMO PLAN -
SECTOR B
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . COMPLETELY REMOVE EXISTING CEILING HEATER, DISCONNECT,
THERMOSTAT, ASSOCIATED WIRING, ETC. REPAIR ANY DAMAGED
CEILING GRID/TILE CAUSE BY DEMOLITION. PROVIDE NEW CEILING
TILE TO MATCH EXISTING TILE WHERE CEILING HEATER WAS
REMOVED.
2 . REMOVE EXISTING ROOF MOUNTED EXHAUST FAN. SEE NEW
WORK PLAN FOR INSTALLATION OF NEW EXHAUST FAN IN SAME
LOCATION.
3 . REMOVE EXISTING PAD MOUNTED PACKAGED HEAT PUMP,
ASSOCIATED DUCTWORK, AND DUCT COVER UP TO LOCATION
SHOWN. REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT AND
STORE FOR REINSTALLATION IN NEW PACKAGED HEAT PUMP
SAME LOCATION.
4 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SEE NEW
WORK PLAN FOR INSTALLATION OF NEW PTHP IN SAME LOCATION.
5 . REMOVE EXISTING INTAKE VENTILATOR ON ROOF. EXISTING ROOF
CURB TO REMAIN. CAP EXISTING CURB AND PROVIDE SUPPORTS
AS REQUIRED FOR INSTALLATION OF NEW DUCTLESS HEAT PUMP.
SEE NEW WORK PLAN FOR INSTALLATION OF NEW DUCTLESS
HEAT PUMP ON EXISTING CURB THIS LOCATION.
6 . REMOVE EXISTING FAN COIL UNIT MOUNTED ABOVE CEILING,
ASSOCIATED DUCTWORK, SUPPORTS, PIPING, GRILLES, ETC.
REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT AND STORE
FOR REUSE IN NEW DUCTLESS FAN COIL UNIT SAME LOCATION.
EXISTING CONDENSATE PIPE TO REMAIN FOR REUSE, SEE NEW
WORK PLAN.
7 . REMOVE EXISTING HEAT PUMP MOUNTED ATOP EQUIPMENT
SUPPORT PLATFORM ON ROOF, AND ASSOCIATED PIPING.
EXISTING EQUIPMENT SUPPORT TO BE REUSED. SEE NEW WORK
PLAN FOR INSTALLATION OF NEW DUCTLESS HEAT PUMP.
8 . REMOVE EXISTING AIR HANDLING UNIT AND ASSOCIDATED PIPING
COMPLETELY. REMOVE DUCTWORK UP TO LOCATION SHOWN. SEE
SHEET M102 FOR NEW AIR HANDLING UNIT.
9 . COMPLETELY REMOVE EXISTING HEAT PUMP, ASSOCIATED
PIPING, ETC. SEE NEW WORK PLAN FOR INSTALLATION OF NEW
HEAT PUMP SAME LOCATION.
10 . REMOVE EXISTING CEILING HEATER. SEE NEW WORK PLAN FOR
INSTALLATION OF NEW CEILING HEATER.
11 . EXISTING INLINE FAN MOUNTED IN ATTIC TO REMAIN.
12 . REMOVE EXISTING ROOF MOUNTED EXHAUST FAN. EXISTING
ROOF CURB TO REMAIN. CAP EXISTING CURB AND PROVIDE
SUPPORTS AS REQUIRED FOR INSTALLATION OF NEW DUCTLESS
HEAT PUMP. SEE NEW WORK PLAN FOR INSTALLATION OF NEW
DUCTLESS HEAT PUMP ATOP EXISTING CURB THIS LOCATION.
13 . EXISTING DUCTWORK TO REMAIN. CLEAN DUCTWORK IN
ACCORDANCE WITH DUCT CLEANING SPEC.
14 . EXISTING ROOF MOUNTED EXHAUST FAN, ASSOCIATED
DUCTWORK, SUPPORTS, ETC. SERVING DISHWASHER TO REMAIN.
