CASCADES
Job Corps Center Sedro-Woolley, WA
Facility Planning Report Volume II
Supporting Data
Preliminary December 2014
Department of Labor/ Office of Job Corps
CASCADES
Job Corps Center Sedro-Woolley, WA
Facility Planning Report Volume II
Supporting Data
Preliminary December 2014
Campus Green in front of Admin/Education/Med-Dental building 32
VOLUME I - PLANNING STRATEGY
Acronyms and Abbreviations Defi nition of Terms Executive Summary Exsting Site Plan Center Statistics Facility Survey Assement Results and Recommentdations
1.0 INTRODUCTIONS
• Objective and Scope
• Report Contents
2.0 EXISTING CONDITIONS
• Background
• Ownership
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Facility Assessment by Function
• Environmental Management
• Resource Use/Conservation
• Sustainability
• Accessibility Standards
• Completed and Current Projects
• Health and Life Safety Issues
• Defi ciency Summary
3.0 PLANNING ANALYSIS
• Space Utilization Analysis
• Federal Real Property Assest Management
• Defi ciency Analysis
• Facility Condition Summary
• Building Condition by Function
• Planning Analysis Results and Conculsions
3.0 RECOMMENDATIONS
• Status of Previous Plan
• Proposed Plan
• Funded Not Corrected (FNC) Defi ciencies
• Summary of Proposed Plan
• Proposed Site Plan
• Implementation Plan
• Summary List of National Projects
• Project Data Sheets
Appendix A. Energy and Water Evaluation Report
VOLUME II - SUPPORTING DATA
Acronyms and Abbreviations Defi nition of Terms Executive Summary
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Appendix E.
• FRPC Performance Measures Matrix
Acronyms and Abbreviations
ACRONYMS AND ABBREVIATIONS
A Amperage ABAAS Architectural Barriers Act Accessibility Standard ACM Asbestos-Containing Materials AFUE Annual Fuel Utilization Efficiency AHU Air Handling Unit ANSI American National Standards Institute ARRA American Recovery and Reinvestment Act of 2009 BTU British Thermal Units\ CAA Clean Air Act CCF Hundred Cubic Feet CCTV Closed Circuit Television CDC Child Development Center CDC Centers for Disease Control and Prevention CDP Career Development Period CDSS Career Development Service System CFL Compact Fluorescent Light Bulbs CFM Cubic Feet per Minute CIS Center Information System CMA Certified Medical Assistant CMMS Computerized Maintenance Management System CMU Concrete Masonry Unit CAN Certified Nursing Assistant CO Carbon Monoxide CO Contracting Officer COR Contracting Officer’s Representative CPP Career Preparation Period CRA Construction, Rehabilitation, and Acquisition CTP Career Transition Period CTS Career Transition Services
CTST Career Technical Skills Training (formerly Vocational Skills Training [VST])
CW Cold Water CWA Clean Water Act DDC Direct Digital Controls DFAM Division of Facilities and Asset Management DOL Department of Labor EISA Energy Independence and Security Act of 2007 EMT Emergency Medical Technician
EMT Electrical Metal Tubing (Conduit) EO Executive Order EPA U.S. Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act (1986) EPMD Ethylene Propylene Diene Terpolymer ESC Engineering Support Contractor ESCIS Engineering Support Contractor Information System ESL English as a Second Language oF Degrees Fahrenheit FACP Fire Alarm Control/Annunciator Panel fc Foot Candle FNC Funded Not Corrected FOP Financial Operating Plan FRPC Federal Real Property Council FY Fiscal Year GAO General Accounting Office GED General Educational Development GFCI Ground Fault Circuit Interrupter gph Gallons per Hour GSA General Services Administration GSF Gross Square Feet HID High Intensity Discharge HP Horsepower HSD High School Diploma HTW Hazard and Toxic Waste HVAC Heating, Ventilating, and Air Conditioning HW Hot Water IBC International Building Code IMC International Mechanical Code ION Inventory of Needs IPC International Plumbing code KBTU Thousand British Thermal Unit/Gross Square Foot/Year kV Kilovolt kVA Kilovolt-Amps kw Kilowatt JCC Job Corps Center JCDC Job Corps Data Center JCH Job Corps Handbook kWh Kilowatt Hours LAN Local Area Network LED Light Emitting Diode LF Linear Feet MBH Thousand BTUs per Hour MBTU Thousand British Thermal Unit MWH Megawatt Hour MC Mission Critical MCF Million Cubic Feet MDNC Mission Dependent, Not Critical MDP Main Distribution Panel MLO Main Lug Only m/s Meters/Second MTS Manual Transfer Switch NEC National Electric Code NEMA National Electrical Manufacturers Association NEPA National Environmental Protection Act NFPA National Fire Protection Association NMD Not Mission Dependent NSF Net Square Feet OA Outreach and Admissions OBS On Board Strength OCM Office of Contract Management OIG Office of Inspector General O&M Operations and Maintenance OSHA Occupational Safety and Health Administration PA Public Address pCi Picocurie PV Photovoltaic PVC Polyvinyl Chloride RCRA Resource Conservation and Recovery Act RTU Rooftop Unit SGA Student Government Association SHPO State Historic Preservation Office SF Square Feet SPCC Spill Prevention, Control and Countermeasure SST Social Skills Training T5 Fluorescent Lighting Designation (High Efficiency)
T8 Fluorescent Lighting Designation T12 Fluorescent Lighting Designation (Low Efficiency TSCA Toxic Substances Control Act of 1976 TV Television TVSS Transient Voltage Surge Suppression UEV Unevaluated UFAS Uniform Federal Accessibility Standards UL Underwriters Laboratories USDA U. S. Department of Agriculture V Volt VCR Video Cassette Recorder VST Vocational Skills Training W Watt WAN Wide Area Network WBL Work-Based Learning WIA Workforce Investment Act WIB Workforce Investment Board
Defi nition of Terms
DEFINITION OF TERMS
Accessibility: The degree to which a product, device, service, or environment is available to as many people as possible. Accessibility can be viewed as the "ability to access" and benefit from some system or entity. The Federal Government is required to comply with published law (Architectural Barriers Act (ABA) of 1968 , American Disabilities Act of 1990), regulations and related standards. Accessibility laws and standards have evolved over the past 12 years. DOL now follows ABA Accessibility Standards for Federal Facilities (ABAAS) adopted by the General Services Administration.
Annual Operating Cost: This FRPC performance measure reflects the cost to operate each used asset and consists of lease costs as well as costs related to recurring maintenance, utilities, janitorial, and roads and grounds expenses (Source: FRPC 2012).
Building: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a building includes an enclosure for human occupancy that serves a variety of functions (food service, education, recreation, medical/dental, storage, administration) and is likely to have full utility services (heating, cooling, etc.). A building typically is over 400 square feet.
Building Condition Rating by Function: Each building is assigned a building condition based on the physical condition of the building and the impact on the functional use of the facility. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required.
Building/Structure Ratings: Each building is rated according to three ratings (good, fair, and poor) based on evaluations of the structure, exterior, interior, mechanical, and electrical elements. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required
Construction Type: The International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type II and III. Any type of construction where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
Contract Strength: The authorized number of students at a Center in accordance with the contract between the Region and Center Operator.
Deficiency: A deficiency at a Center represents the spectrum of conditions related to the Center’s mission and/or its physical, functional, or operational features do not meet related goals, standards, codes, or other measures of acceptability. Each deficiency at a JCC or CCC initially is categorized as one of the following three deficiencies: Program, Site, or Building:
Program: Program deficiencies address issues such as square footage shortages or the omission of amenities required or standard for the proper operation of a particular Job Corps function.
Site: Site deficiencies indicate adverse site and infrastructure conditions which negatively impact operations and environment (e.g., site lighting, sidewalks, roads, etc.)
Building: Building deficiencies indicate adverse conditions at the building level.
This element includes the substructure, shell, interior, services (plumbing, HVAC, fire protection, and electrical), and equipment and furnishings.
Deficiency Classifications (I to IV): Deficiency classifications are defined as follows:
Class IA - Deficiencies which address imminent life safety and health hazards.
Class II - Deficiencies which address code violations, however, do not represent imminent life safety and health hazards.
A - Deficiencies which violate code (Federal, State or Local) and may result in an interruption of center operations if not corrected.
B - Deficiencies which violate code (Federal, State or Local) and have no immediate impact on center operations if not corrected.
C- Deficiencies which are not in compliance for accessibility in accordance with the Architectural Barriers Act (ABA), Americans with Disabilities Act (ADA), Uniform Federal Accessibility Standards (UFAS), or other applicable standards.
Class III - Deficiencies which address facility repair, replacement or maintenance.
A - Deficiencies which if not corrected may result in an interruption of center operations.
B - Deficiencies which if not corrected will have minimal impact on center operations or can be mitigated through temporary measures until the deficiency is corrected.
Class IV – Deficiencies which address programmatic needs.
A - Deficiencies which if corrected produce substantial improvements in the quality of the learning and living environment.
B - Deficiencies which if corrected are desirable enhancements.
Deficiency Funding Status: The status of the deficiency included the following categories:
Funded deficiencies report indicates the funding year for funded Regional projects, which have dollar amounts shown, or deficiencies assigned to funded National and Regional projects without dollar amounts. Major Regional projects are equivalent to National projects but assigned to the Federal agency (e.g., U.S.
Department of Agriculture) that acts as the Center operator. All operations and maintenance (O&M) deficiencies are treated as funded through the Center Operators O&M contract within the Region.
Proposed deficiencies have been assigned to a proposed future National project.
Unfunded deficiencies are Regional projects unless or until they are assigned to a National project.
Deficiency Status: The deficiency status is tracked and updated during the three-year facility survey cycle, or as such deficiencies are corrected and reported. The status includes:
Uncorrected: Once a deficiency is identified, documented, reported, and assigned for correction, the deficiency remains uncorrected until such time that the deficiency is corrected, reported, and verified.
Corrected: A corrected deficiency is one that has been assigned, funded, corrected, reported, and verified. Typically, the ESC verifies completion of the deficiency through the facility survey or site visit. The Center also may report completion and provide verifiable evidence of the correction, subject to review by the ESC.
Funded Not Corrected: A deficiency that has been approved and authorized as a regional project through the CRA budget, emergency or supplemental funding, or the Life Safety Memo. Note: the funding may not have reached the Center yet as the first steps are a FOP allocation by the National Office and a contract modification by the Region.
No Longer Needed: A no longer needed deficiency is one that has been approved and funded as a Regional project, but due to subsequent circumstances, has been reported by the Center as no longer being required to be accomplished. This type of deficiency is verified and confirmed by the ESC and removed from the Funded Not Corrected deficiency category. The Center should take action with its Region to return the funds.
Facility Condition Index: This performance measure reflects the condition of each asset by comparing the current repair needs to the replacement value of the asset. The index is expressed as a percentage, with 100% being a facility with no repair needs.
Gross Square Foot: The sum of all areas on all floors of a building included within the outside faces of its exterior walls, including all vertical penetration areas, for circulation and shaft areas that connect one floor to another. Gross Area is computed by physically measuring or scaling measurements from the outside faces of exterior walls, disregarding cornices, pilasters, buttresses, etc., that extend beyond the wall faces. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Measured in terms of Gross Square Feet (GSF): GSF = Net Usable Area + Structural Space (Source: http://nces.ed.gov/pubs2006/ficm/).
Mission Dependency: The value an asset brings to the performance of the mission as determined by the governing agency. Specific elements of this category include (FRPC 2012):
Mission Critical - – Without constructed asset or parcel of land, mission is compromised.
Mission Dependent, Not critical (MDNC) - Does not fit into Mission Critical or Not Mission Dependent categories.
Not Mission Dependent (NMD) – Mission unaffected
Ownership (Owned vs Leased): If the property is owned, the Federal Government has fee simple interest for the real property asset. If the property is leased, the rights to use the asset are assigned to the Federal Government by a private entity or a non-Federal Government entity for a defined period of time in return for rental payments (FRPC 2012).
National Project: Generally large and complex projects that require professionally prepared drawings and specifications that are time phased (design and construction) and contracted by the DOL National Office.
Net Square Foot: The sum of all areas on all floors of a building assigned to, or available for assignment to, an occupant or specific use. This value is computed by physically measuring or scaling measurements from the inside faces of surfaces that form the boundaries of the designated areas. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Included should be major space use categories for assignable space (e.g., dormitories, education, recreation, etc.) that are used to accomplish the institution’s mission. Net Square foot: NASF = Sum of Areas Designated by the Major Space Use Categories (Source: http://nces.ed.gov/pubs2006/ficm/).
On Board Strength (OBS): The actual number of students on Center on a day to day basis.
Preventive Maintenance: The care and servicing by personnel for the purpose of maintaining equipment and facilities in satisfactory operating condition by providing for systematic inspection, detection, and correction of incipient failures either before they occur or before they develop into major defects (Source: Dictionary of Military and Associated Terms, US DOD 2005).
Property Type: Indicates the asset as one of the following categories of real property:
land, building, structure.
Property Use: Since the elements defined by the FRPC do not match the space use codes employed in ESCIS, a mapping procedure will be created to align the definitions.
In the report, the Federal Real Property Council (FRPC) classifications will be printed for display. The information is available through the property registration field of Engineering Support Contractor Information System (ESCIS), and the current ESCIS designations will be correlated to the FRPC designations as follows:
ESCIS FRPC
Dormitory Dormitories/Barracks Food Service Other Institutional Uses Education School Recreation Other Institutional Uses Medical/Dental Other Institutional Uses Storage Warehouse Administration Office Structure * Storage, Service, Utility
Systems, or Other Land Institutional
* Each structure will be entered manually from the ESCIS database into one of four FRPC categories listed opposite the term “structure”.
Replacement Value: The cost of replacing the existing constructed asset at today’s building standards. It is the amount required to construct an asset of similar size and in the same location at today’s construction standards. The replacement value reported must be greater than zero (FRPC 2012).
Regional Office Project: Generally smaller projects where the funds will be transferred to the region for center execution.
Structure: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a structure serves to provide storage, service, utility systems and is not likely to have full utilities (heating, cooling, etc.). A structure typically is less than 400 square feet.
Sustainability: Formally known as the World Commission on Environment and Development, the Brundtland Commission's mission in the 1980s was to unite countries to pursue sustainable development. The Commission defined sustainability as the “development which meets the needs of current generations without compromising the ability of future generations to meet their own needs".
Sustainability also is defined as the creation or enhancement of environmental, economic, and social-cultural balance, as realized through business activities, individual actions, and community engagement. Sustainability addresses approaches, methods and practices that optimize the use of energy, water, and materials while reducing greenhouse gas emissions.”
Utilization: This performance measure assesses the degree to which each asset is utilized and is expressed as a percentage. It is calculated on a square footage basis, comparing the square footage used to the “design square footage” based on contract strength (Source: FRPC 2012).
Executive Summary
The facility survey for the Cascades JCC was completed June 23 to June 27, 2014.
The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
CASCADES
JOB CORPS CENTER
SEDRO-WOOLLEY, WASHINGTON
CASCADES JCC
10 MI5 0
2.0 - Descriptions
2.0 DESCRIPTIONS
In this section, the following information on the Center and its buildings and structures is presented in tabular format:
Building and Structures – This table indicates the building type, asset number, name, use group, gross square footage (GSF), construction year, number of floors, number of sleeping room and number of beds, construction type (noted as numerical values instead of code-specified Roman numerals), status (active or closed), and overall condition. The possible International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type III. This type of construction is where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces. Fire-retardant-treated wood framing complying with IBC section 2303.2 shall be permitted within exterior wall construction with a 2-hour rating or less.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
The overall building/structure condition is rated in one of three categories: good, fair, or poor.
Space Utilization by Function - This table compares the DOL recommended net square footage per enrollee and for the total function (e.g., housing, education, food service, recreation, medical/dental, administration, storage/support) to the actual values.
Net Square Footage by Building - This table compares the DOL recommended net square footage for the buildings with the function (e.g., housing, education, food service, recreation, medical/dental, storage/support) to the actual values and presents a percentage difference in the two values. In some instances, a recommended value is not available for sub-elements of a function; therefore, the recommended value is shown as “0”.
Environmental Management Report – This table summarizes regulatory related solid and hazardous waste information in accordance with the Resource Conservation and Recovery Act (RCRA) and the presence or absence of hazardous material storage facilities in accordance with Emergency Planning and Community Right-to-Know Act of
1986 (EPCRA). An inventory of petroleum storage tanks is noted as well as asbestos and polychlorinated biphenyls (PCBs) in accordance with the Clean Water Act (CWA) and Toxic Substance Control Act (TSCA), respectively. In addition, this report statuses air quality as required under the Clean Air Act (CAA).Any radon testing of buildings also is documented.
Site Descriptions – Tabular information is documented for the site. Among the data presented are the topography; total number of buildings and structures; roads, parking and sidewalks; fencing; site utilities; storage tanks; accessibility; historic preservation;
natural hazards; and sustainability. The overall condition of the site is rated in one of three categories: good, fair, or poor.
Building Descriptions – Tabular information, as well as photographs and floor plan drawings, are provided for each building or structure, as appropriate, in the following categories: real estate; accessibility; building envelope; interior finishes; vertical circulation; heating, ventilation and air conditioning (HVAC); plumbing; fire protection;
electrical services; fire alarms; carbon monoxide detection; communication; and building metering. The overall condition of the building and its five key subsystems (structure, exterior, interior, mechanical, and electrical) are rated in one of three categories: good, fair, or poor. If applicable, recommendations for renovation or demolition are provided.
BUILDINGS AND STRUCTURES
01003 CASCADES 12/10/2014
1Page: of Date:
0010 - RECREATION/GYMNASIUM
0012 - MOUNT RAINIER DORMITORY
0013 - DINING HALL/CULINARY ARTS
0015 - ACADEMICS/EVERGREEN
DORMITORY
0016 - CHALLENGER DORMITORY
0017 - WHITEWATER DORMITORY
0024 - CAREER TRANSITION
0025 - DENTAL ASSISTANT
0026 - VOCATIONAL STORAGE
0027E - WAREHOUSE/RECEIVING
0027W- FMC/MED ASSIST/MED OFFICE
SPEC/HEALTH OCC
0028 - CENTER MAINTENANCE SHOP
0029 - FLAM STOR/CENTER SUPPORT
0030 - CULTURAL CENTER
0031 - VOCATIONAL BLDG.
0032 - ADMIN/EDUCATION/MED-DENT
0033A - SAFETY/STORAGE
0033B - MENTAL HEALTH MEETING
ROOM
0034 - SECURITY/SAFETY
0048 - LRC/LIBRARY
0050 - CEMENT MASONRY
0057 - BUSINESS/CLERICAL
0063 - CENTER MAINTENANCE
STORAGE
0051 - CARPENTRY P.E.T.S. (74FT X
25FT)
0052 - STORAGE (8FT X 10FT)
0053 - STORAGE (8FT X 15FT)
0054 - CARPENTRY STORAGE (24FT X
64FT)
0055 - CARPENTRY MOCK-UP (14FT X
20FT)
0056 - ELECTRICAL MOCK-UP (15FT X
25FT)
0057A - GAZEBO (15FT DIAMETER)
0057B - GAZEBO (15FT DIAMETER)
0057C - GAZEBO (15FT DIAMETER)
0057D - GAZEBO (15FT DIAMETER)
0057E - PAVILION (35FT DIAMETER)
0057F - PAVILION (35FT DIAMETER)
0057G - PAVILION (13FT X 30FT)
0058 - CARPORT (20FT X 30FT)
0059 - CEMENT MASONRY MOCK-UP
(16FT X 30FT)
0061 - STORAGE (7FT X 8FT)
0062 - STORAGE (12FT X 20FT)
0064 - GREENHOUSE (25FT X 44FT)
0065 - TRANSFORMER BUILDING (8FT X
8FT)
Name GSF
15,740 17,560 26,880 17,560
18,220 29,800 2,100 2,100 7,500
12,750 13,230
3,600 1,590
11,040 13,980 31,240 1,140
1,010 1,850 1,800 1,580 1,200
1,850
1,560
1,050 1,050
1,100
Active Active Active Active
Active Active Active Active Active Active Active
Active Active Active Active Active Active Active
Active Active Active Active Active
Active
Active Active Active
Active
Active
Active Active Active Active Active Active Active Active Active
Active Active Active Active
StatusType
Building Building Building Building
Building Building Building Building Building Building Building
Building Building Building Building Building Building Building
Building Building Building Building Building
Structure
Structure Structure Structure
Structure
Structure
Structure Structure Structure Structure Structure Structure Structure Structure Structure
Structure Structure Structure Structure
Use Group Built Flrs Const
Assembly Residential Assembly Residential
Residential Residential Business Business Storage Storage Business
Business Storage Assembly Business Business Business Business
Business Business Business Business Storage
Storage
Storage Storage Storage
Storage
Business
Assembly Assembly Assembly Assembly Assembly Assembly Assembly Storage Business
Storage Storage Utility/Misc.
Utility/Misc.
Good Good Good Good
Good Good Good Good Good Good Good
Good Good Good Good Good Good Good
Good Good Good Good Good
Good
Fair Good Good
Fair
Good
Good Good Good Good Good Good Good Poor Good
Good Good Good Good
ConditionAsset Number
0100300002 0100300003 0100300004 0100300005
0100300006 0100300007 0100300008 0100300009 0100300019 0100300010 0100300029
0100300011 0100300012 0100300013 0100300014 0100300015 0100300018 0100300023
0100300016 0100300030 0100300026 0100300027 0100300028
0100300024
0100300031 0100300032 0100300025
0100300034
0100300035
0100300036 0100300037 0100300038 0100300039 0100300040 0100300041 0100300033 0100300022 0100300043
0100300042 0100300021 0100300020 0100300045
BUILDINGS AND STRUCTURES
01003 CASCADES 12/10/2014
2Page: of Date:
0067 - ELECTRICAL MOCK-UP (20FT X
21FT)
Name GSF
525 Active
StatusType
Structure
Use Group Built Flrs Const
Business 2004 1 5 Good
ConditionAsset Number
0100308014
23 234,050
20 10,360
43 244,410
Buildings
Structures
Total
GSF
GSF
GSF
Summary
12/10/2014
Space Utilization By Function 01003 Cascades Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 340 Non Residents 0
340Total Students
(340)
(340)
(340)
DIFFERENCE
36,720
24,130
8,840
43,265
60,611
13,508
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (340) Non-Academic
36 -- ACT (Off-Ctr) 30 -- Business Office Technologies 40 -- Carpentry + 20 -- Cement Masonry + 60 -- Cert. Nursing Asst.
20 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 30 -- Medical Assistant 30 -- Medical Office Specialist 30 -- Office Administration 24 -- Painting +
Vocational Theory (128)
Dining (1 Serving) Food Preparation Food Storage
5,330 3,947 5,353
25,381 3,254
10,793 8,893
1,466 9,208 7,106 3,812 2,186 6,451 3,171 1,806
3,878
1,841
5,772 5,573 2,163
3,400 2,720 4,080
24,480 2,040
3,400 3,400
1,200 3,000 1,500 2,400 1,200 1,800
1,350 1,800
1,280
5,440 2,040 1,360
1,930 1,227 1,273
1,214
7,393 5,493
6,208 5,606 1,412
4,651 2,271
-1,350 2,078
3,533
Vocations
6,545
36,481
4,668
12/10/2014
Space Utilization By Function 01003 Cascades Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 306 104,040 168,659
(340)
(340)
(340)
(340)
(0)
DIFFERENCE
234,050
0.72
TOTAL GSF
NET TO GROSS RATIO
17,000
3,750
6,800
6,800
15,903
5,067
10,063
19,031
1,211
Arts & Crafts Gymnasium Pool Hall Recreation Office Recreation Room Recreation/Snack Bar T.V. Room Weight Room
Medical Only Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
4.94 6.09
1,463 7,770 1,970 1,638
1,395
4,682
10,063
2,570 16,461
1,211
1,680 2,070
6,800
2,720 4,080
1,463 7,770 1,970 1,638
1,395
-1,295 2,612
3,263
-150 12,381
1,211
RESIDENT
NON-RESIDENT
(340)
(0) 15
50 17,000
-1,097
1,317
3,263
12,231
1,211
64,619
Net Square Footage By Building Date: 12/10/2014 Page: 1
Center: CASCADES (01003) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
6,670 8,049 7,366 3,296
1,202
2,118 1,438
1,497
1,160
1,074 2,150 1,468
1,139 1,758
0012 - MOUNT RAINIER DORMITORY
0017 - WHITEWATER DORMITORY
0016 - CHALLENGER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0012 - MOUNT RAINIER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0017 - WHITEWATER DORMITORY
0016 - CHALLENGER DORMITORY
0017 - WHITEWATER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0016 - CHALLENGER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0017 - WHITEWATER DORMITORY
0016 - CHALLENGER DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0015 - ACADEMICS/EVERGREEN DORMITORY
0016 - CHALLENGER DORMITORY
0012 - MOUNT RAINIER DORMITORY
0017 - WHITEWATER DORMITORY
Bldg Name Actual NSF Difference
25,381
5,330
3,254
5,353
3,947
Sub Total: 43,265
24,480
3,400
2,040
4,080
2,720
36,720
1,930
1,214
1,273
1,227
( 340
6,545 rooms; beds rooms; beds rooms; beds rooms; beds
Page: 2
Center: CASCADES (01003) of 4
EDUCATION
Academic
Vocational Theory (128)
Carpentry
Cement Masonry
Culinary Arts
Painting
Facilities Maint. and Const.
Medical Assistant
Non-Academic
Business Office Technologies
Medical Office Specialist
Function Suggested
NSF
2,231 4,770
2,226
1,841
4,337 2,807 2,064
1,627 3,505 1,974
2,186
1,426 2,452
2,585 3,044
1,600 1,571
2,002
2,089 1,746
1,354
1,466
1,806
0032 - ADMIN/EDUCATION/MED-DENT
0015 - ACADEMICS/EVERGREEN DORMITORY
0032 - ADMIN/EDUCATION/MED-DENT
0032 - ADMIN/EDUCATION/MED-DENT
0032 - ADMIN/EDUCATION/MED-DENT
0032 - ADMIN/EDUCATION/MED-DENT
0031 - VOCATIONAL BLDG.
0031 - VOCATIONAL BLDG.
0026 - VOCATIONAL STORAGE
0030 - CULTURAL CENTER
0050 - CEMENT MASONRY
0031 - VOCATIONAL BLDG.
0026 - VOCATIONAL STORAGE
0013 - DINING HALL/CULINARY ARTS
0031 - VOCATIONAL BLDG.
0026 - VOCATIONAL STORAGE
0030 - CULTURAL CENTER
0027W- FMC/MED ASSIST/MED OFFICE SPEC/HEALTH OCC
0031 - VOCATIONAL BLDG.
0025 - DENTAL ASSISTANT
0027W- FMC/MED ASSIST/MED OFFICE SPEC/HEALTH OCC
0024 - CAREER TRANSITION
0048 - LRC/LIBRARY
0048 - LRC/LIBRARY
0032 - ADMIN/EDUCATION/MED-DENT
0017 - WHITEWATER DORMITORY
0033A - SAFETY/STORAGE
0031 - VOCATIONAL BLDG.
0057 - BUSINESS/CLERICAL
0027W- FMC/MED ASSIST/MED OFFICE SPEC/HEALTH OCC
Bldg Name Actual NSF Difference
10,793
1,841
9,208
7,106
2,186
3,878
6,451
3,171
8,893
1,466
1,806
3,400
1,280
3,000
1,500
1,200
1,800
1,800
3,400
1,200
7,393
6,208
5,606
2,078
4,651
2,271
5,493
( 340 )
Page: 3
Center: CASCADES (01003) of 4
EDUCATION
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Cert. Nursing Asst.
Food Preparation
Food Storage
Dining (1 Serving)
Arts & Crafts
Gymnasium
Weight Room
Pool Hall
Recreation/Snack Bar
Recreation Room
T.V. Room
Recreation Office
Medical/Dental
Medical Only
Function Suggested
NSF
3,812
5,573
2,163
5,772
1,463
7,770
1,395
1,970
1,109
4,192
0027W- FMC/MED ASSIST/MED OFFICE SPEC/HEALTH OCC
0013 - DINING HALL/CULINARY ARTS
0013 - DINING HALL/CULINARY ARTS
0013 - DINING HALL/CULINARY ARTS
0010 - RECREATION/GYMNASIUM
0010 - RECREATION/GYMNASIUM
0010 - RECREATION/GYMNASIUM
0030 - CULTURAL CENTER
0030 - CULTURAL CENTER
0030 - CULTURAL CENTER
0030 - CULTURAL CENTER
0010 - RECREATION/GYMNASIUM
0030 - CULTURAL CENTER
0033B - MENTAL HEALTH MEETING ROOM
0032 - ADMIN/EDUCATION/MED-DENT
0033A - SAFETY/STORAGE
Bldg Name Actual NSF Difference
3,812
5,573
2,163
5,772
1,463
7,770
1,395
1,970
1,638
4,682
Sub Total:
Sub Total:
Sub Total:
Sub Total:
60,611
13,508
15,903
5,067
2,400
2,040
1,360
5,440
2,070
1,680
22,780
8,840
17,000
3,750
1,412
3,533
2,612
-1,295
37,831
4,668
-1,097
1,317
Page: 4
Center: CASCADES (01003) of 4
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
8,758
11,899 3,742
1,025 1,545
1,211
0027E - WAREHOUSE/RECEIVING
0032 - ADMIN/EDUCATION/MED-DENT
0034 - SECURITY/SAFETY
0033A - SAFETY/STORAGE
0027E - WAREHOUSE/RECEIVING
0028 - CENTER MAINTENANCE SHOP
0027W- FMC/MED ASSIST/MED OFFICE SPEC/HEALTH OCC
0063 - CENTER MAINTENANCE STORAGE
0029 - FLAM STOR/CENTER SUPPORT
0013 - DINING HALL/CULINARY ARTS
Bldg Name Actual NSF Difference
10,063
16,461
2,570
1,211
Sub Total:
Sub Total:
Sub Total:
10,063
19,031
1,211
6,800
4,080
2,720
6,800
6,800
3,263
12,381
-150
1,211
3,263
12,231
1,211
Environmental Management Report Center: CASCADES (01003)
Page: 1 Date: 12/10/2014 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building 29
Oil-based paint (200 gals), organic solvent (100 gals), propane (250 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Rural Skagit Sanitation Yes Organic solvent (< 25 gals/month)
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service
Various licensed contractors
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
01/17/1991 Friable/Non-Friable Dan Singleton
Yes No N/A Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
1 Petroleum - Gasoline 500 Near Building 26 Yes Yes
Tank Status Active
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 12/10/2014Center : Cascades (01003) Page: 1 of 2
Roof Repair/Replacement Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes Floor Finishes
Roof Repair/Replacement
Floor Finishes Floor Finishes
Wall Finishes Floor Finishes Roof Repair/Replacement
Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Roof flashing 9x9 floor tile, brown/white 12x12 floor tile, brown/tan
9x9 floor tile, gray 9x9 floor tile, tan 12x12 floor tile, brown/white 9x9 floor tile, tan/black
Roofing felt
12x12 flr. tile, tan (covered) 12x12 floor tile, tan
Asbestos cement board 12x12 floor tile, tan Roof flashing
12x12 floor tile, tan
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Around vent stacks Hallway, arts/crafts Weight room office
Lobby storage room 1st fl. closet, SW Stairwell landings 1st fl. jan. closet
Culinary arts roof
Dorm rooms, hallways 1st fl. jan. closet
Plaster vocation Bathroom, office Around vent stacks
Bathroom, paint shop
12000
10000
Building :
Building :
Building :
Building :
Building :
Building :
0010 - RECREATION/GYMNASIUM
0012 - MOUNT RAINIER DORMITORY
0013 - DINING HALL/CULINARY ARTS
0016 - CHALLENGER DORMITORY
0027W- FMC/MED ASSIST/MED OFFICE SPEC/HEALTH O
0031 - VOCATIONAL BLDG.
Asbestos-Containing Materials Inventory
Page: 2 of 2
Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Heating Roof Repair/Replacement
Floor Finishes
Bldg System
Bldg System
12x12 floor tile, gray 12x12 floor tile, tan 9x9 floor tile, green 9x9 floor tile, green/white 9x9 floor tile, tan/gray Pipe fitting insulation Roof flashing
9x9 floor tile, tan/red
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Lin. Ft.
Sq. Ft.
Location
Location
Unit
Unit
Quantity
Quantity
Storage/Support Vocational office Medical hallway East wing Southwest wing Storage/Support Rooftop HVAC units
Detention/isolation
14000 12500
Building :
Building :
0032 - ADMIN/EDUCATION/MED-DENT
0034 - SECURITY/SAFETY
Site Description
Satellite View of the Campus
Page: 1 Date: 12/10/2014 of 4
Comments:
Paving Type for Roads & Parking
A gravel road loops around Building 33A. Parking areas located between Administration Building 32 and Vocational Building 31 and near Dining Hall Building 13 and dormitory buildings are concrete. The visitor parking at west side of Security Building 34 is compacted dirt road.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. Center is not fully enclosed by fencing. A chain link fence with lockable gates secures the area of vocational buildings at the north-east side of campus. The site has an abundance of mature trees and well maintained green space and other plantings.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualSkagit County Public Utility District No. 1.Public Water Authority
None 0None
Water is metered at 8 locations for Job Corps buildings.Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 8None Municipal
Nearest fire station is Sedro Woolley Fire Department, approximately 4 miles from the center.
Fire Station Response time is 8 minutes.
Number of Deficiencies = 3
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures23 20Flat
Surrounding
Outdoor Recreation
Forest
Basketball, Football, Soccer, Soft/Baseball, Swing Set, Volleyball Retention Pond, Two Bioswales, Underground Utility Tunnel System
Vocations Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good
Fencing
Other Features
Page: 2 Date: 12/10/2014 of 4
Sewage Treatment Flow
Utility
Publicly Owned Treatment Works
Lessor
Gravity
Maintenance ResponsibilityOwnership
Comments: Propane is provided by Amerigas.
Cascade Natural Gas Corporation
Comments: Steam is provided to the center buildings from the on-site Lessor-operated power plant (Bldg. 19). At most center buildings, the steam is converted to hot water and used for space heating.
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
6. Central Plant
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 7
Drain Type On-Site Storm Water Management
Underground Retention Pond
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Yes GoodLessor
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Type Energy Source
Steam Natural Gas Most Cascades JCC buildings.
Bldgs Served
Ownership Maintenance Responsibility Plant Capacity Adequate Plant Condition
Lessor Lessor Yes Unknown
Page: 3 Date: 12/10/2014 of 4
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Puget Sound Energy (PSE)
Service is brought to the center from the main switchgear located in the lessor's power house. The 4.16/2.4 kV lines are routed through a loop of transformer vaults which are either above ground or underground in the tunnel. From these vaults the secondary 120/208V, 3-phase, 4 wire system is distributed to DOL leased buildings via their respective service disconnects and/or main distribution panels. Some buildings have their own meter while others are zone-metered. Dining Hall Building 13 and Dormitory Buildings 12, 15, 16 and 17 have backup power from an emergency generator in the power house for critical loads such as condensate pumps and cooking equipment. The emergency backup power is metered separately.
Vault Utility
Lessor Lessor
No
Comments:
Telephone Company
On-site Line Owner
Six T-1 lines are brought to the main telephone/server room located in Building 32. Local telephone service is provided by Frontier Communication with a T-1 line connected to router and long distance provided by AT&T travels via VoIP on the Job Corps Data Center network. The data and VoIP communication networks are routed via underground fiber optic cabling. A central fire alarm control/annunciator panel in Security Building 34 monitors fire alarm panels in Dining Hall Building 13, Warehouse Building 27E, Health Occupations Building 27W, and dormitory Buildings 12, 15, 16, and 17. Other fire alarm panels at the center are monitored by lessor's central fire alarm control/annunciator panel in the power house. Comcast provides cable TV in all dormitory lounges and other recreational spaces at the center. The security system is limited to dormitories only with door alarms for unauthorized ingress/egress detection.
Frontier Communication
Maint. Responsibility
Center Center, Lessor
Door Alarms
4.16/2.4 kV, 3-Phase, 4 Wire
120/208V, 3-Phase, 4 WireUnderground
UndergroundPrimary Service
Secondary Service
Distribution Characteristics
9. Electrical (Communication/Alarm/Security)
7. Electrical (Service)
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Sport Light
Photocell, Time Clock Photocell, Time Clock Photocell Photocell Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center, Lessor Center, Lessor Yes Good
Comments: The site lighting system, consisting of building-mounted exterior and pole-mounted fixtures, is owned and maintained by the lessor. The site lighting system is controlled by photocells and time clocks.
ATS MTS
Yes No
Number of Deficiencies = 4
Fire Alarm Security
Metering Individual and Groups
Page: 4 Date: 12/10/2014 of 4
ACCESSIBILITY
Yes
Comments:
UnknownYesYes
The site and nine buildings were listed on the National Historical Preservation Registry in December, 2010.
Yes
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
04/01/1999
04/01/1999
Center
Center
Active
Active
Aboveground
Aboveground
Near Building 26
Near Building 57
Yes
Yes
Petroleum - Gasoline
Propane
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date
Earthquake Risk
High Low LowMedium LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
ID
Reg.
Number of Deficiencies = 1
Number of Deficiencies = 1
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
The site is well maintained and in good condition.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Equip/Veh Fueling
Heating
Purpose
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Comments: The Center currently uses the Benchmate a Computerized Maintenance Management System (CMMS) for preventive maintenance.
Yes
Yes
NO
NO
Yes
Yes
Yes
Yes
50 %
Building Descriptions and Structures
BUILDING 10 - RECREATION/GYMNASIUM
Building Descriptions
Page: 1 of 104
Building: 0010 - RECREATION/GYMNASIUM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
CMU Masonry
Comments: There is stucco finish on the exterior walls.
Wall Roof None Batt
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly 15,740 11,157 1 Leased 1963 Not Evaluated
Comments: Strobes are not provided in the restrooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 3
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
The condition and life expectancy of the roof is based on visual observation during the June 2014 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains, Scuppers 1996 2 Flat Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 104
Building: 0010 - RECREATION/GYMNASIUM
INTERIOR FINISH
Carpet Concrete Rubber Terrazzo Vinyl Tile Wood
Ceramic Tile Drywall Plaster
Metal Units - Metal Frame Metal Units - Wood Frame
Wood Units - Wood Frame
VERTICAL CIRCULATION
Metal Ladder
Comments: There is a steel ladder to the roof hatch.
Casement - Wood Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;
Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Four heating and ventilating units serve the gymnasium.
An air handler with hot water coils serves the offices and restrooms.
Heating hot water is provided by two cast iron Burnham series 8B boilers manufactured in 2002.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Unit Ventilator
Single Duct
Fan Coil
Two-Pipe
Two-Pipe
Two-Pipe
Electric
Electric
Electric
Mechanical
Natural
Mechanical
None
None
None
Gymnasium
Offices
Recreation Area
Ceilings
Page: 3 of 104
Building: 0010 - RECREATION/GYMNASIUM
Mechanical
Mechanical
Mechanical
Toilet/Shower
Restroom
Kiln Area
One 100-gallon commercial gas water heater provides domestic hot water. The water heater is A. O.
Smith model BTR 197 118 with 199 MBH input, 193 GPH recovery capacity, and manufactured on 5/14/2010.
Comments:
Cast-Iron None Cast-Iron
Electric Water Cooler Hose Bibb Lavatory Shower Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Window Unit None Electric Natural None Recreation Area
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
Number of Deficiencies = 1
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution