C_1VIANG VD.pdf
PDF 12 KB Posted
- Attached to
- Virgin Islands Renewable Energy Systems Federal contract opportunity
- Solicitation number
- W50S93-20-B-5002-0001
About this file
This document contains a voltage drop calculation for a photovoltaic system project and the related federal contract opportunity solicitation. The voltage drop calculation specifies wire sizes and lengths for three PV circuits, with circuit one requiring 3/0 aluminum wire over 151 feet, circuit two requiring 1/0 aluminum wire over 220 feet, and circuit three requiring 1/0 aluminum wire over 574 feet. The related solicitation is for renewable energy systems in the U.S. Virgin Islands and seeks design and installation services. Offerors must submit proposals to the Department of the Army Michigan Army National Guard by September 30, 2020. The solicitation was amended to include additional design specifications and points of contact for site visits on St. Croix.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 160861.20 - New Wind Turbine - Air National Guard Station - USVI - Geotechnical Report.pdf | ||
| G-001-Layout1.pdf | ||
| D_FAA FORMS.pdf | ||
| C_62.5kW PV.pdf | ||
| A1_WS-0001_P10-20.pdf | ||
| Structural.pdf | ||
| FAA 7460_Response.pdf | ||
| C_Glare Report.pdf | ||
| W50S93-20-B-5002-0001.pdf | ||
| VIANG Renewable Energy_SPECS.pdf | ||
| A5_PanelClaw.pdf | ||
| A_CUT SHEETS.pdf | ||
| C_20kW Wind Turbine.pdf | ||
| Electrical.pdf | ||
| C_1CUT SHEETS.pdf | ||
| A2_sunmodule-plus-mono-5-busbar-datasheet.pdf | ||
| A3_IQ6-IQ6-plus_DS_EN-US.pdf | ||
| SANGB Base Access List.xlsx | XLSX spreadsheet | |
| A4_S-5.pdf | ||
| New Wind Turbine USVI - Geotechnical Report.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VOLTAGE DROP (BUSSMANN METHOD)
PROJECT : VIANG PV System
JOB NO. : 1160634
DONE BY : Clifford
DATE : 9/19/2017
COMMENTS :
VOLTAGE = 208
PHASE = 3
POWER FACTOR (%) = 90
WIRE TYPE ( C / A ) : C
CONDUIT TYPE ( S / NM ) : NM
NAME
AMPS OR VA *
(AMPS) (VA)
WIRE
SIZE
LENGTH
(FEET)
Runs
TABLE
FACTOR
VD %VD
PV-110 39760 3/0 225 1 151 3.75 1.80
3080 10 228 1 1908 3.72 1.79
Total 1 3.59
PV-100 13440 1/0 369 1 220 3.03 1.46
3080 10 293 1 1908 4.78 2.30
Total 1 3.75
PV-107 12320 1/0 574 1 220 4.32 2.08
3080 10 176 1 1908 2.87 1.38
Total 1 3.46
* - YOU CAN ENTER EITHER AMPS OR VA. IF YOU HAVE VALUES FOR BOTH, THE PROGRAM WILL USE THE (AMPS) VALUE.
NOTE: FOR PARALLEL SETS OF CONDUCTORS, YOU MUST DIVIDE THE TOTAL AMPERAGE BY THE NUMBER OF SETS OF
CONDUCTORS TO GET THE (AMPS) VALUE TO USE IN THE TABLE ABOVE.