The documents represent a comprehensive mechanical, electrical, and architectural plan for a Pool Boiler Replacement project for Chippewa Valley Schools, specifically at Chippewa Valley High School, located in Michigan. The project involves replacing the existing boiler system, installing new boilers, heat exchangers, pumps, and associated mechanical and electrical infrastructure, with bid documents dated March 21, 2025. The project scope includes demolition of existing equipment, installation of two 2,000 MBH natural gas condensing boilers, a packaged pool heat exchanger skid, inline pumps, an expansion tank, and an air/dirt separator, along with necessary electrical connections and controls.
The project appears to be funded through the school district's capital improvement budget, with an estimated electrical and mechanical infrastructure investment. The mechanical design incorporates advanced features such as lead/lag boiler operation, building management system integration, variable frequency drive (VFD) pump controls, and a heating hot water reset schedule based on outside air temperature. The electrical scope includes providing new disconnects, conduit, and wiring for the new equipment, as well as emergency power shut-off stations. The design emphasizes system efficiency, redundancy, and modern control strategies to optimize the school's heating and pool heating systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL ABBREVIATIONS MECHANICAL ABBREVIATIONSMECHANICAL ABBREVIATIONS MECHANICAL SYMBOLS
DRAWING NOTATION
MECHANICAL PIPING SYMBOLS
PIPING LEGEND
CW
HW
HWR
BHW
BCW
HW(140°F)
FOR
FOS
CHWR
CHWS
CD
CWR
CWS
G
GXHR
GXHS
CR
HHWR
HHWS
HPLR
HPLS
NPCW
DT
F
PCR
LPC
HPC
N
PSAN
RC
ORC
RL
RS
SAN
ST
STM
HPS
LPS
V
CA
VAC
O2
MA
PST
HGB
TW
APPLICABLE CODES
AND REGULATIONS
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
MZ
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
MPH
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
MECHANICAL GENERAL
INFORMATION
M0.00
DRAWING INDEX
SHT NO DESCRIPTION
M0.00 MECHANICAL GENERAL INFORMATION
M1.00 MECHANICAL COMPOSITE PLAN
M4.01 ENLARGED MECHANICAL DEMOLITION AND NEW WORK PLANS
M5.00 MECHANICAL DETAILS AND SCHEDULES
M6.00 MECHANICAL PIPING DIAGRAMS AND TEMPERATURE CONTROLS
1, 2 M4.01
1, 2 P4.01
GENERAL DEMOLITION NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
EXTENT OF WORK TO BE PERFORMED. THE EXACT EXTENT OF
DEMOLITION SHALL BE DETERMINED BY THE NEW WORK.
B
ANY INTERRUPTIONS OF EXISTING SERVICES AND/OR EQUIPMENT SHALL
BE PERFORMED AT A TIME APPROVED IN ADVANCE BY OWNER'S
REPRESENTATIVE SO AS NOT TO INTERFERE WITH THE PRESENT
BUILDING'S OPERATION.
C
PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL VISIT THE
SITE AND BECOME FAMILIAR WITH EXISTING SITE CONDITIONS,
SYSTEMS, AND UTILITIES. NOTIFY DESIGN PROFESSIONAL OF ANY
INTERFERENCES OR DISCREPANCIES.
D
ALL ITEMS INDICATED WITH CROSS-HATCHING SHALL BE REMOVED
COMPLETELY WITH ALL RELATED ITEMS INCLUDING HANGERS,
SUPPORTS, INSULATION, CONTROLS, ETC. CAP ALL OPEN-ENDED PIPES
AND DUCTS.
E
THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL EQUIPMENT
BEING REMOVED. ALL ITEMS REMOVED SHALL BE LEGALLY DISPOSED OF.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXISTING
RELOCATED AND OWNER-PROVIDED EQUIPMENT.
F
VERIFY DEPTH, SIZE, LOCATIONS, AND CONDITIONS OF EXISTING
UTILITIES IN THE FIELD, INCLUDING POINTS OF CONNECTION, PRIOR TO
STARTING WORK.
G
ALL ITEMS ON DEMOLITION PLAN SHALL BE CONSIDERED EXISTING
UNLESS OTHERWISE NOTED. ALL WORK INDICATED ON PLANS HAS BEEN
LOCATED PER EXISTING DRAWINGS AND/OR FIELD OBSERVATION AND
REQUIRES FIELD VERIFICATION.
H
ALL EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.
WHERE DUCT WORK PIPE INSULATION HAS BEEN DAMAGED DURING
DEMOLITION, THE CONTRACTOR SHALL REPAIR INSULATION AS
REQUIRED TO MATCH EXISTING.
PLUMBING GENERAL NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
EXTENT OF WORK TO BE PERFORMED. THE EXACT EXTENT OF
DEMOLITION SHALL BE DETERMINED BY THE NEW WORK.
B
ANY INTERRUPTIONS OF EXISTING SERVICES AND/OR EQUIPMENT SHALL
BE PERFORMED AT A TIME APPROVED IN ADVANCE BY OWNER'S
REPRESENTATIVE SO AS NOT TO INTERFERE WITH THE PRESENT
BUILDING'S OPERATION.
C
PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL VISIT THE
SITE AND BECOME FAMILIAR WITH EXISTING SITE CONDITIONS,
SYSTEMS, AND UTILITIES. NOTIFY DESIGN PROFESSIONAL OF ANY
INTERFERENCES OR DISCREPANCIES.
D
ALL ITEMS INDICATED WITH CROSS-HATCHING SHALL BE REMOVED
COMPLETELY WITH ALL RELATED ITEMS INCLUDING HANGERS,
SUPPORTS, INSULATION, CONTROLS, ETC. CAP ALL OPEN-ENDED PIPES
AND DUCTS.
E
THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL EQUIPMENT
BEING REMOVED. ALL ITEMS REMOVED SHALL BE LEGALLY DISPOSED OF.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXISTING
RELOCATED AND OWNER-PROVIDED EQUIPMENT.
F
VERIFY DEPTH, SIZE, LOCATIONS, AND CONDITIONS OF EXISTING
UTILITIES IN THE FIELD, INCLUDING POINTS OF CONNECTION PRIOR TO
STARTING WORK.
G
ALL ITEMS ON DEMOLITION PLAN SHALL BE CONSIDERED EXISTING
UNLESS OTHERWISE NOTED. ALL WORK INDICATED ON PLANS HAS BEEN
LOCATED PER EXISTING DRAWINGS AND/OR FIELD OBSERVATION AND
REQUIRES FIELD VERIFICATION.
H
ALL EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.
WHERE DUCT WORK PIPE INSULATION HAS BEEN DAMAGED DURING
DEMOLITION, THE CONTRACTOR SHALL REPAIR INSULATION AS
REQUIRED TO MATCH EXISTING.
J
INSTALL ALL SANITARY AND STORM PIPING 2 1/2" OR LESS AT 1/4" PER
FOOT AND 3" AND LARGER PIPING AT 1/8" PER FOOT MINIMUM UNLESS
NOTED OTHERWISE. MINIMUM UNDERGROUND PIPE SIZE SHALL BE 3".
K PROVIDE "INLINE" WATERLESS PRIMER TRAP SEAL PROTECTION ON ALL
FLOOR DRAINS AND TRAPS SUBJECT TO EVAPORATION.
L AT EACH CONNECTION OF GAS SUPPLY TO EQUIPMENT, PROVIDE A PIPE
UNION, GAS SHUT OFF VALVE, TEE, AND 6" LONG DIRT LEG WITH CAP.
M
THE CEILING SPACE IS USED AS A RETURN AIR PLENUM. NO PLASTIC
MATERIALS INCLUDING PVC PIPING, CONDUIT WIRING, ETC. SHALL BE
USED. ALL MATERIALS TO BE USED ARE TO BE PLENUM-RATED.
HVAC GENERAL NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL
EXTENT OF WORK TO BE PERFORMED. PROVIDE AND EXECUTE ALL HVAC
SYSTEMS PER ENGINEER'S SPECIFICATION, AND LOCAL APPLICABLE
CODES INCLUDING AMENDMENTS, BULLETINS, ETC; AS WELL AS
STANDARDS OF INSTALLATION AND EQUIPMENT ESTABLISHED FOR THE
BUILDINGS, AND REQUIREMENTS OF OWNER.
B
EXCEPT FOR CHANGES AS MAY BE SPECIFICALLY APPROVED BY THE
ENGINEER OF RECORD, IN ACCORDANCE WITH ALTERNATES OF OPTIONS
AS STATED HEREINAFTER, ALL WORK MUST BE IN FULL ACCORDANCE
WITH THE INTENT OF THE PLANS AND SPECIFICATIONS. SYSTEMS ARE
TO BE COMPLETE, EFFICIENT, AND SATISFACTORY OPERATION WHEN
PROJECT IS DELIVERED TO THE OWNER.
C
THE CONTRACTOR AND EACH SUBCONTRACTOR COVENANTS AND
AGREES TO INDEMNIFY, DEFEND, AND HOLD HARMLESS THE
CONSULTING ENGINEER, ARCHITECT, AND OWNER FROM AND AGAINST
ANY LIABILITY, LOSS, DAMAGE, OR EXPENSE INCLUDING ATTORNEYS
ARISING FROM A FAILURE OR ALLEGED FAILURE ON THE PART OF THE
CONTRACTOR, SUBCONTRACTORS, AND THEIR AGENTS/EMPLOYEES
PROPERLY TO DISCHARGE THE OBLIGATIONS ASSUMED BY HIM/HER IN
THE PERFORMANCE OF THE WORK, INCLUDING ANY ACT OR OMISSION
ALLEGEDLY RESULTING IN DEATH, PERSONAL INJURY, PROPERTY
DAMAGE, OR IMPROPER CONSTRUCTION PROTOCOL.
D
CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND APPROVAL
FROM GOVERNING AUTHORITIES, FILE NECESSARY FORMS, PAY ALL
INSPECTION FEES.
E
CONTRACTOR TO EXAMINE ALL ADJOINING WORK BEFORE
COMMENCEMENT OF HIS/HER SCOPE OF WORK. REPORT ANY
DISCREPANCIES TO THE CONSTRUCTION MANAGER FOR REVIEW AND
APPROVAL. COORDINATE ALL WORK WITH OTHER TRADES TO ENSURE
THAT INSTALLATION IS MADE IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
F
PROVIDE REQUIRED CLEARANCE IN FRONT OF ELECTRICAL EQUIPMENT;
DUCTWORK/PIPING SHALL NOT INTERFERE WITH ELECTRICAL
EQUIPMENT CLEARANCE.
G
CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH
MANUFACTURER'S CERTIFIED DRAWINGS. ALL PIPING CONNECTIONS
SHALL BE MINIMUM 3/4" UNLESS NOTED OTHERWISE.
H FURNISH ADEQUATE LIABILITY INSURANCE AND BONDING DOCUMENTS
AS REQUIRED BY THE OWNER.
J
ALL SUPPORT ANCHORS SECURED TO THE BOTTOM OF FLOOR SLABS
SHALL BE DROP-IN OR SLEEVE ANCHOR TYPE. ALL SUPPORTING STEEL
SHALL BE PROVIDED BY THE CONTRACTOR.
K DUCTWORK/PIPING SHALL NOT BE INSTALLED IN A LOCATION THAT
RESTRICTS THE ACCESS TO MECHANICAL DEVICES REQUIRING ACCESS.
L THE CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS SUPPORTING
STEEL FOR THE PROPER INSTALLATION OF MECHANICAL SYSTEMS.
M
BRANCH DUCTWORK TO GRILLES, REGISTERS, AND DIFFUSERS SHALL BE
THE SAME SIZE AS TERMINAL DEVICE NECK SIZE WHERE NO DUCT SIZE
IS INDICATED.
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
MZ
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
MPH
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
MECHANICAL COMPOSITE
PLAN
M1.00
SCALE:
MECHANICAL COMPOSITE PLAN
1/32" = 1'-0"
(E)DWH-1
(E)ET-1
(E)12Ø
FLUE
(E)12Ø
FLUE
(E)12Ø
FLUE
(E)G
(E)G
(E)FD(E)HX-1
(E)CP-4
(E)AS-1
(E)CW
VFD-1 VFD-2
(E)6" GAS
THRU ROOF
3/4" 4"
(E)6" CW METER
ASSEMBLY
(E)FD
1 1 1
(E)2" POOL
HEATING
SUPPLY/RETURN
(E)HHWS
(E)HHWR
(E)HHWS
(E)HHWR
(E)HHWR
(E)HHWR
(E)HHWR
(E)HHWR
(E)CP-3
POOL EQUIPMENT
PIT
MECHANICAL ROOM
MEZZANINE
GENERAL DEMOLITION NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
EXTENT OF WORK TO BE PERFORMED. THE EXACT EXTENT OF
DEMOLITION SHALL BE DETERMINED BY THE NEW WORK.
B
ANY INTERRUPTIONS OF EXISTING SERVICES AND/OR EQUIPMENT SHALL
BE PERFORMED AT A TIME APPROVED IN ADVANCE BY OWNER'S
REPRESENTATIVE SO AS NOT TO INTERFERE WITH THE PRESENT
BUILDING'S OPERATION.
C
PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL VISIT THE
SITE AND BECOME FAMILIAR WITH EXISTING SITE CONDITIONS,
SYSTEMS, AND UTILITIES. NOTIFY DESIGN PROFESSIONAL OF ANY
INTERFERENCES OR DISCREPANCIES.
D
ALL ITEMS INDICATED WITH CROSS-HATCHING SHALL BE REMOVED
COMPLETELY WITH ALL RELATED ITEMS INCLUDING HANGERS,
SUPPORTS, INSULATION, CONTROLS, ETC. CAP ALL OPEN-ENDED PIPES
AND DUCTS.
E
THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL EQUIPMENT
BEING REMOVED. ALL ITEMS REMOVED SHALL BE LEGALLY DISPOSED OF.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXISTING
RELOCATED AND OWNER-PROVIDED EQUIPMENT.
F
VERIFY DEPTH, SIZE, LOCATIONS, AND CONDITIONS OF EXISTING
UTILITIES IN THE FIELD, INCLUDING POINTS OF CONNECTION, PRIOR TO
STARTING WORK.
G
ALL ITEMS ON DEMOLITION PLAN SHALL BE CONSIDERED EXISTING
UNLESS OTHERWISE NOTED. ALL WORK INDICATED ON PLANS HAS BEEN
LOCATED PER EXISTING DRAWINGS AND/OR FIELD OBSERVATION AND
REQUIRES FIELD VERIFICATION.
H
ALL EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.
WHERE DUCT WORK PIPE INSULATION HAS BEEN DAMAGED DURING
DEMOLITION, THE CONTRACTOR SHALL REPAIR INSULATION AS
REQUIRED TO MATCH EXISTING.
DEMOLITION KEYED NOTES
REMOVE BOILER AND ASSOCIATED PRIMARY PUMP COMPLETE INCLUDING ALL
CONTROLS, ACCESSORIES, FLUE, GAS VENT PIPING, AND HYDRONIC PIPING AS
INDICATED. CAP FLUE OPENING AND SEAL WEATHER TIGHT. PREPARE PIPING FOR
NEW CONNECTION.
2 REMOVE BASE PUMP COMPLETE INCLUDING ALL ACCESSORIES, ASSOCIATED VFD,
AND VIBRATION BASE. PREPARE PIPING FOR NEW CONNECTION.
3 REMOVE BLADDER EXPANSION TANK COMPLETE INCLUDING ALL HANGERS PIPING,
AND ACCESSORIES. PREPARE CONCRETE PAD FOR UNIT INSTALLATION.
4 REMOVE CHEMICAL SHOT FEEDER COMPLETE INCLUDING ALL PIPING AND
ACCESSORIES.
5 REMOVE SIDESTREAM FILTER COMPLETE INCLUDING ALL PIPING AND
ACCESSORIES.
REMOVE POOL HEAT EXCHANGER COMPLETE INCLUDING ALL HANGERS,
ACCESSORIES, AND CONTROLS. CAP PIPING AT HEATING HOT WATER MAIN.
PREPARE POOL HEATING PIPING FOR NEW CONNECTION.
X NEW WORK KEYED NOTES
INSTALL BOILER ON EXISTING HOUSEKEEPING PAD. EXTEND 8"Ø FLUE AND
COMBUSTION AIR PIPING THRU ROOF. COMBUSTION AIR PIPING SHALL BE
GOOSENECK WITH BIRDSCREEN AND OPENING SHALL BE MIN. 24" ABOVE ROOF.
FLUE SHALL TERMINATE A MINIMUM OF 3 FEET ABOVE THE ROOF OR 2 FEET
ABOVE ANYTHING WITHIN 10 FEET. PROVIDE GUY WIRES AS NECESSARY IF
RECOMMENDED BY THE FLUE MANUFACTURER. ROUTE 1-1/2" CONDENSATE
FROM BOILER TO NEARBY FLOOR DRAIN PROVIDE ACID NEUTRALIZER. PROVIDE
ALL ACCESSORIES REQUIRED FOR INSTALLATION.
INSTALL PACKAGED POOL HEAT EXCHANGER SKID PACKAGE ON EXISTING
HOUSEKEEPING PAD. POOL HEAT EXCHANGER IS A PACKAGED SKID
ASSEMBLY. CONNECT 3" HEATING HOT WATER PIPING TO SYSTEM
HEADER AND 2-1/2" POOL HEATING/RETURN PIPING TO SHELL AND
TUBE HEADER. TERMINATE ALL CONNECTIONS WITH ISOLATION VALVES.
3 INSTALL INLINE PUMP ON EXISTING CONCRETE PAD. PROVIDE NEW PIPE
SUPPORTS AS REQUIRED.
4 INSTALL EXPANSION TANK ON EXISTING HOUSEKEEPING PAD. CONFIRM EXACT
LOCATION WITH OWNER.
PRIOR TO FINAL TURNOVER, FLUSH ENTIRE HEATING HOT WATER
DISTRIBUTION SYSTEM WITH POLISH COMPOUND CLEANING MIXTURE
AND PROVIDE HVAC WATER TREATMENT.
X HVAC GENERAL NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL
EXTENT OF WORK TO BE PERFORMED. PROVIDE AND EXECUTE ALL HVAC
SYSTEMS PER ENGINEER'S SPECIFICATION, AND LOCAL APPLICABLE
CODES INCLUDING AMENDMENTS, BULLETINS, ETC; AS WELL AS
STANDARDS OF INSTALLATION AND EQUIPMENT ESTABLISHED FOR THE
BUILDINGS, AND REQUIREMENTS OF OWNER.
B
EXCEPT FOR CHANGES AS MAY BE SPECIFICALLY APPROVED BY THE
ENGINEER OF RECORD, IN ACCORDANCE WITH ALTERNATES OF OPTIONS
AS STATED HEREINAFTER, ALL WORK MUST BE IN FULL ACCORDANCE
WITH THE INTENT OF THE PLANS AND SPECIFICATIONS. SYSTEMS ARE
TO BE COMPLETE, EFFICIENT, AND SATISFACTORY OPERATION WHEN
PROJECT IS DELIVERED TO THE OWNER.
C
THE CONTRACTOR AND EACH SUBCONTRACTOR COVENANTS AND
AGREES TO INDEMNIFY, DEFEND, AND HOLD HARMLESS THE
CONSULTING ENGINEER, ARCHITECT, AND OWNER FROM AND AGAINST
ANY LIABILITY, LOSS, DAMAGE, OR EXPENSE INCLUDING ATTORNEYS
ARISING FROM A FAILURE OR ALLEGED FAILURE ON THE PART OF THE
CONTRACTOR, SUBCONTRACTORS, AND THEIR AGENTS/EMPLOYEES
PROPERLY TO DISCHARGE THE OBLIGATIONS ASSUMED BY HIM/HER IN
THE PERFORMANCE OF THE WORK, INCLUDING ANY ACT OR OMISSION
ALLEGEDLY RESULTING IN DEATH, PERSONAL INJURY, PROPERTY
DAMAGE, OR IMPROPER CONSTRUCTION PROTOCOL.
D
CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND APPROVAL
FROM GOVERNING AUTHORITIES, FILE NECESSARY FORMS, PAY ALL
INSPECTION FEES.
E
CONTRACTOR TO EXAMINE ALL ADJOINING WORK BEFORE
COMMENCEMENT OF HIS/HER SCOPE OF WORK. REPORT ANY
DISCREPANCIES TO THE CONSTRUCTION MANAGER FOR REVIEW AND
APPROVAL. COORDINATE ALL WORK WITH OTHER TRADES TO ENSURE
THAT INSTALLATION IS MADE IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
F
PROVIDE REQUIRED CLEARANCE IN FRONT OF ELECTRICAL EQUIPMENT;
DUCTWORK/PIPING SHALL NOT INTERFERE WITH ELECTRICAL
EQUIPMENT CLEARANCE.
G
CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH
MANUFACTURER'S CERTIFIED DRAWINGS. ALL PIPING CONNECTIONS
SHALL BE MINIMUM 3/4" UNLESS NOTED OTHERWISE.
H FURNISH ADEQUATE LIABILITY INSURANCE AND BONDING DOCUMENTS
AS REQUIRED BY THE OWNER.
J
ALL SUPPORT ANCHORS SECURED TO THE BOTTOM OF FLOOR SLABS
SHALL BE DROP-IN OR SLEEVE ANCHOR TYPE. ALL SUPPORTING STEEL
SHALL BE PROVIDED BY THE CONTRACTOR.
K DUCTWORK/PIPING SHALL NOT BE INSTALLED IN A LOCATION THAT
RESTRICTS THE ACCESS TO MECHANICAL DEVICES REQUIRING ACCESS.
L THE CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS SUPPORTING
STEEL FOR THE PROPER INSTALLATION OF MECHANICAL SYSTEMS.
(E)DWH-1
(E)G
(E)G
(E)FD
(E)CW
(E)6" GAS
THRU ROOF
3/4"4"
(E)6" CW METER
ASSEMBLY
(E)FD
(E)2 1/2" POOL
HEATING
SUPPLY/RETURN
(E)HHWS
(E)HHWR
4"
4"
4"
4"
B-1
BP-1
BP-2
AS-1
ET-1
3/4"
1 1/4"
B-2
HX-12
CP-3
CP-4
2"
2"
HHWS
HHWR
CW
4"
3"
2 1/2"
CHEMICAL
SHOT FEEDER
3/4"
3/4"
POOL EQUIPMENT
PIT
MECHANICAL ROOM
MEZZANINE
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
MZ
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
MPH
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
ENLARGED MECHANICAL
DEMOLITION AND NEW WORK
PLANS
M4.01
SCALE:
ENLARGED MECHANICAL DEMOLITION PLAN - MECHANICAL ROOM
1/4" = 1'-0"
M1-00 SCALE:
ENLARGED MECHANICAL NEW WORK PLAN - MECHANICAL ROOM
1/4" = 1'-0"
M1-00
EXPANSION TANK SCHEDULE
UNIT ID SYSTEM SERVED TYPE MIN PSIG MAX PSIG MIN
(°F)
MAX
(°F)
TANK VOLUME
(GAL)
DIA
(IN) HEIGHT (IN) MODEL NO. REMARKS
ET-1 HEATING HOT
WATER BLADDER 55 125 50.0 220.0 106 30 49 NLA-400
NOTES:
1. MODEL NUMBER IS WESSELS.
2. PERFORMANCE BASED ON WATER.
AIR/DIRT SEPARATOR SCHEDULE
UNIT ID SYSTEM LOCATION
CONN.
SIZE
(IN.)
DRAIN
SIZE (IN.)
WEIGHT
(LBS) MODEL NO. REMARKS
AS-1 HEATING HOT
WATER
BOILER
ROOM 6" 1" 260 VDT-600
NOTES:
1. MODEL NUMBER IS SPIROTHERM UNLESS NOTED OTHERWISE.
2. PROVIDE COALESCING TYPE, CENTRIFUGAL NOT ACCEPTED.
3. VESSEL SHALL BE CERTIFIED FOR 150# WORKING PRESSURE AND BE FURNISHED WITH ANSI/ASME B16.5 OR B16.47 CLASS 150 STEEL
WELD NECK FLANGES.
4. UNIT SHALL INCLUDE STRUCTURED COALESCING MEDIA FILLING THE ENTIRE VESSEL.
5. UNIT SHALL REMOVE 100% OF FREE AND ENTRAINED AIR AND 99.6% OF DISSOLVED AIR AS TESTED BY INDEPENDENT LAB.
6. UNIT SHALL REMOVE 80% OF THE 30 MICRON PARTICLES IN 100 CIRCULATIONS. UNIT CAPABLE OF 5 MICRON PARTICLE SIZE
REMOVAL.
VARIABLE FREQUENCY DRIVE SCHEDULE
UNIT ID UNIT
SERVICE LOCATION
MOUNTING
REMARKS
SURFACE
MOTOR
CONTROL
CENTER
PACKAGED
WITH EQUIP.
UNISTRUT
SUPPORTED
VFD-1 CP-1 BOILER X
VFD-2 CP-2 BOILER X
NOTES:
1. VARIABLE SPEED DRIVE RATED HORSEPOWER SHALL MATCH THE REQUIREMENTS OF THE EQUIPMENT THAT IT SERVES.
COORDINATE WITH MANUFACTURER.
PUMP SCHEDULE
UNIT ID SYSTEM SERVED TYPE FLOW (GPM) HEAD (FT) IMPELLER DIA
(IN.)
MIN DUTY %
EFF
ELECTRICAL
MODEL NO. REMARKS
BHP HP RPM VOLTS PHASE
CP-3 HEATING HOT WATER SYSTEM INLINE SPLIT CASE 190 60.0 8.5 65.1 - 10.0 2910 480 3 GRUNDFOS: TP 65-410 INTEGRAL VFD (VFD-1)
CP-4 HEATING HOT WATER SYSTEM INLINE SPLIT CASE 190 60.0 8.5 65.1 - 10.0 2910 480 3 GRUNDFOS: TP 65-410 INTEGRAL VFD (VFD-2)
BP-1 B-1 INLINE 150 15.0 PROVIDED WITH BOILER 1.0 1800 480 3 PROVIDED WITH BOILER
BP-2 B-2 INLINE 150 15.0 PROVIDED WITH BOILER 1.0 1800 480 3 PROVIDED WITH BOILER
NOTES:
1. MODEL NUMBERS ARE BELL & GOSSETT UNLESS NOTED OTHERWISE.
2. PERFORMANCE BASED ON WATER, UNLESS OTHERWISE INDICATED.
3. PUMPS SHALL BE NON-OVERLOADING.
4. PUMPS PACKAGED WITH BUILT-IN VARIABLE FREQUENCY DRIVE.
5. PROVIDE WITH FLANGE MOUNTING SUPPORTS (CP-3, CP-4)
CONDENSING BOILER SCHEDULE
WATER ELECTRICAL DISCONNECT/STARTER
B-1 NAT GAS 2,000 1900 20:1 160 150 120 160 350 <5 120 1 16.0 SWITCH 26 26 26 BMK2000
B-2 NAT GAS 2,000 1900 20:1 160 150 120 160 350 <5 120 1 16.0 SWITCH 26 26 26 BMK2000
NOTES:
1. MODEL NUMBERS ARE AERCO.
2. PERFORMANCE DATA IS BASED ON WATER.
3. BOILER MUST HAVE INTEGRAL CASCADE CONTROL WITH BACNET MSTP INTERFACE, LEAD/LAG, EFFICIENCY OPTIMIZATION
AND CASCADE REDUNDANCY.
4. MANUFACTURER TO PROVIDE GE GAP GAS TRAIN.
5. PROVIIDE FLOW SWITCH.
6. PROVIDE ACID NEUTRALIZER KIT.
7. PROVIDE BOILER PRIMARY PUMP.
8. BOILER FLUE AND COMBUSTION AIR PIPING SHALL BE AL29-4C.
SPLIT
COUPLER
SYSTEM
INLET
SYSTEM
OUTLET
SUCTION
GUIDE
TRIPLE DUTY
VALVE
FLUSH
LINE
PRESSURE GAGE
AND PIPING
PET
COCK
(TYP)
DRAIN
CONNECTION STANCHION PLATE
(TYP)
NEOPRENE PAD
WITH DOUBLE NUT
SEE BLOW UP DETAIL
BELOW (TYP)
STRUCTURE
NEOPRENE PAD
EQUIPMENT FOOT
GROMMET
STEEL WASHER
DOUBLE NUT
PUMP MOTOR
SEE SPECIFICATIONS
FOR DETAILS
TYPICAL SEISMIC VERTICAL INLINE PUMP INSTALLATIONIN-LINE CIRCULATING PUMP PIPING DIAGRAM
1/4 GAUGE LINE (TYP)
IN-LINE CIRCULATING PUMP
UNION TYPE CONNECTION (TYP)
PROVIDE CLEARANCE FOR PUMP
AND MOTOR REMOVAL
MOTOR BOLTED TO PUMP HOUSING.
INSTALL MOTOR DEAD LEVEL WITH
LUBRICATION POINTS UP
RIGIDLY SUPPORT PIPING ADJACENT
TO PUMP TO ALLOW PUMP REMOVAL
WITHOUT DISTURBING PIPING SYSTEM
INSULATED PIPE HANGER DETAIL
RIGID PIPE OR FIBERGLASS
INSULATION (REFER TO SPEC)
20 GAGE GALVANIZED STEEL
NSULATION SHIELD
(REFER TO SPEC)
CLEVIS HANGER
VAPOR TIGHT SEAL AT JOINT
OF INSULATION TO PREVENT
MOISTURE PENETRATION &
SWEATING (TYP EA JOINT)
PIPE
RIGID PIPE OR FIBERGLASS INSULATION
(REFER TO SPEC)
20 GAGE GALVANIZED
STEEL INSULATION
SHIELD (REFER TO SPEC)
PIPE
CLEVIS HANGER
CONDENSING BOILER STACK DETAIL
1. PROVIDE STACK SUPPORTS, GUIDES AND EXPANSION SECTIONS AS REQUIRED PER
MANUFACTURER'S INSTRUCTIONS.
2. COORDINATE INSTALLATION OF STACK SUPPORTS DURING CONSTRUCTION.
ROOF
PRE-FABRICATED ROOF
CURB AND FLASHING FOR
SLOPED ROOF
STAINLESS STEEL DRAWBAND
AND CONTINUOUS SEALANT
STORM COLLAR
TALL CONE FLASHING
SEALANT
STACK SUPPORT
PLATE
M
IN
. 8
GOOSENECK DETAIL
SCREEN FRAME
ANGLE IRON REINF.
RIVETED OR WELDED
AS REQD.
1/2" BIRD
SCREEN
EXTEND BUILT UP ROOFING ON
ROOF DECK TO TOP OF CURB
CURB FASTENING FLANGE
BACK DRAFT DAMPER AS REQD.
HEAT EXCHANGER SKID SCHEDULE
UNIT ID SYSTEM
SERVED TYPE CAPACITY
(MBH)
SOURCE WATER SYSTEM WATER
MANUFACTURER/
MODEL NO.
SKID
MANUFACTUREREWT
(°F)
LWT
(°F)
FLOW
(GPM)
FOULING
FACTOR
MAX WPD
(FT HEAD)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
FOULING
FACTOR
MAX WPD (FT
HEAD)
NUMBER
OF PASSES
HX-1 POOL SHELL AND
TUBE 940.1 180 160 96.25 0.00025 2.5 82.0 97.0 125.7 0.00025 3.0 2 BELL AND GOSSETT /
QDWU-104-26 BELL & GOSSETT
NOTES:
1. SHALL BE PROVIDED AS FULL EQUIPMENT HEAT EXCHANGER PACKAGE WITH CONTROLS.
2. SHALL BE PROVIDED WITH CONTROL PANEL EQUIPPED WITH BACNET MSTP INTERFACE.
3. SHELL AND TUBE HEAT EXCHANGER SHALL BE DOUBLE WALL, 90/10 COPPER NICKEL TUBES.
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
MZ
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
MPH
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
MECHANICAL DETAILS AND
SCHEDULES
M5.00
HHWS
HHWS
FINISHED FLOOR
THERMOMETER
(TYP)
HEATING HOT WATER SYSTEM PIPING DIAGRAM
FROM BUILDING
TO BUILDING
ET-1
1 1/4
(E)6
4AAV
MAV
(E)FD
HHWR
HHWS
(E)G
8 FLUE
HH
W
R
HH
W
S
4 4
BP-1
FLOW CHECK
VALVE (TYP.)
Y-STRAINER (TYP.)
RELIEF
VALVE
(TYP.)
B-1
(E)8 FLUE
HH
W
R
HH
W
S
4 4
(E)G (E)6
AS-1
BP-2
HX-1
HH
W
R
HH
W
S
HHWR(POOL)
HHWS(POOL)
HHWR(POOL)
HHWS(POOL)
HHWS
HHWR
2 1/2
2 1/2
2 1/2
2 1/2
8 INTAKE
8 INTAKE
B-2
ACID NEUTRALIZER
(TYP.)
3/43/4
SIDESTREAM FILTER/SHOT FEEDER
MODEL: ENERCO 4FOS1
W/ PEDESTRAL
TRIPLE DUTY
VALVE (TYP)
FLOW MEASURING
DEVICE
HHWS
HHWS
FINISHED FLOOR
THERMOMETER
(TYP)
FROM BUILDING
TO BUILDING
AAV
MAV
(E)FD
HHWR
HHWS
HH
W
R
HH
W
S
BP-1
B-1
HH
W
R
HH
W
S
BP-2
HX-1
HHWR(POOL)
HHWS(POOL)
HHWR(POOL)
HHWS(POOL)
HHWS
HHWR
B-2
PACKAGED SKID
CONTROL PANEL
HEATING HOT WATER SYSTEM CONTROL DIAGRAM
HEATING HOT WATER SYSTEM SEQUENCE OF OPERATIONS:
NOTE: ALL SETPOINTS AND TIME INTERVALS SHALL BE ADJUSTABLE BY THE SYSTEM OPERATOR.
HEATING HOT WATER PLANT MANAGER
1. THE BUILDING MANAGEMENT SYSTEM (BMS) SHALL INCLUDE A HEATING HOT WATER PLANT MANAGER TO CONTROL THE SECONDARY
HEATING HOT WATER PUMPS AND STAGE THE BOILERS IN A LEAD/LAG OPERATION.
2. THE HEATING HOT WATER SYSTEM SHALL BE ENABLED TO RUN WHENEVER THE OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG. F.
3. TO PREVENT SHORT CYCLING, THE HEATING HOT WATER SYSTEM SHALL RUN FOR AND BE OFF FOR A MINIMUM ADJUSTABLE TIME (BOTH
TIMES USER ADJUSTABLE).
SECONDARY PUMP CONTROL
1. WHEN THE HEATING HOT WATER SYSTEM IS ENABLED, THE LEAD HEATING HOT WATER PUMP SHALL BE ENABLED.
3. EACH PUMP WILL PROVE OPERATION TO THE BMS WITH ITS CURRENT SWITCH. IF A PUMP FAILS, AN ALARM WILL BE SENT TO THE BMS
AND THE LAG PUMP WILL BE ACTIVATED (IF NOT OPERATING).
4. THE PLANT MANAGER SHALL ALTERNATE PUMP OPERATION BASED ON RUN TIME HOURS OR AT THE BEGINNING OF EACH MONTH.
5. THE CONTROLLER SHALL MEASURE THE HEATING HOT WATER RETURN WATER TEMPERATURE AND MODULATE THE SECONDARY HEATING HOT WATER PUMP VFDS IN SEQUENCE TO MAINTAIN THE HEATING HOT WATER RETURN WATER SETPOINT. ALL SETPOINTS SHALL BE FIELD ADJUSTED DURING TESTING AND BALANCING TO MEET THE REQUIREMENTS OF THE ACTUAL FIELD CONDITIONS.
BOILER CONTROL:
1. WHEN THE BOILER IS STAGED ON BY THE PLANT MANAGER, THE BOILER'S INTERNAL CONTROLS SHALL START THE ASSOCIATED PRIMARY
HEATING HOT WATER PUMP. THE DDC SYSTEM SHALL MONITOR PRIMARY PUMP STATUS THROUGH CURRENT SWITCH.
HEAT EXCHANGER CONTROL:
1. THE PACKAGED HEAT EXCHANGER CONTROL PANEL SHALL MODULATE THE 3-WAY CONTROL VALVE TO MAINTAIN SYSTEM FLOW AND POOL
HEATING
UPON PROOF OF FLOW, THE BOILER'S INTERNAL CONTROLS WILL START THE BOILER AND ENERGIZE THE STAGES OF HEATING TO MAINTAIN THE BOILER DISCHARGE TEMPERATURE SETPOINT (SYSTEM SUPPLY TEMPERATURE SETPOINT). THE SUPPLY SETPOINT SHALL ADJUST BASED
ON THE SYSTEM RESET SCHEDULE.
MONITOR AND ALARM:
1. THE BMS SHALL MONITOR AND GRAPHICALLY SHOW, AT A MINIMUM, THE FOLLOWING POINTS. ALL POINTS SHALL BE ALARMED WHEN
OUT OF RANGE:
1.1. BOILER STATUS AND STAGING
1.2. BOILER RUN TIMES AND START/STOPS
1.3. BOILER ALARM
1.4. BOILER ENTERING AND LEAVING WATER TEMPERATURES (HIGH AND LOW ALARMS)
1.5. BOILER WATER SYSTEM SUPPLY AND RETURN WATER TEMPERATURES (HIGH AND LOW ALARMS)
1.6. SECONDARY PUMP SPEED
1.7. ALL PUMPS STATUS (ALARMS WHEN SCHEDULED ON, BUT NOT OPERATING)
2. DATA TRENDS SHALL BE ESTABLISHED TO RECORD AND TREND ALL POINTS INDICATED ABOVE.
3. ADDITIONAL BOILER INFORMATION AVAILABLE THROUGH THE BACNET INTEGRATION SHALL BE ACCESSIBLE THROUGH THE BMS FRONT
END SYSTEM, BUT DOES NOT NEED TO BE PRESENTED ON THE GRAPHIC DISPLAY.
110°F< 50°F
< 25°F 160°F
HEATING HOT WATER SUPPLY (HHWS)
RESET SCHEDULE
HHWS
TEMPERATURE
OUTSIDE AIR
TEMP.
< 10F 180°F
START/STOP
VFD SPEED
VFD FAULT
START/STOP
VFD SPEED
VFD FAULT
SETPOINT
FAULT
FAULT
SETPOINT
FAULT
FAULT
(E)EMERGENCY
SHUT-OFF
SWITCH
(E)DWH
OUTDOOR AIR
TEMPERATURE
SENSOR
BUILDING AUTOMATION SYSTEM NOTES:
1. CONFIGURATION AND ORDER OF CONTROLLER CONNECTION IS FOR REPRESENTATION PURPOSES ONLY. UPDATE
CONTROL SYSTEM
DRAWINGS TO REFLECT ACTUAL AS-BUILT CONDITIONS, INCLUDING ORDER IN WHICH CONTROLLERS ARE CONNECTED
WITHIN THE NETWORK.
2. PROVIDE NEW SOFTWARE FOR THE DISTRICT'S BUILDING AUTOMATION SYSTEM (AKA ENERGY MANAGEMENT SYSTEM) FRONT END SYSTEM. PROVIDE FOR BACNET OVER IP LICENSING FOR THE ENTIRE BUILDING. NEW SYSTEM SHALL BE OPEN PROTOCOL TRIDIUM NIAGARA AX SUPERVISOR VERSION N4 WITH CURRENT PATCHES AS OF AUGUST 2022.
BUILDING AUTOMATION SYSTEM RISER DIAGRAM
NO SCALE
BACNET OVER IP NETWORK TO
SUPERVISORY SYSTEM. PROVIDE
NEW WORK STATION.
HX-1 CP-1
(E) JACE
BUILDING
FRONT END
SYSTEM (JACE
VYKON J8000)
TRIDIUM
NIAGARA
CP-2
TO ADDITIONAL
EQUIPMENT
B-1 B-2
NO SCALE
NO SCALE
PACKAGED & PRE-PIPED
SKID ASSEMBLY
HH
W
R
HH
W
S
CP-3 CP-4
CP-3 CP-4
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
MZ
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
MPH
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
MECHANICAL PIPING
DIAGRAMS AND
TEMPERATURE CONTROLS
M6.00
ELECTRICAL ABBREVIATIONS
SECTION
DRAWING NOTATION
POWER SYMBOL LIST
FIRE ALARM SYMBOL LIST
AUXILIARY SYST. SYMBOL LIST
Z1 1A
APPLICABLE CODES
AND REGULATIONS
ERS
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
TJO
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
ELECTRICAL GENERAL
INFORMATION
E0.00
DRAWING INDEX
SHT NO DESCRIPTION
E0.00 ELECTRICAL GENERAL INFORMATION
E1.00 ELECTRICAL COMPOSITIE PLAN
EP4.01 ENLARGED ELECTRICAL POWER DEMOLITON AND NEW WORK PLANS
E6.00 ELECTRICAL PANEL SCHEDULES AND DETAILS
E7.00 ELECTRICAL ONE-LINE RISER DIAGRAMS
1, 2
EP4.01
LP-P
RP-P2
RP-P1
PDP-PP
GENERAL DEMOLITION NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
EXTENT OF WORK TO BE PERFORMED. THE EXACT EXTENT OF
DEMOLITION SHALL BE DETERMINED BY THE NEW WORK.
B
ANY INTERRUPTIONS OF EXISTING SERVICES AND/OR EQUIPMENT SHALL
BE PERFORMED AT A TIME APPROVED IN ADVANCE BY OWNER'S
REPRESENTATIVE SO AS NOT TO INTERFERE WITH THE PRESENT
BUILDING'S OPERATION.
C
PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL VISIT THE
SITE AND BECOME FAMILIAR WITH EXISTING SITE CONDITIONS,
SYSTEMS, AND UTILITIES. NOTIFY DESIGN PROFESSIONAL OF ANY
INTERFERENCES OR DISCREPANCIES.
D
ALL ITEMS INDICATED WITH CROSS-HATCHING SHALL BE REMOVED
COMPLETELY WITH ALL RELATED ITEMS INCLUDING HANGERS,
SUPPORTS, INSULATION, CONTROLS, ETC. CAP ALL OPEN-ENDED PIPES
AND DUCTS.
E
THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL EQUIPMENT
BEING REMOVED. ALL ITEMS REMOVED SHALL BE LEGALLY DISPOSED OF.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXISTING
RELOCATED AND OWNER-PROVIDED EQUIPMENT.
F
VERIFY DEPTH, SIZE, LOCATIONS, AND CONDITIONS OF EXISTING
UTILITIES IN THE FIELD, INCLUDING POINTS OF CONNECTION, PRIOR TO
STARTING WORK.
G
ALL ITEMS ON DEMOLITION PLAN SHALL BE CONSIDERED EXISTING
UNLESS OTHERWISE NOTED. ALL WORK INDICATED ON PLANS HAS BEEN
LOCATED PER EXISTING DRAWINGS AND/OR FIELD OBSERVATION AND
REQUIRES FIELD VERIFICATION.
H
ALL EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.
WHERE DUCT WORK PIPE INSULATION HAS BEEN DAMAGED DURING
DEMOLITION, THE CONTRACTOR SHALL REPAIR INSULATION AS
REQUIRED TO MATCH EXISTING.
POWER GENERAL NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL
EXTENT OF THE WORK TO BE PERFORMED. PROVIDE AND EXECUTE ALL
HVAC SYSTEMS PER ENGINEER'S SPECIFICATION, AND LOCAL APPLICABLE
CODES INCLUDING AMENDMENTS, BULLETINS, ETC; AS WELL AS THE
STANDARDS OF INSTALLATION AND EQUIPMENT ESTABLISHED FOR THE
BUILDINGS, AND REQUIREMENTS OF THE OWNER.
B
EXCEPT FOR CHANGES AS MAY BE SPECIFICALLY APPROVED BY THE
ENGINEER OF RECORD IN ACCORDANCE WITH ALTERNATES OF OPTIONS
AS STATED HEREINAFTER, ALL WORK MUST BE IN FULL ACCORDANCE
WITH THE INTENT OF THE PLANS AND SPECIFICATIONS. SYSTEMS ARE
TO BE COMPLETE, EFFICIENT, AND SATISFACTORY OPERATION WHEN
PROJECT IS DELIVERED TO THE OWNER.
D
CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND APPROVAL
FROM GOVERNING AUTHORITIES, FILE NECESSARY FORMS, PAY ALL
INSPECTION FEES.
E
ELECTRICAL CONTRACTOR SHALL COMPLY WITH THE LATEST NATIONAL
ELECTRICAL CODE, LIFE SAFETY CODE AND APPLICABLE STATE AND
LOCAL CODES AND ORDINANCES.
F
ELECTRICAL EQUIPMENT AND WIRING SHALL BE NEW AND SHALL BE
FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR, UNLESS
OTHERWISE NOTED.
G WIRING SHALL BE IN CONDUIT. CONDUIT SHALL BE 3/4" CONDUIT
MINIMUM. CONDUITS IN FINISHED AREAS SHALL BE CONCEALED.
H
NEW WIRES SHALL BE TYPE THHN. MINIMUM SIZE SHALL BE #12 AWG,
UNLESS OTHERWISE NOTED. FINAL CONNECTIONS TO EQUIPMENT,
FURNISHED AND INSTALLED BY OTHERS, SHALL BE PROVIDED BY THIS
CONTRACTOR.
J ALL P.A. AND SPEAKER SCOPE BY OTHERS. REFER TO TECH DRAWINGS
FOR FURTHER INFORMATION.
NEW WORK KEYED NOTES
PROPOSED PATH FOR NEW CONDUITS FROM PDP-PP DISTRIBUTION
BOARD TO BOILER ROOM EQUIPMENT. ESTIMATED RUN IS 150 FEET
LONG.
X
ERS
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
TJO
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
ELECTRICAL COMPOSITIE
PLAN
E1.00
SCALE:
ELECTRICAL COMPOSITIE PLAN
1/32" = 1'-0"
(E)DWH-1
(E)CP-4
(E)VFD-1 (E)VFD-2
3 3 3
(E)CP-3
J J
4 4 4
J J J
RP-P2-8PDP-PPPDP-PP RP-P2-10 RP-P2-36
PDP-PP PDP-PP PDP-PP
POOL EQUIPMENT
PIT
MECHANICAL ROOM
MEZZANINE
GENERAL DEMOLITION NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
EXTENT OF WORK TO BE PERFORMED. THE EXACT EXTENT OF
DEMOLITION SHALL BE DETERMINED BY THE NEW WORK.
B
ANY INTERRUPTIONS OF EXISTING SERVICES AND/OR EQUIPMENT SHALL
BE PERFORMED AT A TIME APPROVED IN ADVANCE BY OWNER'S
REPRESENTATIVE SO AS NOT TO INTERFERE WITH THE PRESENT
BUILDING'S OPERATION.
C
PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL VISIT THE
SITE AND BECOME FAMILIAR WITH EXISTING SITE CONDITIONS,
SYSTEMS, AND UTILITIES. NOTIFY DESIGN PROFESSIONAL OF ANY
INTERFERENCES OR DISCREPANCIES.
D
ALL ITEMS INDICATED WITH CROSS-HATCHING SHALL BE REMOVED
COMPLETELY WITH ALL RELATED ITEMS INCLUDING HANGERS,
SUPPORTS, INSULATION, CONTROLS, ETC. CAP ALL OPEN-ENDED PIPES
AND DUCTS.
E
THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL EQUIPMENT
BEING REMOVED. ALL ITEMS REMOVED SHALL BE LEGALLY DISPOSED OF.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXISTING
RELOCATED AND OWNER-PROVIDED EQUIPMENT.
F
VERIFY DEPTH, SIZE, LOCATIONS, AND CONDITIONS OF EXISTING
UTILITIES IN THE FIELD, INCLUDING POINTS OF CONNECTION, PRIOR TO
STARTING WORK.
G
ALL ITEMS ON DEMOLITION PLAN SHALL BE CONSIDERED EXISTING
UNLESS OTHERWISE NOTED. ALL WORK INDICATED ON PLANS HAS BEEN
LOCATED PER EXISTING DRAWINGS AND/OR FIELD OBSERVATION AND
REQUIRES FIELD VERIFICATION.
H
ALL EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.
WHERE DUCT WORK PIPE INSULATION HAS BEEN DAMAGED DURING
DEMOLITION, THE CONTRACTOR SHALL REPAIR INSULATION AS
REQUIRED TO MATCH EXISTING.
DEMOLITION KEYED NOTES
BASE MOUNTED CIRCULATION PUMP AND ALL ASSOCIATED CONTROLS
BEING REMOVED COMPLETE BY MECHANICAL TRADES. ELECTRICAL
CONTRACTOR SHALL DISCONNECT AND MAKE SAFE. DEMO COMPLETE
INCLUDING ALL CONDUIT AND WIRING BACK TO RESPECTIVE VFD. REFER
TO NEW WORK PLANS FOR MORE INFORMATION.
VFD BEING REMOVED COMPLETE BY MECHANICAL TRADES. ELECTRICAL
CONTRACTOR SHALL DISCONNECT AND MAKE SAFE. DEMO COMPLETE
BACK TO SOURCE INCLUDING ALL CONDUIT AND WIRING. REFER TO NEW
WORK PLANS FOR MORE INFORMATION.
HEATING HOT WATER BOILER BEING REMOVED COMPLETE BY
MECHANICAL TRADES. ELECTRICAL CONTRACTOR SHALL DISCONNECT
AND MAKE SAFE. DEMO COMPLETE BACK TO SOURCE INCLUDING ALL
CONDUIT AND WIRING. REFER TO NEW WORK PLANS FOR MORE
INFORMATION.
PRIMARY PUMP BEING REMOVED COMPLETE BY MECHANICAL TRADES.
ELECTRICAL CONTRACTOR SHALL DISCONNECT AND MAKE SAFE. DEMO
COMPLETE BACK TO SOURCE INCLUDING ALL CONDUIT AND WIRING.
RETAIN BREAKER AS SPARE.
X NEW WORK KEYED NOTES
NEW BOILER BEING INSTALLED BY MECHANICAL TRADES. ELECTRICAL
CONTRACTOR SHALL PROVIDE DISCONNECT SWITCH AND FINAL
ELECTRICAL CONNECTIONS USING NEW CONDUIT AND WIRING.
NEW BOILER PRIMARY PUMP BEING INSTALLED BY MECHANICAL TRADES.
ELECTRICAL CONTRACTOR SHALL PROVIDE DISCONNECT AND FINAL
ELECTRICAL CONNECTIONS USING NEW CONDUIT AND WIRING.
NEW BOILER EMERGENCY POWER OFF. REFER TO EMERGENCY BOILER POWER
OFF WIRING DIAGRAM LOCATED ON ELECTRICAL DETAILS SHEET. LOCATION TO
BE ON MEZZANINE ABOVE MAIN FLOOR. COORDINATE THE EXACT LOCATION FOR
MOUNTING WITH THE OWNER PRIOR TO INSTALLATION.
NEW BOILER EMERGENCY POWER OFF. REFER TO EMERGENCY BOILER
POWER OFF WIRING DIAGRAM LOCATED ON ELECTRICAL DETAILS SHEET.
LOCATION TO BE ON MAIN FLOOR BELOW MEZZANINE ON LATCH SIDE OF
DOOR. COORDINATE EXACT LOCATION FOR MOUNTING WITH THE
OWNER PRIOR TO INSTALLATION.
NEW CIRCULATION PUMP BEING INSTALLED BY MECHANICAL TRADES.
ELECTRICAL CONTRACTOR SHALL PROVIDE DISCONNECT AND FINAL
ELECTRICAL CONNECTIONS USING NEW CONDUIT AND WIRING.
NEW HEAT EXCHANGER BEING INSTALLED BY MECHANICAL TRADES.
ELECTRICAL CONTRACTOR TO PROVIDE FINAL ELECTRICAL
CONNECTIONS OF CONTROL PANEL USING NEW CONDUIT AND WIRING.
X POWER GENERAL NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL
EXTENT OF THE WORK TO BE PERFORMED. PROVIDE AND EXECUTE ALL
HVAC SYSTEMS PER ENGINEER'S SPECIFICATION, AND LOCAL APPLICABLE
CODES INCLUDING AMENDMENTS, BULLETINS, ETC; AS WELL AS THE
STANDARDS OF INSTALLATION AND EQUIPMENT ESTABLISHED FOR THE
BUILDINGS, AND REQUIREMENTS OF THE OWNER.
B
EXCEPT FOR CHANGES AS MAY BE SPECIFICALLY APPROVED BY THE
ENGINEER OF RECORD IN ACCORDANCE WITH ALTERNATES OF OPTIONS
AS STATED HEREINAFTER, ALL WORK MUST BE IN FULL ACCORDANCE
WITH THE INTENT OF THE PLANS AND SPECIFICATIONS. SYSTEMS ARE
TO BE COMPLETE, EFFICIENT, AND SATISFACTORY OPERATION WHEN
PROJECT IS DELIVERED TO THE OWNER.
D
CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND APPROVAL
FROM GOVERNING AUTHORITIES, FILE NECESSARY FORMS, PAY ALL
INSPECTION FEES.
E
ELECTRICAL CONTRACTOR SHALL COMPLY WITH THE LATEST NATIONAL
ELECTRICAL CODE, LIFE SAFETY CODE AND APPLICABLE STATE AND
LOCAL CODES AND ORDINANCES.
F
ELECTRICAL EQUIPMENT AND WIRING SHALL BE NEW AND SHALL BE
FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR, UNLESS
OTHERWISE NOTED.
G WIRING SHALL BE IN CONDUIT. CONDUIT SHALL BE 3/4" CONDUIT
MINIMUM. CONDUITS IN FINISHED AREAS SHALL BE CONCEALED.
H
NEW WIRES SHALL BE TYPE THHN. MINIMUM SIZE SHALL BE #12 AWG,
UNLESS OTHERWISE NOTED. FINAL CONNECTIONS TO EQUIPMENT,
FURNISHED AND INSTALLED BY OTHERS, SHALL BE PROVIDED BY THIS
CONTRACTOR.
J ALL P.A. AND SPEAKER SCOPE BY OTHERS. REFER TO TECH DRAWINGS
FOR FURTHER INFORMATION.
(E)DWH-1
B-1 B-2CP-3
CP-4
BP-1
BP-2
J J
1 1
230A 3P
600V30A 3P 600V
PDP-PPPDP-PP PDP-PP PDP-PP
HX-1
RP-P2-8
RP-P2-10
J
RP-P2-36
30A 3P 600V
30A 3P 600V
POOL EQUIPMENT
PIT
MECHANICAL ROOM
MEZZANINE
ERS
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
TJO
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
ENLARGED ELECTRICAL
POWER DEMOLITON AND
NEW WORK PLANS
EP4.01
SCALE:
ENLARGED ELECTRICAL POWER DEMOLITION PLAN - MECHANICAL ROOM
1/4" = 1'-0"
E1-00 SCALE:
ENLARGED ELECTRICAL POWER NEW WORK PLAN - MECHANICAL ROOM
1/4" = 1'-0"
E1-00
C
BOILER EMERGENCY POWER OFF PUSHBUTTON -
SAFETY TECHNOLOGY INTERNATIONAL
MODEL SS2081PO-EN OR EQUIVALENT
(TYPICAL)
BOILER EMERGENCY POWER OFF CONTACTOR
SQUARE D MODEL 8903LA1200V02 OR EQUIVALENT
120VAC COIL, (12) N.O. 600VAC RATED CONTACTS
CONTACT STATUS IS SHOWN
WITH THE COIL ENERGIZED (TYPICAL)
BOILER EMERGENCY POWER SHUT OFF WIRING DIAGRAM
L1
N
L1
N
ERS
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
TJO
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
ELECTRICAL PANEL
SCHEDULES AND DETAILS
E6.00
TO (E) MSB-H1
PDP
1600A, 480/277V, 3P, 4W
PDP-PP
800A, 480/277V, 3P, 4W
480V
208Y/120V
VSD
PARTIAL ONE-LINE DIAGRAM DEMOLITON WORK
(E)RF-1 (E)RF-2 (E)SF-1
(E)AHU-3
(E)CP-1 (E)CP-2(E)CP-4 (E)BC-1 (E)DRAIN
PUMP
(E)FILTER
PUMP
(E)STANDBY
FILTER PUMP(E)
U.V.GENERATOR
(E)CU-1
TO (E) RDP
VSD
(E)CP-10
SP
AC
E
SP
AC
E
(E)CP-7 (E)CP-8
VSD
(E)CP-3
(E)ERU-1 (E)DU-1 (E)CHILLER
(E)SF-2
TO (E) MSB-H1
PDP
1600A, 480/277V, 3P, 4W
PDP-PP
800A, 480/277V, 3P, 4W
480V
208Y/120V
PARTIAL ONE-LINE DIAGRAM DEMOLITON WORK
(E)RF-1 (E)RF-2 (E)SF-1
(E)AHU-3
(E)BC-1 (E)DRAIN
PUMP
(E)FILTER
PUMP
(E)STANDBY
FILTER PUMP(E)
U.V.GENERATOR
(E)CU-1
TO (E) RDP
VSD
(E)CP-7 (E)CP-8
(E)ERU-1 (E)DU-1 (E)CHILLER
(E)SF-2CP-3
10HP
CP-4
10HP
BP-1
1 HP
BP-2
1 HP
SPARESPARE
SPARESPARE
SPARE
4 WIRE WITH GROUND
FEEDER AND CONDUIT SIZES
3 WIRE WITH GROUNDSIZE
COND.FEEDER
(AMPS)
4#12, 1#12 GND IN 3/4"C3#12, 1#12 GND IN 3/4"C12
4#10, 1#10 GND IN 3/4"C3#10, 1#10 GND IN 3/4"C10
ERS
BIDS 03/21/2025
DATE:
DESIGN DEVELOPMENT
JOB NO.
SHEET NO.
CHECKED BY
REVISIONS
DRAWN BY
FINAL RECORD
CONSTRUCTION
PRELIMINARY
MARCH 21, 2025
FX: 586.573.0822
PH: 586.573.4100
SUITE 209
www.WakelyAIA.com
WARREN, MICHIGAN 48093
30500 VAN DYKE AVENUE
ARCHITECTS
WAKELY ASSOCIATES, INC.
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 007.25.02
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
TJO
252068
C H
IP
PE
W A
VA
LL
EY
S
C H
O O
LS
C H
IP
PE
W A
VA
LL
EY
H
IG
H
S C
H O
O L
PO
O
L
BO
IL
ER
R
EP
LA
C
EM
EN
T
ELECTRICAL ONE-LINE RISER
DIAGRAMS
E7.00
| Sheets and Views |
| M0.00 MECHANICAL GENERAL INFORMATION |
| M1.00 MECHANICAL COMPOSITE PLAN |
| M4.01 ENLARGED MECHANICAL DEMOLITION AND NEW WORK PLANS |
| M5.00 MECHANICAL DETAILS AND SCHEDULES |
| M6.00 MECHANICAL PIPING DIAGRAMS AND TEMPERATURE CONTROLS |
| E0.00 ELECTRICAL GENERAL INFORMATION |
| E1.00 ELECTRICAL COMPOSITIE PLAN |
| EP4.01 ENLARGED ELECTRICAL POWER DEMOLITON AND NEW WORK PLANS |
| E6.00 ELECTRICAL PANEL SCHEDULES AND DETAILS |
| E7.00 ELECTRICAL ONE-LINE RISER DIAGRAMS |