D.4 ATTACHMENT 4 - EXHIBIT D - DAMPER REPORT [2018].pdf
PDF 70 KB Posted
- Attached to
- J063--Fire Suppression System Inspection, Testing Maintenance, and Repair Services Federal contract opportunity
- Solicitation number
- 36C26125Q0538
About this file
This document is a damper inspection report for the San Francisco VA Health Care Systems, conducted on September 15, 2018 by Corry Railey. The report covers damper inspections across multiple buildings (200, 203, 208), detailing the location, type, and status of fire and smoke dampers. The majority of dampers were marked as "NON-ACCESSIBLE" due to various issues such as blocked access, no access doors, pipes blocking the damper, or being longer than arm's reach. Only a small percentage of dampers passed the inspection, with one damper in Building 203 (FD-001-003) explicitly marked as "FAIL" due to being bound in tracks. The systematic inspection focused on dampers in hallways, rooms, administrative offices, electrical equipment rooms, and other areas throughout the VA healthcare facility.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26125Q0538 0002 - Updated Price Schedule and Q-As.pdf | ||
| 36C26125Q0538 0002.docx | DOCX document | |
| 36C26125Q0538_2.docx | DOCX document | |
| D.5 ATTACHMENT 5 - STANDARD EP LIST AND FREQUENCY.pdf | ||
| 36C26125Q0538_1.docx | DOCX document | |
| D.3 ATTACHMENT 3 - EXHIBIT C VASF CORRECTED ACTION FORM.pdf | ||
| D.7 ATTACHMENT 7 - DOL WAGE DETERMININATION 2015-5637 REV.29, DATED 05-21-2025 - SAN FRANCISCO-SAN MATEO.pdf | ||
| D.6 ATTACHMENT 6 - 2024 SFVA STANDPIPE 5-YEAR BUILDING INSPECTIONS.pdf | ||
| D.2 ATTACHMENT 2 - EXHIBIT B VASF FA TEST AND DEVICE COUNT.pdf | ||
| D.1 ATTACHMENT 1 - EXHIBIT A TJC LIFE SAFETY EC DOCUMENT LIST REVIEW TOOL.pdf | ||
| RFQ 36C26125Q0538 - Fire Suppression.pdf | ||
| D.9 ATTACHMENT 9 - PAST PERFORMANCE SURVEY.docx | DOCX document | |
| D.8 ATTACHMENT 8 - VASF TEST AND DEVICE COUNT.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contracted By: San Francisco VA Health Care Systems
Facility: San Francisco VA Health Care Systems
Last Inspection Date: September 15, 2018
Last Inspected By: Corry Railey
Building 200
Date Damper
Number
Damper
Location
Damper Type Job Type Result Issues Current Status
09/15/18 FD-00G-001 Above double doors to administrations offices
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-00G-002 Above double doors to administrations offices
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-001-001 Next to room
1b-103 and service elevator
Smoke Inspection PASS PASS
09/15/18 FD-001-002 Above door 1A-
Fire Inspection PASS PASS
09/15/18 FD-001-003 In hall by room
1A-229
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-001-004 In hall by room
1A-229
Fire Inspection PASS PASS
09/15/18 FD-001-005 In hall by room
1A-136
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-001-006 In hall by room
1A-136
Fire Inspection PASS PASS
09/15/18 FD-002-001 Above double doors by 2B-
Fire Inspection NON-
ACCESSIBLE
Pipes blocking NON-
ACCESSIBLE
09/15/18 FD-002-002 Above double doors by 2B-
Fire Inspection NON-
ACCESSIBLE
Pipes blocking NON-
ACCESSIBLE
09/15/18 FD-002-003 Inside hall by room 2A-159A and room 2A-
Fire Inspection NON-
ACCESSIBLE
Pipes blocking NON-
ACCESSIBLE
09/15/18 FD-002-004 In hall by room
2A-127 and the exit stairs
Fire Inspection NON-
ACCESSIBLE
Pipes blocking NON-
ACCESSIBLE
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
Date Damper
Number
Damper
Location
Damper Type Job Type Result Issues Current Status
09/15/18 FD-003-001 Inside OR above room
#3A-145
Fire Inspection NON-
ACCESSIBLE
Hard Ceiling NON-
ACCESSIBLE
09/15/18 FD-003-002 Inside OR by pump room above the emergency exit stairs
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-003-003 Inside SPD station
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
Last Inspection Date: September 15, 2018
Last Inspected By: Corry Railey
Building 203
Date Damper
Number
Damper
Location
Damper Type Job Type Result Issues Current Status
09/15/18 FD-00B-001 Above double doors by room
BA-4 and BA-3
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FSD-00B-002 Above double doors by room
BA-4 and BA-3
Smoke Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FSD-00B-003 Above double doors by room
BA-4 and BA-3
Smoke Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FSD-00B-004 Above double doors by room
BA-4 and BA-3
Smoke Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-00B-005 Inside electrical equipment room by MRI zone 2
Fire Inspection PASS PASS
09/15/18 FD-00G-004 In hall by room
GB3
Fire Inspection PASS PASS
09/15/18 FD-00G-005 In hall by room
GB3
Fire Inspection PASS PASS
09/15/18 FD-00G-006 In hall by room
GB3
Fire Inspection PASS PASS
09/15/18 FD-00G-007 In hall by room
GA-18
Fire Inspection PASS PASS
09/15/18 FD-00G-008 In hall by room
GA-18
Fire Inspection NON-
ACCESSIBLE
Pipes blocking NON-
ACCESSIBLE
09/15/18 FD-001-001 In hall by room
1DU-3
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-001-002 Inside room
1DU-3 by elevators
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-001-003 Inside room
1DU-3 by elevators
Fire Inspection FAIL Bound in tracks
(racking)
FAIL
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
Date Damper
Number
Damper
Location
Damper Type Job Type Result Issues Current Status
09/15/18 FD-001-004 Inside room
1DU-3 by elevators
Fire Inspection PASS PASS
09/15/18 FD-001-005 Inside room
1DU-3 by elevators
Fire Inspection PASS PASS
09/15/18 FD-001-006 In hall by room
1B-1
Fire Inspection NON-
ACCESSIBLE
Longer than arm's reach
NON-
ACCESSIBLE
09/15/18 FSD-001-007 In hall by room
1B26A
Smoke Inspection PASS PASS
09/15/18 FD-001-008 In hall by room
1A-24
Fire Inspection PASS PASS
09/15/18 FD-001-009 In hall by room
1A-24
Fire Inspection PASS PASS
09/15/18 FD-001-010 Inside room
1EL-1
Fire Inspection NON-
ACCESSIBLE
No access door NON-
ACCESSIBLE
09/15/18 FD-002-001 In hall by room
2DU-4
Fire Inspection PASS PASS
09/15/18 FD-002-002 In hall by room
2DU-4
Fire Inspection PASS PASS
09/15/18 FD-002-003 In hall by room
2A-25
Fire Inspection NON-
ACCESSIBLE
Pipes blocking NON-
ACCESSIBLE
09/15/18 FD-002-004 In hall by room
2A-25
Fire Inspection NON-
ACCESSIBLE
Longer than arm's reach
NON-
ACCESSIBLE
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
VHASFCTangcR Highlight
Last Inspection Date: September 15, 2018
Last Inspected By: Corry Railey
Building 208
Date Damper Number Damper Location Damper Type Job Type Result Issues Current Status
09/15/18 FD-00P-002 Inside penthouse Fire Inspection PASS PASS
09/15/18 FD-00P-003 Inside penthouse Fire Inspection PASS PASS
09/15/18 FD-00P-004 Inside penthouse Fire Inspection PASS PASS
09/15/18 FD-001-001 In hall by room 1A-108 Fire Inspection NON-ACCESSIBLE No access door NON-
ACCESSIBLE
VHASFCTangcR Highlight
VHASFCTangcR Highlight
File details come from the government source that posted it. Updated .