Carrier Specifications for Parfet RTU Replacement Project 2025.pdf

PDF 596 KB Posted

Attached to
Parfet Building RTU Replacement 2025
Solicitation number
25-15499R-FM
Issued by
Jefferson County, Colorado

About this file

This document is a proposal from Carrier West for Jefferson County Facilities, identified by Proposal Number 0725CZSI0905, detailing a comprehensive HVAC equipment installation and temperature control project. The proposal involves the startup and installation of twelve (12) Rooftop Units (RTUs), specifically WeatherMaster Gas/Electric Rooftop units with high gas heat, 5-ton capacity, two-stage cooling, and various advanced features like an Ultra Low Leak Temperature Economizer and Condensate Overflow Switch. The project includes custom curb installations, and the units will be integrated with an existing Carrier i-Vu Web Building Automation System (BAS).

The technical specifications outline specific equipment requirements, including factory single zone RTUs, BACnet controllers for monitoring and control, wire space temperature sensors, and detailed wiring specifications. The proposal indicates that duct smoke detector shutdown interlocks will be provided by others, and all wiring above drop ceilings must use plenum-rated cable, with mechanical room wiring to be installed in EMT conduit. The equipment includes features like high static-vane axial fans, AI/Cu condenser and evaporator coils, and SystemVu™ controls with BACnet capability, suggesting a comprehensive and technologically advanced HVAC solution for the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Startup on (12) RTU by Carrier West

(12) GPS-FC48-AC Installation by Carrier West

Temperature Controls

Proposal General Notes:

• Existing Carrier i-Vu Web Building Automation System (BAS).

• WHERE EXISTING SYSTEMS ARE CALLED OUT, IT IS ASSUMED THAT SAID SYSTEMS ARE IN FUNCTIONAL CONDITION AND HAVE NOT BEEN REPLACED BY OR SUPPLEMENTED WITH OTHER MANUFACTURERS’ CONTROL SYSTEMS.

Building Automation Equipment:

• (12) Factory Single Zone RTU

• Factory AHU provided by others with BACnet Controller that provides monitoring and control of the unit

• Wire space temperature sensor

• Wire duct smoke detector shutdown interlock to unit (provided, installed, powered, supervised by others)

• All wiring above drop ceilings and in accessible areas to be exposed plenum rated cable.

• All Mechanical Room wiring to be in EMT conduit.

wyates Text Box by Carrier wyates Text Box Alternate Pricing wyates Text Box wyates Text Box

• Connect new equipment to the existing i-Vu wyates Text Box

• Contractor shall Install wire space temp sensors wyates Text Box wyates Text Box independently supported with appropriate hangers.

Slide 1