Site Description Center: DENISON (00702)

Page: 1 Date: 04/22/2008

ACCESSIBILITY

Yes

The site has limited accessibility due to slopes.Comments:

NoNoNoNo

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Drain System Soil Erosion Soil Erosion Location

No NoneUnderground

Comments:

Paving Type for Roads & Parking

There are concrete sidewalks with steps throughout the center.

Paving Type for Sidewalks

Asphalt Concrete

Comments:

Structures Fencing Outdoor Recreation

Five Storage Structures, Four Gazebos, Cook Out Shelter, Ball Field Booth

Chain Link, Wood Fence Field, Playground, Soft/Baseball

The concrete retaining walls are located at the west side of Recreation Building 21 and at the west side of Building

3. The sport field is enclosed by chain link fence.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water

Treatment Type Storage Type Storage Capacity Maintenance Responsibility

Center

NoMasterDenison Municipal UtilitiesPublic Water Authority

None 0None

Fire Hydrants On-Site Water Supply Storage Capacity Pressure Source # of Fire Pumps

Yes 0 0None Municipal

Sewage Treatment Sewer Line Owner

N/APublicly Owned Treatment Works CenterCenter

Maintenance ResponsibilityCapacity(Gallons)

Accessible Parking: Accessible Slope:

No

Curb Cuts:

No

Ramps:

NoNo

Site Accessible Route:

HISTORIC PRESERVATION

STORM WATER SYSTEM Number of Deficiencies = 2

Number of Deficiencies = 1SITE FEATURES

UTILITY

3. Sanitary Sewer System/ Sewage Treatment Plant

2. Fire Protection

Page: 2 Date: 04/22/2008

Natural

None

Comments:

Electric Company

PCB

Trans.

Transformer Mounting

Transformer Ownership

Systems Ownership

Maintenance Responsibility

Denison Municipal Utility Company

The majority of the primary distribution on center was upgraded by the utility company in 2003. Primary power dips underground where it enters the site from an overhead switch located west of Building 17 and Opportunity Drive.

Most distribution on the site is now distributed underground utilizing pad-mounted sectionalizing switches and pad-mounted transformers. There is an additional 13.2/7.6 kV underground feeder on center providing power to the gym as of the November 2005 Facility Survey. The utility is planning to convert the recently upgraded 4.16 kV distribution on center and change the incoming voltage to 13.2 kV, then to tie the two services together effectively loop feeding the center from two locations, all within the next ten years. Metering on center is a mix of primary and secondary, zoned and individual building meters. Storage buildings by the ball field, adjacent to HWY 30, are fed overhead from a pad-mounted transformer located where the property borders a small private college. Building 1 has the only 480/277V service on center. There is one center-owned generator, with both standby and life-safety automatic transfer switches, located at Building 1 and installed in 2004. The utility company owns and maintains most pole-mounted, photocell-controlled high intensity discharge security lights on center. The ball field has sports lighting for evening use.

Pole and Pad Utility, Center Utility, Center Utility, CenterNo

Comments:

Telephone Company On-site Line Owner

There is a site siren for site emergencies, located at Building 1. Fire alarm panels of Buildings 1, 2, 3, 10, 13, 17 and 21 are connected to a central annunciator panel located in Security Building 10. There are two T1 communication lines provided by Frontier, which enter at Building 4. Most buildings on center are connected by fiber utilizing VoIP for telephone and data. CCTV cameras are located throughout Dormitory Building 17 and are monitored in the RA offices for their respective zones. Security Building 10 also has CCTV cameras. Some buildings on center have cable TV and some have a satellite dish.

Frontier Telephone Company

Maint. Responsibility

Center Center

Security

CCTV Cameras, Black and White Monitors

06/01/1992

06/01/1992

Center

Center

Active

Active

Aboveground

Aboveground

Adjacent to Building

Adjacent to Building

Yes

Yes

Petroleum - Gasoline

Petroleum - Diesel Fuel

STORAGE TANK

TypeStatus Location Owner Fuel Type Capacity Install Date

4.16/2.3 kV, 3-Phase, 4 Wire

120/208V, 1&3-Phase and 120/240V, 1-PhaseOverhead & Underground

Overhead & UndergroundPrimary Service

Secondary Service

Distribution Characteristics

ID

Reg.

4. Gas

5. Central Plant

6. Electric

7. Communication

Purpose

Page: 3 Date: 04/22/2008

Earthquake Risk

Low Low LowMedium HighIBC Low

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Hail storms are common in this area.Comments:

GENERAL SITE CONDITION

Rating X Good Fair Poor

NATURAL HAZARDS

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.