This document is an Addendum No. One for the Chippewa Valley Schools, specifically for the Chippewa Valley High School Pool Boiler Replacement project, dated April 3, 2025. The addendum modifies the original project specifications issued on March 21, 2025, with project number 252068. The addendum introduces two key modifications: first, it adds Bass Controls to the list of approved control systems installers in Specification Section 230925, and second, it revises the mechanical piping diagrams (sheet M6.01) to clarify the boiler system controller requirements.
The addendum does not introduce significant changes to project scope, pricing, or overall contract terms. The modification appears to be a minor update to the technical specifications, focusing on expanding the list of approved contractors and providing additional detail about the boiler system control architecture. No drawings are being issued with this addendum, and the changes seem to be administrative in nature, likely aimed at providing more precise guidance to potential contractors bidding on the pool boiler replacement project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WAKELY ASSOCIATES, INC. ADDENDUM NO. ONE
ARCHITECTS CHIPPEWA VALLEY SCHOOLS
30500 Van Dyke Avenue Suite 209 CHIPPEWA VALLEY HIGH SCHOOL Warren, Michigan 48093 POOL BOILER REPLACEMENT
Page 1 of 1 (write up only)
April 3, 2025
ADDENDUM NO. ONE to the plans and specifications for the CHIPPEWA VALLEY
SCHOOLS, CHIPPEWA VALLEY HIGH SCHOOL, POOL BOILER REPLACEMENT,
Architect’s Project No. 252068 dated March 21, 2025.
The above plans and specifications are modified, supplemented, or augmented as follows, and this ADDENDUM NO. ONE, is hereby made a part of the contract documents.
No Drawings are being issued with this Addendum.
Specification Section 230925 Digital Control (DDC) Systems for HVAC is being issued with this Addendum
SPECIFICATION ITEMS:
ITEM NO. S1: Refer to Specification Section 230925 Digital Control (DDC) Systems for HVAC (Re-Issued):
1. Refer to paragraph 1.07 for revised list of approved contractors to include Bass Controls.
ITEM NO. M1: Refer to sheet M6.01 – Mechanical Piping Diagrams and Temperature Controls (Re-Issued):
1. Revised system DDC architecture to indicate boiler clarify that a boiler system controller to be provided.
END OF ADDENDUM NO. 1
jatkins Text Box M6.00
CHIPPEWA VALLEY SCHOOLS
CHIPPEWA VALLEY HIGH SCHOOL
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 1
SECTION 23 09 25
DIGITAL CONTROL (DDC) SYSTEMS FOR HVAC
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Control Equipment B. Software
1.02 RELATED REQUIREMENTS
A. Division 01 - General Requirements: Project administrative and procedural requirements.
B. Division 02 - Existing Conditions.
C. Section 23 0005 - Basic HVAC Requirements.
D. Section 23 0553 - Identification for HVAC Piping and Equipment.
E. Section 23 0800 - Commissioning of HVAC.
F. Section 23 0913 - Instrumentation and Control Devices for HVAC.
G. Section 23 0915 - Variable Frequency Drives.
H. Section 23 2123 - Hydronic Pumps.
I. Section 23 3300 - Air Duct Accessories.
J. Section 23 3423 - HVAC Power Ventilators.
K. Section 23 5233.13 - Finned Water-Tube Boilers.
L. Section 23 7223 - Packaged Air-to-Air Energy Recovery Units.
M. Section 23 7413 - Packaged Outdoor Central-Station Air-Handling Units.
N. Section 23 8148 - Water Source Heat Pumps.
O. Division 26 - Electrical.
1.03 REFERENCE STANDARDS
A. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having
Jurisdiction, Including All Applicable Amendments and Supplements.
1.04 PRODUCT INSTALLED BUT NOT FURNISHED UNDER THIS SECTION
A. Section 23 0913 - Instrumentation and Control Devices for HVAC:
1. Duct static pressure sensors
2. H2O Pressure Differential/Flow Switches
B. Section 28 4600 - Fire Detection and Alarm:
1. Smoke Detectors/Fire Stats
1.05 PRODUCTS NOT FURNISHED OR INSTALLED BUT INTEGRATED WITH THE WORK OF THIS
SECTION
A. General:
1. Coordination Meeting: The Installer furnishing the DDC network shall meet with the Installer(s) furnishing each of the following products to coordinate details of the interface between these products and the DDC network. The Owner or his designated representative shall be present at this meeting. Each Installer shall provide the Owner and all other Installers with details of the proposed interface, hardware and software identifiers for the interface points, network identifiers, wiring requirements, communication speeds, and required network accessories. The purpose of this meeting shall be to insure there are no unresolved issues regarding the integration of these products into the DDC network. Submittals for these products shall not be approved prior to the completion of this meeting.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 2
B. Communications with Third Party Equipment:
1. Any additional integral control systems included with the products integrated with the work of this section shall be furnished with a open protocol network interface for integration into the Direct Digital Control System described in this section.
1.06 DESCRIPTION
A. General: The control system shall consist of a high-speed, peer-to-peer network of DDC controllers and a web-based operator interface. Depict each mechanical system and building floor plan by a point-and-click graphic. A web server with a network interface card shall gather data from this system and generate web pages accessible through a conventional web browser on each PC connected to the network. Operators shall be able to perform all normal operator functions through the web browser interface.
B. The system shall directly control HVAC equipment as detailed on the drawings. Each zone controller shall provide occupied and unoccupied modes of operation by individual zone.
Furnish energy conservation features such as optimal start and stop, night setback, request-based logic, and demand level adjustment of setpoints as specified in the sequence.
C. System shall use open protocol communications to the operator workstation or web server and for communication between control modules.
1.07 APPROVED CONTROL SYSTEMS INSTALLERS
A. Bass Controls B. Inclusion on this list does not guarantee acceptance of products or installation. Control systems shall comply with the terms of this specification.
1. The Contractor shall use only operator workstation software, controller software, custom application programming language, and controllers from the corresponding manufacturer and product line unless the Owner approves use of multiple manufacturers.
1.08 QUALITY ASSURANCE
A. Installer and Manufacturer Qualifications
1. Installer shall have an established working relationship with the Control System Manufacturer.
2. Installer shall have successfully completed Control System Manufacturer's control system training. Upon request, Installer shall present record of completed training including course outlines.
B. Perform work in accordance with NFPA 70.
C. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories, Inc., as suitable for purpose specified and indicated.
1.09 CODES AND STANDARDS
A. Work, materials, and equipment shall comply with the most restrictive of local, state, and federal authorities' codes and ordinances or these plans and specifications. As a minimum, the installation shall comply with current editions in effect 30 days prior to receipt of bids of the following codes:
1. National Electric Code (NEC)
2. International Building Code (IBC)
a. Section 719 Ducts and Air Transfer Openings
b. Section 907 Fire Alarm and Detection Systems
c. Section 909 Smoke Control Systems
d. Chapter 28 Mechanical
3. International Mechanical Code (IMC)
4. ANSI/ASHRAE 135-2004: Data Communication Protocol for Building Automation and
Control Systems (BACNET)
1.10 SYSTEM PERFORMANCE
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 3
A. Performance Standards. System shall conform to the following minimum standards over network connections. Systems shall be tested using manufacturer's recommended hardware and software for operator workstation (server and browser for web-based systems).
1. Graphic Display. A graphic with 20 dynamic points shall display with current data within 10 sec.
2. Graphic Refresh. A graphic with 20 dynamic points shall update with current data within 8 sec. and shall automatically refresh every 15 sec.
3. Configuration and Tuning Screens. Screens used for configuring, calibrating, or tuning points, PID loops, and similar control logic shall automatically refresh within 6 sec.
4. Object Command. Devices shall react to command of a binary object within 2 sec.
Devices shall begin reacting to command of an analog object within 2 sec.
5. Alarm Response Time. An object that goes into alarm shall be annunciated at the workstation within 15 sec.
6. Program Execution Frequency. Custom and standard applications shall be capable of running as often as once every 5 sec. Select execution times consistent with the mechanical process under control.
7. Performance. Programmable controllers shall be able to completely execute DDC PID control loops at a frequency adjustable down to once per sec. Select execution times consistent with the mechanical process under control.
8. Multiple Alarm Annunciation. Each workstation on the network shall receive alarms within 5 sec of other workstations.
9. Reporting Accuracy. System shall report values with minimum end-to-end accuracy as listed below:
a. Space Temperature: +/- 1 degrees F
b. Ducted Air: +/- 1 degrees F
c. Outside Air: +/- 2 degrees F
d. Dew Point: +/- 3 degrees F
e. Water Temperature: +/- 1 degrees F
f. Delta-T: +/- 0.25 degrees F
g. Relative Humidity: +/- 5% RH
h. Water Flow: +/- 2% of full scale
i. Airflow (terminal): +/- 10% of full scale
1) Accuracy applies to 10% - 100% of scale
j. Airflow (measuring stations): +/- 5% of full scale
k. Air Pressure (ducts): +/- 0.1 in. w.g.
l. Air Pressure (space): +/- 0.01 in. w.g.
m. Water Pressure: +/- 2% of full scale
1) For both absolute and differential pressure
n. Electrical (A, V, W, Power Factor): +/- 1% of reading
1) Not including utility supplied meters
o. Carbon Monoxide (CO): +/- 5% of reading
p. Carbon Dioxide (CO2): +/- 50 ppm
10. Control Stability and Accuracy. Control loops shall maintain measured variable at setpoint within tolerances as listed below:
a. Air Pressure (0 to 6 in. w.g.): +/- 0.2 in. w.g.
b. Air Pressure (-0.1 to 0.1 in. w.g.): +/- 0.01 in. w.g.
c. Airflow: +/-10% of full scale
d. Space Temperature: +/- 2.0 degrees F
e. Duct Temperature: +/- 3 degrees F
f. Humidity: +/- 5% RH
g. Fluid Pressure (1 to 150 psi): +/- 1.5 psi
h. Fluid Pressure (0 to 50 in. w.g. differential): +/- 1.0 in. w.g.
1.11 SUBMITTALS
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 4
A. Direct Digital Control System Hardware
1. Complete bill of materials indicating quantity, manufacturer, model number, and relevant technical data of equipment to be used.
2. Manufacturer's description and technical data such as performance curves, product specifications, and installation and maintenance instructions for items listed below and for relevant items not listed below:
a. Direct digital controllers (controller panels)
b. Transducers and transmitters
c. Sensors (include accuracy data)
d. Actuators
e. Valves
f. Relays and switches
g. Control panels
h. Power supplies
i. Batteries
j. Operator interface equipment
k. Wiring
3. Wiring diagrams and layouts for each control panel. Show termination numbers.
4. Floor plan schematic diagrams indicating field sensor and controller locations.
5. Riser diagrams showing control network layout, communication protocol, and wire types.
B. Central System Hardware and Software
1. Complete bill of material indicating quantity, manufacturer, model number, and relevant technical data of equipment used.
2. Manufacturer's description and technical data such as product specifications and installation and maintenance instructions for items listed below and for relevant items furnished under this contract not listed below:
a. Central Processing Unit (CPU) or web server
b. Monitors
c. Keyboards
d. Power supplies
e. Battery backups
f. Interface equipment between CPU or server and control panels
g. Operating System software
h. Operator interface software
i. Color graphic software
j. Third-party software
3. Schematic diagrams of control, communication, and power wiring for central system installation. Show interface wiring to control system.
4. Network riser diagrams of wiring between central control unit and control panels.
C. Controlled Systems
1. Riser diagrams showing control network layout, communication protocol, and wire types.
2. Schematic diagram of each controlled system. Label control points with point names.
Graphically show locations of control elements.
3. Schematic wiring diagram of each controlled system. Label control elements and terminals. Where a control element is also shown on control system schematic, use the same name.
4. Instrumentation list (Bill of Materials) for each controlled system. List each control system element in a table. Show element name, type of device, manufacturer, model number, and product data sheet number.
5. Complete description of control system operation including sequences of operation.
Include and reference schematic diagram of controlled system. List I/O points and software points specified in Section 23 09 93. Indicate alarmed and trended points.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 5
D. Training Materials: Provide course outline and materials for each class at least six weeks before first class. Training shall be furnished via instructor-led sessions, computer-based training, or web-based training. Engineer will modify course outlines and materials if necessary to meet Owner's needs. Engineer will review and approve course outlines and materials at least three weeks before first class.
1.12 WARRANTY
A. Warrant work as follows:
1. Warrant labor and materials for specified control system free from defects for a period of 12 months after final acceptance. Control system failures during warranty period shall be adjusted, repaired, or replaced at no additional cost or reduction in service to Owner.
Respond during normal business hours within 24 hours of Owner's warranty service request.
2. Work shall have a single warranty date, even if Owner receives beneficial use due to early system start-up. If specified work is split into multiple contracts or a multi-phase contract, each contract or phase shall have a separate warranty start date and period.
3. Provide updates to operator workstation or web server software, project-specific software, graphic software, database software, and firmware that resolve Contractor-identified software deficiencies at no charge during warranty period. If available, Owner can purchase in-warranty service agreement to receive upgrades for functional enhancements associated with above-mentioned items. Do not install updates or upgrades without Owner's written authorization.
4. Exception: Contractor shall not be required to warrant reused devices except those that have been rebuilt or repaired. Installation labor and materials shall be warranted.
Demonstrate operable condition of reused devices at time of Engineer's acceptance.
1.13 OWNERSHIP OF PROPRIETARY MATERIAL
A. Project-specific software and documentation shall become Owner's property. This includes, but is not limited to:
1. Graphics
2. Record drawings
3. Database
4. Application programming code
5. Documentation
PART 2 PRODUCTS
2.01 MATERIALS
A. Use new products the manufacturer is currently manufacturing and selling for use in new installations. Do not use this installation as a product test site unless explicitly approved in writing by Owner. Spare parts shall be available for at least five years after completion of this contract.
2.02 COMMUNITCATION
A. Control products, communication media, connectors, repeaters, hubs, and routers shall comprise an open protocol internetwork.
B. Install new wiring and network devices as required to provide a complete and workable control network.
C. Each controller shall have a communication port for temporary connection to a laptop computer or other operator interface. Connection shall support memory downloads and other commissioning and troubleshooting operations.
D. Internetwork operator interface and value passing shall be transparent to internetwork architecture.
1. An operator interface connected to a controller shall allow the operator to interface with each internetwork controller as if directly connected. Controller information such as data, POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 6 status, and control algorithms shall be viewable and editable from each internetwork controller.
2. Inputs, outputs, and control variables used to integrate control strategies across multiple controllers shall be readable by each controller on the internetwork. Program and test all cross-controller links required to execute control strategies. An authorized operator shall be able to edit cross-controller links by typing a standard object address or by using a point-and-click interface.
E. Controllers with real-time clocks shall synchronize with the building management system.
System shall automatically synchronize system clocks daily from an operator-designated controller via the internetwork. If applicable, system shall automatically adjust for daylight saving and standard time.
F. System shall be expandable to at least twice the required input and output objects with additional controllers, associated devices, and wiring.
G. System shall support Web services data exchange with any other system that complies with XML (extensible markup language) and SOAP (simple object access protocol) standards specified by the Web Services Interoperability Organization (WS-I) Basic Profile 1.0 or higher.
Web services support shall as a minimum be provided at the workstation or web server level and shall enable data to be read from or written to the system.
