D.6 ATTACHMENT 6 - 2024 SFVA STANDPIPE 5-YEAR BUILDING INSPECTIONS.pdf

PDF 2 MB Posted

Attached to
J063--Fire Suppression System Inspection, Testing Maintenance, and Repair Services Federal contract opportunity
Solicitation number
36C26125Q0538
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

These documents are a comprehensive set of Standpipe and Hose System Inspection, Testing, and Maintenance reports for multiple buildings located at 4150 Clements St. in San Francisco, CA, performed by Kell Fire Protection Services Inc. on November 4, 2024, as part of a 5-year inspection cycle mandated by the California Code of Regulations, Title 19, and NFPA 25 standards. The inspections cover buildings including Building 2, Building 7, Building 41, Building 200, Building 203, Building 205, Building 208, Building 209, and Building 211, with each report detailing a systematic evaluation of standpipe system components such as control valves, hose connections, pressure gauges, fire department connections, and other critical infrastructure.

The reports reveal multiple deficiencies across different buildings, including missing hose racks, corroded standpipe mains, rusted hangers, non-operational butterfly valves, and missing brass caps. Each report follows a standardized format with four sections: property information, riser information, a comprehensive inspection and testing checklist, and a deficiencies and comments section. The inspections were conducted using a pass/fail/not applicable methodology, with many components receiving a "pass" rating, while others were marked with deficiencies that will require repair or replacement to maintain the fire suppression system's integrity and compliance with safety regulations.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Form AES 3.1 Sept. 3, 2013

Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19

Property Information:

Name: Building 2 Occupancy/Use: Choose an item.

Address: 4150 Clements St. Construction Type: Choose an item.

City: San Francisco, CA No. Stories:

ZIP: 94121 Year Constructed:

Contact: Christopher Jocson

Telephone: 415-559-9541

Contractor Information: Number of System Risers 1

Copy sent to:

Name: Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth

CA. 95669

916-826-2968

Owner Date:

Address Fire AHJ Date:

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906.

2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes No

*See "Deficiencies and Comments" section at end of each respective form.

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Property Information

Contractor or Licensed Owner Information

Building Name 4150 Clements St. Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA.

Address San Francisco, CA

94121

City Christopher Jocson License # Contact Person 415-559-9541 SFM Job #

Phone 4150 Clements St. CSLB Misc.

Type of Standpipe System Class of Standpipe System

Manual Wet Automatic Dry Class I Manual Dry Semi-Automatic Dry Class II Automatic Wet Combined Sprinkler/Standpipe Class III

Riser Information Main Drain Test (ANNUAL)

Riser No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

Final Static Pressure P,F,N/A

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

5-Year INSPECTION, TESTING, AND MAINTENANCE Includes ALL Quarterly and Annual Inspections, Tests, and Maintenance Items

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item

Description NFPA 25 CA ed.

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

P

1.13 I Heat Tape 5.2.7 11-4-24 N

Inspection, Testing, and Maintenance

5-Year Report

Building Name 4150 Clements St.

Kell Fire Protection services Inc.

Name

Address San Francisco, CA Job # City 94121 Misc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

2.11 T Pressure Reducing Valves 13.5.3.2 11-4-24 N

2.12 T Pressure Gauges 6.3.4 11-4-24 P

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

D = Deficiency C = Comment (Indicate type )

Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced

Check here if additional Deficiencies and Comments are listed on Form AES9.

See Correction Form AES 10 for corrected deficiencies.

Number attached

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

Print Name Ty Kell

Signature Ty kell Date 11-4-24

2 ½” PRV OUTLET TEST RESULTS

Annual 5-Year Other DATE: 11-4-24

OUTLET

LOCATION

(STAIR )

RESIDUAL

PRESSURE

Deficiencies/ comments

Stair 1 5th floor . 142

Stair 1 4th floor 144

Stair 1 3rd floor . 146

Stair 1 2nd floor 148

Stair 1 1st floor 150

Stair 2 roof

Stair 2 7th

Stair 2 6th

Stair 2 5th

Stair 2 4th

Stair 2 3rd

Stair 2 2nd

Stair 2 1st

Stair 2 ground

Stair 2 basement

Stair 3 6th

Stair 3 5th

Stair 3 4th

Stair 3 3rd

Stair 3 2nd

Stair 3 1st

Stair 3 ground

NFPA25 as amended by CCR, Title 19

Name: Building 7 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

Final Static

STAIRWELL CLOSETS

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 F

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 F

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 F

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 F

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 F

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

11-4-24 X All hose racks are missing rack and hoses

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

Print Name Ty kell

(STAIR )

RESIDUAL

PRESSURE

@ GPM

Deficiencies/ comments

OUTLET

LOCATION

(STAIR )

