Bid_#2027-12_PD_Drone_Plans_20260615.pdf
PDF 6 MB Posted
- Attached to
- Police Department Drone Installation
- Solicitation number
- Bid # 2027-12
- Issued by
- Mclean County, Illinois
About this file
This is a project description and design document set for the City of Bloomington, Illinois Police Department Drone Installation project (Bid #2027-12). The project involves the structural, electrical, and technology infrastructure required to support drone dock and radio antenna installations on the existing police department building roof located at 305 Southeast Street, Bloomington, Illinois 61701. The work includes construction of an 8-inch concrete masonry unit (CMU) wall with bond beams and vertical reinforcement, installation of a pre-manufactured drone docking station, radio antenna mounting structure with non-penetrating rooftop supports, electrical power and data infrastructure including new panelboard EM-2 fed from existing emergency panel EM-1, conduit routing for power and data connections, and associated roof membrane modifications with flashing details. The sealed bid submission deadline is Friday, August 28, 2026, at 11:30 am CST via the City's e-Procurement Portal. The project includes structural observations per International Building Code 2018 requirements, with special inspection provisions for masonry construction at Level 2 compliance per TMS 602 standards.
The contract is estimated to exceed $50,000 in public funds and therefore requires a project labor agreement unless the City determines such an agreement would not advance its interests in cost, efficiency, quality, safety, timeliness, skilled labor force stability, and support for minority-owned or female-owned businesses. The design documents indicate electrical work includes provision of new 50-amp, three-phase breakers for dock and antenna circuits, installation of weather-resistant duplex receptacles and disconnects on the roof, new surge protective devices, and data cabling infrastructure using Category 6 UTP cabling routed through conduit to the existing telecommunications room 209. All masonry materials, reinforcement, grout, and post-installed anchors must meet specified standards with documented material certifications and compressive strength verification. The contractor is responsible for all means, methods, construction sequencing, coordination with other trades, verification of dimensions against existing conditions, and compliance with all applicable building codes and governmental regulations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Exp Date:
Seal Date: 06/15/2026
11/30/2027
Exp Date:
Seal Date: 06/15/2026
11/30/2027
ELECTRICAL
TECHNOLOGY DETAILST-401
jftacek Placed Image jftacek Placed Image jftacek Placed Image jftacek Typewriter
CONFIDENTIAL - SECURITY MEASURES
DESIGN LOAD SCHEDULE (IBC 2018)
ITEMS
LEVEL
DEAD LOAD (PSF)
ROOFING/
INSULATION/ MEP CEILING
FLOOR/
FRAMING
SNOW LIVE LOAD
ROOF (PER EXISTING DWGS) 30.0 100.0
RISK CATEGORY: IV
WIND LOADS (APPURTENANCES):
1. BASIC WIND SPEED (3 SEC. GUST), V = 119 MPH
2. WIND DIRECTIONALITY FACTOR, Kd 0.85 (DOCK), 1.00 (ANTENNA)
3. WIND EXPOSURE CATEGORY = C
4. TOPOGRAPHIC FACTOR, Kz 1.114 (DOCK), 1.142 (ANTENNA)
5. GUST EFFECT FACTOR, GCr = 1.9 (LATERAL), 1.5 (UPLIFT)
6. INTERNAL PRESSURE COEFFICIENT: ±0.18
7. ROOF COMPONENTS AND CLADDING SEE SCHEDULE
MEAN ROOF HEIGHT:
ROOF: 52 FT
ROOF SNOW LOAD:
1. GROUND SNOW LOAD (Pg) = 30 PSF
2. EXPOSURE FACTOR (Ce) = 0.90
3. SNOW IMPORTANCE FACTOR (Is) = 1.20
4. THERMAL FACTOR (Ct) = 1.00
5. FLAT ROOF SNOW LOAD (Pf) = 24.0
SEISMIC LOADS (APPURENANCES):
1. MAPPED SPECTRAL RESPONSE ACCELERATION SS = 0.147 S1 = 0.082
2. DESIGN SPECTRAL ACCELERATION FOR SHORT PERIODS SDS = 0.157
3. DESIGN SPECTRAL ACCELERATION FOR 1-SEC PERIOD SD1 = 0.131
4. SITE CLASSIFICATION D
5. IMPORTANCE FACTOR 1.250
6. SEISMIC DESIGN CATEGORY C
APPURTENANCES
1. DRONE DOCK 240 LBS
2. ANTENNA, POLE AND BASE PLATE (ASSUMED) 31 LBS
6.0ROOF (FOR DESIGN) 24.0 20.0
NOT STATED
7.0
2.5
61.0
DESIGN CRITERIA
A. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE INTERNATIONAL BUILDING
CODE 2018, LATEST EDITION, WITH THE SPECIFICATION AND WITH THE REGULATIONS OF
ALL GOVERNMENTAL AGENCIES HAVING JURISDICTION.
B. ALL APPLICABLE DESIGN LOADS AND INFORMATION USED IN THE DESIGN OF THE
STRUCTURE ARE LOCATED ON THIS SHEET.
C. ALL GENERAL STRUCTURAL NOTES CONTAINING "THE MOST CURRENT EDITION" REFERS
TO THE LATEST EDITION ADOPTED BY THE BUILDING CODE MENTIONED ABOVE.
GENERAL CONSTRUCTION
A. THIS PROJECT HAS BEEN DESIGNED FOR THE WEIGHTS OF MATERIALS INDICATED IN THE
DESIGN DATA. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ALLOWABLE
CONSTRUCTION LOADS AND TO PROVIDE PROPER DESIGN AND CONSTRUCTION OF
FALSEWORK, FORMWORK, STAGING, BRACING, SHEETING, SHORING, ETC.
B. PRIOR TO CONSTRUCTION, CONTRACTOR SHALL VERIFY ALL STRUCTURAL ELEVATIONS
AND DIMENSIONS WITH EXISTING CONDITIONS AND WITH OTHER PROJECT DRAWINGS;
COORDINATE LOCATION OF SLEEVES AND OPENINGS THROUGH THE STRUCTURE, SLAB
DEPRESSIONS, FLOOR DRAINS, INSERTS, AND OTHER RELATED ITEMS.
C. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CORRECTNESS OF DIMENSIONS
OR QUANTITIES AND FOR THE FITTING TO OTHER WORK; FOR WORK TO BE CONFIRMED
AND CORRELATED AT THE SITE; FOR INFORMATION PERTAINING TO THE FABRICATION
PROCEDURE OR TO THE MEANS, METHODS, TECHNIQUES, SEQUENCES AND
PROCEDURES OF CONSTRUCTION; AND FOR THE COORDINATION OF STRUCTURAL WORK
WITH THE WORK OF ALL OTHER TRADES. THE VERIFICATION OF THE PHYSICAL
INTERRELATIONSHIPS OF ELEMENTS OF THE WORK FROM PLANS AND SPECIFICATIONS
AND IN THE FIELD IS THE CONTRACTOR'S SOLE RESPONSIBILITY. REVIEW OF
CONTRACTOR'S SUBMISSIONS DOES NOT RELIEVE CONTRACTOR FROM THESE
RESPONSIBILITIES.
D. HOLES OF ANY SIZE SHALL NOT BE DRILLED INTO STRUCTURAL MEMBERS, EXCEPT AS
SHOWN IN THE DRAWINGS, WITHOUT THE ACCEPTANCE OF THE ENGINEER.
E. ALL CONCRETE MASONRY UNITS SHALL BE FILLED SOLID WITH GROUT.
MASONRY
A. ENGINEERED MASONRY SHALL BE FABRICATED AND CONSTRUCTED IN ACCORDANCE WITH THE
FOLLOWING:
"BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" (ACI 530, LATEST EDITION)
"TECHNICAL NOTES ON BRICK CONSTRUCTION" BY THE BRICK INSTITUTE OF AMERICA.
B. MINIMUM COMPRESSIVE STRENGTH OF MASONRY UNITS (ASTM C90):
HOLLOW AND/OR SOLID UNITS 2600 PSI
C. MINIMUM COMPRESSIVE STRENGTH (F'c) AT 28 DAYS:
GROUT PER ASTM C1019 2250 PSI
D. THE DESIGN COMPRESSIVE STRENGTH OF MASONRY (f'm) BASED ON THE COMPRESSIVE
STRENGTH OF MASONRY UNITS AND MORTAR TO BE USED ARE AS FOLLOWS:
CONCRETE MASONRY f'm = 2250 PSI
E. FOR ALL WALLS AS INDICATED ON THE STRUCTURAL DRAWINGS THE MORTAR SHALL BE TYPE S
AND ONLY NORMAL WEIGHT UNITS SHALL BE USED.
F. MASONRY REINFORCEMENT SHALL BE AS FOLLOWS:
BOND BEAMS AND ALL VERTICAL REINFORCEMENT:
DEFORMED BARS - ASTM A615 GRADE 60
BED JOINT REINFORCEMENT:
PARALLEL WIRES - ASTM A82 WITH MINIMUM YIELD STRESS OF 70.0 KSI AT 16" OC MAX.
CONTINUOUS HORIZONTAL WIRE TIES SHALL BE PLACED SUCH THAT THE DISTANCE BETWEEN
THE FACE OF THE MASONRY WALL AND THE PARALLEL WIRE IS NOT MORE THAN ONE INCH.
FOR SINGLE AND DOUBLE WYTHE BLOCK PROVIDE:
(2)#9 GAGE DEFORMED WIRES,(1) AT EACH FACE SHELL, LADDER TIED.
G. ALL PRE-INSTALLED AND POST-INSTALLED ANCHORS TO BE LOCATED IN CMU WALLS SHALL BE
ANCHORED INTO FULLY GROUTED CELLS WITHIN A 12" RADIUS.
H. TYPICAL VERTICAL WALL REINFORCING AND SPACING SHALL BE PROVIDE AS INDICATED ON THE
DRAWINGS AND/OR SCHEDULES. GROUT SOLID ALL CELLS.
I. UNLESS OTHERWISE NOTED, ALL BOND BEAMS SHALL HAVE (2) #5 BARS CONTINUOUS.
J. DELIVERY, STORAGE, AND HANDLING
STORE MASONRY UNITS ON ELEVATED PLATFORMS IN A DRY LOCATION. IF UNITS ARE NOT
STORED IN AN ENCLOSED LOCATION, COVER TOPS AND SIDES OF STACKS WITH
WATERPROOF SHEETING, SECURELY TIED. IF UNITS BECOME WET, DO NOT INSTALL UNTIL
THEY ARE DRY.
