HAWAII/MAUI

Job Corps Center Makawao, Maui, HI

Facility Planning Report Volume II

Supporting Data

Final June 2015

Department of Labor/ Office of Job Corps

HAWAII/MAUI

Job Corps Center Makawao, Maui, HI

Facility Planning Report Volume II

Supporting Data

Final June 2015

Center Courtyard from Building 1 Balcony

VOLUME I - PLANNING STRATEGY

Acronyms and Abbreviations Defi nition of Terms Executive Summary Existing Site Plan Center Statistics Facility Survey Assessment Results and Recommendations

1.0 INTRODUCTION

• Objective and Scope

• Report Contents

2.0 EXISTING CONDITIONS

• Background

• Ownership

• General Site Conditions

• General Building Conditions

• Preventive Maintenance

• Facility Assessment by Function

• Environmental Management

• Resource Use/Conservation

• Sustainability

• Accessibility Standards

• Completed and Current Projects

• Health and Life Safety Issues

• Defi ciency Summary

3.0 PLANNING ANALYSIS

• Space Utilization Analysis

• Federal Real Property Asset Management

• Defi ciency Analysis

• Facility Condition Summary

• Building Condition by Function

• Planning Analysis Results and Conclusions

4.0 RECOMMENDATIONS

• Status of Previous Plan

• Proposed Plan

• Funded Not Corrected (FNC) Defi ciencies

• Summary of Proposed Plan

• Proposed Site Plan

• Implementation Plan

• Summary List of National Projects

• Project Data Sheets

VOLUME II - SUPPORTING DATA

Acronyms and Abbreviations Defi nition of Terms Executive Summary

1.0 SITE LAYOUT AND PLANS

• Location Map

• Exisiting Site Plan

2.0 DESCRIPTIONS

• Buildings and Structures

• Space Utilization By Function

• NSF by Building

• Environmental Management Report

• Asbestos Report

• Radon Report

• Site Descriptions

• Building Descriptions

3.0 DEFICIENCIES

APPENDICES - CORRESPONDENCE AND REPORTS

Appendix A.

• Center Review Meeting Minutes

• Survey Brief

• Student Questionnaire

Appendix B.

• Life Safety Defi ciencies and List

Appendix C.

• O&M Defi ciencies List

Appendix D.

• Active Warranty List

Appendix E.

• FRPC Performance Measures Matrix

Acronyms and Abbreviations

ACRONYMS AND ABBREVIATIONS

A Amperage ABAAS Architectural Barriers Act Accessibility Standard ACM Asbestos-Containing Materials AFUE Annual Fuel Utilization Efficiency AHU Air Handling Unit ANSI American National Standards Institute ARRA American Recovery and Reinvestment Act of 2009 BTU British Thermal Units\ CAA Clean Air Act CCF Hundred Cubic Feet CCTV Closed Circuit Television CDC Child Development Center CDC Centers for Disease Control and Prevention CDP Career Development Period CDSS Career Development Service System CFL Compact Fluorescent Light Bulbs CFM Cubic Feet per Minute CIS Center Information System CMA Certified Medical Assistant CMMS Computerized Maintenance Management System CMU Concrete Masonry Unit CAN Certified Nursing Assistant CO Carbon Monoxide CO Contracting Officer COR Contracting Officer’s Representative CPP Career Preparation Period CRA Construction, Rehabilitation, and Acquisition CTP Career Transition Period CTS Career Transition Services

CTST Career Technical Skills Training (formerly Vocational Skills Training [VST])

CW Cold Water CWA Clean Water Act DDC Direct Digital Controls DFAM Division of Facilities and Asset Management DOL Department of Labor EISA Energy Independence and Security Act of 2007 EMT Emergency Medical Technician

EMT Electrical Metal Tubing (Conduit) EO Executive Order EPA U.S. Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act (1986) EPMD Ethylene Propylene Diene Terpolymer ESC Engineering Support Contractor ESCIS Engineering Support Contractor Information System ESL English as a Second Language oF Degrees Fahrenheit FACP Fire Alarm Control/Annunciator Panel fc Foot Candle FNC Funded Not Corrected FOP Financial Operating Plan FRPC Federal Real Property Council FY Fiscal Year GAO General Accounting Office GED General Educational Development GFCI Ground Fault Circuit Interrupter gph Gallons per Hour GSA General Services Administration GSF Gross Square Feet HID High Intensity Discharge HP Horsepower HSD High School Diploma HTW Hazard and Toxic Waste HVAC Heating, Ventilating, and Air Conditioning HW Hot Water IBC International Building Code IMC International Mechanical Code ION Inventory of Needs IPC International Plumbing code KBTU Thousand British Thermal Unit/Gross Square Foot/Year kV Kilovolt kVA Kilovolt-Amps kw Kilowatt JCC Job Corps Center JCDC Job Corps Data Center JCH Job Corps Handbook kWh Kilowatt Hours LAN Local Area Network LED Light Emitting Diode LF Linear Feet MBH Thousand BTUs per Hour MBTU Thousand British Thermal Unit MWH Megawatt Hour MC Mission Critical MCF Million Cubic Feet MDNC Mission Dependent, Not Critical MDP Main Distribution Panel MLO Main Lug Only m/s Meters/Second MTS Manual Transfer Switch NEC National Electric Code NEMA National Electrical Manufacturers Association NEPA National Environmental Protection Act NFPA National Fire Protection Association NMD Not Mission Dependent NSF Net Square Feet OA Outreach and Admissions OBS On Board Strength OCM Office of Contract Management OIG Office of Inspector General O&M Operations and Maintenance OSHA Occupational Safety and Health Administration PA Public Address pCi Picocurie PV Photovoltaic PVC Polyvinyl Chloride RCRA Resource Conservation and Recovery Act RTU Rooftop Unit SGA Student Government Association SHPO State Historic Preservation Office SF Square Feet SPCC Spill Prevention, Control and Countermeasure SST Social Skills Training T5 Fluorescent Lighting Designation (High Efficiency)