15 . REMOVE EXISTING DOOR AIR CURTAIN. SEE NEW WORK PLAN FOR
INSTALLATION OF NEW DOOR AIR CURTAIN SAME LOCATION.
16 . REMOVE EXISTING KITCHEN UPBLAST EXHAUST FAN ON ROOF.
SEE NEW WORK PLAN FOR INSTALLATION OF NEW FAN SAME
LOCATION.
17 . REMOVE EXISTING KITCHEN MAKE-UP AIR UNIT. SEE NEW WORK
PLAN FOR INSTALLATION OF NEW KITCHEN MAKE-UP AIR UNIT
SAME LOCATION.
18 . EXISTING LOUVER, ACTUATOR, SCREEN, ASSOCIATED DUCTWORK
AND GRILLES TO REMAIN.
19 . EXISTING MOTOR ACTUATOR TO REMAIN. MAINTAIN EXISTING
START/STOP SIGNAL FOR EXISTING LOUVER ACTUATOR MOTOR.
20 . CAP EXISTING OUTSIDE AIR DUCT AND SEAL AIR AND WATER
TIGHT.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
1 1
1 1
1 1
2 2 2
3 3 3 3
5 5 5
4TH GRADE CR
C102
4TH GRADE CR
C123
4TH GRADE CR
C122
5TH GRADE CR
C113
4TH GRADE CR
C104
4TH GRADE CR
C103
2ND GRADE CR
D102
2ND GRADE CR
D123
2ND GRADE CR
D122
2ND GRADE CR
D103
2ND GRADE CR
D104
EIP
D112
3RD GRADE CR
D111
3RD GRADE CR
D110
3RD GRADE CR
D109
3RD GRADE CR
D108
P.F.
D107
BOYS TOILET
D105
ELEC
D114
JAN
D106
VESTIBULE
D118
WORK ROOM
D119
BOOK STOR.
D120
IDF
D121
5TH GRADE CR
C109
5TH GRADE CR
C110
5TH GRADE CR
C111
5TH GRADE CR
C112
KINDERGARTEN CR
E102
KINDERGARTEN
CLASSROOM
E106
KINDERGARTEN
CLASSROOM
E131
KINDERGARTEN CR
E135
1ST GRADE CR
E121
1ST GRADE CR
E120
1ST GRADE CR
E111
MOID
E110
PID CR
E107
WORK ROOM
E128
JAN
E122
GIRLS TLT
E123
BOYS TLT
E124
VESTIBULE
E127
WOMEN
E125
MEN
E126
IDF
E130
ELEC
E129
BATHROOM
E108
KITCHEN/LAUND
E109
RECEPTION/WAITING
E116
BOOK STOR.
E117
GIRLS TLT
E118
BOYS TLT
E119
BOOK STOR.
E112
GIRLS TLT
E113
BOYS TLT
E114
RECEPTION/WAITING
E115
SPEECH CR
C108
RESOURCE CR
C107
JAN
C106
BOYS TOILET
C105
BOOK STOR.
C120
IDF
C121
WORK ROOM
C119
VESTIBULE
C118
WOMEN
C116
MEN
C117
ELEC
C114
MEN
D117
WOMEN
D116
BOYS TLT
E134
GIRLS TLT
E133
BOOK STOR.
E132
BOOK STOR.
E103
GIRLS TLT
E104
BOYS TLT
E105
CORRIDOR
E101
CORRIDOR
C101
GIRLS TOILET
C115
CORRIDOR
D101
GIRLS TOILET
D115
9 9
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
MD103
MECHANICAL DEMO PLAN -
SECTORS C, D & E
A L
IC
E C
O A
C H
M A
N E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
WBF/JA3
JA3
W
O A
K R
ID
G
E D
R A
L B
A N
Y G
A
NOTES: (THIS SHEET ONLY)
1 . REMOVE EXISTING WALL HUNG HEAT PUMP. REMOVE EXISTING
GPS BIPOLAR IONIZATION UNIT AND STORE FOR INSTALLATION IN
NEW WALL HUNG HEAT PUMP SAME LOCATION. SEE NEW WORK
PLAN.
