A5_PanelClaw.pdf

PDF 328 KB Posted

Attached to
Virgin Islands Renewable Energy Systems Federal contract opportunity
Solicitation number
W50S93-20-B-5002-0001
Issued by
Department of the Army Michigan Army National Guard

About this file

This document contains specifications for solar panel mounting systems and details for a related federal contract opportunity. The specifications cover PanelClaw mounting systems for roof slopes up to 70 degrees, wind speeds up to 150 mph, building heights up to 60 feet, and setbacks as low as 3 feet. Standard ballast block sizes and array layout guidelines are also provided. The related federal contract opportunity is a solicitation from the Department of the Army Michigan Army National Guard for renewable energy systems in the Virgin Islands. Responses are due on August 28, 2020 and the contract is to be awarded by September 30, 2020. The opportunity involves designing and installing solar photovoltaic systems at various sites on St. Croix and St. Thomas in the U.S. Virgin Islands.

View the file

Other files for this federal contract opportunity

Other files attached to Virgin Islands Renewable Energy Systems, newest first.
File Type Posted
C_20kW Wind Turbine.pdf PDF
Electrical.pdf PDF
FAA 7460_Response.pdf PDF
C_Glare Report.pdf PDF
W50S93-20-B-5002-0001.pdf PDF
VIANG Renewable Energy_SPECS.pdf PDF
A_CUT SHEETS.pdf PDF
160861.20 - New Wind Turbine - Air National Guard Station - USVI - Geotechnical Report.pdf PDF
G-001-Layout1.pdf PDF
D_FAA FORMS.pdf PDF
C_62.5kW PV.pdf PDF
C_1VIANG VD.pdf PDF
A1_WS-0001_P10-20.pdf PDF
Structural.pdf PDF
C_1CUT SHEETS.pdf PDF
A2_sunmodule-plus-mono-5-busbar-datasheet.pdf PDF
A3_IQ6-IQ6-plus_DS_EN-US.pdf PDF
SANGB Base Access List.xlsx XLSX spreadsheet
A4_S-5.pdf PDF
New Wind Turbine USVI - Geotechnical Report.pdf PDF
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

© 2016 PanelClaw, Inc. All Rights Reserved.

PA R T N E RS H I P | We h e l p y o u w i n S E R V I C E | A t o Z p ro j e c t s u p p o r t R E L I A B I L I T Y | M a d e t o o u t l a s t

Polar Bear® III HD SPECIFICATIONS and LAYOUT GUIDELINES

10 Degree 5 Degree

Polar Bear® III HD 5˚ & 10˚ Specifications

Roof Loading 2.5 psf to 12 psf (12.2 kg/m² to 58.6 kg/m²) including racking, modules and ballast

Roof Slope 7˚ max slope (1.5/12 pitch) in all directions

Wind Speed 150 mph (193 km/h) – 3 second gust per ASCE 7-05 (190 mph per ASCE 7-10) Higher wind speeds require PanelClaw engineering review

Exposures B and C D upon request

Seismic Design Category

A, B, C, D Category D may require mechanical attachments, or as required by the permitting authority

Maximum Building Height

60 ft (18.3 m), measured from grade Heights above 60 ft generally require mechanical attachments; check with PanelClaw engineering

Standard Setback 4 ft (1.2 m) Set backs as low as 3 ft (0.9 m) are possible, but require PanelClaw engineering review

Roof Material EPDM, TPO, PVC, Mod Bitumen, Asphalt, Coal Tar, Foam, Concrete, and Gravel

Fire Certification Requirements

System Fire Rating Class A with Type 1 and Type 2 modules No additional components required for compliance

Ballast Block Size Nominal 2”x8”x16”, 3”x8”x16”, or 4”x8”x16” blocks Actual dimensions: 1 5/8” or 2 5/8” or 3 5/8”x7 5/8”x15 5/8” with +/- 1/8” tolerance

2 v1

Array Layout Guidelines for 5˚ & 10˚

Maximum array row length - 150’ | Maximum array column length - 150’

Maintain a minimum of 6” clearance from obstructions and separate sub arrays

Diagonal connections between arrays not allowed