building_descriptions.pdf
PDF 284 KB Posted
- Attached to
- Operation of the Denison Job Corps Center
- Solicitation number
- DOLJ09RA00024
About this file
Attachment J-19 - Facility Survey Vol II
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SF30 AMENDMENT No. 1 to RFP-Denison_00024.doc | DOC document | |
| Property List_J-13.pdf | ||
| deficiency_text.pdf | ||
| acm_inventory.pdf | ||
| Denison00024_RFP_FINAL_6-4-08.doc | DOC document | |
| Denison00024_MPO35 MSO20_J-20.pdf | ||
| Denison00024_CTT 10_J-20.pdf | ||
| energy_management.pdf | ||
| asset_management.pdf | ||
| Denison00024_inventory Estimate_J-23.doc | DOC document | |
| Denison00024_Workforce Investment Goals_J-7.pdf | ||
| Denison00024_Site Map_J-14.pdf | ||
| building_structures.pdf | ||
| site_description.pdf | ||
| PRH Regional Supplement 032007_w revised GAP_J-22.doc | DOC document | |
| Denison00024_Space Itilization Table_J-12.pdf | ||
| Denison00024_Itilities Fuel Usage_J-8.doc | DOC document | |
| Natl Compensation Model _Denison00024_J-17.xls | XLS spreadsheet | |
| o_and_m_deficiencies.pdf | ||
| environmental_management.pdf | ||
| Denison00024_OMS 10_J-20.pdf | ||
| Denison Facility Survey Report_Vol I_J-19.pdf |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building Descriptions Date: Apr. 22, 2008Center : Denison (00702) Page: 1 of 80
Building: 0001 - ADMINISTRATION/ACADEMICS/DINING
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry CMU Masonry
Wall Roof Rigid Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business/Assembly 36,820 26,013 3 Owned 1965 Unevaluated
Comments: Second egress is available at the basement and first floor, but not on the second floor. Top landing at the second floor north stairs has inadequate wheelchair maneuvering space.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
No
Yes
Yes
Yes
No
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material Drainage Year Life
Remaining Type Area Served
Metal
EPDM
Gutters and Downspouts
Gutters and Downspouts
Gable
Flat
Addition to Dining Hall
Original Building
3. Roof
Entire Building
Area Served
Page: 2 of 80
Building: 0001 - ADMINISTRATION/ACADEMICS/DINING
INTERIOR FINISH
Carpet Ceramic Tile Concrete Porcelain Tile Vinyl Tile Wood
CMU Ceramic Tile Drywall Fiberglass Plaster
Metal Unit - Metal Frame Wood Unit - Wood Frame
Wood Unit w/ Sidelight - Wood Frame
VERTICAL CIRCULATION
Metal Pan w/Concrete Stairs
Metal Unit w/Sidelight - Metal Frame Metal Units - Metal Frame Storefront - Metal Frame Wood Units - Wood Frame
Casement - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Fixed - None Frame; Glass Block Glazing; Sliding - Wood Frame; Double Glazing;
Acoustical Tile Exposed Metal Roof Deck Gypsum Board
Number of Deficiencies = 2
Exterior Doors5. Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Each of the three floors in the main building is served by a multi-zone air handler (Trane #SAMZ304A, five zones, 7-1/2 HP fan motor). The basement unit is 100% outdoor air. The auditorium is served by a similiar system. The source of the heat is two water boilers built by Thermal Solutions (#EVA1000BN1- UAA, 880 MBH output). The water is circulated by two pumps (one as standby) built by Taco (15 HP each).
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Multi- Zone/Single
AHU
Two-Pipe Pneumatic Mechanical None Entire Building
Ceilings
Page: 3 of 80
Building: 0001 - ADMINISTRATION/ACADEMICS/DINING
Mechanical
Mechanical
Restroom
Kitchen
Comments:
Comments:
The restrooms are exhausted by rooftop fans.
The kitchen is ventilated by two kitchen hood exhaust fans. This air is made-up by a supply fan (Trane #T20-B). Each doorway from the dining hall and kitchen to the outdoors is served by an air curtain built by Mars.
The domestic water heater was built by Rheem (#G50-60N, 60 MBH input, 50 gallon tank, built 12/2002)). There are also two water heaters (Rheem #G65-440A, 400 MBH input, 65 gallon tank, built in 1996) dedicated to the kitchen dishwashers.