2 . REMOVE EXISTING INLINE EXHAUST FAN MOUNTED ABOVE
CEILING. FIELD VERIFY EXACT LOCATION. REMOVE PORTION OF
DUCTWORK AS REQUIRED FOR INSTALLATION OF NEW EXHAUST
FAN IN SAME LOCATION. REPAIR / REPLACE ANY CEILING TILE OR
GRID DAMAGED DURING DEMOLITION.
3 . REMOVE EXISTING CEILING HEATER. FIELD VERIFY EXACT
LOCATION. CAREFULLY REMOVE CEILING TILE / GRID AS
REQUIRED FOR REMOVAL AND INSTALLATION OF NEW CEILING
HEATER IN SAME LOCATION. REPAIR / REPLACE CEILING TILE /
GRID DAMAGED DURING DEMOLITION.
4 . COMPLETELY REMOVE EXISTING DEHUMIDFIER IN BOOK STORAGE
ROOM.
5 . EXISTING PROPELLER FAN MOUNTED IN ATTIC TO REMAIN.
6 . REMOVE EXISTING WALL HUNG HEAT PUMP. EXISTING DUCTWORK
TO REMAIN. REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT
AND STORE FOR REINSTALLATION IN NEW WALL HUNG HEAT PUMP
SAME LOCATION.
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTORS C, D, & ENOTES: (THIS SHEET ONLY)
7 . REMOVE EXISTING WALL HUNG HEAT PUMP. EXISTING DUCTWORK
AND SIDEWALL GRILLES TO REMAIN. CLEAN GRILLES TO REMOVE
DIRT AND DEBRIS IN ACCORDANCE WITH DUCT CLEAN
SPECIFICATION. SALVAGE EXISTING GPS BIPOLAR IONIZATION
UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME
LOCATION.
8 . EXISTING EXHAUST DUCTWORK & GRILLES TO REMAIN. CLEAN
FACE OF GRILLES TO REMOVE DIRT, DUST, & DEBRIS.
9 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SEE NEW
WORK PLAN FOR INSTALLATION OF NEW PTHP IN SAME LOCATION.
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
ATS
SB
SB
ATS
1 PROVIDE A NEMA 3R 24"X24"X8" LOCKABLE LOW VOLTAGE SYSTEM CABINET FOR
MOBILE CLASSROOM SYSTEMS CABLING EXTENSION. INSTALL CABINET ON STANCHION
AT 24" ABOVE FINISHED GRADE. COORDINATE EXACT LOCATION WITH THE OWNER.
2 PROVIDE TWO (2) 3" CONDUITS WITH PULL ROPES FROM THE TELEPHONE BACKBOARD
(TEL) TO THE CABINET SPECIFIED IN NOTE 7 ABOVE. PROVIDE THE FOLLOWING CABLES
AS SPECIFIED FROM THE CABINET TO THE LOCATION INDICATED:
A. 48 PAIR INTERCOM CABLE AND 12 STRAND FIBER OPTIC CABLE IN 11/2" INNERDUCT
TO INTERCOM CABINET (MIC) THROUGH TEL.
B. 12 STRAND FIBER OPTIC CABLE TO MDF RACK.
C. 24 PAIR TELEPHONE CABLE.
PROVIDE SURGE SUPPRESSION FOR ALL COPPER CABLES ENTERING THE BUILDING.
ROUTE CABLES CONCEALED ABOVE ACCESSIBLE CEILINGS INSIDE THE BUILDING.
LEAVE MIN. 10' OF SLACK CABLES COILED AT EACH END. MAKE ALL CONNECTIONS.
3 CONTRACTOR SHALL PROVIDE AND INSTALL DATA NETWORK AND INTERCOM SYSTEM
EXTENSION INCLUDING ALL CONNECTIVITY AND ELECTRONIC EQUIPMENT TO THE
CONTRACTOR PROVIDED MODULAR CLASSROOMS. ROUTE SPECIFIED SYSTEM CABLES
FROM THE LOCKABLE LOW VOLTAGE SYSTEM CABINET TO EACH MODULAR
CLASSROOM. PROVIDE FIBER OPTIC CABLE FROM THE MODULAR CLASSROOM IDF
CORE SWITCH LOCATION TO EACH MODULAR CLASSROOM FOR DATA NETWORK
BACKBONE AND CONNECTIVITY AS SPECIFIED. PROVIDE INTERCOM SYSTEM
EXTENSION CABLES, COMPONENTS, SPEAKER, AND CONNECTIVITY TO THE MAIN
BUILDING INTERCOM SYSTEM VIA THE SPECIFIED MULTI-ZONE INTERCOM EXTENSION
PANEL. THE INTERCOM SYSTEM EXTENSION SHALL ALLOW EMERGENCY TONE
ANNUNCIATION FROM THE MAIN BUILDING INTERCOM SYSTEM. MAKE ALL
CONNECTIONS.
4 GENERAL: MODULAR CLASSROOMS ARE BEING PROVIDED BY THE CONTRACTOR PRIOR TO
THE START OF CONSTRUCTION. THE CONTRACTOR WILL REMOVE THESE CLASSROOMS
NEAR COMPLETION OF CONSTRUCTION. THE QUANTITY OF MODULAR CLASSROOM
UNITS IS SHOWN ON THIS SHEET. CONTRACTOR SHALL PROVIDE ALL POWER
SERVICE CONNECTIONS TO EACH UNIT. CONTRACTOR SHALL PROVIDE TEMPORARY
POWER SERVICE BY COORDINATING WITH THE POWER UTILITY COMPANY. OWNER SHALL PAY
ALL METER FEES AND SHALL PAY FOR UTILITY USAGE FOR ALL MODULAR UNITS FOR THE
DURATION OF THE PROJECT. PROVIDE 120/240V, 1PH, 150A SERVICE INCLUDING SECONDARY
CONDUCTORS FROM THE UTILITY COMPANY TRANSFORMERS, WEATHERHEADS, METER
SOCKETS, CONNECTION TO MODULAR CLASSROOM SERVICE PANEL, GROUNDING, RACEWAYS,
AND ETC FOR EACH MODULAR CLASSROOM.
5 GENERAL: CONTRACTOR SHALL PROVIDE AN EXIT UNIT COMBO BY LITHONIA, LHQM
LED R, OR EQUAL IN EACH MODULAR CLASSROOM. MOUNT THIS EXIT UNIT COMBO
ABOVE ONE OF THE EXIT DOORS INSIDE THE MODULAR CLASSROOMS AS SHOWN ON
THE ARCHITECTURAL DRAWINGS. CONNECT THIS UNIT TO THE UN-SWITCHED LIGHTING
CIRCUIT IN THE SPACE WITH 2#12, #12G CONDUCTORS IN 1/2" CONDUIT. MAKE ALL
CONNECTIONS. THE QUANTITY OF MODULAR CLASSROOM UNITS IS SHOWN ON THIS SHEET.
G. ALL EXISTING AUDIO- VISUAL COMPONENTS AND CABLING IN
CONFERENCE ROOMS INCLUDING THE PROJECTORS, SPEAKERS,
AUDIO ENHANCEMENT SYSTEM, TV TUNERS, AND CONNECTIVITY
SHALL REMAIN AND BE REINSTALLED. PROTECT, SECURE, AND
CLEAN THESE COMPONENTS DURING CONSTRUCTION. REINSTALL
THIS EQUIPMENT IN NEW CEILINGS AND NEW CEILING ENCLOSURES.
CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THIS
EQUIPMENT DURING CONSTRUCTION. ANY EXISTING DAMAGED
EQUIPMENT SHALL BE REPORTED TO THE ARCHITECT AND OWNER
PRIOR TO COMMENCEMENT OF WORK.
H. ALL EXISTING ELECTRICAL CIRCUITS FOR TELEPHONE, INTERCOM,
TV, SECURITY, AND VIDEO SURVEILLANCE SHALL BE MAINTAINED IN
THE OCCUPIED AREAS DURING CONSTRUCTION UNLESS NOTED
OTHERWISE.CONTRACTOR IS CAUTIONED THAT NOT ALL OF THE
EXISTING LOW VOLTAGE SYSTEM CABLING IS IN CONDUIT.
I. ALL EXISTING VIDEO SURVEILLANCE SYSTEM CAMERAS AND
RECORDER HEAD- END EQUIPMENT INCLUDING NVR, MONITORS AND
CABLES SHALL REMAIN. SECURE, PROTECT, AND RE- MOUNT
EXISTING IP VIDEO SURVEILLANCE CAMERAS IN NEW CEILING
TILES.
J. ALL EXISTING WIRELESS DATA NETWORK ACCESS POINTS SHALL
REMAIN. THIS CONTRACTOR SHALL SECURE, PROTECT, AND
REINSTALL ALL EXISTING ACCESS POINTS AND ASSOCIATED
CIRCUITRY ENTIRELY.
K. CEILING MOUNTED LIGHT FIXTURES IN THE AREAS OF MECHANICAL
EQUIPMENT DEMOLITION AND INSTALLATION SHALL BE EMPORARILY
SECURED TO STRUCTURE, PROTECTED, AND REINSTALLED IN NEW
OR EXISTING CEILINGS PER MECHANICAL DRAWINGS UNLESS
NOTED OTHERWISE. CONTRACTOR SHALL BE RESPONSIBLE FOR
ANY DAMAGE TO LIGHT FIXTURES DURING CONSTRUCTION.
(MODULAR CLASSROOMS)GENERAL NOTES:
A. SECURE ALL EXISTING INTERIOR AND EXTERIOR LIGHT FIXTURES
AND EXIT SIGNS IN THE BUILDING, INCLUDING CIRCUIT
CONDUCTORS, CONDUITS, AND SWITCHES ETC. UNLESS NOTED
OTHERWISE.
B. DISCONNECT POWER FROM ALL MECHANICAL EQUIPMENT
SHOWN ON THE DEMOLITION DRAWINGS UNLESS OTHERWISE
NOTED, INCLUDING ROOF TOP UNITS, EXHAUST FANS, WALL
HEATERS, AIR HANDLERS, WATER SOURCE HEAT PUMPS,
COOLING TOWERS, BOILERS, UNIT VENTILATORS AND ETC. ALL
ELECTRICAL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS
OTHERWISE NOTED.
C. ALL EXISTING COMPUTER DATA OUTLETS, CABLES, AND
RACEWAYS SHALL REMAIN. ALL EXISTING COMPUTER DATA
OUTLETS, CABLES, AND RACEWAYS THAT ARE ASSOCIATED
WITH THE EXISTING MDF'S AND IDF'S TO REMAIN SHALL REMAIN
UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE
RESPONSIBLE FOR THE PROTECTION OF EXISTING DATA
OUTLETS AND ALL ASSOCIATED DATA NETWORKING ELECTRONIC
EQUIPMENT DURING DEMOLITION AND RENOVATIONS OF ALL
AREAS.
D. ALL EXISTING FIRE ALARM SYSTEM DEVICES INCLUDING SMOKE
DETECTORS, HORNS, STROBES, PULL STATIONS, PANELS AND
ETC. SHALL REMAIN IN THEIR ENTIRETY UNLESS NOTED
OTHERWISE.
E. ALL EXISTING INTERCOM SYSTEM COMPONENTS INCLUDING
WALL AND CEILING SPEAKERS, HANDSETS, PUSH BUTTONS,
CLOCKS, CABLES, AND RACEWAYS SHALL REMAIN IN THEIR
ENTIRETY.
F. ALL EXISTING CEILING MOUNTED EQUIPMENT AD DEVICES FOR
VIDEO SURVEILLANCE, INTRUSION DETECTION / SECURITY, AND
WIRELESS DATA NETWORK SYSTEMS SHALL BE SECURED AND
REINSTALLED IN NEW CEILINGS PER ARCHITECTURAL DRAWINGS
UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO THIS EQUIPMENT DURING
CONSTRUCTION. ANY EXISTING DAMAGED EQUIPMENT SHALL BE
REPORTED TO THE ENGINEER AND OWNER PRIOR TO
COMMENCEMENT OF WORK. CONTRACTOR SHALL COORDINATE
AIMING OF EACH SECURITY CAMERA TOUCHED AS PART OF THIS
PROJECT WITH OWNER. DURING REINSTALLATION OWNER’S REP
SHALL VERIFY FIELD OF VIEW IS ACCEPTABLE. CONTRACTOR
SHALL NOTIFY OWNER 7 DAYS IN ADVANCE OF INSTALLATION SO
OWNER’S REPRESENTATIVES MAY BE SCHEDULED TO BE
AVAILABLE ON SITE.
(CEILING REMOVAL WORK )GENERAL NOTES:
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
E001
ELECTRICAL OVERALL PLAN
A L
IC
E
C O
A C
H M
A N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
CTS
KAB
W
O A
K R
ID
G
E D
R A
L B
A N
Y
G A
SCALE: 1/16" = 1'-0"
ELECTRICAL OVERALL PLAN
1 . APPROXIMATE LOCATION OF EXISTING FIRE ALARM PANEL (SECUTRON MODEL MR-2400)
2 . APPROXIMATE LOCATION OF EXISTING INTERCOM SYSTEM HEAD END (BOGEN MULTICOM 2000)
3 . APPROXIMATE LOCATION OF EXISTING DATA MAIN DISTRIBUTION FRAME (MDF)
4 . GENERAL: HATCHED AREAS SHOW LOCATIONS WHERE CEILING TILE AND GRID ARE BEING REMOVED FOR DEMOLITION AND REPLACEMENT OF HVAC EQUIPMENT. SEE GENERAL NOTES THIS SHEET FOR ADDITIONAL WORK.
NOTES: (THIS SHEET ONLY)
No. Description Date
1 ADDENDUM #3 6/15/22
1. CONTRACTOR SHALL REPLACE 104 EXISTING CEILING MOUNTED
INTERCOM SPEAKERS WITH NEW AS PART OF THIS PROJECT. IT IS THE
INTENT OF THE OWNER TO REPLACE ALL CEILING MOUNTED INTERCOM
SPEAKERS BUILDING WIDE WITH NEW. NEW SPEAKER PROVIDED BY THIS
CONTRACTOR SHALL BE BOGEN #ACD2X2U OR APPROVED EQUAL.
CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF DEMOLISHED
SPEAKERS AND MOUNTING HARDWARE.
GENERAL NOTES: (INTERCOM SYSTEM)
J
ATS
J
M
R
C
FACTORY INSTALLED PIGTAIL
INSUL. BUSHING (TYP)
TO 120 VAC
PROVIDE IN-WALL JUNCTION BOX
WITH STAINLESS STEEL COVER
PLATE AND HOLE FOR CABLE
BUT SPLICE
BUTT SPLICE BY DIV. 16 MADE
INSIDE IN-WALL BOX
DUPLEX OUTLET
HARD CEILING 1' X 1' REMOVABLE ACCESS
PANEL (TYPICAL)
OBTAIN STD. &
HANDICAP SINK
MTG. HEIGHT FROM
DIV. 15 " ROUGH-IN"
DRAWING
1/2"MIN, 2"MAX
BENEATH LOWER
EDGE OF SINK
1/2"C IN WALL BY DIV. 16
FOR LOW VOLTAGE
(ONE PER LAV.)
120/24 VAC XFMR
BY DIV. 15
FIELD INSTALLED
MIN.18-2 PLENUM
RATED CABLE UP
TO XFMR IIN CELL
CAVITY BY DIV.16
MAXIMUM OF 1 LAVORATORIES, TOILET
OR URINAL PER XFMR/J BOX
(PER OWNER'S REQUEST)
SCALE: NONE
TYPICAL ELECTRIC FAUCET, TOILET OR URINAL SENSOR DETAIL
ELECTRICAL LEGEND
CONVENIENCE OUTLETS
SPECIAL PURPOSE OUTLET- WALL, CEILING
DUPLEX OUTLET- WALL, CEILING
ELECTRICAL PANELS- SEE SCHEDULE AND RISERS
SIMPLEX
JUNCTION BOX- WALL, CEILING
ONE SECTION PANEL
TWO SECTION PANEL
THREE SECTION PANEL
TRANSFORMER
AUTO TRANSFER SWITCH
GENERAL EQUIPMENT
CIRCUITS
RACEWAY IN CEILING OR WALL
ONE CROSSMARK PER WIRE, 2 WIRES UNLESS SHOWN
HOMERUN - ONE ARROW PER CIRCUIT
RACEWAY UNDER FLOOR OR SLAB
EXPOSED RACEWAY
FLEXIBLE RACEWAY
CONDUIT - UP, DOWN
CABLE TRAY
MOTOR CONTROLLER
STARTER / DISCONNECT
ENCLOSED CIRCUIT BREAKER
DISCONNECT (SEE DRAWING FOR F= FUSED, NR= NON-FUSED)
PUSH BUTTON
SINGLE POLE, MOTOR RATED
CONTACTOR
RELAY
NOTE
IG = ISOLATED GROUND
GFCI = GROUND FAULT CIRCUIT INTERRUPTER
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C D E
2021191
05/20/2022
GA DOE ID #: 0299
E801
ELECTRICAL SCHEDULE AND
LEGEND
A L
IC
E
C O
A C
H M
A N
E L
E M
E N
T A
R Y
S C
H O
O L
H
V A
C
P L
U M
B
IN
G U
P G
R A
D E
S
Author
Checker
W
O A
K R
ID
G
E D
R A
L B
A N
Y
G A
No. Description Date
1 ADDENDUM #3 6/15/22
| ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210 |
| ADDENDUM NUMBER: THREE DATED: June 15, 2022 |
| CHANGES TO SPECIFICATIONS |
| CHANGES TO DRAWINGS |
| 095113 - Acoustical Panel Ceilings_06152022.pdf |
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section includes acoustical panels and exposed suspension systems for ceilings. |
| 1.3 ACTION SUBMITTALS |
| A. Product Data: For each type of product. |
| 1.4 CLOSEOUT SUBMITTALS |
| A. Maintenance Data: For finishes to include in maintenance manuals. |
| 1.5 MAINTENANCE MATERIAL SUBMITTALS |
| A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. |
| 1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2. |
| 2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1. |
| 1.6 DELIVERY, STORAGE, AND HANDLING |
| A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, tempe... |
| B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content. |
| C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way. |
| 1.7 FIELD CONDITIONS |
| A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained ... |
| B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed. Do not proceed with installation of ceilings until deficiencies hav... |
| 1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation. |
| 2. Before notifying Architect, complete the following in areas to receive ceilings: |
| a. Installation of lighting fixtures, powered for operation. |
| b. Installation, insulation, and leak and pressure testing of water piping systems. |
| c. Installation of air-duct systems. |
| d. Installation of air devices. |
| e. Installation of mechanical system control-air tubing. |
| f. Installation of ceiling support framing. |
C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.
| PART 2 - PRODUCTS |
| 2.1 PERFORMANCE REQUIREMENTS |
| A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. |
| 1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials. |
| 2. Smoke-Developed Index: 450 or less. |
| 2.2 ACOUSTICAL PANELS, GENERAL |
| A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer. |
| B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated. |
| C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type. |
| 2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS) |
| A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following: |
| 1. Armstrong World Industries, Inc. |
| 2. CertainTeed Corp. |
| 3. USG Interiors, Inc. |
| B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows: |
| 1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted. |
| 2. Pattern: E. |
| C. Color: White. |
| D. LR: Not less than 0.90. |
| E. NRC: Not less than 0.95. |
| F. Humidity/Sag Resistance: Humiguard Plus. |
| G. Edge/Joint Detail: Square edge. |
| H. Thickness: 5/8 inch. |
| I. Modular Size: 24 by 24 inches. |
| 2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS) |
| A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following: |
| 1. Armstrong World Industries, Inc.; Clean Room VL |
| 2. CertainTeed Corp.; Performa, Vinyrock |
| 3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus |
| B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows: |
| 1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile. |
| 2. Pattern: As indicated by manufacturer’s designation. |
| C. Color: White. |
| D. LR: Not less than 0.78. |
| E. CAC: Not less than 38. |
| F. Edge/Joint Detail: Square. |
| G. Thickness: 1/2 inch. |
| H. Modular Size: 24 by 24 inches. |
| 2.5 METAL SUSPENSION SYSTEMS, GENERAL |
| A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M. |
| 1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated. |
| B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements: |
| 1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper. |
| 2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire. |
| 2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings> |
| A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer: |
| 1. Armstrong World Industries, Inc. |
| 2. CertainTeed Corp. |
| 3. USG Interiors, Inc.; Subsidiary of USG Corporation |
| B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating desig... |
| 1. Structural Classification: Intermediate-duty system. |
| 2. End Condition of Cross Runners: Override (stepped) type. |
| 3. Face Design: Flat, flush. |
| 4. Cap Material: Steel cold-rolled sheet. |
| 5. Cap Finish: Painted white. |
| 2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings> |
| A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following: |
| 1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard |
| 2. CertainTeed Corp.; Classic Environmental Stab |
| 3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA |
| B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-ro... |
| 1. Structural Classification: Intermediate-duty system. |
| 2. Face Design: Flat, flush. |
| 3. Face Finish: Painted white. |
| 2.8 METAL EDGE MOLDINGS AND TRIM |
| A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: |
| 1. Armstrong World Industries, Inc. |
| 2. CertainTeed Corp. |
| 3. USG Interiors, Inc.; Subsidiary of USG Corporation. |
| B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, fi... |
| 1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated. |
| 2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member. |
| 3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly. |
| PART 3 - EXECUTION |
| 3.1 EXAMINATION |
| A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installatio... |
| B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged. |
| C. Proceed with installation only after unsatisfactory conditions have been corrected. |
| 3.2 PREPARATION |
| A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans. |
| 3.3 INSTALLATION |
| A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook." |
| B. Suspend ceiling hangers from building's structural members and as follows: |
| 1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system. |
| 2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means. |
| 3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hange... |
| 4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and... |
| 5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the ty... |
| 6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete. |
| 7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires. |
| 8. Do not attach hangers to steel deck tabs. |
| 9. Do not attach hangers to steel roof deck. Attach hangers to structural members. |
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| DRAWINGS | — | |
| Addendum 4 | — | |
| Addendum 1 | — | |
| Bid tab | — | |
| Bid Invitation | — | |
| Award Information | — | |
| Addendum 2 | — |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .