GadsdenGadsden
Job Corps Center Gadsden, AL
Facility Planning ReportFacility Planning Report Volume II
Supporting Data
Fi lFinal January 2012
Department of Labor/ Office of Job Corps
22Gadsden Job Corps Center
GadsdenGadsden
Job Corps Center Gadsden, AL
Facility Planning ReportFacility Planning Report Volume II
Supporting Data
Fi lFinal January 2012
Male Dormitory Building 3
33 Gadsden Job Corps Center
CONTENTS
GADSEN JOB CORPS CENTER
FACILITY PLANNING REPORT
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Ownership
• Facility Assessment by Function
• Energy
• Environmental Issues
• Sustainability
• Accessibility Standards
• Current and Completed Project Since the Last Survey
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY08) Plan
• Signifi cant Issues
• PY 11 Plan Overview
• Summary of Proposed Projects
• Regional Projects
• Proposed Site Plan Implementation Plan
• Summary of National Projects
• Project Data Sheets
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• Vicinity Map
• Location Map
• Existing Site Plan
D. DESCRIPTIONS
• Building and Structures
• Space Utilization By Function
• NSF by Building
• Energy Management Report
• Environmental Management
Radon Report
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
44Gadsden Job Corps Center
55 Gadsden Job Corps Center
G adsden Job C orps C enter
77 Gadsden Job Corps Center
D Descriptions
BUILDINGS AND STRUCTURES
00425 GADSDEN 06-JAN-12
1Page: of 1
0001 - ADMIN/EDUCATION/WELLNESS
0002 - COUNSELOR
0003 - MALE DORMITORY
0004 - FEMALE DORMITORY
0005 - DRIVER'S EDUCATION
0006 - EDUCATION
0009 - CAFETERIA/CULINARY ARTS
0010 - GUARD HOUSE
0011 - VACANT
0013 - ACADEMIC
0014 - PHYSICAL FITNESS CENTER
A - GAZEBO
B - GAZEBO
Name GSF
14,610 2,210
22,760 28,540
13,250 7,000
1,390 1,467
11,463
Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Structure Structure
Use Group Built Flrs Const
Business Business Residential Residential Business Business Assembly Business Business Business Assembly Assembly Assembly
Good Good Good Good Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0042500003 0042500011 0042500008 0042500009 0042500010 0042500005 0042500004 0042500002 0042500012 0042500014 0042508104 0042508103 0042508105
11 103,435
2 160
13 103,595
Buildings
Structures
Total
GSF
GSF
GSF
Summary
January 06, 2012 Space Utilization By Function 00425 Gadsden
Page: 1 of 2
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 256 Non Residents 30
286Total Students
(256)
(286)
(286)
DIFFERENCE
25,600
16,260
5,148
31,667
18,052
4,027
Lounge Other Shower/Toilet Sleeping Storage
Academic (286) Non-Academic
10 -- ACT (Off-Ctr) 60 -- Business Office Technologies 24 -- Carpentry + 30 -- Cert. Nursing Asst.
