BACKUP_AOC_IFB_DRAWINGS.pdf
PDF 17 MB Posted
- Solicitation number
- 26-008-ITB
- Issued by
- Bell County, Kentucky
About this file
This is a set of electrical design drawings and specifications for the Backup Airport Operations Center (AOC) Interior Modifications at the South ARFF Fire Station, 2100 Tower Drive, Hebron, Kentucky, prepared by Emboss Design, P.S.C. for the Kenton County Airport Board. The drawings document comprehensive electrical work including demolition plans, overall electrical plans, enlarged floor plans for the backup AOC area, and detailed installation specifications. Key electrical systems include power distribution from the existing switchboard to new panels (EMA, EMA1, and AOC), installation of an 8 kilowatt-hour UPS system, a 15 kilowatt-hour transformer for the AOC, lighting controls with occupancy sensors, fire alarm integration, data and voice cabling infrastructure, and various receptacle and device installations throughout the facility. The project includes relocation of existing equipment such as the Honeywell workstation and rolling door controls, demolition of abandoned panels and associated wiring, and coordination with multiple trades for HVAC, mechanical, and structural work. A pre-bid meeting and site visit are scheduled for Thursday, February 26, 2026 at 1:00 pm. Written questions must be submitted by 11:59 pm on Monday, March 9, 2026, with answers posted by Thursday, March 12, 2026. Sealed bids are due by Thursday, March 19, 2026 at 2:00 pm at the South ARFF Station location.
The drawings indicate that contractors must provide all conduit, cabling, devices, power connections, and installation labor for systems designated as "Contractor Furnished, Contractor Installed" (CFCI), while coordinating with owner-provided equipment and existing systems. All work must comply with the latest editions of the National Electrical Code (NEC), NFPA standards, and local building codes. The contractor bears responsibility for site verification, coordination with all trades, shop drawing submissions for approval, testing and commissioning of all systems, and provision of four hours of training for each system as required by the owner. All materials and equipment must be listed and labeled by Underwriter's Laboratories or equivalent, installed in a neat and workmanlike manner, and guaranteed for one full calendar year from substantial completion. Specific mounting heights, cable tray specifications, device color selections, and equipment nameplate requirements are detailed throughout the drawings, with contractors instructed to contact system vendors for pricing and exact installation requirements prior to bid submission.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SD
UON
EM
CFOI
OFOI
CFCI
OFCI
J
DESCRIPTION
S
OS
POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES
SLASH THROUGH ANY DEVICE INDICATES MOUNTING
ABOVE COUNTERTOP 2" ABOVE BACKSPLASH, OR AT
48" WHERE NO COUNTER IS PRESENT
VS
LV
FILLED CENTER BAR INDICATES INTEGRAL GROUND
FAULT PROTECTION (GFCI)
NON-REVERSING MOTOR STARTER SNAP SWITCH
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
PHOTO-ELECTRIC SMOKE DETECTOR
MAIN CONTROL PANEL CENTRAL PROCESSING
UNIT (CPU)
LIGHT SWITCH:GENERAL PURPOSE
AS NOTED
6'-6'' TO
TOP
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
46"
ABBREVIATIONS
POWER OUTLETS
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
JUNCTION BOX, CEILING OR WALL
OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT
LOW VOLTAGE SWITCH ON OFF WITH ZONES
CLG
46"
46"
1'-6"
1'-6"
1'-6"
CLG
S
S M
M O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
IN
G
S
Y M
B O
L
ADDRESSABLE RELAY MODULE R
CONDUIT CONCEALED IN WALLS OR IN CEILING
SPACE: ARROW(S) INDICATE(S) HOME RUN & #
OF CIRCUITS: HASHMARKS INDICATE # OF
CONDUCTORS. DASHED LINE INDICATES
CONDUIT BELOW FLOOR.
PANELBOARD, SURFACE OR FLUSH MOUNTED,
HATCHING INDICATES EMERGENCY
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
AS NOTED
MISCELLANEOUS
DISCONNECT SWITCH
TRANSFORMER
TAGGED NOTE
CONDUIT PATH
5'-0"
6'-6'' TO TOP
C A
B L
IN
G C
O N
D U
C T
O R
S
O F
O I
C A
B L
IN
G
C O
N D
U C
T O
R S
O
F C
I
C O
N D
U
IT
R
O U
G H
-I N
O
F O
I
IT
E
M U
S E
D O
N P
R O
J E
C T
D E
V
IC
E S
O
F C
I
D E
V
IC
E S
C
F C
I
SYSTEM D
E
V
IC
E S
O
F O
I
SYSTEM
RESPONSIBILITY
MATRIX
DATA
SYSTEM RESPONSIBILITY GENERAL NOTES:
A. CMTA IS NOT RESPONSIBILE FOR ASSIGNING SCOPE(S) OR WORK. THE INTENT OF
CONTRACTOR IN THIS MATRIX IS TO SEPERATE OWNER PROVIDED ITEMS FROM THE
GENERAL CONTRACTOR / CONSTRUCTION MANAGER. THE GC OR CM SHALL BE
RESPONSIBLE FOR A COMPLETE SCOPE OF WORK.
B. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO
VENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS SHALL
BE INCLUDED BY THE CONTRACTOR.
C. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS CONTROL
DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.
D. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.
CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT
INSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL
SYSTEMS PRIOR TO CONSTRUCTION.
E. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS, CONTRACTOR
SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO CABLE PATHS AS
REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS AT CABINETS/ON
BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH APPROPRIATE
VENDORS PRIOR TO CONSTRUCTION.
F. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS
INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING,
LABELING, ETC.
G. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM
COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE
CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID. ALL
SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY COMPATIBLE
WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL COORDINATE EXACT
SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW COMPONENTS SHALL BE
INTERCONNECTED WITH EXISTING SYSTEMS WHERE POSSIBLE. ALL NEW SYSTEM
DESIGNS AND PROGRAMMING SHALL BE COORDINATED WITH THE OWNER PRIOR TO
ORDERING. ALL PROGRAMMING SHALL BE INCLUDED AS REQUIRED BY THE OWNER.
PROVIDE 4 HOURS OF TRAINING FOR EACH SYSTEM.
SWITCHES
FIRE ALARM
E,EMINDICATES EMERGENCY POWER
NAC
FACP
AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED
EQUIP-1
GROUND
NEUTRAL
PHASE
, J
#D/#V
#D
INTERMEDIATE DISTRIBUTION FRAME - REFERENCE
DATA SYSTEM SCHEMATICS AND DETAILS FOR
ADDITIONAL REQUIREMENTS
MAIN DISTRIBUTION FRAME - REFERENCE DATA
SYSTEM SCHEMATICS AND DETAILS FOR ADDITIONAL
REQUIREMENTS
WIRELESS ACCESS POINT WITH PROVISIONS FOR (1
DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE
DATA OUTLET WITH FACEPLATE ABOVE CEILING,
MOUNTED AT AN ACCESSIBLE HEIGHT NO MORE THAN
24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A 20'
COIL OF CABLE AHEAD OF THE OUTLET FOR
ADJUSTMENT OF FINAL OUTLET LOCATION. THE
CONTRACTOR SHALL COORDINATE EXACT LOCATIONS
WITH THE OWNER AND ADJUST OUTLET LOCATIONS AT
SUBSTANTIAL COMPLETION TO ACCOMMODATE
OWNER'S WAP LOCATIONS. WAP'S ARE OWNER-
FURNISHED, OWNER-INSTALLED
WAP
DATA OUTLET : NUMBER BESIDE OUTLET
INDICATES NUMBER OF DATA JACKS
VOICE OUTLET : NUMBER BESIDE OUTLET
INDICATES NUMBER OF VOICE JACKS
COMBINATION OUTLET : NUMBER BESIDE OUTLET
INDICATES NUMBER OF DATA/VOICE JACKS
DATA / VOICE
1'-6"
1'-6"
1'-6"
#V
MDF
IDF
GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''
DESCRIPTION M
O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
M
B O
L
DESCRIPTION M
O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
M
B O
L
DESCRIPTION
LV#S,
W H
IT
E
DEVICE
WALL SWITCHES
DEVICE COLOR
MATRIX
RECEPTACLE (NORMAL)
DEVICE COLOR GENERAL NOTES:
A. DEVICE PLATE TO MATCH DEVICE UNLESS NOTED OTHERWISE.
B. NOT ALL DEVICES MAYBE USED THAT ARE SHOWN.
C. IF DEVICE COLOR NOT DEFINED REFER TO SPECIFICATIONS.
DESCRIPTION
IV
O
R Y
R E
D
O R
A N
G E
B L
U E
Y E
L L O
W
C U
S T
O M
S T
A
IN
L E
S S
S T
E E
L
LEGEND
INDICATES SELECTED COLOR
INDICATES COLOR NOT AVAILABLE
INDICATES COLOR NOT SELECTED
LEGEND
INDICATES SELECTED SYSTEM
INDICATES NOT AVAILALBE
INDICATES NOT SELECTED
C O
N D
U
IT
R
O U
G H
-I N
O
F C
I
C O
N D
U
IT
R
O U
G H
-I N
C
F C
I
C A
B L
IN
G
C O
N D
U C
T O
R S
C
F C
I
P R
O G
R A
M M
IN
G
S
E T
U P
O
F O
I
P R
O G
R A
M M
IN
G
S
E T
U P
O
F C
I
P R
O G
R A
M M
IN
G
S
E T
U P
C
F C
I
ST
SECURITY: ACCESS CONTROL
CONDUIT PATH UNDERNEATH RAISED FLOOR
FIRE ALARM
HONEYWELL SYSTEM
PUSHBUTTON STATION 46"
RECEPTACLE (UPS)
RECEPTACLE (ISOLATED GROUND)
T E
R M
IN
A
T
IO
N S
O
F C
I
T E
R M
IN
A
T
IO
N S
C
F C
I
T E
R M
IN
A
T
IO
N S
O
F O
I
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 0 0 0
E L E C T R I C A L L E G E N D
ELECTRICAL GENERAL NOTES:
A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS
PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT
WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.
B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE
UNDERSTANDING OF THE PROJECT REQUIREMENTS.
C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.
INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.
D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.
F. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING
OR THE COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.
G. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOW CLARIFICATION BY WRITTEN ADDENDUM.
H. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.
I. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND
MUST BE SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.
J. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).
K. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.
L. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE
ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.
M. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE
RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.
N. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.
O. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER.
WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER
P. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY
PERIODS FOR EQUIPMENT ARE SPECIFIED.
Q. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.
R. COORDINATE WITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEWORK DETAILS FOR LOCATION OF
ADDITIONAL RECEPTACLES, UTILITY OUTLETS, ELECTRICAL DEVICES, ETC.
S. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.
T. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE
ENGINEER.
U. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT V. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE
THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY
OF THE PURCHASER.
W. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS
PROJECT.
X. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.
Y. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS
REQUIRED TO MAINTAIN CEILING RATINGS.
Z. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE
CONTRACTOR(S).
AA. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE
ENGINEER IN WRITING.
BB. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL
POINT.
CC. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER
TRADES (I.E. VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.
DD. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL APPLY.
EE. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN
PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.
FF. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS
NEEDED.
GG. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND EQUIPMENT. IF IN DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.
HH. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK
FROM PHASE TO PHASE.
II. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.
JJ. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.
KK. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND
TRANSMISSION FROM ROOM TO ROOM.
LL. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH
SPECIFICATIONS, WHICHEVER IS MORE STRINGENT.
MM. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST
STRINGENT SHALL APPLY.
NN. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM
DIMENSIONED DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.
OO. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO
CONSTRUCTION.
PP. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO
CONSTRUCTION.
QQ. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. WORK SHALL BE COMPLETED IN PHASES PER THE PHASING PLAN AND AS COORDINATED WITH OWNER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS REQUIRED BY OWNER
TO ACCOMPLISH THE PHASING PLAN.
ELECTRICAL DEMOLITION NOTES:
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE
EXISTING ITEMS TO REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT
CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN
ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR
SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM"
ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER"
CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS
SPARES IN THEIR PANELS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS
AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE
TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO
VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE
INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK
INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT
THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES /
FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), WHETHER INDICATED OR NOT
(UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING WALLS, FLOORS OR
CEILINGS WHERE DEVICES ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO
RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION)
WITH OWNER. TURN OVER ITEMS REMOVED TO OWNER AT THEIR OPTION.
F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF
ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.
G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS
REQUIRED.
H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGS AS REQUIRED
WHERE DEVICES ARE BEING REMOVED OR INSTALLED.
I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL
BE REMOVED IN ACCORDANCE WITH NEC REQUIREMENTS.
J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALL BE
RELOCATED TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENT SHOWN ON PLANS.
K. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE, PROTECT, AND
REINSTALL IN NEW LOCATION INDICATED ON NEW WORK PLANS. INTERCEPT AND
EXTEND ALL EXISTING CABLING TO NEW LOCATION. CLEAN AND RE-LAMP RELOCATED
LUMINAIRES.
L. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL BE PROVIDED
WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL
DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAWINGS.
DIRECTORIES SHALL BE DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS,
FINAL ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSED
BREAKERS SHALL BE IN OFF POSITION.
GENERAL NOTES (LIGHTING):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK
DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL
DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE
FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH
BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL
CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE
INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER
N.E.C. #310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER N.E.C. #300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN N.E.C #100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN
AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.
GENERAL NOTES (POWER):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK
DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL
DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE
FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH
BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL
CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE
INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER
NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX
C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN
AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.
MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.
D. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE
COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS
AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF
REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS.
DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS
PANELS OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER
TRADES.
J
J
J
J
SD
J
GEN ANN PANEL
EXIST
BASEBOARD
HEATER
M
M
EXIST
BASEBOARD
HEATER
EMA #42
CRASH PHONE
EXIST.
DESK/CONSOLES
DE2
DE7
DE6
DE5
DE5
EMA 11
DUPLEX AND IN LINE FAN
EMA-40
SPARE TO ALARM ROOM
DE3
DE11
DE16
DE6
DE14
DE8
DE4
(TYP)
DE9
DE13
R R
R R
R
DE15
MAIN ELEC.
ROOM
IDF ROOM
E001
DE12
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 0 0 1
E L E C T R I C A L D E M O L I T I O N P L A N
SCALE:E001 1/2" = 1'-0"
2 CONTROL TOWER ELECTRICAL DEMOLITION PLAN
TAGGED NOTES
DE2 DEMOLISH ALL WIRING ASSOCIATED WITH CRASH PHONE.
COORDINATE WITH CVG COMMUNICATIONS CONSULTANT.
OTHER DEVICES CONNECTED TO SYSTEM MUST REMAIN
OPERATIONAL DURING CONSTRUCTION.
DE3 DEMOLISH EXISTING CONNECTED SMOKE DETECTOR SITTING
ON DESK. PRESERVE WIRING FOR NEW SMOKE DETECTOR IN
NEW WORK PHASE.
DE4 DEMOLISH EXISTING ABANDONED FIRE ALARM PANEL.
REMOVE WIRING BACK TO SOURCE.
DE5 DEMOLISH ALL ELECTRICAL CONNECTIONS AND WIRING TO
EXISTING BASEBOARD HEATER. BASEBOARD HEATERS TO BE
REMOVED BY OWNER'S MECHANICAL CONTRACTOR.
DE6 EXISTING VRF AND INLINE FAN TO REMAIN.
DE7 DEMOLISH PATHWAYS FOR GARAGE DOOR CONTROL WIRING
INSIDE DESK. GARAGE DOOR CONTROLS TO BE RELOCATED IN
NEW WORK PHASE.
DE8 DEMOLISH PLUG MOLD. DEMOLISH WIRING BACK TO STUB OUT
INTO CONTROL TOWER ROOM.
DE9 PROTECT AND REMOVE EXISTING LIGHT FIXTURES. EXISTING
FIXTURES TO BE INSTALLED IN NEW ACT CEILING IN NEW
WORK PHASE. PRESERVE EXISTING WIRING SERVING LIGHT
FIXTURES. FIXTURES TO BE RECONNECTED TO EXISTING
CIRCUIT.
DE11 DEMOLISH ALL ELECTRICAL POWER STRIPS, LOW VOLTAGE
CABLING, AND ELECTRICAL BRANCH WIRING INSIDE EXISTING
DESK CONSOLE.
DE12 EXISTING HONEYWELL IN THIS LOCATION TO BE RELOCATED
TO AOC TOWER. DEMOLISH ANY LOW-VOLTAGE CABLING
ASSOCIATED WITH SYSTEM BACK TO HONEYWELL SWITCH.
DE13 EXISTING GENERATOR ANNUNCIATOR PANEL TO REMAIN.
DE14 PRESERVE ALL CONDUIT AND BRANCH WIRING FROM PANEL
EMA. EMA CIRCUITS TO BE REUSED IN NEW WORK PHASE.
DE15 DEMOLISH DEVICE AND WIRING. PROVIDE COVER PLATE FOR
DEMOLISHED DEVICE LOCATION.
DE16 EXISTING CONDUIT STUBBING UP THROUGH DECK UNDER
RAISED FLOOR TO REMAIN. VERIFY WHETHER EXISTING
CONDUIT CAN BE REUSED FOR NEW LOW VOLTAGE CABLING
FROM IDF AND MDF.
DEMOLISH ALL DEVICES
AND WIRING
INSIDE DESK
CONSOLES.
DEMOLISH POWER
SERVING
POWER STRIPS
INSIDE DESK BACK
TO SOURCE.
DEMOLISH/REWORK ALL EXISTING
WIRING LOCATED UNDERNEATH
EXISTING RAISED WOOD
SHEATHING PLATFORM.
COORDINATE WITH CVG TO
REROUTE ANY ACTIVE WIRING
PRIOR TO DISCONNECTION.
2" C.
SCALE:E001 1" = 30'-0"
1 OVERALL ELECTRICAL DEMOLITION PLAN
SEE SHEET E-101 FOR
ENLARGED VIEW OF AOC
(E)SWBD
EXISTING
HONEYWELL SWITCH
EXISTING MDF
EXISTING IDF
E100
E100
E10
E11
E12 E13
(2) #8 AWG CU &
(1) #10 AWG CU GND IN
3/4" EMT
TO T-AOC
EMA-6
EMA-7
EMA-9
EMA1-33
EMA1-34
EMA1-36
EMA1-38
1-1/2" EMT
EMA1-40
EMA1-42
EMA1-19
EMA1-21
EMA1-31
EMA1-41
1" EMT
(E)EMA1
(E)T-EMA
(E)EMA
(E)EMB
E14
E101
E101
(E)DP-1
E19
E22
E23
MEZZANINE
LEVEL
E1
EXISTING PHONE
EXIST PHONE
E1
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 1 0 0
E L E C T R I C A L O V E R A L L P L A N S
TAGGED NOTES
E1 RELOCATE ROLLING DOOR CONTROLS TO NEW LOCATION.
REWORK PATHWAYS AND CABLING FOR WIRING AS NEEDED
TO RECONNECT CONTROL WIRING TO GARAGE DOORS.
VERIFY CABLING TYPE WITH CVG ARFF.
E10 PROVIDE AND INSTALL NEW CONDUIT AND CONDUCTORS
FROM SWBD IN MAIN ELECTRICAL ROOM TO T-AOC IN AOC
TOWER. SEE SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
E11 STUB CONDUITS SERVING AOC THROUGH WALL INTO
UNOCCUPIED SHAFT AND TURN UP TO SECOND FLOOR. SEE
E-101 FOR STUB OUT LOCATION INTO AOC TOWER.
E12 EXISTING HONEYWELL WORKSTATION IN CORRIDOR TO BE
RELOCATED TO AOC TOWER BY OWNER. PULL NEW RED
CAT5 FROM HONEYWELL SWITCH IDF ROOM TO NEW
WORKSTATION LOCATION IN NEW AOC TOWER. VERIFY
WHETHER EXISTING CONDUITS SERVING RAISED FLOOR CAN
BE REUSED FOR AOC TOWER CABLING. VERIFY DATA
CABLING TYPE AND QUANTIY WITH CVG IT DEPARTMENT.
E13 PROVIDE/VERIFY PATHWAY AND DATA CABLING FOR AOC
CPUS FROM EXISTING IDF ROOM UP INTO RAISED SHEATHED
FLOORING SPACE IN AOC. VERIFY WHETHER EXISTING
CONDUITS SERVING RAISED FLOOR CAN BE REUSED. VERIFY
DATA CABLING TYPES AND QUANTITIES WITH CVG IT
DEPARTMENT.
E14 PROVIDE AND INSTALL NEW CONDUIT AND BRANCH WIRING
FROM EMA AND EMA1 TO AOC TOWER. RUN CONDUIT FROM
PANELS IN MEZZANINE AREA DOWN TO ABOVE FIRST FLOOR
CEILING. FOLLOW PATH OF EXISTING EMA CIRCUITS SERVING
AOC TOWER.
E19 PROVIDE AND INSTALL NEW ISOLATED GROUND BAR INSIDE
INSIDE PANEL EMA. PULL #6 IG CONDUCTOR INSIDE EXISTING
CONDUIT FROM NEW GROUND BAR IN PANEL EMA TO
EXISTING GROUND BAR INSIDE TRANSFORMER TX-2.
TERMINATE IG RECEPTACLE CONDUCTORS ON NEW IG
GROUND BUSBAR.
E22 PROPOSED T-AOC FEEDER CONDUIT ROUTING. CONTRACTOR
TO CONFIRM FINAL ROUTING WITH CVG PRIOR TO
INSTALLATION.
E23 CONTRACTOR TO CONFIRM EXISTING LOCATION OF LOW
VOLTAGE CONDUIT SERVING TOWER. REUSE AS NECESSARY.
SCALE:E100 1/16" = 1'-0"
1 OVERALL ELECTRICAL PLAN
SCALE:E100 1/4" = 1'-0"
2 ELECTRICAL ENLARGED PLAN EAST
SCALE:E100 1/4" = 1'-0"
3 ELECTRICAL ENLARGED PLAN WEST
CR
J
J
J
J
FSD
J
J
J
J
KP
OS
OS
ER
GEN ANN PANEL
NEW 8KVA
UPS
M
M
AOC
VRF
IN-LINE OA FAN
E6
T-AOC
D-UPS
E6
E6
E6
60AF
50AT
-21EMA1
-19EMA1
-31EMA1
-40EMA1
-1AOC
-34EMA1
-9EMA
-2AOC
-33EMA1
-6EMA
-4AOC
-36EMA1
-6AOC
-7EMA
-42EMA1
-38EMA1
-3AOC
AOC-6
3/4" EMT.
AOC-2
AOC-4
EMA-6
EMA1-36
EMA1-33
3/4" EMT
3/4" EMT
3/4" EMT
EMA-7
EMA1-42
EMA1-19
EMA1-31
3/4" C.
EMA1-40
EMA1-42
EMA1-19
EMA1-21
EMA1-31
EMA1-41
1" EMT
AOC-1
AOC-2
AOC-3
AOC-4
EMA-6
EMA-9
EMA1-33
EMA1-34
EMA1-36
EMA1-38
2" EMT EMA-6
EMA-7
EMA-9
EMA1-33
EMA1-34
EMA1-36
EMA1-38
1-1/2" EMT
3/4" C.
(3) #8 AWG CU &
(1) #10 AWG CU GND IN
3/4" EMT
E4
E2
E5
E5
E5 E5
E7
E7
E7
E7
(TYP)
E8
(TYP)
E8
(TYP)
E8
E9
E9
E9
ELECTRICAL DEVICE COLOR LEGEND
UPS POWER
ISOLATED GROUND
"SHORE" (UTILITY) POWER
PURPLE LINES DENOTE ACCESS PANELS IN RAISED FLOOR
E16
E17
E17
E17
E18
E20
E20
E20
E21
E21
E21
E24
-41EMA1
E25
(TYP)
E3
LV1AOC
-40EMA
R R R
RR
E15
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 1 0 1
B A C K U P A O C E N L A R G E D P L A N S
TAGGED NOTES
E2 VERIFY EXISTING 2" CONDUITS STUBBING THROUGH AOC
ROOM DECK INTO RAISED FLOOR SPACE CAN BE USED AS
PATHWAY FOR AOC LOW VOLTAGE AND DATA CABLING.
E3 CONTRACTOR TO INSTALL OWNER-PROVIDED LIGHT
FIXTURES.
E4 VERIFY BRANCH POWER CONNECTION TYPE FOR
HONEYWELL UNIT WITH OWNER.
E5 PROVIDE 6" WIDE BY 3" DEEP SOLID SINGLE-CHANNEL CABLE
TRAY. RUN CABLE TRAY UNDER RAISED WOOD SHEATHING
PLATFORM AS SHOWN. SEE DETAIL ON E200.
E6 PROVIDE 16"X16" ACCESS PANEL IN RAISED FLOOR.
E7 RUN CONDUIT AS SHOWN TO JUNCTION BOX UNDER RAISED
ACCESS PANEL. SWITCH TO LFMC CONDUIT TO STUB BRANCH
CIRCUITS UP THROUGH RAISED ACCESS PANEL IN FLOOR
AND HOLES IN BOTTOM OF XYBIX CABINET. LAND BRANCH
CIRCUITS ON SURFACE-MOUNT RECEPTACLES INSIDE
CABINET.
E8 MOUNT RECEPTACLES AND GROUND BAR INSIDE CPU
CABINET. SEE OWNER SPECIFICATIONS FOR DEVICE
COLORS. VERIFY EXACT MOUNTING LOCATION FOR EACH
RECEPTACLE INSIDE CPU CABINET WITH OWNER.
E9 REFER TO XYBIX DRAWINGS FOR LOCATIONS AND
DIMENSIONS OF ACCESS HOLES TO BE DRILLED IN THE
BOTTOM OF CPU CABINETS.
E15 PROVIDE EMERGENCY TRANSFER DEVICE FOR FIXTURES.
WHEN NORMAL POWER IS AVAILABLE, TRANSFER DEVICE
SHALL ALLOW LIGHTING CONTROLS TO CONTROL LIGHTING
FIXTURES (WITH FULL DIMMING CONTROL). WHEN NORMAL
POWER IS LOST, EMERGENCY TRANSFER DEVICE SHALL
TURN ON ALL EMERGENCY FIXTURES TO 100% REGARDLESS
OF POSITION OF LOCAL SWITCHING.
E16 STUB CONDUIT FROM UNOCCUPIED SHAFT THROUGH WALL
ABOVE BACKUP AOC CEILING. SEE E-100 FOR CONTINUATION
DOWN TO FIRST FLOOR CEILING
E17 STUB CONDUIT FROM UNOCCUPIED SHAFT THROUGH WALL
BETWEEN DECK AND AOC RAISED FLOOR. CONTINUE
CONDUIT RUN UNDER AOC RAISED FLOOR. SEE E-100 FOR
CONTINUATION DOWN TO FIRST FLOOR CEILING.
E18 SUSPEND TRANSFORMER FROM ROOF STRUCTURE ABOVE.
PROVIDE CEILING SUPPORTS AND TILES COMPLETELY
AROUND TRANSFORMER SUPPORTS TO CONCEAL AS MUCH
AS POSSIBLE. REFER TO DETAIL 3 ON SHEET E201 FOR MORE
INFORMATION.
E20 RUN (2) GROUNDS FOR ISOLATED GROUND RECEPTACLE. AT
RECEPTACLE, TERMINATE NORMAL GROUND ON
RECEPTACLE BOX. TERMINATE IG GROUND ON RECEPTACLE
IG GROUND LUG. SEE OVERALL PLAN ON SHEET E100 FOR IG
CONDUCTOR TERMINATION INSTRUCTIONS AT PANEL.
E21 ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL
GROUND BAR INSIDE CPU ENCLOSURE. RUN #12 GROUND
FROM GROUND BAR BACK TO GROUND IN AOC PANEL.
GROUND CONNECTIONS TO EQUIPMENT INSIDE CPU CABINET
BY CVG.
