DJCC Environmental Survey Report

8 MB Posted

Attached to
New Dormitory, Welcome Center Construction and Demolition at Detroit JCC
Solicitation number
DOL121RB20559
Issued by

About this file

DOL121RB20559 - Environmental Survey Report (June 7 2011)

Text of this file

TABLE 1A

Building 1A Asbestos Bulk Sample Results Detroit Job Corp Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

TEC-01 Unknown No location listed in TTL report SM Spray-on Fireproofing ACM 4 Material not observed by GZA

TEC-02 Unknown TSI Corrugated Straight Pipe Insulation ACM

TEC-03 Unknown TSI Corrugated Straight Pipe Insulation ACM

TEC-04 Unknown TSI White Fibrous Straight Pipe Insulation ACM

TEC-05 Unknown TSI Gray Fibrous Elbow Pipe Insulation ACM

TEC-06 Unknown TSI Gray Fibrous Elbow Pipe Insulation ACM

TEC-07 Unknown No location listed in TTL report MM 9" x 9" Dark Gray, Black and White

Streaked Floor Tile ACM Material not observed by GZA

TEC-08 Unknown No location listed in TTL report MM 9" x 9" Dark Gray, Black and White

Streaked Floor Tile ACM Material not observed by GZA

TEC-09 Unknown No location listed in TTL report MM 9" x 9" Beige and Tan Speckled Floor

Tile NAD 5 NA 6

TEC-10 Unknown No location listed in TTL report MM 9" x 9" Beige and Tan Speckled Floor

Tile

NAD NA

TEC-11 Unknown No location listed in TTL report MM 9" x 9" Putty Streaked Floor Tile ACM Material not observed by GZA

TEC-12 Unknown No location listed in TTL report MM 9" x 9" Coffee Streaked Floor Tile ACM Material not observed by GZA

TEC-13 Unknown No location listed in TTL report MM 9" x 9" Dark Coffee Streaked Floor Tile ACM Material not observed by GZA

TEC-14 Unknown No location listed in TTL report MM 1' x 1' Random Groove Ceiling Tile NAD NA

TEC-15 Unknown No location listed in TTL report SM Ceiling/Wall Plaster NAD NA

TEC-16 Unknown No location listed in TTL report MM 1' x 1' Small Dot Cream Colored Ceiling

Tile

NAD NA

TEC-17 Unknown No location listed in TTL report MM Glue Pods Above 1' x 1' Ceiling Tile NAD NA

TEC-18 Unknown No location listed in TTL report SM Wallboard NAD NA

TEC-19 Unknown No location listed in TTL report MM Carpet Mastic NAD NA

TEC-20 Unknown No location listed in TTL report MM 2' x 4' Random Dot Suspended Ceiling

Tile

NAD NA

TEC-21 Unknown No location listed in TTL report MM 2' x 4' False 2' x 2' Suspended Ceiling

Tile

NAD NA

TEC-22 Unknown No location listed in TTL report MM 12" x12" Pink Floor Tile NAD NA

TEC-23 Unknown No location listed in TTL report MM Mastic Below 12" x 12" Pink Floor Tile NAD NA

TEC-24 Unknown No location listed in TTL report MM Roof Filed Membrane NAD NA

TEC-25 Unknown No location listed in TTL report MM Vent Through Roof Flashing ACM 80 square feet

TEC-26 Unknown No location listed in TTL report MM Wall Base Flashing ACM 1,110 square feet

TEC-27 Unknown No location listed in TTL report MM Pitch Pan Flashing ACM 100 square feet

TEC-28 Unknown No location listed in TTL report MM Fan Base Flashing ACM 100 square feet

TEC-29 Unknown In Walls MM Duct Insulation Mastic ACM 2,450 square feet

TEC-30 Unknown No Location Given in Report TSI Tunnel Roof Insulation NAD NA

TEC-31 Unknown On Tunnel Ceiling SM Tunnel Plaster ACM 2,500 square feet

Analytical Results 3

13,600 linear feet

1,920 each

In walls and tunnels

In walls and tunnels

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 4 5/13/2011

Detroit Job Corp Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

TEC-32 Unknown On Tunnel Ceiling TSI Tunnel Insulation ACM 2,500 square feet

TEC-33 Unknown No location listed in TTL report MM 1' x 1' Glued-on SCT (Cream Colored) NAD NA

TEC-34 Unknown No location listed in TTL report MM 9" x 9" Green with Black and White

Streaks Floor Tile ACM 1,725 square feet

TEC-35 Unknown No location listed in TTL report 9" x 9" Green with Black and White

Streaks Floor Tile Mastic ACM 1,725 square feet

TEC-36 Unknown No location listed in TTL report MM Tan Linoleum ACM Material not observed by GZA

TEC-37 Unknown No location listed in TTL report MM Pebble Pattern Linoleum ACM 2,010 square feet

TEC-38 Unknown No location listed in TTL report MM 9" x 9" Cream Floor Tile ACM Material not observed by GZA

TEC-39 Unknown No location listed in TTL report MM 12" x 12" White with Grey Specks Floor

Tile

NAD NA

TEC-40 Unknown No location listed in TTL report MM 12" x 12"White with Dark Gray Streaks

Floor Tile

NAD NA

TEC-41 Unknown No location listed in TTL report MM 9" x 9" Dark Gray with Cream and Black

Streaks Floor Tile ACM Material not observed by GZA

TEC-42 Unknown No location listed in TTL report MM 9" x 9" Tan and Black Floor Tile ACM Material not observed by GZA

TEC-43 Unknown No location listed in TTL report MM 12" x 12" Bluish Gray with White and gray Streaks Floor Tile

NAD NA

TEC-44 Unknown No location listed in TTL report MM 9" x 9" Brownish Red with White and

Dark Brown Specks Floor Tile ACM Material not observed by GZA

TEC-45 Unknown No location listed in TTL report MM Black Mastic Under TEC-34 ACM Material not observed by GZA

TEC-46 Unknown No location listed in TTL report MM Tan Mastic Under TEC-35 NAD NA

TEC-47 Unknown No location listed in TTL report MM Black Mastic Under TEC-38 ACM Material not observed by GZA

TEC-48 Unknown No location listed in TTL report MM Tan Mastic Unser TEC-39 NAD NA

TEC-49 Unknown No location listed in TTL report MM Yellow/Tan Mastic Under TEC-40 NAD NA

TEC-50 Unknown No location listed in TTL report MM Black Mastic Under TEC-41 ACM Material not observed by GZA

TEC-51 Unknown No location listed in TTL report MM Black Mastic Under TEC-42 ACM Material not observed by GZA

TEC-52 Unknown No location listed in TTL report MM Yellow/Tan Mastic Under TEC-43 NAD NA

TEC-53 Unknown No location listed in TTL report MM Black Mastic Under TEC-44 NAD NA

TEC-54 Unknown No location listed in TTL report MM Sprayed-on Fireproofing Insulation ACM Material not observed by GZA

TEC-55 Unknown No location listed in TTL report TSI Pipe Joint Insulation (On Fiberglass

Line)