30 -- Food Service + 20 -- Human Services Worker 60 -- Security Services
Vocational Theory (54)
Dining (2 Servings) Food Preparation Food Storage
2,835 4,236 2,734
20,262 1,600
4,657 4,315
1,000 2,721 1,537
1,426
1,872 1,724
2,560
3,072 18,432
1,536
2,860 2,860
2,400 1,800 1,200 1,800
2,100
2,288 1,716 1,144
-338 1,830
1,797 1,455
-1,400 -822
-1,148
-74
-416
-713
Vocations
6,067
1,792
-1,121
January 06, 2012 Space Utilization By Function 00425 Gadsden
Page: 2 of 2
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 255.08 72,953 75,298
(286)
(286)
(286)
(286)
(0)
DIFFERENCE
103,435
0.73
TOTAL GSF
NET TO GROSS RATIO
13,250
1,255
5,720
12,273
1,400
4,451
2,173
1,255
Canteen Gymnasium Hair Salon Meeting Room Men's Exercise Room Miscellaneous Recreation Pool Hall Recreation Office Recreation Storage Women's Exercise Room
Medical Only
Administration
Operations & Maintenance Warehouse
Vacant
4.39
7,832
1,484
1,400
4,451
1,288
1,255
2,288 3,432
-1,269
-1,403 -2,144
RESIDENT
NON-RESIDENT
(256)
(30) 15
50 12,800
-977
-1,269
-3,547
2,345
Net Square Footage By Building Date: 01/06/2012 Page: 1Center: GADSDEN (00425) of 4
HOUSING
Sleeping
Lounge
Storage
Shower/Toilet
Other
Function Suggested NSF
11,062 9,200
2,835
1,600
1,520 1,214
3,906
0004 - FEMALE DORMITORY
0003 - MALE DORMITORY
0003 - MALE DORMITORY
0003 - MALE DORMITORY
0003 - MALE DORMITORY
0004 - FEMALE DORMITORY
0003 - MALE DORMITORY
0004 - FEMALE DORMITORY
Bldg Name Actual NSF Difference
20,262
2,835
1,600
2,734
4,236
Sub Total: 31,667
18,432
2,560
1,536
3,072
25,600
1,830
-338
4,236
( 256
6,067
Page: 2Center: GADSDEN (00425) of 4
EDUCATION
Academic
Vocational Theory (54)
Carpentry
Security Services
Food Service
Non-Academic
Business Office Technologies
Cert. Nursing Asst.
Human Services Worker
Function Suggested NSF
2,721
1,095
1,000
1,537
1,426
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0013 - ACADEMIC
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0014 - PHYSICAL FITNESS CENTER
0004 - FEMALE DORMITORY
0009 - CAFETERIA/CULINARY ARTS
0001 - ADMIN/EDUCATION/WELLNESS
0001 - ADMIN/EDUCATION/WELLNESS
0002 - COUNSELOR
0003 - MALE DORMITORY
0006 - EDUCATION
0002 - COUNSELOR
0004 - FEMALE DORMITORY
0001 - ADMIN/EDUCATION/WELLNESS
0005 - DRIVER'S EDUCATION
0001 - ADMIN/EDUCATION/WELLNESS
0006 - EDUCATION
0006 - EDUCATION
Bldg Name Actual NSF Difference
4,657
2,721
4,315
1,000
1,537
1,426
Sub Total: 18,052
2,860
1,800
2,100
1,800
2,860
2,400
1,200
16,260
1,797
-74
-1,148
-822
1,455
-1,400
( 286
1,792
Page: 3Center: GADSDEN (00425) of 4
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Dining (2 Servings)
Food Preparation
Food Storage
Gymnasium
Miscellaneous Recreation
Pool Hall
Canteen
Hair Salon
Meeting Room
Men's Exercise Room
Women's Exercise Room
Recreation Storage
Recreation Office
Medical Only
Function Suggested NSF
1,872
1,724
7,832
1,484
1,400
0009 - CAFETERIA/CULINARY ARTS
0009 - CAFETERIA/CULINARY ARTS
0009 - CAFETERIA/CULINARY ARTS
0014 - PHYSICAL FITNESS CENTER
0014 - PHYSICAL FITNESS CENTER
0004 - FEMALE DORMITORY
0004 - FEMALE DORMITORY
0004 - FEMALE DORMITORY
0004 - FEMALE DORMITORY
0014 - PHYSICAL FITNESS CENTER
0014 - PHYSICAL FITNESS CENTER
0004 - FEMALE DORMITORY
0014 - PHYSICAL FITNESS CENTER
0004 - FEMALE DORMITORY
0014 - PHYSICAL FITNESS CENTER
0001 - ADMIN/EDUCATION/WELLNESS
Bldg Name Actual NSF Difference
1,872
1,724
7,832
1,484
1,400
Sub Total:
Sub Total:
Sub Total:
4,027
12,273
1,400
2,288
1,716
1,144
1,255
5,148
13,250
1,255
-416
-713
-1,121
-977
Page: 4Center: GADSDEN (00425) of 4
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Warehouse
Operations & Maintenance
Vacant
Function Suggested NSF
4,265
1,255
0001 - ADMIN/EDUCATION/WELLNESS