E24 NEW LOCATION FOR RELOCATED HONEYWELL STATION. PULL
RED CAT5 CABLE IN CABLE TRAY TO THIS LOCATION. VERIFY
ANY ADDITIONAL REQUIREMENTS WITH OWNER.
E25 CONTRACTOR TO PROVIDE MATRIX KEYPAD CARD READER,
MODEL MX2, WITH CONNECTION BACK TO MATRIX ACCESS
CONTROL SYSTEM IN IDF ROOM. CONFIRM REQUIREMENTS
AND DOOR FUNCTION WITH OWNER PRIOR TO INSTALLATION"
SCALE:E101 1/2" = 1'-0"
1 BACKUP AOC POWER PLAN
SCALE:E101 1/4" = 1'-0"
2 BACKUP AOC LIGHTING PLAN
EXAMPLE CPU CABINET
FIRE ALARM
AUDIO/VISUAL DEVICES
THERMOSTAT
CARBON DIOXIDE/
TEMPERATURE SENSOR
SWITCHES
FIRE ALARM
PULL STATION
TELEPHONE /
DATA OUTLET
RECEPTACLEFINISHED FLOOR
DEVICE MOUNTING DETAIL - GENERAL NOTES:
A. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN TO BE MOUNTED AT A SIMILAR HEIGHT, ALIGN HORIZONTALLY ALONG TOP OF DEVICE BACKBOX (AS SHOWN IN DETAIL AND DESCRIBED IN KEY NOTE #2).
B. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN MOUNTED AT DIFFERENT HEIGHTS, ALIGN VERTICALLY
ALONG THE CENTERLINE OF THE DEVICE BACKBOX (AS SHOWN IN DETAIL).
C. FOR ANY WALL OTHER THAN PAINTED GYPSUM BOARD OR CMU, DEVICE LOCATIONS MUST BE FIELD APPROVED BY ENGINEER OR ARCHITECT PRIOR TO INSTALLATION OF
FINISHES.
D. ADA REQUIRES 48" ABOVE FINISH FLOOR FOR FRONT ACCESS. SIDE REACH ACCESS ALLOWS A MAXIMUM OF 54" AND A LOW SIDE REACH OF NO LESS THAN 9" ABOVE FINISH FLOOR. ADA FRONT AND SIDE REACH ACCESS MUST BE MAINTAINED FOR NEW AND EXISTING CONSTRUCTION. NOTIFY ARCHITECT AND ENGINEER OF ANY
DISCREPANCIES.
8"
CARD READER / KEYPAD
DEVICE MOUNTING DETAIL - KEY NOTES:
1. MOUNT VISUAL NOTIFICATION APPLIANCES SO THAT ENTIRE LENS IS BETWEEN 80" AND 96" AFF. IF CEILING IS TOO LOW FOR DEVICE TO BE MOUNTED ABOVE 80", MOUNT
SO THAT THE LENS IS WITHIN 6" OF FINISHED CEILING.
2. ALIGN BACKBOXES OF DEVICES AT THE MOUNTING HEIGHT INDICATED. MEASURE TO THE CENTER OF THE BACKBOX FOR STANDARD OUTLET BOXES. NON-STANDARD BACKBOXES ARE TO BE INSTALLED SUCH THAT THE FINISHED DEVICES ARE ALIGNED ALONG THEIR RESPECTIVE CENTERLINES.
3. MOUNTING HEIGHTS SHOWN ILLUSTRATE DESIGN INTENT AND ARE TO BE FOLLOWED UNLESS CONTRADICTED BY APPLICABLE CODE. WHERE DEVICES ARE SHOWN ADJACENT TO DOOR FRAMES ON PLANS INSTALL 12" FROM FRAME TO AVOID SLUSHED SECTIONS OR BRACING. SPECIFIC DEVICES ARE SHOWN IN RELATIVE ORDER FROM DOOR FRAME; WHERE THESE DEVICES ARE NOT PRESENT AT A PARTICULAR LOCATION, ADJUST LOCATIONS CLOSER TO DOOR ACCORDINGLY.
4. THE CONTRACTOR IS TO COORDINATE ALL ROUGH-INS WITH ANY COUNTERTOPS/BACKSPLASHES/WALL PROTECTION TO AVOID CONFLICT. ALIGN DEVICE BACKBOXES IN THE BOTTOM OF THE NEXT FULL BLOCK ABOVE THE BACKSPLASH AS SHOWN. FOR NON-BLOCK WALLS ALIGN BOTTOM OF DEVICE BACKBOXES 2" ABOVE BACKSPLASH.
COORDINATE WORK WITH CASEWORK AND KITCHEN SHOP DRAWINGS ACCORDINGLY. IF CONFLICT STILL ARISES CONTACT THE ENGINEER FOR DIRECTION ON HOW TO
PROCEED.
X
COUNTERTOP (WHERE
APPLICABLE)
BACKSPLASH (WHERE
APPLICABLE)
CEILING
DOOR FRAME
(WHERE
APPLICABLE)
ADA PUSH PLATE
WALL TELEPHONES
INTERCOM CALL STATION
A/V TOUCH PANEL
F I R E
F I R E
FIRE
CASEWORK / FURNITURE
(WHERE APPLICABLE)
PP
(T O
C E
N T
E R
O F
B O
X
(T O
C E
N T
E R
O
F B
O X
PROVIDE REMOVABLE FIRESTOPPING PILLOW (FSB OR
EQUAL) IN UL LISTED FIRESTOPPING ASSEMBLY TO ALLOW
FOR EASY REMOVAL AND INSTALLATION OF NEW CABLES.
8"+, TO CLEAR
OBSTRUCTIONS
CL
2" EA. SIDE
CEILING
STRUCTURE
LOCATE SO THAT ACCESSIBLE CEILING IS AT EACH SIDE OF
SLEEVES OR PROVIDE ACCESS PANEL.
PROVIDE CAULKING-STYLE FIRESTOPPING BETWEEN
SLEEVE AND WALL MATERIAL TO ANCHOR SLEEVE AND
RESTORE RATING OF WALL PER LOCAL AUTH. HAVING
JURISDICTION.
SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH
INSULATED THROAT CONDUIT TERMINATORS ON EACH
END. PROVIDE A THREADED CAP ON EACH END IF NOT
USED FOR WIRING . LINE-UP WITH "CABLE TRAY" OR ''HOOK
PATH'' WHERE APPLICABLE.
FIRE/SMOKE RATED OR UN-RATED PARTITION OF VARIOUS
CONSTRUCTIONS. REFER TO ARCHITECTURAL PLANS OR
FIELD VERIFY TYPE.
GENERAL NOTES:
A. PROVIDE ONE 2" SPARE CONDUIT SLEEVE THROUGH ALL FULL HEIGHT
PARTITIONS FOR FUTURE USE. LABEL AS SPARE FOR OWNER'S USE ONLY.
REFER TO ARCHITECTURAL PLANS FOR FULL HEIGHT PARTITION LOCATIONS.
B. USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS,
ETC.
NOTE: IF THE SLEEVE SIZE AND NUMBER
INDICATED ON PLANS WILL NOT BE ADEQUATE TO
CONTAIN ALL CABLES AND STILL LEAVE 25%
SPARE CAPACITY, PROVIDE ADD'L SLEEVES AS
NEEDED TO PROVIDE THIS SPARE CAPACITY.