1. System shall support Web services read data requests by retrieving requested trend data or point values (I/O hardware points, analog value software points, or binary value software points) from any system controller or from the trend history database.
2. System shall support Web services write data request to each analog and binary object that can be edited through the system operator interface by downloading a numeric value to the specified object.
3. For read or write requests, the system shall require user name and password authentication and shall support SSL (Secure Socket Layer) or equivalent data encryption.
4. System shall support discovery through a Web services connection or shall provide a tool available through the Operator Interface that will reveal the path/identifier needed to allow a third party Web services device to read data from or write data to any object in the system which supports this service.
2.03 OPERATOR INTERFACE
A. Operator Interface. Web server shall reside on high-speed network with building controllers.
Each standard browser connected to server shall be able to access all system information. In addition to the primary operator interface, the system shall include a secondary interface compatible with a locally available commercial wireless network and viewable on a commercially available wireless device such as a Wireless Access Protocol (WAP) enabled cellular telephone or personal digital assistant (PDA). This secondary interface may be text-based and shall provide a summary of the most important data. As a minimum, the following capabilities shall be provided through this interface:
1. An operator authentication system that requires an operator to log in before viewing or editing any data, and which can be configured to limit the privileges of an individual operator.
2. The ability to view and acknowledge any alarm in the system. Alarms or links to alarms shall be provided on a contiguous list so the operator can quickly view all alarms.
3. A summary page or pages for each piece of equipment in the system. This page shall include the current values of all critical I/O points and shall allow the operator to lock binary points on or off and to lock analog points to any value within their range.
4. Navigation links that allow the operator to quickly navigate from the home screen to any piece of equipment in the system, and then return to the home screen. These links may be arranged in a hierarchical fashion, such as navigating from the home screen to a particular building, then to a specific floor in the building, and then to a specific room or piece of equipment.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 7
B. Communication. Web server or workstation and controllers shall communicate using an open protocol communications language. Web server or workstation and control network backbone shall communicate using ISO 8802-3 (Ethernet) Data Link/Physical layer protocol.
C. Hardware. Each workstation or web server shall consist of the following:
1. Hardware Base. Industry-standard hardware shall meet or exceed DDC system manufacturer's recommended specifications and shall meet response times as specified.
Hard disk shall have sufficient memory to store system software, one year of data for trended points, and a system database at least twice the size of the existing database at system acceptance. Configure computers and network connections if multiple computers are required to meet specified memory and performance. Web server or workstations shall be IBM-compatible PCs with a minimum of:
a. Intel Pentium 2.66 GHz processor
b. 1 GB RAM
c. 40 GB hard disk providing data at 100 MB/sec
d. 48x CD-ROM drive
e. Serial, parallel, and network communication ports and cables required for proper system operation
2. Modem. Auto-dial modem and associated cables shall transmit over voice-grade telephone lines at a nominal 56,000 baud and shall provide communication between workstation or web server and remote buildings and workstations.
D. Operator Functions. Operator interface shall allow each authorized operator to execute the following functions as a minimum:
1. Log In and Log Out. System shall require user name and password to log in to operator interface.
2. Point-and-click Navigation. Operator interface shall be graphically based and shall allow operators to access graphics for equipment and geographic areas using point-and-click navigation.
3. View and Adjust Equipment Properties. Operators shall be able to view controlled equipment status and to adjust operating parameters such as setpoints, PID gains, on and off controls, and sensor calibration.
4. View and Adjust Operating Schedules. Operators shall be able to view scheduled operating hours of each schedulable piece of equipment on a weekly or monthly calendar-based graphical schedule display, to select and adjust each schedule and time period, and to simultaneously schedule related equipment. System shall clearly show exception schedules and holidays on the schedule display.
5. View and Respond to Alarms. Operators shall be able to view a list of currently active system alarms, to acknowledge each alarm, and to clear (delete) unneeded alarms.
6. View and Configure Trends. Operators shall be able to view a trend graph of each trended point and to edit graph configuration to display a specific time period or data range.
Operator shall be able to create custom trend graphs to display on the same page data from multiple trended points.
7. View and Configure Reports. Operators shall be able to run preconfigured reports, to view report results, and to customize report configuration to show data of interest.
8. Manage Control System Hardware. Operators shall be able to view controller status, to restart (reboot) each controller, and to download new control software to each controller.
9. Manage Operator Access. Typically, only a few operators are authorized to manage operator access. Authorized operators shall be able to view a list of operators with system access and of functions they can perform while logged in. Operators shall be able to add operators, to delete operators, and to edit operator function authorization. Operator shall be able to authorize each operator function separately.
E. System Software.
1. Operating System. Web server shall have an industry-standard professional-grade operating system. Acceptable systems include Microsoft Windows XP Pro, Red Hat Linux, POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 8 or Sun Solaris. Coordinate operating system type with the Owner.
2. System Graphics. Operator interface shall be graphically based and shall include at least one graphic per piece of equipment or occupied zone, graphics for each chilled water and hot water system, and graphics that summarize conditions on each floor of each building included in this contract. Indicate thermal comfort on floor plan summary graphics using dynamic colors to represent zone temperature relative to zone setpoint.
a. Functionality. Graphics shall allow operator to monitor system status, to view a summary of the most important data for each controlled zone or piece of equipment, to use point-and-click navigation between zones or equipment, and to edit setpoints and other specified parameters.
b. Animation. Graphics shall be able to animate by displaying different image files for changed object status.
c. Alarm Indication. Indicate areas or equipment in an alarm condition using color or other visual indicator.
d. Format. Graphics shall be saved in an industry-standard format such as BMP, JPEG, PNG, or GIF. Web-based system graphics shall be viewable on browsers compatible with World Wide Web Consortium browser standards. Web graphic format shall require no plug-in (such as HTML and JavaScript) or shall only require widely available no-cost plug-ins (such as Active-X and Macromedia Flash).
F. System Tools. System shall provide the following functionality to authorized operators as an integral part of the operator interface or as stand-alone software programs. If furnished as part of the interface, the tool shall be available from each workstation or web browser interface. If furnished as a stand-alone program, software shall be installable on standard IBM-compatible PCs with no limit on the number of copies that can be installed under the system license.
1. Automatic System Database Configuration. Each workstation or web server shall store on its hard disk a copy of the current system database, including controller firmware and software. Stored database shall be automatically updated with each system configuration or controller firmware or software change.
2. Controller Memory Download. Operators shall be able to download memory from the system database to each controller.
3. System Configuration. Operators shall be able to configure the system.
4. Online Help. Context-sensitive online help for each tool shall assist operators in operating and editing the system.
5. Security. System shall require a user name and password to view, edit, add, or delete data.
a. Operator Access. Each user name and password combination shall define accessible viewing, editing, adding, and deleting functions in each system application, editor, and object. Authorized operators shall be able to vary and deny each operator's accessible functions based on equipment or geographic location.
b. Automatic Log Out. Automatically log out each operator if no keyboard or mouse activity is detected. Operators shall be able to adjust automatic log out delay.
c. Encrypted Security Data. Store system security data including operator passwords in an encrypted format. System shall not display operator passwords.
6. System Diagnostics. System shall automatically monitor controller and I/O point operation.
System shall annunciate controller failure and I/O point locking (manual overriding to a fixed value).
7. Alarm Processing. System input and status objects shall be configurable to alarm on departing from and on returning to normal state. Operator shall be able to enable or disable each alarm and to configure alarm limits, alarm limit differentials, alarm states, and alarm reactions for each system object. Configure and enable alarm points as detailed on the drawings.
8. Alarm Messages. Alarm messages shall use an English language descriptor without acronyms or mnemonics to describe alarm source, location, and nature.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 9
9. Alarm Reactions. Operator shall be able to configure (by object) actions workstation or web server shall initiate on receipt of each alarm. As a minimum, workstation or web server shall be able to log, print, start programs, display messages, send e-mail, send page, and audibly annunciate.
10. Alarm Maintenance. Operators shall be able to view system alarms and changes of state chronologically, to acknowledge and delete alarms, and to archive closed alarms to the workstation or web server hard disk from each workstation or web browser interface.
11. Trend Configuration. Operator shall be able to configure trend sample or change of value (COV) interval, start time, and stop time for each system data object and shall be able to retrieve data for use in spreadsheets and standard database programs. Controller shall sample and store trend data and shall be able to archive data to the hard disk.
12. Object and Property Status and Control. Operator shall be able to view, and to edit if applicable, the status of each system object and property by menu, on graphics, or through custom programs.
13. Reports and Logs. Operator shall be able to select, to modify, to create, and to print reports and logs. Operator shall be able to store report data in a format accessible by standard spreadsheet and word processing programs.
14. Standard Reports. Furnish the following standard system reports:
a. Objects. System objects and current values filtered by object type, by status (in alarm, locked, normal), by equipment, by geographic location, or by combination of filter criteria.
b. Alarm Summary. Current alarms and closed alarms. System shall retain closed alarms for an adjustable period.
c. System shall log the following to a database or text file and shall retain data for an adjustable period:
1) Alarm History.
2) Trend Data. Operator shall be able to select trends to be logged.
3) Operator Activity. At a minimum, system shall log operator log in and log out, control parameter changes, schedule changes, and alarm acknowledgment and deletion. System shall date and time stamp logged activity.
15. Custom Reports. Operator shall be able to create custom reports that retrieve data, including archived trend data, from the system, that analyze data using common algebraic calculations, and that present results in tabular or graphical format. Reports shall be launched from the operator interface.
16. Graphics Generation. Graphically based tools and documentation shall allow Operator to edit system graphics, to create graphics, and to integrate graphics into the system.
Operator shall be able to add analog and binary values, dynamic text, static text, and animation files to a background graphic using a mouse.
17. Graphics Library. Complete library of standard HVAC equipment graphics shall include equipment such as chillers, boilers, air handlers, terminals, fan coils, and unit ventilators.
Library shall include standard symbols for other equipment including fans, pumps, coils, valves, piping, dampers, and ductwork. Library graphic file format shall be compatible with graphics generation tools.