0010 - GUARD HOUSE
0004 - FEMALE DORMITORY
0001 - ADMIN/EDUCATION/WELLNESS
0001 - ADMIN/EDUCATION/WELLNESS
0011 - VACANT
Bldg Name Actual NSF Difference
4,451
1,288
1,255
Sub Total:
Sub Total:
Sub Total:
4,451
2,173
1,255
5,720
3,432
2,288
5,720
5,720
-1,269
-2,144
-1,403
1,255
-1,269
-3,547
1,255
Energy Management Report Center: GADSDEN (00425)
Page: 1 Date: 01/06/2012 of 3
CENTER ENERGY DATA
None
ENERGY CONSUMPTION ASSESSMENT
19% 94,452 95,314 116,237
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Electric Company :
Percent Reduction since Baseline Year :
Natural Gas Company :
Property Status :
N/A
Alabama Power Company Alabama Gas Corporation (Alagasco)
Leased
2,146,900 7,325=
Total 9,769
MBtu
MBtu
Total $305,068 MBtu/ $31.228
BTU/GSF
BTU/GSF
BTU/GSF
Electricity
Natural Gas kWh
2,371 MCF = 2,444 MBtu
$275,986 $0.129= kWhElectricity
Natural Gas $29,082 = $12.266 MCF
ENERGY COST BY FUEL TYPE
WATER CONSUMPTION ASSESSMENT
FY 2007 Baseline:
Percent Reduction Since Baseline Year:
1,000 Gallons
1,000 Gallons
FY 2011 Energy Goal:
Energy Goals are being met. Keed up the Good Work to further Reduce Energy Usage.
FY 2011 Energy Consumption:
Note: The Federal Government has set a goal of 3% Energy Consumption Reduction per year in EO 13423.
6,783 6,240 4,597
32%
Water Goals are being met. Keep reducing Water Consumption.
Note: The Federal Government has set a goal of 2% Water Consumption Reduction per year in EO 13423.
FY 2011 Goal:
FY 2011 Water Consumption:
1,000 Gallons
FY 2003 Energy Baseline:
Page: 2 Date: 01/06/2012 of 3
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 78°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 Date: 01/06/2012 of 3
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 01/06/2012 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
N/A N/A
N/A No
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Browning Ferris Industries, Inc.
No N/A
N/A N/A N/A
N/A
N/A N/A
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
No Survey Performed None
No No
No No
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Radon
Date: Jan. 06, 2012Center : Gadsden (00425) Page: 1 of 1
0001 - ADMIN/EDUCATION/WELLNESS
0002 - COUNSELOR
0003 - MALE DORMITORY
0004 - FEMALE DORMITORY
0005 - DRIVER'S EDUCATION
0006 - EDUCATION
0009 - CAFETERIA/CULINARY ARTS
0010 - GUARD HOUSE
0011 - VACANT
0013 - ACADEMIC
0014 - PHYSICAL FITNESS CENTER
Bldg Name
09/28/2001
09/28/2001
09/28/2001
09/28/2001
09/28/2001
Test Date
Yes
No
Yes
Yes
No
Yes
Yes
No
No
N/A
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
GadsdenGadsden
Job Corps Center Site Description
Lower tier of the Campus
Page: 1 Date: 01/06/2012 of 4
Comments:
Paving Type for Roads & Parking
The road leading to Building 2 has a sinkhole.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterGadsden Water Works and Sewer BoardPublic Water Authority
Source Water Disinfection 0None
The lessor is responsible for maintenance of the water system. Only Physical Fitness Center Building 14 has an individual water meter.
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 5None Municipal
The center is provided with fire hydrants for fire protection. A city fire station is one mile away with a response time of five minutes.
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures11 2Terraced
Surrounding
Outdoor Recreation
Residential
Basketball None
Northeast corner of Building 1
Northern portion of perimeter
Northern portion of perimeter
Western portion of site
Wrought Iron
Chain Link
Wood
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 01/06/2012 of 4
Comments:
Sewage Treatment Flow
Sanitary drain collection is through the Lessor-owned sewer lines to publicly owned sewer lines.