RECESSED MOUNTED
TROFFER
PROVIDE A MINIMUM OF 3
TIGHT TWISTS AT CONNECTION
TO FIXTURE (TYPICAL OF ALL
FOUR CORNERS).
PROVIDE TRAPEZE
SUPPORT WIRE
(TYP)
PROVIDE A MINIMUM OF TWO (2) TIGHT WRAPS
AROUND STRUCTURE ABOVE OR PROVIDE 400LB.
PULLOUT HILTI ANCHORS IN CONCRETE SLAB, TO
SUIT ACTUAL FIELD CONDITIONS (TYPICAL OF ALL
FOUR CORNERS).
STRUCTURE ABOVE
CEILING
GENERAL TROFFER SUPPORT DETAIL NOTES:
A. SUPPORT WIRES SHALL BE GALVANIZED REGULAR COATING, SOFT TEMPER,
0.1055 INCHES IN DIAMETER (12 GAUGE).
B. SUPPORT FIXTURE INDEPENDITLY FROM THE CEILING (GRID) SUPPORT.
C. ALTERNATELY, CONTRACTOR MAY SUPPORT FIXTURES WITH SINGLE WIRE FROM
ALL FOUR CORNERS OF FIXTURE PER SPECIFICATIONS WITH NUMBER OF TWISTS
AT FIXTURE AND NUMBER OF WRAPS AROUND STRUCTURE INDICATED IN THIS
DETAIL.
SUSPENDED CEILING TILE
GENERAL NOTES:
A. NORMAL POWER LABELS SHALL BE BLACK WITH WHITE LETTERS.
B. EMERGENCY POWER LABELS SHALL BE RED WITH WHITE LETTERS. LABEL SHOULD ALSO INCLUDE
THE WORD "EMERGENCY" IN 1/4" LETTERS.
C. EMERGENCY POWER LABELS IN HEALTHCARE APPLICATIONS SHOULD INCLUDE SYSTEM SEVERED
"LIFE SAFETY", "CRITICAL" OR "EQUIPMENT" .
D. UTILIZE SCREW-ON TYPE LAMACOID PLATES.
E. THIS DETAILS APPLIES TO ALL ELECTRICAL EQUIPMENT INCLUDING PANELS, SWITCHGEAR, DISCONNECTS, TRANSFORMERS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES (VDF'S), SPECIAL DEVICE PLATES, INVERTER, AND SIMILAR MATERIALS SHALL BE CLEARLY MARKED AS TO
THEIR FUNCTION AND USE.
TYPICAL POWER PANEL NAMEPLATE DETAIL
NO SCALE
1/2'' HIGH
LETTERS
1/4'' HIGH
LETTERS
PANEL LXW
120/208V/3PH/4W
FEED: 200 AMPS
(4) #3/0, #6 GND, 2" C.
FED FROM: MDP
NO SCALE
PUMP P-1
208V/3PH/4W
FEED: 600 AMPS
FED FROM: MDP
CKT # 6
TYPICAL EQUIPMENT NAMEPLATE
LAMACOID
NAME PLATE
1/2'' HIGH
LETTERS
1/4'' HIGH
LETTERS
LAMACOID
NAME PLATE
NOTE :
PROVIDE WITH 4" TALL IN-LINE DIVIDER TO DIVIDE
SHARED TRAY BETWEEN DATA-VOICE CABLES AND
ALL OTHER CABLES.
COORDINATE EXACT ROUTING WITH ALL
OTHER TRADES AND OFFSET AS
REQUIRED
BUNDLE/WRAP CABLING AT EACH SIDE OF
SEPARATION
''SOLID'' TYPE CABLE TRAY SHALL BE 4"
DEEP WITH WIDTH AS INDICATED ON
DRAWINGS. CABLE TRAY SHALL HAVE
COVER. B-LINE OR EQUAL.
#6 BARE
GROUND
1" C AT ALL
TELECOM
ROOMS
TO TGB
OR TGMB
#6 BARE BONDED
TO TGB OR TGMB
RAISED WOOD SHEATHING PLATFORM
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 2 0 0
E L E C T R I C A L D E T A I L S
NOT TO SCALEE200
TYPICAL WALL DEVICE MOUNTING DETAIL2
NOT TO SCALEE200
CONDUIIT WALL SLEEVE INSTALLATION1
NOT TO SCALEE200
LUMINAIRE SUPPORT DETAIL3
NOT TO SCALEE200
ELECTRICAL EQUIPMENT NAMEPLATE4
NOT TO SCALEE200
CABLE TRAY INSTALLATION DETAIL5
CAT 5 CABLE
NX OCCUPANCY SENSOR
NX OCCUPANCY SENSOR
RED (24VDC)
BLUE (CONTROL)
BLACK
(COMMON)
R J A
D A
P T
E R
CAT 5 CABLE
CAT 5 CABLE
NXRC-1RD
NXRC-UL924-UNV
EMERGENCY
LIGHTING LOAD
G
V
H
N
VIOLET/WHITE
CAP
OFF
VIOLET
GRAY
RED
WHITE
BLUE WIRE
BLUE LOOP FOR USE WITH A
NORMALLY CLOSED
MAINTAINED TEST SWITCH
EMERGENCY
LIGHTING LOAD
G
V
H
N
GRAY
VIOLET
W H
IT
E
R E
D
B L
A C
K
/2
/3
V A
C
W H
IT
E
N
E U
T R
A L
B L
A C
K
/2
/3
V A
C
W H
IT
E
N
E U
T R
A L
ON / OFF
OS CEILING MOUNTED OCCUPANCY SENSOR
A. LOW VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR BASIS OF
DESIGN: nLIGHT nCM SERIES.
B. LIGHTING TO AUTOMATICALLY TURN ON TO 100% WHEN OCCUPANCY IS
DETECTED.
C. WHILE IN UNOCCUPIED MODE NORMAL AND EMERGENCY LIGHTING
SHALL TURN OFF.
D. LIGHTING SHALL HAVE AUTOMATIC SHUT-OFF OF LIGHTING WITHIN 15
MINUTES OF OCCUPANTS LEAVING.
E. WHERE LIFE-SAFETY LIGHTING CIRCUIT(S) ARE PRESENT, PROVIDE
UL924 DEVICE(S) TO REVERT LIGHTS TO 100% UPON FAILURE OF
NORMAL POWER.
ON / OFF
A. LOW VOLTAGE MANUAL CONTROL STATION WITH INDIVIDUAL BUTTONS AS
SHOWN ON DETAIL. BASIS OF DESIGN: nLIGHT nPODMA SERIES.
B. ADDITIONAL CONTROL INPUTS: VACANCY SENSOR, PHOTOCELL. REFER TO
FLOOR PLANS AND SEQUENCE OF OPERATIONS FOR ADDITIONAL CONTROL
REQUIREMENTS.
C. SWITCH REQUIREMENTS:
a. MANUAL ON BUTTON
b. MANUAL OFF BUTTON
c. RAISE BUTTON
d. LOWER BUTTON
$LV1 LOW VOLTAGE ON/OFF, DIMMING CONTROL STATION
A. PROVIDE A STANDALONE LIGHTING CONTROL SYSTEM EQUAL TO nLIGHT BRANDS WITH ROOM
CONTROLLER TECHNOLOGY. REFER TO SPECIFICATIONS FOR ADDITIONAL ACCEPTABLE
MANUFACTURER.
B. PROVIDE FIRE-ALARM CONTROL/RELAY MODULE(S) AS REQUIRED TO MAKE LIGHTING CONTROL SYSTEM BRING ALL LIGHTING ON EGRESS PATHS TO 100% WHEN THE FIRE ALARM SYSTEM IS ACTIVATED.
C. INSTALL CONTROLLERS AND BRIDGES ABOVE ACCESSIBLE CEILING NEAR LUMINAIRE(S) TO BE CONTROLLED. PROVIDE CAD DRAWINGS INDICATING EXACT LOCATION OF CONTROL DEVICES AND
SUBMIT INFORMATION AS SHOP DRAWINGS FOR APPROVAL BY ENGINEER.
D. THE INTENTION IS TO PROVIDE A FULLY WIRED SYSTEM. WIRELESS AND/OR DEVICES THAT REQUIRE A
BATTERY ARE NOT ACCEPTABLE UNLESS SPECIFICALLY APPROVED BY THE ENGINEER.
E. CAT5, 5E, OR 6 NETWORK CABLE. NETWORK CABLE SHALL BE PLENUM RATED IF REQUIRED PER
SPECIFICATIONS AND /OR SITE CONDITIONS. MANIMUN CABLE LENGTH PER ZONE 1500 FEET.
LIGHTING CONTROL GENERAL NOTES:
NETWORK CABLE USED TO
INTERCONNET SWITCH TO
ROOM CONTROLLER
GENERAL NOTES:
A. THIS DETAIL ONLY APPLIES TO DRY-TYPE
TRANSFORMERS UP TO 45 KVA. CASE HARDENED NUTS
WASHERS
DRILL HOLE
3/4" THREADED ROD
2" x 2" x 3/8" ANGLE
1" x 1" x 3/16" ANGLE
1/2" x 4" SQ. VIBRATION
ISOLATION PADS
WELD (TYP.)
NEW STRUCTURE ABOVE TRANSFORMER - SIZE
FRAME APPROPRIATELY
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 2 0 1
E L E C T R I C A L D E T A I L S
NOT TO SCALEE201
TYPICAL UL924 CONTROL DIAGRAM1
NOT TO SCALEE201
SUSPENDED DRY-TYPE TRANSFORMER INSTALLATION3
EG8
375KVA
DIESEL
480Y/277V/3Φ/4W
600ASWBD (MAIN ELECTRIC ROOM)
480Y/277V, 3-PHASE, 4-WIRE
600A BUSSING
DISTRIBUTION SECTION(S)
100AT/
100AF
GENERAL POWER RISER NOTES:
A. REFER TO SPECIFICATIONS FOR CONDUCTOR REQUIREMENTS. FEEDERS SHALL
BE COPPER.
B. PROVIDE ENGRAVED LAMACOID LABELS FOR ALL POWER DISTRIBUTION
EQUIPMENT FURNISHED OR MODIFIED IN THIS PROJECT, LABELS PER DETAILS
AND SPECIFICATIONS.
C. SERVICE EQUIPMENT SHALL BE MARKED WITH THE MAXIMUM AVAILABLE FAULT-
CURRENT AT THE EQUIPMENT AND THE DATE THE CALCULATION WAS
PERFORMED. APPLY A TYPE-WRITTEN ADHESIVE LABEL WITH WHITE
BACKGROUND, 1/2'' HIGH BLACK LETTERING.
D. CONTRACTOR SHALL INSTALL SEPARATE CONDUITS, PULL BOXES, ETC. FOR EACH
EMERGENCY POWER BRANCH & NORMAL POWER PER NEC FOR COMPLETE
SEPARATION OF POWER SERVICES.
E. ALL SPARE BREAKERS SHALL BE SO LABELED IN CIRCUIT DIRECTORIES AND
SHALL BE LEFT IN THE OFF POSITION.
F. MINIMUM PANEL MOUNTING SPACE IS NOTED ON DRAWINGS AND SCHEDULES.
ALL MOUNTING SPACE SHALL BE PREPARED TO ACCEPT FUTURE BREAKERS.
G. SEE SPECIFICATIONS FOR POWER STUDY REQUIREMENTS.
H. PROVIDE ELECTRONIC TRIP BREAKERS ON ALL EMERGENCY BRANCH CIRCUITS
WHERE REQUIRED FOR SELECTIVE COORDINATION.
N E
ATS-1
600A
ATS
RTU-1
480Y/277V,3Φ,4W
EMB
PANEL
225A
MCB
TX-2
TRANSFORMER
75 kVA
208Y/120V,3Φ,4W
EMA
PANEL
225A MCB
208Y/120V,3Φ,4W
KP
PANEL
100A
TR-1
TRANSFORMER
75 kVA
225AT/
400AF
208Y/120V,3Φ,4W
LPA
PANEL
225A MLO
120/240V,1Φ,3W
60A MLO
AOC
PANEL
A
A
A
A
A
A
A
A
A
600A600A
(2) SETS OF (4) #350MCM
(1) #1 GND
IN 4" C.
FROM UTILITY
TRANS.
(2) SETS OF (4) #350MCM
(1) #1 GND
IN 4" C.
(4) 4/0 &
(1) #6 GND IN
2-1/2" C.
(4) #1 &
GND IN
1-1/2" C.
(3) #2 &
(1) #8 GND IN
1-1/2" C.
(4) 4/0 &
(1) #6 GND IN
2-1/2" C.
(4) 4/0 &
(1) #6 GND IN
2-1/2" C.
(4) #2 &
(1) #8 GND IN
1-1/2" C.
DP-1
A
A
DP-2
A
SPARE
M
UTILITY METER
# 108 262 173
59.8KW PEAK DEMAND
(4) #1/0 THWN &
(1) #6 GND IN
2-1/2" C.
(3) #2 THWN &
(1) #8 GND IN
1-1/2" C.
A
SINGLE LINE TAGGED NOTES
1. DEMOLISH EXISTING FUSE INSIDE EXISTING BUCKET ON SWITCHBOARD.
PROVIDE AND INSTALL NEW 40A FUSES IN BUCKET.
2. DEMOLISH ANY EXISTING ABANDONED CONDUIT AND CONDUCTORS
CONNECTED TO EXISTING SWITCHBOARD SPACE.
3. PROVIDE AND INSTALL NEW CONDUIT AND CONDUCTORS AND CONNECT TO
REPURPOSED SWITCHBOARD BUCKET.
4. PROVIDE NEW ISOLATED GROUND BAR.
5. PULL #6 IG CONDUCTOR IN EXISTING CONDUIT. CONNECT NEW IG BAR IN PANEL
EMA TO EXISTING GROUND BAR TRANSFORMER TX-2.
SPARE
50AT/
60AF
T-AOC
TRANSFORMER
15 kVA
2CU-40A
3CU-50A
3CU-50A
3CU-50A
208Y/120V,3Φ,4W
EMA1
PANEL
100A
23.3KW
FROM DRAWINGS
50KW
(4) #3 &
GND IN
CU.