T8 Fluorescent Lighting Designation T12 Fluorescent Lighting Designation (Low Efficiency TSCA Toxic Substances Control Act of 1976 TV Television TVSS Transient Voltage Surge Suppression UEV Unevaluated UFAS Uniform Federal Accessibility Standards UL Underwriters Laboratories USDA U. S. Department of Agriculture V Volt VCR Video Cassette Recorder VST Vocational Skills Training W Watt WAN Wide Area Network WBL Work-Based Learning WIA Workforce Investment Act WIB Workforce Investment Board

Defi nition of Terms

DEFINITION OF TERMS

Accessibility: The degree to which a product, device, service, or environment is available to as many people as possible. Accessibility can be viewed as the "ability to access" and benefit from some system or entity. The Federal Government is required to comply with published law (Architectural Barriers Act (ABA) of 1968 , American Disabilities Act of 1990), regulations and related standards. Accessibility laws and standards have evolved over the past 12 years. DOL now follows ABA Accessibility Standards for Federal Facilities (ABAAS) adopted by the General Services Administration.

Annual Operating Cost: This FRPC performance measure reflects the cost to operate each used asset and consists of lease costs as well as costs related to recurring maintenance, utilities, janitorial, and roads and grounds expenses (Source: FRPC 2012).

Building: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a building includes an enclosure for human occupancy that serves a variety of functions (food service, education, recreation, medical/dental, storage, administration) and is likely to have full utility services (heating, cooling, etc.). A building typically is over 400 square feet.

Building Condition Rating by Function: Each building is assigned a building condition based on the physical condition of the building and the impact on the functional use of the facility. Three ratings are possible:

Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.

Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.

Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required.

Building/Structure Ratings: Each building is rated according to three ratings (good, fair, and poor) based on evaluations of the structure, exterior, interior, mechanical, and electrical elements. Three ratings are possible:

Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.

Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.

Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required

Construction Type: The International Building Code (IBC) construction classifications include the following:

Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.

Type II and III. Any type of construction where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.

Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces.

Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.

Contract Strength: The authorized number of students at a Center in accordance with the contract between the Region and Center Operator.

Deficiency: A deficiency at a Center represents the spectrum of conditions related to the Center’s mission and/or its physical, functional, or operational features do not meet related goals, standards, codes, or other measures of acceptability. Each deficiency at a JCC or CCC initially is categorized as one of the following three deficiencies: Program, Site, or Building:

Program: Program deficiencies address issues such as square footage shortages or the omission of amenities required or standard for the proper operation of a particular Job Corps function.

Site: Site deficiencies indicate adverse site and infrastructure conditions which negatively impact operations and environment (e.g., site lighting, sidewalks, roads, etc.)

Building: Building deficiencies indicate adverse conditions at the building level.

This element includes the substructure, shell, interior, services (plumbing, HVAC, fire protection, and electrical), and equipment and furnishings.

Deficiency Classifications (I to IV): Deficiency classifications are defined as follows:

Class IA - Deficiencies which address imminent life safety and health hazards.

Class II - Deficiencies which address code violations, however, do not represent imminent life safety and health hazards.

A - Deficiencies which violate code (Federal, State or Local) and may result in an interruption of center operations if not corrected.

B - Deficiencies which violate code (Federal, State or Local) and have no immediate impact on center operations if not corrected.

C- Deficiencies which are not in compliance for accessibility in accordance with the Architectural Barriers Act (ABA), Americans with Disabilities Act (ADA), Uniform Federal Accessibility Standards (UFAS), or other applicable standards.

Class III - Deficiencies which address facility repair, replacement or maintenance.

A - Deficiencies which if not corrected may result in an interruption of center operations.

B - Deficiencies which if not corrected will have minimal impact on center operations or can be mitigated through temporary measures until the deficiency is corrected.

Class IV – Deficiencies which address programmatic needs.

A - Deficiencies which if corrected produce substantial improvements in the quality of the learning and living environment.

B - Deficiencies which if corrected are desirable enhancements.

Deficiency Funding Status: The status of the deficiency included the following categories:

Funded deficiencies report indicates the funding year for funded Regional projects, which have dollar amounts shown, or deficiencies assigned to funded National and Regional projects without dollar amounts. Major Regional projects are equivalent to National projects but assigned to the Federal agency (e.g., U.S.

