This document is a Salient Characteristics specification for the procurement and installation of replacement Computer Room Air Conditioning (CRAC) units and air-cooled chillers for a data center facility.
The procurement requires six (6) indoor downflow chilled water CRAC units (designated CRAC-01 through CRAC-06) and two (2) outdoor air-cooled scroll chillers (CH-1 and CH-2) operating in a parallel N+1 redundant configuration. The CRAC units must feature direct-drive, high-efficiency electronically commutated (EC) fans with air foil plug fan design, motors up to 15 HP, and external static pressure capability of minimum 0.75 inches water gauge. Cooling capacities range from 214.8 to 352.0 MBH depending on unit designation, with chilled water flows from 15 to 75 GPM and total airflow from 9,000 to 19,500 CFM. CRAC units must include high-capacity pleated filtration rated MERV 8 minimum. Each chiller must provide minimum 75-ton capacity at 110°F design ambient conditions, supply 233.3 GPM chilled water flow at 44°F leaving temperature, and achieve minimum 15.3 EER part-load efficiency. Chiller specifications include all-aluminum microchannel condenser coils with corrosion-resistant e-coat, direct-drive composite fans, low-ambient operation capability down to –20°F, and ANSI 316 stainless steel evaporators with factory freeze protection heaters.
All equipment must operate on 460V AC, 3-phase, 60 Hz power with minimum 65 kA short-circuit current rating. Piping must utilize type-L seamless copper or schedule 40 carbon steel with Victaulic-style mechanical couplings, supported by an inline centrifugal air separator, diaphragm-type expansion tank rated 150 psig, and 40-mesh Y-strainers at each chiller inlet. Both chillers and CRAC units require BACnet MS/TP or BACnet/IP communication for Building Management System integration, with chillers featuring integrated master/slave parallel control algorithms for automatic run-hour equalization and lead/lag staging. Indoor units must fit within existing Bravo 2000 floor grid constraints (24" x 24" panels, 18" raised floor height), and outdoor chillers must maintain minimum NEC clearances of 4 feet on electrical panel doors and 3.5 to 6 feet around condenser coils while not exceeding existing structural loading thresholds.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Note: the links and images in this document may point to external sources. Please review them before opening.
Salient Characteristics for Data Center CRAC & Chiller Replacement
1. General Scope This document outlines the salient characteristics and minimum requirements for the procurement, delivery, and installation of replacement Computer Room Air Conditioning (CRAC) units and the supporting outdoor Air-Cooled Chillers for the Data Center. The new equipment must meet or exceed the performance, capacity, footprint, and efficiency metrics of the legacy equipment as detailed in the facility’s as-built schedules.
The systems operate as an integrated chilled water loop where the outdoor chillers supply chilled water directly to the indoor CRAC units to maintain precise environmental conditions within the critical data center whitespace.
2. CRAC Equipment Overview The indoor mechanical replacement includes six (6) downflow Chilled Water (CHW) CRAC units currently servicing the data center.
• Equipment Tags: CRAC-01, CRAC-02, CRAC-03, CRAC-04, CRAC-05, and CRAC-
• Cooling Method: Chilled Water (CHILL WTR)
• Airflow Configuration: Downflow (for raised-floor distribution)
• Location: Indoor Data Center
2.1. CRAC Mechanical & Fan Specifications
• Fan Type: Air Foil Plug Fan (or modern equivalent high-efficiency, direct-drive
Electronically Commutated [EC] fans)
• Drive Type: Direct Drive (to minimize maintenance and belt-shedding particulates in the white space)
• Motor Capacity: Up to 15.00 HP (must match or exceed legacy CFM and static pressure requirements)
• External Static Pressure (ESP): Designed for a minimum of 0.75 in. w.g.
2.2. CRAC Cooling & Performance Capacities
Replacement CRAC units must support the varying airflow and cooling load profiles defined by the existing design baseline:
Unit Designation
Total Airflow
(CFM)
Entering Air Temp
(DB / WB /
RH)
Chilled Water Flow
(GPM)
Min. Total Capacity
(MBH)
Min.
Sensible Capacity
(MBH)
CRAC-01 17,500 72°F / 60°F
/ 50%
75.0 352.0 310.8
CRAC-02 19,500 72°F / 60°F
/ 50%
75.0 352.0 310.8
CRAC-03 16,000 72°F / 60°F
/ 50%
75.0 352.0 310.8
CRAC-04 17,500 72°F / 60°F
/ 50%
75.0 352.0 310.8
CRAC-05 9,000 67.4°F /
57.8°F / 50%
15.0 214.8 90.0
CRAC-06 9,000 67.4°F /
57.8°F / 50%
15.0 214.8 90.0
Chilled Water Coil Performance (Baseline):
• Entering Chilled Water Temperature: Ranging from 44.0°F to 54.4°F (depending on loop conditions)
• Maximum Air Pressure Drop Across Coil: 0.4 in. w.g.
2.3. CRAC Filtration Requirements
• Filter Type: High-capacity Pleated
• Efficiency Rating: MERV 8 minimum (providing at least 70% dust spot efficiency)
• Maximum Initial Pressure Drop: 0.23 in. w.g. @ 500 FPM
3. Chiller Equipment Overview The outdoor utility replacement includes two (2) high-efficiency, air-cooled, packaged scroll chillers operating in a parallel N+1 redundant configuration to supply the indoor CRAC loop Product Data 30RAP Air-Cooled Scroll Chiller | Carrier Building Solutions Middle East.
• Equipment Tags: CH-1 and CH-2
• Cooling Method: Air-Cooled Condenser Coils (utilizing environmentally friendly
HFC Puron R-410A or approved low-GWP refrigerants) Product Data
• Compressor Type: Hermetic Scroll (featuring multiple compressors per unit or digital scroll unloading to match partial load swings) Product Data
• Location: Outdoor Ground Pad / Chiller Yard
3.1. Chiller Performance & Capacity Specs
Each chiller must meet or exceed the performance capabilities of the legacy 75-Ton baseline units Product Data:
• Minimum Capacity (Tons): 75 Tons at design ambient conditions Product Data
• Design Outdoor Ambient Temperature: 110.0°F Product Data
• Chilled Water Flow Rate (GPM): 233.3 GPM per chiller Product Data
• Leaving Chilled Water Temperature (LVT): 44.0°F Product Data
• Entering Chilled Water Temperature (ENT): ~51.7°F to 52.0°F (yielding a design Delta T of approx. 7.7°F)
• Maximum Evaporator Pressure Drop: 21.2 ft wg (approx. 9.2 psi) Product
Data
• Minimum Part-Load Efficiency (IPLV): 15.3 EER or better Product Data https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://www.carrier.com/commercial/en/kw/products/commercial/chillers/30rap/ https://www.carrier.com/commercial/en/kw/products/commercial/chillers/30rap/ https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf
3.2. Chiller Mechanical & Condenser Specifications
• Condenser Coils: All-aluminum microchannel (MCHX) technology to reduce overall refrigerant charge and operating weight Product Data. Coils must feature protective corrosion-resistant e-coat encapsulation to ensure durability in outdoor environments Product Data.
• Condenser Fans: Direct-drive, low-sound composite AeroAcoustic vertical discharge fans with protective wire safety guards Product Data.
• Low-Ambient Operation: Standard operation down to –20°F ambient (requiring integrated head-pressure fan controls and factory-installed wind baffles) to support winter-time data center cooling loads Product Data.
• Evaporator: Single-pass, brazed plate direct expansion heat exchanger constructed of ANSI 316 stainless steel Product Data, insulated with 3/4-in.
closed-cell foam and wrapped with factory freeze protection heaters down to - 20°F Product Data.
4. Electrical Requirements (All Equipment) All indoor and outdoor mechanical systems must be fully compatible with the facility's existing electrical infrastructure:
• Operating Voltage: 460 V AC
• Phase/Frequency: 3 Phase / 60 Hz
• Power Connection: Single-point electrical connection at each unit-mounted terminal block or integrated non-fused disconnect switch Product Data.
• Chiller Safety Locks: Electrical components must have high short-circuit current ratings (minimum SCCR of 65 kA) to protect internal motor circuits Product Data.
5. Piping, Hydronics & Loop Infrastructure The mechanical contractor must align replacement piping and accessories with the parallel N+1 as-built hydraulic schematic:
• Common Chilled Water Header Flow: Sized for a combined maximum design flow of 466.0 GPM.
https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf
• Piping Material: Type-L seamless copper tubing or schedule 40 carbon steel piping with Victaulic-style mechanical couplings to isolate structural vibrations Product Data.
• Air Separator: Inline centrifugal-type air separator with automatic air vents installed at the system's highest and warmest return points to prevent loop cavitation Product Data.
• Expansion Tank: Diaphragm-type expansion tank, pre-charged and rated for a maximum system working pressure of 150 psig, located on the suction side of the pumps Product Data.
• Water Filtration: A 40-mesh Y-strainer with an integrated blow-down ball valve must be installed at each chiller's evaporator inlet Product Data.
6. Controls & BMS Integration Both the chillers and the CRAC units must have robust, open-protocol communication cards to integrate seamlessly with the existing Building Management System (BMS):
• Protocols Supported: Native BACnet MS/TP or BACnet/IP over Ethernet Product Data.
• Chiller Plant Automation: The chillers must feature an integrated master/slave parallel control algorithm Product Data. The controller must automatically equalize compressor run hours, manage lag chiller staging based on loop temperature reset metrics, and immediately switch leads in the event of a primary circuit fault Product Data.
• CRAC Controls: Local microprocessor screens displaying entering/leaving water temperatures, air temperatures, fan status, and alarm history (up to the last 20 alarm logs) Product Data.
• BMS Control Points Required:
• Entering/Leaving Chilled Water Temperature Product Data.
• Compressor and Pump run hours / start count Product Data.
• Flow switch verification alarm Product Data.
• Water pressure drop calculations (via factory-installed pressure transducers) Product Data.
• Dynamic demand-limiting status (load shedding) Product Data.
https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf
7. Footprint & Site Coordination
• Indoor Footprint Constraints: CRAC replacement units must fit entirely within the structural limits of the existing Bravo 2000 floor grid (24" x 24" floor panel dimensions, 18" raised floor height).
• Outdoor Pad Clearances: Chillers must fit on the existing concrete equipment pad while maintaining National Electrical Code (NEC) clearances (minimum 4.0 ft clearance on electrical panel doors and 3.5 ft to 6.0 ft airflow clearance around condenser coils) Product Data.
• Weight Constraints: Replacement units must not exceed the structural loading thresholds of the existing pad and floor panel pedestals.
https://media.ptsdcs.com/wpp/Carrier/AquaSnap%2030RAP%20Product%20Data%20Sheet.pdf
| Salient Characteristics for Data Center CRAC & Chiller Replacement |
| 1. General Scope |
| 2. CRAC Equipment Overview |
| 2.1. CRAC Mechanical & Fan Specifications |
| 2.2. CRAC Cooling & Performance Capacities |
| 2.3. CRAC Filtration Requirements |
| 3. Chiller Equipment Overview |
| 3.1. Chiller Performance & Capacity Specs |
| 3.2. Chiller Mechanical & Condenser Specifications |
| 4. Electrical Requirements (All Equipment) |
| 5. Piping, Hydronics & Loop Infrastructure |
| 6. Controls & BMS Integration |
| 7. Footprint & Site Coordination |
File details come from the government source that posted it. Updated .