23.3KW
20.4 KW
FROM DRAWINGS
42.8KW FROM DRAWINGS
BOD: SQUARE D
BOD: SCHNEIDER APC
SYMMETRA LX
470/277V, 1PH PRIMARY
120/240V, 1PH, 3W SECONDARY
2.2kAFC
A
8KVA UPS
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 7 0 0
E L E C T R I C A L S I N G L E L I N E
FEEDER SCHEDULE
Size Type WireSize
2CU-40A 2CU-40A (2) #8 CU & #10 CU GND. IN 3/4"C
3CU-50A 3CU-50A (3) #8 CU & #10 CU GND. IN 3/4"C
2025-048
Cincinnati/Northern Kentucky International Airport
BACKUP AOC
Interior Modifications
South ARFF Fire Station 2100 Tower Dr.
TH
IS
D O
C U M
EN
T, A N
D T
H E
ID
EA
S A N
D D
ES
IG
N S
IN
C O
R
PO
R A
TE
D H
ER
EI
N , A
S A N
I N
ST
R U M
EN
T
O F
PR
O
FE
SS
IO
N
A L
SE
R V
IC
E, I S
TH
E
PR
O
PE
R
TY
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
A N
D I S
N O
T
TO
B E
U
SE
D I N
W H
O
LE
O R I N
P A R T
FO
R A
N Y
O
TH
ER
P
R O
JE
C T, W
IT
H O
U T
TH
E
W R
IT
TE
N
A U
TH
O R
IZ
A
TI
O N
O F
EM
BO
SS
D
ES
IG
N , P
.S .C
C O
PY
R
IG
H T
-2
5:
E
M
BO
SS
D
ES
IG
N , P
.S .C
A
LL
R
IG
H
TS
R
ES
ER
V
ED
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
15141312 161110987654321
A
D
B
C
E
F
G
H
J
K
L
M
IS
SU
E DATE DESCRIPTION
9/3/25 60% REVIEW
NO.
P
\P
R
-0
-B
A C
K U
P A
O C
-S O
U T
H A
R F
F \0
-D
R A
W
IN
G S
10/16/25 90% REVIEW
11/20/25 BIDDING & PERMIT
906 Monmouth Street, Newport, KY 41071
EmbossDesign.com (859)431-8612
S y c a m o re S t, S u it e
C in c in n a ti
O H
.4
.4
E 8 0 0
P A N E L S C H E D U L E S
NOTES:
TOTAL EST. DEMAND CURRENT: 8 A
REC 5940 VA 100.00% 5940 VA TOTAL CONN. CURRENT: 8 A
LTNG 145 VA 100.00% 145 VA TOTAL EST. DEMAND: 6 kVA
EQUIP 300 VA 100.00% 300 VA TOTAL CONN. LOAD: 6 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
8 SPACE -- -- -- -- 3 -- -- --
7 E RTU1 -- -- -- -- 3 100 A 100 A 0.0
6 E TR1 -- -- -- -- 3 100 A 100 A 0.0
5 E SPARE -- -- -- -- 3 100 A 100 A 0.0
4 T-AOC 2 100 A 40 A 1.8
3 E DP-2 -- -- -- -- 3 100 A 100 A 0.0
2 E DP-1 -- -- -- -- 3 100 A 100 A 0.0
1 E EMB 3 200 A 125 A 4.6
CKT CIRCUIT DESCRIPTION SETS WIRE GND COND POLES FRAME TRIP LOAD (kVA) REMARKS
AMPERES: 600 A MOUNTING: FLOOR SUPPLY FROM: UTILITY
VOLTAGE: 480Y/277V,3P,4W SPD: No LOCATION: MAIN ELECTRICAL ROOM
SWITCHBOARD: SWBD MAINS TYPE: 600A MCB kAIC RATING: EXISTING
SWITCHBOARD AND WIRING SCHEDULE kAIC VALUE: EXISTING
ADD ISOLATED GROUND BAR TO EXISTING PANEL.
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.
TOTAL ESTIMATED DEMAND CURRENT: 13 A
REC 4140 VA 100.00% 4140 VA TOTAL CONNECTED CURRENT: 13 A
LTNG 145 VA 100.00% 145 VA TOTAL ESTIMATED DEMAND: 4585 VA
EQUIP 300 VA 100.00% 300 VA TOTAL CONNECTED LOAD: 4585 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
13 A 18 A 8 A
1.5 kVA 2.1 kVA 1.0 kVA
E SPARE 20 1 41 0.0 0.0 42 1 20 E CORD DROP F-5
E WATER HEATER RR/SHOWER 20 1 39 0.0 0.1 40 1 20 BACKUP AOC TOWER LIGHTS
E F3 LADDER CORD DROP 20 1 37 0.0 0.0 38 1 20 E RADIO BATTERY CHARGERS
E CORD DROP WEST WALL 20 1 35 0.0 0.8 36
E CORD DROP WEST 20 1 33 0.0 1.8 34
E CORD DROP WEST 20 1 31 0.0 1.3 32
3 100 EMA1
29 0.0 0.0 30 1 20 E WEST WALL AND PIDS
27 0.0 0.0 28KP 100 3
25 0.0 0.0 26
2 30 E SHORELINE DISASTER TRAILER
E CORD DROP DOOR F3 20 1 23 0.0 0.0 24
E RADIO 20 1 21 0.0 0.0 22
2 20 E AC-1
E RADIO 20 1 19 0.0 0.0 20
E GATE CAMERA INTERCOM 20 1 17 0.0 0.0 18
2 20
E GENERATOR BATTERY CHARGER BLOCK
HEATER
E OPEN DOOR LIGHT 20 1 15 0.0 0.0 16 1 20 E SPARE
E EF LOUVER 20 1 13 0.0 0.0 14 1 20 E DUPLEX WEST F2 CORD DROP
E DUPLEX ALARM ROOM/INLINE FAN 20 1 11 0.0 0.0 12 1 20 E BAY HEATERS WEST
BACKUP AOC CPU IG DUPLEX 20 1 9 0.2 0.0 10 1 20 E BAY HEATERS WEST
BACKUP AOC CPU IG DUPLEX 20 1 7 0.2 0.0 8 1 20 E CORD DROP BATALLION DOOR
E PAGING SYSTEM 20 1 5 0.0 0.2 6 1 20 BACKUP AOC CPU IG DUPLEX
E FIRE ALARM PANEL 20 1 3 0.0 0.0 4 1 20 E DUPLEX CAPTAIN'S OFFICE
E DUPLEX AT TELEPHONE 20 1 1 0.0 0.0 2 1 20 E EX LOAD
CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: T-EMA
VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION: WEST MEZZANINE
PANEL: EMA MAINS TYPE: 225A MCB PANEL INTERRUPTING RATING: EXISTING
PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.
TOTAL ESTIMATED DEMAND CURRENT: 8 A
TOTAL CONNECTED CURRENT: 8 A
TOTAL ESTIMATED DEMAND: 1800 VA
REC 1800 VA…
This is the start of the file's text. The full file is on GovTribe.