Department of Agriculture) that acts as the Center operator. All operations and maintenance (O&M) deficiencies are treated as funded through the Center Operators O&M contract within the Region.

Proposed deficiencies have been assigned to a proposed future National project.

Unfunded deficiencies are Regional projects unless or until they are assigned to a National project.

Deficiency Status: The deficiency status is tracked and updated during the three-year facility survey cycle, or as such deficiencies are corrected and reported. The status includes:

Uncorrected: Once a deficiency is identified, documented, reported, and assigned for correction, the deficiency remains uncorrected until such time that the deficiency is corrected, reported, and verified.

Corrected: A corrected deficiency is one that has been assigned, funded, corrected, reported, and verified. Typically, the ESC verifies completion of the deficiency through the facility survey or site visit. The Center also may report completion and provide verifiable evidence of the correction, subject to review by the ESC.

Funded Not Corrected: A deficiency that has been approved and authorized as a regional project through the CRA budget, emergency or supplemental funding, or the Life Safety Memo. Note: the funding may not have reached the Center yet as the first steps are a FOP allocation by the National Office and a contract modification by the Region.

No Longer Needed: A no longer needed deficiency is one that has been approved and funded as a Regional project, but due to subsequent circumstances, has been reported by the Center as no longer being required to be accomplished. This type of deficiency is verified and confirmed by the ESC and removed from the Funded Not Corrected deficiency category. The Center should take action with its Region to return the funds.

Facility Condition Index: This performance measure reflects the condition of each asset by comparing the current repair needs to the replacement value of the asset. The index is expressed as a percentage, with 100% being a facility with no repair needs.

Gross Square Foot: The sum of all areas on all floors of a building included within the outside faces of its exterior walls, including all vertical penetration areas, for circulation and shaft areas that connect one floor to another. Gross Area is computed by physically measuring or scaling measurements from the outside faces of exterior walls, disregarding cornices, pilasters, buttresses, etc., that extend beyond the wall faces. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Measured in terms of Gross Square Feet (GSF): GSF = Net Usable Area + Structural Space (Source: http://nces.ed.gov/pubs2006/ficm/).

Mission Dependency: The value an asset brings to the performance of the mission as determined by the governing agency. Specific elements of this category include (FRPC 2012):

Mission Critical - – Without constructed asset or parcel of land, mission is compromised.

Mission Dependent, Not critical (MDNC) - Does not fit into Mission Critical or Not Mission Dependent categories.

Not Mission Dependent (NMD) – Mission unaffected

Ownership (Owned vs Leased): If the property is owned, the Federal Government has fee simple interest for the real property asset. If the property is leased, the rights to use the asset are assigned to the Federal Government by a private entity or a non-Federal Government entity for a defined period of time in return for rental payments (FRPC 2012).

National Project: Generally large and complex projects that require professionally prepared drawings and specifications that are time phased (design and construction) and contracted by the DOL National Office.

Net Square Foot: The sum of all areas on all floors of a building assigned to, or available for assignment to, an occupant or specific use. This value is computed by physically measuring or scaling measurements from the inside faces of surfaces that form the boundaries of the designated areas. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Included should be major space use categories for assignable space (e.g., dormitories, education, recreation, etc.) that are used to accomplish the institution’s mission. Net Square foot: NASF = Sum of Areas Designated by the Major Space Use Categories (Source: http://nces.ed.gov/pubs2006/ficm/).

On Board Strength (OBS): The actual number of students on Center on a day to day basis.

Preventive Maintenance: The care and servicing by personnel for the purpose of maintaining equipment and facilities in satisfactory operating condition by providing for systematic inspection, detection, and correction of incipient failures either before they occur or before they develop into major defects (Source: Dictionary of Military and Associated Terms, US DOD 2005).

Property Type: Indicates the asset as one of the following categories of real property:

land, building, structure.

Property Use: Since the elements defined by the FRPC do not match the space use codes employed in ESCIS, a mapping procedure will be created to align the definitions.

In the report, the Federal Real Property Council (FRPC) classifications will be printed for display. The information is available through the property registration field of Engineering Support Contractor Information System (ESCIS), and the current ESCIS designations will be correlated to the FRPC designations as follows:

ESCIS FRPC

Dormitory Dormitories/Barracks Food Service Other Institutional Uses Education School Recreation Other Institutional Uses Medical/Dental Other Institutional Uses Storage Warehouse Administration Office Structure * Storage, Service, Utility

Systems, or Other Land Institutional

* Each structure will be entered manually from the ESCIS database into one of four FRPC categories listed opposite the term “structure”.

Replacement Value: The cost of replacing the existing constructed asset at today’s building standards. It is the amount required to construct an asset of similar size and in the same location at today’s construction standards. The replacement value reported must be greater than zero (FRPC 2012).

Regional Office Project: Generally smaller projects where the funds will be transferred to the region for center execution.