STORE CEMENTITIOUS MATERIALS ON ELEVATED PLATFORMS, UNDER COVER, AND IN A DRY
LOCATION. DO NOT USE CEMENTITIOUS MATERIALS THAT HAVE BECOME DAMP.
STORE AGGREGATES WHERE GRADING AND OTHER REQUIRED CHARACTERISTICS CAN BE
MAINTAINED AND CONTAMINATION AVOIDED.
DELIVER PREBLENDED, DRY MORTAR MIX IN MOISTURE-RESISTANT CONTAINERS. STORE
PREBLENDED, DRY MORTAR MIX IN DELIVERY CONTAINERS ON ELEVATED PLATFORMS IN A
DRY LOCATION OR IN COVERED WEATHERPROOF DISPENSING SILOS.
STORE MASONRY ACCESSORIES, INCLUDING METAL ITEMS, TO PREVENT CORROSION AND
ACCUMULATION OF DIRT AND OIL.
K. PROTECTION OF MASONRY: DURING CONSTRUCTION, COVER TOPS OF WALLS, PROJECTIONS,
AND SILLS WITH WATERPROOF SHEETING AT END OF EACH DAY'S WORK. COVER PARTIALLY
COMPLETED MASONRY WHEN CONSTRUCTION IS NOT IN PROGRESS.
L. COLD-WEATHER REQUIREMENTS: DO NOT USE FROZEN MATERIALS OR MATERIALS
MIXED OR COATED WITH ICE OR FROST. DO NOT BUILD ON FROZEN SUBSTRATES. REMOVE
AND REPLACE UNIT MASONRY DAMAGED BY FROST OR BY FREEZING CONDITIONS. COMPLY
WITH COLD-WEATHER CONSTRUCTION REQUIREMENTS CONTAINED IN
TMS 602/ACI 530.1/ASCE 6.
COLD-WEATHER CLEANING: USE LIQUID CLEANING METHODS ONLY WHEN AIR
TEMPERATURE IS 40 DEG F (4 DEG C) AND HIGHER AND WILL REMAIN SO UNTIL MASONRY
HAS DRIED, BUT NOT LESS THAN SEVEN DAYS AFTER COMPLETING CLEANING.
M. HOT-WEATHER REQUIREMENTS: COMPLY WITH HOT-WEATHER CONSTRUCTION
REQUIREMENTS CONTAINED IN TMS 602/ACI 530.1/ASCE 6.
STRUCTURAL OBSERVATIONS
A. SPECIAL INSPECTOR SHALL PROVIDE STRUCTURAL OBSERVATIONS IN ACCORDANCE
WITH THE SCHEDULE ON THE SPECIAL INSPECTIONS PAGE. THESE OBSERVATIONS DO
NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR OTHER INSPECTIONS OR SPECIAL
INSPECTIONS INDICATED IN THE CONTRACT DOCUMENTS.
B. STRUCTURAL OBSERVATION REPORTS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL,
OWNER, AND ARCHITECT/ENGINEER FOR REVIEW. REPORTS SHALL INDICATE THAT
WORK OBSERVED WAS OR WAS NOT COMPLETED IN CONFORMANCE TO APPROVED
CONSTRUCTION DOCUMENTS. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF THEY ARE NOT CORRECTED, THE
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND
THE ARCHITECT PRIOR TO COMPLETION OF THAT PHASE OF THE WORK.
C. THE CONSTRUCTION OR WORK FOR WHICH STRUCTURAL OBSERVATIONS IS REQUIRED
SHALL REMAIN ACCESSIBLE AND EXPOSED UNTIL COMPLETION OF THE REQUIRED
OBSERVATIONS.
D. A FINAL REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL, OWNER, AND
ARCHITECT/ENGINEER DOCUMENTING THE COMPLETION OF THE NOTED SITE VISITS AND
IDENTIFYING ANY REPORTED DEFICIENCIES THAT HAVE NOT BEEN RESOLVED.
DEMOLITION
A. DO NOT ALLOW DEMOLISHED OR REMOVED MATERIALS TO DROP, FALL OR IMPACT
AGAINST STRUCTURE-TO-REMAIN. PROTECT ALL STRUCTURE-TO-REMAIN FROM DAMAGE
OF ANY KIND.
B. REMOVE ALL DEMOLISHED MATERIAL PROMPTLY FROM SITE.
C. REPAIR ALL STRUCTURE DAMAGED DURING DEMOLITION OPERATIONS TO THE
SATISFACTION OF THE ENGINEER.
I. Verify compliance with the approved submittals. - X
II.
Verification of f’m prior to construction, except where specifically exempted by this Code.
- X
III. N/A - -
IV.
As masonry construction begins, verify that the following are in compliance:
a. Proportions of site-prepared mortar. - X
b. N/A - -
c. Grade, type and size of reinforcement, connectors, and anchor bolts. - X
d. N/A - -
e. N/A
V. Prior to grouting, verify that the following are in compliance:
a. Grout space. - X
b. N/A - -
c. Placement of reinforcement, connectors, and anchor bolts. - X
d. Proportions of site-prepared grout. - X
VI. Verify during construction:
c. Size and location of structural elements. - X
d. Type, size, and location of anchors, including other details of anchorage of masonry to structural members, frames, or other construction.
- X
e. Welding of reinforcement. X -
f. Preparation, construction, and protection of masonry during cold weather (temperature below 40°F) or hot weather (temperature above 90°F).
- X
g. N/A - -
h. N/A - -
i. N/A
VII.
Observe preparation of grout specimens, mortar specimens, and/or prisms.
- X
MASONRY CONSTRUCTION - LEVEL 2 TMS 602, TABLES 3 & 4
CONTINUOUS PERIODICREQUIRED VERIFICATION AND INSPECTION TASK
f. N/A - -
a. Materials and procedures with the approved submittals. - X
b. Placement of masonry units and mortar joint construction. - X
SPECIAL INSPECTION SCHEDULE NOTES
CONTINUOUS = SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT WHEN AND WHERE THE
WORK TO BE INSPECTED IS BEING PERFORMED.
PERIODIC = SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT WHERE THE
WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED.
OBSERVE = OBSERVE AND INSPECT THESE ITEMS ON AN INTERMITTENT RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. FREQUENCY OF OBSERVATIONS SHALL BE ADEQUATE TO CONFIRM THAT THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE APPLICABLE DOCUMENTS.
PERFORM = PERFORM THESE TASKS FOR EACH ELEMENT PRIOR TO THEIR FINAL ACCEPTANCE.
PERMIT APPLICANT'S RESPONSIBILITIES PER IBC 1704
1. THE PERMIT APPLICANT SHALL SUBMIT THIS SHEET AS THE STATEMENT OF SPECIAL
INSPECTION PERPARED BY THE REGISTERED DESIGN PROFESSIONAL IN RESPONISBLE
CHARGE AS A CONIDTION FOR PERMIT ISSUANCE.
2. THE PERMIT APPLICANT SHALL LIST BELOW THE INDIVIDUALS, APPROVED AGENCIES OR
FIRMS INTENDED TO BE RETAINED FOR CONDUCTING SUCH INSPECTIONS.
A. CMU
3. THE PERMIT APPLICANT SHALL OBTAIN ALL NECESSARY SIGNATURES INCLUDING
CONTRACTOR ACKNOWLEDGEMENT OF SPECIAL INSPECTIONS REQUIREMENTS.
NAME OR FIRM NAME
STATEMENT OF SPECIAL INSPECTIONS PER IBC 1704
1. INFORMATION ON THIS SHEET IS BEING SUBMITTED IN ACCORDANCE WITH THE SPECIAL
INSPECTIONS PROVISIONS OF THE 2018 INTERNATIONAL BUILDING CODE. THIS INFORMATION
CONSTITUTES THE SCHEDULE OF SPECIAL INSPECTIONS (SSI) REQUIRED FOR THIS PROJECT.
2. THE GENERAL CONTRACTOR SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS TO
PROVIDE INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED HEREIN.
3. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE
COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL, FOR INSPECTION OF THE
PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION.
4. THE SPECIAL INSPECTOR SHALL FULFILL THE FOLLOWING REPORT REQUIREMENTS:
A. SPECIAL INSPECTORS SHALL KEEP RECORDS OF ALL INSPECTIONS.
B. THE SPECIAL INSPECTORS SHALL FURNISH INSPECTION REPORTS TO THE BUILDING
OFFICIAL, THE OWNER, THE GENERAL CONTRACTOR, THE STRUCTURAL ENGINEER, AND
THE ARCHITECT. IN ADDITION, REPORTS RELATED TO GEOTECHNICAL ISSUES SHALL BE
DISTRIBUTED TO THE GEOTECHNICAL ENGINEER. WHEN TESTS OR INSPECTIONS INDICATE
THAT THE WORK DOES NOT COMPLY WITH THE CONSTRUCTION DOCUMENTS, THE
SPECIAL INSPECTOR SHALL NOTIFY THE OWNER, CONTRACTOR, ARCHITECT AND
STRUCTURAL ENGINEER BY PHONE ON THE DAY OF THE TEST OR INSPECTION AND SHALL
FOLLOW THAT CALL WITH AN EXPEDITED WRITTEN REPORT WITHIN ONE BUSINESS DAY.
ALL OTHER REPORTS SHALL BE SUBMITTED WITHIN 5 BUSINESS DAYS OF THE EVENT
DOCUMENT.
C. REPORTS SHALL INDICATE THAT WORK INSPECTED WAS DONE IN CONFORMANCE TO
APPROVED CONSTRUCTION DOCUMENTS.
D. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
CONTRACTOR FOR CORRECTION.
E. IF THE DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT
TO THE ATTENTION OF THE BUILDING OFFICIAL AND TO THE REGISTERED DESIGN
PROFESSIONAL IN RESPONSIBLE CHARGE WITHIN ONE BUSINESS DAY.
F. A FINAL REPORT DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND CORRECTION
OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS SHALL BE SUBMITTED BY THE
SPECIAL INSPECTOR AT A POINT IN TIME AGREED UPON BY THE PERMIT APPLICANT AND
THE BUILDING OFFICIAL PRIOR TO THE START OF WORK.
G. THE SPECIAL INSPECTORS REPORT SHALL STATE THE FOLLOWING:
"IN MY PROFESSIONAL OPINION AND TO THE BEST OF MY INFORMATION, KNOWLEDGE AND
BELIEF, THE SPECIAL INSPECTIONS REQUIRED FOR THE PROJECT, AS ITEMIZED IN THE
STATEMENT OF SPECIAL INSPECTIONS SUBMITTED FOR PERMIT, HAVE BEEN PERFORMED
AND ALL DISCOVERED DISCREPANCIES HAVE BEEN REPORTED AND RESOLVED."
5. THE INSPECTIONS LISTED HEREIN ARE IN ADDITION TO THE INSPECTIONS TO BE
PERFORMED BY THE BUILDING OFFICIAL AND LISTED IN SECTION 110 OF THE IBC.
6. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL INFORMATION, QUANTITY,
FREQUENCY AND DETAILED INFORMATION ON TESTING, INSPECTION, AND REPORTING.
7. PRIOR TO THE START OF CONSTRUCTION, THE CONTRACTOR SHALL CONDUCT A PRE-
CONSTRUCTION MEETING TO DISCUSS THE SPECIAL INSPECTION REQUIREMENTS WITH ALL
INVOLVED PARTIES.
8. THE SPECIAL INSPECTIONS PROGRAM OUTLINED HEREIN, DOES NOT RELIEVE THE
CONTRACTOR OR ANY OTHER ENTITY OF ANY CONTRACTUAL DUTIES, INCLUDING QUALITY
CONTROL, QUALITY ASSURANCE, OR SAFETY. THE CONTRACTOR IS SOLELY RESPONSIBLE
FOR CONSTRUCTION MEANS, METHODS, AND JOB SITE SAFETY.
9. THE CONTRACTOR SHALL PAY FOR ENGINEERING SERVICES REQUIRED TO INVESTIGATE
AND CORRECT WORK THAT DOES NOT CONFORM TO THE PROJECT DOCUMENTS OR IS FOUND
DEFICIENT OR DEFECTIVE.
SCHEDULE OF SPECIAL INSPECTIONS
2018 INTERNATIONAL BUILDING CODE
SUBMMITTALS
A. GENERAL: SUBMIT SHOP DRAWINGS, PRODUCT DATA, AND TEST REPORTS. SHOP
DRAWINGS SHALL CONFORM TO THE BEST STANDARDS OF THE CONSTRUCTION
INDUSTRY.
B. MASONRY CONSTRUCTION: PRODUCT DATA FOR EACH TYPE OF PRODUCT, MATERIAL
CERTIFICATES FOR EACH TYPE AND SIZE OF MASONRY UNIT (MATERIAL PROPERTIES AND
MATERIAL TEST REPORTS), CEMENTITIOUS MATERIALS, MORTAR ADMIXTURES, PRE-
BLENDED DRY MORTAR MIXES, GROUT MIXES, REINFORCEMENT BARS, ETC.
STATEMENT OF COMPRESSIVE STRENGTH OF MASONRY: FOR EACH COMBINATION OF
MASONRY UNIT TYPE AND MORTAR TYPE, PROVIDE STATEMENT OF AVERAGE NET-AREA
COMPRESSIVE STRENGTH OF MASONRY UNITS, MORTAR TYPE, AND RESULTING NET-
AREA COMPRESSIVE STRENGTH OF MASONRY DETERMINED IN ACCORDANCE WITH
TMS 602/ACI 530.1/ASCE 6
COLD-WEATHER AND HOT-WEATHER PROCEDURES: DETAILED DESCRIPTION OF
METHODS, MATERIALS, AND EQUIPMENT TO BE USED TO COMPLY WITH REQUIREMENTS.
POST-INSTALLED ANCHORS
A. ALL CONCRETE EXPANSION ANCHORS SHALL BE GALVANIZED OR ZINC PLATED.
B. GROUT ALL CMU CELLS FULL WITHIN A 12" RADIUS WHEN CONCRETE ANCHORS ARE PLACED
INTO CMU WALLS.
C. UNLESS OTHERWISE INDICATED ON PLANS, POST-INSTALLED ANCHORS SHALL CONSIST OF
THE FOLLOWING ANCHOR TYPES, OR APPROVED EQUAL:
ADHESIVE ANCHOR MECHANICAL ANCHOR
SOLID CONCRETE HILTI HY 200 SAFE SET SYSTEM HILTI KWIK HUS EZ (ICC ESR-3027)
(ICC ESR-3187) A36 U.N.O.
HILTI RE 500V3 SAFE SET SYSTEM HILTI KWIK BOLT TZ (ICC ESR-1917)
(ICC ESR-3814) HAS-E ROD
OR GRADE 60 REBAR U.N.O.
GROUTED MASONRY HILTI HY 270 (ICC ESR-2682) HILTI KWIK BOLT 3 (ICC ESR-1385)
A36 U.N.O.
HOLLOW MASONRY HILTI HY 270 WITH APPROPRIATE HILTI HLC SLEEVE ANCHOR
OR BRICK SCREEN TUBE (ICC ESR-3342)
A36 U.N.O.
D. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY
THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE
CALCULATIONS DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF
ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT. SUBSTITUTIONS WILL
BE EVALUATED BY THEIR HAVING AN ICC ESR SHOWING COMPLIANCE WITH THE RELEVANT
BUILDING CODE.
E. INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN THE ANCHOR
PACKAGING.
F. THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO
PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS
SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED
CONFIRMATION THAT ALL OF THE CONTRACTOR'S PERSONNEL WHO INSTALL ANCHORS ARE
TRAINED PRIOR TO THE COMMENCEMENT OF INSTALLING ANCHORS.
G. ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND
PROXIMITY OF ANCHORS TO EDGE OF MATERIAL. INSTALL ANCHORS IN ACCORDANCE WITH
SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS.
3 3 a a a
COMPONENTS & CLADDING SCHEDULE (FLAT)
ROOF
EFFECTIVE
WIND AREA
REGION 1 REGION 2 REGION 3
10 SQ FT 16.2 PSF
20 SQ FT
50 SQ FT
100 SQ FT
200 SQ FT
500 SQ FT
-63.6 PSF 16.2 PSF -83.9 PSF 16.2 PSF -114.4 PSF
16.0 PSF -59.4 PSF 16.0 PSF -78.5 PSF 16.0 PSF -103.6 PSF
16.0 PSF -53.9 PSF 16.0 PSF -71.4 PSF 16.0 PSF -89.3 PSF
16.0 PSF -49.7 PSF 16.0 PSF -66.0 PSF 16.0 PSF -78.5 PSF
16.0 PSF -45.5 PSF 16.0 PSF -60.6 PSF 16.0 PSF -67.7 PSF
16.0 PSF -39.9 PSF 16.0 PSF -53.5 PSF 16.0 PSF -53.5 PSF
b b b b a
"a" = 10'-0" "b" = 31'-3"
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
401 Southwest Water Street Suite 701 Peoria, IL 61602
309.282.8000 Phone
IL DESIGN FIRM REG.
#184005007-0006
IL DESIGN FIRM REG.
#184000358-0001
/1
/2
:0
:5
A
M
GENERAL
STRUCTURAL
NOTES
TNT
BMB
NRH
06/15/2026
50193648
C
IT
Y O
F B
L O
O M
IN
G
T O
N P
O L
IC
E
D E
P A
R T
M E
N T
D R
O N
E I
N S
T A
L L
A T
IO
N
C
IT
Y O
F B
L O
O M
IN
G
T O
N
IS
S
U E
D F
O R
B
ID
D
IN
G
P E
R M
IT
S
O U
T H
E A
S T
S T
R E
E T
B L O
O M
IN
G
T O
N
IL
Dewberry Architects Inc.
401 Southwest Water Street Suite 701 Peoria, Illinois 61602
309.282.8000 Phone
S-001
Dewberry Engineers Inc.
ABBREVIATIONS
Key Name Structural Abbreviation
ADDL ADDITIONAL
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARCH ARCHITECTURAL
BM BEAM
BOTT BOTTOM
BRG BEARING
BS BOTH SIDES
C = CAMBER
CF CUBIC FOOT
CJ CONTROL JOINT
CJP PREQUALIFIED COMPLETE
JOINT PENETRATION WELD
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
DET, DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DWGS DRAWINGS
(E), EXIST EXISTING
EA EACH
EJ EXPANSION JOINT
ELECT ELECTRICAL
ELEV ELEVATION
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EXP EXPANSION
EXT EXTERIOR
FIN FINISH
FNDN FOUNDATION
FTG FOOTING
GA GAUGE
GALV GALVANIZED
HORIZ HORIZONTAL
HSS HOLLOW STRUCTURAL
SECTION
INT INTERIOR
INV INVERT
JB JOIST BEARING
K KIPS
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LB POUNDS
LD DEVELOPMENT LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
MANUF MANUFACTURER
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MPH MILES PER HOUR
NIC NOT IN CONTRACT
NO., # NUMBER
NTS NOT TO SCALE
OC ON CENTER
PJP PREQUALIFIED PARTIAL JOINT
PENETRATION WELD
PL PLATE
PLCS PLACES
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
R RADIUS
REINF REINFORCING
REQ'D REQUIRED
RTU ROOF TOP UNIT
S.S. STAINLESS STEEL
SAN SANITARY
SCHED SCHEDULE
SF SQUARE FEET
SIM SIMILAR
SPA SPACES
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
T/STL, T.O.S. TOP OF STEEL
TS TUBE STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT. VERTICAL
VIF VERIFY IN FIELD
WP WORK POINT
WWF WELDED WIRE FABRIC
GENERAL STRUCTURAL NOTES
NO. DESCRIPTION DATE
RDRD
RDRD
RDRD
6 7 8 9
A
B
C
D
E
F
G
32' - 1" * 33' - 4" * 32' - 1" *
(E) W21X44 (30) (E) W21X44 (30)
(E) W16X31 (18)
(E) W16X31 (18) (E) W16X31 (18)
(E
W X
(E
W X
(E
W X
(E
W X
(E
W X
(E
W X
(E
W
X
(E
W X
(E
W X
(E
W
X
(E
W X
(E
W
X
(E
W X
(E
W X
(E
W
X
(E
W X
(E
W X
(E
W X
(E
W X
(E
W X
(E
W X
(E
W X
(E) W16X31 (26)(E) W16X31 (26) (E) W18X50 (28)
(E) W16X31 (26)(E) W16X31 (26) (E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26) (E) W16X31 (26)
(E) W16X31 (18)(E) W16X31 (18) (E) W16X31 (18)
(E) W21X50 (30)(E) W21X50 (30)
(E) W18X50 (28)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (26)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X31 (18)
(E) W16X26 (8)
(E) W16X26 (8)
(E
W X
(E
W X
(E
W X
(E
W X
(E) W16X26 (8)
(E) W16X26 (8)
(E) W16X26 (8)
(E
W X
(E
W X
(E
W X
(E
W X
(E) W16X26 (8)
(E
W X
(E
W X
(E
W X
(E) W10X12
(E) W10X12
97' - 6" *
N O
T E
N O
T E
N O
T E
S
P A
S
P A
S
P A
S
P A
S
P A
S
P A
S-100
6' - 0"
NOTE #6 TYP
S-100
RADIO ANTENNA
(E) HATCH
34' - 9"
(E) EDGE OF BRICK
(E) EDGE
OF BRICK
1' - 3"1' - 3"
NOTE #7
S-100
19' - 4"
17' - 0" MIN
16' - 4" (10' - 0" MIN)
PLAN NOTES
1. FOR GENERAL NOTES, ABBREVIATIONS, AND LOADING CRITERIA, SEE DRAWING S-001.
2. REFERENCE ELEVATION FOR TOP OF STEEL AND BOTTOM OF DECK SHALL BE AT ELEVATION (+)26'-3" UNLESS OTHERWISE NOTED.
3. EXISTING 3" CONCRETE SLAB ON 2" COMPOSITE 20 GAGE METAL DECK TO REMAIN AND DIRECTION OF SPAN IS INDICATED THUS:
4. * INDICATES DIMENSION TO BE COORDINATED WITH ARCHITECTURAL OR MECHANICAL DRAWINGS, MANUFACTURER OR EXISTING CONSTRUCTION PRIOR TO ANY
FABRICATION OR CONSTRUCTION.
5. 8" MASONRY WALL WITH #5 VERTICAL BARS @ 16" OC. GROUT ALL CELLS. 8" BOND BEAMS WITH (2) #5 CONTINUOUS BARS AT TOP OF WALL. DO NOT DOWELS
VERTICAL BARS INTO EXISTING CONCRETE ON METAL DECK.
6. DRONE DOCK PROFILES ARE GENERIC AND SHOULD NOT BE USED FOR DIMENSIONING OR COORDINATION. REFER TO MANUFACTURER WRITTEN
DOCUMENTATION FOR ADDITIONAL INFORMATION.
7. PROVIDE 3" MAXIMUM DIAMETER CORE THROUGH EXISTING CONCRETE ON METAL DECK. MIN 12" CENTER TO CENTER SEPARATION. SEE ELECTRICAL AND
ARCHITECTURAL DRAWINGS FOR MORE INFORMATION.
8. EXTERIOR, HEAVY-DUTY LANDSCAPE ADHESIVE SHALL BE LOCTITE PL500 LANDSCAPE CONSTRUCTION ADHESIVE OR APPROVED EQUAL. ADHESIVE SHALL BE
INSTALLED PER THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS, INCLUDING ANY SURFACE PREPARATION.
T/STL
(+)26'-3"
ROOFING
SEE ARCH
(E) CONC ON MTL
DECK SEE PLAN
(E) STL BEAM
SEE PLAN
DOCK BY OTHERS
(CENTER ON
TOP OF WALL)
CMU WALL
SEE PLAN
BOND BEAM
w/ (2) #5 CONT
S-100
EXTERIOR,
HEAVY-DUTY
LANDSCAPE
ADHESIVE
MIN 3/8" BEAD
ALONG EA FACE
SHELL -TYP
(PLAN NOTE #8)
BED JOINT
REINF. TYP
ANCHOR BOLTS
SEE DTL
FOR MORE INFO
/5 S-100
3' - 6"
S-100
(E) STL BEAM
SEE PLAN
EXTERIOR, HEAVY-
DUTY LANDSCAPE
ADHESIVE
MIN 3/8" BEAD ALONG
EA FACE SHELL -TYP
(PLAN NOTE #8)
CMU WALL
SEE PLAN
T/STL
(+)26'-3"
(E) CONC ON MTL
DECK SEE PLAN
DOCK BY OTHERS
(CENTER ON
TOP OF WALL)
SEE PLAN
ROOFING
SEE ARCH
ANCHOR BOLTS
SEE DTL
FOR MORE INFO
/5 S-100
2' - 1 7/8"1' - 8 1/4" *
1' - 6" 1' - 6"
SECTION A-A
1' - 6" 1' - 6"
(8) 8x8x16 SOLID
CMU BLOCKS
(MIN 72 LB EACH)
A A
POLE PROVIDE
BY MANUF
BASE PL PROVIDE
BY MANUF
RADIO ANTENNA
PROVIDE BY MANUF
RUBBER
ROOFING MAT (E) ROOFING
FRONT
2' - 9 3/8" *
2' - 11" *
/4
3/4" 3/4"
(4) 3/8" DIA (Gr 36) GALV
HEADED ANCHORS
w/4" EMBED COORD LOC w/ DOCK MANUF.
w/1" MIN, 2 3/8" MAX
THREADED PROJECTION
(POST INSTALLED
ANCHORS WILL NOT BE
ACCEPTED)
DOCK
BY OTHERS
PRE-MANUFACTURED
NON-PENETRATING ROOFTOP
MOUNT SEE ELECTRICAL DWGS
(7) 8x8x16 SOLID
CMU BLOCKS
PER TRAY
(14 TOTAL)
(MIN 72 LBS EACH) (E) ROOFING
RUBBER ROOTING MAT TYP
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
401 Southwest Water Street Suite 701 Peoria, IL 61602
309.282.8000 Phone
IL DESIGN FIRM REG.
#184005007-0006
IL DESIGN FIRM REG.
#184000358-0001
/1
/2
:3
:0
A
M
ROOF FRAMING
PLAN & DETAILS
CEB
BMB
NRH
06/15/2026
50193648
C
IT
Y O
F B
L O
O M
IN
G
T O
N P
O L
IC
E
D E
P A
R T
M E
N T
D R
O N
E I
N S
T A
L L
A T
IO
N
C
IT
Y O
F B
L O
O M
IN
G
T O
N
IS
S
U E
D F
O R
B
ID
D
IN
G
P E
R M
IT
S
O U
T H
E A
S T
S T
R E
E T
B L O
O M
IN
G
T O
N
IL
Dewberry Architects Inc.
401 Southwest Water Street Suite 701 Peoria, Illinois 61602
309.282.8000 Phone
S-100
Dewberry Engineers Inc.
Scale: 1/8" = 1'-0"
ROOF FRAMING PLAN
N
Scale: 3/4" = 1'-0"
1/S-100 Scale: 3/4" = 1'-0"
1/S-100
Scale: 3/4" = 1'-0"
1/S-100 Scale: 1 1/2" = 1'-0"
ANCHOR BOLT LAYOUT
NO. DESCRIPTION DATE
Scale: 3/4" = 1'-0"
1/S-100
RD
RD
RD
RD
RD
RD
RD
VTR
VTR
VTR
C
VTR VTR
VTR
VTR
C
C C
6 7 8 9
A
B
C
D
E
F
G
RADIO
ANTENNA
EXISTING
HATCH
6' - 0" 34' - 9"
A1 A-162
A4 A-162
PROVIDE NEW
WALKING PAD
DOCKING
STATION
CLEAR
MIN 17' - 0" TYP
CLEAR
MIN 17' - 0" TYP
C
LE
AR
M
IN
7'
0"
T
YP
C
LE
AR
M
IN
7'
0"
T
YP
CLEAR
MIN 12' - 0" TYP
CLEAR
MIN 12' - 0" TYP
C
LE
AR
M
IN
2'
0"
T
YP
C
LE
AR
M
IN
2'
0"
T
YP
3'
6"
6 7 8 9
A
B
C
D
E
F
G
VTR
VTR
VTR
C
VTR VTR
VTR
VTR
C
C C
EXISTING
HATCH
7' - 0"
4'
6"
DEMOLISH ROOF MEMBRANE,
REMOVE INSULATION TO DECK,
PREPARE FOR NEW CMU WALL
CONSTRUCTION.
41' - 3"
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000
IL DESIGN FIRM #184000358-0001
Dewberry Engineers Inc.
401 Southwest Water Street Suite 701 Peoria, Illinois 61602
ILLINOIS DESIGN FIRM REG.
#184005007-0006
6/
/2
4:
:2
PM
ROOF OVERALL
PLAN &
DEMOLITION
PLAN
CB
NLC
06/15/2026
50193648
C
IT
Y O
F
BL
O O
M
IN
G
TO
N P
O
LI
C E
D
EP
AR
TM
EN
T
D R
O N
E
IN
ST
AL
LA
TI
O N
C
IT
Y O
F
BL
O O
M
IN
G
TO
N
IS
SU
ED
F
O R
B
ID
D
IN
G A
N D
P
ER
M
IT
SO
U
TH
E
AS
T
ST
R
EE
T
BL
O
O M
IN
G
TO
N
, I L
A-161
Scale: 1/8" = 1'-0"A4 ROOF ANNOTATION & DIMENSION PLAN Scale: 1/8" = 1'-0"A1 ROOF DEMOLITION PLAN
PER SECTION 1015.6
Guards shall be provided where various components that require service are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof or grade below. Therefore, no guardrail required.
ROOF T/DECK
26' - 8"
ROOF
26' - 8"
D E F G
40 DEGREES
40 DEGREESA4
A-162
RADIO
ANTENNA
DOCKING
STATION
CLEAR
CLEAR
CLEAR
17' - 0"
EXISTING ROOF
27' - 7 1/2"
A-162 C1
ROOF T/DECK
26' - 8"
ROOF
26' - 8"
7 8 9
A1 A-162
40 DEGREES 40 DEGREES
A-162 C3
CLEAR
17' - 0"
CLEAR
CLEAR
EXISTING ROOF
27' - 7 1/2"
ROOF T/DECK
26' - 8"
ROOF
26' - 8"
BOND BEAM, SEE
STRUCTURAL DRAWINGS.
NEW CMU WALL
EXISTING CONCRETE ON
METAL DECK TO REMAIN
DOCKING STATION PROVIDED
BY MANUFACTURER
NEW INSULATION TO MATCH EXISTINGEXISTING ROOF
27' - 7 1/2"
A-162 E1
A-162 E3
EXISTING ROOF AND INSULATION
TO REMAIN
8" M
IN
ROOF T/DECK
26' - 8"
ROOF
26' - 8"
BASE PLINTH PROVIDED BY
MANUFACTURER
EXISTING CONCRETE ON
METAL DECK TO REMAIN
EPDM BOOT FLASHING BY
ROOF PROVIDER
NEW EPDM FLASHING MEMBRANE
NEW EPDM ROOF MEMBRANE
EXISTING ROOF
27' - 7 1/2"
A-162 C5
A-162 E5
RADIO ANTENNA PROVIDED
BY MANUFACTURER
POLE PROVIDED BY
MANUFACTURER
EXISTING ROOF
27' - 7 1/2"
MORTAR STRUCK FLUSH
BOLT
NEW EPDM FLASHING MEMBRANE
EXISTING ROOF
27' - 7 1/2"
NEW EPDM FLASHING MEMBRANE
NEW EPDM ROOF MEMBRANE
SEAM PLATE
EPDM BOOT FLASHING BY
ROOF PROVIDER
CLAMPING RING (BY OTHERS)
EPDM PIPE FLASHING
EPDM SEALING MASTIC
CAULK (BEADED)
ANCHOR DISC AND FASTENER
F
EXISTING ROOF
27' - 7 1/2"
NEW EPDM FLASHING MEMBRANE
NEW 1/2" COVERBOARD
SEAM PLATE
EXISTING EPDM MEMBRANE
ADHESIVE TAPE
NEW EPDM ROOF MEMBRANE
1/8" TO 1/2"
ADHESIVE
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000
IL DESIGN FIRM #184000358-0001
Dewberry Engineers Inc.
401 Southwest Water Street Suite 701 Peoria, Illinois 61602
ILLINOIS DESIGN FIRM REG.
#184005007-0006
ROOF SECTIONS
& ENLARGED
DETAILS
CB
NLC
06/15/2026
50193648
C
IT
Y O
F
BL
O O
M
IN
G
TO
N P
O
LI
C E
D
EP
AR
TM
EN
T
D R
O N
E
IN
ST
AL
LA
TI
O N
C
IT
Y O
F
BL
O O
M
IN
G
TO
N
IS
SU
ED
F
O R
B
ID
D
IN
G A
N D
P
ER
M
IT
SO
U
TH
E
AS
T
ST
R
EE
T
BL
O
O M
IN
G
TO
N
, I L
A-162
Scale: 3/16" = 1'-0"A1 NORTH-SOUTH SECTION Scale: 3/16" = 1'-0"A4 EAST-WEST SECTION
Scale: 1/2" = 1'-0"C1 ROOF CONNECTION DETAIL (DOCKING STATION) Scale: 1/2" = 1'-0"C3 ROOF CONNECTION DETAIL (RADIO ANTENNA)
Scale: 3" = 1'-0"E1 ENLARGED DOCKING STATION DETAIL
Scale: 3" = 1'-0"C5 RADIO ANTENNA PLINTH CONNECTION DETAIL
Scale: 3" = 1'-0"E5 RADIO ANTENNA FLASHING BOOT DETAIL Scale: 3" = 1'-0"E3 EXISTING TO NEW ROOF CONNECTION
C L
A
F F
O R
A S
I N
D
IC
A T
E D
O
N D
R A
W
IN
G S
A D
J U
S T
S L
IG
H T
L Y
T O
A
C C
O M
M O
D A
T E
C M
U U
N
IT
D
IM
E
N S
IO
N
S
XXX-#,#,#
FACE PLATE
LABEL
- REPRESENTS CIRCUIT NUMBER
- REPRESENTS PANEL DESIGNATION
LABELS SHALL BE MACHINE ENGRAVED ON VISIBLE FACE OF PLATE.
REFER TO SPECIFICATIONS.
XXX-#,#,#
LEGEND:
NOTES:
1.
XXX
1/4" (TYP.)
NEUTRAL TERMINAL IN
THE TOP POSITION
ELECTRICAL SYMBOLS LEGEND
THIS IS A MASTER SYMBOLS LIST -
NOT ALL SYMBOLS APPLY TO THIS PROJECT
DUPLEX RECEPTACLE
"GF" = GROUND FAULT, "WR" = WEATHER-RESISTANT
"WP" = WEATHERPROOF BOX
JUNCTION BOX, CEILING MOUNTEDJ
PULL BOX
EQUIPMENT - SIZE & TYPE AS SHOWN
208V PANELBOARD - NORMAL BRANCH
208V PANELBOARD - EMERGENCY/LIFE SAFETY BRANCH
480V PANELBOARD - NORMAL BRANCH
480V PANELBOARD - EMERGENCY/LIFE SAFETY BRANCH
PB
SYMBOL DESCRIPTION
FIRE ALARM CONTROL PANEL
J JUNCTION BOX, WALL MOUNTED
12 GA, 1-5/8" METAL
FRAMING CHANNEL - 1FT
1" C. PWR
WIDE FLANGE STRUCTURAL
FRAMING GIRDER, (E), TYP
MEMBRANE ROOF(E)
CUT SEAM SEALANT
PRE-FABRICATED MEMBRANE
FLASHING, TYP OF 2
THROUGH-ROOF PIPE
PENETRATION, TYP OF 2
PIPE HANGER - EACH SIDE
OF CHANNEL
CONDUIT CLAMP
DEEP-TYPE JUNCTION BOX
MOUNTED TO STRUT
1-1/2" C. DATA
BEAM CLAMP
BUSHING FOR DATA CABLE
CONDUIT TRANSITION
12 GA, 1-5/8" METAL FRAMING
CHANNEL - LENGTH AS REQ'D TO
SUPPORT CONDUITS TO ROOF
12 GA, 1-5/8" METAL FRAMING CHANNEL -
LENGTH TO SPAN GIRDER BOTTOM
CHORDS AS SHOWN
GENERAL NOTES:
1. ALL STRUT CHANNEL, ASSOCIATED MOUNTING & PIPE-HANGING
HARDWARE, SCREWS, AND ALL ACCESSORIES ON ROOF SHALL BE
ATKORE WITH DEFENDER CORROSION PROTECTION, OR EQUAL.
DO NOT USE TOUCH UP PAINT OVER CUT STRUT EDGES,
DEFENDER STRUT HAS SELF-HEALING PROPERTIES THAT
PROPAGATE OVER CUT EDGES AND SCRATCHES.
2. ALL CONDUIT ON ROOF SHALL HAVE WATER-TIGHT CONNECTIONS.
3. DATA CABLE CONDUIT ROUTING TO DOCKS NOT SHOWN. REFER
TO TECHNOLOGY PLANS AND DETAILS.
4. PROVIDE ALL NECESSARY HARDWARE AND ACCESSORIES FOR A
COMPLETE & WATER-PROOF INSTALLATION OF EQUIPMENT
SHOWN ON RACK AND CONDUIT PENETRATIONS THROUGH ROOF.
5. = REFER TO CONDUIT AND WIRING SCHEDULE ABOVE FOR
SPECIFIC RUN OF CIRCUITRY.
DETAIL NOTES:
1. GALVANIZED RIGID STEEL CONDUIT TO DOCK. REFER TO E-100 FOR
CONTINUATION.
2. ALL HOLES MADE THROUGH ENCLOSURE SHALL BE MADE WITH A
KNOCKOUT PUNCH KIT. ENSURE THE NEMA RATING IS MAINTAINED.
3. 1" GALVANIZED RIGID STEEL CONDUIT FOR DATA. REFER TO
TECHNOLOGY PLANS FOR ROUTING. CENTER MOUNT CONDUITS
BETWEEN EDGE OF BOX AND INCOMING 1-1/2" CONDUIT FROM
BELOW ROOF SUCH THAT (2) 1" CONDUITS CAN BE MOUNTED ON
EACH SIDE OF (2) PROVIDED CONDUITS.
4. DO NOT PENETRATE ROOF MEMBRANE WHEN MOUNTING
STRUCTURE. UTILIZE ROOF & FLASHING POLYURETHANE SEALANTS
AT FLASHING EDGES.
5. 10 FOOT BALLASTED HEAVY DUTY ROOFTOP FOR REMOTE RADIO
UNIT STRUCTURE SHALL BE SITE PRO RT-RRU10HD, OR EQUAL. TOP
UNISTRUT SHALL BE MOUNTED AT 4 FT ABOVE ROOF. TOP UNISTRUT
SHALL BE MOUNTED AT 4 FT ABOVE ROOF TO TOP.
6. RUN CIRCUITRY FROM NEW PANELBOARD TO DISCONNECT TO
SERVE FUTURE EQUIPMENT.
GRID CEILING(E)
A
EMT
GALVANIZED RIGID
STEEL CONDUIT
SUPPORT CONDUIT AS
REQ'D BACK TO
MECHANICAL ROOM
POWER
ENCL DATA
ENCL
FUTURE
DOCK DOCK #1
12 GA, 1-5/8" METAL
FRAMING CHANNEL -
2.5 FT, TYP OF 2
F
FUTURE
DOCK
E
D
C
12" H x 10" W x 6" D, 16 GA, GASKETED, NEMA 4, HINGED-DOOR ENCLOSURE:
HOFFMAN LHC302515,
OR EQUAL
PIPE CAP, TYP OF 2
20A, GF, WR, EXTRA HEAVY DUTY
DUPLEX RECEPTACLE IN A DEEP-TYPE,
SINGLE-GANG,CAST BOX & HORIZONTAL
METAL WHILE-IN-USE-COVER
30A, 600V, 3P, NEMA 3R,
HEAVY DUTY, NON-
FUSED, LOCKABLE
DISCONNECT, TYP OF 3
16" H x 16" W x 6" D, 16 GA, GASKETED, NEMA 4, HINGED-DOOR ENCLOSURE:
HOFFMAN A16H16ALP3PT,
OR EQUAL
STAINLESS STEEL DRAWBAND &
WATERPROOFING SEALANT,
TYP OF 2
DATA
ENCL
ROOF CONDUIT
MOUNTING SUPPORT 4
GRID CEILING(E)
WIDE FLANGE STRUCTURAL
FRAMING GIRDER, (E), TYP
MEMBRANE ROOF(E)
SIDE VIEW
FRONT VIEW
PIPE CLAMPS, TYP
6 6
12 GA, 1-5/8" METAL
FRAMING CHANNEL -
10 FT, TYP OF 4
SUPPORT PLATE &
HARDWARE, TYPE
U-BOLTS &
HARDWARE, TYP
2-3/8" x 84" SCH 40 GALVANIZED
PIPE, V-CLAMP & ASSOCIATED
HARDWARE, TYP OF 2
BALLASTED TRAY WELDMENT,
TYP OF 2
2-3/8" x 63" SCH 40 GALVANIZED
PIPE, V-CLAMP & ASSOCIATED
HARDWARE, TYP OF 2
NON-PENETRATING
ROOFTOP MOUNT
NON-PENETRATING
ROOFTOP MOUNT
BALLASTED TRAY WELDMENT,
TYP OF 2
SUPPORT PLATE &
HARDWARE, TYP OF 4
CONDUIT OFFSET, TYP
STRUT MOUNTED TO
PIPE VIA U-BOLT
5" V-CLAMP, TYP OF 2
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
401 Southwest Water Street Suite 701 Peoria, IL 61602
309.282.8000 Phone
IL DESIGN FIRM REG.
#184005007-0006
IL DESIGN FIRM REG.
#184000358-0001
/1
/2
:5
:0
A
M
ELECTRICAL
SYMBOLS,
ABBREVIATIONS,
& NOTES
JAM
GTR
JAM
06/15/2026
50193648
C
IT
Y O
F B
L O
O M
IN
G
T O
N P
O L
IC
E
D E
P A
R T
M E
N T
D R
O N
E I
N S
T A
L L
A T
IO
N
C
IT
Y O
F B
L O
O M
IN
G
T O
N
IS
S
U E
D F
O R
B
ID
D
IN
G A
N D
P E
R M
IT
S
O U
T H
E A
S T
S T
R E
E T
B L O
O M
IN
G
T O
N
IL
Dewberry Architects 401 SW Water Street, Suite 701 Peoria, Illinois 61602-1530 309.202.8100
E-001
ELECTRICAL GENERAL NOTES
1. REFER TO SHEET E-001 (THIS SHEET) ELECTRICAL SYMBOLS,
ABBREVIATIONS FOR DESCRIPTIONS OF ALL GRAPHIC
SYMBOLS USED ON THESE DRAWINGS.
2. ALL EQUIPMENT, DEVICES, AND FIXTURES DEPICTED IN THESE
DRAWINGS ARE BASIS OF DESIGN ONLY. CONTRACTOR SHALL
BE RESPONSIBLE FOR COORDINATING THE EXACT
INSTALLATION REQUIREMENTS OF ACTUAL EQUIPMENT
PROVIDED WITH ALL OTHER TRADES.
3. ALL WIRING 120-VOLT & ABOVE SHALL BE IN CONDUIT.
LOW-VOLTAGE CABLING MAY BE INDEPENDENTLY SUPPORTED
FROM STRUCTURE ABOVE ACCESSIBLE CEILINGS BY J-HOOKS
OR ANY OTHER APPROVED METHOD PER THE
SPECIFICATIONS. LOW-VOLTAGE CABLING UP WALLS OR IN
EXTERIOR LOCATIONS SHALL BE IN CONDUIT.
4. CONTRACTOR SHALL CALCULATE FOR AND INCREASE WIRE
SIZE TO COMPENSATE FOR VOLTAGE DROP.
5. ALL CONDUITS SHALL BE INSTALLED CONCEALED FROM VIEW
ABOVE CEILINGS AND IN WALLS OR FLOORS EXCEPT IN
MECHANICAL ROOMS AND ON CEILINGS OF AREAS WITH
EXPOSED STRUCTURE. EXPOSED CONDUIT AND BOXES SHALL
BE PAINTED TO MATCH ADJACENT EXISTING STRUCTURE.
6. WIRE SIZES SHALL REMAIN CONSISTENT THROUGHOUT THE
ENTIRE CIRCUIT.
7. PROVIDE A DEDICATED GROUNDING CONDUCTOR FOR EACH
A-B-C PHASE GROUPING FOR ALL 20 AMP CIRCUITS.
8. PROVIDE STEEL SLEEVES IN ALL FIRE WALLS, SMOKE WALLS,
OR COMBINATION SMOKE/FIRE WALLS FOR CONDUIT/WIRING
PENETRATIONS. PROVIDE FIRE SEALANT FOR ALL PARTITION
TYPES OF EQUIVALENT RATING AFTER ALL WIRING IS
INSTALLED. REFER TO CODE PLAN.
9. UNLESS OTHERWISE NOTED, ALL CIRCUITS SHALL ORIGINATE
FROM THE PANELBOARD AREA SHOWN.
10. ALL CIRCUITS SHALL CONTAIN DEDICATED NEUTRAL
CONDUCTORS, UNLESS SHOWN OTHERWISE.
11. ALL EMPTY CONDUITS SHALL HAVE PULL STRINGS INSTALLED
PER SPECIFICATIONS.
12. EXPOSED CONDUIT ENDS SHALL BE FITTED WITH PLASTIC
BUSHINGS.
13. ALL WORK SHALL BE PHASED IN ACCORDANCE WITH
CONTRACT DRAWINGS AND OWNERS REQUIREMENTS.
14. REFER TO 'T'-SERIES DRAWINGS FOR ADDITIONAL
REQUIREMENTS FOR RACEWAYS, OUTLET BOXES, PULL
BOXES, AND ENCLOSURES FOR LOW VOLTAGE SYSTEMS.
Scale: N.T.S.
FACEPLATE - LABEL DETAIL
THIS IS A MASTER ABBREVIATIONS LIST. SOME ABBREVIATIONS MAY NOT
APPLY TO THIS PROJECT.
ABBREVIATIONS - ELECTRICAL
A, AMP AMPERE
AC ABOVE CEILING
ADA AMERICANS WITH DISABILITIES ACT
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERES INTERRUPTING CAPACITY
AL, ALUM ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BRKR, BKR BREAKER
BTU BRITISH THERMAL UNIT
C CONDUIT
C/B, CB CIRCUIT BREAKER
CKT CIRCUIT
CL CENTERLINE
CLG CEILING
CNT CONTACTS
CP CIRCULATING PUMP
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
DD DUCT DETECTOR
DET DETECTOR
DIA DIAMETER
DN DOWN
DP DISTRIBUTION PANEL
DTEN DETENTION
DWG DRAWING
E EXISTING
EA EACH
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EOL END OF LINE RESISTOR
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FC FOOTCANDLE
FFB FROM FLOOR BELOW
FLA FULL LOAD AMPS
FLEX FLEXIBLE CONDUIT CONNECTION
FLR FLOOR
G GROUND
GALV GALVANIZED
GFCI, GF GROUND FAULT CIRCUIT INTERRUPTER
GRC, GRMC GALVANIZED RIGID METALLIC CONDUIT
HP HORSE POWER
HVAC HEATING, VENTILATION AND AIR
CONDITIONING
Hz HERTZ, FREQUENCY
IMC INTERMEDIATE METALLIC CONDUIT
JB JUNCTION BOX
K KELVIN
KCMIL THOUSAND CIRCULAR MILLS
KVA KILOVOLT-AMPERES
KW KILOWATT
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LP LIGHTING PANEL
LSIG LONG, SHORT, INSTANTANEOUS & GROUND
LTG LIGHTING
LV LOW VOLTAGE
LVRC LOW VOLTAGE RELAY CABINET
MATL MATERIAL
MC METAL CLAD CABLE
MCA MAXIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MTR MOTOR
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
N/A NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NECA NATIONAL ELECTRICAL CONTRACTORS
ASSOCIATION
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHTING
NO NUMBER
NTS NOT TO SCALE
OCC OCCUPANCY (SENSOR)
P POLE
PB PULL BOX
PH, Ø PHASE
PNL PANEL
POE POWER OVER ETHERNET
PP POWER PANEL
PVC POLYVINYL CHLORIDE
PWR POWER
QTY, QUAN QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
REC, RECP RECEPTACLE
REQ, REQ'D REQUIRED
RHC REHEAT COIL
RMC RIGID METALLIC CONDUIT
RNC RIGID NON-METALLIC CONDUIT
RP RECEPTACLE PANEL
RR REMOVE AND RELOCATE
RTU ROOF TOP UNIT
SBD, SWBD SWITCHBOARD
SGR, SWGR SWITCHGEAR
SMK SMOKE
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SS STAINLESS STEEL (TYPE 304, UNO)
SSC STAINLESS STEEL RIGID CONDUIT (TYPE 304,
UNO)
SSU SWITCH & FUSE UNIT (BUSS)
STD STANDARD
TEMP TEMPORARY
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTABLE POWER SUPPLY
V VOLTS
VA VOLT AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATT
WG WIRE GUARD
Scale: 3/4" = 1'-0"
THRU-ROOF CONDUIT ROUTING & DOCK STRUCTURE DETAIL
* Indicates Breaker Type: 1=Standard, 2=HACR (HVAC Rated), 3=6MA GFCI, 4=30MA GFCI, 5=Shunt Trip, 6=AFCI ** See Specifications for Panel Type
Legend:
Total Amps: 53 A 49 A 64 A
Total Load: 6267 5867 7667
29 SPACE -- -- 1 -- 3167 30
27 SPACE -- -- 1 -- 3167 28
25 RECEPTACLE PUBLIC WAITING 104 20 1 1 500 3367
3 1 50 'EM2'
23 TELE/DATA EQUIPMENT RACK 20 1 1 500 800 1 1 20 RECEPTACLE CONFERENCE MAJOR CASE 215A 24
21 TELE/DATA EQUIPMENT RACK 20 1 1 500 800 1 1 20 RECEPTACLE CONFERENCE MAJOR CASE 215A 22
19 REC CONFERENCE MAJOR CASE 215A 20 1 1 1000 1000 1 1 20 RECEPTACLE ROOM 215 - MONITORS 20
17 RECEPTACLE RTCC 215 20 E 1 1000 1000 1 E 20 RECEPTACLE ROOM 215 - MONITORS 18
15 EQUIPMENT 20 E 1 400 1000 1 E 20 RECEPTACLE ROOM 215 - MONITORS 16
13 EQUIPMENT 20 E 1 400 0 1 -- 20 RECEPTACLES 14
11 RECEPTACLE ROOM 215P 20 E 1 1200 0 1 -- 20 RECEPTACLES 12
9 FIRE PANEL 20 -- 1 0 0 1 -- 20 RECEPTACLES 10
7 CCTV CAMERA 20 -- 1 0 0 1 -- 20 RECETPACLES 8
5 CCTV CAMERAS 20 -- 1 0 0 1 -- 20 LIGHTING 6
3 LIGHTING FLOOR 20 -- 1 0 0 1 -- 20 RECEPTACLES 4
1 FACP 20 -- 1 0 0 1 -- 20 RECEPTACLES 2
CKT Circuit Description Trip * Pole A B C Pole * Trip Circuit Description CKT
Notes:
Contactor: NO
Enclosure: Type 1 Shunt Trip: NO
Mounting: RECESSED Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type: MLO
Location: Room 215I Volts: 120/208 Wye A.I.C. Rating: EXISTING
Panel: 'EM1'(E) Branch: EMERGENCY
CONDUIT & WIRING SCHEDULE
= 1" CONDUIT FOR PANEL 'EM-2' CIRCUIT FROM 'EM-1':
- (1) #8 HOT, (1) #8 NEUTRAL, & (1) #10 GROUND
- THHN/THWN-2 INSULATED CONDUCTORS
= 3/4" CONDUIT FOR 'SPD' CIRCUIT
- (1) #10 HOT, (1) #10 HOT & (1) #10 GROUND.
- THHN/THWN-2 INSULATED CONDUCTORS
= 1" CONDUIT FOR DOCK & REC CIRCUITS
- (3) SETS OF: (2) #10 HOT, & (1) #10 GROUND
- (1) #10 HOT, (1) #10 NEUTRAL, & (1) #10 GROUND
- THHN/THWN-2 INSULATED CONDUCTORS
= 3/4" CONDUIT FOR INDIVIDUAL DOCK CIRCUIT TO DISC
- (2) #10 HOT, & (1) #10 GROUND
- THHN/THWN-2 INSULATED CONDUCTORS
= 3/4" CONDUIT FOR INDIVIDUAL DOCK CIRCUIT
- (2) #12 HOT, & (1) #12 GROUND
- XHHW-2 INSULATED CONDUCTORS
= 3/4" CONDUIT FOR RECEPTACLE
- (1) #10 HOT, (1) #10 NEUTRAL, & (1) #10 GROUND
- THHN/THWN-2 INSULATED CONDUCTORS
A
B
C
D
E
CALCULATIONS:
90° RATED CONDUCTORS: THHN/THWN-2, UNO
100°F (40°C) ROOFTOP AMBIENT TEMP
@90°: #12 = 30A RATED, #10 = 40A RATED
CONDUIT & WIRE 'C':
1. #10 CONDUCTORS
2. CURRENT-CARRYING CONDUCTORS: 8 = 70% DERATE
3. OUTDOOR AMBIENT TEMP DE-RATE:
I' = I ((90°- 40°)/(90°- 30°))1/2 = 40A x 0.91 = 36.5 A
4. 36.5 A x 0.7 = 25.6 A
5. CONDUCTORS ARE ACCEPTABLE FOR EACH 20A CIRCUIT.
6. CONDUIT SIZE:
12 (#10) = 12 x 0.0211 IN2 = 0.2532 IN2
EMT MOST LIMITING TYPE: 40% FILL - 0.346 IN2 FOR 1" C.
CONDUIT & WIRE 'E':
1. #12 CONDUCTORS
2. CURRENT-CARRYING CONDUCTORS: 2 = NO DE-RATE
3. OUTDOOR AMBIENT TEMP DE-RATE:
I' = I ((90°- 40°)/(90°- 30°))1/2 = 30A x 0.91 = 27.3 A
A. ROOFTOP DE-RATE FOR RACEWAY LESS THAN 7/8"
ABOVE ROOF: UTILIZE XHHW-2 CONDUCTORS TO AVOID
33°C TEMP ADDER.
4. CONDUCTORS ARE ACCEPTABLE FOR THE 20A CIRCUIT.
F
PANELBOARD NOTES:
1. PROVIDE NEW EQUIPMENT AND CIRCUITRY. NEW BREAKER SHALL BE UL LISTED
FOR INSTALLATION IN PANELBOARD AND HAVE MATCHING KAIC RATING.
2. PROVIDE NEW EQUIPMENT IN ENTIRETY.
* Indicates Breaker Type: 1=Standard, 2=HACR (HVAC Rated), 3=6MA GFCI, 4=30MA GFCI, 5=Shunt Trip, 6=AFCI ** See Specifications for Panel Type
Legend:
Total Amps: 28 A 26 A 26 A
Total Load: 3367 3167 3167
17 167 0 18
15 167 0
2 -- 20 SPARE
SPD 30 1 3
167 0 14
11 1500 0
2 -- 20 SPARE
DOCK - FUTURE 20 -- 2
1500 0 1 -- 20 SPARE 10
7 1500 0 1 -- 20 SPARE 8
DOCK #1 - ROOF 20 1 2
1500 0 1 -- 20 SPARE 6
3 1500 0 1 -- 20 SPARE 4
DOCK - FUTURE 20 -- 2
1500 200 1 1 20 DRONE DOCK STAND REC - ROOF 2
CKT Circuit Description Trip * Pole A B C Pole * Trip Circuit Description CKT
Notes:
Contactor: NO
Enclosure: Type 1 Shunt Trip: NO
Mounting: RECESSED Wires: 4 Mains Rating: 100 A
Supply From: 'EM1'(E) Phases: 3 Mains Type: MLO
Location: Room 215I Volts: 120/208 Wye A.I.C. Rating: MATCH EXISTING
Panel: 'EM2' Branch: EMERGENCY
NO. DESCRIPTION DATE
Exp Date:
Seal Date: 06/15/2026
11/30/2027
DATA
ENCL
ROOF CONDUIT
MOUNTING SUPPORT 4
GRID CEILING(E)
WIDE FLANGE STRUCTURAL
FRAMING GIRDER, (E), TYP
MEMBRANE ROOF(E)
SIDE VIEW
5 NON-PENETRATING
ROOFTOP MOUNT
BALLASTED TRAY WELDMENT,
TYP OF 2
SUPPORT PLATE &
HARDWARE, TYP OF 4
CONDUIT OFFSET, TYP
STRUT MOUNTED TO
PIPE VIA U-BOLT
5" V-CLAMP, TYP OF 2
TRAINING/
MULTI-USE
STOR.
STORAGE
EMERGENCY
OPERATIONS
CENTER
STORAGE
STAIR
STORAGE
(FUTURE OFFICE)
EQUIP.
STORAGE
INTERVIEW STAIR COMMS RM
CORRIDOR
CORRIDOR
C O
R R
ID
O
R
C O
R R
ID
O
R
MENS TOILET
WOMENS TOILET
YOUTH WAITING
RECEPTIONIST
INTERVIEW
JANITOR
SERGEANTS
INVESTIGATIONS
C O
R R
ID
O
R
CORRIDOR
MECHANICAL
ROOM
INTERVIEW/
CONFERENCE
INTERVIEW
INTERVIEW
INTERVIEW
INTERVIEW INTERVIEW
INTERVIEW
INVESTIGATORS
ELEV.
STAIR
CORRIDOR
C O
R R
ID
O
R
C O
R R
ID
O
R
INVESTIGATIONS
LIEUTENANT
ANALYST
CRIME
TOILET
A
VEST.
212A
210A
VEST.
202 C
B
203A
203B
200A
VENDING
SECRETARY/
LOBBY
6 7 8 9
A
B
C
D
E
F
G
'CA'(E)'CDP'(E)
'EM1'(E)
'B'(E)
'A'(E)
OUT OF
SCOPE
J
4 6
5 6
FIRE ALARM
PANEL (E)
A
C
CONDUIT THRU-ROOF
PENETRATIONS TO
STRUCTURE
B
'SPD' 8
E-001
2 THRU-ROOF CONDUIT
ROUTING & DOCK
STRUCTURE DETAIL
'EM2'
7 8
E
F
G
POWER
ENCLOSURE
DATA
ENCLOSURE
WR/GF/WP
DOCK
DISCONNECT
TYP OF 3.
EXHAUST FAN (E), TYP
'EM2'-5,7
DOCK #1
'EM2'-2
1 CONDUIT ROOF
SUPPORTS, TYP
E-001
2THRU-ROOF CONDUIT
ROUTING & DOCK
STRUCTURE DETAIL
RADIO #1
RADIO #1
RADIO #3
F R
O N
T
E
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
401 Southwest Water Street Suite 701 Peoria, IL 61602
309.282.8000 Phone
IL DESIGN FIRM REG.
#184005007-0006
IL DESIGN FIRM REG.
#184000358-0001
/1
/2
:5
:1
A
M
ELECTRICAL
PLANS
JAM
GTR
JAM
06/15/2026
50193648
C
IT
Y O
F B
L O
O M
IN
G
T O
N P
O L
IC
E
D E
P A
R T
M E
N T
D R
O N
E I
N S
T A
L L
A T
IO
N
C
IT
Y O
F B
L O
O M
IN
G
T O
N
IS
S
U E
D F
O R
B
ID
D
IN
G A
N D
P E
R M
IT
S
O U
T H
E A
S T
S T
R E
E T
B L O
O M
IN
G
T O
N
IL
Dewberry Architects 401 SW Water Street, Suite 701 Peoria, Illinois 61602-1530 309.202.8100
E-100Scale: 1/8" = 1'-0"
SECOND FLOOR PLAN - ELECTRICAL
Scale: 1/4" = 1'-0"
LARGE SCALE ROOF PLAN - ELECTRICAL
GENERAL NOTES:
1. REFER TO SHEET #E-001 FOR GENERAL NOTES, SYMBOLS & ABBREVIATIONS THAT
PERTAIN TO THIS SHEET.
2. = REFER TO CONDUIT AND WIRING SCHEDULE ON SHEET #E-001 FOR SPECIFIC
RUN OF CIRCUITRY.
PLAN NOTES:
1. UNIPIER POLYCARBONATE BASE UNISTRUT MOUNTING SUPPORT - 24-BS-4, OR
EQUAL, FOR SUPPORT OF CONDUIT TO DOCKS & ANTENNAS VIA PIPE HANGERS. DO
NOT PENETRATE ROOF MEMBRANE WHEN MOUNTING STRUCTURE. UTILIZE ROOF &
FLASHING POLYURETHANE SEALANTS AT FLASHING EDGES. PROVIDE ALL
NECESSARY HARDWARE FOR INSTALLATION. SUPPORTS SHOWN WITHOUT
CONDUITS ARE UTILIZED FOR DATA. REFER TO TECHNOLOGY DRAWINGS FOR DATA
CONDUIT ROUTING.
2. 3/4" DOCK POWER CONDUIT FROM ASSOCIATED DISCONNECT TO DOCK.
GALVANIZED RIGID METALLIC CONDUIT FROM DISCONNECT ROUTED ALONG ROOF
MOUNTING SUPPORTS & LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT FROM LAST
ROOF MOUNTING SUPPORT TO DOCK. PROVIDE APPROPRIATE CONDUIT FITTINGS.
ROUTING IS SHOWN FOR REFERENCE ONLY AND ACTUAL ROUTING SHALL BE
DETERMINED IN THE FIELD.
3. WALL-MOUNTED JUNCTION BOX. SIZE AND PROVIDE ALL WALL MOUNTING
HARDWARE AS REQUIRED.
4. PERFORM THE FOLLOWING WORK AT EMERGENCY PANEL 'EM-1' IN THE MECHANICAL
ROOM 208.