Comments:
Cast Iron, PVC Indoor None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Service Sink Shower Sink Urinal Water Closet (Tank)
Gas (Natural)
Wet None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: There are wet chemical systems for the kitchen hoods.
Ventilation Area Served
Copper Copper Gas-Fired Building Water Softener No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Multi- Zone/Single
AHU
Refrigerant Pneumatic Mechanical Economizer Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
Each of the three floors in the main building is served by a multi-zone air handler (Trane #SAMZ304A, five zones, 7-1/2 HP fan motor). The basement unit is 100% outdoor air and the other two are equipped with an economizer mode. The source of the cooling is a reciprocating compressor (#2F5D68) packaged in each air handler and an associated condenser unit (Trane #CA-3008) on the roof. The auditorium is served by a similiar system.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 1
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 4 of 80
Building: 0001 - ADMINISTRATION/ACADEMICS/DINING
Comments: 480/227V service is brought from an underground transformer vault, just east of the building's southeast corner, to a two-section switchboard with 1200A main switch fused at 1200A. Dry-type transformers within the building provide 120/208V, 3-phase, 4-wire service. The building has an 85 kW Onan natural gas generator, installed in 1994, complete with both standby and life safety transfer switches, for critical control power and life safety loads. Most lighting is 277V.
FIRE ALARM
Comments: The fire alarm panel is an FCI model. This panel reports to the fire alarm central annunciator panel in Security Building 10.
Comments: The building is connected to the center LAN system (VoIP network) for both telephone and data communications. Locally annunciating door alarms are utilized for unauthorized egress. The auditorium has a video and sound room.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
Comments: The recorded footcandle levels include natural light contribution. The food preparation area and serving lines have an average of 40 foot candles.
High Intensity Discharge (HID)
Comments: Exterior lighting is controlled by photocells.
LIGHTING
T12 - Fluorescent
T12 - Fluorescent
Incandescent
T12 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Storage/Warehouse-Active
Medical/Dental
Storage/Warehouse-Active
Offices
Classrooms
Food Preparation
Area Recommended Level
Recorded Level Light Type
Generator Backup Generator Backup
Switchboard 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Electric Water Gas No YesNo
BUILDING UTILITY METERING
Page: 5 of 80
Building: 0001 - ADMINISTRATION/ACADEMICS/DINING
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Fair Interior: Good Mechanical: Fair Electrical: Good
Page: 6 of 80
Building: 0002 - VOCATIONAL/GYMNASIUM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry Metal Siding
Wall Roof Rigid Fiberglass
Metal Overhead - Metal Frame Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Industrial/Assembly 22,950 18,294 1 Owned 1980 Unevaluated
Comments: Some visual alarms are provided along egress pathways.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
No
Yes
Yes
N/A
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Gutters and downspouts are only on the west side of the vocation building. The east side has runoff drainage.
Drainage Year Life
Remaining Type Area Served
Metal
Metal
Gutters and Downspouts
Gutters and Downspouts
Gable
Gable
Gymnasium
Shop Area
Comments:
3. Roof
Page: 7 of 80
Building: 0002 - VOCATIONAL/GYMNASIUM
Comments: Single glazed windows are interior windows. There are no exterior windows.
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Brick Ceramic Tile Drywall Glass Block Metal
Metal Units - Metal Frame Wood Units - Wood Frame
VERTICAL CIRCULATION
Wood Ladder
Comments: The ladder is from the paint shop to the open attic.
Fixed - Aluminum Frame; Single Glazing; Sliding - Aluminum Frame; Single Glazing;
Exposed Structure Gypsum Board
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A heating only air handling unit (Trane #CCDA143L06, 7-1/2 HP fan motor) located in the mechanical room serves the classroom and shop areas. There are four hot water Trane heating and ventilating ceiling-hung units serving the separate needs in the shop areas. The source of the heat for all heating units in the building is a hot water boiler (Burnham #4FW.563A3.50.LB, 3769 MBH output) located in the mechanical room. Two pumps circulate water to the heating units.
Offices and classrooms have through-wall heat pumps that use shop area air as evaporator air to absorb heat from the shop.
A heating only air handling unit (Trane #LAL7-B) located in the mechanical room serves the gymnasium.
There are three ceiling-hung hot water unit heaters serving as spot heaters.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Heat Pump
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Single Duct
Through-The- Wall Unit
Single Duct
Unit Heater
Two-Pipe
None
Two-Pipe
None
Pneumatic
Electric
Pneumatic
Electric
Mechanical
Natural
Natural
Natural
None
None
None
None
Shop Area
Classrooms and Offices
Gymnasium
Shop Area
Page: 8 of 80
Building: 0002 - VOCATIONAL/GYMNASIUM
Mechanical
Mechanical
Fume Collection
Mechanical
Restroom
Shop Area
Welding Booths
Gymnasium
Comments:
Comments:
The exhaust system serves 16 welding stations.
There is a small rooftop exhaust fan on the roof that is interlocked with a 6 ft. x 7-1/2 ft. motorized damper at a wall louver at floor level.
The water heater was built by Ruud (#RFD86-250A, 250 MBH input, 86 gallon tank).Comments:
Cast-Iron, PVC None None
Electric Water Cooler Emergency Eye Wash Hose Bibb Lavatory Multi-Compartment Sink Service Sink Shower Urinal Water Closet (Tank)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Heat Pump Through-The- Wall Unit
None Electric Natural None Classrooms and Offices
PLUMBING
Exhaust Ventilation
Offices and classrooms have through-wall heat pumps that use shop area air as condenser air to reject heat to the shop.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 3
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 9 of 80
Building: 0002 - VOCATIONAL/GYMNASIUM
None None ABC Type Fire Extinguisher
Comments: 120/208V service is brought underground from a pad-mounted transformer, located just west of the building, to an 800A rain-tight main disconnect located on the building's west exterior wall. In addition to a switchboard and panelboards, the educational section of the building uses plug-in-type bus duct for power distribution. The service has transient voltage surge protection.
FIRE ALARM
Comments: The fire alarm panel is an FCI model. This panel reports to the fire alarm central annunciator panel in Security Building 10.
Comments: The building is connected to the center LAN system (VoIP network) for both telephone and data communications. Locally annunciating door alarms are utilized for unauthorized egress.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm None None
Telephone Security Public Address Television
High Intensity Discharge (HID)
Comments: Building-mounted exterior lighting is controlled by a mechanical timeclock.
LIGHTING
T12 - Fluorescent
High Intensity Discharge (HID)
T12 - Fluorescent
T8 - Fluorescent
Incandescent
T12 - Fluorescent
Classrooms
Recreation
Offices
Classrooms
Storage/Warehouse-Active
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Disconnect Switch 120/208V, 3-Phase, 4 Wire Switchboard, Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Page: 10 of 80
Building: 0002 - VOCATIONAL/GYMNASIUM
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Roof leaks in several locations. Toilets are deteriorated. Exterior siding is deteriorated.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesNo
Structure: Good Exterior: Fair Interior: Fair Mechanical: Fair Electrical: Good
Page: 11 of 80
Building: 0003 - DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry
Wall Roof Batt Rigid
Metal Unit w/Transom Panel - Metal Frame Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 51,450 27,243 3 Owned 1965 Unevaluated
Comments: The stair configuration at the east and west dormitory wings does not meet accessibilty criteria. Some visual alarms are provided along egress pathways.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
No
No
Yes
Yes
No
No
No
No
No
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Gutters and Downspouts 1996 12 Flat Entire Building
3. Roof
Page: 12 of 80
Building: 0003 - DORMITORY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Brick CMU Carpet Ceramic Tile Drywall Mirror Wood Panel
Metal Units - Metal Frame Sliding Glass Door - Metal Frame
Wood Unit - Metal Frame Wood Units - Wood Frame
VERTICAL CIRCULATION
Metal Pan w/Concrete Stairs
Fixed - Metal Frame; Double Glazing; Single Hung - Metal Frame; Double Glazing;
Sliding - Wood Frame; Double Glazing;
Acoustical Tile Gypsum Board Plaster
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Page: 13 of 80
Building: 0003 - DORMITORY
Mechanical Toilet/Shower
Ventilation Area ServedExhaust Ventilation
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The common areas, such as recreation and lounge areas, are served by packaged gas-fired rooftop units ranging in capacity from 36 MBH to 80 MBH input, typical of these units is a York #D6CG060NO7925B and manufactured in the mid 1990s. Four of the eight units are equipped with minimum outside air.
The corridors are served by electric baseboard heaters.
The dorm rooms and resident advisors' offices are served by McQuay through-the-wall heat pumps (#MQR007C0321SL1Y, 7 MBH heat with 2.8 kW supplementary electric heaters).
A counselor's office and the staff lounge at the interior of the building are served by EMI ductless split system heat pumps (approximatly 18 MBH heat).
These units are mounted on the surface of the ceiling.
Comments:
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Packaged Heat Pump (Air Source)
Electric Resistance
Electric Resistance
Packaged Heat Pump (Air Source)
Split Heat Pump (Air Source)
Electric Resistance
Gas-Fired Furnace
Fan Coil
Radiant Panel
Baseboard Heaters
Through-The- Wall Unit
Fan Coil
Unit Heater
Single Duct
Refrigerant
None
None
None
Refrigerant
None
None
Electric
Electric
Electric
Electric
Electric
Electric
Electric
Natural
Natural
Natural
Mechanical
Natural
Natural
Natural
None
None
None
None
None
None
None
Common Area
Bathrooms
Common Area
Dorm Rooms
Offices
Bathrooms
Recreation Area
Ventilation2.
Page: 14 of 80
Building: 0003 - DORMITORY
The domestic hot water is supplied by a Raypack (#WH1-0824, max input 825 MBH) gas-fired water heater that supplies a 250 gallon water storage tank. The other three gas-fired water heaters were manufactured in 1990 by Rheem (#RF250-76A, 250 MBH, 76 gallon tank) and supply hot water to the laundry rooms and the two large commercial washers in the mechanical room. There are also two electric water heaters (Rheem #EGS54-120-G, 56 kW, 120 gallon tank) that are not in operation and serve as standby.
Comments:
Cast Iron, PVC None None
Bathtub Electric Water Cooler Hose Bibb Lavatory Shower Urinal Water Closet (Tank)
Gas (Natural)
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Heat Pump
Packaged Heat Pump (Air Source)
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Through-The- Wall Unit
Single Duct
Fan Coil
Fan Coil
None
None
Refrigerant
Refrigerant
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Natural
Natural
None
None
None
None
Dorm Rooms
Common Area
Recreation Area
Offices
PLUMBING
The dorm rooms and resident advisor offices are served by McQuay through-the-wall heat pumps (#MQR007C0321SL1Y, 7 MBH cooling capacity).
The common areas, such as recreation and lounge areas, are served by packaged rooftop units ranging in capacity from 3 tons to 5 tons nominal cooling capacity; typical of these units is a York #D6CG060NO7925B manufactured in the mid 1990s. Four of the eight units are equipped with minimum outside air.
The two systems serve the pool room and weight room.
A counselor's office and the staff lounge at the interior of the building are served by EMI ductless split system heat pumps (1-1/2 tons cooling capacity).
Comments:
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 15 of 80
Building: 0003 - DORMITORY
None None ABC Type Fire Extinguisher
Comments: The extinguishers are inspected monthly.
Comments: Underground electrical service is brought to the basement electrical room, where it feeds a 2000A switchboard with 2000A main circuit breaker and fuse type distribution. The service has transient voltage surge protection.
FIRE ALARM
Comments: The fire alarm panel is an FCI model. This panel reports to the fire alarm central annunciator panel in Security Building 10.
Comments: Pay phones are provided. The building is connected to the center LAN system (VoIP network) for both telephone and data communications. Locally annunciating door alarms are utilized to detect unauthorized egress.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm None Local Cable Company
Telephone Security Public Address Television
Comments: The recorded footcandle levels include natural light contribution. T12-fluorescent fixtures are also utilized in some storage and support areas. Corridors have compact fluorescent fixtures.
Comments: Central batteries are used for most emergency lighting.
High Intensity Discharge (HID) Incandescent
Comments: Exterior HID lights are each controlled by an individual integral photocell. Incandescent lights are switched.
LIGHTING
T12 - Fluorescent
T12 - Fluorescent
Incandescent
T12 - Fluorescent
Offices
Sleeping Rooms
Storage/Warehouse-Active
Recreation
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
COMMUNICATION
Page: 16 of 80
Building: 0003 - DORMITORY
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The dormitory finishes are deteriorated. Rooms are dark. Doors are damaged and worn. Restrooms are poorly ventilated. Temperature control is poor.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesNo
Structure: Good Exterior: Good Interior: Fair Mechanical: Fair Electrical: Good
Page: 17 of 80
Building: 0004 - VOCATIONAL/MAINTENANCE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry
Wall Roof Rigid Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 15,770 10,860 1 Owned 1965 Unevaluated
Comments: Restrooms in HOT and BOT area are functionally accessible. Some visual alarms are provided along egress pathways.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
Yes
N/A
Yes
Yes
Yes
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material Drainage Year Life
Remaining Type Area Served
Membrane
Asphalt Shingles
Gutters and Downspouts
Gutters and Downspouts
Flat
Gable
Original Building
Storage Addition
3. Roof
Page: 18 of 80
Building: 0004 - VOCATIONAL/MAINTENANCE
INTERIOR FINISH
Carpet Concrete Terrazzo Vinyl Tile Wood
Brick CMU Ceramic Tile Drywall Wood Panel
Aluminum Storefront - Aluminum Frame Wood Units - Metal Frame
Wood Units - Wood Frame
VERTICAL CIRCULATION
Metal Stairs
Comments: The stairs lead from BAM to the west entrance.
Metal Overhead - Metal Frame Metal Overhead - Wood Frame Metal Units - Metal Frame Wood Unit - Metal Frame
Fixed - Aluminum Frame; Double Glazing; Fixed - Steel Frame; Glass Block Glazing;
Fixed w/Mesh - Aluminum Frame; Double Glazing;
Gypsum Board
Exterior Doors5.
Windows6.
Floors1.
Interior Walls2.
3.
Page: 19 of 80
Building: 0004 - VOCATIONAL/MAINTENANCE
Mechanical Restroom
Ventilation Area Served
Packaged Direct
Expansion (Air Source)
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Window Unit
Unit Ventilator
Fan Coil
None
Refrigerant
Refrigerant
Electric
Electric
Electric
Mechanical
Natural
Natural
None
None
None
Offices
Classrooms
Offices
Exhaust Ventilation
Several offices are served by through wall heat pumps.Comments:
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Hot water unit heaters are also located in the maintenance areas. All units are provided heating water by two 1-1/2 horsepower B&G pumps circulating water through four gas-fired Weil McLain boilers.
Radiant panels are also located in the mechanical room. All units are provided heating water by two 1- 1/2 horsepower B&G pumps circulating water through four gas-fired Weil McLain boilers.
All units are provided heating water by two 1-1/2 horsepower B&G pumps circulating water through four gas-fired Weil McLain boilers built in 1983.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Baseboard Convector
Radiant Panel
Unit Ventilator
Two-Pipe
Two-Pipe
Two-Pipe
Electric
Electric
Pneumatic
Natural
Natural
Mechanical
None
None
None
Offices
Bathrooms
Entire Building
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 20 of 80
Building: 0004 - VOCATIONAL/MAINTENANCE
Domestic hot water is provided by a B&G pump circulating water through a Rheem (#81KR41D, 4.5 kW, 40 gallon) water heater and a return piping loop.
Comments:
Cast Iron, PVC None None
Electric Water Cooler Emergency Eye Wash Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: The extinguishers are inspected monthly.
Comments: The underground service is brought to an 800A main distribution panel with 450A main circuit breaker.
The service has transient voltage surge protection.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: The recorded footcandle levels include natural light contribution. The BAM shop and associated classroom have an average of 50 footcandles.
High Intensity Discharge (HID) Incandescent
Comments: Exterior HID lights are each controlled by an individual integral photocell. Incandescent lights are switched.
LIGHTING
T12 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
Offices
Classrooms
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Page: 21 of 80
Building: 0004 - VOCATIONAL/MAINTENANCE
FIRE ALARM
Comments: The fire alarm panel is an FCI model.
Comments: Two T1 communication lines are brought into this building from the service provider. Most buildings on center are connected by fiber utilizing VoIP for voice and data.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesNo
Structure: Good Exterior: Good Interior: Fair Mechanical: Fair Electrical: Good
Page: 22 of 80
Building: 0005 - PAINT SPRAY BOOTH
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry EIFS
Wall Roof None None
Metal Overhead - Metal Frame Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Factory/Industrial 900 850 1 Owned 1999 Unevaluated
Comments: The threshold at the north entrance to the building is six inches in height.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
N/A
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 1999 14 Gable Entire Building
3. Roof
Page: 23 of 80
Building: 0005 - PAINT SPRAY BOOTH
INTERIOR FINISH
Concrete
Drywall Fiberglass
None
Natural Entire Building
Comments: A paint spray booth in the shop is equipped with a downdraft air recirculation system (Sorben Control Technologies #5-15DO).
Ventilation Area Served
VERTICAL CIRCULATION
None
None
None None None None Natural None Entire Building
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The four Chromalox heaters (two #FTEP-3, 3 kW and two #CVEP-C-76-83-32-00, 7.6 kW) are explosion proof for Class 1, Group D hazardous locations.
Comments:
HVAC
Heat1.
Electric Resistance
Convector None Electric Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 24 of 80
Building: 0005 - PAINT SPRAY BOOTH
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: The extinguishers are inspected monthly.
Comments: The underground service is brought to a 200A loadcenter with 200A main circuit breaker. The loadcenter is located in the storage room having only direct exterior access, along with the only receptacle. Shop electrical systems are explosion proof.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: The recorded footcandle levels include natural light contribution. Lighting fixtures and the switch in the shop are explosion proof.
High Intensity Discharge (HID)
Comments: Exterior lights are each controlled by an individual integral photocell.
LIGHTING
T12 - Fluorescent
T12 - Fluorescent
Classrooms
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Main Loadcenter 120/208V, 3-Phase, 4 Wire Service Equipment Only Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 25 of 80
Building: 0005 - PAINT SPRAY BOOTH
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
None None
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/ANo
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Page: 26 of 80
Building: 0007 -QUONSET VOCATIONAL STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Corugated Metal
Wall Roof None None
Metal Overhead - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Storage 5,080 4,582 1 Owned 1957 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
N/A
N/A
Yes
No
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The roof is integrated in the structure, with 50 years of life expectancy. New protective coating was installed in 2002 to extend the roof life.
Drainage Year Life
Remaining Type Area Served
Corrugated Metal Surface Run-off 1957 5 Barrel Entire Building
Comments:
3. Roof
Page: 27 of 80
Building: 0007 -QUONSET VOCATIONAL STORAGE
INTERIOR FINISH
Concrete Plywood
CMU
Metal Overhead - Metal Frame Metal Units - Metal Frame
Natural Entire Building
Comments: There are three gravity roof vents mounted on the roof ridge.
Ventilation Area Served
VERTICAL CIRCULATION
Wood Stairs
Comments: The stairs lead to the mezzanine level.
Louver - Steel Frame; No Glazing;
None None None None Natural None Entire Building
Exposed Structure
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 28 of 80
Building: 0007 -QUONSET VOCATIONAL STORAGE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: The building is fed overhead from a pad-mounted transformer located near the bordering property line of a small college. The main panel has a 100A main circuit breaker and fuse-type distribution. The meter is located on the exterior wall of the building.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None
LIGHTING
Incandescent10Storage/Warehouse-Active 30
Area Recommended Level
Recorded Level Light Type
None None
Main Fuse Panel 120/240V, 1-Phase, 3 Wire Service Equipment Only Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Page: 29 of 80
Building: 0007 -QUONSET VOCATIONAL STORAGE
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
X Good Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/AYes
BUILDING UTILITY METERING
Structure: Fair Exterior: Fair Interior: Fair Mechanical: Fair Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan.
DEMOLITION RECOMMENDATION
Page: 30 of 80
Building: 0008 - QUONSET PROPERTY STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Corrugated Metal
Wall Roof None None
Metal Overhead - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Storage 4,100 3,860 1 Owned 1957 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The roof has holes. Demolition of this building is recommended.
Drainage Year Life
Remaining Type Area Served
Corrugated Metal Surface Run-off 1957 0 Barrel Entire Building
Comments:
3. Roof
Page: 31 of 80
Building: 0008 - QUONSET PROPERTY STORAGE
INTERIOR FINISH
Concrete
CMU
Wood Overhead - Metal Frame Wood Units - Metal Frame
Natural Entire Building
Comments: There are three gravity roof vents mounted on the roof ridge.
Ventilation Area Served
VERTICAL CIRCULATION
None
Louver - Steel Frame; No Glazing;
None None None None Natural None Entire Building
Acoustical Tile Exposed Structure
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 32 of 80
Building: 0008 - QUONSET PROPERTY STORAGE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: The building is fed overhead from a pad-mounted transformer located near the bordering property line of a small college. The main loadcenter has a 60A main circuit breaker. The meter is located on the exterior wall of the building.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Incandescent lighting is also used within the building.
High Intensity Discharge (HID)
Comments: There is one exterior HID light with a photocell.
LIGHTING
T12 - Fluorescent10Storage/Warehouse-Active 30
Area Recommended Level
Recorded Level Light Type
None None
Main Loadcenter 120/240V, 1-Phase, 3 Wire Service Equipment Only Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Page: 33 of 80
Building: 0008 - QUONSET PROPERTY STORAGE
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Quonset roof and walls are leaking in numerous locations.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/AYes
BUILDING UTILITY METERING
Structure: Fair Exterior: Poor Interior: Poor Mechanical: Fair Electrical: Good
Page: 34 of 80
Building: 0009 - QUONSET FACILITIES STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Corrugated Metal
Wall Roof None None
Metal Overhead - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Storage 4,100 3,850 1 Owned 1957 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
N/A
N/A
N/A
No
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The roof is integrated in the structure with 50 years of life expectancy. New protective coating was installed in 2002 to extend the roof life.
Drainage Year Life
Remaining Type Area Served
Corrugated Metal Surface Run-off 1957 5 Barrel Entire Building
Comments:
3. Roof
Page: 35 of 80
Building: 0009 - QUONSET FACILITIES STORAGE
INTERIOR FINISH
Concrete
CMU
None
Natural Entire Building
Comments: There are three gravity roof vents mounted on the roof ridge.
Ventilation Area Served
VERTICAL CIRCULATION
Wood Stairs
Comments: The stairs are to the mezzanine level.
Louver - Steel Frame; No Glazing;
None None None None Natural None Entire Building
Exposed Structure
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 36 of 80
Building: 0009 - QUONSET FACILITIES STORAGE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: The building is fed overhead from a pad-mounted transformer located near the bordering property line of a small college. The main loadcenter has a 60A main circuit breaker. The meter is located on the exterior wall of the building.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None
LIGHTING
Incandescent15Storage/Warehouse-Active 30
Area Recommended Level
Recorded Level Light Type
None None
Main Loadcenter 120/240V, 1-Phase, 3 Wire Loadcenter Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Page: 37 of 80
Building: 0009 - QUONSET FACILITIES STORAGE
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
X Good Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/AYes
BUILDING UTILITY METERING
Structure: Fair Exterior: Fair Interior: Fair Mechanical: Fair Electrical: Good
Page: 38 of 80
Building: 0010 - SECURITY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Brick Masonry
Wall Roof Batt Batt
Metal Units - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 2,030 1,532 1 Owned 1984 Unevaluated
Comments: Several visual alarms are provided along egress pathways.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
N/A
Yes
Yes
N/A
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 2005 20 Gable Entire Building
3. Roof
Page: 39 of 80
Building: 0010 - SECURITY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Drywall
Metal Units - Metal Frame Wood Units - Metal Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
None
Casement - Wood Frame; Double Glazing; Fixed - Wood Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
This room is an isolation room.
The building is heated by an International Comfort Products unit (#PGF060H140B). The outdoor pad-mounted packaged gas-fired unit capacity is 112 MBH output.
Comments:
Comments:
HVAC
Heat1.
Electric Resistance
Gas-Fired Packaged
Baseboard Convector
Single Duct
None
None
Electric
Electric
Natural
Natural
None
None
Dorm Rooms
Entire Building
Page: 40 of 80
Building: 0010 - SECURITY
Cast Iron, PVC None None
Electric Water Cooler Hose Bibb Lavatory Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: The extinguishers are inspected monthly.
Comments: The overhead service is brought to a 200A loadcenter with 200A main circuit breaker.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Natural None Entire Building
High Intensity Discharge (HID)
Comments: Exterior lighting is controlled by photocells.
LIGHTING
Main Loadcenter 120/208V, 3-Phase, 4 Wire Loadcenter Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The building is cooled by a International Comfort Products unit (#PGF060H140B). The outdoor pad-mounted packaged unit nominal cooling capacity is 5 tons.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 41 of 80
Building: 0010 - SECURITY
FIRE ALARM
Comments: The fire alarm panel is an FCI model. This panel reports to the center's fire alarm central annunciator panel, also in this building.
Comments: The building is connected to the center LAN system (VoIP network) for both telephone and data communications. The security system monitors cameras in the vicinity of the building.
Audible Alarm Central Annunciator Panel Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Closed Circuit TV None None
Telephone Security Public Address Television
Comments: The recorded footcandle levels include natural light contribution.
T12 - Fluorescent
Incandescent
Offices
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
Page: 42 of 80
Building: 0011 - PAINT STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Brick Masonry
Wall Roof Rigid None
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Storage 290 250 1 Owned 1982 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
N/A
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 1998 13 Gable Entire Building
3. Roof
Page: 43 of 80
Building: 0011 - PAINT STORAGE
INTERIOR FINISH
Concrete
None
None
Mechanical Entire Building
Comments: An exhaust fan, ducted to within 12" of the floor, provides continuous ventilation and an outdoor air intake is ducted to within 12" of the floor.
Ventilation Area Served
VERTICAL CIRCULATION
None
None
None None None None Natural None Entire Building
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The Chromalox heaters are explosion proof for Class 1, Group D hazardous locations.Comments:
HVAC
Heat1.
Electric Resistance
Convector None Electric Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 44 of 80
Building: 0011 - PAINT STORAGE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: The fire extinguisher is inspected monthly.
Comments: An electrical circuit is provided from Building 2. Electrical systems in the building are explosion proof.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Lighting fixtures and the switch located outside the building are explosion proof.
None
LIGHTING
Incandescent20Storage/Warehouse-Active 30
Area Recommended Level
Recorded Level Light Type
None None
Branch Circuit 120V Branch Circuit Only Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Page: 45 of 80
Building: 0011 - PAINT STORAGE
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/ANo
Page: 46 of 80
Building: 0012 - WAREHOUSE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Wood Siding
Wall Roof Rigid None
Metal Overhead - Metal Frame Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Storage 4,400 3,900 1 Owned 1984 Unevaluated
Comments: Accessible entrance is through the roll-up doors.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
N/A
N/A
Yes
Yes
N/A
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 1997 12 Gable Entire Building
3. Roof
Page: 47 of 80
Building: 0012 - WAREHOUSE
Comments: The single glazed windows are interior windows. There are no exterior windows.
INTERIOR FINISH
Carpet Concrete Vinyl Tile
CMU Drywall
Wood Units - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
None
Fixed - Wood Frame; Single Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The two unit heaters were built by Reznor (58.5 MBH output).Comments:
HVAC
Heat1.
Heat Pump
Electric Resistance
Gas-Fired
Through-The- Wall Unit
Baseboard Convector
Unit Heater
None
None
None
Electric
Electric
Electric
Mechanical
Natural
Natural
None
None
None
Offices
Bathrooms
Storage
Page: 48 of 80
Building: 0012 - WAREHOUSE
The water heater was built by Reliance (#63020RTZ, 4.5 kW, 30 gallon tank).Comments:
Cast Iron, PVC None None
Electric Water Cooler Hose Bibb Lavatory Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: The extinguishers are inspected monthly.
Comments: The building is fed overhead from a pad-mounted transformer located near the bordering property line of a small college. The main loadcenter has a 200A main circuit breaker. The meter is located on the exterior wall of the building.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Heat Pump Through-The- Wall Unit
None Electric Mechanical None Offices
High Intensity Discharge (HID)
Comments: Exterior lights are each controlled by an individual integral photocell.
LIGHTING
Main Loadcenter 120/240V, 1-Phase, 3 Wire Service Equipment Only Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Through-wall heat pumps serve offices.Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 49 of 80
Building: 0012 - WAREHOUSE
FIRE ALARM
Comments: Smoke detectors are stand-alone battery-operated units.
Comments: The building is connected to the center LAN system (VoIP network) for both telephone and data communications.
Smoke Detector
Connected to Main System None None None
Telephone Security Public Address Television
T8 - Fluorescent
T8 - Fluorescent
Offices
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesYes
Page: 50 of 80
Building: 0013 - CARPENTRY BUILDING
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Wood Siding
Wall Roof Batt Batt
Metal Unit w/Sidelight - Metal Frame Metal Units - Metal Frame Wood Overhead - Wood Frame Wood Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 5,200 4,680 1 Owned 1983 Unevaluated
Comments: Several visual alarms are provided along egress pathways.