RESIDUAL

PRESSURE

@ GPM

STATIC

PSI @ GPM

G floor Hall to dining

60 2 1/2

2nd fl by elev 60 Missing hose

2nd FL by staircase

60 Missing hose

1st rm 142 60 Missing hose

1 st 110A 60 Missing hose

(STAIR )

RESIDUAL

PRESSURE

@ GPM

STATIC

PSI @ GPM

OUTLET

LOCATION

(STAIR )

RESIDUAL

PRESSURE

@ GPM

STATIC

PSI @ GPM

NFPA25 as amended by CCR, Title 19

Name: Building 41 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 F

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 F

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 F

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 F

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 F

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

11-4-24 x Roof standpipe starting to rust out

11-4-24 x Missing hoses and hose racks at all locations

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

Print Name

Signature Date 11-4-24

(STAIR )

2nd floor south hose rack

50 No fire hose

2nd floor stairwell 2 ½ hose valve

2nd hose rack north hall

No fire hose

1st floor south hose rack

52 No fire hose

1st floor stairwell 2 ½ hose valve ground floor hose rack

52 No fire hose

Ground floor south hose rack

52 No fire hose

Ground floor hose rack

52 No fire hose

NFPA25 as amended by CCR, Title 19

Name: Building 41 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 F

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

11-4-24 X Roof standpipe starting to rust out

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

(STAIR )

1st floor 45

2nd floor 40

3rd floor 38

Roof 35

NFPA25 as amended by CCR, Title 19

Name: Building 200 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

11-4-24 X Handle broken off 2 ½ hose valve needs to be replaced

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

Print Name

Signature Date 11-4-24

(STAIR )

Stair 1 Roof stair 1 FL 3

Stair 1 floor 2

Stair 1 floor 1

Stair 1 floor G

Stair 1 Basemeant

Stair 2 roof stair 2 3rd stair 2 2nd stair 2 1st

Stair 2 G

Stair 3 3rd stair 3 2nd stair 3 1st stair 3 G

NFPA25 as amended by CCR, Title 19

Name: Building 203 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 N

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

Print Name Ty kell

(STAIR )

RESIDUAL

PRESSURE

@ GPM

Deficiencies/ comments

Stair 1 Roof stair 1 FL 3

Stair 1 floor 2

Stair 1 floor 1

Stair 1 floor G

Stair 1

Stair 2 roof stair 2 3rd stair 2 2nd stair 2 1st

Stair 2 G

Stair 2 basement stair 3 roof stair 3 3rd stair 3 2nd stair 3 1st stair 3 G stair 3

NFPA25 as amended by CCR, Title 19

Name: Building 205 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 F

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 F

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 F

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 F

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 F

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 F

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

11-4-24 X 3 Hose racks in building they are missing hose and rack. These need to be reinstalled per code

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

(STAIR )

RESIDUAL

PRESSURE

@ GPM

Deficiencies/ comments

OUTLET

LOCATION

(STAIR )

RESIDUAL

PRESSURE

@ GPM

STATIC

PSI @ GPM

1st south floor hose Missing hose and rack

1st north floor hose

2nd Floor center hose

NFPA25 as amended by CCR, Title 19

Name: Building 208 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 P

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 N

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 P

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3 15.7

11-4-24 Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

(STAIR )

RESIDUAL

PRESSURE

@ GPM

Deficiencies/ comments

Stair 1 1st floor 55

Stair 1 2nd 45

Stair 2 basement

Stair 2 1st

Stair 2 2nd

Stair 2 3rd

Stair 3 2nd 50

Stair 3 1st 60

Stair 2 1st

Stair 2 basement

NFPA25 as amended by CCR, Title 19

Name: Building 211 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 P

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 F

1.21 I Hangers 6.2.1 11-4-24 P

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 N

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 P

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 P

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See Deficiencies and

Comments Section for Results 14.2 11-4-24 N

3.4 M

Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3 11-4-24 Yes

No N

3.5 M System Returned to Service

4.5.3

15.7 11-4-24

Yes No P

Standpipe and Hose System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

11-4-24 X Standpipe mains next to stairwell are heavily corroded and will start leaking in the future

I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.

(STAIR )

RESIDUAL

PRESSURE

@ GPM

Deficiencies/ comments

Stair 1 5th floor . 142

Stair 1 4th floor 144

Stair 1 3rd floor . 146

Stair 1 2nd floor 148

Stair 1 1st floor 150

Stair 2 roof

Stair 2 7th

Stair 2 6th

Stair 2 5th

Stair 2 4th

Stair 2 3rd

Stair 2 2nd

Stair 2 1st

Stair 2 ground

Stair 2 basement

Stair 3 6th

Stair 3 5th

Stair 3 4th

Stair 3 3rd

Stair 3 2nd

Stair 3 1st

Stair 3 ground

NFPA25 as amended by CCR, Title 19

Name: Building 209 Occupancy/Use: Choose an item.

ZIP: 94121 Year Constructed:

Inc.

8850 Randolph Dr.

Plymouth

City: Contractor Date:

State:

NOTES:

1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011

§904.1(a)

Telephone:

CA License#: 1103729

Job #:

Performed by:

Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.

Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass

Automatic Sprinkler System 5

Standpipe and Hose System 6

Private Water Supply System 7

Fire Pump 8

Water Storage Tank 9

Water Spray System 10

Foam Water Sprinkler System 11

Water Mist System 12

Inspection, Testing, and Maintenance

5-Year Report

City Christopher Jocson License #

No. Location Riser

Diameter Main Drain Diameter

Initial Static Pressure

Residual Pressure

This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached

Reference Date Comments Only P, F, N/A

1.1 I Control Valves – Identification Sign 13.3.1 11-4-24 P

1.2 I Control Valves – Inspection 13.3.2 11-4-24 F

1.3 I Waterflow Alarm Devices 5.2.5 11-4-24 N

1.4 I Supervisory Alarm Devices 5.2.5 11-4-24 N

1.5 I Pressure Gauges

Pass = Normal Pressures

6.2.1 6.2.2

11-4-24 P

1.6 I Water Supply Pressure Below Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.7 I Water Supply Pressure Above Dry Pipe or Preaction

Valve

6.2.1 6.2.2

11-4-24 psi N

1.8 I Pressure at Top of Standpipe Riser 6.2.1

6.2.2, 13.2.7

11-4-24 psi P

1.9 I Air/Nitrogen Pressure 6.2.1

6.2.2, 13.2.7

11-4-24 psi N

1.10 I Pressure at Discharge of Fire Pump or Pressure Tank 6.2.1 6.2.2, 13.2.7

11-4-24 psi N

1.11 I Pressure Readings Acceptable 6.2.2

13.2.7

11-4-24 P

1.12 I Hydraulic Design Information Sign (For

Hydraulically Designed Systems) 6.2.3 11-4-24

Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

1.14 I Standpipe Hose Valves 13.5.6.1 11-4-24 P

1.15 I Pressure Reducing Hose Valves 13.5.2.1 11-4-24 N

1.16 I Pressure Reducing Valves 13.5.1.1 11-4-24 N

1.17 I Fire Department Connections 13.7 11-4-24 P

1.18 I Backflow Preventers 13.6.1 11-4-24 N

1.19 I Buildings (Freeze Protection) 4.1.1.1 11-4-24 Owner’s Responsibility N

1.20 I Pipe and Fittings 6.2.1

Table 6.1.2

11-4-24 F

1.21 I Hangers 6.2.1 11-4-24 F

1.22 I Seismic Braces 6.2.1 11-4-24 P

1.23 I Hose Connection

6.2.1

Table 6.1.2 11-4-24 N

1.24 I Cabinet 6.2.1

Table 6.1.2

11-4-24 N

1.25 I Hose

6.2.1

Table 6.1.2 11-4-24 N

1.26 I Hose Storage Device 6.2.1

Table 6.1.2

11-4-24 N

1.27 I Hose Nozzle 6.2.1

Table 6.1.2

11-4-24 N

2.1 T Control Valve - Position 6.2.1

13.3.3.1

11-4-24 P

2.2 T Control Valve - Operation 6.2.1

13.3.3.2

11-4-24 F

2.3 T Supervisory Devices 13.3.3.5 11-4-24 N

2.4 T Waterflow Alarm Devices 90

sec max. Enter time

5.3.3 13.2.6

11-4-24 sec. N

2.5 T Main Drain Test

(Enter Data on Page 1 of this Form)

13.2.5 13.3.3.4

11-4-24 P

2.6 T Standpipe Flow Test 6.3.1 11-4-24 Provide results in table on 1st page. P

2.7 T Standpipe Hydrostatic Test 6.3.2 11-4-24 P

2.8 T Hose Rack Assembly Flow Test 13.5.3.2 11-4-24 N

2.9 T Backflow Preventer Assemblies 13.6.2 11-4-24 N

2.10 T Pressure Reducing Hose Valves 13.5.2.2 11-4-24 N

California Code of Regulations - Title 19 Inspection, Testing, and Maintenance

5-Year Report

Kell Fire Protection services Inc.

8850 Randolph Dr.

Plymouth, CA

Name

I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable

Item Description NFPA 25 CA ed.

Reference Date Comments Only P,F,N/A

2.13 T Hose Test 6.2.1 NFPA

11-4-24 N

3.1 M Control Valves 13.3.4 11-4-24 F

3.2 M FDC - Backflush 14.3.2.3

14.3.2.4

11-4-24 P

3.3 M Internal Pipe Inspection: See…