18. Custom Application Programming. Operator shall be able to create, edit, debug, and download custom programs. System shall be fully operable while custom programs are edited, compiled, and downloaded. Programming language shall have the following features:
a. Language. Language shall be graphically based and shall use function blocks arranged in a logic diagram that clearly shows control logic flow. Function blocks shall directly provide functions listed below, and operators shall be able to create custom or compound function blocks.
b. Programming Environment. Tool shall provide a full-screen, cursor-and-mouse-driven programming environment that incorporates word processing features such as cut and paste. Operators shall be able to insert, add, modify, and delete custom
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 10 programming code, and to copy blocks of code to a file library for reuse in other control programs.
c. Independent Program Modules. Operator shall be able to develop independently executing program modules that can disable, enable and exchange data with other program modules.
d. Debugging and Simulation. Operator shall be able to step through the program observing intermediate values and results. Operator shall be able to adjust input variables to simulate actual operating conditions. Operator shall be able to adjust each step's time increment to observe operation of delays, integrators, and other time-sensitive control logic. Debugger shall provide error messages for syntax and for execution errors.
e. Conditional Statements. Operator shall be able to program conditional logic using compound Boolean (AND, OR, and NOT) and relational (EQUAL, LESS THAN, GREATER THAN, NOT EQUAL) comparisons.
f. Mathematical Functions. Language shall support floating-point addition, subtraction, multiplication, division, and square root operations, as well as absolute value calculation and programmatic selection of minimum and maximum values from a list of values.
g. Variables: Operator shall be able to use variable values in program conditional statements and mathematical functions.
1) Time Variables. Operator shall be able to use predefined variables to represent time of day, day of the week, month of the year, and date. Other predefined variables or simple control logic shall provide elapsed time in seconds, minutes, hours, and days. Operator shall be able to start, stop, and reset elapsed time variables using the program language.
2) System Variables. Operator shall be able to use predefined variables to represent status and results of Controller Software and shall be able to enable, disable, and change setpoints of Controller Software as described in Controller Software section.
G. Portable Operator's Terminal. Provide all necessary software to configure an IBM-compatible laptop computer for use as a Portable Operator's Terminal. Operator shall be able to connect configured Terminal to the system network or directly to each controller for programming, setting up, and troubleshooting.
2.04 CONTROLLER SOFTWARE
A. Building and energy management application software shall reside and operate in system controllers. Applications shall be editable through operator workstation, web browser interface, or engineering workstation.
B. Scheduling. System shall provide the following schedule options as a minimum:
1. Weekly. Provide separate schedules for each day of the week. Each schedule shall be able to include up to 5 occupied periods (5 start-stop pairs or 10 events).
2. Exception. Operator shall be able to designate an exception schedule for each of the next
365 days. After an exception schedule has executed, system shall discard and replace exception schedule with standard schedule for that day of the week.
3. Holiday. Operator shall be able to define 24 special or holiday schedules of varying length on a scheduling calendar that repeats each year.
C. System Coordination. Operator shall be able to group related equipment based on function and location and to use these groups for scheduling and other applications.
D. Binary and Analog Alarms. See Paragraph 2.3.F.7 (Alarm Processing).
E. Alarm Reporting. See Paragraph 2.3.F.9 (Alarm Reactions).
F. Remote Communication. System shall automatically contact operator workstation or server on receipt of critical alarms. If no network connection is available, system shall use a modem connection.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 11
G. Maintenance Management. System shall generate maintenance alarms when equipment exceeds adjustable runtime, equipment starts, or performance limits.
H. Sequencing. Application software shall sequence chillers, boilers, and pumps as detailed on the drawings.
I. PID Control. System shall provide direct- and reverse-acting PID (proportional-integral-derivative) algorithms. Each algorithm shall have anti-windup and selectable controlled variable, setpoint, and PID gains. Each algorithm shall calculate a time-varying analog value that can be used to position an output or to stage a series of outputs.
J. Staggered Start. System shall stagger controlled equipment restart after power outage.
Operator shall be able to adjust equipment restart order and time delay between equipment restarts.
K. Energy Calculations.
1. System shall accumulate and convert instantaneous power (kW) or flow rates (L/s [gpm]) to energy usage data.
2. System shall calculate a sliding-window average (rolling average). Operator shall be able to adjust window interval to 15 minutes, 30 minutes, or 60 minutes.
L. Anti-Short Cycling. Binary output objects shall be protected from short cycling by means of adjustable minimum on-time and off-time settings.
M. On and Off Control with Differential. System shall provide direct- and reverse-acting on and off algorithms with adjustable differential to cycle a binary output based on a controlled variable and setpoint.
N. Runtime Totalization. System shall provide an algorithm that can totalize runtime for each binary input and output. Operator shall be able to enable runtime alarm based on exceeded adjustable runtime limit.
2.05 CONTROLLERS
A. General. Provide Building Controllers (BC), Advanced Application Controllers (AAC), Application Specific Controllers (ASC), Smart Actuators (SA), and Smart Sensors (SS) as required to achieve performance specified.
B. Communication.
1. Service Port. Each controller shall provide a service communication port for connection to a Portable Operator's Terminal. Connection shall be extended to space temperature sensor ports where shown on drawings.
2. Signal Management. BC and ASC operating systems shall manage input and output communication signals to allow distributed controllers to share real and virtual object information and to allow for central monitoring and alarms.
3. Data Sharing. Each BC and AAC shall share data as required with each networked BC and AAC.
4. Stand-Alone Operation. Each piece of equipment specified shall be controlled by a single controller to provide stand-alone control in the event of communication failure. All I/O points specified for a piece of equipment shall be integral to its controller. Provide stable and reliable stand-alone control using default values or other method for values normally read over the network.
C. Environment. Controller hardware shall be suitable for anticipated ambient conditions.
1. Controllers used outdoors or in wet ambient conditions shall be mounted in waterproof enclosures and shall be rated for operation at -29°C to 60°C (-20°F to 140°F).
2. Controllers used in conditioned space shall be mounted in dust-protective enclosures and shall be rated for operation at 0°C to 50°C (32°F to 120°F).
D. Keypad. Provide a local keypad and display for each BC and AAC. Operator shall be able to use keypad to view and edit data. Keypad and display shall require password to prevent unauthorized use. If the manufacturer does not normally provide a keypad and display for each
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 12
BC and AAC, provide the software and any interface cabling needed to use a laptop computer as a Portable Operator's Terminal for the system.
E. Real-Time Clock. Controllers that perform scheduling shall have a real-time clock.
F. Serviceability.
1. Controllers shall have diagnostic LEDs for power, communication, and processor.
2. Wires shall be connected to a field-removable modular terminal strip or to a termination card connected by a ribbon cable.
3. Each BC and AAC shall continually check its processor and memory circuit status and shall generate an alarm on abnormal operation. System shall continuously check controller network and generate alarm for each controller that fails to respond.
G. Memory.
1. Controller memory shall support operating system, database, and programming requirements.
2. Each BC and AAC shall retain BIOS and application programming for at least 72 hours in the event of power loss.
3. Each ASC and SA shall use nonvolatile memory and shall retain BIOS and application programming in the event of power loss. System shall automatically download dynamic control parameters following power loss.
H. Immunity to Power and Noise. Controllers shall be able to operate at 90% to 110% of nominal voltage rating and shall perform an orderly shutdown below 80% nominal voltage. Operation shall be protected against electrical noise of 5 to 120 Hz and from keyed radios up to 5 W at 1 m (3 ft).
I. Transformer. ASC power supply shall be fused or current limiting and shall be rated at a minimum of 125% of ASC power consumption.
2.06 INPUT AND OUTPUT INTERFACE
A. General. Hard-wire input and output points to BCs, AACs, ASCs, or SAs.
B. Protection. Shorting an input or output point to itself, to another point, or to ground shall cause no controller damage. Input or output point contact with up to 24 V for any duration shall cause no controller damage.
C. Binary Inputs. Binary inputs shall monitor the on and off signal from a remote device. Binary inputs shall provide a wetting current of at least 12 mA and shall be protected against contact bounce and noise. Binary inputs shall sense dry contact closure without application of power external to the controller.
D. Pulse Accumulation Inputs. Pulse accumulation inputs shall conform to binary input requirements and shall accumulate up to 10 pulses per second.
E. Analog Inputs. Analog inputs shall monitor low-voltage (0-10 Vdc), current (4-20 mA), or resistance (thermistor or RTD) signals. Analog inputs shall be compatible with and field configurable to commonly available sensing devices.
F. Binary Outputs. Binary outputs shall send an on-or-off signal for on and off control. Building Controller binary outputs shall have three-position (on-off-auto) override switches and status lights. Outputs shall be selectable for normally open or normally closed operation.
G. Analog Outputs. Analog outputs shall send a modulating 0-10 Vdc or 4-20 mA signal as required to properly control output devices. Each Building Controller analog output shall have a two-position (auto-manual) switch, a manually adjustable potentiometer, and status lights.
Analog outputs shall not drift more than 0.4% of range annually.
H. Tri-State Outputs. Control three-point floating electronic actuators without feedback with tri-state outputs (two coordinated binary outputs). Tri-State outputs may be used to provide analog output control in zone control and terminal unit control applications such as VAV terminal units, duct-mounted heating coils, and zone dampers.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 13
I. Universal Inputs and Outputs. Inputs and outputs that can be designated as either binary or analog in software shall conform to the provisions of this section that are appropriate for their designated use.
2.07 POWER SUPPLIES AND LINE FILTERING
A. Power Supplies. Control transformers shall be UL listed. Furnish Class 2 current-limiting type or furnish over-current protection in primary and secondary circuits for Class 2 service in accordance with NEC requirements. Limit connected loads to 80% of rated capacity.
1. DC power supply output shall match output current and voltage requirements. Unit shall be full-wave rectifier type with output ripple of 5.0 mV maximum peak-to-peak. Regulation shall be 1.0% line and load combined, with 100-microsecond response time for 50% load changes. Unit shall have built-in over-voltage and over-current protection and shall be able to withstand 150% current overload for at least three seconds without trip-out or failure.
a. Unit shall operate between 0°C and 50°C (32°F and 120°F). EM/RF shall meet FCC
Class B and VDE 0871 for Class B and MILSTD 810C for shock and vibration.
b. Line voltage units shall be UL recognized and CSA listed.
B. Power Line Filtering.
1. Provide internal or external transient voltage and surge suppression for workstations and controllers. Surge protection shall have:
2. Dielectric strength of 1000 V minimum
3. Response time of 10 nanoseconds or less
4. Transverse mode noise attenuation of 65 dB or greater
5. Common mode noise attenuation of 150 dB or greater at 40-100 Hz
2.08 AUXILIARY CONTROL DEVICES
A. Local Control Panels.
1. Indoor control panels shall be fully enclosed NEMA 1 construction with hinged door key-lock latch and removable sub-panels. A common key shall open each control panel and sub-panel.
2. Prewire internal and face-mounted device connections with color-coded stranded conductors tie-wrapped or neatly installed in plastic troughs. Field connection terminals shall be UL listed for 600 V service, individually identified per control and interlock drawings, with adequate clearance for field wiring.
3. Each local panel shall have a control power source power switch (on-off) with overcurrent protection.
2.09 WIRING AND RACEWAYS
A. General. Provide copper wiring, plenum cable, and raceways as specified in applicable sections of Division 26.
B. Insulated wire shall use copper conductors and shall be UL listed for 90°C (200°F) minimum service.
2.10 FIBER OPTIC CABLE SYSTEM
A. Optical Cable. Optical cables shall be duplex 900 mm tight-buffer construction designed for intra-building environments. Sheath shall be UL listed OFNP in accordance with NEC Article
770. Optical fiber shall meet the requirements of FDDI, ANSI X3T9.5 PMD for 62.5/125mm.
B. Connectors. Field terminate optical fibers with ST type connectors. Connectors shall have ceramic ferrules and metal bayonet latching bodies.
PART 3 EXECUTION
3.01 EXAMINATION
A. Thoroughly examine project plans for control device and equipment locations. Report discrepancies, conflicts, or omissions to Architect or Engineer for resolution before starting
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 14 rough-in work.
B. Inspect site to verify that equipment can be installed as shown. Report discrepancies, conflicts, or omissions to Engineer for resolution before starting rough-in work.
C. Examine drawings and specifications for work of others. Report inadequate headroom or space conditions or other discrepancies to Engineer and obtain written instructions for changes necessary to accommodate Section 23 0923 work with work of others. Controls Contractor shall perform at his expense necessary changes in specified work caused by failure or neglect to report discrepancies.
3.02 PROTECTION
A. Controls Contractor shall protect against and be liable for damage to work and to material caused by Contractor's work or employees.
B. Controls Contractor shall be responsible for work and equipment until inspected, tested, and accepted. Protect material not immediately installed. Close open ends of work with temporary covers or plugs during storage and construction to prevent entry of foreign objects.
3.03 COORDINATION
1. Assist in coordinating space conditions to accommodate the work of each trade where work will be installed near or will interfere with work of other trades. If installation without coordination causes interference with work of other trades, Contractor shall correct conditions without extra charge.
2. Coordinate and schedule work with other work in the same area and with work dependent upon other work to facilitate mutual progress.
B. Test and Balance.
1. Provide Test and Balance Contractor a single set of necessary tools to interface to control system for testing and balancing.
2. Train Test and Balance Contractor to use control system interface tools.
3. Provide a qualified technician to assist with testing and balancing the first 20 terminal units.
4. Test and Balance Contractor shall return tools undamaged and in working condition at completion of testing and balancing.
C. Life Safety.
1. Duct smoke detectors required for air handler shutdown are provided under Division 28.
Interlock smoke detectors to air handlers for shutdown as indicated on drawings.
2. Smoke dampers and actuators required for duct smoke isolation are provided under Division 23. Interlock smoke dampers to air handlers as indicated on drawings.
3. Fire and smoke dampers and actuators required for fire-rated walls are provided under Division 23. Fire and smoke damper control is provided under Division 28.
D. Coordination with Other Controls. Integrate with and coordinate controls and control devices furnished or installed by others as follows.
1. Communication media and equipment shall be provided as specified.
2. Each supplier of a controls product shall configure, program, start up, and test that product to meet the sequences of operation detailed on the drawings.
3. Coordinate and resolve incompatibility issues that arise between control products provided under this section and those provided under other sections or divisions of this specification.
4. Controls Contractor shall be responsible for integration of control products provided by multiple suppliers regardless of where integration is described within the contract documents.
3.04 GENERAL WORKMANSHIP
A. Install equipment, piping, and wiring or raceway horizontally, vertically, and parallel to walls wherever possible.
POOL BOILER REPLACEMENT 252068 MARCH 21, 2025
DIGITAL CONTROL (DDC)
SYSTEMS FOR HVAC
23 09 25 - 15
B. Provide sufficient slack and flexible connections to allow for piping and equipment vibration isolation.
C. Install equipment in readily accessible locations as defined by National Electrical Code (NEC) Chapter 1 Article 100 Part A.
D. Verify wiring integrity to ensure continuity and freedom from shorts and ground faults.
E. Equipment, installation, and wiring shall comply with industry specifications and standards and local codes for performance, reliability, and compatibility.
3.05 FILED QUALITY CONTROL
A. Work, materials, and equipment shall comply with rules and regulations of applicable local, state, and federal codes and ordinances.
B. Continually monitor field installation for code compliance and workmanship quality.
C. Contractor shall arrange for work inspection by local or state authorities having jurisdiction over the work.
3.06 WIRING
A. Control and interlock wiring and installation shall comply with national and local electrical codes, Division 26, and manufacturer's…