D.4 ATTACHMENT 4 - EXHIBIT D - DAMPER REPORT [2018].pdf

PDF 70 KB Posted

Attached to
J063--Fire Suppression System Inspection, Testing Maintenance, and Repair Services Federal contract opportunity
Solicitation number
36C26125Q0538
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

This document is a damper inspection report for the San Francisco VA Health Care Systems, conducted on September 15, 2018 by Corry Railey. The report covers damper inspections across multiple buildings (200, 203, 208), detailing the location, type, and status of fire and smoke dampers. The majority of dampers were marked as "NON-ACCESSIBLE" due to various issues such as blocked access, no access doors, pipes blocking the damper, or being longer than arm's reach. Only a small percentage of dampers passed the inspection, with one damper in Building 203 (FD-001-003) explicitly marked as "FAIL" due to being bound in tracks. The systematic inspection focused on dampers in hallways, rooms, administrative offices, electrical equipment rooms, and other areas throughout the VA healthcare facility.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contracted By: San Francisco VA Health Care Systems

Facility: San Francisco VA Health Care Systems

Last Inspection Date: September 15, 2018

Last Inspected By: Corry Railey

Building 200

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-00G-001 Above double doors to administrations offices

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-00G-002 Above double doors to administrations offices

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-001 Next to room

1b-103 and service elevator

Smoke Inspection PASS PASS

09/15/18 FD-001-002 Above door 1A-

Fire Inspection PASS PASS

09/15/18 FD-001-003 In hall by room

1A-229

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-004 In hall by room

1A-229

Fire Inspection PASS PASS

09/15/18 FD-001-005 In hall by room

1A-136

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-006 In hall by room

1A-136

Fire Inspection PASS PASS

09/15/18 FD-002-001 Above double doors by 2B-

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-002 Above double doors by 2B-

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-003 Inside hall by room 2A-159A and room 2A-

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-004 In hall by room

2A-127 and the exit stairs

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-003-001 Inside OR above room

#3A-145

Fire Inspection NON-

ACCESSIBLE

Hard Ceiling NON-

ACCESSIBLE

09/15/18 FD-003-002 Inside OR by pump room above the emergency exit stairs

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-003-003 Inside SPD station

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

Last Inspection Date: September 15, 2018

Last Inspected By: Corry Railey

Building 203

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-00B-001 Above double doors by room

BA-4 and BA-3

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FSD-00B-002 Above double doors by room

BA-4 and BA-3

Smoke Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FSD-00B-003 Above double doors by room

BA-4 and BA-3

Smoke Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FSD-00B-004 Above double doors by room

BA-4 and BA-3

Smoke Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-00B-005 Inside electrical equipment room by MRI zone 2

Fire Inspection PASS PASS

09/15/18 FD-00G-004 In hall by room

GB3

Fire Inspection PASS PASS

09/15/18 FD-00G-005 In hall by room

GB3

Fire Inspection PASS PASS

09/15/18 FD-00G-006 In hall by room

GB3

Fire Inspection PASS PASS

09/15/18 FD-00G-007 In hall by room

GA-18

Fire Inspection PASS PASS

09/15/18 FD-00G-008 In hall by room

GA-18

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-001-001 In hall by room

1DU-3

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-002 Inside room

1DU-3 by elevators

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-003 Inside room

1DU-3 by elevators

Fire Inspection FAIL Bound in tracks

(racking)

FAIL

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-001-004 Inside room

1DU-3 by elevators

Fire Inspection PASS PASS

09/15/18 FD-001-005 Inside room

1DU-3 by elevators

Fire Inspection PASS PASS

09/15/18 FD-001-006 In hall by room

1B-1

Fire Inspection NON-

ACCESSIBLE

Longer than arm's reach

NON-

ACCESSIBLE

09/15/18 FSD-001-007 In hall by room

1B26A

Smoke Inspection PASS PASS

09/15/18 FD-001-008 In hall by room

1A-24

Fire Inspection PASS PASS

09/15/18 FD-001-009 In hall by room

1A-24

Fire Inspection PASS PASS

09/15/18 FD-001-010 Inside room

1EL-1

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-002-001 In hall by room

2DU-4

Fire Inspection PASS PASS

09/15/18 FD-002-002 In hall by room

2DU-4

Fire Inspection PASS PASS

09/15/18 FD-002-003 In hall by room

2A-25

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-004 In hall by room

2A-25

Fire Inspection NON-

ACCESSIBLE

Longer than arm's reach

NON-

ACCESSIBLE

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

Last Inspection Date: September 15, 2018

Last Inspected By: Corry Railey

Building 208

Date Damper Number Damper Location Damper Type Job Type Result Issues Current Status

09/15/18 FD-00P-002 Inside penthouse Fire Inspection PASS PASS

09/15/18 FD-00P-003 Inside penthouse Fire Inspection PASS PASS

09/15/18 FD-00P-004 Inside penthouse Fire Inspection PASS PASS

09/15/18 FD-001-001 In hall by room 1A-108 Fire Inspection NON-ACCESSIBLE No access door NON-

ACCESSIBLE

VHASFCTangcR Highlight

VHASFCTangcR Highlight