ACM

Included with pipe joint quantity listed for sample TEC-05

TEC-56 Unknown No location listed in TTL report TSI Incinerator Gasket ACM 700 square feet

TEC-57 Unknown No location listed in TTL report TSI Incinerator Fire Brick NAD NA

42911-1A-02 4th Rm 603A 7 MM Grey Window Caulk NAD NA

42911-1A-03 4th Rm 612F MM Grey Window Caulk NAD NA

42911-1A-20 3rd Rm 413A Lounge MM Grey Window Caulk NAD NA

42911-1A-28 3rd Rm 404F MM Grey Window Caulk NAD NA

42911-1A-49 2nd Rm 203A MM Grey Window Caulk NAD NA

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 2 of 4 5/13/2011

Detroit Job Corp Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

42911-1A-05 4th Hall H-1 SM Plaster NAD NA

42911-1A-06 4th Hall H-1 SM Plaster NAD NA

42911-1A-37 2nd Rm 201A SM Plaster NAD NA

42911-1A-54 2nd Hall H-9 SM Plaster NAD NA

42911-1A-57 2nd Rm 209A Lounge MM Grey Cove Base NAD NA

42911-1A-58 2nd Rm 209A Lounge MM Grey Cove Base NAD NA

42911-1A-59 2nd Rm 209A Lounge MM Grey Cove Base NAD NA

42911-1A-07 4th Hall H-1 MM 12" x 12" Yellow Floor Tile NAD NA

42911-1A-08 4th Hall H-2 MM 12" x 12" Yellow Floor Tile NAD NA

42911-1A-09 4th Hall H-3 MM 12" x 12" Yellow Floor Tile NAD NA

42911-1A-45 2nd Hall H-7 MM 12" x 12" Yellow Floor Tile NAD NA

42911-1A-50 2nd Hall H-7 MM 12" x 12" Yellow Floor Tile NAD NA

42911-1A-55 2nd Hall H-9 MM 12" x 12" Yellow Floor Tile NAD NA

42911-1A-10 4th Hall H-1 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

42911-1A-11 4th Hall H-2 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

42911-1A-12 4th Hall H-3 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

42911-1A-46 2nd Hall H-7 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

42911-1A-51 2nd Hall H-7 MM 12" x 12" Yellow Floor Tile Mastic NA

42911-1A-56 2nd Hall H-9 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

42911-1A-39 2nd Rm 202A MM 12" x 12" Black with White Flecks Floor

Tile <0.25% Chrysotile NA

42911-1A-40 2nd Rm 202A MM 12" x 12" Black with White Flecks Floor

Tile

NAD NA

42911-1A-41 2nd Rm 202A MM 12" x 12" Black with White Flecks Floor

Tile

NAD NA

42911-1A-42 2nd Rm 202A MM 12" x 12" Black with White Flecks Floor

Tile Mastic

NAD NA

42911-1A-43 2nd Rm 202A MM 12" x 12" Black with White Flecks

Floor Tile Mastic

NAD NA

42911-1A-44 2nd Rm 202A MM 12" x 12" Black with White Flecks Floor

Tile Mastic

NAD NA

42911-1A-22 3rd Hall H-4 MM 12" x 12" Tan Floor Tile NAD NA

42911-1A-24 3rd Hall H-4 MM 12" x 12" Tan Floor Tile NAD NA

42911-1A-26 3rd Hall H-4 MM 12" x 12" Tan Floor Tile NAD NA

42911-1A-33 3rd Hall H-5 MM 12" x 12" Tan Floor Tile <0.25% Chrysotile NA

42911-1A-35 3rd Hall H-6 MM 12" x 12" Tan Floor Tile NAD NA

42911-1A-23 3rd Hall H-4 MM 12" x 12" Tan Floor Tile Mastic NAD NA

Insufficient Material

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 3 of 4 5/13/2011

Detroit Job Corp Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

42911-1A-25 3rd Hall H-4 MM 12" x 12" Tan Floor Tile Mastic 0.3% Chrysotile

42911-1A-27 3rd Hall H-4 MM 12" x 12" Tan Floor Tile Mastic 1.7% Chrysotile

42911-1A-34 3rd Hall H-5 MM 12" x 12" Tan Floor Tile Mastic 15.9% Chrysotile

42911-1A-36 3rd Hall H-6 MM 12" x 12" Tan Floor Tile Mastic 4.9% Chrysotile

42911-1A-01 4th Rm 614 MM Brown Cove Base NAD NA

42911-1A-13 4th Rm 604 MM Brown Cove Base NAD NA

42911-1A-14 4th Rm 606 MM Brown Cove Base NAD NA

42911-1A-21 3rd Rm 401 Lounge MM Brown Cove Base NAD NA

42911-1A-29 3rd Rm 406 Lounge MM Brown Cove Base NAD NA

42911-1A-04 4th Rm 633A MM Black Cove Base NAD NA

42911-1A-15 4th Rm 611F MM Black Cove Base NAD NA

42911-1A-16 4th Rm 611F Lounge MM Black Cove Base NAD NA

42911-1A-38 2nd Rm 210A SM Drywall/Drywall Compound NAD NA

42911-1A-47 2nd Hall H-7 SM Drywall/Drywall Compound NAD NA

42911-1A-48 2nd Hall H-7 SM Drywall/Drywall Compound NAD NA

42911-1A-52 2nd Hall H-8 SM Drywall/Drywall Compound NAD NA

42911-1A-53 2nd Hall H-9 SM Drywall/Drywall Compound NAD NA

42911-1A-17 4th 4th Floor Mechanical Room TSI Fiber Glass Insulation Jacket NAD NA

42911-1A-18 4th 4th Floor Mechanical Room TSI Fiber Glass Insulation Jacket NAD NA

42911-1A-19 4th 4th Floor Mechanical Room TSI Fiber Glass Insulation Jacket NAD NA

Notes:

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

5. NAD = No asbestos detected

7. Rm = room

6. NA = Not applicable. Quantities were not calculated for non-ACM materials.

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

3. Analytical results for samples collected by GZA GeoEnvironmental, Inc. in 2011 provided by EMSL Laboratories in Ann Arbor, Michigan using PLM U.S. EPA Method 600 and PLM-NOB U.S. EPA Method 600/R-93/116.

4. ACM = Asbestos containing material as reported in 2005 TTL Report.

1935 square feet

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 4 of 4 5/13/2011

TABLE 1B

Building 1B - Asbestos Bulk Sample Results Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

TEC-01 Unknown No location listed in TTL report MM 12" x 12" White, Tan and Gray

Blotched Floor Tile ACM 4 Material not observed by GZA

TEC-02 Unknown No location listed in TTL report MM Bumpy Surfacing Material ACM Material not observed by GZA

TEC-03 Unknown No location listed in TTL report SM Wallboard NAD 5 NA 6

TEC-04 Unknown No location listed in TTL report SM Spray-on Fireproofing NAD NA

TEC-05 Unknown No location listed in TTL report MM 2' x 4' Dot and Squiggle Suspended

Ceiling Tile

NAD NA

TEC-06 Unknown No location listed in TTL report MM Carpet Mastic NAD NA

TEC-07 Unknown No location listed in TTL report MM 2' x 4' Random Dot Suspended Ceiling

Tile

NAD NA

TEC-08 Unknown No location listed in TTL report MM 2' x 4' False 2' x 2' Suspended Ceiling

Tile

NAD NA

TEC-09 Unknown No location listed in TTL report MM Roof Field Membrane NAD NA

TEC-10 Unknown No location listed in TTL report MM Base Flashing NAD NA

TEC-11 Unknown No location listed in TTL report MM Vent Through Roof Flashing ACM 50 square feet

TEC-12 Unknown No location listed in TTL report TSI Pipe Joint Insulation NAD NA

42811-1B-12 3rd Rm 443 7 MM Tan Cove Base NAD NA

42811-1B-14 2nd Rm 247 MM Tan Cove Base NAD NA

42811-1B-15 2nd Rm 259 MM Tan Cove Base NAD NA

42811-1B-33 1st Library MM Tan Cove Base NAD NA

42811-1B-11 3rd Rm 443 MM 12" x 12" Tan Floor Tile and Mastic NAD NA

42811-1B-34 1st Rm 054 MM 12" x 12" Tan Floor Tile and Mastic NAD NA

42811-1B-21 2nd Hall H-13 SM Plaster NAD NA

42811-1B-22 2nd Hall H-13 SM Plaster NAD NA

42811-1B-23 2nd Hall H-13 SM Plaster NAD NA

42811-1B-35 1st Rm 054 MM Maroon Cove Base NAD NA

42811-1B-36 1st Rm 058 MM Maroon Cove Base NAD NA

42811-1B-37 1st Rm 063 MM Maroon Cove Base NAD NA

42811-1B-20 2nd Rm D-7 SM Vinyl Wall Covering 15% Chrysotile

42811-1B-24 2nd Rm D-7 SM Vinyl Wall Covering 20% Chrysotile

42811-1B-25 2nd Rm D-7 SM Vinyl Wall Covering 15% Chrysotile

42811-1B-17 2nd Hall H-13 MM 12" x 12" Purple Floor Tile and Mastic NAD NA

42811-1B-18 2nd Hall H-13 MM 12" x 12" Beige with Gray Fleck Floor

Tile and Mastic

NAD NA

42811-1B-29 1st Stairwell S-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile

NAD NA

42811-1B-30 1st Stairwell S-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile Mastic

NAD NA

Analytical Results 3

12,000 square feet

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 2 5/13/2011

TABLE 1B

Building 1B - Asbestos Bulk Sample Results Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

42811-1B-31 1st Stairwell S-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile

NAD NA

42811-1B-32 1st Stairwell S-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile Mastic

NAD NA

42811-1B-26 1st Elevator Mechanical Room SM White Spray-on Fire Proofing 15% Chrysotile

42811-1B-27 1st Elevator Mechanical Room SM White Spray-on Fire Proofing 15% Chrysotile

42811-1B-28 1st Elevator Mechanical Room SM White Spray-on Fire Proofing 10% Chrysotile

42811-1B-01 4th Rm D-2 MM 9" x 9" Brown Floor Tile and Mastic NAD NA

42811-1B-07 3rd Rm D-5 MM 9" x 9" Brown Floor Tile and Mastic 0.4% Chrysotile NA

42811-1B-09 3rd Rm D-4 MM 9" x 9" Brown Floor Tile and Mastic 0.7% Chrysotile NA

42811-1B-02 4th Rm D-2 MM 1' x 1' Groove Lay-in Ceiling Tile NAD NA

42811-1B-08 3rd Rm D-5 MM 1' x 1' Groove Lay-in Ceiling Tile NAD NA

42811-1B-10 3rd Rm D-4 MM 1' x 1' Groove Lay-in Ceiling Tile NAD NA

42811-1B-19 2nd Rm D-8 MM 1' x 1' Groove Lay-in Ceiling Tile NAD NA

42811-1B-04 4th Rm H-5 MM Gray Cove Base NAD NA

42811-1B-05 4th Hall H-5 MM Gray Cove Base NAD NA

42811-1B-06 4th Hall H-5 MM Gray Cove Base NAD NA

42811-1B-03 4th Hall H-5 MM Black Cove Base NAD NA

42811-1B-13 3rd Hall H-8 MM Black Cove Base NAD NA

42811-1B-16 2nd Hall H-10 MM Black Cove Base NAD NA

Notes:

5. NAD = No asbestos detected

7. Rm = room

420 square feet

4. ACM = Asbestos containing material as reported in 2005 TTL Report.

6. NA = Not applicable. Quantities were not calculated for non-ACM materials.

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

3. Analytical results for samples collected by GZA GeoEnvironmental, Inc. in 2011 provided by EMSL Laboratories in Ann Arbor, Michigan using PLM U.S. EPA Method 600 and PLM-NOB U.S. EPA Method 600/R-93/116.

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 2 of 2 5/13/2011

TABLE 1C

Building 1C - Asbestos Bulk Sample Results Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

TEC-01 Unknown No location listed in TTL report MM 9" x 9" Light Gray Streaked Floor Tile NAD 4 NA 5

TEC-02 Unknown No location listed in TTL report MM 9" x 9" Slate Gray Marbled Floor Tile NAD NA

TEC-03 Unknown No location listed in TTL report MM 9" x 9" Beige Marbled Floor Tile NAD NA

TEC-04 Unknown No location listed in TTL report MM 9" x 9" Beige Streaked Floor Tile ACM 6 Material not observed by GZA

TEC-05 Unknown No location listed in TTL report MM 9" x 9" Tan Speckled Floor Tile NAD NA

TEC-06 Unknown No location listed in TTL report MM 9" x 9" Black, White Streaked Floor

Tile

NAD NA

TEC-07 Unknown No location listed in TTL report MM 1' x 1' Dot and Groove Glued-on

Ceiling Tile

NAD NA

TEC-08 Unknown No location listed in TTL report MM Clue Pod from TEC-08 NAD NA

TEC-09 Unknown No location listed in TTL report SM Wall Plaster NAD NA

TEC-10 Unknown No location listed in TTL report SM Wall Board NAD NA

TEC-11 Unknown No location listed in TTL report MM Carpet Mastic NAD NA

TEC-12 Unknown No location listed in TTL report MM 9" x 9" White Floor Tile ACM Material not observed by GZA

TEC-13 Unknown No location listed in TTL report MM Black Mastic Under TEC-12 ACM Material not observed by GZA

TEC-14 Unknown No location listed in TTL report MM 2' x 4' Dot and Groove Ceiling Tile NAD NA

TEC-15 Unknown No location listed in TTL report MM Roof Field Membrane NAD NA

TEC-16 Unknown No location listed in TTL report MM Vent Through Roof Flashing ACM 50 square feet

TEC-17 Unknown No location listed in TTL report MM Fan Base Flashing NAD NA

TEC-18 Unknown No location listed in TTL report MM Edge Flashing NAD NA

TEC-19 Unknown No location listed in TTL report MM Wall Base Flashing NAD NA

TEC-20 Unknown No location listed in TTL report TSI Pipe Joint Insulation on Fiberglass NAD NA

TEC-21 Unknown No location listed in TTL report SM Spray-on Fireproofing ACM Material not observed by GZA

42811-1C-01 2nd Rm 2 7 MM 12" x 12" White w/ Gray Fleck Floor

Tile

NAD NA

42811-1C-02 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile

NAD NA

42811-1C-03 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile

NAD NA

42811-1C-04 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile

NAD NA

42811-1C-05 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile

NAD NA

42811-1C-06 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile Mastic 0.3% Chrysotile NA

42811-1C-07 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile Mastic

NAD NA

42811-1C-08 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile Mastic

NAD NA

42811-1C-09 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile Mastic 0.7% Chrysotile NA

42811-1C-10 2nd Rm 2 MM 12" x 12" White w/ Gray Fleck Floor

Tile Mastic 0.3% Chrysotile NA

42811-1C-11 2nd Barber Shop MM White and Black Speckled Floor Tile NAD NA

42811-1C-12 2nd Barber Shop MM White and Black Speckled Floor Tile NAD NA

42811-1C-13 2nd Barber Shop MM White and Black Speckled Floor Tile 0.4% Chrysotile NA

42811-1C-14 2nd Barber Shop MM White and Black Speckled Floor Tile

Mastic <0.25% Chrysotile NA

Analytical Results 3

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 2 5/13/2011

TABLE 1C

Building 1C - Asbestos Bulk Sample Results Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

42811-1C-15 2nd Barber Shop MM White and Black Speckled Floor Tile

Mastic

NAD NA

42811-1C-16 2nd Barber Shop MM White and Black Speckled Floor Tile

Mastic

NAD NA

42911-1C-17 1st Hall H-1 SM Plaster NAD NA

42911-1C-18 1st Hall H-1 SM Plaster NAD NA

42911-1C-19 1st Hall H-1 SM Plaster NAD NA

42911-1C-20 1st Rm 090 MM Tan Cove Base NAD NA

42911-1C-21 1st Rm 081 MM Tan Cove Base NAD NA

42911-1C-22 1st Rm 101 MM Tan Cove Base NAD NA

42911-1C-23 1st Rm 098 MM Tan Cove Base NAD NA

42911-1C-24 1st Rm 097 MM Tan Cove Base NAD NA

42911-1C-25 1st Rm 087 MM 12" x 12" Tan Floor Tile NAD NA

42911-1C-26 1st Rm 087 MM 12" x 12" Tan Floor Tile NAD NA

42911-1C-27 1st Rm 087 MM 12" x 12" Tan Floor Tile NAD NA

42911-1C-28 1st Rm 087 MM 12" x 12" Tan Floor Tile Mastic 0.4% Chrysotile

42911-1C-29 1st Rm 087 MM 12" x 12" Tan Floor Tile Mastic 0.6% Chrysotile

42911-1C-30 1st Rm 087 MM 12" x 12" Tan Floor Tile Mastic 1.0% Chrysotile

42911-1C-31 1st Hall H-2 MM 12" x 12" Purple Floor Tile NAD NA

42911-1C-32 1st Hall H-2 MM 12" x 12" Purple Floor Tile Mastic 1.7% Chrysotile 970 square feet

42911-1C-33 1st Hall H-3 MM 12" x 12" Purple Floor Tile NAD NA

42911-1C-34 1st Hall H-3 MM 12" x 12" Purple Floor Tile Mastic 2.3% Chrysotile 970 square feet

42911-1C-35 1st Hall H-4 MM 12" x 12" Purple Floor Tile NAD NA

42911-1C-36 1st Hall H-4 MM 12" x 12" Purple Floor Tile Mastic NAD NA

42911-1C-37 1st Hall H-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile

NAD NA

42911-1C-38 1st Hall H-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile

NAD NA

42911-1C-39 1st Hall H-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile

NAD NA

42911-1C-40 1st Hall H-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile Mastic 0.3% Chrysotile NA

42911-1C-41 1st Hall H-1 MM 12" x 12" Beige with Gray Fleck Floor

Tile Mastic 0.5% Chrysotile NA

Notes:

4. NAD = No asbestos detected

7. Rm = room

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

3. Analytical results for samples collected by GZA GeoEnvironmental, Inc. in 2011 provided by EMSL Laboratories in Ann Arbor, Michigan using PLM U.S. EPA Method 600 and PLM-NOB U.S. EPA Method 600/R-93/116.

6. ACM = Asbestos containing material as reported in 2005 TTL Report.

5. NA = Not applicable. Quantities were not calculated for non-ACM materials.

30 square feet

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 2 of 2 5/13/2011

TABLE 1D

Building 1D - Asbestos Bulk Sample Results Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

TEC-01 Unknown No location listed in TTL report MM 9" x9" Black, Micro White

Speckled Floor Tile NAD 4 NA 5

TEC-02 Unknown No location listed in TTL report MM 12" x 12" Beige, Brown and White

Streaked Floor Tile

NAD NA

TEC-03 Unknown No location listed in TTL report Sm Wallboard NAD NA

TEC-04 Unknown No location listed in TTL report MM 2' x 2' Small Dot and Groove

Suspended Ceiling Tile

NAD NA

TEC-05 Unknown No location listed in TTL report MM Carpet Mastic NAD NA

TEC-06 Unknown No location listed in TTL report MM 1' x 1' Large Groove Suspended

Ceiling Tile

NAD NA

TEC-07 Unknown No location listed in TTL report SM Ceiling/Wall Plaster NAD NA

TEC-08 Unknown No location listed in TTL report TSI Straight Pipe Insulation (FG Line) NAD NA

TEC-09 Unknown No location listed in TTL report MM 2' x 4' Dot and Groove Suspended

Ceiling Tile

NAD NA

TEC-10 Unknown No location listed in TTL report MM 2' x 4' Pinhole and Groove

Suspended Ceiling Tile

NAD NA

TEC-11 Unknown No location listed in TTL report MM 2' x 2' Multidot Suspended Ceiling

Tile

NAD NA

TEC-12 Unknown No location listed in TTL report MM 1' x 1' Small Groove Suspended

Ceiling Tile

NAD NA

TEC-13 Unknown No location listed in TTL report TSI Straight Pipe Insulation (Paper) ACM 6 Material not observed by GZA

TEC-14 Unknown No location listed in TTL report TSI Pipe Joint Insulation ACM 225 each

TEC-15 Unknown No location listed in TTL report SM Spray-on Fireproofing ACM Material resampled, tested negative

TEC-16 Unknown No location listed in TTL report MM 12" x12" Light Brown Floor Tile NAD NA

TEC-17 Unknown No location listed in TTL report MM Mastic Below 12' x 12' Light

Brown Floor Tile

NAD NA

TEC-18 Unknown No location listed in TTL report MM 2' X 4' False 2' x 2' Suspended

Ceiling Tile

NAD NA

TEC-19 Unknown No location listed in TTL report MM Roof Field Membrane NAD NA

TEC-20 Unknown No location listed in TTL report MM Vent Through Roof Flashing ACM 100 square feet

TEC-21 Unknown No location listed in TTL report MM Base Flashing ACM 880 square feet

TEC-22 Unknown No location listed in TTL report MM Edge Flashing ACM 880 square feet

TEC-23 Unknown No location listed in TTL report MM Pitch Pan Flashing ACM 1,000 square feet

TEC-24 Unknown No location listed in TTL report SM Spray-on Fireproofing NAD NA

TEC-25 Unknown No location listed in TTL report MM Fire Door Insulation (FG) NAD NA

TEC-26 Unknown No location listed in TTL report MM Fire Door Insulation (Paper) NAD NA

TEC-27 Unknown No location listed in TTL report MM Fire Door Insulation (Mag) ACM 20 ea

TEC-28 Unknown No location listed in TTL report MM 9" x 9" Mint Green with Gray and

Cream Streaks Floor Tile ACM Material not observed by GZA

Analytical Results 3

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 5 5/13/2011

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

TEC-29 Unknown No location listed in TTL report MM Mastic Below 9" x 9" Mint Green with Gray and Cream Streaks Floor NAD NA

TEC-30 Unknown No location listed in TTL report MM 9" x 9" Dark Green with White and

Black Streaks Floor Tile

NAD NA

TEC-31 Unknown No location listed in TTL report MM Mastic Under 9" x 9" Dark Green with White and Black Streaks Floor NAD NA

TEC-32 Unknown No location listed in TTL report MM 12" x 12" White with Brown

Streaks Floor Tile

NAD NA

TEC-33 Unknown No location listed in TTL report MM Mastic Under 12" x 12" White with

Brown Streaks Floor Tile

NAD NA

TEC-34 Unknown No location listed in TTL report MM 9" x 9" Beige with Cream and Gray

Streaks Floor Tile

NAD NA

TEC-35 Unknown No location listed in TTL report MM 9" x 9" Beige with Cream and Gray

Streaks Floor Tile Mastic

NAD NA

TEC-36 Unknown No location listed in TTL report MM 9" x 9" Gray with Black Streaks

Floor Tile

NAD NA

TEC-37 Unknown No location listed in TTL report MM Mastic Under 9" x 9" Gray with

Black Streaks Floor Tile

NAD NA

TEC-38 Unknown No location listed in TTL report Found beneath existing floor tile

MM

12" x 12" Black with Cream

Streaks Floor Tile ACM 5,010 square feet

TEC-39 Unknown No location listed in TTL report MM Mastic Under 12" x 12" Black with

Cream Streaks Floor Tile

NAD NA

TEC-40 Unknown No location listed in TTL report MM 9" x 9" Black with Tan Floor

Specks Floor Tile

NAD NA

TEC-41 Unknown No location listed in TTL report MM Mastic Under 9" x 9" Black with

Tan Floor Specks Floor Tile

NAD NA

TEC-42 Unknown No location listed in TTL report MM Gray and Cream Pebble Pattern

Linoleum ACM Material not observed by GZA

TEC-43 Unknown No location listed in TTL report MM Gray and Cream Pebble Pattern

Linoleum Mastic ACM Material not observed by GZA

TEC-44 Unknown No location listed in TTL report MM 9" x 9" Dark Gray with Cream

Specks Floor Tile

NAD NA

TEC-45 Unknown No location listed in TTL report MM Mastic Under 9" x 9" Dark Gray with Cream Specks Floor Tile

NAD NA

TEC-46 Unknown No location listed in TTL report MM 9" x 9" White with Brown Specks

Floor Tile

NAD NA

TEC-47 Unknown No location listed in TTL report MM Mastic Under 9" x 9" White with

Brown Specks Floor Tile

NAD NA

TEC-48 Unknown No location listed in TTL report MM Green Pebble Pattern Linoleum ACM Material not observed by GZA

TEC-49 Unknown No location listed in TTL report MM Green Pebble Pattern Linoleum

Mastic ACM Material not observed by GZA

TEC-50 Unknown No location listed in TTL report MM Gray Mastic Under TEC-01 NAD NA

TEC-51 Unknown No location listed in TTL report MM 9" x 9" Gray with Yellow Specks

Floor Tile

NAD NA

TEC-52 Unknown No location listed in TTL report MM Brown Mastic Under 9" x 9" Gray with Yellow Specks Floor Tile

NAD NA

TEC-53 Unknown No location listed in TTL report MM Brown Mastic Under TEC-02 NAD NA

TEC-54 Unknown No location listed in TTL report MM 9" x 9" Red with Black and White

Streaks Floor Tile ACM Material not observed by GZA

TEC-55 Unknown No location listed in TTL report MM Black Mastic Under 9" x 9" Red with Black and White Streaks Floor NAD NA

TEC-56 Unknown No location listed in TTL report MM 12" x 12" Black with White Streaks

Floor Tile

NAD NA

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 2 of 5 5/13/2011

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

TEC-57 Unknown No location listed in TTL report 12" x 12" Black with White Streaks

Floor Tile Mastic

NAD NA

TEC-58 Unknown No location listed in TTL report MM 12" x 12" White with Black Flecks

Floor Tile

NAD NA

TEC-59 Unknown No location listed in TTL report MM Black Mastic Under 12" x 12"

White with Black Flecks Floor Tile

NAD NA

TEC-60 Unknown No location listed in TTL report MM 9" x 9" Cream with Brown Specks

Floor Tile ACM Material not observed by GZA

TEC-61 Unknown No location listed in TTL report MM Brown Mastic Under 9" x 9" Cream with Brown Specks Floor Tile

NAD NA

TEC-62 Unknown No location listed in TTL report SM Wall Covering Material ACM 15,840 square feet

TEC-63 Unknown No location listed in TTL report SM Bumpy Surfacing Material ACM 5,250 square feet

TEC-64 Unknown No location listed in TTL report SM Wall Covering (Linoleum Type) ACM Material included in the quantity listed for sample TEC-62

TEC-65 Unknown No location listed in TTL report MM 9" x 9" White Floor Tile NAD NA

TEC-66 Unknown No location listed in TTL report MM Mastic Under 9" x 9" White Floor

Tile

NAD NA

TEC-67 Unknown No location listed in TTL report MM 9" x 9" Gray Floor Tile ACM Material not observed by GZA

TEC-68 Unknown No location listed in TTL report MM Mastic Under 9" x 9" Gray Floor

Tile

NAD NA

TEC-69 Unknown No location listed in TTL report SM Ceiling Plaster ( Rough) NAD NA

TEC-70 Unknown No location listed in TTL report TSI Duct Insulation NAD NA

42711-1D-01 2nd Rm Career Prep 7 MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-02 2nd Rm Career Prep MM 12" x 12" White with Grey Flecks

Floor Tile Mastic

NAD NA

42711-1D-03 2nd Rm 361 MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-04 2nd Rm 361 MM 12" x 12" White with Grey Flecks

Floor Tile Mastic 0.3% Chrysotile NA

42711-1D-05 2nd Rm 356 MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-06 2nd Rm 356 MM 12" x 12" White with Grey Flecks

Floor Tile Mastic

NA

42711-1D-07 2nd Rm CCP Counseling MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-08 2nd Rm CCP Counseling MM 12" x 12" White with Grey Flecks

Floor Tile Mastic

NA

42711-1D-09 2nd Rm CCP 1 MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-10 2nd Rm CCP 1 MM 12" x 12" White with Grey Flecks

Floor Tile Mastic 0.3% Chrysotile NA

42711-1D-11 2nd Rm Drivers Education MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-12 2nd Rm Drivers Education MM 12" x 12" White with Grey Flecks

Floor Tile Mastic <0.25% Chrysotile NA

42711-1D-13 2nd Rm CCP Counselor MM 12" x 12" White with Grey Flecks

Floor Tile

NAD NA

42711-1D-14 2nd Rm CCP Counselor MM 12" x 12" White with Grey Flecks

Floor Tile Mastic

NA

42711-1D-15 2nd Rm 361 SM Grey Spray-on Fire Proofing NAD NA

Insufficient Material

Insufficient Material

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 3 of 5 5/13/2011

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

42711-1D-16 2nd Rm 356 SM Grey Spray-on Fire Proofing NAD NA

42711-1D-17 2nd Rm 356A SM Grey Spray-on Fire Proofing NAD NA

42711-1D-18 2nd Rm 356 SM Plaster <1% Chrysotile NA

42711-1D-19 2nd Hall H-5 SM Plaster <1% Chrysotile NA

42711-1D-20 2nd Rm 365A SM Plaster NAD NA

42711-1D-21 2nd Rm CCP 1 MM Tan Cove Base NAD NA

42711-1D-22 2nd Rm Drivers Education MM Tan Cove Base NAD NA

42711-1D-23 2nd Rm CCP Counselor MM Tan Cove Base NAD NA

42711-1D-24 2nd Hall H-1 MM Maroon Cove Base NAD NA

42711-1D-25 2nd Hall H-2 MM Maroon Cove Base NAD NA

42711-1D-26 2nd Hall H-5 MM Maroon Cove Base NAD NA

42711-1D-27 2nd Hall H-3 MM Maroon Cove Base NAD NA

42711-1D-28 2nd Hall H-4 MM Maroon Cove Base NAD NA

42711-1D-30 2nd Hall H-1 MM 12" x 12" Purple Floor Tile NAD NA

42711-1D-31 2nd Hall H-1 MM 12" x 12" Purple Floor Tile Mastic NAD NA

42711-1D-32 2nd Hall H-2 MM 12" x 12" Purple Floor Tile NAD NA

42711-1D-33 2nd Hall H-2 MM 12" x 12" Purple Floor Tile Mastic NAD NA

42711-1D-34 2nd Hall-H-5 MM 12" x 12" Purple Floor Tile NAD NA

42711-1D-35 2nd Hall H-5 MM 12" x 12" Purple Floor Tile Mastic NAD NA

42711-1D-36 2nd Hall H-3 MM 12" x 12" Purple Floor Tile NAD NA

42711-1D-37 2nd Hall H-3 MM 12" x 12" Purple Floor Tile Mastic 0.3% Chrysotile NA

42711-1D-38 2nd Hall H-4 MM 12" x 12" Purple Floor Tile NAD NA

42711-1D-39 2nd Hall H-4 MM 12" x 12" Purple Floor Tile Mastic 0.7% Chrysotile NA

42711-1D-40 2nd 2nd Floor Mechanical Room MM Vibration Dampener NAD NA

42711-1D-41 2nd 2nd Floor Mechanical Room MM Vibration Dampener NAD NA

42711-1D-42 2nd 2nd Floor Mechanical Room MM Vibration Dampener NAD NA

42711-1D-43 2nd 2nd Floor Mechanical Room TSI Insulation Jacket NAD NA

42711-1D-44 2nd 2nd Floor Mechanical Room TSI Insulation Jacket NAD NA

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 4 of 5 5/13/2011

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

Analytical Results 3

42711-1D-45 2nd 2nd Floor Mechanical Room TSI Insulation Jacket NAD NA

42711-1D-46 1st Rm 129 MM 12" x 12" Blue/Green Floor Tile NAD NA

42711-1D-47 1st Rm 129 MM 12" x 12" Blue/Green Floor Tile NAD NA

42711-1D-48 1st Rm 129 MM 12" x 12" Blue/Green Floor Tile NAD NA

42711-1D-49 1st Rm 123 MM 12" x 12" Blue/Green Floor Tile NAD NA

42711-1D-50 1st Rm 123 MM 12" x 12" Blue/Green Floor Tile NAD NA

42711-1D-51 1st Rm 129 MM 12" x 12" Blue/Green Floor Tile

Mastic

NAD NA

42711-1D-52 1st Rm 129 MM 12" x 12" Blue/Green Floor Tile

Mastic

NAD NA

42711-1D-53 1st Rm 129 MM 12" x 12" Blue/Green Floor Tile

Mastic

NAD NA

42711-1D-54 1st Rm 123 MM 12" x 12" Blue/Green Floor Tile

Mastic

NAD NA

42711-1D-55 1st Rm 123 MM 12" x 12" Blue/Green Floor Tile

Mastic

NA

42711-1D-56 1st Rm 301 MM 12" x 12" Yellow Floor Tile NAD NA

42711-1D-57 1st Rm 301 MM 12" x 12" Yellow Floor Tile NAD NA

42711-1D-58 1st Rm 301 MM 12" x 12" Yellow Floor Tile NAD NA

42711-1D-59 1st Rm 301 MM 12" x 12" Yellow Floor Tile NAD NA

42711-1D-60 1st Rm 301 MM 12" x 12" Yellow Floor Tile NAD NA

42711-1D-61 1st Rm 301 MM 12" x 12" Yellow Floor Tile Mastic NA

42711-1D-62 1st Rm 301 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

42711-1D-63 1st Rm 301 MM 12" x 12" Yellow Floor Tile Mastic NA

42711-1D-64 1st Rm 301 MM 12" x 12" Yellow Floor Tile Mastic 0.5% Chrysotile NA

42711-1D-65 1st Rm 301 MM 12" x 12" Yellow Floor Tile Mastic NAD NA

Notes:

4. NAD = No asbestos detected

7. Rm = room

6. ACM = Asbestos containing material as reported in 2005 TTL Report.

5. NA = Not applicable. Quantities were not calculated for non-ACM materials.

3. Analytical results for samples collected by GZA GeoEnvironmental, Inc. in 2011 provided by EMSL Laboratories in Ann Arbor, Michigan using PLM U.S. EPA Method 600 and PLM-NOB U.S. EPA Method 600/R-93/116.

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

Insufficient Material

Insufficient Material

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 5 of 5 5/13/2011

TABLE 1E

Building 1E Upper - Asbestos Bulk Sample Results

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

TEC-01 Unknown No location listed in TTL report MM 12" x 12" White Floor Tile NAD 4 NA 5

TEC-02 Unknown No location listed in TTL report MM 12" x 12" White Floor Tile Mastic NAD NA

TEC-03 Unknown No location listed in TTL report MM 2' x 4' Dot and Groove Suspended

Ceiling Tile

NAD NA

TEC-04 Unknown No location listed in TTL report SM Wall Board NAD NA

TEC-05 Unknown No location listed in TTL report MM 2' x 4' Random Dot Suspended

Ceiling Tile

NAD NA

TEC-06 Unknown No location listed in TTL report MM Roof Field Membrane NAD NA

TEC-07 Unknown No location listed in TTL report MM Vent Through Roof Flashing ACM 6 100 square feet

TEC-08 Unknown No location listed in TTL report MM Fan Base Flashing ACM 50 square feet

TEC-09 Unknown No location listed in TTL report MM Asphalt Shingles NAD NA

TEC-10 Unknown No location listed in TTL report MM Edge Flashing ACM 300 square feet

TEC-11 Unknown No location listed in TTL report MM 12" x 12" Floor Tile - Unknown Color NAD NA

TEC-12 Unknown No location listed in TTL report MM 12" x 12" Floor Tile Mastic NAD NA

TEC-13 Unknown No location listed in TTL report MM 9" x 9" Green Floor Tile with Black

Streaks

NAD NA

TEC-14 Unknown No location listed in TTL report MM 9" x 9" Green Floor Tile with Black

Streaks Mastic

NAD NA

Notes:

4. NAD = No asbestos detected

Analytical Results 3

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

5. NA = Not applicable. Quantities were not calculated for non-ACM materials.

6. ACM = Asbestos containing material as reported in 2005 TTL Report.

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

3. Analytical results for samples collected by GZA GeoEnvironmental, Inc. in 2011 provided by EMSL Laboratories in Ann Arbor, Michigan using PLM U.S. EPA Method 600 and PLM-NOB U.S. EPA Method 600/R-93/116.

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 1 5/13/2011

TABLE 1F

Building 1E Lower - Asbestos Bulk Sample Results

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Floor Location Material

Category 2 Materials / Items Estimated Quantity of ACM

Material

TEC-01 Unknown No location listed in TTL report TSI Sticky Brown Fibrous Straight Pipe

Insulation ACM 4

TEC-02 Unknown No location listed in TTL report TSI Brown Condensate Straight Pipe

Insulation

ACM

TEC-03 Unknown No location listed in TTL report TSI Yellow Straight Pipe Insulation ACM Material not observed by GZA

TEC-04 Unknown No location listed in TTL report TSI Condensate Tank Insulation ACM Material not observed by GZA

TEC-05 Unknown No location listed in TTL report TSI Pipe Joint Insulation ACM 85 each

TEC-06 Unknown No location listed in TTL report TSI Chiller Line Pipe Joint Insulation ACM Material not observed by GZA

TEC-07 Unknown No location listed in TTL report TSI Boiler Exhaust Flue Insulation ACM 500 square feet

TEC-08 Unknown No location listed in TTL report MM Roof Field Membrane NAD 5 NA 6

TEC-09 Unknown No location listed in TTL report MM Pitch Pan Flashing ACM

TEC-10 Unknown No location listed in TTL report MM Base Flashing ACM

TEC-11 Unknown No location listed in TTL report MM Vent Through Roof Flashing ACM

TEC-12 Unknown No location listed in TTL report MM Edge Flashing ACM

TEC-13 Unknown No location listed in TTL report TSI Boiler Insulation (White Powder) ACM

TEC-14 Unknown No location listed in TTL report TSI Boiler Insulation (Brown Fibrous) ACM

TEC-15 Unknown No location listed in TTL report TSI Boiler Insulation (Brown Metallic) ACM

TEC-16 Unknown No location listed in TTL report TSI Fire Brick (White) NAD NA

TEC-17 Unknown No location listed in TTL report TSI Fire Brick (Orange) NAD NA

No Sample Collected- Assumed

1 Electrical Room TSI Asbestos-Cement Panel ACM 500 square feet

Notes:

5. NAD = No asbestos detected

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

3. Analytical results for samples collected by GZA GeoEnvironmental, Inc. in 2011 provided by EMSL Laboratories in Ann Arbor, Michigan using PLM U.S. EPA Method 600 and PLM-NOB U.S. EPA Method 600/R-93/116.

4. ACM = Asbestos containing material as reported in 2005 TTL Report.

6. NA = Not applicable. Quantities were not calculated for non-ACM materials.

Analytical Results 3

6,410 square feet

Quantity included on Table 1E Upper

220 linear feet

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 1 5/13/2011

TABLE 1G

Penthouse (Building 1A) - Asbestos Bulk Sample Results

Detroit Job Corps Center, Detroit, Michigan

Sample Number 1 Location Material

Category 2 Materials / Items

Estimated Quantity of ACM Material

TEC-01 No location listed in TTL report MM Roofing Material NAD 3 NA 4

TEC-02 No location listed in TTL report SM Spray-on Fireproofing NAD NA

Notes:

3. NAD = No asbestos detected

Analytical Results

1. Sample names that begin with "TEC" were collected by Testing Engineers and Consultants, Inc. and reported in the “Re-Inspection of Asbestos-Containing Materials”, TTL Associates, Inc., July 2005 (TTL Report). Sample locations were not listed in this report.

2. Materials include the following: TSI = Thermal System Insulation, MM = Miscellaneous Materials, SM = Surfacing Materials

4. NA = Not applicable. Quantities were not calculated for non-ACM materials.

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 1.xlsx 1 of 1 5/13/2011

TABLE 2

Lead Paint Bulk Sampling Results

Detroit Job Corps Center, Detroit, Michigan

Sample # Building # Floor # Room # Medium Lead Concentrations

% wt.

LBP-01 1D 2nd Hall H-4 Maroon paint on door frame <0.010

LBP-02 1D 2nd Hall H-5 Cream paint on radiator 0.029

LBP-03 1D 2 Hall H-2 Red paint on fire extinguisher box 0.050

LBP-04 1D 2 Rm CCP-3 Peach paint on drywall <0.010

LBP-05 1D 2 Rm CCP-3 Orange paint on drywall <0.010

LBP-06 1D 2 Rm CCP-3 Tan paint on drywall <0.010

LBP-07 1D 2 Rm 365 Salmon paint on drywall <0.010

LBP-08 1D 2 Rm 301 White paint on door frame <0.010

LBP-09 1D 2 2nd Floor Mechanical Room Light blue paint on drywall <0.010

LBP-10 1D 1 Rm 147 Dark blue paint on drywall <0.010

LBP-11 1B 1 Stairwell S-2 Gray paint on drywall <0.010

LBP-12 1A 4 RA Room Green paint on door frame <0.010

LBP-13 1A 4 RA Room White paint on drywall <0.010

LBP-14 1A 3 Rm 421 Brown paint on door 0.130

LBP-15 1A 3 Rm 421 Dark brown paint on door frame 0.220

LBP-16 1A 2 Stairwell S-1 Yellow paint on door frame 0.016

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 2.xls 1 of 1 5/13/2011

TABLE 3

Hazardous Materials Summary Detroit Job Corps Center, Detroit, Michigan

Location Fluorescent Tubes

(Mercury Containing) Ballasts Leaking Ballasts

Mercury Containing Devices

Refrigerants Mold Transformers

Building 1A 926 354 None observed None observed Drinking Fountains - 4 None observed None observed

Building 1B 920 340 None observed None observed None None observed None observed

Building 1C 347 138 None observed None observed Drinking Fountains - 2 None observed None observed

Building 1D 2050 863 None observed None observed Drinking Fountians - 6 None observed 2nd Floor Mechanical Room - 3 Wet Type

Building 1E 439 59 None observed None observed Window AC Units - 2 None observed Room 284 - 1 Dry Type

Notes:

AC = Air Conditioning

J:\61000\61718 - Detroit Job Corps Center\Environmental Survey\Survey Report\Environmental Report Table 3.xls 1 of 1 5/13/2011

N

S

EW

MICHIGAN

SOURCE:

QUADRANGLE LOCATION

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

LOCUS MAP

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

MAY 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM 1" = 2000'

HIGHLAND PARK, MICHIGAN

SITE

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

EXISTING SITE PLAN

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

MAY 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM AS SHOWN

N

S

EW

0 20 120 240

APPROXIMATE SCALE IN FEET

NOTE:

SITE LAYOUT TAKEN FROM A DRAWING

ENTITLED "EXISTING SITE PLAN".

ORIGINAL SCALE: 1" = 120'.

FIRST FLOOR

MECH

MECHLOUNGE

STORAGE

STORAGE

RA

STORAGE

LIVING

LOUNGE

LOUNGE

LIVING

LOUNGE INCINERATOR

ROOM

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

DORMITORY, BUILDING 1A, FIRST FLOOR

SAMPLE LOCATION PLAN

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

MAY 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM AS SHOWN

N

S

EW

0 20 40 80

SCALE IN FEET

NOTES:

1. LAYOUT TAKEN FROM DRAWING FILE A1035

ORIGINAL.DWG, TAB "A1ST", ENTITLED DETROIT

JOB CORPS CENTER, FIRST FLOOR, DORMITORY

BUILDING 1A. ORIGINAL SCALE: 1" = 40'.

2. NO SAMPLES WERE COLLECTED FROM THE

FIRST FLOOR OF BUILDING 1A.

SECOND FLOOR

5F

5A

4F

4A

6A

6F

7A

7F

S2

H-8

S1

203F 203A 202F 202A 201A

212A 212F 213A 213F 214A

9A

9F

8A

8F

0F

0A

1F

1A

S3

H-7

H-9

LIVING

LIVING

LIVING

RA

INDEPENDENT

LIVING

SPECIALIST

LIVING

STORAGE

LAUNDRY

LIVING

OFFICE

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

DORMITORY, BUILDING 1A, SECOND FLOOR

SAMPLE LOCATION PLAN

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

JUNE 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM AS SHOWN

N

S

EW

0 20 40 80

SCALE IN FEET

NOTE:

LAYOUT TAKEN FROM DRAWING FILE A1035

ORIGINAL.DWG, TAB "A2ND", ENTITLED DETROIT JOB

CORPS CENTER, SECOND FLOOR, DORMITORY

BUILDING 1A. ORIGINAL SCALE: 1" = 40'.

LEGEND

ASBESTOS SAMPLE LOCATION

LOCATION WHERE CARPET WAS PULLED DURING

DESTRUCTIVE TESTING

THIRD FLOOR

5F

5A

4F

4A

6A

6F

7A

7F

S2

H-5

S1

403F 403A 402F 402A 401

412A 412F 413A 413F 414

9A

9F

8A

8F

0F

0A

1F

1A

S3

H-4

H-6

RA

OFFIC

E

LAUNDRY

STORAGE

JAN.

RA

STORAGE

LAUNDRY

STORAGE

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

DORMITORY, BUILDING 1A, THIRD FLOOR

SAMPLE LOCATION PLAN

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

JUNE 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM AS SHOWN

N

S

EW

0 20 40 80

SCALE IN FEET

NOTE:

LAYOUT TAKEN FROM DRAWING FILE A1035

ORIGINAL.DWG, TAB "A3RD", ENTITLED DETROIT JOB

CORPS CENTER, THIRD FLOOR, DORMITORY

BUILDING 1A. ORIGINAL SCALE: 1" = 40'.

LEGEND

ASBESTOS SAMPLE LOCATION

LEAD-BASED PAINT (LBP) SAMPLE LOCATION

3RD FLOOR

BATHROOM

LOCATION WHERE CARPET WAS PULLED DURING

DESTRUCTIVE TESTING

LOCATION WHERE WALL WAS OPENED

DURING DESTRUCTIVE TESTING

FOURTH FLOOR

5F

5A

4F

4A

6A

6F

7A

7F

S2

H-2

S1

603F 603A 602F 602A 601

612A 612F 613A 613F 614

9A

9F

8A

8F

0F

0A

1F

1A

S4

H-1

H-3

S3

B1

RA JAN.

MECH

MECH

STORAGE

LAUNDRY

STORAGE

LAUNDRY

LOUNGE

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

DORMITORY, BUILDING 1A, FOURTH FLOOR

SAMPLE LOCATION PLAN

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

JUNE 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM AS SHOWN

N

S

EW

0 20 40 80

SCALE IN FEET

NOTE:

LAYOUT TAKEN FROM DRAWING FILE A1035

ORIGINAL.DWG, TAB "A4TH", ENTITLED DETROIT JOB

CORPS CENTER, FOURTH FLOOR, DORMITORY

BUILDING 1A. ORIGINAL SCALE: 1" = 40'.

LEGEND

ASBESTOS SAMPLE LOCATION

LEAD-BASED PAINT (LBP) SAMPLE LOCATION

LOCATION WHERE CARPET WAS PULLED DURING

DESTRUCTIVE TESTING

S2 B-1 B-2 B-3

ELEVATOR

MECH

H-9

H-9

H-9

063B

063A 063 063

059 059A

ADMISSION

ADMISSION

STORAGE

S1

FIRST FLOOR

TRAINING/CONFERENCE

LIBRARY OFFICE

FINANCE

DIRECTOR OF

ADMINISTRATION

PURCHASING

HUMAN RESOURCE

DIRECTOR

HUMAN RESOURCE

DEPARTMENT

MAILROOM

STORAGE

SERVER ROOM

KITCHENETTE

WAITING

SHEET NO.

GZA GeoEnvironmental, Inc.

Engineers and Scientists

PREPARED BY: PREPARED FOR:

www.gza.com

PROJECT NO.DATE: REVISION NO.

DESIGNED BY:

PROJ MGR:

DRAWN BY:

REVIEWED BY: CHECKED BY:

SCALE:

DETROIT JOB CORPS CENTER

11801 WOODROW WILSON STREET

DETROIT, MICHIGAN 48206

ASBESTOS AND BUILDING HAZARD ASSESSMENT

ADMINISTRATION/DORMITORY, BUILDING 1B,

FIRST FLOOR - SAMPLE LOCATION PLAN

M.C. Smith Associates and Architectural Group, Inc.

East Grand Rapids, MI 49506

MAY 2011 16.0061718.00

FIGURE

LMN

MAR

JMC

NAM AS SHOWN

N

S

EW

0 10 20 40

SCALE IN FEET

NOTE:

LAYOUT TAKEN FROM DRAWING FILE A1035

ORIGINAL.DWG, TAB "B1ST", ENTITLED DETROIT JOB

COR…