Lessor
Publicly Owned Treatment Works
Lessor
Gravity
Maintenance ResponsibilityOwnership
Comments: A master gas meter is located in the yard near the northeast corner of Cafeteria/Culinary Arts Building 9. Individual buildings are not provided with gas meters.
Alabama Gas Corporation (Alagasco)
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Alabama Power Company
The primary overhead lines are brought from power poles on Lawier Circle along the campus northern boundary and North Fourth Place along the southern boundary. The system is radial, with multiple points of entry from the north and south. The secondary service to buildings on center is mostly overhead with pole-mounted transformers.
Three buildings, Male Dormitory Building 3, Female Dormitory Building 4 and Physical Fitness Center Building 14 each have an underground service with a pad-mounted transformer located in the back of the respective building.
All buildings have their own meter located on the exterior walls. Although all buildings are leased except Dormitory Buildings 3 & 4, Guard House Building 10 and Physical Fitness Building 14, all pole- and pad-mounted transformers are owned and maintained by the utility and lessor.
Pole and Pad Utility
Utility Utility
No
12,470/7,200 Volts, 3-Phase
120/240, 120/208 Volts, 3-Phase, 4 WireUnderground
OverheadPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System Number of Deficiencies = 1
System Capacity Adequate System Condition
Yes Good
4. Storm Water System
Drain Type On-Site Storm Water Management
Surface Run-off, Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Yes GoodLessor
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Lessor Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility,Lessor
System Capacity Adequate System Condition
Yes Good
Generator
None
ATS MTS
No No
6. Central Plant: None
Metering Individual
Page: 3 Date: 01/06/2012 of 4
ACCESSIBILITY
Yes
Site information reflects the condition of the main campus on Valley Street. The center also leases a small portion of a building at the Broad Street campus of the Gadsden State Community College; information on this site is not included.
Comments:
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Comments:
Telephone Company
On-site Line Owner
AT&T provides local telephone service with five T1 lines which terminate in the main telephone closet (MC) located on Building 1 first floor. One T1 line is dedicated to the long distance digital telephone VoIP service via Cisco Call Manager system. Another T1 line is dedicated to the wide area network (WAN) and two others are dedicated to local area networks (LAN), one for staff and one students. Cisco server/router in the MC transmits data to each building by fiber optic cables. The server is backed-up by portable UPS modules. Job Corp Data Center (JCDC) provides and maintains all data communication and VoIP systems on the center. The fire alarm systems on leased and center-owned buildings are stand alone. There are CCTV cameras on site but they are not in use. Male and Female Dormitory Buildings 3 and 4 have CCTV cameras installed in the corridor with color monitor in the RA room and door alarm at the egress door on each floor. Cable TV is provided in dormitories, cafeteria and gymnasium.
AT&T
Maint. Responsibility
Utility Utility
CCTV Cameras, Color Monitors, Door Alarms
There are no active or abandoned tanks on site.
STORAGE TANKS
Comments:
TypeStatus Location Owner Fuel Type Capacity Install Date
Earthquake Risk
Low Low LowLow LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
ID Reg.
Number of Deficiencies = 2
Accessible Parking: Accessible Slope:
No
Curb Cuts:
Yes
Ramps:
YesNo
Site Accessible Route:
HISTORIC PRESERVATION
9. Electrical (Communication/Alarm/Security)
NATURAL HAZARDS
Purpose
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center, Lessor Utility, Center, Lessor Yes Good
Comments: All pole-mounted lights are owned and maintained by the utility company. Building-mounted exterior lights on leased buildings and on DOL owned buildings are owned and maintained by the lessor and the center respectively.
Number of Deficiencies = 6
Fire Alarm Security
Page: 4 Date: 01/06/2012 of 4
GENERAL SITE CONDITION
Rating X Good Fair Poor
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
99 Gadsden Job Corps Center
F Correspondence and Reports
Building Descriptions and Utilities Gadsden
BUILDING 1 ADMIN/EDUCATION/WELLNESSBUILDING 1 - ADMIN/EDUCATION/WELLNESS
Building Descriptions Date: Dec. 20, 2011Center : Gadsden (00425) Page: 1 of 50
Building: 0001 - ADMIN/EDUCATION/WELLNESS
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Concrete Tees
Brick Masonry Concrete Panel Window Spandrel Panel
Wall Roof None Rigid
Metal Unit - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 14,610 10,320 2 Leased 1964 Unevaluated
Comments: There is grade level access to both floors.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Gutters and Downspouts 2007 16 Flat Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 50
Building: 0001 - ADMIN/EDUCATION/WELLNESS
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile Wood
CMU Ceramic Tile Drywall Exposed Structure FRP Plywood Wood Paneling
Aluminum Storefront - Aluminum Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs
Awning Unit - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;
Fixed - Metal Frame; Single Glazing; Hopper - Aluminum Frame; Single Glazing;
Acoustical Tile Fiberboard
Number of Deficiencies = 4
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating is provided by two furnaces located in the mechanical room that serve the 1st floor administration offices and the 2nd floor academic and medical areas.
Through-the-wall heat pump unit serves the maintenance office on the 1st floor.
Heating is provided by a split system heat pump. The indoor air handler is Carrier model FB4ANF024 that serves the receiving property specialist clerk and copy/mail room.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Packaged Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Single Duct
Through-The- Wall Unit
Single Duct
None
None
Refrigerant
Electric
Electric
Electric
Mechanical
Natural
Natural
None
None
None
Classrooms and Offices
Offices
Storage
Ceilings
Page: 3 of 50
Building: 0001 - ADMIN/EDUCATION/WELLNESS
Mechanical Restroom
Ventilation Area Served
Split Direct Expansion (Air
Source)
Packaged Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Single Duct
Through-The- Wall Unit
Single Duct
Fan Coil
Window Unit
Refrigerant
None
Refrigerant
Refrigerant
None
Electric
Electric
Electric
Electric
Electric
Mechanical
Natural
Mechanical
Natural
Natural
None
None
None
None
None
Classrooms and Offices
Offices
Storage
Electronic Equipment
Room
Classrooms
Exhaust Ventilation
Two DX split -systems provide cooling to the 1st floor administration offices and the 2nd floor academic and medical areas. The outdoor air-cooled condensing units are Rheem model RAWE120CAZ with 10 ton cooling capacity and manufactured in 06/2008 and RAWE241CAZ with 20 ton cooling capacity and manufactured in 06/2005.
Through-the-wall heat pump unit serves the maintenance office on the 1st floor.
An outdoor heat pump provides cooling to a DX coil in an indoor air handler Carrier model FB4ANF024 that serves the receiving property specialist clerk and copy/mail room.
The server room on 1st floor is served by a split system A/C unit. The condensing unit is located on the roof that provides cooling to an indoor ductless evaporating unit.
Two window units serve the business tech classes. These are no longer in operation and have been abandoned in-place.
Comments:
Comments:
Comments:
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Air Conditioning
Page: 4 of 50
Building: 0001 - ADMIN/EDUCATION/WELLNESS
A 10 gallon electric water heater under the counter in the women's toilet is Rheem model 61VP10S, 2 KW input.
Comments:
Cast-Iron None Cast-Iron
Electric Water Cooler Hose Bibb Lavatory Service Sink Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: This building is a jointly used by the center and Gadsden State Community College (GSCC). The building electrical service originates from a bank of three pole-mounted transformers and a meter located on the north side of the building. Service terminates in a main distribution panelboard located in the GSCC main electrical room. Two 225A panels located on the second floor serve the admin/education/wellness facilities.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
LIGHTING
Page: 5 of 50
Building: 0001 - ADMIN/EDUCATION/WELLNESS
FIRE ALARM
Comments: The fire alarm control/annunciator panel located in the corridor near center director's office on the first floor is a Notifier Model SFP-400.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Storage Rooms
Classrooms
Medical/Dental
Corridors & Stairs
Toilets
Reception
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
BUILDING 2 COUNSELORBUILDING 2 - COUNSELOR
Page: 6 of 50
Building: 0002 - COUNSELOR
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Wood Siding
Wall Roof Batt Batt
Metal Unit - Metal Frame Storefront - Aluminum Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 2,210 1,192 1 Owned 1996 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 1996 5 Hip Entire Building
3. Roof
Page: 7 of 50
Building: 0002 - COUNSELOR
INTERIOR FINISH
Carpet Concrete Vinyl Tile
Drywall
Wood Unit - Metal Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Ramp
Comments: There are concrete stairs and a concrete ramp leading to the entries.
Sliding - Metal Frame; Double Glazing;
Acoustical Tile
Exhaust Ventilation
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating is provided by a split system heat pump with supplemental electric resistance heating coil. The indoor air handler is York model MA20DN21A and the condensing unit is York model THRD60S41S1A.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 3
Page: 8 of 50
Building: 0002 - COUNSELOR
The 20-gallon electric water heater is Rheem model 81VP20S, S/N R0697306481, 2 KW input.Comments:
Cast-Iron None None
Electric Water Cooler Hose Bibb Lavatory Service Sink Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Comments: Service is brought from a pole-mounted transformer located on the south side of the building. Service terminates in a 200A main circuit breaker and a meter installed on the south exterior wall. A 200A panelboard with main circuit breaker is located in the mechanical room.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Main Circuit Breaker 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling is provided by a split system heat pump. The indoor air handler is York model MA20DN21A and the condensing unit is York model THRD60S41S1A with 5 ton cooling capacity.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 9 of 50
Building: 0002 - COUNSELOR
FIRE ALARM
None
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Toilets
Storage Rooms
Corridors & Stairs
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING 3 MALE DORMITORYBUILDING 3 - MALE DORMITORY
Page: 10 of 50
Building: 0003 - MALE DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood, Concrete
CMU Masonry
Wall Roof Granulated Styrofoam Beads Batt
Metal Unit - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 22,760 15,815 2 Owned 1993 Unevaluated
Comments: The common areas are provided with A/V alarm devices but not in the designated ADA sleeping rooms and bathrooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The remaining life expectancy is based on visual observation during the survey. The roof was repaired in 2010.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 1993 10 Hip Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Page: 11 of 50
Building: 0003 - MALE DORMITORY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Concrete Drywall Fabricated Marble Panel Grooved Block
Metal Unit - Metal Frame Storefront - Metal Frame
Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Ramp
Comments: There are concrete ramps leading to the entries.
Fixed - Metal Frame; Double Glazing; Fixed - Metal Frame; Single Glazing;
Single Hung - Metal Frame; Double Glazing; Sliding - Metal Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 3
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Each of dormitory wings A, B, C and D has two HVAC zones. Each zone is served by a set of split system heat pumps. Eight dormitory heat pumps and two common area heat pumps are located in the equipment yard and the associated air handlers with supplemental electric resistance heating coils are located in the mechanical rooms. The typical air handler that serves the dormitory is a Trane model 4TEC3F484B1000AA, manufactured in 12/2007 and each common area unit is a Trane model TWE090A300BA, manufactured in 9/2003. The typical outdoor unit that serves the dormitory is a Trane model 4TWA3048A3000AA, manufactured in 12/2007 and each common area unit is a Trane model TWA090A300EA, manufactured in 9/2003.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Page: 12 of 50
Building: 0003 - MALE DORMITORY
Mechanical
Mechanical
Toilet/Shower
Laundry
There are four electric water heaters and four hot water storage tanks in each of the two mechanical rooms. The typical electric water heater is Rheem model E120A-54-G and has a capacity of 120 gallon, 54 KW input, 98% efficiency and manufactured in 6/2006. The typical storage tank is Lochinvar model
RJA120.
Comments:
Cast-Iron None None
Bathtub Electric Water Cooler Hose Bibb Laundry Tray Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)
None
Ventilation Area Served
Copper Copper Electric None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
PLUMBING
Exhaust Ventilation
Each of dormitory wings A, B, C and D has two HVAC zones. Each zone is served by a set of split system heat pumps. Eight dormitory heat pumps and two common area heat pumps are located in the equipment yard and the associated air handlers with DX coils are located in the mechanical rooms. The typical air handler that serves the dormitory is a Trane model 4TEC3F484B1000AA, manufactured in 12/2007 and each common area unit is a Trane model TWE090A300BA, manufactured in 9/2003. The typical outdoor unit that serves the dormitory is a Trane model 4TWA3048A3000AA with 4 ton cooling capacity and manufactured in 12/2007 and each common area unit is a Trane model TWA090A300EA with 7.5 ton cooling capacity and manufactured in 9/2003.
Comments:
Number of Deficiencies = 4
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 3
Fuel Distribution4.
Page: 13 of 50
Building: 0003 - MALE DORMITORY
Wet None ABC Type Fire Extinguisher
Comments: Only the janitor closets and mechanical rooms are sprinklered, not the rest of the building.
Comments: Service is brought from a pad-mounted transformer located in the back of the building near the HVAC equipment. A meter is installed on the building exterior across from the transformer. Service terminates in a 2000A main distribution panel (MDP) located in the mechanical room on the first floor. The MDP feeds distribution panels throughout the building including a 600A panel serving HVAC equipment.
FIRE ALARM
Comments: The fire alarm control panel located in the mechanical room is a Notifier System 500. A remote annunciator panel is located in the main lobby on first floor.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Toilets
Shaving, Make-Up, Grooming
Housing Lounge
Corridors & Stairs
Recreation
Equipment Rooms (Elec/Mech)
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
Number of Deficiencies = 1
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
Page: 14 of 50
Building: 0003 - MALE DORMITORY
Comments: CCTV cameras are installed in the corridor on each dormitory floor with a color monitor located in the RA office.
Connected to Main System Closed Circuit TV None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
Comments: There is no plausible means by which harmful levels of CO could enter sleeping rooms.
CARBON MONOXIDE DETECTION
BUILDING 4 FEMALE DORMITORYBUILDING 4 - FEMALE DORMITORY
Page: 15 of 50
Building: 0004 - FEMALE DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry, Concrete
Wood, Concrete
CMU Masonry Concrete
Wall Roof Granulated Beads Batt
Metal Unit - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 28,540 19,587 3 Owned 1993 Unevaluated
Comments: The common areas are provided with A/V alarm devices but not in the designated ADA sleeping rooms and bathrooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The remaining life expectancy is based on visual observation during the survey. The roof was repaired in 2010.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 1993 10 Hip Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Page: 16 of 50
Building: 0004 - FEMALE DORMITORY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Concrete Drywall Fabricated Marble Panel
Metal Unit - Metal Frame Storefront - Metal Frame
Wood Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs Ramp
Comments: There are concrete ramps leading to the entries.
Fixed - Metal Frame; Double Glazing; Fixed - Metal Frame; Single Glazing;
Fixed - No Frame; Glass Block Glazing; Single Hung - Metal Frame; Double Glazing;
Sliding - Metal Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 3
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Each of dormitory wings A, B, C and D has two HVAC zones. Each zone is served by a set of split system heat pumps. Eight dormitory heat pumps, two common area heat pumps and one basement heat pump are located in the equipment yard and the associated air handlers with supplemental electric resistance heating coils are located in the mechanical rooms. The typical air handler that serves the dormitory is a Trane model 4TEC3F484B1000AA, manufactured in 01/2008, each common area unit is a Trane model TWE090A300BA, manufactured in 10/1992 and the air handler that serves the basement is York model F4EH120A33A. The typical outdoor unit that serves the dormitory is a Trane model 4TWA3048A3000AA and manufactured in 01/2008, each common area unit is a Trane model TWA090A300EA and manufactured in 9/2003 and the outdoor unit that serves the basement is a York model E2FB120A25A.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Page: 17 of 50
Building: 0004 - FEMALE DORMITORY
Mechanical
Mechanical
Mechanical
Toilet/Shower
Laundry
Barber Room
There are four electric water heaters and four hot water storage tanks in each of the two mechanical rooms. The typical electric water heater is Rheem model E120A-54-G and has a capacity of 120 gallon, 54 KW input and 98% efficiency. The typical storage tank is Lochinvar model RJA120.
Comments:
Cast-Iron None None
Bathtub Electric Water Cooler Hose Bibb Laundry Tray Multi-Compartment Sink Service Sink Shower Water Closet (Flush Valve)
None
Ventilation Area Served
Copper Copper Electric None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
PLUMBING
Exhaust Ventilation
Each of dormitory wings A, B, C and D has two HVAC zones. Each zone is served by a set of split system heat pumps. Eight dormitory heat pumps, two common area heat pumps and one basement heat pump are located in the equipment yard and the associated air handlers with DX coils are located in the mechanical rooms. The typical air handler serves the dormitory is a Trane model 4TEC3F484B1000AA, manufactured in 01/2008, each common area unit is a Trane model TWE090A300BA, manufactured in 10/1992 and the air handler serves the basement is York model F4EH120A33A. The typical outdoor unit serves the dormitory is a Trane model 4TWA3048A3000AA with 4 ton cooling capacity and manufactured in 01/2008, each common area unit is a Trane model TWA090A300EA with 7.5 ton cooling capacity and manufactured in 9/2003 and the outdoor unit serves the basement is a York model E2FB120A25A with 10 ton cooling capacity.
Comments:
Number of Deficiencies = 3
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 1
Fixtures3. Number of Deficiencies = 4
Fuel Distribution4.
Page: 18 of 50
Building: 0004 - FEMALE DORMITORY
Wet None ABC Type Fire Extinguisher
Comments: Only the janitor closets and mechanical rooms are sprinklered, not the rest of the building.
Comments: Service is brought from a pad-mounted transformer located in the back of the building near the HVAC equipment. A meter is installed on the building exterior across from the transformer. Service terminates in a 2500A main distribution panel (MDP) located in the mechanical room on the first floor. The MDP feeds distribution panels throughout the building including a 600A panel serving HVAC equipment.
FIRE ALARM
Comments: The fire alarm control panel located in the mechanical room is a Notifier System 500. A remote annunciator panel is located in the main lobby on the first floor.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Lounges
Offices
Sleeping Rooms
Toilets
Shaving, Make-Up, Grooming
Housing Lounge
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
Number of Deficiencies = 2
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 2
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 19 of 50
Building: 0004 - FEMALE DORMITORY
Comments: CCTV cameras are installed in the corridor on each dormitory floor with a color monitor located in the RA office.
Connected to Main System Closed Circuit TV None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
Comments: There is no plausible means by which harmful levels of CO could enter sleeping rooms.
CARBON MONOXIDE DETECTION
BUILDING 5 DRIVER'S EDUCATIONBUILDING 5 - DRIVER S EDUCATION
Page: 20 of 50
Building: 0005 - DRIVER'S EDUCATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Concrete Tees
Brick Masonry
Wall Roof None Rigid
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 500 438 1 Leased 1964 Unevaluated
Comments: Gadsden Job Corps Center occupies 500 GSF of this 7,700 GSF building.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Gutters and Downspouts 1998 7 Flat Entire Building
3. Roof
Page: 21 of 50
Building: 0005 - DRIVER'S EDUCATION
INTERIOR FINISH
Carpet
Drywall
Wood Unit - Wood Frame
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
None
None
Acoustical Tile
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The only area currently occupied by GJCC is the Driver's Education classroom and the associated small office and storage room at the northeast corner of the building. Heating and ventilation air for this area is supplied from the GSCC building system.
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Single Duct None Electric Mechanical None Classrooms and Offices
Ventilation2.
Page: 22 of 50
Building: 0005 - DRIVER'S EDUCATION
None None None
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: A small portion of this building is occupied by GJCC which includes the Driver's Ed classroom, an office and a storage room. The branch circuits serving this space originate from the building distribution panels.
Service is brought from three pole-mounted transformers located in the back of the building with a meter.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics…