DRAWINGS

15 MB Posted

Attached to
LAMAR REESE ELEM. HVAC AND PLUMBING UPGRADES
Solicitation number
22-FAC-014
Issued by
Douglas County, Georgia

About this file

This set of construction drawings documents the HVAC and plumbing upgrade project for Lamar Reese Elementary School located at 1215 Lily Pond Road, Albany, Georgia 31701. The project involves the comprehensive replacement of heating, air conditioning, and plumbing systems throughout the facility, with work organized into six construction phases to minimize disruption to ongoing school operations. The scope includes demolition and removal of existing wall-hung heat pumps (WHHP), rooftop heat pump units (RTU), fan coil units (FCU), and associated refrigerant piping, followed by installation of new HVAC equipment including 35 wall-hung heat pumps, multiple rooftop units, ductless fan coil units, outside air units, and exhaust fans. The project also requires extensive ductwork modifications, condensate drain piping installations, and architectural modifications including new ceiling grid work and chase walls to conceal mechanical systems. The contractor is responsible for R-22 refrigerant recovery from all removed equipment, with recovered cylinders to be returned to the owner for processing. Construction sequencing allows for temporary modular classroom units to house displaced students, with a maximum of six classrooms relocated per phase.

The drawings specify detailed mechanical schedules and performance requirements for all HVAC components, including supply and exhaust fan specifications with defined CFM ratings, static pressure requirements, and motor horsepower specifications. Installation details address critical construction requirements such as condensate drain trap configurations, refrigerant piping routing through exterior walls, fire damper installations at wall and floor penetrations, and bi-polar ionization unit integration into new equipment. The project includes substantial ductwork fabrication with insulation requirements for exterior rooftop ductwork and detailed lintel installations for new duct penetrations through existing walls. Plumbing components are scheduled on separate drawings (P101-P103), and electrical work for power circuits and controls is coordinated through electrical drawings with mechanical installation responsibilities clearly delineated. The construction documents establish phased work completion requirements with attention to maintaining occupied building access, protecting existing structures, and restoring affected areas upon completion of each phase.

Text of this file

D A

D E

BLECKLEY LAURENS

CHATHAM

EFFINGHAM

IRWIN

BERRIEN

LOWNDESGRADY

SE

M

IN

OL

E

DECATUR

EARLY

MILLER

BAKER

THOMAS

BROOKS

COLQUITT

MITCHELL

COOK

TIFT

SCHLEY

TERRELL

DOUGHERTY

WEBSTER

RANDOLPH

QUITMAN

CLAY

CALHOUN

CHATTAHOOCHEE

STEWART

MARION

WILCOX

CRISP

WORTH

LEE

TURNER

DOOLY

MACON

SUMTER

HOUSTON

PULASKI

McINTOSH

PIERCE

CHARLTON

LA

NI

ER

CLINCH

ECHOLS

ATKINSON

WARE

CAMDEN

BRANTLEY

GLYNN

TOOMBS

APPLING

COFFEE

BEN HILL

TELFAIR

DAVIS

JEFF

WHEELER

DODGE

TREUTLEN

M

ON

TG

OM

ER

Y

LONG

WAYNE

LIBERTY

BULLOCH

EVANS

CANDLER

TATTNALL

BRYAN

DAWSON FRANKLIN

CLARKE

OCONEE

PUTNAM

BALDWIN

TWIGGS

HENRY

FA

YE

TT

E

PIKE

UPSON

SPALDING

M

ER

IW

ET

HER

HARRIS

MUSCOGEE

TALBOT

COWETA

HEARD

TROUP

PEACH

CRAWFORD

TAYLOR

BIBB

MONROE

LAMAR

BUTTS

JASPER

JONES

CHEROKEE

FULTON

PAULDING

HARALSON

CARROLL

DOUGLAS

BARTOWFLOYD

POLK

COBB

NEWTON

DEKALB

CL

AY

TO

N

ROCKD

AL

E

WALTON

MORGAN

GWINNETT

FORSYTH

JACKSON

HALL BANKS

BARROW

M cD

U F

F

IE

JEFFERSON

EMANUEL

WASHINGTON

WILKINSON

JOHNSON

HANCOCK

WARREN

GLASCOCK

JENKINS

SCREVEN

RICHMOND

BURKE

COLUMBIA

OGLETHORPE

WILKES

TALIAFERROGREENE

LINCOLN

ELBERT

HART

MADISON

RABUN

STEPHENS

FANNIN

PICKENS

GILMER

WHITF

IELD

GORDON

C H

AT

TO

O G

A

WALKER M

U

R R

A Y

CATOOSA

UNION

LUMPKIN

WHITE

HABERSHAM

TOWNS

BACON

DOUGHERTY

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION

T100

TITLE SHEET

2021203

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

L ily P o n d R d A lb a n y G

A

LAMAR REESE ELEMENTARY SCHOOL - HVAC

& PLUMBING UPGRADES

1215 Lily Pond Rd, Albany, GA 31701

No. Description Date

GA DOE ID#: 0199

T100 TITLE SHEET

C101 SITE PLAN

A100 CONSTRUCTION PHASING PLAN

A200 ARCHITECTURAL CEILING PLAN

A300 ARCHITECTURAL CHASE PLAN & DETAILS

MD100 MECHANICAL DEMO PLAN - OVERALL

MD101 MECHANCAL DEMO PLAN - SECTOR A

MD102 MECHANCAL DEMO PLAN - SECTOR B

MD103 MECHANCAL DEMO PLAN - SECTORS C, D, & E

M100 MECHANICAL NEW WORK PLAN - OVERALL

M101 MECHANICAL NEW WORK PLAN - SECTOR A

M102 MECHANICAL NEW WORK PLAN - SECTOR B

M103 MECHANICAL NEW WORK PLAN - SECTORS C, D, & E

M501 MECHANICAL DETAILS

M502 MECHANICAL DETAILS

M503 MECHANICAL DETAILS

M601 MECHANICAL SCHEDULES

M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES

P101 PLUMBING FLOOR PLAN - SECTOR A

P102 PLUMBING FLOOR PLAN - SECTOR B

P103 PLUMBING FLOOR PLAN - SECTORS C, D, & E

E001 ELECTRICAL OVERALL PLAN

ED101 ELECTRICAL DEMO POWER PLAN - SECTOR A

ED102 ELECTRICAL DEMO POWER PLAN - SECTOR B

ED103 ELECTRICAL DEMO POWER PLAN - SECTOR C, D, & E

E101 ELECTRICAL NEW WORK POWER PLAN - SECTOR A

E102 ELECTRICAL NEW WORK POWER PLAN - SECTOR B

E103 ELECTRICAL NEW WORK POWER PLAN - SECTORS C, D, & E

E801 ELECTRICAL SCHEDULES & LEGEND

TEMPORARY PORTABLE

CLASSROOM

TEMPORARY PORTABLE

CLASSROOM

TEMPORARY PORTABLE

CLASSROOM

SIDEWALK SIDEWALK

SIDEWALK

GENERAL NOTE: LOCATIONS OF CLASSROOM TRAILERS IS APPROXIMATE.

CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF EXISTING STORM

DRAINS, FENCING, SIDEWALKS, PLAYGROUNDS, DRIVES, ETC. AND

CAREFULLY COORDINATE PLACEMENT OF CLASSROMS TO AVOID

CONFLICT AND MAINTAIN REQUIRED CLEARANCES.

EXISTING PORTABLE

CLASSROOM TO REMAIN

EXISTING PLANTER BOXES

TO REMAIN (TYP)

TEMPORARILY REMOVE EXISTING GATE

AND PORTION OF FENCE AS REQUIRED

FOR ACCESS DURING CONSTRUCTION.

REPLACE FENCE AND GATE AT END OF

CONSTRUCTION.

1 1/2" DCW 2" DCW

2" DCW 2" DCW

D C

W

D C

W

2" D C W

1 1/2" DCW

1 1/2" DCW1 1/2" DCW

CONTRACTOR SHALL COORDINATE WITH OWNER FOR

TEMPORARY CONNECTION OF 2" DOMESTIC COLD

WATER PIPING TO EXISTING IN THIS APPROXIMATE

LOCATION BELOW GRADE.

APPROXIMATE LOCATION OF EXISTING

PLAYGROUND TO REMAIN. FIELD VERIFY

EXISTING CLEARANCES FOR REMOVAL OF

EQUIPMENT. RESTORE PLAYGROUND AREA TO

ORIGINAL CONDITION AT THE END OF

CONSTRUCTION.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

C101

SITE PLAN

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L

IL

Y

P O

N D

R D

A

L B

A N

Y

G A

1/16" = 1'-0"1 SITE PLAN

No. Description Date

PHASE 1

PHASE 1

PHASE 2 PHASE 3 PHASE 4 PHASE 5 PHASE 6

PHASE 3

PHASE 4

PHASE 5

PHASE 6

2 2

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

A100

CONSTRUCTION PHASING

PLAN

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L

IL

Y

P O

N D

R D

A

L B

A N

Y

G A

1/16" = 1'-0"1 CONSTRUCTION PHASING PLAN

NOTES: (THIS SHEET ONLY)

1 . ADJUST TEMPORARY WALLS AS REQUIRED TO MAINTAIN

SEPARATION FROM WORK AREAS AND OCCUPIED STUDENT

AREAS. ACCESS TO EXIT DOORS SHALL BE MAINTAINED AT ALL

TIMES.

2 . ADJUST TEMPORARY WALLS AS REQUIRED TO ALLOW ACCESS TO

RESTROOMS WHILE MAINTAINING SEPARATION OF WORK AREAS

FROM OCCUPIED STUDENT AREAS.

3 . PROVIDE TEMPORARY WALL (MIN 6' TALL) TO SEPARATE WORK

AREAS FROM OCCUPIED AREAS BASED ON PHASING. PROVIDE

DOORS AS REQUIRED FOR ACCESS TO WORK AREA. PROVIDE

PROTECTION FOR EXISTING FLOORING, WALLS, ETC. TO PREVENT

DAMAGE TO EXISTING ITEMS DURING INSTALLATION / REMOVAL

OF TEMPORARY WALL.

GENERAL NOTE: PRIOR TO CONSTRUCTION, CONTRACTOR SHALL COORDINATE WITH OWNER

TO REMOVE ALL PERSONAL ITEMS FROM SPACES AFFECTED BY DEMOLITION. CONTRACTOR

SHALL PROTECT EXISTING CASEWORK, FURNITURE, FLOORING, WALLS, CEILINGS, ETC. NOT

ABLE TO BE REMOVED. AT THE END OF CONSTRUCTION, CONTRACTOR SHALL REMOVE ALL

PROTECTIVE COVERS AND WIPE DOWN AND CLEAN ALL SURFACES AFFECTED BY DUST, DIRT,

CONSTRUCTION DEBRIS, ETC.

GENERAL NOTE: THERE WILL BE 3 MODULAR CLASSROOM BUILDINGS WITH (2) CLASSROOMS

PER MODULAR UNIT ON THIS SITE PROVIDED BY THE CONTRACTOR. NO MORE THAN 6

CLASSROOMS MAY BE MOVED TO MODULAR UNITS FOR EACH PHASE. PHASES SHOWN

HEREIN ARE SUGGESTED PHASES AND MAY BE CHANGED DUE TO CONSTRUCTION

TIMELINES, CONSTRUCTION SCHEDULES, EQUIPMENT LEAD TIMES, UNFORESEEN

CIRCUMSTANCES ENCOUNTERED DURING THE CONSTRUCTION PROCESS OR FURTHER

COORDINATION WITH OWNER. VERIFY ALL PHASING, TEMPORARY WALL/PARTITION

INSTALLATION AND/OR SCHEDULING PRIOR TO COMMENCEMENT OF WORK.

1 1

DEMO EXISTING CEILNG TILE & GRID AS

REQUIRED AND REPLACE WITH NEW

CEILING TILE & GRID

DEMO EXISTING CEILING TILE &

REPLACE WITH NEW CEILING TILE

CEILING HATCH LEGEND

(NO HATCH) EXISTING CEILING TILE

& GRID TO REMAIN

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

A200

ARCHITECTURAL CEILING

PLAN - OVERALL

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L

IL

Y

P O

N D

R D

A

L B

A N

Y

G A

1/16" = 1'-0"1 ARCHITECTURAL CEILING PLAN - OVERALL

NOTES: (THIS SHEET ONLY)

1 . PROVIDE NEW BORDER AROUND NEW CHASE AND INTEGRATE WITH

EXISTING CEILING GRID.

2 . REMOVE GRID AS REQUIRED FOR INSTALLATION OF NEW LINESETS,

DUCTWORK, CONDENSATE DRAINS, ETC. EXISTING GRID "MAINS" AND

BORDER TO REMAIN TO MAINTATIN EXISTING LIGHTING, SPEAKER, ETC.

LAYOUT. SEE MECHANICAL DRAWINGS FOR ALL NEW ABOVE CEILING

ITEMS.

WHHP

PROVIDE STEEL CORNER BEAD AT 90

DEG GYP. BOARD OUTSIDE CORNERS.

PROVIDE FRAMED OPENING FOR

SUPPLY DUCT AND RETURN GRILLE

AND DUCT. SEE MECHANICAL

DRAWINGS FOR EXACT SIZE.

SEE MECHANICAL DRAWINGS FOR

SUPPLY & RETURN DUCT SIZES.

EXTERIOR WALL

24" MAXIMUM

48" MAXIMUM

1 LAYER ABUSE RESISTANT 5/8" GYPSUM BOARD (ONE SIDE).

ACOUSTICAL TILE T-BAR CEILING

EXTEND WALL 0'-6" (MAXIMUM) PAST CEILING - OR AS DICTATED BY

EXITING STRUCTURAL CONDITIONS, SUPPLY DUCT, ETC.

3" BATTS INSULATION BETWEEN STUD FOR SOUND ATTENUATION.

CONTINUOUS SEALANT AT CEILING INTERFACE OF 5/8" GYP.

MTL. RUNNER - DO NOT FASTEN TO STUD.

HEAD

PLAN

BASE

OVERALL DIMENSION = 4-1/4"

'C' SHAPED MTL. STUD. DO NOT FASTEN TO RUNNER ABOVE.

FASTENERS @ 2'-0" O.C. MAX WITHIN 1" OF ENDS.

TOP OF STRUCTURAL SLAB.

CONTINUOUS SEALANT.

CONTINUOUS C'SHAPED METAL RUNNER.

BASEBOARD.

CLASSROOMCHASE

METAL STUD SIZE - 3-5/8"

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

A300

ARCHITECTURAL CHASE

PLAN & DETAILS

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L

IL

Y

P O

N D

R D

A

L B

A N

Y

G A

1/16" = 1'-0"1 ARCHITECTURAL CHASE PLAN

NOTES: (THIS SHEET ONLY)

1 . NEW CHASE TO CONCEAL WHHP DUCT. SEE ARCHITECTURAL WALL CHASE

DETAIL THIS SHEET.

NOT TO SCALE

WHHP CHASE WALL DETAIL

NOT TO SCALE

CHASE WALL DETAIL

MD103

MD101

MD102

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD100

MECHANICAL DEMO PLAN -

OVERALL

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/16" = 1'-0"1 MECHANICAL DEMO PLAN - OVERALL

MUSIC LAB

ART LAB

MEDIA CENTER

CONF. RM.

114F

AV. STOR.

114E

BOOK STOR.

114D

PRODUCTION ROOM

114C

WORK RM.

114B

MEDIA SPEC. OFFICE

114A

LOBBY

CONF. ROOM

PRINC. OFF.

TLT.

104A

TLT.

108A

ASST. PRINCIPAL

COUNSELOR

VAULT

RM.

103B

OFFICE MANAGER

CLINIC

TLT.

103A

WORK RM.

DATA ROOM

111A

COMPUTER LAB

CLOSET

STOR.

118A

KILN RM.

116A

STOR.

116B

DATA RM.

LOBBY

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD101

MECHANCAL DEMO PLAN -

SECTOR A

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A

NOTES: (THIS SHEET ONLY)

1 . REMOVE CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL

UNIT AND ASSOCIATED REFRIGERANT PIPING. REMOVE

CONDENSATE PIPING AND MAKE NOTE OF ROUTING. SEE NEW

WORK PLAN FOR INSTALLATION OF NEW CEILING MOUNTED

DUCTLESS FAN COIL UNIT IN SAME LOCATION.

2 . REMOVE EXISTING ROOF MOUNTED DUCTLESS HEAT PUMP AND

ASSOCIATED PIPING. EXISTING EQUIPMENT SUPPORT PLATFORM

TO REMAIN.

3 . REMOVE EXISTING ROOFTOP HEAT PUMP AND ASSOCIATED

CONDENSATE DRAIN. REMOVE EXISTING GPS BIPOLAR IONIZATION

UNIT AND STORE FOR REUSE IN NEW ROOFTOP HEAT PUMP.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOFTOP UNIT IN SAME LOCATION.

4 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOF MOUNTED EXHAUST FAN.

5 . EXISTING ROOFTOP UNIT, DRAIN, ETC. TO REMAIN.

6 GENERAL: UNLESS OTHERWISE NOTED, ALL DUCTWORK, GRILLES,

DIFFUSERS, ETC ARE TO REMAIN. CLEAN EXISTING DUCTWORK AS

SPECIFIED. CLEAN ALL DIFFUSERS AND GRILLES TO REMOVE ALL

DUST, DIRT, SMUDGES, ETC.

7 GENERAL: CONTRACTOR SHALL REMOVE ALL EXISTING BIPOLAR

IONIZATION UNITS IN EXISTING EQUIPMENT FOR REINSTALLATION

IN NEW EQUIPMENT. ALL BIPOLAR IONIZATION UNITS NOT REUSED

SHALL BE TURNED OVER TO THE OWNER.

8 . EXISTING POWER CIRCUIT FOR RTU/CONVENIENCE OUTLET RISES

THROUGH EXISTING PITCH POCKET. SEE ELECTRICAL DRAWINGS

FOR REMOVAL OF POWER CIRCUIT TO BELOW ROOF DECK, AND

JUNCTIONING BELOW ROOF LEVEL AND ROUTING CIRCUIT UP

INSIDE ROOF CURB ADAPTER OF NEW EQUIPMENT. FILL PITCH

POCKET FOLLOWING POWER CIRCUIT REMOVAL. PROVIDE 18

GAUGE METAL CAP TO COVER EXISTING PITCH POCKET. SEAL AIR

& WATER TIGHT.

No. Description Date

GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF

WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL

UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING

WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).

CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT

REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY

CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS

HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR

PROCESSING.

CAFETERIA

SERVING

KITCHEN

OFFICE

JAN.

LAUNDRY

TLT.

132A

LOCKER

DRY STOR.

STOR.

MECH.

113A

MEN

115A

MECH.

100A

OFF.

STOR.

150A

STOR.

100C

ELECT.

100B

STOR.

112A

P.E. FACILITY

LIFT

122B

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD102

MECHANCAL DEMO PLAN -

SECTOR B

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B

NOTES: (THIS SHEET ONLY)

1 . REMOVE CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL

UNIT AND ASSOCIATED REFRIGERANT PIPING. REMOVE

CONDENSATE PIPING AND MAKE NOTE OF ROUTING. SEE NEW

WORK PLAN FOR INSTALLATION OF NEW CEILING MOUNTED

DUCTLESS FAN COIL UNIT IN SAME LOCATION.

2 . REMOVE EXISTING ROOF MOUNTED DUCTLESS HEAT PUMP AND

ASSOCIATED PIPING. EXISTING EQUIPMENT SUPPORT PLATFORM

TO REMAIN.

3 . REMOVE EXISTING ROOFTOP HEAT PUMP AND ASSOCIATED

CONDENSATE DRAIN. REMOVE EXISTING GPS BIPOLAR IONIZATION

UNIT AND STORE FOR REUSE IN NEW ROOFTOP HEAT PUMP.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOFTOP UNIT IN SAME LOCATION.

4 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOF MOUNTED EXHAUST FAN.

5 . REMOVE EXISTING DUCTLESS HEAT PUMP MOUNTED ON

CONCRETE PAD, ASSOCIATED PIPING, ETC. SEE NEW WORK PLAN

FOR INSTALLATION OF NEW DUCTLESS HEAT PUMP TO REUSE

EXISTING PIPE ROUTING.

6 . COMPLETELY REMOVE EXISTING LOUVER AND ASSOCIATED DUCT

ABOVE LOW ROOF. SEE NEW WORK PLAN FOR REUSE OF

EXISTING OPENING. TEMPORARILY SEAL OPENINGS DURING

CONSTRUCTION AS REQUIRED TO PREVENT AIR & WATER

INFILTRATION.

7 . COMPLETELY REMOVE EXISTING SUSPENDED AIR HANDLING UNIT,

ASSOCIATED SUPPORTS, CONDENSATE PIPING, REFRIGERANT

PIPING, ETC.

8 . COMPLETELY REMOVE EXISTING CONCRETE PAD MOUNTED HEAT

PUMPS, ASSOCIATED PIPING, ETC. PATCH PIPING PENETRATIONS

TO MATCH EXISTING BRICK EXTERIOR.

9 . COMPLETELY REMOVE EXISTING DUCTWORK, SUPPORT,

INSULATION, ETC. UP TO LOCATION SHOWN.

10 . COMPLETELY REMOVE EXISTING REFRIGERANT PIPING,

CONDENSATE PIPING, SUPPORTS, INSULATION, ETC. SERVING AIR

HANDLING UNITS.

11 . REMOVE EXISTING KITCHEN HOOD EXHAUST FAN MOUNTED ON

ROOF. SEE NEW WORK PLAN FOR INSTALLATION OF NEW

EXHAUST FAN SAME LOCATION.

12 . EXISTING KITCHEN HOOD SUPPLY FAN ABOVE COOLER / FREEZER.

REMOVE A SHORT PORTION OF DUCT AS REQUIRED TO REMOVE

EXHAUST FAN. SEE NEW WORK PLAN FOR INSTALLATION OF NEW

EXHAUST FAN SAME LOCATION.

13 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.

14 . REMOVE EXISTING INLINE EXHAUST FAN MOUNTED ABOVE

CEILING AT THIS APPROXIMATE LOCATION. SEE NEW WORK PLAN

FOR INSTALLATION OF NEW EXHAUST FAN SAME LOCATION.

15 . REMOVE EXISITNG SUPPLY DUCTWORK AS REQUIRED FOR

REMOVAL OF AIR HANDLER. REMAINDER OF EXISTING SUPPLY

DUCTWORK TO REMAIN. SEE NEW WORK PLAN FOR CONNECTION

OF NEW DUCTWORK TO EXISTING DUCTWORK AT THIS LOCATION.

16 . GENERAL: UNLESS OTHERWISE NOTED, ALL DUCTWORK, GRILLES,

DIFFUSERS, ETC ARE TO REMAIN. CLEAN EXISTING DUCTWORK AS

SPECIFIED. CLEAN ALL DIFFUSERS AND GRILLES TO REMOVE ALL

DUST, DIRT, SMUDGES, ETC.

17 . GENERAL: CONTRACTOR SHALL SALVAGE ALL EXISTING BIPOLAR

IONIZATION UNITS IN EXISTING EQUIPMENT FOR REINSTALLATION

IN NEW EQUIPMENT. ALL BIPOLAR IONIZATION UNITS NOT REUSED

SHALL BE TURNED OVER TO THE OWNER.

18 . REMOVE EXISTING DOOR AIR CURTAIN, SEE NEW WORK PLAN FOR

NEW DOOR AIR CURTAIN IN SAME LOCATION.

19 . REMOVE EXISTING FENCING AS REQUIRED FOR INSTALLATION OF

NEW DUCTLESS HEAT PUMPS. SEE NEW WORK PLAN.

20 . EXISTING POWER CIRCUIT FOR RTU/CONVENIENCE OUTLET RISES

THROUGH EXISTING PITCH POCKET. SEE ELECTRICAL DRAWINGS

FOR REMOVAL OF POWER CIRCUIT TO BELOW ROOF DECK, AND

JUNCTIONING BELOW ROOF LEVEL AND ROUTING CIRCUIT UP

INSIDE ROOF CURB ADAPTER OF NEW EQUIPMENT. FILL PITCH

POCKET FOLLOWING POWER CIRCUIT REMOVAL. PROVIDE 18

GAUGE METAL CAP TO COVER EXISTING PITCH POCKET. SEAL AIR

& WATER TIGHT.

No. Description Date

GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF

WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL

UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING

WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).

CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT

REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY

CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS

1 1

TT TT

TTTT

TT

TT

TT

TT

TT

TT TT

TT TT

TT

TT TT

TT

TTTT

TT TT

TTTT

TTTT

TT TT

TT

TT

TT

TT

TT TT

TT

TT

4 4 4 4

4 4

4 4

3 3

6 6

8 8

F.D./S.D. F.D./S.D.

F.D./S.D. F.D./S.D.

F.D./S.D. F.D./S.D.

F.D./S.D.

F.D./S.D.

F.D./S.D.

F.D./S.D. F.D./S.D. F.D./S.D.

9 9

9 9

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

SPECIAL ED.

SPECIAL ED.

TITLE ONE

CLASSROOM

TLT.

205A

TLT.

205B

WORK ROOM

BOOK STOR.

2-3 CLASSROOM

2-3 CLASSROOM

TITLE ONE

CLASSROOM

TITLE ONE

CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

SPECIAL EDUCATION

WORK RM.

BOOK STOR.

SPECIAL EDUCATION

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

ELECT.

TLT.

210A

TLT.

210B

TLT.

211A

TLT.

209A

TLT.

213A

TLT.

213B

TLT.

214A

TLT.

214B

STOR.

TLT.

201A

TLT.

201B

TLT.

202A

TLT.

202B

GIRLS

306B

WORK RM.

BOOK STOR.

ELECT.

STOR.

BOYS

306A

TLT.

310B

TLT.

310A

JAN.

ELEC.

STOR.

TLT.

405C

TLT

405B

KITCHEN

405A

JAN.

TLT.

410A

TLT.

410B

GIRLS

406B

BOYS

406A

CORRIDOR

CORRIDOR

CORRIDOR

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD103

MECHANCAL DEMO PLAN -

SECTORS C, D, & E

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTORS C, D, & E

NOTES: (THIS SHEET ONLY)

1 . REMOVE EXISTING WALL HUNG HEAT PUMP. REMOVE EXISTING

GPS BIPOLAR IONIZATION UNIT AND STORE FOR REUSE IN NEW

WALL HUNG HEAT PUMP.

2 . EXISTING 4"Ø DRYER WALL CAP TO REMAIN.

3 . EXISTING 8" X 6" EXHAUST WALL CAP TO REMAIN.

4 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND

ASSOCIATED DUCTWORK UP TO LOCATION SHOWN. SEE NEW

WORK PLAN FOR INSTALLATION OF NEW EXHAUST FAN SAME

LOCATION.

5 . EXISTING PROPELLER EXHAUST FAN IN ATTIC TO REMAIN.

6 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

SEE NEW WORK PLAN FOR INSTALLATION OF NEW EXHAUST FAN

SAME LOCATION.

7 . REMOVE EXISTING HORIZONTAL FAN COIL UNIT, ASSOCIATED

REFRIGERANT PIPING, CONDENSATE PIPING, ETC. MOUNTED ON

PLATFORM IN ATTIC. NOTE EXISTING REFRIGERANT PIPE AND

CONDENSATE PIPE ROUTING, EXISTING PIPE ROUTINGS TO BE

REUSED. SEE NEW WORK PLAN FOR INSTALLTION OF NEW FAN

COIL UNIT SAME LOCATION. FIELD VERIFY INSTALLATION OF

EXISTING BIPOLAR IONIZATION UNIT AND REMOVE AND STORE

FOR REUSE IN NEW FAN COIL UNIT.

8 . REMOVE EXISTING PAD MOUNTED HEAT PUMP AND ASSOCIATED

PIPING. SEE NEW WORK PLAN FOR INSTALLATION OF NEW HEAT

PUMP IN SAME LOCATION.

9 . EXISTING 16" X 14" FIRE/SMOKE DAMPER IN ATTIC PARTITION TO

REMAIN.

No. Description Date

GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF

WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL

UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING

WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).

CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT

REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY

CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS

M103

M101

M102

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

M100

MECHANICAL NEW WORK

PLAN - OVERALL

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/16" = 1'-0"1 MECHANICAL NEW WORK PLAN - OVERALL

RTU-1

RTU-2

RTU-4

RTU-9 RTU-10

DFCU-3

DHP-3

DHP-1

DFCU-1

EF-25

EF-26

OAU-2

OAU-3

EF-37

RTU-5

RTU-6

RTU-7

RTU-8

MUSIC LAB

118ART LAB

MEDIA CENTER

CONF. RM.

114F

AV. STOR.

114E

BOOK STOR.

114D

PRODUCTION ROOM

114C

WORK RM.

114B

MEDIA SPEC. OFFICE

114A

LOBBY

CONF. ROOM

PRINC. OFF.

TLT.

104A

ASST. PRINCIPAL

COUNSELOR

RM.

103B

OFFICE MANAGER

CLINIC

WORK RM.

DATA ROOM

111A

COMPUTER LAB

CLOSET

STOR.

118A

KILN RM.

116A

STOR.

116B

DATA RM.

LOBBY

CC

CC

SS

16"x16"

16"x16"16"x18"

8 8

RTU-3

S S S

R

OAU-1

260 260

260 260

D

D D

D

D

D

D D

D

D

335 335

335 335 330

D

D

D

D

OAU-1

D

6 6 6

R

D

D

12 12

NOTES: (THIS SHEET ONLY)

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

M101

MECHANICAL NEW WORK

PLAN - SECTOR A

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR A

1 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO

TRANSITION FROM NEW UNIT CONNECTIONS TO EXISTING DUCT

LAYOUT. REINSTALL BIPOLAR IONIZATION UNIT REMOVED DURING

DEMOLITION. SEE BIPOLAR IONIZATION UNIT DETAIL.

2 . NEW CENTRIFUGAL EXHAUST FAN MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO MAKE

TRANSITION FROM NEW FAN CONNECTION TO EXISTING DUCT

DIMENSION.

3 . DUCTLESS HEAT PUMP MOUNTED ATOP EXISTING EQUIPMENT

SUPPORT PLATFORM ON ROOF. PROVIDE NEW CAP AT EXISTING

CURB AND NEW PIPE BOX FOR ROUTING OF PIPING AND CONDUIT.

SEE DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL.

4 . NEW CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL

UNIT. ROUTE CONDENSATE TO SAME LOCATION AS CASSETTE

REMOVED DURING DEMOLITION. REPAIR CEILING GRID / TILE

DAMAGED DURING DEMOLITION TO MATCH EXISTING.

REFRIGERANT PIPING ROUTED FROM FAN COIL UNIT UP THROUGH

PIPE BOX TO DUCTLESS HEAT PUMP ON ROOF.

5 . EXISTING RTAC, DUCTWORK, GRILLES, ETC. TO REMAIN. CLEAN

DUCTWORK IN ACCORDANCE WITH DUCT CLEANING SPEC.

6 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC

CONDENSATE DRAIN PIPING FROM RTAC TO ROOF DRAIN AS

SHOWN. PROVIDE PIPE SUPPORTS ON MAXIMUM 6' CENTERS. SEE

CONDENSATE DRAIN TRAP DETAIL AND CONDENSATE PIPE

SUPPORT ON ROOF DETAIL.

7 . NEW HORIZONTAL DISCHARGE 100% OUTSIDE AIR UNIT MOUNTED

ATOP ROOF CURB. PROVIDE JOIST REINFORCEMENT AT JOISTS

BELOW NEW OUTSIDE AIR UNIT. SEE ROOF CURB DETAIL- CURB

ATOP EXISTING ROOF, AND JOIST REINFORCEMENT DETAIL.

8 . 16" X 16" 100% OUTSIDE AIR DUCT PENETRATES EXTERIOR WALL

AND CONTINUES TO ABOVE CLASSROOM CEILING. SEE SHEET

M103 SECTOR C FOR CONTINUATION. DUCTWORK ROUTED

OUTDOORS SHALL HAVE ONE LAYER OF 2" THICK ARMAFLEX

CLOSED CELL ELASTOMERIC INSULATION ON EXTERIOR OF DUCT.

COVER INSULATION WITH EMBOSSED ALUMINUM COVER. PROVIDE

AN ADDITIONAL SHEET METAL COVER OVER

DUCTWORK/INSULATION ASSEMBLY TO COMPLETELY ENCLOSE

DUCTWORK. SEE ROOF MOUNTED EXTERIOR METAL DUCT HOOD

DETAIL.

9 . CONDENSATE DRAIN CONTINUES TO ROOF DRAIN. SEE SHEET

M102 FOR CONTINUATION.

10 . NEW CONDENSATE DRAIN PIPING ROUTED TO SAME LOCATION AS

CONDENSATE DRAIN PIPE REMOVED DURING DEMOLITION. FIELD

VERIFY EXISTING PIPE ROUTING.

11 . REFRIGERANT PIPING ROUTED DOWN THRU PIPE BOX. SEE

DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL AND PIPE

BOX/HOOD ASSEMBLY DETAIL.

12 . DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY

ELECTRICAL. INSTALLED BY MECHANICAL.

No. Description Date

GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS

THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.

RTU-15

RTU-16

RTU-14

DHP-2

DFCU-2

DHP-4

DFCU-4

RTU-13

EF-27

EF-32

EF-30

EF-33

D D

D

D

D

D

D

D

CAFETERIA

SERVING

KITCHEN

OFFICE

JAN.

LAUNDRY

TLT.

132A

LOCKER

DRY STOR.

STOR.

MECH.

113A

MEN

115A

MECH.

100A

OFF.

STOR.

150A

STOR.

100C

ELECT.

100B

STOR.

112A

P.E. FACILITY

LIFT

122B

RTU-17

"ø

"ø

"ø

"ø

26"x32"

26"x32"

26"x32"

26"x32"

56"x30"

EF-31

CORRIDOR

WOMEN

115B

SF-1

DHP-5

DHP-6

DFCU-5

DFCU-6

TT

CC

TT

RTU-12

RTU-11

DAC-1

56"x30"

1 1/2" D

D

D

R

R(TYP)

D

R

R

1 1/2" D

S

S

S

D

D

R

D

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

M102

MECHANICAL NEW WORK

PLAN - SECTOR B

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR B

NOTES: (THIS SHEET ONLY)

1 . NEW DUCTWORK OF INDICATED SIZE PENETRATES EXTERIOR

WALL AT EXISTING OPENING LOCATION. FIELD VERIFY EXACT

DIMENSIONS OF OPENING.

2 . NEW EXPOSED ROUND SPIRAL DUCTWORK CONNECTS TO

EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PAINT

DUCTWORK, SUPPORTS, ETC. TO MATCH EXISTING.

3 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO

TRANSITION FROM NEW UNIT CONNECTIONS TO EXISTING DUCT

LAYOUT. REINSTALL BIPOLAR IONIZATION UNIT REMOVED DURING

DEMOLITION. SEE BIPOLAR IONIZATION UNIT DETAIL.

4 . EXISTING ROOF DRAIN AT THIS APPROXIMATE LOCATION.

7 . DUCTLESS HEAT PUMP MOUNTED ATOP EXISTING EQUIPMENT

SUPPORT PLATFORM ON ROOF. PROVIDE NEW CAP AT EXISTING

CURB AND NEW PIPE BOX FOR ROUTING OF PIPING AND CONDUIT.

SEE DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL.

8 . CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL UNIT.

9 . NEW DUCTLESS HEAT PUMP MOUNTED ON EXISTING CONCRETE

EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL.

10 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC

CONDENSATE DRAIN PIPING FROM RTAC TO ROOF DRAIN AS

SHOWN. BASIS OF DESIGN CONDENSATE DRAIN CONNECTION IS IN

A DIFFICULT TO ACCESS LOCATION, INSTALL TRAP IN AN

ACCESSIBLE LOCATION AS SHOWN. ENSURE DRAIN PIPING DOES

NOT BLOCK ACCESS PANELS. SEE CONDENSATE DRAIN TRAP

DETAIL AND CONDENSATE ROOF SUPPORT DETAIL.

11 . INSTALL CONDENSATE P-TRAP AT THIS LOCATION.

12 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC

CONDENSATE DRAIN PIPING FROM RTAC TO ROOF DRAIN AS

SHOWN. SEE CONDENSATE DRAIN TRAP DETAIL AND

CONDENSATE ROOF SUPPORT DETAIL.

13 . DUCT PENETRATES EXTERIOR WALL 56" X 30", TRANSITIONS IN

ELBOW TO 56" X 16", RISES TO ABOVE BOTTOM OF STRUCTUAL

TRUSS AND IS ROUTED AS SHOWN. PROVIDE TRANSITIONS &

OFFSETS AS REQUIRED TO AVOID CONFLICTS WITH STRUCTURAL

MEMBERS.

14 . COORDINATE DUCT ROUTING WITH EXISTING STRUCTURAL

FRAMING AND BASKETBALL GOAL SUPPORTS.

15 . NEW DUCTLESS CASSETTE MOUNTED IN CEILING. MODIFY

EXISTING CEILING GRID AS REQUIRED TO INSTALL NEW DUCTLESS

FAN COIL UNIT. BLANK OFF SUPPLY LOUVER FACING KITCHEN

HOOD TO ENSURE DFCU AIRFLOW DOES NOT AFFECT KITCHEN

HOOD.

16 . NEW SUPPLY FAN MOUNTED ABOVE COOLER/FREEZER. FIELD

VERIFY EXISTING LOCATION, SUPPLY, & RETURN CONNECTIONS.

PROVIDE FITTINGS / TRANSITIONS AS REQUIRED TO MAKE A

SMOOTH TRANSITION FROM NEW FAN CONNECTIONS TO EXISTING

DUCTWORK.

17 . NEW DOOR AIR CURTAIN MOUNTED IN SAME LOCATION AS DOOR

AIR CURTAIN REMOVED DURING DEMOLITION. FIELD VERIFY

EXISTNG DOOR DIMENSIONS.

18 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ON ROOF. PROVIDE

JOIST REINFORCEMENT AT BAR JOISTS BELOW RTU. SEE ROOF

CURB DETAIL - NEW CURB ON EXISTING ROOF AND JOIST

REINFORCEMENT DETAIL.

19 . NEW DUCTLESS HEAT PUMP MOUNTED ON NEW CONCRETE

EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL.

20 . EXTEND EXISTING CONCRETE EQUIPMENT PAD FOR NEW

DUCTLESS HEAT PUMPS. SEE CONCRETE EQUIPMENT PAD DETAIL.

FIELD VERIFY EXISTING FENCING HEIGHT AND DISTANCE FROM

BUILDING. MODIFY AMD EXTEND EXISTING FENCING AS SHOWN TO

INCLUDE NEW DUCTLESS HEAT PUMPS.

21 . DUCTWORK ROUTED EXPOSED ON ROOF. CAREFULLY

COORDINATE ROUTING WITH EXISTING PLUMBING VENT STACKS,

FLUES, ETC. DUCTWORK ROUTED OUTDOORS SHALL HAVE ONE

LAYER OF 2" THICK ARMAFLEX CLOSED CELL ELASTOMERIC

INSULATION ON EXTERIOR OF DUCT. COVER INSULATION WITH

EMBOSSED ALUMINUM COVER. PROVIDE NON-PENETRATING DUCT

SUPPORTS ON MAXIMUM 4' CENTERS TO SUPPORT DUCTWORK ON

ROOF. SEE NON-PENETRATING DUCT SUPPORT DETAIL. COVER

SUPPLY AND RETURN DUCT INDIVIDUALLY WITH SHEET METAL

COVERS. SEE ROOF MOUNTED EXTERIOR METAL DUCT HOOD

22 . REFRIGERANT PIPING RISES UP EXTERIOR WALL AND

PENETRATES BUILDING AT EXISTING PIPING PENETRATION

ELEVATION. PROVIDE COVER FOR REFRIGERANT PIPING AND

PAINT TO MATCH EXISTING BUILDING.

23 . CONDENSATE PIPE CONTINUES TO EXISTING CONDENSATE

TERMINATION. FIELD VERIFY EXACT LOCATION.

24 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO

TRANSITION FROM NEW UNIT CONNECTIONS TO EXISTING DUCT

LAYOUT. COORDINATE DUCT CURB TO PREVENT INTERFERENCE

WITH ADJACENT ROOF SOFFIT & EXTERIOR WALL. REINSTALL

BIPOLAR IONIZATION UNIT REMOVED DURING DEMOLITION. SEE

BIPOLAR IONIZATION UNIT DETAIL.

25 . NEW CENTRIFUGAL EXHAUST FAN MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO MAKE

TRANSITION FROM NEW FAN CONNECTION TO EXISTING DUCT

DIMENSION.

26 . CAREFULLY COORDINATE ROOFTOP PLACEMENT TO MAINTAIN

MINIMUM 10' FROM OUTSIDE AIR INTAKE TO EXISTING WATER

HEATER FLUE.

27 . PROVIDE NON-PENETRATING KEEGUARD CONTRACTOR ROOFTOP

GUARDRAIL OR PRIOR APPROVED EQUAL AROUND EDGE OF

ROOFTOP UNIT TO ALLOW FOR MAINTENANCE.

28 . NEW CONDENSATE DRAIN PIPING ROUTED TO SAME LOCATION AS

CONDENSATE DRAIN PIPE REMOVED DURING DEMOLITION. FIELD

VERIFY EXISTING PIPE ROUTING.

29 . REFRIGERANT PIPING ROUTED DOWN THRU PIPE BOX. SEE

DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL AND PIPE

BOX/HOOD ASSEMBLY DETAIL.

30 . DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY

ELECTRICAL. INSTALLED BY MECHANICAL.

No. Description Date

TT

TT

TT

4 4 4 4

4 4

4 4

F.D./S.D.

F.D./S.D. F.D./S.D. F.D./S.D.

F.D./S.D.F.D./S.D.

F.D./S.D. F.D./S.D.

F.D./S.D.

F.D./S.D.

F.D./S.D. F.D./S.D.

WHHP-1

WHHP-2

WHHP-3

WHHP-4

WHHP-5

WHHP-6

WHHP-7

WHHP-8

WHHP-9

WHHP-10

WHHP-11

WHHP-12

WHHP-14

WHHP-15 WHHP-23

WHHP-24 WHHP-25

WHHP-26

WHHP-27

WHHP-28

WHHP-22

WHHP-21

WHHP-29

WHHP-20

WHHP-30

WHHP-19

WHHP-17

WHHP-16

WHHP-18

WHHP-31

WHHP-32

WHHP-33

WHHP-34

WHHP-35

EF-1 EF-2 EF-13 EF-14

EF-3

EF-4

EF-11 EF-12

EF-6EF-5

EF-8EF-7 EF-10 EF-9

EF-15 EF-16

EF-22

FCU-1

HP-1

EF-23

EF-17

EF-21 EF-20

FCU-2

EF-18

EF-19

EF-24

F.D.

F.D.

F.D.

F.D.

F.D.

F.D.

EF-34 EF-35 EF-36

ø6" ø6" ø6"ø6" ø6" ø6" ø6" ø6" ø6" ø6" ø6" ø6" ø6" ø6" ø6"

"x

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"x

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

A2

A2

A2

A2

A2

A2

A1

A1

A1

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

250 A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

A3

14"x14" 8"x14"

10"ø 10"ø

10"ø 10"ø

14"x14" 8"x14"

10"ø 10"ø

10"ø 10"ø

14"x14" 8"x14"

10"ø 10"ø

10"ø 10"ø

14"x14" 8"x14"

10"ø 10"ø

10"ø 10"ø

14"x14" 8"x14"

10"ø 10"ø

10"ø 10"ø

14"x14" 8"x14"

10"ø 10"ø

10"ø 10"ø

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10" ø6" ø6" ø6" ø6"

8"ø

8"ø8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

WHHP-13

30"x10"

30"x10"

30"x10"

30"x10"

30"x10"

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

275A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

8"x14"

10"ø 10"ø

10"ø 10"ø

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

A3

A3

A3

A3

10"ø 10"ø

10"ø 10"ø

14"x14"

8"x14"

30"x10"

14"x14"

14"x14"

14"x14"

14"x14"

14"x14"

14"x14"

14"x14"

14"x14"

14"x14"

8"ø 8"ø

8"ø 8"ø

C1

C1

C1

C1

C1

C1 C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1

C1 C1

C1

C1

C1

C1

8"ø

8"ø

8"ø 8"ø

8"ø

8"ø

8"ø 8"ø

8"ø 8"ø

"x

8"ø

28"x8" 12"x14"

8"x14" ø10" 10"ø

A3

A3

A1

10"ø

10"ø

A3

A3

10"ø

10"ø

10"ø

A3

A3

10"ø

28"x8"

14"x14"

28"x8"

14"x14"

10"ø

28"x8"

14"x14" 10"ø 10"ø

A3

A3

A3

A1

6"ø

6"ø

A1

6"ø

A1

A3

A3

A1

12"x14"

8"x14"

10"ø 10"ø

28"x8"

6"ø

A1

C1

C1

C1

C1

C1 ø6" ø6" ø6"

A3

A3

6"ø

6"ø

A1

6"ø

6"ø

A1

6"ø

A1

6"ø

6"ø

A1

A1

6"ø

A1

6"ø

6"ø A1

6"ø

A1

A1

6"ø

A1

6"ø

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

SPECIAL ED.

SPECIAL ED.

TITLE ONE

CLASSROOM

K-1 CLASSROOM

TLT.

205A

TLT.

205B

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

WORK ROOM

BOOK STOR.

2-3 CLASSROOM

2-3 CLASSROOM

TITLE ONE

CLASSROOM

TITLE ONE

CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

SPECIAL EDUCATION

WORK RM.

410BOOK STOR.

SPECIAL EDUCATION

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

ELECT.

TLT.

210A

TLT.

210B

TLT.

211A

TLT.

209A

TLT.

213A

TLT.

213B

TLT.

214A

TLT.

214B

STOR.

TLT.

201A

TLT.

201B

TLT.

202A

TLT.

202B

2-3 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

GIRLS

306B

WORK RM.

BOOK STOR.

ELECT.

STOR.

BOYS

306A

TLT.

310B

TLT.

310A

JAN.

ELEC.

STOR.

TLT.

405C

TLT

405B

KITCHEN

405A

JAN.

TLT.

410A

TLT.

410B

GIRLS

406B

BOYS

406A

CORRIDOR

CORRIDOR

CORRIDOR

16"x16"

HP-2

MM MM MM MM

MM MM

MM

MM

MM MM

MM MM MM MM

CC MM MM

CC

MM

MM

MM MMCC

2 2

CC

TT TT

TTTT

TT

TT

TT

TT

TT

TT TT

TTTT

TTTT

TT TT

TTTT

TT

TTTT

TT

TT TT TT

TTTT

TT

TT

TTTT

TT TT

TT

10 10

16"x18"

6"ø

6"ø 6"ø

6"ø

8"ø

8"ø

8"ø 8"ø

6"ø

8"ø

8"ø

6"ø

6"ø A1

6"ø

A1

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

M103

MECHANICAL NEW WORK

PLAN - SECTORS C, D, & E

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

NOTES: (THIS SHEET ONLY)

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTORS C, D, & E

1 . NEW WALL HUNG HEAT PUMP MOUNTED IN SAME LOCATION AS

REMOVED WALL HUNG HEAT PUMP. PROVIDE CURB ADAPTER AS

REQUIRED FOR NEW INSTALLATION OF WHHP. SEE WALL HUNG

HEAT PUMP DUCTED DETAIL.

2 . DUCT ROUTED OVER FIRE RATED MEZZANINE. NO FIRE DAMPER

REQUIRED. DO NOT PENETRATE CORRIDIR FIRE RATED WALL.

3 . 6"Ø DUCT ROUTED OVER FIRE RATED MEZZANINE. DUCT ELBOWS

DOWN AND PENETRATES FIRE RATED MEZZANINE FOR

CONNECTION TO INDICATED GRILLE. PROVIDE FIRE DAMPER AT

DUCT PENETRATION OF RATED MEZZANINE. PROVIDE APPROX. 1'

OF FLEX DUCT AT DUCT CONNECTION TO GRILLE.

4 . NEW CEILING MOUNTED EXHAUST FAN. PROVIDE FLEX DUCT OF

SIZE INDICATED TO CONNECT TO EXISTING DUCTWORK. PROVIDE

FITTINGS/OFFSETS AS REQUIRED TO MAKE CONNECTION.

5 . NEW PROPELLER EXHAUST FAN MOUNTED IN ATTIC IN SAME

LOCATION AS FAN REMOVED DURING DEMOLITION.

6 . NEW ROOF MOUNTED CENTRIFUGAL EXHAUST FAN CONNECTS TO

EXISTING DUCTWORK OF SIZE INDICATED. PROVIDE FITTINGS AND

OFFSETS AS REQUIRED TO MAKE CONNECTION.

7 . NEW HORIZONTAL FAN COIL UNIT MOUNTED IN MEZZANINE SAME

LOCATION AS FAN COIL UNIT REMOVED DURING DEMOLITION.

PROVIDE DUCT TRANSITIONS/OFFSETS AS REQUIRED TO

CONNECT NEW FCU TO EXISTING DUCTWORK. ROUTE

REFRIGERANT AND CONDENSATE PIPING TO SAME LOCATION AS

REMOVED FCU.

8 . NEW HEAT PUMP MOUNTED EXISTING CONCRETE PAD. EXTEND

PAD AS REQUIRED TO MAINTAIN MINIMUM 6" BETWEEN HEAT PUMP

AND EDGE OF PAD.

9 . 100% OUTSIDE AIR DUCT ROUTED ABOVE CEILING IN ATTIC.

10 . REFRIGERANT PIPING ROUTED UP EXTERIOR WALL IN NEW

PAINT-GRIP SHEET METAL PIPE CHASE. PAINT TO MATCH EXISTING

COLOR. FIELD VERIFY EXACT LOCATION OF EXISTING PIPE CHASE.

REFRIGERANT PIPING ROUTED TO ASSOCATED FAN COIL UNIT.

FIELD VERIFY EXACT ROUTING OF EXISTING PIPING.

NOTES: (THIS SHEET ONLY - CONTINUED)

No. Description Date

MAIN ROUND TRUNK DUCT

DUCT WRAP INSULATION FOR

SUPPLY AND RETURN DUCT

OPENING IN SIDE OF RECTANGULAR SHEET METAL

DUCT SHALL BE CUT WITH DRILL-CUTTER OR TIN

SNIPS. DIAMETER OF OPENING SHALL MATCH INNER

DIAMETER OF FOAM GASKET OR DIAMETER

RECOMMENDED BY TAKEOFF MANUFACTURER

DUCT

DUCT MASTICSHEET METAL SCREWS ON 6" CENTERS

FOAM GASKET

EXTERIOR VAPOR BARRIER (ONLY) SECURED

TO FITTING WITH NYLON "ZIP STRIP" BAND

SECURE INNER DUCT TO FITTING WITH NYLON

ZIP STRIP BAND IN ADDITION TO NYLON

STRIPBAND. SEAL INNER CORE TO DUCT.

FLEXIBLE DUCTWORK

90° SADDLE TAKEOFF COLLAR DAMPER AND THERMA-SEAL

GASKET FLANGE AND DAMPER HANDLE STANDOFF, SIMILAR TO

CROWN PRODUCT MODEL #314-DSO

FOR SUPPLY/RETURN DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR

HANDLE) WITH DUCT WRAP SEALED WITH VAPOR PROOF MASTIC AND FABRIC

CLTOH TO FLEX DUCT VAPOR BARRIER (NOT SHOWN FOR CLARITY)

CEILING, BY ARCHITECTURAL

SQUARE TO ROUND TRANSITION (WHERE ELBOW CONNECTS TO SQUARE

NECK DIFFUSERS). PROVIDE ROUND TO ROUND TRANSITION WHERE GRILLE

NECK SIZE DIFFERS FROM CONNECTING DUCT SIZE (EITHER LARGER OR

SMALLER). INSULATE ON SUPPLY DUCTS.

3 GORE ADJUSTABLE ELBOW. INSULATE

ON SUPPLY DUCTS.

NYLON ZIP STRIP ON OUTER VAPOR BARRIER.

ENSURE INSULATION IS PULLED DOWN WITH

VAPOR BARRIER SO NO DUCTWORK IS

UNINSULATED.

NOTE: DETAIL IS TYPICAL FOR ALL FLEX DUCT RUNOUTS TO DIFFUSERS

STAINLESS STEEL DRAWBAND

ON INNER DUCT

FLEX DUCT

INSULATION BLANKET ON TOP

OF SUPPLY DIFFUSERS

CEILING DIFFUSER

J

POWER WIRING AND CONDUIT BY ELECTRICAL

PROVIDE "KNOCK OUT" AND GROMMET

FOR POWER CABLE

EXISTING ROOF CURB.

POWER CABLE BY ELECTRICAL

REMOVABLE ACCESS COVER FOR MOTOR

COMPARTMENT

INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT

SWITCH UNLESS SCHEDULED OTHERWISE

SEE SCHEDULE FOR DRIVE TYPE. (PROVIDE

ADJUSTABLE SHEAVE FOR ALL BELT DRIVE)

FACTORY WIRED FROM MOTOR TO

DISCONNECT SWITCH.

EXHAUST FAN

EXISTING EXHAUST DUCT UP FROM

BELOW

FACTORY INSTALLED, MINIMUM 1/2"

DIA. CONDUIT CHASE

J

POWER WIRING AND CONDUIT BY ELECTRICAL

EXISTING ROOF CURB.

POWER CABLE BY ELECTRICAL

REMOVABLE ACCESS COVER FOR MOTOR

COMPARTMENT

INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT

SWITCH UNLESS SCHEDULED OTHERWISE

SEE SCHEDULE FOR DRIVE TYPE.

FACTORY WIRED FROM MOTOR TO

DISCONNECT SWITCH.

UPBLAST EXHAUST FAN

EXISTING EXHAUST DUCT UP FROM

BELOW

FACTORY INSTALLED, MINIMUM 1/2"

DIA. CONDUIT CHASE GALVANIZED BIRD SCREEN

SECURE CURB CAP TO CURB WITH ANCHORS ON

MAXIMUM 12" CENTERS (MINIMUM 2 ANCHORS

EACH SIDE)

GRADE

WELDED WIRE MESH

AT MID DEPTH OF SLAB

6" X 6" 10/10 WWF

3000 PSI CONCRETE

1" CHAMFER

SEE SPECIFICATIONS FOR

PAD HEIGHT ABOVE

ADJACENT GRADE

2" MINIMUM

EXTERIOR CONCRETE PAD

FLOOR

1" CHAMFER

ANCHOR (TYPICAL OF 4)

INTERIOR CONCRETE PAD

WELDED WIRE MESH

AT MID DEPTH OF SLAB

6" X 6" 10/10 WWF

SEE SPECIFICATIONS FOR

PAD HEIGHT ABOVE

ADJACENT GRADE

2"

3000 PSI CONCRETE

1½"

3"

UNION

AC UNIT

DRAIN CONNECTION

DRAIN PIPE SHALL BE AT LEAST

THE SAME DIAMETER AS THE NIPPLE

ON THE DRAIN PAN CONNECTION

OPEN END NIPPLE

SEE DRAWINGS FOR

PIPE REQUIRED MATERIAL

SLOPE AS REQUIRED

IN SPECIFICATIONS

PIPE NIPPLE

6"

FRONT VIEW

4"

SIDE VIEW

V A

R

IE

S

CONDENSATE PIPE,

VERIFY SIZE (TYP)

UV - STABILIZED, EDPM ADJUSTABLE RUBBER PIPE

SUPPORT, VERIFY PIPE DIAMETER BEING SUPPORTED.

SPACED ON MAXIMUM 8 FT. CENTERS AND 24" OF

FITTINGS (ERICO CADDY PYRAMID RPSE - TYPICAL)

INSTALL CONDENSATE PIPE AT THE LOWEST

POSSIBLE ELEVATION TO REDUCE TOP

HEAVY PIPE AND TO REDUCE TIPPING OVER

BUT TO MAINTAIN SPECIFIED SLOPE.

GENERAL: THIS CONDENSATE SUPPORT SHALL BE USED WITH DRAIN ELEVATIONS ABOVE ROOF OF 7" OR LESS. CONDENSATE ELEVATIONS ABOVE 8" SHALL USE ERICO CADDY PYRAMID ST ADJUSTABLE

STRUT SUPPORT OR EQUAL BY MIRO.

OPENING IN SIDE OF RECTANGULAR

SHEET METAL DUCT SHALL BE CUT

WITH DRILL CUTTER (NOT TIN SNIPS).

DIAMETER OF OPENING SHALL MATCH

INNER DIAMTER OF FOAM GASKET.

DUCT

DUCT MASTIC

FOAM GASKET

SHEET METAL SCREWS

ON 4" CENTERSDUCT

2 3/16" DUCT WRAP INSULATION FOR SUPPLY DUCT

EXTERIOR VAPOR BARRIER (ONLY) SECURED TO

FITTING WITH NYLON "ZIP-STRIP" BAND

FLEXIBLE DUCTWORK

BELLMOUTH OR 45° FITTING WITH DAMPER

FOR SUPPLY DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR HANDLE)

WITH 2 3/16" DUCTWRAP SEALED WITH VAPOR PROOF MASTIC AND FABRIC

CLOTH TO FLEX DUCT VAPOR BARRIER (NOT SHOWN FOR CLARITY)

PROVIDE OPTIONAL EXTENDED NECK SHAFT

FOR INSULATED DUCTS TO CLEAR INSULATION THICKNESS

SECURE INNER DUCT TO FITTING WITH 1/2" STAINLESS STEEL

DRAW BAND. CONTRACTOR SHALL NOT UTILIZE NYLON "ZIP-

STRIP" BAND TO SECURE INNER DUCT TO FITTING.

DIA. -",

(SEE PLANS)

3"

DIM. + ?"

DIM. + ?"

3"

PAINT INTERIOR OF BOX MATTE BLACK.1

2 MINIMUM 26 GAUGE GALV. SHEET METAL.

4 ADAPTER MAY BE FABRICATED BY CONTRACTOR OR PROVIDED BY CROWN

PRODUCTS MODEL #666 ADAPTER OR EQUAL.

PROVIDE 1/2" DUCT LINER ON RETURN DUCT

APPLICATIONS AND NO LINER ON EXHAUST APPLICATION.

NOTES: (THIS DETAIL ONLY)

AIR

NOTE: SINGLE BI-POLAR IONIZATION UNIT SHOWN. INSTALLATION SIMILAR WHEN

MULTIPLE UNITS ARE INSTALLED IN ONE HVAC UNIT, EXCEPT 24V WIRING FROM

HVAC UNIT'S TERMINAL SIDE SHALL FEED CONTRACTOR FURNISHED TERMINAL

STRIP, WHICH SHALL THEN FEED POWER TO MULTIPLE UNITS. CONTRACTOR

FURNISHED TERMINAL STRIP SHALL BE ELECTRICALLY ISOLATED FROM THE HVAC

UNIT CASING AND ALL OTHER METAL COMPONENTS.

SECURE WITH SCREWS IN LOCATION THAT

WILL NOT DAMAGE HVAC EQUIPMENT OR

ASSOCIATED REFRIGERANT PIPE, WIRING

OR OTHER COMPONENTS

NEEDLEPOINT ELECTRODES. ENSURE UNIT IS

ORIENTED AND INSTALLED SO THAT AIR FLOW

PASSES BETWEEN ELECTRODES (INSTALL

PERPENDICULAR TO AIRFLOW). MAINTAIN

MANUFACTURER'S DISTANCE FROM NEEDLES

TO METAL SURFACE TO PREVENT ARCING.

FACTORY

FURNISHED

24VAC WIRING

BI-POLAR UNIT. SEE SCHEDULE FOR QUANTITY.

SEE ENLARGED DRAWING BELOW.

LED CONFIRMING IONIZATION OPERATION

B.A.S. CONTACTS TO ALLOW OWNER TO MONITOR STATUS.

MONITORING IS NOT INCLUDED IN THIS PROJECT.

BI-POLAR IONIZATION UNIT MOUNTED INSIDE UNIT DOWNSTREAM OF

FILTER IN SUPPLY AIRSTREAM IN LOCATION APPROVED BY HVAC

EQUIPMENT MANUFACTURER AND BI-POLAR MANUFACTURER

(FAN)

(24V POWER)

G

R

Y W

C

O

CONNECT TO FAN AND 24V POWER TERMINALS ON 24 VAC

TERMINAL STRIP IN HVAC EQUIPMENT. ADDITIONAL GENERIC

TERMINALS ARE SHOWN FOR SYMBOLIC PURPOSES AND

ACTUAL TERMINALS WILL VARY BASED ON TYPE OF

EQUIPMENT.

PROVIDE ADDITIONAL WIRING (AS REQUIRED) IF FACTORY FURNISHED

WIRING WILL NOT REACH 24VAC TERMINAL STRIP. PROVIDE WIRE NUTS

AND ELECTRICAL TAPE AT JOINT. MATCH WIRE GAUGE OF

MANUFACTURER'S WIRING.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

2021203

05/20/2022

GA DOE ID #: 0199

M501

MECHANICAL DETAILS

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

NOT TO SCALE

90° SADDLE TAP TAKEOFF FITTING DETAIL

NOT TO SCALE

CEILING GRILLE DUCT CONNECTION DETAIL

NOT TO SCALE

CENTRIFUGAL DOWN BLAST EXHAUST FAN DETAIL

NOT TO SCALE

CENTRIFUGAL UPBLAST EXHAUST FAN DETAIL (CHECK)

NOT TO SCALE

CONCRETE EQUIPMENT PAD DETAIL

NOT TO SCALE

CONDENSATE DRAIN TRAP DETAIL

NOT TO SCALE

CONDENSATE PIPE SUPPORT ON ROOF DETAIL

NOT TO SCALE

BELLMOUTH AND 45° TAKEOFF FITTING DETAIL1

NOT TO SCALE

RECTANGULAR TO ROUND FLAT ADAPTER

No. Description Date

NOT TO SCALE

COMPACT BI-POLAR IONIZATION UNIT DETAIL

PROVIDE INSULATED HOUSING WHERE SCHEDULED

DUCT

AIRFLOW

PARALLEL BLADE BACKDRAFT DAMPER

SQUARE ACCESS PANEL FOR DAMPER ACTUATOR ACCESS

ACCESS PANEL (BOTH SIDES)

MOUNTING BRACKETS (TYP)

HANGING VIBRATION ISOLATORS. SEE SPECS FOR TYPE.

THREADED ROD

SUPPLEMENTAL ANGLE IRON FRAMING

DOUBLE NUTS

DOUBLE NUTS

DUCT

MOTOR. SEE SPECS FOR TYPE.

NOTE: BELT DRIVE FAN SIMILAR, EXCEPT MOTOR

OUTISDE OF FAN CASING, AND WITH INSULATED

MOTOR COVER WHERE SPECIFIED.

DUCT MOUNTING COLLAR (TYP INLET AND OUTLET). PROVIDE

1/2" X 1/2" WELDED WIRE GALVANIZED INLET GUARD FOR

NON-DUCTED INLET APPLICATIONS AS SCHEDULED.

MAINTAIN MINIMUM 2.5 TIMES WHERE DIAMETER STRAIGHT

DUCT LENGTH AT INLET AND OUTLET OF FAN BEFORE

ELBOW, TRANSITION, DAMPER, ETC.

PROVIDE MOTORIZED DAMPER WITH INTERNAL ACTUATOR WHERE

SCHEDULED. DAMPER VOLTAGE SHALL MATCH FAN VOLTAGE.

FLEXIBLE DUCT

CONNECTION (TYP)

GALVANIZED MOTOR COVER

WHERE SCHEDULED

BACKWARD

INCLINED WHEEL

MAINTAIN MINIMUM 2.5 TIMES

WHEEL DIAMETER STRAIGHT

DUCT LENGTH AT INLET AND

OUTLET OF FAN BEFORE ELBOW,

TRANSITION, DAMPER, ETC.

FACTORY INSTALLED NEMA-1

DISCONNECT SWITCH

FACTORY WIRED FROM MOTOR

TO DISCONNECT SWITCH

WELD SIDE ANGLE CLIP TO PAN (TYP OF 4)

TO CORNERS. SUSPEND WITH 3/8"

THREADED ROD. DO NOT BLOCK ACCESS

TO CONTROLLER.

PAN SHALL BE MIN. 18 GAUGE

GALVANIZED STEEL

2"

3/4" NIPPLE WELDED

TO PAN

PIPE 3/4" PAN DRAIN TO SAME

LOCATION AS PRIMARY DRAIN.

SLOPE PAN TO THIS SIDE.

FABRICATE DRAIN PAN MINIMUM

12" LONGER AND WIDER THAN

MAIN/SUB CONTROLLER

FABRICATE DRAIN PAN MINIMUM

12" LONGER AND WIDER THAN

MAIN/SUB CONTROLLER

CAULK AROUND FULL PERIMETER OF ANGLE

EACH SIDE OF WALL.

3" X 3", 22 GAUGE SHEET METAL ANGLE

AROUND PERIMETER OF DUCT EACH SIDE

OF WALL. ANCHOR TO WALL WITH

EXPANSION ANCHOR.

DUCT WRAP INSULATION WITH FSK JACKET.

INSULATION IS CONTINUOUS THROUGH WALL

OPENING.

ELEVATION SECTION

NOTE: DETAIL IS SIMILAR FOR UNINSULATED DUCTS.

SEAL WITH VAPOR PROOF MASITC AND CLOTH FABRIC

OVERLAPPING ANGLE AND DUCT WRAP FSK JACKET TO

PREVENT PASSAGE OF SMOKE.

CAULK AROUND FULL PERIMETER OF ANGLE

EACH SIDE OF WALL.

3" X 3", 22 GAUGE SHEET METAL ANGLE AROUND

PERIMETER OF DUCT EACH SIDE OF WALL.

ANCHOR TO WALL WITH EXPANSION ANCHOR.

DUCT WRAP INSULATION WITH FSK JACKET.

INSULATION IS CONTINUOUS THROUGH

WALL OPENING.

SEAL WITH VAPOR PROOF MASTIC AND CLOTH FABRIC

OVERLAPPING ANGLE AND DUCT WRAP FSK JACKET

TO PREVENT PASSAGE OF SMOKE.

S T

Y

LE

A

S T

Y

LE

B

S T

Y

LE

C

2" MAX.

1" 1"

FOLDING BLADE STATIC RATED FIRE DAMPER

IN TYPE 'B' FRAME (EXCEPT TYPE 'A' SHALL BE

USED AT SIDEWALL REGISTERS AND NON-DUCTED

TRANSFER OPENING). DYNAMIC RATED DAMPERS

SHALL BE USED WHERE SPECIFICALLY SHOWN

ON DRAWINGS

ATTACH FIRE DAMPER TO SLEEVE IN

ACCORDANCE WITH MANUFACTUER'S

UL INSTALLATION INSTRUCTIONSFACTORY FURNISHED ROUND OR OVAL

TRANSITION WITH BLADE STACK OUT

OF AIR STREAM

ROUND AND OVAL FIRE DAMPER

INSTALLATION SIMILAR

DUCT (WHERE APPLICABLE)

SLEEVE LENGTH SHALL BE DETERMINED BY CONTRACTOR TO

BE WITHIN MINIMUM AND MAXIMUM DISTANCE FROM

WALL/FLOOR AS REQUIRED BY MANUFACTUER

NOTE: INSTALLATION SHALL CONFORM TO THE FIRE

DAMPERS MANUFACTURER'S "UL" INSTALLATION

INSTRUCTIONS

WALL OR FLOOR. CONTRACTOR SHALL VERIFY

THICKNESS RATING, AND MATERIAL OF

CONSTRUCTION FROM ARCHITECTURAL DRAWINGS,

AND USE THIS INFORMATION TO SELECT FIRE

DAMPER AND FIRE DAMPER ACCESSORIES.

PROVIDE MINIMUM OVERLAP ALL AROUND AS REQUIRED BY

MANUFACTURER'S UL INSTALLATION INSTRUCTIONS

CLEARANCE (TYPICAL) AS REQUIRED BY MANUFACTURER'S

UL INSTALLATION INSTRUCTIONS

165° FUSIBLE LINK

DUCT TO SLEEVE CONNECTION SHALL BE AN APPROVED

TYPE AS LISTED IN THE MANUFACTURER'S UL INSTALLATION

INSTRUCTIONS. PROVIDE DUCT SEALANT APPROVED BY

FIRE DAMPER MANUFACTURER.

PROVIDE ACCESS PANEL FOR RECTANGULAR DUCTS. FOR ROUND DUCTS,

DOOR SIZE SHALL BE AS NOTED IN SPECIFICATIONS. FOR FLOOR

PENETRATIONS ACCESS PANEL SHALL BE ABOVE FLOOR.

FACTORY PROVIDED SLEEVE. SLEEVE LENGTH AND GAUGE SHALL

BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH

MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.

FACTORY PROVIDED RETAINING ANGLES. ANGLE SIZE AND GAUGE

SHALL BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH

MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.

INSIDE

UNINSULATED REFRIGERANT LIQUID PIPE

REFRIGERANT PIPE DROPS

IN WALL AS REQUIRED

INSULATED REFRIGERANT

SUCTION PIPE

20 GAUGE GALVANIZED

STEEL SHEET METAL SLEEVE

TERMINATE SLEEVE

FLUSH WITH WALL

OUTSIDE

PIPE PENETRATES WALL

NEAR GRADE LEVEL

EXTERIOR PAINTABLE SILICON CAULK.

PAINT TO MATCH EXTERIOR. EXTERIOR WALL. SEE ARCHITECTURAL PLANS

FOR CONSTRUCTION

FIRE RESISTANT FOAM OF APPROPRIATE

THICKNESS TO MAINTAIN WALL'S FIRE RATING

(1" MINIMUM THICKNESS)

LIGHT

RETURN

DUCT

22 GAUGE PAINT GALV GRIP GALVANIZED FLASHING. PAINT

FLASHING TO MATCH WHHP COLOR. FLASHING SHALL EXTEND

UP 4". CAULK AND SEAL WATERTIGHT AT FLASHING OVERLAP

FLASHING OVER WHHP'S INTEGRAL VERTICAL FLASHING.

WALL HUNG HEAT PUMP (WHHP)

INTEGRAL SLOPED TOP

WALL HUNG HEAT PUMP MOUNTED TO WALL CURB PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

EXTERIOR WALL.

INTEGRAL DISCONNECT SWITCH

INTEGRAL VINYL DRAIN TUBING BY EQUIPMENT

MANUFACTURER. PVC TUBING SHALL BE

INSERTED INTO VINYL TUBING

STAINLESS STEEL HOSE CLAMP

3/4" PAINTED SCHEDULE 80 PVC DRAIN PIPE

PIPE CLAMP SECURED TO WALL

ON MAX 18" CENTERS

HEAVY DUTY STEEL RETURN GRILLE.

CONDENSATE LINE DOWN WALL TO GRADE. AT

GRADE, ELBOW PIPE AWAY FROM BUILDING

ROUTE DUCT HARD AGAINST

WALL AS POSSIBLE.

PROVIDE 1" LINER FROM UNIT CONNECTION

THRU BOTH ELBOWS. REMAINDER OF SUPPLY

DUCT SHALL BE EXTERNALLY INSULATED WITH

R-8 DUCT WRAP.

MOUNTING HEIGHT OF WHHP UNIT ABOVE GRADE / FINISHED

FLOOR VARIES. MAINTAIN MINIMUM 12" FROM BOTTOM OF

WHHP TO GRADE.

SEE

INSERT

ROUTE DUCT HARD AGAINST

WALL AS POSSIBLE.

WALL CURB TO ALLOW INSTALLATION OF NEW

WHHP IN SAME LOCATION AS EXISTING WHHP.

CAULK FULL LENGTH, BOTH SIDES AND TOP OF

UNIT. COLOR SHALL MATCH EXTERIOR WALL.

1" DUCT LINER INSIDE ALL RETURN DUCT.

PROVIDE CLOSED CELL EPDM ADHESIVE BACKED WEATHER

STRIPPING AROUND FULL PERIMETER OF UNIT PRIOR TO

MOUNTING AGAINST WALL TO SERVE AS INSECT AND

INFILTRATION BARRIER.

FILTER ACCESS PANEL

INTERNALLY MOUNTED BI-POLAR

IONIZATION UNIT

8" A.F.F. TO B.E. GRILLE

SOUND TRAP ELBOW

MAINTAIN DUCT WIDTH BUT REDUCE DEPTH

IN DROP WITH SIZE INDICATED ON PLANS.

BRICK AND BLOCK WALL

FILTER IN INTEGRAL FILTER RACK

3" X 3" X 1/4" STRUCTURAL ANGLE. PAINT EXPOSED ANGLE

WITH TWO COATS OF PANT TO MATCH BUILDING COLOR

NEW ARCHITECTURAL CHASE TO CONCEAL DUCT.

SEE ARCH DRAWINGS FOR DETAILS.

SUPPLY DUCTWORK

STEEL BAR JOIST

EXISTING INSULATION BATTS

ON CEILING.

T

DDC SUPPLY AIR

TEMPERATURE SENSOR.

CEILING

TRANSITION AS

SHOWN ON PLAN

ELECTRIC HEAT

SUPPLY

DUCT

DUCT SUPPORT KIT SHALL BE MIRO OR ERICO

SECURE DUCT TO UNISTRUT

WITH GALVANIZED SCREWS.

SEAL WATERTIGHT.

SEE PLANS FOR SIZES

ADJUSTABLE

HORIZONTAL STRUT

DUCT. SEE PLANS

FOR SIZES.

ROOFROOF

ISOMETRIC VIEW

M

IN

V A

R

IE

S

1 5/8" X 1 5/8" HOT

DIPPED GALVANIZED

UNISTRUT

16 X 18 POLYCARBONATE

BASE (TYP)

PROVIDE EXTRA EPDM OR

TPO PAD UNDER FEET OF

STANDS (TYP)

SUPPLY DUCT

INSIDE

OUTSIDE

(NOTE: SUPPLY DUCT SHOWN. RETURN DUCT IS SIMILAR)

ROOF

NON-PENETRATING DUCT

SUPPORT. SEE NON-PENETRATING

DUCT SUPPORT DETAIL.

SEE PLANS FOR DUCT SIZES

4" X 4", 22 GAUGE GALV-GRIP SHEET METAL

ANGLE AROUND FULL PERIMETER OF DUCT INSIDE.

PAINT TO MATCH EXISTING WALL COLOR.

DUCT INSIDE

CAULK PERIMETER OF DUCT

EXTERIOR DUCT SHALL BE PAINT GRIP SHEET METAL. ALL DUCTWORK,

JOINTS AND SEAMS SHALL BE TAPED OFF AND SEALED NEATLY AND

WATERTIGHT, THEN THE TAPE SHALL BE REMOVED. PAINT EXTERIOR

DUCTWORK WITH 2 COATS OF PAINT. VERIFY COLOR WITH OWNER.

22 GAUGE METAL COUNTER FLASHING FULL

WIDTH OF DUCT ANCHORED TO RTAC AND

OVERLAPPING FLANGE OF COVER

RTU / OAU

CAULK FULL WIDTH

CAULK FULL WIDTH OF FLANGE

TURN CONNECTING DUCT UPWARD WITH 2"

FLANGE ON RTAC CONNECTION. CAULK FULL

PERIMETER OF DUCT.

INTERIOR 2" THICK ARMACELL CLOSED CELL

ELASTOMERIC INSULATION. FIBERGLASS

INTERNAL DUCT LINER IS NOT ALLOWED ON THE

INTERIOR OF DUCT.

NOTE: THE DUCT ROUTING SHOWN BETWEEN THE RTAC AND THE EXTERIOR WALL IS

SYMBOLIC IN THIS DETAIL AND DOES NOT INTEND TO INDICATE ALL ELBOWS, TRANSITIONS,

OFFSETS, ETC. SEE FLOOR PLANS FOR ACTUAL ROUTING.

GROUT

1" ABOVE FLOOR; FLUSH FOR WALLS

SCHEDULE 10 (MINIMUM)

STEEL PIPE

CONDUIT OR PIPING

PIPING INSULATION AS SPECIFIED.

PIPE INSULATION SHALL BE CONTINUOUS

THRU PENETRATION.

SEAL BETWEEN SLEEVE AND PIPING WITH FIRE RESISTANT

SEALANT OF SUFFICIENT THICKNESS TO MAINTAIN WALL'S

OR FLOOR FIRE RATING (1" MINIMUM THICKNESS). IF WALL

IS NOT FIRE RATED, PROVIDE CAULKING IN LIEU OF FIRE

RESISTANT SEALANT. SEALANT IS ONLY REQUIRED ON

ONE SIDE OF WALL, UNLESS REQUIRED BY MANUFACTURER

ON BOTH SIDES.

FIBERGLASS BATTS PACKED BETWEEN SLEEVE

AND PIPE (OR PIPE INSULATION ON INSULATED PIPE)

WALL OR FLOOR. CONTRACTOR SHALL VERIFY

CONSTRUCTION TYPE (MASONRY, CONCRETE,

BRICK AND CMU, ETC.) AND THICKNESS.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

2021203

05/20/2022

GA DOE ID #: 0199

M502

MECHANICAL DETAILS

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

NOT TO SCALE

CENTRIFUGAL INLINE FAN DETAIL

NOT TO SCALE

CONDENSATE AUXILIARY DRAIN PAN DETAIL

NOT TO SCALE

DUCT PENETRATION THRU WALL DETAIL

NOT TO SCALE

FIRE DAMPER DETAIL

NOT TO SCALE

PIPE SLEEVE DETAIL - REFRIGERANT PIPE THRU EXTERIOR WALL

NOT TO SCALE

WALL HUNG AIR CONDITIONER - DUCTED SUPPLY DETAIL

NOT TO SCALE

NON-PENETRATING DUCT SUPPORT ON ROOF DETAIL

NOT TO SCALE

RTAC EXTERIOR DUCT DETAIL

NOT TO SCALE

PIPE SLEEVE DETAIL

EXISTING ROOF

RE-WORK ROOFING FOR INSTALLATION

OF NEW ROOF CURB IN ACCORDANCE WITH

ROOF MANUFACTURER'S BOND REQUIREMENTS.

C U

R B

H E

IG

H

T

EQUIPMENT

GASKET SEALER

PRESSURE

TREATED

WOOD NAILER

RIGID INSULATION

METAL ROOF CURB

LAG BOLT

PRESSURE TREATED BLOCKING

AS REQUIRED TO MATCH INSULATION

THICKNESS.

ANCHOR TO DECK

ROOF DECK TO EXTEND

BENEATH ENTIRE ROOF CURB.

FULL PERIMETER STRUCTURAL STEEL FRAMING

UNDER ROOF CURB.

EXISTING METAL DECK

5/16" X 1/2" (MINIMUM) HEX HEAD

SCREWS ON 18"…

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
Addendum 3 —