A. PROVIDE NEW 50A/3P BREAKER AT CIRCUIT LOCATIONS '26', '28', & '30 AND
ASSOCIATED CIRCUITRY TO NEW PANEL 'EM-2'.
5. PROVIDE & INSTALL NEW SUB-PANELBOARD 'EM-2' AND FEED FROM EMERGENCY
PANEL 'EM-1'. NEW PANEL AND ASSOCIATED BREAKERS SHALL MATCH KAIC RATING
OF 'EM-1'.
6. REFER TO PANELBOARD SCHEDULE ON SHEET #E-001 FOR ADDITIONAL
INFORMATION. UPDATE PANELBOARD DIRECTORY AFTER ALL NEW LOADS ARE
ADDED PER THE SPECIFICATIONS.
7. CONDUIT ROUTING SHOWN FOR REFERENCE. COORDINATE EXACT ROUTING IN THE
FIELD.
8. PROVIDE NEW SURGE PROTECTIVE DEVICE TO SERVE NEW PANEL 'EM-2'.
A
0' 8' 16'4'
SCALE: 1/8" = 1' - 0"
0' 4' 8'2'
SCALE: 1/4" = 1' - 0"
NO. DESCRIPTION DATE
Exp Date:
Seal Date: 06/15/2026
11/30/2027
7 8
E
F
G
POWER
ENCLOSURE
DATA
ENCLOSURE
WR/GF/WP
DOCK
DISCONNECT
TYP OF 3.
EXHAUST FAN (E), TYP
'EM2'-5,7
DOCK #1
'EM2'-2
1 CONDUIT ROOF
SUPPORTS, TYP
E-001
2THRU-ROOF CONDUIT
ROUTING & DOCK
STRUCTURE DETAIL
RADIO #1
RADIO #1
RADIO #3
F R
O N
T
E
Scale: 1/4" = 1'-0"
LARGE SCALE ROOF PLAN - ELECTRICAL
0' 4' 8'2'
SCALE: 1/4" = 1' - 0"
7 8
E
F
G
POWER
ENCLOSURE
DATA
ENCLOSURE
WR/GF/WP
DOCK
DISCONNECT
TYP OF 3.
EXHAUST FAN (E), TYP
'EM2'-5,7
DOCK #1
'EM2'-2
CONDUIT ROOF
SUPPORTS, TYP
E-001
2THRU-ROOF CONDUIT
ROUTING & DOCK
STRUCTURE DETAIL
RADIO #1
F R
O N
T
E
Scale: 1/4" = 1'-0"
LARGE SCALE ROOF PLAN - ELECTRICAL
0' 4' 8'2'
SCALE: 1/4" = 1' - 0"
TECHNOLOGY SYMBOL LEGEND
SYMBOL DESCRIPTION SPECIFICATION SECTION BACK BOX MOUNTING HEIGHT NOTESCONDUIT SIZEWIRING REQUIREMENTS
TELECOMMUNICATIONS DATA CONNECTION 1" N/A27 15 00 1N/ACATEGORY 6 4 PAIR UTP, CMP, UON
TELECOMMUNICATIONS DATA CONNECTION. UNDER DIVISION 26 SCOPE OF WORK, FURNISH AND INSTALL RACEWAY SYSTEM. UNDER DIVISION 27 SCOPE OF WORK, FURNISH AND
INSTALL CABLE, J-HOOKS, CONDUIT, AND CONDUIT BASE.1
TECHNOLOGY SYMBOL LEGEND KEYED NOTES: TECHNOLOGY GENERAL NOTES:
1. INDICATED MOUNTING HEIGHTS ARE FOR DESIGN PURPOSES ONLY. COORDINATE FINAL MOUNTING HEIGHT OF ALL EQUIPMENT WITH SURROUNDING EQUIPMENT AND SURROUNDING CONDITIONS. MOUNTING HEIGHTS
INDICATED ARE TO CENTER OF BOX.
2. CABLE WILL BE CMP.
3. CATEGORY 6A CABLING USED FOR IN-SLAB FLOOR BOXES SHALL BE INDOOR/OUTDOOR RATED CABLING.
4. STORE EQUIPMENT IN A CLEAN AND DRY PLACE UNTIL READY FOR INSTALLATION.
5. PROTECT FROM WEATHER, THEFT, DIRT, FUMES, WATER, CONSTRUCTION DEBRIS, ETC., AT ALL TIMES.
DAMAGED EQUIPMENT WILL BE RESTORED TO LIKE NEW CONDITION OR REPLACED BY THE CONTRACTOR.
6. CLEAN ALL EQUIPMENT TO PRESENT A "NEW" CONDITION AT PROJECT COMPLETION. VACUUM, CLEAN
INTERNAL AREAS OF EQUIPMENT RACKS AND ENCLOSURES.
7. CONTRACTOR IS REQUIRED TO ACCOMMODATE INCIDENTAL MOVEMENT OF THE FIELD DEVICES AS
DIRECTED BY THE ARCHITECT FROM THE LOCATION INDICATED UP TO 10 FEET PROVIDED THE DEVICE
ROUGH IN HAS NOT COMMENCED.
8. NO CONDUIT LARGER THAN 2" SHALL BE USED FOR THE HORIZONTAL STRUCTURED CABLE.
9. ALL TELECOMMUNICATIONS CONDUIT SHALL HAVE LONG RADIUS BENDS.
10. REFER TO RISER DIAGRAMS FOR ADDITIONAL WIRING REQUIREMENTS. FURNISH AND INSTALL ALL
ADDITIONAL WIRING REQUIRED TO COMPLETE THE RISERS.
11. ALL ASPECTS OF THE STRUCTURED CABLE SYSTEM ARE TO BE INCLUDED IN THE CONTRACT.
12. ELECTRICAL METALLIC TUBING (EMT); CONDUIT SHALL BE FORMED FROM COLD-ROLLED STRIP STEEL, AND
SHALL MEET ANSI AND UL REQUIREMENTS. FITTINGS IN DRY LOCATIONS MAY BE SCREW TYPE WITH INSULATED PLASTIC BUSHINGS. BENDS WILL BE AT LEAST TEN (10) TIMES THE INTERNAL DIAMETER OF THE
CONDUIT SIZE.
13. ALL COMMUNICATIONS CABLE SHALL BE A CONTINUOUS RUN FROM THE COMMUNICATIONS WIRING CLOSET
TO THE OUTLET FREE OF ANY SPLICES OR TAPS.
14. CONDUIT, CABLE TRAY, OR J-HOOKS SHALL BE USED TO SUPPORT ALL WIRE.
15. ALL WIRE RUNS SHOULD FOLLOW THE SHORTEST PATH POSSIBLE. IF ANY RUNS EXCEED 90 METERS, OR
LENGTHS SPECIFIED IN THE REFERENCE AND REGULATIONS THE CONTRACTOR SHOULD NOTIFY THE
ARCHITECT IMMEDIATELY.
16. PATCH PANELS SHALL BE MOUNTED ON 19-INCH RELAY RACKS. PROPER WIRE MANAGEMENT AND
SUPPORTS ARE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE PROVIDED.
17. THE PATCH PANELS SHALL LABELED AS PER THE WIRE NUMBERING SCHEME.
18. CABLE TRAYS ARE TO BE MOUNTED TO SUPPORT WIRING ABOVE AND BETWEEN THE RACKS AND WALL
FIELD. ALL WIRING SHOULD BE RUN THROUGH THE CABLE TRAY AND DROP DOWN AT THE POINT OF
TERMINATION.
19. CABLING ROUTED ABOVE THE CEILING SHALL BE SUPPORTED UTILIZING J-HOOKS MOUNTED 5'-0" ON
CENTER.
20. CATEGORY 6A CABLE LENGTHS SHALL NOT EXCEED 295' IN LENGTH.
21. CABLING IN PUBLIC SPACES SHALL BE INSTALLED ABOVE ACCESSIBLE CEILINGS USING J HOOKS, OR
CONCEALED IN CONDUIT. NO EXPOSED CABLE SHALL BE VISIBLE TO THE STAFF OR PUBLIC.
22. REFERENCE FURNITURE/ARCHITECTURAL DRAWINGS FOR DIMENSIONING OF FLOOR BOXES AND OTHER
DEVICES.
23. REFERENCE ELECTRICAL DRAWINGS FOR COORDINATION OR POWER.
24. 'RACEWAY SYSTEM' INCLUDES ALL CONDUITS, BACKBOXES, FITTINGS, PLASTIC BUSHINGS OR GROMMETS, STRUCTURAL, CABLE TRAYS, GROUNDING BUSHINGS, AND PULL STRINGS/PULL ROPES. THE DIVISION 27
CONTRACTOR SHALL PROVIDE J-HOOKS
25. REFER TO DIVISION 26 DRAWINGS AND SPECIFICATIONS FOR FIRE STOPPING SYSTEM REQUIREMENTS.
26. CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE SIZED AS FOLLOWS:
(MAXIMUM NUMBER OF UTP CABLES PER TRADE SIZE)
1"
1-1/4"
1-1/2"
2"
ABBREVIATIONS
ABA - ARCHITECTURAL BARRIERS ACT
AC - ABOVE COUNTER
ACT - ACOUSTIC TILE CEILING
ACS - ACCESS CONTROL SYSTEM
ADA - AMERICANS WITH DISABILITIES ACT
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE
API - APPLICATION PROGRAMMING INTERFACE
ATS - AUTOMATIC TRANSFER SWITCH
AWG - AMERICAN WIRE GAUGE
BAS - BUILDING AUTOMATION SYSTEM
BBC - BACKBONE BONDING CONDUCTOR
BLDG - BUILDING
BMS - BUILDING MANAGEMENT SYSTEM
CATV - COMMUNITY ANTENNA TELEVISION
CCTV - CLOSED CIRCUIT TELEVISION
CLG - CEILING
CMP - COMMUNICATIONS MULTIPURPOSE CABLE PLENUM
CMR - COMMUNICATIONS MULTIPURPOSE CABLE RISER
COMM - COMMUNICATION
CU - COPPER
DB - DUCTBANK
DC - DIRECT CURRENT
DWG - DRAWING
EF - ENTRANCE FACILITY
EIA - ELECTRONIC INDUSTRIES ALLIANCE
ELEC - ELECTRIC, ELECTRICAL
EMT - ELECTRICAL METALLIC TUBING
F/UTP - OVERALL FOIL SHIELD TWISTED PAIR
FLR - FLOOR
FO - FIBER OPTIC
FURN - FURNITURE
GND - GROUND
GRC - GALVANIZED RIGID METALLIC CONDUIT
HH -…