Structure: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a structure serves to provide storage, service, utility systems and is not likely to have full utilities (heating, cooling, etc.). A structure typically is less than 400 square feet.

Sustainability: Formally known as the World Commission on Environment and Development, the Brundtland Commission's mission in the 1980s was to unite countries to pursue sustainable development. The Commission defined sustainability as the “development which meets the needs of current generations without compromising the ability of future generations to meet their own needs".

Sustainability also is defined as the creation or enhancement of environmental, economic, and social-cultural balance, as realized through business activities, individual actions, and community engagement. Sustainability addresses approaches, methods and practices that optimize the use of energy, water, and materials while reducing greenhouse gas emissions.”

Utilization: This performance measure assesses the degree to which each asset is utilized and is expressed as a percentage. It is calculated on a square footage basis, comparing the square footage used to the “design square footage” based on contract strength (Source: FRPC 2012).

Executive Summary

The facility survey for the Golconda CCC was completed September 22, 2014 – September 26, 2014. The information presented in Volume II, Supporting Data, represents the current status of the campus.

The information includes the following:

Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;

active warranties; and Federal Real Property Council (FRPC) Measures Matrix

Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:

Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix

EXECUTIVE SUMMARY

1.0 - Site Layout and Plans

MAUI

JOB CORPS CENTER

MAKAWAO, HAWAII

MAUI JCC

10 MI50

2.0 - Descriptions

2.0 DESCRIPTIONS

In this section, the following information on the Center and its buildings and structures is presented in tabular format:

Building and Structures – This table indicates the building type, asset number, name, use group, gross square footage (GSF), construction year, number of floors, number of sleeping room and number of beds, construction type (noted as numerical values instead of code-specified Roman numerals), status (active or closed), and overall condition. The possible International Building Code (IBC) construction classifications include the following:

Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.

Type III. This type of construction is where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.

Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces. Fire-retardant-treated wood framing complying with IBC section 2303.2 shall be permitted within exterior wall construction with a 2-hour rating or less.

Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.

The overall building/structure condition is rated in one of three categories: good, fair, or poor.

Space Utilization by Function - This table compares the DOL recommended net square footage per enrollee and for the total function (e.g., housing, education, food service, recreation, medical/dental, administration, storage/support) to the actual values.

Net Square Footage by Building - This table compares the DOL recommended net square footage for the buildings with the function (e.g., housing, education, food service, recreation, medical/dental, storage/support) to the actual values and presents a percentage difference in the two values. In some instances, a recommended value is not available for sub-elements of a function; therefore, the recommended value is shown as “0”.

Environmental Management Report – This table summarizes regulatory related solid and hazardous waste information in accordance with the Resource Conservation and Recovery Act (RCRA) and the presence or absence of hazardous material storage facilities in accordance with Emergency Planning and Community Right-to-Know Act of

1986 (EPCRA). An inventory of petroleum storage tanks is noted as well as asbestos and polychlorinated biphenyls (PCBs) in accordance with the Clean Water Act (CWA) and Toxic Substance Control Act (TSCA), respectively. In addition, this report statuses air quality as required under the Clean Air Act (CAA).Any radon testing of buildings also is documented.

Site Descriptions – Tabular information is documented for the site. Among the data presented are the topography; total number of buildings and structures; roads, parking and sidewalks; fencing; site utilities; storage tanks; accessibility; historic preservation;

natural hazards; and sustainability. The overall condition of the site is rated in one of three categories: good, fair, or poor.

Building Descriptions – Tabular information, as well as photographs and floor plan drawings, are provided for each building or structure, as appropriate, in the following categories: real estate; accessibility; building envelope; interior finishes; vertical circulation; heating, ventilation and air conditioning (HVAC); plumbing; fire protection;

electrical services; fire alarms; carbon monoxide detection; communication; and building metering. The overall condition of the building and its five key subsystems (structure, exterior, interior, mechanical, and electrical) are rated in one of three categories: good, fair, or poor. If applicable, recommendations for renovation or demolition are provided.

BUILDINGS AND STRUCTURES

00912 HAWAII/MAUI 06/17/2015

1Page: of Date:

0001 - HAWAII ADMINISTRATION

BUILDING

0004 - LANA'I MAINTENANCE

0006 - ARTS AND CRAFTS

0009 - LOKELANI DORMITORY

0010 - MAKAI DORMITORY

0011 - MOLOKA'I DINING HALL

0012 - MALAMA OLA DORMITORY

0013 - KAUA'I OA/CTS/BUSINESS

0017 - FRONT GAZEBO (15Ft Diameter) 0018 - GAZEBO #2 (15.5Ft Diameter) 0019 - MAINTENANCE (25Ft x 30Ft) 0019A - MAINT. STORAGE #1 (8Ft X 20Ft) 0019B - MAINT. STORAGE #2 (8Ft X 20Ft) 0020 - RECEIVING (19Ft x 21Ft) 0021 - 20KW WIND TURBINE (15Ft Triangle) 0021A - TURBINE STRUCTURE (3Ft x 5Ft) 0022 - SMALL WIND TURBINE (1.5Ft Diameter)

Name GSF

24,065

1,680

7,825 7,825 4,540 7,929 2,850

Active

Active Active Active Active Active Active Active Active Active Active Active Active Active Active

Active Active

StatusType

Building

Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure Structure

Structure Structure

Use Group Built Flrs Const

Business

Business Assembly Residential Residential Assembly Residential Business Assembly Assembly Storage Storage Storage Storage Utility/Misc.

Utility/Misc.

Utility/Misc.

Good

Fair Fair

Good Good Fair

Good Fair

Good Good Good Fair Fair

Good Fair

Good Good

ConditionAsset Number

0091200002

0091200013 0091200007 0091208009 0091208010 0091200010 0091208017 0091200012 0091208012 0091208013 0091208014 0091208020 0091208021 0091208015 0091208016

0091208018 0091208019

8 57,214

9 1,880

17 59,094

Buildings

Structures

Total

GSF

GSF

GSF

Summary

06/17/2015

Space Utilization By Function 00912 Hawaii/Maui Page: 1 of Date:

HOUSING

EDUCATION

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 128 Non Residents 0

128Total Students

(128)

(128)

(128)

(128)

(128)

(128)

DIFFERENCE

13,824

7,870

2,304

6,400

2,560

17,318

12,593

3,170

4,137

1,102

2,818

Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage

Academic (128) Non-Academic

20 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 30 -- Office Administration 24 -- Retail Sales +

Dining (2 Servings) Food Preparation Food Storage

Arts & Crafts Multipurpose Room Recreation Office

Medical/Dental

Administration

7.3

2,100 1,162 3,065

10,321

3,398 3,829

1,492 1,724 1,217

1,160 1,040

3,724

1,102

2,818

1,280 1,024 1,536 9,216

1,280 1,280

1,200 1,800 1,350

1,024

2,560

1,529 1,105

-98

2,118 2,549

-76

-133 -27

3,724

Vocations

RESIDENT

NON-RESIDENT

(128)

(0) 15

50 6,400

3,494

4,723

-2,263

06/17/2015

Space Utilization By Function 00912 Hawaii/Maui Page: 2 of Date:

STORAGE/SUPPORT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

TOTAL 272.78 34,916 42,703

70 (128)

DIFFERENCE

57,214

0.75

TOTAL GSF

NET TO GROSS RATIO

1,024 1,565

Operations & Maintenance 8 1,565 1,024 541

7,787

Net Square Footage By Building Date: 06/17/2015 Page: 1

Center: HAWAII/MAUI (00912) of 3

HOUSING

Sleeping excl. SPD

Lounge

Storage

Shower/Toilet

Other

Function Suggested

NSF

3,285 3,751 3,285

1,025 1,025 1,015

0010 - MAKAI DORMITORY

0012 - MALAMA OLA DORMITORY

0009 - LOKELANI DORMITORY

0010 - MAKAI DORMITORY

0012 - MALAMA OLA DORMITORY

0009 - LOKELANI DORMITORY

0009 - LOKELANI DORMITORY

0010 - MAKAI DORMITORY

0009 - LOKELANI DORMITORY

0010 - MAKAI DORMITORY

0012 - MALAMA OLA DORMITORY

0010 - MAKAI DORMITORY

0009 - LOKELANI DORMITORY

0012 - MALAMA OLA DORMITORY

Bldg Name Actual NSF Difference

10,321

2,100

3,065

1,162

Sub Total: 17,318

9,216

1,280

1,536

1,024

13,824

1,105

-98

1,529

( 128

3,494 rooms; beds rooms; beds rooms; beds

Page: 2

Center: HAWAII/MAUI (00912) of 3

EDUCATION

FOOD SERVICE

RECREATION

Academic

Culinary Arts

Retail Sales

Facilities Maint. and Const.

Non-Academic

Office Administration

Dining (2 Servings)

Food Preparation

Food Storage

Multipurpose Room

Arts & Crafts

Recreation Office

Function Suggested

NSF

1,872

1,492

1,724

1,354

1,217

1,160

1,040

3,724

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0011 - MOLOKA'I DINING HALL

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0012 - MALAMA OLA DORMITORY

0001 - HAWAII ADMINISTRATION BUILDING

0013 - KAUA'I OA/CTS/BUSINESS

0013 - KAUA'I OA/CTS/BUSINESS

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0013 - KAUA'I OA/CTS/BUSINESS

0011 - MOLOKA'I DINING HALL

0011 - MOLOKA'I DINING HALL

0011 - MOLOKA'I DINING HALL

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0006 - ARTS AND CRAFTS

0001 - HAWAII ADMINISTRATION BUILDING

Bldg Name Actual NSF Difference

3,398

1,492

1,724

3,829

1,217

1,160

1,040

3,724

Sub Total:

Sub Total:

Sub Total:

12,593

3,170

4,137

1,280

1,200

1,800

1,280

1,350

1,024

7,870

2,304

6,400

2,118

-27

-76

2,549

-133

4,723

-2,263

Page: 3

Center: HAWAII/MAUI (00912) of 3

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

Medical/Dental

Administration

Operations & Maintenance

Function Suggested

NSF

1,102

2,818

1,565

0001 - HAWAII ADMINISTRATION BUILDING

0001 - HAWAII ADMINISTRATION BUILDING

0004 - LANA'I MAINTENANCE

Bldg Name Actual NSF Difference

1,102

2,818

1,565

Sub Total:

Sub Total:

Sub Total:

1,102

2,818

1,565

2,560

1,024

2,560

1,024

Environmental Management Report

Center: HAWAII/MAUI (00912) Page: 1 Date: 06/17/2015 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

Commercial Waste Service

HAZARDOUS MATERIALS STORAGE (EPCRA)

Yes Maintenance Shops/Facilities Maintenance Trade

No

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

None None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance :

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Maui/Best Desposal Service No

HIR000111435

Municipal Hazardous Waste Disposal Service Maui County Landfill

No No

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

N/A N/A

01/01/2001 Non-Friable Only Kalani Vaivela

No Yes N/A No Yes

ID Fuel Type Capacity Location Overfill

Prevention Secondary ContainmentTank Status

Tank Status Prevention/Detection

Asbestos-Containing Materials Inventory

Date: 06/17/2015Center : Hawaii/Maui (00912) Page: 1 of 1

Floor Finishes Floor Finishes

Bldg System 9" x 9" vinyl floor tiles Vinyl floor sheeting

Category Description Sq. Ft.

Sq. Ft.

Location Unit Quantity Basement Medical Wing

Building : 0001 - HAWAII ADMINISTRATION BUILDING

Radon

Page: 1 of 1

0001 - HAWAII ADMINISTRATION BUILDING

0004 - LANA'I MAINTENANCE

0006 - ARTS AND CRAFTS

0009 - LOKELANI DORMITORY

0010 - MAKAI DORMITORY

0011 - MOLOKA'I DINING HALL

0012 - MALAMA OLA DORMITORY

0013 - KAUA'I OA/CTS/BUSINESS

Bldg Name Test Date

No

No

No

No

No

No

No

No

Radon Testing

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

Site Description

HAWAII/MAUI

Aerial view of the Center

Page: 1 Date: 06/17/2015 of 4

Comments:

Paving Type for Roads & Parking

There is no staff parking; they currently park on the grass and median area along the access road.

Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is not fully enclosed by fencing. There are two wind turbine generators on the site.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterCounty of Maui Department of Water SupPublic Water Authority

None 0None

Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time

(Minutes)

Yes 0 4None Municipal

Nearest fire department is the Makawao/Paia fire department. Response time is 4 minutes.

Sewage Treatment Flow

Center

On-site Septic System

Center

Gravity

Maintenance ResponsibilityOwnership

Number of Deficiencies = 3

Number of Deficiencies = 4

Number of Deficiencies = 2SITE FEATURES

UTILITIES

3. Sanitary Sewer System/ Sewage Treatment Plant

2. Fire Protection System

Buildings Structures8 9Flat

Surrounding

Outdoor Recreation

Residential, Rural

Basketball Wind Turbine Generators

Basketball Court

Wind Turbine Generator

Chain Link

Chain Link

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

System Capacity Adequate System Condition

Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition No Good Yes Good

Number of Deficiencies = 1

Fencing

Other Features

Page: 2 Date: 06/17/2015 of 4

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Maui Electric Company

The overhead electric service is brought to the center from power poles along Ike Drive. Service enters the center at the main entrance southwest of the campus and distributes power to buildings via pole-mounted transformers around the center perimeter running from south, then east and terminated in the north. A 50 kVA and two 25 kVA pole-mounted transformers along the south side serve Building 6, Building 4 and Building 9. A 25 kVA pole-mounted transformer at the northeast serves Makai Building 10. Two 75 kVA pole-mounted transformers at the north provide services to Building 1, Building 11 and Building 13. All buildings are metered individually. A 60 kW propane fueled generator with an automatic transfer switch (ATS) and exterior enclosure provides backup power for kitchen equipment in Building 11. Also, the center is provided with two wind power generators for dormitory buildings and to back-feed the electric utility network. The wind power generators are as follows: SkyStream 3.7 with rated capacity of 2.4 kW and Jacobs 31-20 with rated capacity of 20kW. The generators are located east side of the building and ATSs are mounted on the east exterior wall.

Pole Utility

Utility Utility

No

12.4 kV, 3-Phase, 3 Wire

120/240V, 1-Phase, 3 WireOverhead

OverheadPrimary Service

Secondary Service

Distribution Characteristics

4. Storm Water System

Drain Type On-Site Storm Water Management

Surface Run-off N/A

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes GoodCenter

7. Electrical (Service)

Transformer Maint Resp

Utility

System Capacity Adequate System Condition

Yes Good

Generator

Propane Gas

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Post-Mounted Post-Mounted Building Sport Light

Photocell and Time Clock

Photocell and Time Clock

Photocell and Time Clock

Photocell and Time Clock

Switch

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Comments: The site lighting consists of mostly building-mounted exterior lights and some post-mounted lights along the center main entrance roadway. The basketball court is provided with sport lights which are controlled by a local switch. The building-mounted and post-mounted lights are controlled by photocells and time clock. The center owns and maintains the site lighting system. Some of HID site lighting fixtures have been retrofitted with 42W compact flourescent and 40W induction lamps.

ATS MTS

Yes No

5. Fuel Distribution System: None

6. Central Plant: None

Metering Individual

Page: 3 Date: 06/17/2015 of 4

Comments:

Telephone Company

On-site Line Owner

Telephone service is brought to the center by Hawaii Telephe Co. and terminated in the server room located on the first floor of Administration Building 1. From this location Job Corps Data Center provides and maintains the digital voice over IP (VoIP) and data network for the entire center. The fire alarm system in all buildings are connected to the main fire alarm control/annunciator panel located in the security office in Administration Building 1. Dormitory Buildings 9,10,and 12 are provided with satellite dishes.

Hawaii Telephe Co.

Maint. Responsibility

Center Center

Door Alarms

01/01/1992

01/01/1992

01/01/2005

Private

Private

Private

Active

Active

Active

Aboveground

Aboveground

Aboveground

Near Building 1

Near Building 11

Between Buildings 10 and 12

Propane tank near Building 1 has been abandoned in place and will be removed. The gas-fired water heater has been removed.

No

No

No

Propane

Propane

Propane

STORAGE TANKS

Comments:

TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID

Reg.

Number of Deficiencies = 1

9. Electrical (Communication/Alarm/Security)

Domestic Hot Water

Cooking

Domestic Hot Water

Purpose

Yes

Central & Stand-Alone

VOIP

System Capacity Adequate System Condition

GoodYes

Number of Deficiencies = 6

Fire Alarm Security

Page: 4 Date: 06/17/2015 of 4

ACCESSIBILITY

Yes

Comments:

UnknownNoYes

The land, Building 1 and Building 13 are eligible for the historic register.

No

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Earthquake Risk

Medium Low LowMedium LowUniform Medium

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Number of Deficiencies = 9

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X Good Fair Poor

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Active Energy Use Reduction Program

Active Water Use Reduction Program

Approximate or Measured Waste Recycled

Use of School Dude or CMMS for Preventative Maintenance

Green Purchasing Policy Practiced

Site Stormwater Absorption Measures in Place

Center has Onsite Renewable Energy (PV or Wind)

Center has a Chartered Green Committee & Roster

Center Uses Green Cleaning Practices

SUSTAINABILITY

Comments: The Center has two wind turbines and photovoltaic panels on the Lokelani Domitory.

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

75 %

Building Descriptions and Structures

BUILDING 1 - HAWAII ADMINISTRATION BUILDING

Building Descriptions

Page: 1 of 38

Building: 0001 - HAWAII ADMINISTRATION BUILDING

BUILDING ENVELOPE

Foundation RoofBuilding

Wood Piers & Beams Wood Wood

There are portions of the foundation that are constructed of cobblestones, mostly in the basement area.

Stone Wood Siding

Wall Roof None None

Metal Rollup - Metal Frame Metal Unit - Metal Frame Wood Unit - Metal Frame Wood Unit - Wood Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

Business 24,065 17,111 2 Leased 1900 Candidate

Comments: The wood interior stairs are accessible; the exterior metal fire escape stairs are not accessible.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

No

No

Yes

N/A

Yes

Yes

Yes

No

No

Yes

Yes

ACCESSIBILITY

Structural Systems1.

Exterior Walls2. Number of Deficiencies = 2

Insulation4.

Exterior Doors5. Number of Deficiencies = 1

Material

There is corrugated metal roofing over the back steps and over the corner garden.

Drainage Year Life

Type Area Served

Asphalt Shingles Gutters and Downspouts 2009 14 Hip Original Building

Number of Deficiencies = 1

Comments:

3. Roof

Entire Building

Area Served

Comments:

Page: 2 of 38

Building: 0001 - HAWAII ADMINISTRATION BUILDING

INTERIOR FINISH

Carpet Ceramic Tile Concrete Resilient Vinyl Tile Wood

Ceramic Tile Concrete Drywall Fencing Fiberglass Panel Mirror Plaster Plywood Wood

Metal Unit - Metal Frame Wood Dutch Unit - Metal Frame

Wood Unit - Metal Frame Wood Unit - Wood Frame

VERTICAL CIRCULATION

Concrete Stairs Metal Stairs Wood Stairs Comments: There are exterior metal fire escape stairs serving the second floor. Wood stairs access the second floor. Concrete stairs access the basement level.

Double Hung - Wood Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;

Fixed - Wood Frame; Single Glazing; Single Hung - Vinyl Frame; Single Glazing;

Sliding - Aluminum Frame; Single Glazing;

Acoustical Tile Exposed Structure Gypsum Board Wood

Number of Deficiencies = 1

Windows6. Number of Deficiencies = 1

Floors1. Asbestos: Yes Number of Deficiencies = 9

Interior Walls2.

3. Number of Deficiencies = 1

Interior Doors4. Number of Deficiencies = 2

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None None

Ceilings

Page: 3 of 38

Building: 0001 - HAWAII ADMINISTRATION BUILDING

Mechanical

Mechanical

Janitor's Closet

Toilet/Shower

Ventilation Area Served

Packaged Direct

Expansion (Air Source)

Split Direct Expansion (Air

Source)

Packaged Direct

Expansion (Air Source)

Window Unit

Single Duct

Portable Air Conditioner

None

Refrigerant

None

Electric

Electric

Electric

Natural

Natural

Natural

None

None

None

Offices

Medical/Dental

Offices

Exhaust Ventilation

Window units also cool the math classroom and an electronic equipment room.

This is a Rheem model RBHC-24J00NHG air handler with evaporator coils matched to a Rheem RAMC-060JAZ condensing unit.

One office is cooled by a Freecom model M2000 unit.

Comments:

Comments:

Comments:

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

3. Air Conditioning

Page: 4 of 38

Building: 0001 - HAWAII ADMINISTRATION BUILDING

Propane water heater has failed. Unit was sized for dormitory. A deficiency was written to replace it with a smaller unit and to remove the propane storage tank.

Comments:

Cast-Iron None None

Electric Bottled Water Cooler Electric Water Cooler Emergency Eye Wash Hose Bibb Lavatory Shower Shower/Bathtub Sink Urinal Water Closet (Tank)

None

Comments:

Wet None ABC Type Fire Extinguisher

Comments: A wet pipe sprinkler system serves the basement level.

Comments: Service is brought from a 75 kVA pole-mounted transformer southwest of the building and terminated in a wire trough which feeds one 250A disconnect switch, two 250A circuit breakers, two 200A circuit breakers, a C/T cabinet and a meter. The 200A disconnect switch serve panel “M3”, the two 200A circuit breakers serves panels “CO” and “C” and the two 250A circuit breakers serves panels “BF” and “K”.

Copper Copper None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.

Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES Number of Deficiencies = 4

Exterior Lighting1.

The Center is arranging to have the propane tank removed.

LIGHTING

Page: 5 of 38

Building: 0001 - HAWAII ADMINISTRATION BUILDING

FIRE ALARM

Comments: The main fire alarm control/annunciator panel is a Simplex model 4020 located in the security office, and is connected to other buildings fire alarm systems.

Audible Alarm Control/Annunciator Panel Flow Switch Heat Detector Manual Pull Station Smoke Detector Tamper Switch

Connected to Main System Magnetic Door/Alarm None Satellite Dish

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution. Some of the lighting fixtures in the northeast wing are retrofitted with 4-foot liner LED bulbs.

T8 - Fluorescent and LED

T8 - Fluorescent

T8 - Fluorescent and LED

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Conference Rooms

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Lounges

Mail Room

Reception

Toilets

Storage Rooms

Classrooms

Medical/Dental

Wards (Patient)

Recreation

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Emergency Exit

Number of Deficiencies = 3

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 3

COMMUNICATION

Type Location N/A N/A

There is no plausible means by which harmful levels of CO could enter the medical wing sleeping rooms.

CARBON MONOXIDE DETECTION

Detection Required No

Number of Deficiencies = 0

Page: 6 of 38

Building: 0001 - HAWAII ADMINISTRATION BUILDING

GENERAL BUILDING CONDITION

Rating

Comments:

X Good Fair Poor

The interior vinyl tile, carpeting and some of the underlayment are in deteriorated condition. The second floor balcony floors need to be repaired

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No N/AYes

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good

BUILDING 4 - LANA'I MAINTENANCE

Page: 7 of 38

Building: 0004 - LANA'I MAINTENANCE

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood

Plywood Wood Siding

Wall Roof None Batt

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership #Floors

Business 1,680 1,565 1 Leased 1992 Not Evaluated

Comments: Entrance door only 31" wide.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

No

N/A

N/A

N/A

Yes

N/A

N/A

No

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

Remaining roof life is based on visual observation during the January 2015 Facility Survey.

Remaining roof life is based on visual observation during the January 2015 Facility Survey.

Drainage Year Life

Type Area Served

Corrugated Aluminum

Metal

Surface Run-off

Surface Run-off

Shed

Gable

Storage

Original Building

Number of Deficiencies = 1

Comments:

Comments:

3. Roof

Entire Building

Page: 8 of 38

Building: 0004 - LANA'I MAINTENANCE

INTERIOR FINISH

Ceramic Tile Concrete Vinyl Tile

CMU Ceramic Tile Drywall

Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

None

Metal Overhead - Metal Frame Plywood Unit - Wood Frame Wood Unit - Metal Frame

Louvered - Aluminum Frame; Single Glazing; Sliding - Aluminum Frame; Double Glazing;

Gypsum Board

Exhaust Ventilation

Exterior Doors5. Number of Deficiencies = 2

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

None None None None Natural None None

Ventilation2.

Page: 9 of 38

Building: 0004 - LANA'I MAINTENANCE

Hot water is provided by an undersink electric instantaneous water heater.Comments:

Cast-Iron None None

Electric Bottled Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Sink Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Comments: Service is brought…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .