Addendum 3

4 MB Posted

Attached to
LAMAR REESE ELEM. HVAC AND PLUMBING UPGRADES
Solicitation number
22-FAC-014
Issued by
Douglas County, Georgia

About this file

Summary

This is Addendum No. 3, dated June 15, 2022, issued by Andrews, Hammock & Powell, Inc. on behalf of the Dougherty County Board of Education in Albany, Georgia, for HVAC and plumbing upgrades at Lamar Reese Elementary School. The addendum modifies the original contract documents dated May 20, 2022, and must be acknowledged by all bidders to avoid disqualification. Key changes include revised specifications for temporary modular classrooms (68' x 28' minimum) with fire alarm systems, emergency lighting, intercom speakers, ADA-accessible restrooms, HVAC equipment maintaining 70–75°F temperatures, and above-ground septic tanks with weekly pumping service. The addendum identifies two modular classroom distributors: Wilscot in Tallahassee, Florida, and Mobile Modular in Arcade, Georgia. Additional specification changes modify Section 095113 for acoustical panel ceilings and Section 234100 for particulate air filtration and bi-polar ionization units, requiring manufacturers such as Global Plasma Solutions for ionization equipment. The addendum replaces eight mechanical and electrical drawing sheets (MD101–MD103, M101–M102, M601, E001, and E801) with revised versions dated June 15, 2022, addressing mechanical demolition and new work plans across five building sectors.

The revised mechanical and electrical drawings incorporate comprehensive HVAC and plumbing system changes across the school facility, including new rooftop heat pumps, ductless fan coil units, ceiling-mounted cassette systems, exhaust fans, outside air units, and condensate drain piping with P-traps. Specifications require coordination with existing structural systems, proper insulation of exterior ductwork with Armaflex closed-cell elastomeric insulation and aluminum covers, fire-rated duct penetrations through walls, and bi-polar ionization units salvaged from existing equipment for reinstallation in new units. Equipment schedules detail supply and return grilles from Titus, including louvered face diffusers and return filter grilles, alongside exhaust fans from Greenheck with specified CFM ratings and motor horsepower. All removed equipment not retained by the owner becomes contractor property; GPS needlepoint bi-polar ionization devices must be labeled, stored, and reinstalled by the controls contractor. The project requires compliance with ASTM standards for acoustical panels, proper ceiling installation before mechanical systems are operational, above-ceiling observations by the architect, and fire marshal coordination prior to ceiling installation.

Text of this file

Lamar Reese Elementary School May 20, 2022 HVAC & Plumbing Upgrades Dougherty County Board of Education Albany, Georgia

Addendum No. 3- Page 1 of 3

ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210

ADDENDUM NUMBER: THREE DATED: June 15, 2022

To: All contract bidders of record.

This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings dated May 20, 2022, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Price Form; failure to do so may subject bidder to disqualification.

CHANGES TO SPECIFICATIONS

1. SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS

A. On page 015000-3, delete paragraph 2.2.C. in its entirety and replace with the following:

“C. Modular Classrooms: Of sufficient size (68’ x 28’ minimum) to accommodate two

(2) standard size classrooms (600-700 s.f.) and two (2) restrooms with ADA access. Furnish and equip modular classrooms as follows:

1. Fire Alarm Pull Station at door (one in each classroom). Connect pull station to the main building Fire Alarm Panel.

2. Fire Alarm Horn/Strobe (one in each classroom). Connect fire alarm to the main building Fire Alarm Panel.

3. Exit Light/Emergency Light (one in each classroom at egress).

4. Computer Hub/Switch. Connect to nearest IDF in the main building.

5. Wireless internet access, associated with main building. Connect portable classroom hub/switch to nearest IDF in the main building.

6. Wireless Access Point (one in each classroom). Connect to hub/switch.

7. Intercom Speaker (one in each classroom). Bogen model number

MB8TSL(VR) or approved equal.

8. Relay Board/s and Analog Card to Main Intercom Head End to support the additional temporary classroom intercom speakers.

9. Intrusion Alarm on Exterior Doors. Connect to main building alarm panel.

10. ADA Accessible Rest Room (one in each classroom).

11. Cooling and heating equipment necessary to maintain a uniform indoor temperature of 70-75 deg. F.

12. Lighting fixtures capable of maintaining average illumination of 50fc at desk height

13. One Set of Steps and One ADA Ramp.

14. Above ground septic tank, which will include weekly pumping service.

15. Exterior Light (Hubbell Model # LMC-30LU-4K-3-1-BZ or equal (one each portable).

16. Above ground septic tank, which will include weekly pumping service.

Addendum No. 3- Page 2 of 3

17. Modular Classroom Distributers:

a. Wilscot, 4742 Blountstown Hwy., Tallahassee, FL 3204;

(850) 574-9222, Contact Person; Rusty Young (850) 228-6575.

b. Mobile Modular, 530 Etheridge Rd., Arcade GA 30549,

(770) 366-3356, wendy.grenske@mobilemodular.com”

2. SECTION 095113 - ACOUSTICAL PANEL CEILINGS

A. Delete Section 095113 - Acoustical Panel Ceilings dated May 20, 2022, in its entirety and replace with Section 095113 - Acoustical Panel Ceilings, revised June 15, 2022, included herewith.

3. SECTION 234100 - PARTICULATE AIR FILTRATION AND BI-POLAR IONIZATION

UNITS

A. On page 234100-3, paragraph 2.3.A, delete the last sentence of this paragraph in its entirety and replace with the following:

“Bi-polar ionization unit shall be manufactured by Global Plasma Solutions or prior approved equal.”

CHANGES TO DRAWINGS

1. SHEET MD101 - MECHANICAL DEMO PLAN - SECTOR A

A. Delete Sheet MD101 in its entirety and replace with Sheet MD101, revised 06/15/2022, included herewith.

2. SHEET MD102 - MECHANICAL DEMO PLAN - SECTOR B

A. Delete Sheet MD102 in its entirety and replace with Sheet MD102, revised 06/15/2022, included herewith.

3. SHEET MD103 - MECHANICAL DEMO PLAN - SECTORS C, D & E

A. Delete Sheet MD103 in its entirety and replace with Sheet MD103, revised 06/15/2022, included herewith.

4. SHEET M101 - MECHANICAL NEW WORK PLAN - SECTOR A

A. Delete Sheet M101 in its entirety and replace with Sheet M101, revised 06/15/2022, included herewith.

5. SHEET M102 - MECHANICAL NEW WORK PLAN - SECTOR B

A. Delete Sheet M102 in its entirety and replace with Sheet M102, revised 06/15/2022, included herewith.

Addendum No. 3- Page 3 of 3

6. SHEET M601 - MECHANICAL SCHEDULES

A. Delete Sheet M601 in its entirety and replace with Sheet M601, revised 06/15/2022, included herewith.

7. SHEET E001- ELECTRICAL OVERALL PLAN

A. Delete Sheet E001 in its entirety and replace with Sheet E001, revised 06/15/2022, included herewith.

8. SHEET E801- ELECTRICAL SCHEDULES AND LEGEND

A. Delete Sheet E801 in its entirety and replace with Sheet E801, revised 06/15/2022, included herewith.

END OF ADDENDUM #3

Lamar Reese Elementary School Revised June 15, 2022

ACOUSTICAL PANEL CEILINGS 095113 - 1

SECTION 095113 - ACOUSTICAL PANEL CEILINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes acoustical panels and exposed suspension systems for ceilings.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1.4 CLOSEOUT SUBMITTALS

A. Maintenance Data: For finishes to include in maintenance manuals.

1.5 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.

2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.

B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.

C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.

1.7 FIELD CONDITIONS

A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.

ACOUSTICAL PANEL CEILINGS 095113 - 2

B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed.

Do not proceed with installation of ceilings until deficiencies have been corrected.

1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.

2. Before notifying Architect, complete the following in areas to receive ceilings:

a. Installation of lighting fixtures, powered for operation.

b. Installation, insulation, and leak and pressure testing of water piping systems.

c. Installation of air-duct systems.

d. Installation of air devices.

e. Installation of mechanical system control-air tubing.

f. Installation of ceiling support framing.

C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.

2. Smoke-Developed Index: 450 or less.

2.2 ACOUSTICAL PANELS, GENERAL

A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.

B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.

C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.

2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)

A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.

ACOUSTICAL PANEL CEILINGS 095113 - 3

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.

2. Pattern: E.

C. Color: White.

D. LR: Not less than 0.90.

E. NRC: Not less than 0.95.

F. Humidity/Sag Resistance: Humiguard Plus.

G. Edge/Joint Detail: Square edge.

H. Thickness: 5/8 inch.

I. Modular Size: 24 by 24 inches.

2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)

A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:

1. Armstrong World Industries, Inc.; Clean Room VL

2. CertainTeed Corp.; Performa, Vinyrock

3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.

2. Pattern: As indicated by manufacturer’s designation.

C. Color: White.

D. LR: Not less than 0.78.

E. CAC: Not less than 38.

F. Edge/Joint Detail: Square.

G. Thickness: 1/2 inch.

H. Modular Size: 24 by 24 inches.

ACOUSTICAL PANEL CEILINGS 095113 - 4

2.5 METAL SUSPENSION SYSTEMS, GENERAL

A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.

1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.

B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:

1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.

2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.

2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>

A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.; Subsidiary of USG Corporation

B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating designation; with prefinished 15/16-inch-wide metal caps on flanges.

1. Structural Classification: Intermediate-duty system.

2. End Condition of Cross Runners: Override (stepped) type.

3. Face Design: Flat, flush.

4. Cap Material: Steel cold-rolled sheet.

5. Cap Finish: Painted white.

2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>

A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:

1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard

2. CertainTeed Corp.; Classic Environmental Stab

3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA

ACOUSTICAL PANEL CEILINGS 095113 - 5

B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System:

Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-rolled, 15/16-inch-wide aluminum caps on flanges.

1. Structural Classification: Intermediate-duty system.

2. Face Design: Flat, flush.

3. Face Finish: Painted white.

2.8 METAL EDGE MOLDINGS AND TRIM

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.; Subsidiary of USG Corporation.

B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.

1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated.

2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member.

3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.

B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

ACOUSTICAL PANEL CEILINGS 095113 - 6

3.2 PREPARATION

A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.

3.3 INSTALLATION

A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."

B. Suspend ceiling hangers from building's structural members and as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.

4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.

6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.

7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.

8. Do not attach hangers to steel deck tabs.

9. Do not attach hangers to steel roof deck. Attach hangers to structural members.

10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.

11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

ACOUSTICAL PANEL CEILINGS 095113 - 7

C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or post installed anchors.

D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.

1. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.

2. Do not use exposed fasteners, including pop rivets, on moldings and trim.

E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.

F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.

1. Arrange directionally patterned acoustical panels as follows:

a. Install panels in a basket-weave pattern.

2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.

3. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.

3.4 CLEANING

A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

END OF SECTION 095113

ACOUSTICAL PANEL CEILINGS 095113 - 8

THIS PAGE INTENTIONALLY LEFT BLANK

MUSIC LAB

ART LAB

MEDIA CENTER

CONF. RM.

114F

AV. STOR.

114E

BOOK STOR.

114D

PRODUCTION ROOM

114C

WORK RM.

114B

MEDIA SPEC. OFFICE

114A

LOBBY

CONF. ROOM

PRINC. OFF.

TLT.

104A

TLT.

108A

ASST. PRINCIPAL

COUNSELOR

VAULT

RM.

103B

OFFICE MANAGER

CLINIC

TLT.

103A

WORK RM.

DATA ROOM

111A

COMPUTER LAB

CLOSET

STOR.

118A

KILN RM.

116A

STOR.

116B

DATA RM.

LOBBY

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD101

MECHANCAL DEMO PLAN -

SECTOR A

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A

NOTES: (THIS SHEET ONLY)

1 . REMOVE CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL

UNIT AND ASSOCIATED REFRIGERANT PIPING. REMOVE

CONDENSATE PIPING AND MAKE NOTE OF ROUTING. SEE NEW

WORK PLAN FOR INSTALLATION OF NEW CEILING MOUNTED

DUCTLESS FAN COIL UNIT IN SAME LOCATION.

2 . REMOVE EXISTING ROOF MOUNTED DUCTLESS HEAT PUMP AND

ASSOCIATED PIPING. EXISTING EQUIPMENT SUPPORT PLATFORM

TO REMAIN.

3 . REMOVE EXISTING ROOFTOP HEAT PUMP AND ASSOCIATED

CONDENSATE DRAIN. REMOVE EXISTING GPS BIPOLAR IONIZATION

UNIT AND STORE FOR REUSE IN NEW ROOFTOP HEAT PUMP.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOFTOP UNIT IN SAME LOCATION.

4 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOF MOUNTED EXHAUST FAN.

5 . EXISTING ROOFTOP UNIT, DRAIN, ETC. TO REMAIN.

6 GENERAL: UNLESS OTHERWISE NOTED, ALL DUCTWORK, GRILLES,

DIFFUSERS, ETC ARE TO REMAIN. CLEAN EXISTING DUCTWORK AS

SPECIFIED. CLEAN ALL DIFFUSERS AND GRILLES TO REMOVE ALL

DUST, DIRT, SMUDGES, ETC.

7 GENERAL: CONTRACTOR SHALL REMOVE ALL EXISTING BIPOLAR

IONIZATION UNITS IN EXISTING EQUIPMENT FOR REINSTALLATION

IN NEW EQUIPMENT. ALL BIPOLAR IONIZATION UNITS NOT REUSED

SHALL BE TURNED OVER TO THE OWNER.

8 . EXISTING POWER CIRCUIT FOR RTU/CONVENIENCE OUTLET RISES

THROUGH EXISTING PITCH POCKET. SEE ELECTRICAL DRAWINGS

FOR REMOVAL OF POWER CIRCUIT TO BELOW ROOF DECK, AND

JUNCTIONING BELOW ROOF LEVEL AND ROUTING CIRCUIT UP

INSIDE ROOF CURB ADAPTER OF NEW EQUIPMENT. FILL PITCH

POCKET FOLLOWING POWER CIRCUIT REMOVAL. PROVIDE 18

GAUGE METAL CAP TO COVER EXISTING PITCH POCKET. SEAL AIR

& WATER TIGHT.

GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

2 ADDENDUM #3 06/15/22

CAFETERIA

SERVING

KITCHEN

OFFICE

JAN.

LAUNDRY

TLT.

132A

LOCKER

DRY STOR.

STOR.

MECH.

113A

MEN

115A

MECH.

100A

OFF.

STOR.

150A

STOR.

100C

ELECT.

100B

STOR.

112A

P.E. FACILITY

LIFT

122B

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD102

MECHANCAL DEMO PLAN -

SECTOR B

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B

NOTES: (THIS SHEET ONLY)

1 . REMOVE CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL

UNIT AND ASSOCIATED REFRIGERANT PIPING. REMOVE

CONDENSATE PIPING AND MAKE NOTE OF ROUTING. SEE NEW

WORK PLAN FOR INSTALLATION OF NEW CEILING MOUNTED

DUCTLESS FAN COIL UNIT IN SAME LOCATION.

2 . REMOVE EXISTING ROOF MOUNTED DUCTLESS HEAT PUMP AND

ASSOCIATED PIPING. EXISTING EQUIPMENT SUPPORT PLATFORM

TO REMAIN.

3 . REMOVE EXISTING ROOFTOP HEAT PUMP AND ASSOCIATED

CONDENSATE DRAIN. REMOVE EXISTING GPS BIPOLAR IONIZATION

UNIT AND STORE FOR REUSE IN NEW ROOFTOP HEAT PUMP.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOFTOP UNIT IN SAME LOCATION.

4 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

EXISTING ROOF CURB TO REMAIN. SEE NEW WORK PLAN FOR

INSTALLATION OF NEW ROOF MOUNTED EXHAUST FAN.

5 . REMOVE EXISTING DUCTLESS HEAT PUMP MOUNTED ON

CONCRETE PAD, ASSOCIATED PIPING, ETC. SEE NEW WORK PLAN

FOR INSTALLATION OF NEW DUCTLESS HEAT PUMP TO REUSE

EXISTING PIPE ROUTING.

6 . COMPLETELY REMOVE EXISTING LOUVER IN EXISTING WINDOW

FRAME AND ASSOCIATED DUCT ABOVE LOW ROOF. FIELD VERIFY

EXISTING SIZE. SEE NEW WORK PLAN FOR REUSE OF EXISTING

OPENING. TEMPORARILY SEAL OPENINGS DURING

CONSTRUCTION AS REQUIRED TO PREVENT AIR & WATER

INFILTRATION.

7 . COMPLETELY REMOVE EXISTING SUSPENDED AIR HANDLING UNIT,

ASSOCIATED SUPPORTS, CONDENSATE PIPING, REFRIGERANT

PIPING, ETC.

8 . COMPLETELY REMOVE EXISTING CONCRETE PAD MOUNTED HEAT

PUMPS, ASSOCIATED PIPING, ETC. PATCH PIPING PENETRATIONS

TO MATCH EXISTING BRICK EXTERIOR.

9 . COMPLETELY REMOVE EXISTING DUCTWORK, SUPPORT,

INSULATION, ETC. UP TO LOCATION SHOWN.

10 . COMPLETELY REMOVE EXISTING REFRIGERANT PIPING,

CONDENSATE PIPING, SUPPORTS, INSULATION, ETC. SERVING AIR

HANDLING UNITS.

11 . REMOVE EXISTING KITCHEN HOOD EXHAUST FAN MOUNTED ON

ROOF. SEE NEW WORK PLAN FOR INSTALLATION OF NEW

EXHAUST FAN SAME LOCATION.

12 . EXISTING KITCHEN HOOD SUPPLY FAN ABOVE COOLER / FREEZER.

REMOVE A SHORT PORTION OF DUCT AS REQUIRED TO REMOVE

EXHAUST FAN. SEE NEW WORK PLAN FOR INSTALLATION OF NEW

EXHAUST FAN SAME LOCATION.

13 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.

14 . REMOVE EXISTING INLINE EXHAUST FAN MOUNTED ABOVE

CEILING AT THIS APPROXIMATE LOCATION. SEE NEW WORK PLAN

FOR INSTALLATION OF NEW EXHAUST FAN SAME LOCATION.

15 . REMOVE EXISITNG SUPPLY DUCTWORK AS REQUIRED FOR

REMOVAL OF AIR HANDLER. REMAINDER OF EXISTING SUPPLY

DUCTWORK TO REMAIN. SEE NEW WORK PLAN FOR CONNECTION

OF NEW DUCTWORK TO EXISTING DUCTWORK AT THIS LOCATION.

16 . GENERAL: UNLESS OTHERWISE NOTED, ALL DUCTWORK, GRILLES,

DIFFUSERS, ETC ARE TO REMAIN. CLEAN EXISTING DUCTWORK AS

SPECIFIED. CLEAN ALL DIFFUSERS AND GRILLES TO REMOVE ALL

DUST, DIRT, SMUDGES, ETC.

17 . GENERAL: CONTRACTOR SHALL SALVAGE ALL EXISTING BIPOLAR

IONIZATION UNITS IN EXISTING EQUIPMENT FOR REINSTALLATION

IN NEW EQUIPMENT. ALL BIPOLAR IONIZATION UNITS NOT REUSED

SHALL BE TURNED OVER TO THE OWNER.

18 . REMOVE EXISTING DOOR AIR CURTAIN, SEE NEW WORK PLAN FOR

NEW DOOR AIR CURTAIN IN SAME LOCATION.

19 . REMOVE EXISTING FENCING AS REQUIRED FOR INSTALLATION OF

NEW DUCTLESS HEAT PUMPS. SEE NEW WORK PLAN.

20 . EXISTING POWER CIRCUIT FOR RTU/CONVENIENCE OUTLET RISES

THROUGH EXISTING PITCH POCKET. SEE ELECTRICAL DRAWINGS

FOR REMOVAL OF POWER CIRCUIT TO BELOW ROOF DECK, AND

JUNCTIONING BELOW ROOF LEVEL AND ROUTING CIRCUIT UP

INSIDE ROOF CURB ADAPTER OF NEW EQUIPMENT. FILL PITCH

POCKET FOLLOWING POWER CIRCUIT REMOVAL. PROVIDE 18

GAUGE METAL CAP TO COVER EXISTING PITCH POCKET. SEAL AIR

& WATER TIGHT.

GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

2 ADDENDUM #3 06/15/22

1 1

TT TT

TTTT

TT

TT

TT

TT

TT

TT TT

TT TT

TT

TT TT

TT

TTTT

TT TT

TTTT

TTTT

TT TT

TT

TT

TT

TT

TT TT

TT

TT

4 4 4 4

4 4

4 4

3 3

6 6

8 8

F.D./S.D. F.D./S.D.

F.D./S.D. F.D./S.D.

F.D./S.D. F.D./S.D.

F.D./S.D.

F.D./S.D.

F.D./S.D.

F.D./S.D. F.D./S.D. F.D./S.D.

9 9

9 9

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

K-1 CLASSROOM

SPECIAL ED.

SPECIAL ED.

TITLE ONE

CLASSROOM

TLT.

205A

TLT.

205B

WORK ROOM

BOOK STOR.

2-3 CLASSROOM

2-3 CLASSROOM

TITLE ONE

CLASSROOM

TITLE ONE

CLASSROOM

2-3 CLASSROOM

2-3 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

SPECIAL EDUCATION

WORK RM.

BOOK STOR.

SPECIAL EDUCATION

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

4-5 CLASSROOM

ELECT.

TLT.

210A

TLT.

210B

TLT.

211A

TLT.

209A

TLT.

213A

TLT.

213B

TLT.

214A

TLT.

214B

STOR.

TLT.

201A

TLT.

201B

TLT.

202A

TLT.

202B

GIRLS

306B

WORK RM.

BOOK STOR.

ELECT.

STOR.

BOYS

306A

TLT.

310B

TLT.

310A

JAN.

ELEC.

STOR.

TLT.

405C

TLT

405B

KITCHEN

405A

JAN.

TLT.

410A

TLT.

410B

GIRLS

406B

BOYS

406A

CORRIDOR

CORRIDOR

CORRIDOR

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

MD103

MECHANCAL DEMO PLAN -

SECTORS C, D, & E

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTORS C, D, & E

NOTES: (THIS SHEET ONLY)

1 . REMOVE EXISTING WALL HUNG HEAT PUMP. REMOVE EXISTING

GPS BIPOLAR IONIZATION UNIT AND STORE FOR REUSE IN NEW

WALL HUNG HEAT PUMP.

2 . EXISTING 4"Ø DRYER WALL CAP TO REMAIN.

3 . EXISTING 8" X 6" EXHAUST WALL CAP TO REMAIN.

4 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN AND

ASSOCIATED DUCTWORK UP TO LOCATION SHOWN. SEE NEW

WORK PLAN FOR INSTALLATION OF NEW EXHAUST FAN SAME

LOCATION.

5 . EXISTING PROPELLER EXHAUST FAN IN ATTIC TO REMAIN.

6 . REMOVE EXISTING ROOF MOUNTED CENTRIFUGAL EXHAUST FAN.

SEE NEW WORK PLAN FOR INSTALLATION OF NEW EXHAUST FAN

SAME LOCATION.

7 . REMOVE EXISTING HORIZONTAL FAN COIL UNIT, ASSOCIATED

REFRIGERANT PIPING, CONDENSATE PIPING, ETC. MOUNTED ON

PLATFORM IN ATTIC. NOTE EXISTING REFRIGERANT PIPE AND

CONDENSATE PIPE ROUTING, EXISTING PIPE ROUTINGS TO BE

REUSED. SEE NEW WORK PLAN FOR INSTALLTION OF NEW FAN

COIL UNIT SAME LOCATION. FIELD VERIFY INSTALLATION OF

EXISTING BIPOLAR IONIZATION UNIT AND REMOVE AND STORE

FOR REUSE IN NEW FAN COIL UNIT.

8 . REMOVE EXISTING PAD MOUNTED HEAT PUMP AND ASSOCIATED

PIPING. SEE NEW WORK PLAN FOR INSTALLATION OF NEW HEAT

PUMP IN SAME LOCATION.

9 . EXISTING 16" X 14" FIRE/SMOKE DAMPER IN ATTIC PARTITION TO

REMAIN.

GENERAL NOTE:OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

RTU-1

RTU-2

RTU-4

RTU-9 RTU-10

DFCU-3

DHP-3

DHP-1

DFCU-1

EF-25

EF-26

OAU-2

OAU-3

EF-37

RTU-5

RTU-6

RTU-7

RTU-8

MUSIC LAB

118ART LAB

MEDIA CENTER

CONF. RM.

114F

AV. STOR.

114E

BOOK STOR.

114D

PRODUCTION ROOM

114C

WORK RM.

114B

MEDIA SPEC. OFFICE

114A

LOBBY

CONF. ROOM

PRINC. OFF.

TLT.

104A

ASST. PRINCIPAL

COUNSELOR

RM.

103B

OFFICE MANAGER

CLINIC

WORK RM.

DATA ROOM

111A

COMPUTER LAB

CLOSET

STOR.

118A

KILN RM.

116A

STOR.

116B

DATA RM.

LOBBY

CC

CC

SS

16"x16"

16"x16"16"x18"

8 8

RTU-3

S S S

R

OAU-1

260 260

260 260

D

D D

D

D

D

D D

D

D

335 335

335 335 330

D

D

D

D

OAU-1

D

6 6 6

R

D

D

12 12 132

NOTES: (THIS SHEET ONLY)

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

M101

MECHANICAL NEW WORK

PLAN - SECTOR A

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR A

1 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO

TRANSITION FROM NEW UNIT CONNECTIONS TO EXISTING DUCT

LAYOUT. REINSTALL BIPOLAR IONIZATION UNIT REMOVED DURING

DEMOLITION. SEE BIPOLAR IONIZATION UNIT DETAIL.

2 . NEW CENTRIFUGAL EXHAUST FAN MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO MAKE

TRANSITION FROM NEW FAN CONNECTION TO EXISTING DUCT

DIMENSION.

3 . DUCTLESS HEAT PUMP MOUNTED ATOP EXISTING EQUIPMENT

SUPPORT PLATFORM ON ROOF. PROVIDE NEW CAP AT EXISTING

CURB AND NEW PIPE BOX FOR ROUTING OF PIPING AND CONDUIT.

SEE DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL.

4 . NEW CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL

UNIT. ROUTE CONDENSATE TO SAME LOCATION AS CASSETTE

REMOVED DURING DEMOLITION. REPAIR CEILING GRID / TILE

DAMAGED DURING DEMOLITION TO MATCH EXISTING.

REFRIGERANT PIPING ROUTED FROM FAN COIL UNIT UP THROUGH

PIPE BOX TO DUCTLESS HEAT PUMP ON ROOF.

5 . EXISTING RTAC, DUCTWORK, GRILLES, ETC. TO REMAIN. CLEAN

DUCTWORK IN ACCORDANCE WITH DUCT CLEANING SPEC.

6 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC

CONDENSATE DRAIN PIPING FROM RTAC TO ROOF DRAIN AS

SHOWN. PROVIDE PIPE SUPPORTS ON MAXIMUM 6' CENTERS. SEE

CONDENSATE DRAIN TRAP DETAIL AND CONDENSATE PIPE

SUPPORT ON ROOF DETAIL.

7 . NEW HORIZONTAL DISCHARGE 100% OUTSIDE AIR UNIT MOUNTED

ATOP ROOF CURB. PROVIDE JOIST REINFORCEMENT AT JOISTS

BELOW NEW OUTSIDE AIR UNIT. SEE ROOF CURB DETAIL- CURB

ATOP EXISTING ROOF, AND JOIST REINFORCEMENT DETAIL.

8 . 16" X 16" 100% OUTSIDE AIR DUCT PENETRATES EXTERIOR WALL

AND CONTINUES TO ABOVE CLASSROOM CEILING. SEE SHEET

M103 SECTOR C FOR CONTINUATION. DUCTWORK ROUTED

OUTDOORS SHALL HAVE ONE LAYER OF 2" THICK ARMAFLEX

CLOSED CELL ELASTOMERIC INSULATION ON EXTERIOR OF DUCT.

COVER INSULATION WITH EMBOSSED ALUMINUM COVER. PROVIDE

AN ADDITIONAL SHEET METAL COVER OVER

DUCTWORK/INSULATION ASSEMBLY TO COMPLETELY ENCLOSE

DUCTWORK. SEE ROOF MOUNTED EXTERIOR METAL DUCT HOOD

DETAIL.

9 . CONDENSATE DRAIN CONTINUES TO ROOF DRAIN. SEE SHEET

M102 FOR CONTINUATION.

10 . NEW CONDENSATE DRAIN PIPING ROUTED TO SAME LOCATION AS

CONDENSATE DRAIN PIPE REMOVED DURING DEMOLITION. FIELD

VERIFY EXISTING PIPE ROUTING.

11 . REFRIGERANT PIPING ROUTED DOWN THRU PIPE BOX. SEE

DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL AND PIPE

BOX/HOOD ASSEMBLY DETAIL.

12 . DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY

ELECTRICAL. INSTALLED BY MECHANICAL.

13 . NEW MAIN DDC CONTROL PANEL MOUNTED ON 3/4" PLYWOOD

BACKBOARD. COORDINATE EXACT LOCATION WITH EXISTING DATA

ROOM EQUIPMENT, SHELVING, ETC.

GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS

THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL. No. Description Date

RTU-15

RTU-16

RTU-14

DHP-2

DFCU-2

DHP-4

DFCU-4

RTU-13

EF-27

EF-32

EF-30

EF-33

D D

D

D

D

D

D

D

CAFETERIA

SERVING

KITCHEN

OFFICE

JAN.

LAUNDRY

TLT.

132A

LOCKER

DRY STOR.

STOR.

MECH.

113A

MEN

115A

MECH.

100A

OFF.

STOR.

150A

STOR.

100C

ELECT.

100B

STOR.

112A

P.E. FACILITY

LIFT

122B

RTU-17

"ø

"ø

"ø

"ø

26"x32"

26"x32"

26"x32"

26"x32"

56"x30"

EF-31

CORRIDOR

WOMEN

115B

SF-1

DHP-5

DHP-6

DFCU-5

DFCU-6

TT

CC

TT

RTU-12

RTU-11

DAC-1

56"x30"

1 1/2" D

D

D

R

R(TYP)

D

R

R

1 1/2" D

S

S

S

D

D

R

D

E1

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A B

C D

E

2021203

05/20/2022

GA DOE ID #: 0199

M102

MECHANICAL NEW WORK

PLAN - SECTOR B

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR B

NOTES: (THIS SHEET ONLY)

1 . NEW DUCTWORK OF INDICATED SIZE ROUTED THROUGH

APPROXIMATELY 56" X 30" EXISTING WINDOW FRAME IN SAME

LOCATION AS LOUVER REMOVED DURING DEMOLITION. FIELD

VERIFY EXACT DIMENSIONS OF OPENING. SEAL OPENING AIR AND

WATER TIGHT.

2 . NEW EXPOSED ROUND SPIRAL DUCTWORK CONNECTS TO

EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PAINT

DUCTWORK, SUPPORTS, ETC. TO MATCH EXISTING.

3 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO

TRANSITION FROM NEW UNIT CONNECTIONS TO EXISTING DUCT

LAYOUT. REINSTALL BIPOLAR IONIZATION UNIT REMOVED DURING

DEMOLITION. SEE BIPOLAR IONIZATION UNIT DETAIL.

4 . EXISTING ROOF DRAIN AT THIS APPROXIMATE LOCATION.

7 . DUCTLESS HEAT PUMP MOUNTED ATOP EXISTING EQUIPMENT

SUPPORT PLATFORM ON ROOF. PROVIDE NEW CAP AT EXISTING

CURB AND NEW PIPE BOX FOR ROUTING OF PIPING AND CONDUIT.

SEE DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL.

8 . CEILING MOUNTED CASSETTE TYPE DUCTLESS FAN COIL UNIT.

9 . NEW DUCTLESS HEAT PUMP MOUNTED ON EXISTING CONCRETE

EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL.

10 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC

CONDENSATE DRAIN PIPING FROM RTAC TO ROOF DRAIN AS

SHOWN. BASIS OF DESIGN CONDENSATE DRAIN CONNECTION IS IN

A DIFFICULT TO ACCESS LOCATION, INSTALL TRAP IN AN

ACCESSIBLE LOCATION AS SHOWN. ENSURE DRAIN PIPING DOES

NOT BLOCK ACCESS PANELS. SEE CONDENSATE DRAIN TRAP

DETAIL AND CONDENSATE ROOF SUPPORT DETAIL.

11 . INSTALL CONDENSATE P-TRAP AT THIS LOCATION.

12 . ROUTE LINE SIZE, SLOPED (1/4" PER FOOT), TRAPPED, PVC

CONDENSATE DRAIN PIPING FROM RTAC TO ROOF DRAIN AS

SHOWN. SEE CONDENSATE DRAIN TRAP DETAIL AND

CONDENSATE ROOF SUPPORT DETAIL.

13 . DUCT PENETRATES EXTERIOR WALL 56" X 30", TRANSITIONS IN

ELBOW TO 56" X 16", RISES TO ABOVE BOTTOM OF STRUCTUAL

TRUSS AND IS ROUTED AS SHOWN. PROVIDE TRANSITIONS &

OFFSETS AS REQUIRED TO AVOID CONFLICTS WITH STRUCTURAL

MEMBERS.

14 . COORDINATE DUCT ROUTING WITH EXISTING STRUCTURAL

FRAMING AND BASKETBALL GOAL SUPPORTS. INTERNALLY LINE

DUCTWORK WITH 1" LINER. ALL DUCTWORK EXPOSED IN GYM

SHALL BE GALVIGRIP TYPE, PRIMED, AND PAINTED WITH 2 COATS

OF PAINT TO MATCH EXISTING DUCTWORK. DUCTWORK SHALL BE

PAINTED PRIOR TO HANGING.

15 . NEW DUCTLESS CASSETTE MOUNTED IN CEILING. MODIFY

EXISTING CEILING GRID AS REQUIRED TO INSTALL NEW DUCTLESS

FAN COIL UNIT. BLANK OFF SUPPLY LOUVER FACING KITCHEN

HOOD TO ENSURE DFCU AIRFLOW DOES NOT AFFECT KITCHEN

HOOD.

16 . NEW SUPPLY FAN MOUNTED ABOVE COOLER/FREEZER. FIELD

VERIFY EXISTING LOCATION, SUPPLY, & RETURN CONNECTIONS.

PROVIDE FITTINGS / TRANSITIONS AS REQUIRED TO MAKE A

SMOOTH TRANSITION FROM NEW FAN CONNECTIONS TO EXISTING

DUCTWORK.

17 . NEW DOOR AIR CURTAIN MOUNTED IN SAME LOCATION AS DOOR

AIR CURTAIN REMOVED DURING DEMOLITION. FIELD VERIFY

EXISTNG DOOR DIMENSIONS.

18 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ON ROOF. PROVIDE

JOIST REINFORCEMENT AT BAR JOISTS BELOW RTU. SEE ROOF

CURB DETAIL - NEW CURB ON EXISTING ROOF AND JOIST

REINFORCEMENT DETAIL.

19 . NEW DUCTLESS HEAT PUMP MOUNTED ON NEW CONCRETE

EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL.

20 . EXTEND EXISTING CONCRETE EQUIPMENT PAD FOR NEW

DUCTLESS HEAT PUMPS. SEE CONCRETE EQUIPMENT PAD DETAIL.

FIELD VERIFY EXISTING FENCING HEIGHT AND DISTANCE FROM

BUILDING. MODIFY AMD EXTEND EXISTING FENCING AS SHOWN TO

INCLUDE NEW DUCTLESS HEAT PUMPS.

21 . DUCTWORK ROUTED EXPOSED ON ROOF. CAREFULLY

COORDINATE ROUTING WITH EXISTING PLUMBING VENT STACKS,

FLUES, ETC. DUCTWORK ROUTED OUTDOORS SHALL HAVE ONE

LAYER OF 2" THICK ARMAFLEX CLOSED CELL ELASTOMERIC

INSULATION ON EXTERIOR OF DUCT. COVER INSULATION WITH

EMBOSSED ALUMINUM COVER. PROVIDE NON-PENETRATING DUCT

SUPPORTS ON MAXIMUM 4' CENTERS TO SUPPORT DUCTWORK ON

ROOF. SEE NON-PENETRATING DUCT SUPPORT DETAIL. COVER

SUPPLY AND RETURN DUCT INDIVIDUALLY WITH SHEET METAL

COVERS. SEE ROOF MOUNTED EXTERIOR METAL DUCT HOOD

22 . REFRIGERANT PIPING RISES UP EXTERIOR WALL AND

PENETRATES BUILDING AT EXISTING PIPING PENETRATION

ELEVATION. PROVIDE COVER FOR REFRIGERANT PIPING AND

PAINT TO MATCH EXISTING BUILDING.

23 . CONDENSATE PIPE CONTINUES TO EXISTING CONDENSATE

TERMINATION. FIELD VERIFY EXACT LOCATION.

24 . NEW ROOF MOUNTED HEAT PUMP MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO

TRANSITION FROM NEW UNIT CONNECTIONS TO EXISTING DUCT

LAYOUT. COORDINATE DUCT CURB TO PREVENT INTERFERENCE

WITH ADJACENT ROOF SOFFIT & EXTERIOR WALL. REINSTALL

BIPOLAR IONIZATION UNIT REMOVED DURING DEMOLITION. SEE

BIPOLAR IONIZATION UNIT DETAIL.

25 . NEW CENTRIFUGAL EXHAUST FAN MOUNTED ATOP EXISTING

ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO MAKE

TRANSITION FROM NEW FAN CONNECTION TO EXISTING DUCT

DIMENSION.

26 . CAREFULLY COORDINATE ROOFTOP PLACEMENT TO MAINTAIN

MINIMUM 10' FROM OUTSIDE AIR INTAKE TO EXISTING WATER

HEATER FLUE.

27 . PROVIDE NON-PENETRATING KEEGUARD CONTRACTOR ROOFTOP

GUARDRAIL OR PRIOR APPROVED EQUAL AROUND EDGE OF

ROOFTOP UNIT TO ALLOW FOR MAINTENANCE.

28 . NEW CONDENSATE DRAIN PIPING ROUTED TO SAME LOCATION AS

CONDENSATE DRAIN PIPE REMOVED DURING DEMOLITION. FIELD

VERIFY EXISTING PIPE ROUTING.

29 . REFRIGERANT PIPING ROUTED DOWN THRU PIPE BOX. SEE

DUCTLESS HEAT PUMP CAP AT EXISTING CURB DETAIL AND PIPE

BOX/HOOD ASSEMBLY DETAIL.

30 . DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY

ELECTRICAL. INSTALLED BY MECHANICAL.

31 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.

GENERAL NOTE: PROVIDE LINTEL AT ALL NEW DUCT PENETRATIONS

THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.

No. Description Date

2 ADDENDUM #3 06/15/22

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

2021203

05/20/2022

GA DOE ID #: 0199

M601

MECHANICAL SCHEDULES

L A

M A

R R

E E

S E

E L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

WBF

JA3

L ily P o n d R d A lb a n y G

A

GRILLES

TAG

TITUS MODEL

NUMBER

CONN. SIZE FINISH

THROW AND/OR

APPLICATION

NOTES

A1 TMS 6" Ø WHITE 4-WAY 1:4:5:7:8

A2 TMS 8" Ø WHITE 4-WAY 1:4:5:7:8

A3 TMS 10" Ø WHITE 4-WAY 1:4:5:7:8

A4 TMS 12" Ø WHITE 4-WAY 1:4:5:7:8

B1 50F 12" X 12" WHITE CEILING RETURN 3:4:6:7

C1 33RL 30" X 16" WHITE SIDEWALL RETURN 4:6:7:10

D1 45F 24" X 24" WHITE CEILING RETURN 2:5:7:9

E1 30RL 56" X 30" WHITE SIDEWALL RETURN 4:6:7:11

1. LOUVERED FACE SQUARE CONE STEEL CEILING SUPPLY DIFFUSER WITH FIXED AIR 360º DISCHARGE PATTERN AS SCHEDULED. PROVIDE

FULL FACED LOUVERS.

2. RETURN FILTER GRILLE WITH 1/2" X 1/2" X 1/2" ALUMINUM EGGCRATE CORE, DESIGNED TO HOLD 1" FILTER. SEE RETURN FILTER GRILLE

DETAIL.

3. ALL ALUMINUM 1" X 1" X 1" "EGG CRATE" EXHAUST/RETURN GRILLE.

4. PROVIDE OPPOSED BLADE DAMPER.

5. IN 24 X 24 PANEL FOR LAY-IN CEILING.

6. FLANGED FRAME FOR SURFACE MOUNTING.

7. NC LEVEL NOT TO EXCEED NC 25.

8. SEE CEILING GRILLE DUCT CONNECTION DETAIL.

9. PROVIDE RECTANGULAR TO ROUND FLAT ADAPTER OF SIZE REQUIRED. SEE RECTANGULAR TO ROUND FLAT ADAPTER DETAIL.

10. HEAVY DUTY STEEL SIDEWALL RETURN GRILLE WITH FIXED HORIZONTAL BLADES AT 38° TO 45° DEFLECTION. PROVIDE 3/8" TO 1/2" BLADE

SPACING AND WELDED CONSTRUCTION.

11. HEAVY DUTY STEEL SIDEWALL RETURN GRILLE WITH FIXED HORIZONTAL BLADES AT 0° DEFLECTION. PROVIDE 3/8" TO 1/2" BLADE

SPACING AND WELDED CONSTRUCTION.

EXHAUST / SUPPLY FANS

TAG

GREENHECK

MODEL NUMBER

CFM APPROX. E.S.P. (IN.W.G.) FAN RPM MOTOR HP SONES NOTES

EF-1 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-2 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-3 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-4 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-5 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-6 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-7 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-8 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-9 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-10 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-11 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-12 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-13 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-14 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-15 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-16 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-17 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-18 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-19 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-20 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-21 SP-80-VG 75 0.25 879 4W <0.3 2:3:4:8

EF-22 SP-80-VG 75 0.25 897 4W <0.3 2:3:4:8

EF-23 G-090-VG 600 0.25 1496 1/10 7.0 1:3:4:5:7

EF-24 G-090-VG 600 0.25 1496 1/10 7.0 1:3:4:5:7

EF-25 G-070-VG 150 0.25 1260 1/15 2.5 1:3:4:5:7

EF-26 G-060-VG 75 0.25 1385 1/15 2.8 1:3:4:5:7

EF-27 G-095-VG 900 0.25 1595 1/6 9.3 1:3:4:5:7

EF-28 OMITTED - - - - - -

EF-29 OMITTED - - - - - -

EF-30 CUE-240-VG 6000 2.0 1108 5 26 3:4:5:7:10

EF-31 EXISTING TO REMAIN - - - - -

EF-32 G-090-VG 415 0.25 1208 1/10 4.9 1:3:4:5:7

EF-33 SQ-90-VG 290 0.25 1161 1/10 4.6 3:4:5:6

EF-34 EXISTING TO REMAIN - - - - -

EF-35 EXISTING TO REMAIN - - - - -

EF-36 EXISTING TO REMAIN - - - - -

EF-37 G-090-VG 415 0.25 1208 1/10 4.9 1:3:4:5:7

SF-1 BCF-210-20 4200 0.5 1174 2 17.5 4:6:9

1. CENTRIFUGAL CURB MOUNTED EXHAUST FAN. PROVIDE BIRDSCREEN, GRAVITY BACKDRAFT DAMPER, DAMPER TRAY, AND HOOD HASPS.

SEE CENTRIFUGAL ROOF EXHAUST FAN DETAIL.

2. CENTRIFUGAL CEILING EXHAUST FAN WITH INTEGRAL POLYPROPYLENE WHITE GRILLE, FLAPPER BACKDRAFT DAMPER, PLUG-IN TYPE

DISCONNECT AND MOUNTING BRACKETS.

3. DIRECT DRIVE. MOTORS WITH VG IN MODEL SHALL BE PROVIDED WITH ELECTRONICALLY COMMUNICATED MOTOR.

4. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH.

5. VG MOTOR SHALL HAVE FACTORY POTENTIOMETER DIAL.

6 INLINE CENTRIFUGAL FAN WITH BACKDRAFT DAMPER, MOUNTING BRACKETS, AND VIBRATION ISOLATORS. SEE CENTRIFUGAL INLINE FAN

DETAIL.

7. MOUNT EXHAUST FAN ATOP EXISTING ROOF CURB. PROVIDE ADAPTER CURB AS REQUIRED TO TRANSITION FROM EXISTING DUCT

CONNECTION TO NEW FAN DUCT CONNECTION.

8. PROVIDE MANUFACTURER PROVIDED, GRILLE MOUNTED MOTION DETECTOR WITH ADJUSTABLE TIME DELAY.

9. BELT DRIVE.

10. CENTRIFUGAL DIRECT DRIVE UPBLAST EXHAUST FAN FOR GREASE LADEN KITCHEN EXHAUST APPLICATION. FAN SHALL HAVE HIGH-TEMP CURB SEAL RATED FOR CONTINUOUS DUTY AT 1500°F, GREASE TRAP, AND GALVANIZED BIRD SCREEN WITH NOMINAL 70% FREE AREA.

HEAT PUMPS

TAG

CARRIER MODEL

NUMBER

COOLING CAPACITY (MBH) MIN. STAGES CAPACITY

MINIMUM AMBIENT

COOLING TEMP

HEATING

CAPACITY (MBH)

NOTES

HP-1 25HBC530 28.8 2 35 14.8 1:2:3:4:5:6:7:8:9:10:11:12:13

HP-2 25HBC530 28.8 2 35 14.8 1:2:3:4:5:6:7:8:9:10:11:12:13

1. COOLING CAPACITIES BASED ON 95°F AMBIENT AIR TEMPERATURE. HEATING CAPACITY BASED ON 17°F AMBIENT TEMP.

2. ALL REFRIGERANT LINES TO BE INSTALLED AND SIZED PER MANUFACTURER'S INSTALLATION RECOMMENDATIONS.

3. SCHEDULED CAPACITIES ARE OVERALL CAPACITIES REQUIRED FOR MATACHED HEAT PUMP AND EVAPORATOR COIL WITH 2°F SUCTION LINE LOSS.

4. PROVIDE INTEGRAL CONTROLS INCLUDING CONTACTORS, CRANKCASE HEATER, 5 MINUTE COMPRESSOR TIME DELAY RELAY, AND COMPRESSOR OVER TEMPERATURE (OVERLOAD) PROTECTION.

5. PROVIDE ALL CONTROLS, ACCESSORIES, AND SYSTEM MODIFICATIONS TO PERMIT COOLING OPERATION TO SPECIFIED TEMPERATURE.

6. PROVIDE LIQUID AND SUCTION LINE SERVICE VALVES/GAUGE PORTS.

7. PROVIDE HIGH PRESSURE SWITCH AND LOW PRESSURE SWITCH.

8. PROVIDE TIME INITIATED, TEMPERATURE TERMINATE DEFROST CONTROLS.

9. SEE HEAT PUMP/CONDENSING UNIT DETAIL.

10. UNIT SHALL UTILIZE R-410a REFRIGERANT.

11. PROVIDE LOUVERED COIL GUARD.

12. PROVIDE 2-STAGE SCROLL COMPRESSOR.

13. MOUNT UNIT ATOP EXISTING CONCRETE EQUIPMENT PAD. EXTEND CONCRETE PAD AS REQUIRED TO MAINTAIN MINIMUM 6" FROM HEAT PUMP TO EDGE OF PAD ON ALL SIDES.

1. VERTICAL DRAW THRU FAN COIL UNIT, MOUNTED HORIZONTALLY, WITH SINGLE WALL CONSTRUCTION AND 1" THICKNESS R4.2 INTERIOR INSULATION, PROVIDE BAKED ENAMEL FINISH. SEE HORIZONTAL FCU DETAIL.

2. COOLING CAPACITIES BASED ON AIR ENTERING EVAPORATOR AT SCHEDULED CONDITIONS AND MATCHED WITH INDICATED HEAT PUMP UNIT.

3. HEATING CAPACITY BASED ON 70°F RETURN AIR AND OUTDOOR AIR AT 17°F, AND MATCHED WITH INDICATED HEAT PUMP UNIT.

4. PROVIDE DX COOLING COIL WITH FACTORY INSTALLED THERMOSTATIC EXPANSION VALVE FOR REFRIGERANT CONTROL.

5. SCHEDULED CAPACITIES ARE OVERALL CAPACITIES FOR MATCHED HEAT PUMP UNIT AND EVAPORATOR COIL WITH 2°F LINE LOSS.

6. EXTERNAL STATIC PRESSURE SCHEDULED DOES NOT INCLUDE WET COOLING COIL, CASING, ELECTRIC HEAT COIL, OR FILTER LOSSES. BLOWER MOTOR MUST OVERCOME E.S.P. AT CONNECTED VOLTAGE.

7. PROVIDE UNIT MOUNTED FACTORY INSTALLED ELECTRIC STRIP HEATERS OF INDICATED KW AT CONNECTED VOLTAGE. PROVIDE SINGLE POINT UNIT POWER CONNECTION FOR ENTIRE UNIT.

8. PROVIDE FAN MOTOR CONTACTOR, TERMINAL STRIP, AND ALL CONTROLS.

9. PROVIDE INTEGRAL FILTER RACK DESIGNED TO ACCOMODATE 1" FILTERS.

10. PROVIDE DOUBLE SLOPED REMOVABLE CONDENSATE DRAIN PAN. PROVIDE TRAPPED CONDENSATE DRAIN. SEE CONDENSATE DRAIN TRAP DETAIL.

11. PROVIDE ECM CONSTANT TORQUE MOTOR.

12. REUSE EXISTING NEEDLEPOINT BI POLAR IONIZATION UNIT REMOVED DURING DEMOLITION. IF NO BIPOLAR UNIT PRESENT IN EXISTING EQUIPMENT, PROVIDE NEW NEEDLEPOINT BIPOLAR IONIZATION UNIT FOR SCHEDULED

AIRFLOW. SEE SPECIFICATIONS FOR DETAILS.

FAN COIL UNITS

TAG

CARRIER

MODEL

NUMBER

CFM O.A. CFM

COOLING

CAPACITY

(MBH)

SENSIBLE

COOLING

CAPACITY (MBH)

HEATING

CAPACITY

(MBH)

ELECTRIC

HEAT (KW)

APPROX.

E.S.P.

(IN.W.G.)

BLOWER

MOTOR HP

COOLING ENT. AIR

TEMP. NOTES

°F D.B. °F W.B.

FCU-1 FV4CNF003 875 - 26.2 19.7 14.5 5 0.25 1/2 75 63 1:2:3:4:5:6:7:8:9:10:11:12

FCU-2 FV4CNF003 875 - 26.2 19.7 14.5 5 0.25 1/2 75 63 1:2:3:4:5:6:7:8:9:10:11:12

DUCTLESS FAN COIL UNITS

TAG

CARRIER

MODEL NUMBER

TOTAL COOLING MBH SENSIBLE COOLING

CAPACITY (MBH)

TOTAL

SUPPLY CFM

HEATING CAPACITY MBH APPROX. E.S.P.

(IN.W.G.)

BLOWER

MOTOR WATTS

NOTES

RATED MIN. RATED MIN

DFCU-1 40MBCQ18 18.0 4.5 12.8 562 - - - 45 1:2:3:4:5

DFCU-2 40MBCQ18 18.0 4.5 12.8 562 18.0 8.3 - 45 1:2:3:4:6

DFCU-3 40MBCQ18 18.0 4.5 12.8 562 - - - 45 1:2:3:4:5

DFCU-4 40MBCQ18 18.0 4.5 12.8 562 18.0 8.3 - 45 1:2:3:4:6

DFCU-5 40MBCQ36 36.0 9.0 25.6 1095 36.0 16.5 - 246 1:2:3:4:6

DFCU-6 40MBCQ36 36.0 9.0 25.6 1095 36.0 16.5 - 246 1:2:3:4:6

DUCTLESS CONDENSING UNITS/HEAT PUMPS

TAG

CARRIER MODEL

NUMBER

TOTAL COOLING MBH HEATING CAPACITY MBH MINIMUM AMBIENT

COOLING TEMP. °F

NOTES

RATED MIN. RATED MIN.

DHP-1 38MAQB18 18.0 4.5 - - 20 1:2:3:4:5:6:7

DHP-2 38MAQB18 18.0 4.5 18.0 8.3 20 1:2:3:4:5:6:7

DHP-3 38MAQB18 18.0 4.5 - - 20 1:2:3:4:5:6:7

DHP-4 38MAQB18 18.0 4.5 18.0 8.3 20 1:2:3:4:5:6:7

DHP-5 38MAQB36 36.0 9.0 36.0 16.5 20 1:2:3:4:5:6:7

DHP-6 38MAQB36 36.0 9.0 36.0 16.5 20 1:2:3:4:5:6:7

1. CEILING CASSETTE STYLE DUCTLESS FAN COIL UNIT.

2. COOLING CAPACITIES BASED ON AIR ENTERING EVAPORATOR AT 80ºFdb, 67ºFwb AND MATCHED WITH INDICATED CONDENSING UNIT/HEATPUMP.HEATING

CAPACITY BASED ON 47 F.

3. PROVIDE FACTORY CONDENSATE PUMP. CONDENSATE PUMP SHALL BE FACTORY PROVIDED MODEL#X87 BLUE DIAMOND MAXIBLUE PUMP WITH A MINIMUM DISCHARGE HEAD OF 23 FT AND A MINIMUM SUCTION HEAD OF 16.5 FT. MOUNT CONDENSATE PUMP 6" ABOVE CEILING ON WALL ON BRACKET AND PIPE SUCTION DOWN TO UNIT CONNECTION. STANDARD INTERNAL PUMP WILL NOT BE ALLOWED. PROVIDE VINYL TUBING TO DISCHARGE AS NOTED ON DRAWINGS, VERIFY

LENGTH.

4. PROVIDE PERMANENT WALL MOUNTED HARD WIRED THERMOSTAT IN SAME LOCATION AS THERMOSTAT REMOVED DURING DEMOLITION. LOOSE HAND HELD

WIRELESS REMOTE WILL NOT BE ALLOWED.

5. UNIT SERVES IDF/MDF ROOM AND IS DESIGNED TO BE COOLING ONLY UNIT. UNIT SHALL HAVE A LOWER COOLING SET POINT TO PREVENT UNIT FROM

OPERATING IN HEATING MODE.

6. PROVIDE NEEDLEPOINT BIPOLAR IONIZATION UNIT. NOT SHOWN ON DRAWINGS. SEE SPECIFICATIONS FOR MORE INFORMATION.

1. COOLING CAPACITY BASED ON 95ºF AMBIENT AIR TEMPERATURE AND HEATING AT 47ºF AMBIENT AND MATCHED WITH SCHEDULED DUCTLESS FAN COIL UNIT.

2. PROVIDE REFRIGERANT PIPING SIZED AND DESIGNED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTION. NOTE THAT BOTH REFRIGERANT LINES MUST BE INSULATED PER MANUFACTURER'S INSTRUCTIONS. PROVIDE INSULATED LINE SET, VERIFY EXACT LENGTH.

3. SCHEDULED CAPACITIES ARE OVERALL CAPACITIES REQUIRED FOR MATCHED CONDENSING UNIT/HEATPUMP AND EVAPORATOR COIL 2 # LINE LOSS.

4. PROVIDE INTEGRAL CONTROLS INCLUDING CONTACTORS, DEFROST BOARD (HEAT PUMP ONLY), CONTROL TRANSFORMER, ETC

5. UNIT SHALL UTILIZE R-410a REFRIGERANT. PROVIDE DC ROTARY COMPRESSOR WITH VARIABLE SPEED INVERTER TECHNOLOGY.

6. MOUNT ON EXISTING EQUIPMENT SUPPORT RAIL. SEE DUCTLESS UNIT ATOP EQUIPMENT SUPPORT RAIL DETAIL.

7. PROVIDE FACTORY WIND BAFFLE.

ROOFTOP UNITS

TAG

CARRIER

MODEL

NUMBER

TOTAL

COOLING MBH

SENSIBLE

COOLING MBH

TOTAL

SUPPLY CFM

O.A. CFM HEATER KW

APPROX.

E.S.P.

(IN.W.G.)

SUPPLY

FAN BHP

MINIMUM STAGES

COOLING ENTERING

CONDITIONS

MINIMUM

AMBIENT

COOLING TEMP

NOTES

COOLING HEATING E.A.T. D.B. °F E.A.T. W.B. °F

RTU-1 50GCQ05 44.8 35.6 1600 160 10.6 0.4 0.42 2 1 77.3 63.9 40 1:2:3:4:5:6:7:8:9:10:11:12:16:17

RTU-2 50GCQ05 44.8 35.6 1600 160 10.6 0.4 0.42 2 1 77.3 63.9 40 1:2:3:4:5:6:7:8:9:10:11:12:17:18

RTU-3 50GCQ04 30.7 20.9 800 75 4.9 0.3 0.11 2 1 77.0 64.4 40 1:2:3:4:5:6:7:8:9:10:11:12:16:17

RTU-4 50GCQ06 59.5 47.3 2000 150 10.6 0.4 0.75 2 1 76.6 64.1 40 1:2:3:4:5:6:7:8:9:10:11:12:17:18

RTU-5 EXISTING TO REMAIN - - - - - - - - - - - -

RTU-6 EXISTING TO REMAIN - - - - - - - - - - - -

RTU-7 EXISTING TO…

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
Award Information —